Commercial and Industrial Smart Inverter ET Series 12-30kW • Lynx C Series Commercial and Industrial Battery 60kWh • BAT-C Series Commercial and Industrial Battery 61.4-112.6kWh • BAT-S Series High-Voltage Battery 15.3-56.3kWh Solutions Manual
Copyright Statement Copyright Statement All Rights Reserved© GoodWe Technologies Co., Ltd. 2026. All rights reserved. Without authorization from GoodWe Technologies Co., Ltd., no content of this manual may be reproduced, disseminated, or uploaded to public networks or other third-party platforms in any form. Trademark Authorization GOODWE and other GOODWE trademarks used in this manual are the property of GoodWe Technologies Co., Ltd. All other trademarks or registered trademarks mentioned in this manual belong to their respective owners. NOTICE Due to product version upgrades or other reasons, the content of this document is updated periodically. Unless otherwise agreed, the content of this document cannot replace the safety precautions on the product label. All descriptions in this document are for guidance only. 1
About This Manual Overview This document primarily introduces the product information, installation wiring, configuration and commissioning, troubleshooting, and maintenance content for the energy storage system composed of inverters, the Battery system, and smart meters. Please read this manual carefully before installing and using the product to understand product safety information and familiarize yourself with the product's functions and features. The document may be updated periodically; please obtain the latest version of the materials and more product information from the official website. Applicable Model The energy storage system includes the following products: Product Type Product Information Description Inverter ET 12-30kW Nominal output power 12kW to 30kW. Battery system Lynx C series 60kWh commercial and industrial battery system BAT-S series 15.3-56.3kWh high- voltage battery Single cluster storage capacity 60kWh. Parallel cluster storage capacity up to 180kWh. Single cluster storage capacity 15.3/20.4/25.6/30.7/35.8/40.9/46.0/ 51.2/56.3 kWh. Parallel cluster storage capacity up to 91.8/122.4/153.6/184.2/214.8/245.4/ 276.0/307.2/337.8 kWh. 2
Product Type Product Information Description BAT-C series 61.4- 112.6kWh commercial and industrial battery system GM3000 GM330 Meter GMK330 WiFi/LAN Kit-20 LS4G Kit-CN, 4G Kit-CN, 4G Kit- CN-G20 or 4G Kit-CN-G21 (China only) smart dongle Wi-Fi Kit Ezlink3000 Symbol Definition Indicates a situation with a high potential hazard, which, if not avoided, will result in death or serious injury. Single cluster storage capacity 61.4/92.1/102.4/112.6kWh. Monitoring module in the energy storage system, capable of detecting operating voltage, current, and other information in the system. Can upload system operating information to the monitoring platform via WiFi or LAN signals. Can upload system operating information to the monitoring platform via 4G signals. Can upload system operating information to the monitoring platform via WiFi signals. In parallel machine scenarios, connected to the main inverter. Can upload system operating information to the monitoring platform via WiFi or LAN signals. DANGER WARNING 3
Indicates a situation with a moderate potential hazard, which, if not avoided, could result in death or serious injury. Indicates a situation with a low potential hazard, which, if not avoided, could result in moderate or minor injury. Emphasis and supplement to the content, which may also provide tips or tricks for optimal product use, helping you solve a problem or save your time. CAUTION NOTICE 4
1 Safety Precautions 12 1.1 General Safety 12 1.2 personnel requirements 13 1.3 System Safety 13 1.3.1 PV String Safety 15 1.3.2 Inverter Safety 16 1.3.3 Battery Safety 17 1.3.4 Smart Meter Safety 19 1.4 Safety Symbols and Certification Marks 20 1.5 EU Declaration of Conformity 21 1.5.1 Equipment with Wireless Communication Modules 21 1.5.2 Equipment without Wireless Communication Modules (Except Battery) 22 1.5.3 Battery 22 2 System Introduction 24 2.1 System Overview 24 2.2 Product Overview 29 2.2.1 Inverter 29 2.2.2 Battery 31 2.2.2.1 Lynx C Series 60kWh C&I Battery System 32 2.2.2.2 BAT-S Series 15.3-56.3kWh High Voltage Battery 33 2.2.2.3 BAT Series 61.4-112.6kWh C&I Battery System 37 Table of Contents 5
2.2.3 Smart Meter 48 2.2.4 smart dongle 49 2.3 Supported Grid Types 50 2.4 System Working Mode 51 2.5 Features 61 3 Check and Storage 65 3.1 Check Before Receiving 65 3.2 deliverables 65 3.2.1 Inverter Deliverables 65 3.2.2 Batteries Deliverables 68 3.2.2.1 Lynx C Series 60kWh C&I Battery System 68 3.2.2.2 BAT-S Series 15.3-56.3kWh High Voltage Battery 72 3.2.2.3 BAT Series 61.4-112.6kWh C&I Battery System 76 3.2.3 Smart Meter Deliverables (GM3000) 77 3.2.4 Smart Meter Deliverables GM330 & GMK330 78 3.2.4.1 Accessory List 78 3.3 Storage 79 4 Installation 82 4.1 System Installation and Commissioning Procedure 82 4.2 Installation Requirements 83 4.2.1 Installation Environment Requirements 83 4.2.2 Foundation Requirements 86 6
4.2.3 Installation Space Requirements 87 4.2.4 Tool Requirements 89 4.3 Equipment Handling 91 4.4 Installing the Inverter 95 4.5 Installing the Battery System 99 4.5.1 Opening the Cabinet Door 99 4.5.2 Installing the Lynx C Series 60kWh C&I Battery System 100 4.5.3 Installing the BAT-S Series 15.3-56.3kWh High Voltage Battery 101 4.5.4 Installing the BAT Series 61.4-112.6kWh C&I Battery System 105 4.6 Installing the Smart Meter 107 5 System Wirings 109 5.1 System Wiring Electrical Block Diagram 109 5.2 Detailed System Wiring Diagram 112 5.2.1 Detailed System Wiring Diagram for Single Inverter 113 5.2.2 Detailed System Wiring Diagram for Parallel System 118 5.3 Preparing Materials 121 5.3.1 Preparing Breakers 122 5.3.2 Preparing Cables 126 5.3.3 Removing the Cover Plate 129 5.4 Connecting the PE cable 131 5.4.1 Inverter Grounding 132 5.4.2 Battery System Grounding 132 7
5.5 Connecting the PV Cable 133 5.6 Connecting the Battery System Cables 135 5.6.1 With Lynx C Series 60kWh C&I Battery System 139 5.6.1.1 Battery Cable Entry Port Introduction 139 5.6.1.2 Connecting the Power Cable between the Inverter and Battery 140 5.6.1.3 Connecting the Battery Communication Cable 144 5.6.1.4 Connecting the Internal Power Busbars of the Battery System 146 5.6.1.5 Connecting the Air Conditioner Power Cable for the Battery System 5.6.1.6 Connecting the Air Conditioner Drain Pipe for the Battery System 148 5.6.1.7 Turning On the Fire Protection Switch 148 5.6.1.8 Installing the Cover Plate 150 5.6.2 With BAT-S Series 15.3-56.3kWh High Voltage Battery 150 5.6.2.1 Connecting the Power Cable between the Inverter and Battery 151 5.6.2.2 Connecting the Power Cable between Battery Units 154 5.6.2.3 Connecting the Communication Cable 154 5.6.3 With BAT Series 61.4-112.6kWh C&I Battery System 156 5.6.3.1 Battery Cable Entry Port and System Wiring Introduction 157 5.6.3.2 Connecting the Power Cable between the Inverter and Battery 158 5.6.3.3 Connecting the Battery Communication Cable 158 5.6.3.4 Connecting the Battery Air Conditioner Cable 159 5.6.3.5 Installing the Bottom Plate and Releasing the Emergency Stop Switch 8 147 160
5.7 Connecting the AC Cable 161 5.8 Connecting the Meter Cable 162 5.9 Connecting the Inverter Communication Cable 167 5.10 Connecting the Smart Dongle 174 6 System Commissioning 177 6.1 Check Before Power ON 177 6.2 Power ON 177 6.3 Indicators 179 6.3.1 Inverter Indicators 179 6.3.2 Battery Indicators 180 6.3.3 Smart Meter Indicator 182 6.3.4 Smart Dongle Indicator 183 6.4 Closing the Cabinet Door 187 7 System Commissioning & Power Plant Monitoring 190 7.1 Device Commissioning and Power Plant Monitoring via SEMS+ App 190 7.2 Device Commissioning and Power Plant Monitoring via SEMS+ WEB 191 8 Maintenance 193 8.1 Power OFF the System 193 8.2 Removing the Equipment 194 8.3 Disposing of the Equipment 195 8.4 Routine Maintenance 195 8.5 fault 196 9
8.5.1 Viewing Fault/Alarms Information 196 8.5.2 Fault Information and Troubleshooting 197 8.5.2.1 System Fault 197 8.5.2.2 Inverter Fault 199 8.5.2.2.1 Troubleshooting (Fault Code F01-F40) 199 8.5.2.2.2 Troubleshooting (Fault Code F41-F80) 216 8.5.2.2.3 Troubleshooting (Fault Code F81-F121) 225 8.5.2.2.4 Troubleshooting (Fault Code F122-F163) 235 8.5.2.2.5 Troubleshooting Fault Phenomena 245 8.5.2.3 Battery Fault 263 8.5.3 Post-Fault Clearance Handling 278 8.5.3.1 Clearing AFCI Fault Warning 278 9 technical parameter 280 9.1 Inverter Parameters 280 9.2 Battery Parameters 295 9.2.1 Lynx C Series 60kWh C&I Battery System 295 9.2.2 BAT-S Series 15.3-56.3kWh High Voltage Battery 297 9.2.3 BAT-C Series 61.4-112.6kWh C&I Battery System 303 9.3 Smart Meter Technical Data 307 9.3.1 GM330 307 9.3.2 GM3000 308 9.3.3 GMK330 309 10
9.4 Smart Dongle Technical Data 310 9.4.1 4G Kit-CN-G21 311 9.4.2 4G Kit-CN-G20 312 9.4.3 WiFi/LAN Kit-20 313 9.4.4 Ezlink3000 313 10 Appendix 315 10.1 FAQ 315 10.1.1 How to conduct auxiliary detection for smart meters/CT? 315 10.1.2 How to Upgrade the Device Version 315 10.2 Abbreviations 316 10.3 Explanation of Terms 319 10.4 Battery SN Code Meaning 320 10.5 Safety Standard Countries 321 11 Contact Details 328 11
1 Safety Precautions The Safety Precautions information contained in this document must always be followed when operating the equipment. The device has been strictly designed and tested in accordance with safety regulations. However, as electrical equipment, any operation must comply with relevant safety instructions. Improper handling may result in serious injury or property damage. 1.1 General Safety WARNING NOTICE 12
• The content of this document may be updated periodically due to product version upgrades or other reasons. Unless otherwise agreed, the document content cannot replace the safety precautions on the product labels. All descriptions in the document are for guidance only. Please read this document carefully before installing the device to understand the product and the precautions. • • All operations on the device must be performed by professional and qualified electrical technicians who are familiar with the relevant standards and safety regulations at the project location. • When operating the device, use insulated tools and wear personal protective equipment to ensure personal safety. When touching electronic components, wear anti-static gloves, anti-static wrist straps, anti-static clothing, etc., to protect the device from electrostatic damage. Unauthorized disassembly or modification may cause device damage, which is not covered under warranty. • • Device damage or personal injury caused by failure to install, use, or configure the device in accordance with the requirements of this document or the corresponding user manual is beyond the manufacturer’s liability. For more product warranty information, please visit the official website: https://en.goodwe.com/warrantyrelated.html. 1.3 System Safety DANGER 13
• Before performing electrical connections, disconnect all upstream switches of the equipment to ensure the equipment is de-energized. Live operation is strictly prohibited, otherwise risks such as electric shock may occur. • For equipment supporting PV string connection, the PV input terminals have weak surge current capability. It is strictly forbidden to power on the equipment directly from the PV ports using a DC voltage source. If it is necessary to power on from the PV ports, please follow the steps below. Damage caused by improper operation is considered⼈为损坏 and is not covered by the product warranty. First, limit the output current of the DC voltage source within the maximum input current range allowed by the PV ports. 1. Then close the DC switch of the inverter. 2. Finally, slowly increase the output voltage of the DC source from zero to the target value at a rate of ≤50V/s. 3. To prevent personal injury or equipment damage caused by live operation, a circuit breaker must be added to the voltage input side of the equipment. • • All operations such as transportation, storage, installation, operation, use, and maintenance must comply with applicable laws, regulations, standards, and specifications. The specifications of cables and components used for electrical connections must comply with local laws, regulations, standards, and specifications. • • Please use the cable connectors provided in the box to connect the equipment cables. If other models of connectors are used, any resulting equipment damage is not within the responsibility of the equipment manufacturer. Ensure all equipment cables are connected correctly, securely, and without looseness. Improper wiring may cause poor contact or damage the equipment. • The equipment's protective earth wire must be securely connected. • • To protect the equipment and its components from damage during transportation, ensure transport personnel are professionally trained. Record the operation steps during transportation and keep the equipment balanced to avoid dropping. • The equipment is heavy. Please deploy personnel corresponding to the equipment weight to prevent the equipment from exceeding the weight limit for manual handling, which could cause injury. Ensure the equipment is placed stably and not tilted. Equipment tipping over may cause equipment damage and personal injury. • 14
Avoid letting the wiring terminals bear weight during equipment installation, otherwise the terminals may be damaged. • • If the cable is subjected to excessive pulling force, it may cause poor connection. When wiring, leave a certain length of cable slack before connecting it to the equipment's wiring port. • Cables of the same type should be bundled together. Cables of different types should be routed separately with a minimum spacing of 30mm. Intertwining or交 叉布放 is prohibited. • Using cables in high-temperature environments may cause insulation aging or damage. Maintain a distance of at least 30mm between cables and发热器件 or the periphery of heat source areas. 1.3.1 PV String Safety WARNING 15
Ensure the component frame and mounting system are properly grounded. • • After completing the DC cable connections, ensure the connections are tight and secure with no looseness. Improper wiring may lead to poor contact or high impedance, and damage the inverter. • Use a multimeter to measure the positive and negative poles of the DC cables to ensure correct polarity and no reverse connection; and ensure the voltage is within the allowable range. • Use a multimeter to measure the DC cables to ensure correct polarity and no reverse connection; the voltage should be lower than the maximum DC input voltage. Damage caused by reverse connection and overvoltage is not covered by the equipment manufacturer's warranty. • The PV string output does not support grounding. Before connecting the PV string to the inverter, ensure the minimum insulation resistance to ground of the PV string meets the minimum insulation impedance requirement (R=Max. Input Voltage (V)/30mA). Do not connect the same PV string to multiple inverters, as this may cause inverter damage. • The photovoltaic modules used with the inverter must comply with IEC 61730 Class A standards. • When the input voltage or input current of the photovoltaic string is high, it may cause the inverter output power to derate. • 1.3.2 Inverter Safety WARNING 16
Ensure that the voltage and frequency of the grid connection point comply with the inverter's grid connection specifications. • • It is recommended to add protective devices such as circuit breakers or fuses on the AC side of the inverter. The specification of the protective device should be greater than 1.25 times the maximum AC output current of the inverter. • If the inverter triggers an arc fault alarm less than 5 times within 24 hours, the alarm can be automatically cleared. After the 5th arc fault alarm, the inverter will shut down for protection. The inverter can resume normal operation only after the fault is cleared. If no battery is configured in the photovoltaic system, it is not recommended to use the BACK-UP function, as it may cause a risk of system power outage. • Changes in grid voltage and frequency may cause the inverter output power to derate. • 1.3.3 Battery Safety WARNING 17
• Before operating any equipment in the system, ensure the equipment is powered off to avoid the risk of electric shock. Strictly adhere to all safety precautions in this manual and the safety labels on the equipment during operation. • Do not disassemble, modify, or repair the battery or control box without official authorization from the equipment manufacturer. Doing so may cause electric shock or equipment damage, and any resulting losses are beyond the manufacturer’s liability. Do not strike, pull, drag, squeeze, or step on the equipment. Do not place the battery in fire, as there is a risk of explosion. • • Do not place the battery in a high-temperature environment. Ensure there are no heat sources nearby and that it is not exposed to direct sunlight. A fire may occur if the ambient temperature exceeds 60°C. Do not use the battery or control box if there are obvious defects, cracks, damage, or other issues. Battery damage may lead to electrolyte leakage. • Do not move the battery system while it is operating. If battery replacement or addition is required, please contact the after-sales service center. • • A battery short circuit may cause personal injury. The instantaneous high current from a short circuit can release a large amount of energy, potentially causing a fire. The battery DC circuit breaker must comply with the requirements of the AS/NZS 5139 standard. • • Battery current may be affected by factors such as temperature, Humidity, weather conditions, etc., which may lead to current limiting and impact load capacity. If the battery fails to start, please contact the after-sales service center as soon as possible. Otherwise, the battery may be permanently damaged. • Please perform regular inspection and maintenance on the battery according to its maintenance requirements. • Emergency Response Measures DANGER WARNING 18
• Battery electrolyte leakage If electrolyte leaks from the battery module, avoid contact with the leaked liquid or gas. Electrolyte is corrosive and contact may cause skin irritation and chemical burns. If accidental contact with the leaked substance occurs, take the following actions: inhalation: Evacuate from the contaminated area and seek medical help immediately. ○ Eye contact: Flush with clean water for at least 15 minutes and seek medical help immediately. ○ Skin contact: Wash the affected area thoroughly with soap and water and seek medical help immediately. ○ Ingestion: Induce vomiting and seek medical assistance immediately. ○ • Fire When the battery temperature exceeds 150°C, there is a risk of fire. A battery fire may release toxic and harmful gases. ○ To prevent fire, ensure that carbon dioxide, Novec1230, or FM-200 fire extinguishers are available near the equipment. ○ When extinguishing a fire, do not use ABC dry powder fire extinguishers. Firefighters must wear protective clothing and self-contained breathing apparatus. ○ • Battery triggers fire protection For batteries equipped with an optional fire protection function, after the fire protection function is triggered, perform the following actions: Immediately cut off the main power switch to ensure no current flows through the battery system. ○ Conduct a preliminary visual inspection of the battery for any damage, deformation, leakage, or unusual odor. Check the battery casing, connectors, and cables. ○ Use a temperature sensor to detect the temperature of the battery and its surroundings to ensure there is no risk of overheating. ○ Isolate and label the damaged battery, and dispose of it properly according to local regulations. ○ 1.3.4 Smart Meter Safety 19
If the grid voltage fluctuation exceeds 265V, long-term overvoltage operation may damage the meter. It is recommended to add a fuse with a rated current of 0.5A on the voltage input side of the meter to protect it. 1.4 Safety Symbols and Certification Marks After the equipment is installed, the labels and warning signs on the enclosure must be clearly visible. Covering, altering, or damaging them is prohibited. • The following enclosure warning label descriptions are for reference only. Please refer to the actual labels used on the equipment. • No. Symbol Meaning 1 Potential hazard exists during equipment operation. Take protective measures when operating the equipment. 2 High voltage hazard. High voltage is present during equipment operation. Ensure the equipment is powered off before performing any operations. 3 The inverter surface is at high temperature. Do not touch during operation to avoid burns. 4 Use the equipment properly. There is a risk of explosion under extreme conditions. 5 The battery contains flammable materials. Beware of fire. 6 The equipment contains corrosive electrolyte. Avoid contact with leaked electrolyte or vapor. 7 Delayed discharge. After powering off the equipment, wait for 5 minutes until it is completely discharged. 8 Keep the equipment away from open flames or ignition sources. WARNING DANGER 20
No. Symbol Meaning 9 Keep the equipment out of reach of children. 10 Use the equipment properly. There is a risk of explosion under extreme conditions. 11 The battery contains flammable materials. Beware of fire. 12 Do not lift the equipment after the battery system wiring is completed or while the battery system is operating. 13 Do not extinguish with water. 14 Read the product manual carefully before operating the equipment. 15 Wear personal protective equipment during installation, operation, and maintenance. 16 17 Do not directly disconnect or plug/unplug the DC terminals while the equipment is operating. 18 Grounding point. 19 Recycling symbol. 20 CE certification mark. 21 TUV mark. 22 RCM mark. 1.5 EU Declaration of Conformity Do not dispose of the equipment as household waste. Dispose of the equipment according to local laws and regulations, or return it to the manufacturer. 21
1.5.1 Equipment with Wireless Communication Modules Equipment with wireless communication modules sold in the European market must comply with the following directives: Radio Equipment Directive 2014/53/EU (RED) • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS) • Waste Electrical and Electronic Equipment 2012/19/EU • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) • 1.5.2 Equipment without Wireless Communication Modules (Except Battery) Equipment without wireless communication functions that can be sold in the European market must meet the requirements of the following directives: Electromagnetic compatibility Directive 2014/30/EU (EMC) • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD) • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS) • Waste Electrical and Electronic Equipment 2012/19/EU • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) • 1.5.3 Battery Batteries that can be sold in the European market meet the requirements of the following directives: Electromagnetic compatibility Directive 2014/30/EU (EMC) • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD) • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)*1 • Regulation (EU) 2023/1542 Article 12 - Safety of stationary battery energy storage systems • Regulation (EU) 2023/1542 Article 10 - Performance and durability requirements • 22
for rechargeable industrial batteries, LMT batteries and electric vehicle batteries Regulation (EU) 2023/1542 Article 14 - Information on the state of health and expected lifetime of batteries • Waste Electrical and Electronic Equipment 2012/19/EU • • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) *1: Our company's battery products meet the hazardous substance limit requirements stipulated by this regulation. More EU Declarations of Conformity can be obtained from the official website. 23
2 System Introduction 2.1 System Overview Commercial & Industrial Smart Inverter Solution integrates devices such as inverters, batteries, Smart Meters, and smart communication sticks. In a photovoltaic system, it converts solar energy into electricity to meet the power demands of commercial and industrial applications. The energy IoT devices in the system manage the electrical loads by identifying the overall power situation within the system, thereby achieving intelligent management of power for use by loads, storage in the battery, or export to the grid. • Select the battery model according to the inverter and battery compatibility list. For requirements regarding batteries used in the same system, such as whether models can be mixed or capacities must be consistent, please refer to the user manual of the corresponding battery model or contact the battery manufacturer for relevant requirements. Inverter and battery compatibility list: https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_Battery%20Co mpatibility%20Overview-EN.pdf. • Due to product version upgrades or other reasons, the document content will be updated periodically. For the compatibility relationship between inverters and IoT products, please refer to: https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_Compatibility- list-of-GoodWe-inverters-and-IoT-products-EN.pdf. • The PV system is not suitable for connecting devices that rely on stable power supply, such as life-sustaining medical equipment, etc. Please ensure that system power failure will not cause personal injury. The BACK-UP function is not recommended for PV systems without a battery configured, as it may cause a system power failure risk. • The BACK-UP port does not support connecting auto-transformers or isolation transformers. • The battery current may be affected by factors such as temperature, Humidity, weather conditions, etc., which may lead to battery current limiting and affect • WARNING 24
load capacity. The inverter has a UPS function with a switching time of <10ms. Please ensure the BACK-UP Loads capacity is < the inverter's rated power. Otherwise, the UPS function may fail during a grid power outage. • The BACK-UP function is not recommended for PV systems without a battery configured, as it may cause a system power failure risk. • For detailed networking and wiring schemes for each scenario, please refer to: Detailed System Wiring Diagram. • • When the inverter is in an off-grid state, it can be used normally for common household loads. However, the following loads need to be limited, such as: inductive load: inductive load power < 0.4 times the inverter's rated output power. ○ Capacitive load: total power ≤ 0.66 x inverter rated output power. ○ The inverter does not support half-wave loads. Half-wave loads: Some old or non-EMC compliant appliances (such as hair dryers, small heaters using half- wave rectification) may not work properly. ○ • In a system where the inverter operates completely off-grid, if the battery is in low light or rainy weather for a long time and cannot be replenished in time, it may lead to over-discharge, causing battery performance degradation or damage. To ensure long-term stable system operation, avoid completely draining the battery. Recommended measures are as follows: During off-grid operation, set the minimum SOC protection threshold. It is recommended to set the off-grid battery SOC lower limit to 30%. ○ When the SOC approaches the protection threshold, the system will automatically enter load limiting or protection mode. ○ If there are multiple consecutive days of insufficient sunlight and the battery SOC is too low, promptly replenish the battery using external energy sources (such as a generator or grid-assisted charging). ○ Regularly check the battery status to ensure it is within a safe operating range. ○ It is recommended to fully charge and discharge the battery every six months to calibrate the SOC accuracy. ○ WARNING 25
ON-GRID Load BACK-UP Load Smart Dongle £T3010NETOO13 26
Device Type model Description GW12KL-ET GW18KL-ET GW15K-ET GW20K-ET GW25K-ET GW29.9K-ET GW30K-ET Inverter Battery system GW60KWH-D-10 GW60KWH-D-10 (without expansion cabinet) Supports up to 4 inverters to form a parallel system. • • Battery-ready models do not support forming a parallel system when the battery function is not activated. Only machines with the same AC output voltage can form a parallel system. • • GW12KL-ET and GW18KL-ET only support BAT-S Series 15.3kWh-56.3kWh batteries. And the following version requirements must be met: Inverter ARM software version 17.449 or above. ○ Inverter DSP software version 13.13011 or above. ○ • In a coupling scenario, using a dual meter can simultaneously monitor grid-tied inverter power generation and load power consumption. The following version requirements must be met: Inverter ARM software version 15.441 or above. ○ Inverter DSP software version 11.11060 or above. ○ SolarGo version 6.9.0 or above. ○ The system supports up to 3 clusters of battery systems in parallel. 27
Device Type model Description GW15.3-BAT-I-G10 GW20.4-BAT-I-G10 GW25.6-BAT-I-G10 GW30.7-BAT-I-G10 GW35.8-BAT-I-G10 GW40.9-BAT-I-G10 GW46.0-BAT-I-G10 GW51.2-BAT-I-G10 GW56.3-BAT-I-G10 GW61.4-BAT-AC-G10 GW92.1-BAT-AC-G10 GW102.4-BAT-AC-G10 GW112.6-BAT-AC-G10 GM3000 • Smart Meter GM330 • GMK330 • Supports up to 6 clusters of battery systems in parallel. • Battery systems of different models cannot be mixed and used in parallel. • • Due to battery operating voltage range limitations, GW15.3-BAT-I-G10 and GW20.4-BAT-I-G10 do not support GW15K- ET, GW20K-ET, GW25K-ET, and GW30K-ET. Only supports a single cluster. GM3000: Included with the inverter, CT cannot be replaced, CT ratio: 120A: 40mA • • GM330: CT can be purchased from GoodWe or independently, CT ratio requirement: nA: 5A nA: CT primary side input current, n ranges from 200 to 5000 ○ 5A: CT secondary side output current ○ • GMK330: CT shipped with the meter, CT ratio: 120A: 40mA ○ 200A: 50mA (only Brazil) ○ 28
Device Type model Description • For single unit, please use WiFi/LAN Kit-20, Wi-Fi Kit, LS4G Kit-CN, 4G Kit-CN, 4G Kit-CN- G20, or 4G Kit-CN-G21 modules. If using WiFi/LAN Kit-20 to replace Wi-Fi Kit, please upgrade the inverter ARM firmware version to 08.401 or above before switching to WiFi/LAN Kit-20. WiFi/LAN Kit-20 • Wi-Fi Kit • • LS4G Kit-CN、4G Kit-CN、4G Kit-CN- G20 or 4G Kit-CN- G21 (only China) smart dongle • In parallel system, only the master inverter needs to be connected to Ezlink3000, slave inverters do not need communication modules. Ezlink3000 firmware version must be 04 or above. Ezlink3000 • 2.2.1 Inverter The Inverter in photovoltaic systems controls and optimizes energy flow through an integrated energy management system. It can supply the electricity generated in the photovoltaic system for load use, store it in batteries, or output it to the grid. NOTICE The appearance of inverters may vary across different power ranges. Please refer to the actual product. No. model Nominal output power Nominal output voltage 1 GW12KL-ET 12kW 1 2 GW18KL-ET 18kW 220V, 3L/N/PE 2 3 GW15K-ET 15kW 1 380/400V,3L/N/PE 4 GW20K-ET 20kW 1 29 Battery Port Quantity
No. model Nominal output power Nominal output voltage 5 GW25K-ET 25kW 2 6 GW29.9K-ET 29.9kW 2 7 GW30K-ET 30kW 2 Component Introduction Component/Silks No. Description creen 1 DC Switch Lock Hole Australia only. 2 DC Switch Controls the connection or disconnection of the DC input. Connect the DC input cables from the PV modules. 3 PV Input Terminals GW15K-ET, GW20K-ET, GW12KL-ET x 2 • GW25K-ET, GW29.9K-ET, GW30K-ET, GW18KL-ET x 3 • 4 Communication Module Port Connect the communication module, supporting 4G and Wi-Fi/LAN modules. Connect the communication cable, supporting communication with DRED, Remote Shutdown, Rapid Shutdown, RCR, EMS, and generator. 5 Communication Port 30 Battery Port Quantity
6 Battery Connection Port 7 BMS Communication Port 8 AC Port Connect the AC cables, including the ON-GRID and BACK-UP ports. 9 METER Communication Port 10 Handle For moving the inverter. 11 Indicator Indicates the operating status of the inverter. 12 Grounding Terminal Connect the protective ground wire for the enclosure. 13 Fan For inverter cooling. 14 Inverter Mounting Slot For mounting and securing the inverter. Australian Junction Box Dimensions 2.2.2 Battery Connect the battery DC cables. GW15K-ET, GW20K-ET, GW12KL-ET x 1 • GW25K-ET, GW29.9K-ET, GW30K-ET, GW18KL-ET x 2 • Connect the battery communication cable. GW15K-ET, GW20K-ET, GW12KL-ET x 1 • GW25K-ET, GW29.9K-ET, GW30K-ET, GW18KL-ET x 2 • Connect the smart meter. 31
The battery system consists of a PCU and a PACK. The battery system can store and release electrical energy according to the requirements of the photovoltaic energy storage system. The input and output ports of this energy storage system are both high-voltage direct current. A single battery cabinet does not support expansion by adding PACKs after installation. • • BAT series battery systems can expand the cluster within one year after installation by adding battery cabinets of the same model and part number. For details, please consult the after-sales service. 2.2.2.1 Lynx C Series 60kWh Commercial & Industrial Battery System No. model Rated Capacity (kWh) 1 GW60KWH-D-10 60 Yes 2 GW60KWH-D-10(without expansion cabinet) 60 No NOTICE Includes AC Cabinet 32
2.2.2.2 BAT-S Series 15.3-56.3kWh High Voltage Battery No. model PACK Quantity Rated Capacity (kWh) 1 GW15.3-BAT-I-G10 3 15.3 2 GW20.4-BAT-I-G10 4 20.4 3 GW25.6-BAT-I-G10 5 25.6 4 GW30.7-BAT-I-G10 6 30.7 33
No. model PACK Quantity Rated Capacity (kWh) 5 GW35.8-BAT-I-G10 7 35.8 6 GW40.9-BAT-I-G10 8 40.9 7 GW46.0-BAT-I-G10 9 46.0 8 GW51.2-BAT-I-G10 10 51.2 9 GW56.3-BAT-I-G10 11 56.3 Dimension Description Component Introduction 34
No. Name Description 1 Adjustable Feet Adjustable height to keep the base level 2 Base The battery system is stacked and placed on the base Stack Installati on 3 Floor Locking Bracket 4 Stacking Bracket Fixed on the battery PACK for stack installation of batteries 1 Battery Rack Used for installing the battery system 2 Wall Locking Bracket Mounting Hole Used to secure the battery rack to the wall to prevent tipping Rack Mountin g 3 Floor Locking Bracket Mounting Hole Used to secure the base to the floor to prevent tipping Used to secure the battery rack to the floor to prevent tipping 35
No. Name Description 5 Protective Grounding Point Used for connecting the ground wire High-Voltage Box Power Input/Output Port 1 6 7 Battery Indicators Used to indicate the battery system status 8 Dry Contact High-Voltage Box Power Input/Output Port 2 9 10 External Communication Port 11 High-Voltage Box Communication Port 12 Battery System Switch 13 High-Voltage Box / Battery PACK Mounting Hole 14 Battery Module Communication Port Connects the power cable between the high-voltage box and the inverter Contact for external fire protection system activation (Normally, the dry contact remains open. When a closed dry contact is detected, the battery system will automatically power down) Connects the power cable between the high-voltage box and the battery module Communicates with the inverter / Places termination resistor / Battery system cluster communication Communicates with the battery module Controls the start and stop of the battery system Used to secure the high-voltage box / battery PACK to the battery rack Used for communication between adjacent battery PACKs, and communication between battery PACK and high-voltage box 36
No. Name Description Battery Module Power Input/Output Port Connects the power cable between adjacent battery PACKs 15 16 Wall Locking Bracket Mounting Hole Used for installing the wall locking bracket. Only the first and last battery PACKs require installation of the wall locking bracket. 2.2.2.3 BAT Series 61.4-112.6kWh Commercial & Industrial Battery System No. model PACK Quantity Rated Capacity 1 GW61.4-BAT-AC-G10 6 61.4 2 GW92.1-BAT-AC-G10 9 92.1 3 GW102.4-BAT-AC-G10 10 102.4 4 GW112.6-BAT-AC-G10 11 112.6 37 (kWh)
No. Name Description 1 LED Indicator Light - 2 Emergency Stop Button Pressing the emergency stop button will power down the battery system. 3 Front Door Lock - 4 PE Port 1 Connects to the battery grounding cable. 5 Bottom Baffle - 6 Left Side Cable Entry Hole 1 7 Left Side Cable Entry Hole 2 Inverter communication cable. 8 Left Side Cable Entry Hole 3 Inverter power cable. Air conditioner power cable & ET100 power cable. 38
No. Name Description 9 Right Side Cable Entry Hole 1 Battery cluster parallel power cable. 10 Right Side Cable Entry Hole 2 Battery cluster parallel communication cable. 11 Right Side Cable Entry Hole 3 Air conditioner power cable. 12 Back Mounting Plate Installation Hole 13 PE Port 2 Connects to the inverter grounding cable. 14 Air Conditioner Responsible for temperature control; the air conditioner refrigerant model is R134A. 15 Rear Door Lock - 16 Air Conditioner Drain Pipe Installation Port - 17 Explosion-proof Valve 18 Communication Cable Inlet/Outlet (Bottom) 19 Power Cable Inlet/Outlet (Bottom) 20 Battery Communication Cable Inlet/Outlet Installation hole position for the inverter back mounting plate. Responsible for explosion-proof, exhaust, and other functions. When abnormal pressure increase occurs inside the battery system, by opening the explosion-proof one-way valve exhaust port, internal gas is quickly and directionally released to prevent the battery system from exploding. Inlet/outlet for communication cables between the battery and inverter. Inlet/outlet for power cables between the battery and inverter. Inlet/outlet for battery cluster parallel communication cables. 39
No. Name Description 21 Battery Power Cable Inlet/Outlet (Positive) 22 Battery Power Cable Inlet/Outlet (Negative) 23 Foundation Fixing Hole Used to fasten the battery system to the foundation. 24 Handle - 25 Battery PACK Power Input/Output Port Positive 26 Battery PACK Power Input/Output Port Negative 27 Fan - 28 Battery PACK Communication Port 29 High-voltage Box Power Input/Output Port Negative 1 30 High-voltage Box Power Input/Output Port Positive 1 31 Molded Case Circuit Breaker 32 Black Start Button Controls the black start of the battery system. 33 Internal Communication Port 1 Inlet/outlet for battery cluster parallel power cables (positive). Inlet/outlet for battery cluster parallel power cables (negative). - - Communication between adjacent battery PACKs, communication with the high-voltage box, and fan power supply. Connects the power cables between the high- voltage box and battery PACK. Controls the high-voltage output of the battery system. Communication with battery PACK and battery PACK fan power supply port 1. 40
No. Name Description 34 Internal Communication Port 2 35 LAN Communication Port 36 External Communication Port 1 37 Air Switch Controls the low-voltage power supply of the battery system. 38 High-voltage Box Power Input/Output Port Positive 2 39 High-voltage Box Power Input/Output Port Negative 2 40 Access Control Switch Air conditioner communication, access control identification, emergency stop, and fire alarm signal communication port. LAN communication between batteries, used for transmitting cell-level information (Only supported on machines shipped after October 2025). Communication with inverter / placement of terminal resistor / battery system cluster parallel communication. Connects the power cables between the high- voltage box and inverter. Connects the power cables between the high- voltage box and inverter. Automatically disconnects when the door is opened to ensure the energy storage system is powered off. 41
No. Name Description 41 Temperature Detector 42 Smoke Detector The temperature detector monitors temperature through a dual thermistor network and outputs a voltage proportional to the external temperature. One thermistor is exposed to ensure good thermal contact with the surrounding air, while the other thermistor is thermally insulated; when an anomaly is detected, it emits red light to alert the operator. Suitable for environments with dust or smoke under normal conditions. • Wide operating voltage range. • The smoke detector uses the principle of scattered light to detect smoke entering the detector's inner cavity. Good response to slow-burning, smoldering fires. • Unaffected by wind or atmospheric pressure. • Some models are equipped with a flashing LED and magnetic test switch. • Alarm indicator: Red light-emitting diode (LED) emits red light. • 42
No. Name Description 43 Aerosol Fire Extinguishing Device 44 Document Shelf - 45 Fire Action Signal Port 46 Maintenance Hook Shelf 47 Lifting Ring Installation Hole - 48 Air Conditioner Switch Connects to the air conditioner power cable and controls the air conditioner power supply. Fire Protection System Description Monitors fire signals inside the cabinet and implements fire extinguishing. When a fire occurs, the aerosol fire extinguishing device ignites the thermal fuse upon receiving an electrical start signal or open flame. The electric igniter thermal fuse burns and activates the aerosol generator in the fire extinguishing device. The aerosol generator releases heat through a series of reactions to decompose the chemical coolant, allowing the aerosol generator and coolant to combine for fire extinguishing. Dry contact signal interface, normally NC (normally closed state). Voltage: 0-24Vdc, Current: 0.3A. Connects to the audible and visual alarm cable. When disassembling the Pack and PCU, the maintenance hook can be taken from here for operation. 43
1 2 3 4 Smoke Detector Heat Detector Aerosol Fire Extinguishing Device Temperature Detector & Smoke Detector ■ Temperature Detection Principle: The detector uses a negative temperature coefficient thermistor as the sensor, leveraging its sensitivity to ambient temperature to obtain environmental temperature information. The internal circuit converts this information into a voltage signal and transmits it to the microcontroller. The microcontroller analyzes and processes the signal using built-in intelligent algorithms to determine whether a fire alarm or fault condition is present. Smoke Detection Principle: The detector utilizes infrared light scattering principle 44 Explosion-Proof Valve
to detect fires. In a smoke-free state, it receives only very weak infrared light. When smoke enters the optical smoke detection chamber, the scattered light enhances the received light signal. When the smoke concentration reaches a certain level, an alarm signal is output. Technical Specifications Dimensions (mm) 102 × 55 Installation Requirements Screw Fixation indicator (Red) Flashes during monitoring, stays on Operating Temperature (℃) -40~+85 Relative Humidity ≤95%RH (Non-condensing) Explosion-Proof Valve ■ When the internal pressure of sealed products like battery enclosures rises rapidly, the explosion-proof check valve's exhaust port opens to quickly and directionally release the internal gas, thereby preventing explosions in sealed products such as battery boxes. Temperature Smoke Detector Detector when alarming 45
Technical Specifications Explosion Vent Valve Ingress Protection Rating IP68 Opening Area 570 mm2 Operating Temperature -40℃ ~ +130℃ Flame Retardancy UL94-V0 Aerosol Fire Extinguishing Device ■ When a fire occurs, upon receiving an electrical activation signal or when an open flame ignites the thermal fuse, the electric initiator or burning thermal fuse activates the aerosol-forming agent inside the fire extinguishing device. The heat released by the redox reaction of the aerosol-forming agent causes the chemical coolant to decompose, enabling both the aerosol-forming agent and the coolant to participate in fire suppression. Technical Specifications Aerosol Fire Extinguishing Device Operating Ambient Temperature Range -30℃ ~ +70℃ Operating Ambient Relative Humidity ≤95%RH Thermal Activation Temperature 185±10℃ 46
Fire Protection Logic The fire protection for this battery system employs a graded response design. When a fire occurs inside a battery Pack, it is first detected by the Pack-level detector, which immediately activates the Pack's internal aerosol fire extinguishing device for initial suppression. If the fire is not controlled and spreads further, cabinet-level fire protection is triggered. When both the smoke detector and temperature detector detect a fire, or when an open flame ignites the thermal fuse (at a temperature of 180°C), the cabinet-level aerosol fire extinguishing device is automatically activated for comprehensive fire suppression. The aerosol-forming agent produces extinguishing agents through a combustion reaction, and the heat released during the reaction decomposes the chemical coolant. The aerosol fire extinguishing agent and coolant work synergistically to extinguish the fire. Simultaneously, the BMS receives feedback signals from the fire protection system, triggering external audible and visual alarms until the fire is completely extinguished. 47
2.2.3 Smart Meter The Smart Meter can measure parameters such as grid voltage, current, power, frequency, and electrical energy, and transmit this information to the inverter to control the input and output power of the energy storage system. GM3000&CT 48
GM330&GMK330&CT No. model Applicable Scenarios 1 GM3000 CT replacement not supported, CT ratio: 120A: 40mA 2 GM330 3 GMK330 2.2.4 smart dongle The smart dongle is primarily used for real-time transmission of various inverter CT can be purchased from GoodWe or self-sourced, CT ratio requirement: nA: 5A nA: CT primary side input current, the range of n is 200- 5000 • 5A: CT secondary side output current • CT shipped with the meter, CT ratio: 120A: 40mA • 200A: 50mA (Brazil only) • 49
power generation data to the SEMS Portal remote monitoring platform, and for connecting to the smart dongle via the SolarGo APP for local device commissioning and debugging. No. model Signal Type Applicable Scenario 1 Wi-Fi Kit WiFi 2 WiFi/LAN Kit-20 WiFi, LAN, Bluetooth 3 LS4G Kit-CN 4G Kit-CN 4G 4G Kit-CN-G20 4G, Bluetooth 4 4G Kit-CN-G21 4G, Bluetooth, CNSS 5 Ezlink3000 WiFi, LAN, Bluetooth 2.3 Supported Grid Types Single inverter scenario Master unit in multi-inverter scenario 50
2.4 System Working Mode Self-Use Mode The fundamental operating mode of the system. • • PV generation prioritizes supplying power to the loads. Excess power charges the battery, and any remaining power is sold to the grid. When PV generation is insufficient to meet the loads' demand, the battery supplies power to the loads. When the battery power is also insufficient, the grid supplies power to the loads. 51
Backup Mode Recommended for use in areas with an unstable grid. • • When the grid fails, the inverter switches to off-grid operation mode, and the battery discharges to supply power to the loads, ensuring uninterrupted power for the BACK-UP Loads. When the grid is restored, the inverter switches its operation mode back to grid-tied. • To ensure the battery SOC is sufficient to maintain normal system operation during off-grid periods, the system will charge the battery using PV or grid power to the backup power SOC during grid-tied operation. If purchasing electricity from the grid to charge the battery is required, please ensure it complies with local grid regulations and laws. 52
TOU Mode Subject to compliance with local laws and regulations, buy and sell electricity during different time periods based on peak and off-peak grid electricity price differences. For example: During off-peak price periods, set the battery to charging mode to purchase electricity from the grid for charging. During peak price periods, set the battery to discharging mode to supply power to the loads via the battery. 53
TOU Mode $\textcircled{1}$
PV: Charge battery in priority
TOU curve
Valley price
Peak price
Valley price
Peak price
Valley price
Battery fully charged
PV cannot cover load needs
Battery discharge
Battery charge
Self use
Remaining power export
PV curve
Load consumption
Charge
Discharge
Charge
Standby
Discharge
Charge
SLG00NET0004Delayed Charging Mode Suitable for areas with grid-connected power output limitations. • • Setting a peak power limit can direct PV generation exceeding the grid-connection limit to charge the battery; or set a PV charging period to utilize PV generation for charging the battery during that period. 55
Delayed Charging $\textcircled{1}$
PV > Peak Limit
Switch to Charge: enabled/disabled
Battery discharge
Battery charge
Self use
Remaining power export
PV curve
Load consumption
PV covers load needs
Discharge
Standby
Charge
Standby
Discharge
SLG00NET0006Delayed Charging $\textcircled{2}$
PV < Peak Limit
Switch to Charge: enabled
Battery discharge
Battery charge
Self use
Remaining power export
PV curve
Load consumption
Charging start
PV covers load needs
PV cannot cover load needs
Discharge
Standby
Charge
Standby
Discharge
SLG00NET0007Demand Control Mode Primarily applicable to commercial and industrial scenarios. • • When the total load power consumption exceeds the electricity quota within a short period, battery discharge can be utilized to reduce the portion of consumption exceeding the quota. • When the SOC of both inverter battery strings is lower than the reserved SOC for demand control, the system purchases electricity from the grid based on the time period, load consumption, and the peak purchase power limit. When the SOC of only one inverter battery string is lower than the reserved SOC for demand control, the system purchases electricity from the grid based on the load consumption and the peak purchase power limit. 58
Peakshaving $\textcircled{1}$
BAT1/BAT2 SOC < 80
Reserved SOC For Peakshaving: 80
Grid supplies power to loads
Battery discharge
Battery charge
PV supplies power to loads
PV+battery supply power to loads
PV curve
Load consumption < Import Power Limit
Start Time
Import Power Limit
Grid+battery supply power to loads
Standby
Discharge
Charge
Standby
SLG00NET0010Off-Grid Mode Do not operate in pure off-grid mode when the inverter is not connected to the battery system. When the grid fails, the inverter switches to off-grid operation mode. During the day, PV generation prioritizes supplying power to the loads, with excess power charging the battery. • At night, the battery discharges to supply power to the loads, ensuring uninterrupted power for the BACK-UP Loads. • Off-Grid SOC Recovery: After the system operates off-grid, the battery gradually • NOTICE 60
recovers to the minimum SOC level through PV generation or other power generation methods. 2.5 Features Specific features are subject to the product's actual configuration. AFCI The inverter integrates an AFCI circuit protection device to detect arc faults and quickly cut off the circuit when detected, thereby preventing electrical fires. Causes of arc faults: NOTICE 61
Damaged connector connections in the PV system. • Incorrect or damaged cable connections. • Aging connectors or cables. • Arc Detection Method The inverter integrates AFCI functionality, complying with the IEC 63027 standard. • When the inverter detects an arc fault, the time and fault phenomenon can be displayed via the App. • • After the inverter triggers an AFCI alarm, it will shut down for protection. The inverter will automatically reconnect to the grid and resume operation after the alarm is cleared. Auto-reconnection: If the inverter triggers an AFCI alarm < 5 times within 24 hours, the alarm can be automatically cleared after five minutes, and the inverter will reconnect to the grid and resume operation. ○ Manual reconnection: If the inverter triggers the 5th AFCI alarm within 24 hours, the alarm must be cleared manually before the inverter can reconnect to the grid and resume operation. model Label Description GW12KL-ET GW15K-ET F-I-AFPE-1-2/2-2 GW20K-ET GW18KL-ET GW20K-ET GW29.9K-ET F-I-AFPE-1-2/4-2 GW30K-ET Three-Phase Unbalanced Output F: Full coverage I: Integrated AFPE: Detection and interruption capability provided 1: 1 monitored string per input port 2/2: 2/2 input ports per channel 2: 2 monitored channels F: Full coverage I: Integrated AFPE: Detection and interruption capability provided 1: 1 monitored string per input port 2/4: 2/4 input ports per channel 2: 2 monitored channels 62
The inverter's grid-tie port and BACK-UP port both support three-phase unbalanced output, allowing loads of different power ratings to be connected to each phase. The maximum output power per phase for different models is shown in the table below: No. model Maximum Output Power per Phase 1 GW12KL-ET 4kW 2 GW18KL-ET 6kW 3 GW15K-ET 5kW 4 GW20K-ET 6.7kW 5 GW25K-ET 8.3kW 6 GW29.9K-ET 10kW 7 GW30K-ET 10kW load control The inverter's dry contact control port supports connecting additional contactors to control the switching on or off of loads. It supports household loads, heat pumps, etc. The load control methods are as follows: Time control: Set the time to switch the load on or off. The load will automatically turn on or off within the set time period. • Switch control: When the control mode is set to ON, the load will turn on; when set to OFF, the load will turn off. • • BACK-UP Loads control: The inverter has a built-in relay dry contact control port, which can control whether the load is switched off via the relay. In off-grid mode, if an overload is detected on the BACK-UP port and the battery SOC value falls below the off-grid protection setting, the load connected to the relay port can be switched off. Rapid Shutdown(RSD) In a rapid shutdown system, the rapid shutdown transmitter and receiver work together to achieve rapid system shutdown. The receiver maintains module output by receiving signals from the transmitter. The transmitter can be external or built into the inverter. In an emergency, by enabling an external triggering device, the transmitter can be deactivated, thereby shutting down the modules. 63
• External Transmitter Transmitter Models: GTP-F2L-20, GTP-F2M-20 https://en.goodwe.com/Ftp/Installation-instructions/RSD2.0-transmitter.pdf ○ Receiver Models: GR-B1F-20, GR-B2F-20 https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_RSD-20_Quick- Installation-Guide-POLY.pdf ○ • Built-in Transmitter External Triggering Device: External switch ○ Receiver Models: GR-B1F-20, GR-B2F-20 https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_RSD-20_Quick- Installation-Guide-POLY.pdf ○ 64
3 Check and Storage 3.1 Check Before Receiving Before receiving the product, please carefully check the following: 1. Check if the outer packaging is damaged, such as deformation, holes, cracks, or other signs that might cause damage to the equipment inside the packaging. If damaged, do not open the packaging and contact your dealer. Check if the device model is correct. If it does not match, do not open the packaging and contact your dealer. 2. 3.2 deliverables WARNING Check if the type and quantity of the delivered items are correct and if there is any damage to their appearance. If damaged, please contact your dealer. After removing delivered items from the packaging, do not place them on rough, uneven, or sharp surfaces to avoid paint chipping. 3.2.1 Inverter Deliverables Part Description Part Description Inverter x 1 Backplate x 1 Wall-mounting fastening screws x 2 65 PV connector GW12KL-ET, GW15K- ET, GW20K-ET: 4 GW18KL-ET, GW25K- ET, GW29.9K-ET, GW30K-ET: 6
Part Description Part Description PV wiring tool x 1 6PIN communication terminal x 1 Protective PE screw x 1 Grounding terminal x 1 7PIN communication terminal x 1 3PIN communication terminal x 1 PIN terminal x N The quantity of PIN terminals provided with the box varies depending on the inverter configuration. Please refer to the actual shipment. BMS/Meter Communication cable GW12KL-ET, GW15K- ET, GW20K-ET: 2 GW18KL-ET, GW25K- ET, GW29.9K-ET, GW30K-ET: 3 Expansion bolt x 6 66
Part Description Part Description Please refer to the actual shipment OT terminal x 12 • AC terminal flange nut x 20 • • Insulation board for AC terminal x 1 or • AC terminal protective cover x 1 or Hexagon screwdriverx 1 • screwdriver x 1 or smart dongle x 1 Product documentation x 1 (Optional) Wiring tool x 1 Battery connector: GW12KL-ET, GW15K-ET, GW20K-ET: 1 GW18KL-ET, GW25K-ET, GW29.9K-ET, GW30K-ET: 2 Wiring tool Battery connector 67 Smart meter and accessories x 1 Please refer to the actual shipment
Part Description Part Description Wiring tool (Optional) Wiring tool x 2 Hexagon screwdriverx 1 Battery connector: GW12KL-ET, GW15K-ET, GW20K-ET: 1 GW18KL-ET, GW25K-ET, GW29.9K-ET, GW30K-ET: 2 Hexagon screwdriver Battery connector Part Description Part Description cable tie x 10 expansion bolt x 4 M5 hex screw x 10 M5 nut x 5 Right side panel of protective cover x 1 Bottom panel of protective cover x 1 Table39 Protective Cover Accessory (Australia Only) 3.2.2 Batteries Deliverables 3.2.2.1 Lynx C Series 60kWh Industrial & Commercial Battery System 68 Left side panel of protective cover x 1 Front cover panel of protective cover x 1
Component Quantity Component Quantity Battery system x 1 GW60KWH-D-10: Includes AC cabinet GW60KWH-D-10 (without extension cabinet): Does not include AC cabinet or 69 • Battery-to- battery connection aluminum busbar When all busbars are shipped with accessories, the quantity in accessories is 10 • When some busbars are shipped with accessories, the quantity in accessories is 3 (other busbars are pre-installed on the battery)
Component Quantity Component Quantity Battery-to-high voltage box connection aluminum busbar • When the busbar is shipped with accessories, the quantity in accessories is 1 • When the busbar is pre-installed on the battery for shipment, the quantity in accessories is 0 Battery-to-battery fixing screw • When all busbars are shipped with accessories, the quantity of screws in accessories is 22 • Lifting ring x 4 When some busbars are shipped with accessories, the quantity of screws in accessories is 6 Inverter Back-up terminal block x 5 70 Battery-to-high voltage box fixing screw x 2 M12 waterproof component x 2
Component Quantity Component Quantity M18 waterproof component x 2 M22 waterproof component x 4 cable tie x 10 Inverter-to-high voltage box power cable GW60KWH-D-10 (without extension cabinet): 0 GW60KWH-D-10: 1 Expansion screw x 4 Air conditioning water pipe x 1 M5 nut x 9 71 M20 waterproof component x 2 Inverter battery terminal block GW60KWH-D-10 (without extension cabinet): 0 GW60KWH-D-10: N N: Please refer to the actual product shipment High voltage box power terminal block GW60KWH-D-10 (without extension cabinet): 2 GW60KWH-D-10: 1
Component Quantity Component Quantity Grounding terminal x 1 Product documentation x 1 Wrench x 0: Fire department has "Do Not Touch" label Wrench x 1: Other 3.2.2.2 BAT-S Series 15.3-56.3kWh High Voltage Battery Supported configurations and installation plans vary by region. For details, please contact sales. Battery Pack Inverter-to-high voltage box communication cable GW60KWH-D-10: 1 GW60KWH-D-10 (without extension cabinet): 0 Terminating resistor x 2 GW60KWH-D-10 (without extension cabinet): 1 GW60KWH-D-10: 0 - - NOTICE 72
Component Description Stacked Installation Rack Installation PCU Part Description Stack Installation Rack Installation Accessories Stack Mounting • Battery PACK GW15.3-BAT-I-G10:× 3 • GW20.4-BAT-I-G10:× 4 • GW25.6-BAT-I-G10:× 5 • GW30.7-BAT-I-G10:× 6 • GW35.8-BAT-I-G10:× 7 • GW40.9-BAT-I-G10:× 8 • GW46.0-BAT-I-G10:× 9 • GW51.2-BAT-I-G10:× 10 • GW56.3-BAT-I-G10:× 11 • PCU × 1 73
Part Description Part Description Ground lock bracket×4 Equipotential bonding strip×15 M5 screw×N Cable gland×1 Expansion bolt×8 Adjustable foot×4 Base×1 Power connector×2 B- power cable×1 B+ power cable×1 Internal battery power cable ×N Grounding terminal ×2 74 Wall lock bracket×4 Battery to inverter communication cable×1 Internal battery communication cable ×N M12 expansion bolt ×4
Part Description Part Description Nameplate×1 Cable tie×10 adapter bonnet×4 (Included only for units shipped after April 3, 2026) Rack Mounting • Part Description Part Description Battery Rack ×1 Rubber Pad×4 M5 screw×N ST6.3 screw×4 Adjustable Feet×4 Wall Mounting Bracket×2 Power Connector×2 B- Power Cable×1 B+ Power Cable×1 75 Product documentation×1 Battery to Inverter Communication Cable×1
Part Description Part Description Internal Battery Power Cable×N Grounding terminal×2 Nameplate×1 Cable Tie×10 adapter bonnet×1 Product Documentation×1 3.2.2.3 BAT Series 61.4-112.6kWh Industrial & Commercial Battery System Component Description Component Description battery cabinet×1 Expansion screw×4 Grounding M5 screw×3 Grounding terminal×3 Inverter battery connection terminal 25mm²×2 76 Internal Battery Communication Cable×N M12 Expansion Bolt×4 Inter-battery connection terminal 50mm²×2
Component Description Component Description Pack series wiring harness×N GW61.4-BAT-AC-G10:×5 • GW92.1-BAT-AC-G10:×8 • GW102.4-BAT-AC-G10:×9 • GW112.6-BAT-AC-G10:×10 • Inverter battery connection (positive)×1 Inverter battery connection (negative)×1 Battery to inverter communication network cable×1 Lifting ring×4 Cable tie×20 Air conditioner water pipe kit×1 fireproofing mud×8 Corrugated pipe connector×6 Product documentation×1 - - 3.2.3 Smart Meter Deliverables (GM3000) Part Quantity Part Quantity Pack negative to high-voltage box negative wiring harness×1 Adapter bracket×2 (Required for ET100 only) Air conditioner power supply wiring harness kit×1 25mm² to 10mm² round tube terminal×4 77
Smart meter and CT x 1 2PIN terminal and RJ45 terminal adapter cable x 1 PIN terminal x 3 USB plug x 1 screwdriver x 1 Product documentation x 1 3.2.4 Smart Meter Deliverables GM330&GMK330 3.2.4.1 Attachment List Component Description Component Description Smart Meter x1 GMK330: CT×3; GMK360: CT×6; GM330: CT x 0. 6PIN Communication Terminal x1 For GM330. Meter Communication Terminal For GMK330/GMK360. 2PIN Terminal to RJ45 Terminal Adapter Cable x 1 2PIN Communication Terminal x1 For GM330. 7PIN Communication Terminal x1 For GM330. RS485 Communication Terminal x 1 screwdriver x1 78
Component Description Component Description PIN terminal GMK330/GMK360: x 5 ; GM330: x 6. 3.3 Storage [1] Storage time is calculated from the SN date on the battery outer packaging. After exceeding the storage cycle, charging and discharging maintenance is required. (Battery maintenance time = SN date + charging and discharging maintenance cycle). For the method to view the SN date, refer to: 10.4.SN Code Meaning(Page 320). [2] After charging and discharging maintenance is qualified, if there is a Maintaining Label on the outer box, please update the maintenance information on the Maintaining Label. If there is no Maintaining Label, please record the maintenance time and battery SOC yourself and keep the data properly to facilitate the preservation of maintenance records. If the device is not put into use immediately, please store it according to the following requirements. After long-term storage, the device must be inspected and confirmed by professionals before it can be used. 1. If the inverter is stored for more than two years or not operated for more than 6 months after installation, it is recommended to have it inspected and tested by professionals before putting it into use. 2. To ensure the good electrical performance of the internal electronic components of the inverter, it is recommended to power it on every 6 months during storage. If it has not been powered on for more than 6 months, it is recommended to have it inspected and tested by professionals before putting it into use. 3. To protect battery performance and service life, it is recommended to avoid long- term idle storage. Prolonged storage may cause deep discharge of the battery, leading to irreversible chemical loss, capacity attenuation, or even complete failure. It is advised to use it promptly. If the battery needs long-term storage, please maintain it according to the following requirements: Product Documentation x 1 NOTICE 79
Recomm ended Storage Tempera ture Battery Storage Initial SOC Range Charge/Discharge Maintenance Cycle[1] Battery Lynx C Series 60kWh Commercial & Industrial Battery System -20~0℃, ≤1 month 30%~40% 0~35℃ 0~+35℃, ≤6 months 35~+45℃, ≤1 month BAT-S Series 15.3-56.3kWh High Voltage Battery -20~35℃ (≤12 30%~40% 0~35℃ months) 35~+45℃ (≤6 months) BAT-C Series 61.4-112.6kWh Commercial & Industrial Battery System Packaging Requirements: Ensure that the outer packaging box is not removed and the desiccant inside the box is not lost. Environmental Requirements: Ensure that the device is stored in a cool place, avoiding direct sunlight. 1. 2. Ensure the storage environment is clean, with appropriate temperature and humidity ranges, and no condensation. If there is condensation on the device ports, do not install the device. Ensure that the device is stored away from flammable, explosive, corrosive, and other hazardous materials. 3. Stacking Requirements: Ensure that the stacking height and direction of the inverters are arranged according to the instructions on the packaging box labels. 1. 80 Battery Maintena nce Method[2] Please consult the dealer or after- sales service center for the maintena nce method.
Ensure that there is no risk of tipping after the inverters are stacked. 2. 81
4 Installation When performing equipment installation and electrical connections, please use the components delivered with the shipment. Otherwise, any resulting equipment damage will not be covered by the warranty. 4.1 System Installation and Commissioning Procedure DANGER 82
4.2 Installation Requirements 4.2.1 Installation Environment Requirements If installed in an environment below 0°C, the battery will be unable to recharge and restore energy after being depleted, resulting in battery undervoltage protection. GW60KWH-D-10:Charging temperature range: 0<T<55°C;Discharging temperature range: -25<T<55°C The equipment must not be installed in flammable, explosive, corrosive, or similar environments. 1. The temperature and humidity of the equipment installation environment must be within a suitable range. 2. The installation location must be out of reach of children and avoid easily accessible positions. 3. During Inverter operation, the enclosure temperature may exceed 60°C. Do not touch the enclosure before it cools down to prevent burns. 4. The Inverter should be installed in a location sheltered from direct sunlight, rain, 5. NOTICE 83
snow accumulation, etc. It is recommended to install it in a covered position; a sunshade can be constructed if necessary. Adverse environmental conditions such as direct sunlight and high temperatures may cause the Inverter output power to be derated. 6. The installation space must meet the equipment's ventilation, heat dissipation, and operational space requirements. 7. 8. The installation environment must satisfy the equipment's protection rating. Inverters and Smart Communication Sticks are suitable for both indoor and outdoor installation; • Electricity meters are suitable for indoor installation; • • Lynx C Series 60kWh Commercial & Industrial Battery System and BAT-C Series 61.4-112.6kWh Commercial & Industrial Battery System are suitable for indoor and outdoor installation. The BAT-S Series 15.3-56.3kWh High Voltage Battery is suitable for indoor installation and must be kept ventilated. When installing equipment indoors, ensure there are no obstacles within a 10- meter diameter of the installation location. 9. During construction and installation, ensure the bottom of the equipment is higher than the local historical highest water level. 10. 11. The installation height of the equipment should facilitate operation and maintenance, ensuring the equipment indicator lights, all labels are easily viewable, and the wiring terminals are easily accessible. The installation altitude of the equipment must be below the maximum operating altitude. 12. 13. The battery system must be installed on a flat, dry ground surface. It must not be placed in a recessed or sloped area and is strictly prohibited from being installed on ground prone to water accumulation or sinking. Ensure the ground can bear the weight of the battery system. 14. Before installing equipment outdoors in salt damage areas, consult the equipment manufacturer. Salt damage areas mainly refer to regions within 500m of the coastline. The affected area is related to sea wind, precipitation, terrain, etc. 15. Keep away from strong magnetic field environments to avoid electromagnetic interference. If there are radio stations or wireless communication equipment operating below 30MHz near the installation location, install the equipment according to the following requirements: • Inverter: Add a ferrite core with multiple windings on the Inverter's DC input or AC output lines, or add a low-pass EMI filter; OR the distance between the Inverter and the wireless electromagnetic interference source should exceed 30m. Other equipment: The distance between the equipment and the wireless • 84
electromagnetic interference source should exceed 30m. The length of DC and communication cables between the battery and the Inverter must be less than 3m. Please ensure the installation distance between the Inverter and the battery meets the cable length requirement. 16. 85
4.2.2 Foundation Installation Requirements The foundation material must be C25 plain concrete hardened ground or other 1. 86
non-combustible surfaces. The foundation must have pre-reserved trenches or cable outlets to facilitate equipment cabling. 2. Equipment (including height, embedded expansion screw parts, conduits, etc.) should be adjusted according to the process and on-site conditions. 3. The top elevation of the equipment foundation can be adjusted according to the equipment and actual on-site requirements. 4. Ensure the equipment is installed level and must not be tilted or inverted. 5. 6. Trench Requirements: If the equipment uses bottom cable entry, the trench must have a dust-proof and rodent-proof design to prevent foreign objects from entering. • • The trench must have a waterproof and moisture-proof design to prevent cable aging and short circuits, which could affect the normal operation of the equipment. • As the equipment cables are relatively thick, sufficient space for the cables must be reserved in the trench design to ensure smooth and unworn cable connections. The conduit may be replaced with four 125mm-diameter PVC pipes on-site. Conduit does not need to be pre-installed for indoor environments. NOTICE 87
4.2.3 Installation Space Requirements When installing devices in the system, sufficient space should be reserved around the devices to ensure adequate installation and heat dissipation space. The specific numerical values for battery installation space can be adjusted based on the actual installation scenario and local regulations. NOTICE 88
BAT 61.4-112.6kWh C&I BAT 15.3-56.3kWh HV
4.2.4 Tool Requirements During installation, it is recommended to use the following installation tools. If necessary, other auxiliary tools can be used on-site. Installation Tools Tool Type Description Tool Type Description diagonal plier RJ45 connector crimping tool wire stripper YQK-70 hydraulic pliers VXC9 hydraulic pliers Level bar open-end wrench hammer drill (drill bit Φ8mm) rubber hammer socket wrench NOTICE PV terminal crimping tool PV-CZM-61100 torque wrench M5/M6/M8/M12/M16/ M18/M22 90
Tool Type Description Tool Type Description marker pen multimeter range ≤1100V heat shrink tubing heat gun cable tie vacuum cleaner Level bar Personal Protective Equipment Tool Type Description Tool Type Description Insulated gloves, protective gloves Goggle Safety shoes 4.3 Equipment Handling Dust mask 91
1. When performing operations such as transportation, turnover, and installation, it must comply with the laws, regulations, and relevant standard requirements of the country or region. 2. Before installation, the equipment needs to be moved to the installation site. To avoid personal injury or equipment damage during the moving process, please note the following: • Please assign personnel according to the weight of the equipment to prevent the equipment from exceeding the weight range that can be manually carried, which could cause injury. Please wear safety gloves to avoid injury. • Please ensure that the equipment remains balanced during the moving process to avoid dropping and tipping over. • During the moving process, please ensure that the cabinet doors are locked. • The equipment can be transported to the installation site using hoisting or a forklift. • When using hoisting to move the equipment, please use flexible slings or lifting belts, with a single belt's load-bearing capacity ≥2t. • When using a forklift to move the equipment, the forklift's load-bearing capacity must be ≥2t. • Lynx C Series 60kWh Commercial & Industrial Battery System • Forklift Transport Method One WARNING NOTICE 92
Forklift Transport Method Two Hoisting Transport: 93
BAT-SSeries 15.3-56.3kWh High Voltage Battery • BAT-CSeries 61.4-112.6kWh Commercial & Industrial Battery System • Remove the baffles before using a forklift to move the equipment. • The battery system is secured to the pallet with bottom screws during shipment. Please remove the pallet before installation. • NOTICE 94
4.4 Installing the Inverter Installing the Inverter in the Battery System Cabinet Ensure that the inverter is installed securely to prevent it from falling and injuring people. Secure the inverter backplate bracket to the battery system cabinet. 1. 2. (Optional) Use a DC switch lock to lock the DC switch in the “OFF” position, and hang the inverter on the backplate. The DC switch lock is user-provided; please ensure the aperture of the DC switch lock meets the requirements. Tighten the screws on both sides to secure the backplate and inverter, ensuring the inverter is installed firmly. 3. CAUTION 95
Installing the Inverter on the Wall When drilling holes, ensure the drilling location avoids water pipes, cables, etc., inside the wall to prevent danger. • When drilling, please wear safety goggles and a dust mask to avoid inhaling dust into the respiratory tract or getting it in the eyes. • Ensure the inverter is installed securely to prevent it from falling and injuring personnel. • Place the backplate horizontally on the wall, and use a marker to mark the drilling positions. 1. Use an impact drill to drill holes. 2. Use expansion screws to secure the inverter backplate bracket to the wall. 3. 4. Use a DC switch lock to lock the DC switch in the “OFF” position, and hang the inverter on the backplate. (Optional) For Australia only, the DC switch lock is user- provided; please ensure the aperture of the DC switch lock meets the requirements. CAUTION 96
(Optional) Lower the handle. 5. Tighten the screws on both sides to secure the backplate and inverter, ensuring the inverter is installed firmly. 6. Installing the Protective Cover (Australia Only) 97
Step1: Assemble the protective cover. Step2: Install the front cover plate. Step3: Secure the protective cover to the wall/side of the battery cabinet, and install the circuit breaker, waterproof box, and cable tray according to local regulations. For specific requirements, refer to the table below. Equipment Recommended Model/Specifications Description break er Select according to local laws and regulations 2P DC switch • User to provide. Rated Current ≥63A • Nominal Voltage ≥1000V • 98
Equipment Recommended Model/Specifications Description Water proof Box Cable Tray 4.5 Installing the Battery System Check that the ground is level and not sloped before installation. • Ensure the energy storage system is vertical and flush against the ground, with no risk of tipping. • 4.5.1 Open the Cabinet Door User to provide. If the hole spacing of the waterproof box does not meet the requirements and cannot be fixed on the battery cabinet, please provide your own mounting plate. First, drill holes in the mounting plate according to the requirements and fix it on the battery cabinet, then fix the waterproof box on the mounting plate. Waterproof rating > IP65 Hole spacing requirements: Left-right hole spacing: 157mm • Up-down hole spacing: 318mm • Style and dimensions are for reference only a: 250mm b: 150mm c: 510mm Style for reference only User to provide. WARNING 99
Do not open the cabinet door during handling and installation. • Please close the cabinet door after system installation, wiring, and commissioning. • Step 1: Use the key to unlock the cabinet door. Step 2: Turn the door handle to open the cabinet door. Lynx C Series 60kWh Commercial & Industrial Battery System • BAT Series 61.4-112.6kWh Commercial & Industrial Battery System • 4.5.2 Installing the Lynx C Series 60kWh Commercial & Industrial Battery System Step 1: Use a marker pen to mark the drilling positions on the level ground. Step 2: Use an impact drill with a 14mm diameter drill bit to create holes WARNING 100
approximately 80mm deep, and install expansion bolts. Step 3: Move the battery system to the hole positions and use a socket wrench to tighten the expansion bolts. 4.5.3 Installing BAT-S Series 15.3-56.3kWh High-Voltage Battery Stack Installation • Step 1: Install adjustable feet under the base. The adjustable height range is 35- 45mm. Step 2: Secure the floor-lock bracket onto the base. Step 3: Use a pen to mark the drilling positions for expansion bolts on the floor. Step 4: Install the expansion bolts. Step 5: Secure the floor-lock bracket to the floor using the expansion bolts. Step 6: Stack the battery PACKs. Pre-tighten the wall-lock brackets on the first and last battery PACK. Step 7: Use a pen to mark the drilling positions for expansion bolts on the wall. Secure the wall-lock bracket with expansion bolts, then tighten the wall-lock bracket on the battery PACK. Step 8: Place the high-voltage box. Step 9: Install the equipotential bonding strap and the wire protection sleeve. 101
Battery Rack Installation • Installing the Battery Rack Step1: Lay the bracket flat. Align all holes according to the serial number markings and secure them using M5 screws. Step2: Position the rack vertically according to the arrow markings. Securing the Battery Cabinet Type I ○ 102
Step3: Use a marker to mark the drilling positions for expansion bolts on the level floor. Step4: Install the expansion bolts and secure the battery rack to the level floor using them. Type II ○ Step3: Lay the rack horizontally and install adjustable feet on the bottom of the rack. Step4: Position the rack vertically. Secure the rack to the wall using wall-lock brackets. Installing the High-Voltage Box and Battery PACK Step5: Slide the high-voltage box and battery PACKs into the rack in sequence, and attach the labels on the side of the rack. Step6: Secure the high-voltage box and battery PACK using M5 screws. 103
1. 190mm 2. M5 4N·m 3. Type I /类型 I 4. M12 50N·m BAT10INT0020
4.5.4 Installing BAT Series 61.4-112.6kWh Commercial & Industrial Battery System Step 1: Secure the battery system to the foundation. Mark the drilling positions according to the dimensions shown in the diagram. 1. Use an impact drill to create the holes and install expansion bolts. 2. 105
Move the battery rack to the hole positions and fasten the batteries to the foundation using the expansion bolts. 3. Step 2: Remove the protective covers from the smoke and temperature sensor alarms. The smoke sensor and temperature sensor alarms are shipped with protective covers on the batteries. These covers must be removed for the alarms to function properly. Step 3: Install the air conditioning drain pipe. Install the air conditioning drain pipe connector. 1. Secure the air conditioning drain pipe to the connector. 2. 106
4.6 Installing the Smart Meter In areas with lightning danger, if the meter cable length exceeds 10m and the cable is not laid using grounded metal conduits, it is recommended to install external lightning protection devices. GM3000 GM330&GMK330 WARNING 107
GMK10INT0003 108 GMK10INTOO03 108
5 System Wirings The erection, routing, and connection of cables must comply with local laws, regulations, and standard requirements. • All operations during electrical connections, as well as the specifications of cables and components used, must meet local legal and regulatory requirements. • • Before performing electrical connections, please disconnect the device's DC switch and AC output switch to ensure the device is powered off. Live working is strictly prohibited, otherwise it may lead to DANGER such as electric shock. Cables of the same type should be bundled together and separated from cables of different types. It is prohibited to intertwine or cross-arrange them. • • If the cable is subjected to excessive tension, it may lead to poor connections. When connecting, please leave a certain length of cable slack before connecting it to the inverter's terminal ports. • When crimping terminal lugs, ensure that the conductor part of the cable is in full contact with the terminal lug. Do not crimp the cable insulation together with the terminal lug. Otherwise, it may cause the device to fail to operate, or after operation, unreliable connections may lead to heating and damage to the inverter terminal block, among other conditions. When performing electrical connections, wear personal protective equipment such as safety shoes, protective gloves, and insulating gloves as required. • Only qualified professionals are permitted to perform electrical connection operations. • The cable colors in the diagrams of this document are for reference only. Specific cable specifications must comply with local regulatory requirements. • For parallel systems, please adhere to the safety precautions in the user manuals corresponding to the related products within the system. • 5.1 System Wiring Electrical Block Diagram DANGER NOTICE 109
• Depending on regional regulatory requirements, the wiring methods for the N and PE lines of the inverter's ON-GRID and BACK-UP ports differ. Please comply with local regulations. • The inverter's ON-GRID AC port has a built-in relay. When the inverter is in off- grid mode, the built-in ON-GRID relay is open; when the inverter is in grid- connected mode, the built-in ON-GRID relay is closed. • When the inverter is powered on, the BACK-UP AC port is live. If maintenance on the BACK-UP Loads is required, please power down the inverter to avoid the risk of electric shock. N and PE lines are connected together in the distribution box • To maintain neutral integrity, the neutral wires on the grid-connected side and the off-grid side must be connected together; otherwise, the off-grid function cannot operate normally. The diagram below illustrates the grid system for regions such as Australia and New Zealand: • NOTICE NOTICE 110
N and PE lines are separately wired in the distribution box • Ensure the protective earth wire for BACK-UP is correctly and securely connected; otherwise, the BACK-UP function may operate abnormally in the event of a grid fault. The following wiring method applies to regions other than Australia, New Zealand, etc.: • NOTICE 111
5.2 Detailed System Wiring Diagram When all loads in the photovoltaic system cannot consume the electricity generated by the system, the surplus power will be fed back into the grid. In this case, a smart meter or CT can be used to monitor the system's power generation and control the amount of electricity fed into the grid. Connecting a smart meter enables the output power limit and load monitoring functions. • After connecting the smart meter, please enable the "Export power limit" function via the SolarGo App. • The Detailed System Wiring Diagram only shows wiring examples using some model devices. Please refer to the corresponding wiring instruction chapters based on the actual devices used for wiring. 112
• In coupling scenarios, to implement grid-connected inverter power generation monitoring and load monitoring functions, dual-meter networking is required. Meter 1 is used to monitor the system's grid-connected power. ○ Meter 2 is used to monitor the grid-connected inverter's power generation. ○ By integrating the data from Meter 1 and Meter 2, the monitoring platform can achieve real-time monitoring of load power consumption. ○ If the grid-connected inverter requires output power limitation, please connect a meter or CT device separately. • Meter 1 (Grid Side) Meter 2 (Grid-tied Inverter AC Side) GM3000 GM3000 GM3000 GM330 GM3000 GMK330 GM330 GM330 GM330 GM3000 GM330 GMK330 GMK330 GMK330 GMK330 GM3000 GMK330 GM330 Wiring diagram with protective cover (Australia only) NOTICE Dual Meter Configuration Scenarios 113
5.2.1 Detailed System Wiring Diagram for Single Inverter General Scenarios Scenario with GM3000 Scenario with GM330 114
Scenario with GMK330 115
Grid-tied Inverter Power Generation Monitoring and Load Monitoring Networking Solution for Coupled Scenarios For output power limitation in coupled scenarios, please connect meters or CTs separately for the grid-tied inverter. GM330 meter + GM330 meter 116
GMK330 meter + GMK330 meter 117
5.2.2 Detailed System Wiring Diagram for Parallel System • In a parallel system scenario, the inverter connected to the Ezlink3000 smart communication stick and the meter is the master inverter, while others are slave inverters. In the system, do not connect the smart communication stick to slave inverters. • If devices such as DRED, RCR, remote shutdown devices, NS Protection, SG Ready heat pumps, etc., need to be connected in the system, please connect them to the master inverter. The following diagrams focus on wiring related to parallel systems. For other port wiring requirements, please refer to the single-unit system. • WithGM3000Scenario 118
WithGM330Scenario WithGMK330Scenario 119
Coupling Scenario Load Monitoring and Grid-tied Inverter Power Generation Monitoring Networking Solution GMK330 meter +GMK330 meter 120
5.3 Preparing Materials 121
Do not connect loads between the inverter and the AC switch directly connected to the inverter. • Each inverter must be equipped with an AC output circuit breaker. Multiple inverters must not be connected to a single AC circuit breaker simultaneously. • • To ensure the inverter can be safely disconnected from the grid in case of an abnormality, please connect an AC circuit breaker on the AC side of the inverter. Select a suitable AC circuit breaker according to local regulations. • When the inverter is powered on, the BACK-UP AC port is live. If maintenance is required on the BACK-UP Loads, power down the inverter first, otherwise electric shock may occur. • For cables used within the same system, it is recommended that the following be consistent: conductor material, cross-sectional area, length, etc. BACK-UP AC cable for each inverter ○ ON-GRID AC cable for each inverter ○ Power cable between the inverter and the battery ○ Power cable between batteries ○ • The system only supports connecting a generator via an ATS switch in a single- unit scenario to achieve switching between grid and generator power supply. The ATS switch is connected to the grid by default. 5.3.1 Preparing Breakers WARNING 122
No. breaker Recommended Specifications 1 ON-GRID breaker When the BACK-UP port is not loaded, the Rated Current requirements are as follows: GW15K-ET: Rated Current ≥32A; Nominal Voltage ≥400V • GW20K-ET: Rated Current ≥40A; Nominal Voltage ≥400V • GW25K-ET: Rated Current ≥50A; Nominal Voltage ≥400V • GW29.9K-ET, GW30K-ET: Rated Current ≥63A; Nominal Voltage ≥400V • GW12KL-ET: Rated Current ≥50A; Nominal Voltage ≥230V • GW18KL-ET: Rated Current ≥63A; Nominal Voltage ≥230V • When the BACK-UP port is loaded, the Rated Current requirements are as follows: GW15K-ET: Rated Current ≥50A; Nominal Voltage ≥400V • • GW20K-ET, GW25K-ET, GW29.9K-ET, GW30K-ET: Rated Current ≥63A; Nominal Voltage ≥400V GW12KL-ET, GW18KL-ET: Rated Current ≥63A; Nominal Voltage ≥230V • 123 Acquisit ion Method Remark s Self- provide d If the inverter' s BACK- UP port is not used, a suitable breaker can be selected based on the AC maximu m output current.
No. breaker Recommended Specifications Nominal Voltage ≥400V, Rated Current requirements are as follows: GW15K-ET: Rated Current ≥32A; Nominal Voltage ≥400V • GW20K-ET: Rated Current ≥40A; Nominal Voltage ≥400V • 2 BACK-UP breaker GW25K-ET: Rated Current ≥50A; Nominal Voltage ≥400V • GW29.9K-ET, GW30K-ET: Rated Current ≥63A; Nominal Voltage ≥400V • GW12KL-ET: Rated Current ≥40A; Nominal Voltage ≥230V • GW18KL-ET: Rated Current ≥63A; Nominal Voltage ≥230V • 124 Acquisit ion Method Remark s Self- provide d -
No. breaker Recommended Specifications The ATS switch for the same model has the same specifications as the ON-GRID breaker. Specification requirements (recommended): GW15K-ET: Rated Current ≥32A; • 3 ATS Switch GW20K-ET: Rated Current ≥40A; • GW25K-ET: Rated Current ≥50A; • GW29.9K-ET, GW30K-ET: Rated Current ≥63A; • GW12KL-ET: Rated Current ≥40A; • GW18KL-ET: Rated Current ≥63A; • Select according to local laws and regulations 4 Battery Switch 2P DC Switch • Rated Current ≥63A • Nominal Voltage ≥1000V • 125 Acquisit ion Method Remark s During actual selectio n, you can also choose a breaker that complie s with local installati on regulati ons based on the actual operatin g current. Self- provide d Self- provide d -
No. breaker Recommended Specifications Select according to local laws and regulations Type A type • 5 RCD ON-GRID side: 300mA • BACK-UP side: 30mA • Nominal Voltage: 380V/400V • 6 Meter Switch Rated Current: 0.5A • 5.3.2 Preparing Cables No. Cable Recommended Specifications Acquisition Method Single-core outdoor copper cable • 1 Inverter Protective Grounding Cable Conductor cross-sectional area: 6mm²-10mm² • Customer- supplied 2 Customer- supplied Battery Protective Grounding Cable Lynx C Series 60kWh Commercial Single-core outdoor copper cable • Conductor cross-sectional area: 6mm² • & Industrial Battery System Battery Protective Grounding Cable BAT-S Series 15.3- 56.3kWh High Voltage Battery Single-core outdoor copper cable • Conductor cross-sectional area: 10-16mm² • 126 Acquisit ion Method Remark s Self- provide d - Self- provide d -
No. Cable Recommended Specifications Acquisition Method Battery Protective Grounding Cable BAT-C Series 61.4- 112.6kWh Commer cial & Industrial Battery System Single-core outdoor copper cable • Conductor cross-sectional area: 16-25mm² • Industry-standard outdoor PV cable • Conductor cross-sectional area: 4mm²-6mm² • 3 PV DC Cable Cable outer diameter: 5.9mm- 8.8mm • Terminal TypeI Single-core outdoor copper cable • Conductor cross-sectional area: 10mm² • Cable outer diameter: 6.5mm- 9.5mm • 4 Battery DC Cable Terminal Type Ⅱ Single-core outdoor copper cable • Conductor cross-sectional area: 10mm² • Cable outer diameter: 5mm- 8.5mm • 127 Customer- supplied Included/ Customer- supplied
No. Cable Recommended Specifications Acquisition Method 5 Battery Cluster Power Cable Lynx C Series 60kWh Commercial & Industrial Battery System Single-core outdoor copper cable • Conductor cross-sectional area: 32mm²-35mm² • Cable outer diameter: 10mm- 12mm • Battery Cluster Power Cable BAT-S Series 15.3- Single-core outdoor copper cable • Conductor cross-sectional area: 25mm² • 56.3kWh High Voltage Battery Cable outer diameter: 9mm- 11mm • Multi-core outdoor copper cable • Conductor cross-sectional area: 10mm²-16mm² • 6 AC Cable Cable outer diameter: 21mm- 26mm • Outdoor copper cable Conductor cross-sectional area: 1mm² 7 Smart Meter Power Cable 8 BatteryBMS Communication cable - Included 9 MeterRS485 Communication cable - 10 Battery Cluster Communication cable CAT 5E or higher standard Ethernet cable and RJ45 connector 128 Customer- supplied Customer- supplied Customer- supplied Customer- supplied RJ45-2PIN terminal adapter cable and standard Ethernet cable, Included Customer- supplied
No. Cable Recommended Specifications Acquisition Method 11 load controlDO Communication cable Shielded cable meeting local standards • Conductor cross-sectional area: 0.2mm²-0.3mm² • 12 Remote Shutdown Communication cable Cable outer diameter: 5mm-8mm • 13 RCR/DRED Signal Cable Customer- supplied 14 Inverter Parallel Communication Cable CAT 5E or higher standard Ethernet cable and RJ45 connector EMS Communication cable/Charging Pile Communication cable CAT 5E or higher standard Ethernet cable and RJ45 connector 15 Outdoor copper cable • 16 12V External Power Supply Conductor cross-sectional area: 0.2mm²-0.3mm² • Cable outer diameter: 5mm-8mm • Air Conditioner Power Cable Lynx C Series 60kWh Commercial & Industrial Battery System - Pre-installed 17 Air Conditioner Power Cable BAT-C Series 61.4- 112.6kWh Commer cial & Industrial Battery System - Included 129 Customer- supplied Customer- supplied Customer- supplied Customer- supplied Customer- supplied
5.3.3 Removing the Baffle Remove the baffle after the system installation is complete and before starting wiring. • After completing the system wiring, install the baffle to the enclosure. • Remove the bottom baffle Inverter wiring area baffle WARNING 130
5.4 Connecting the PE cable 131
• The protective grounding of the chassis enclosure cannot replace the protective ground wire of the AC output port. When wiring, ensure the protective ground wires at both locations are reliably connected. • To improve the corrosion resistance of the terminal, it is recommended to apply silicone gel or paint to the exterior of the grounding terminal for protection after the protective ground wire connection installation is complete. • When installing the equipment, the protective ground wire must be installed first; when removing the equipment, the protective ground wire must be removed last. 5.4.1 Inverter Grounding 5.4.2 Battery System Grounding Lynx C series 60kWh industrial and commercial battery system • Type 1 WARNING 132
Type 2 BAT-Sseries 15.3-56.3kWh high voltageBattery • BAT-Cseries 61.4-112.6kWh industrial and commercial battery system • 5.5 Connecting the PV Cable 133
Do not connect the same PV string to multiple inverters, as this may cause inverter damage. • • Before connecting the PV string to the inverter, verify the following information. Failure to do so may result in permanent inverter damage, and in severe cases, fire causing personal injury or property loss. Ensure the maximum short-circuit current and maximum input voltage for each MPPT are within the inverter's allowable range. 1. Ensure the positive terminal of the PV string is connected to the inverter's PV+, and the negative terminal to the inverter's PV-. 2. • The PV string output does not support grounding. Before connecting the PV string to the inverter, ensure the minimum insulation resistance to ground of the PV string meets the minimum insulation resistance requirement (R=Max. Input Voltage/30mA). After completing the DC cable connection, ensure the cable connections are secure and not loose. • • Use a multimeter to measure the positive and negative poles of the DC cable to ensure the positive and negative poles are correct without reverse polarity, and the voltage is within the allowable range. Within each MPPT circuit, the two photovoltaic strings should use the same model, the same number of panels, and the same tilt and azimuth angles to ensure maximum efficiency. DANGER WARNING NOTICE 134
5.6 Connecting Battery System Cables Do not connect the same battery pack to multiple inverters, otherwise it may cause inverter damage. • It is prohibited to connect loads between the inverter and the battery. • When connecting battery cables, use insulated tools to prevent accidental electric shock or causing a battery short circuit. • Ensure that the battery open-circuit voltage is within the allowable range of the inverter. • • Before connecting battery cables, confirm that the battery module and high- voltage box are powered off, and the battery cluster switch and DC power supply switch are disconnected. Between the inverter and the battery, choose whether to configure a DC switch according to local laws and regulations. • DANGER 135
• Use a multimeter to measure the positive and negative poles of the DC cable, ensuring that the polarity is correct and not reversed; and the voltage is within the allowable range. • When wiring, ensure that the battery cables match the battery terminals 'BAT+', 'BAT-', and grounding port exactly. If the cables are connected incorrectly, it may cause equipment damage. Ensure that the wire core is fully inserted into the terminal connection hole, with no exposed parts. • • Ensure that the cable connections are tight; otherwise, during equipment operation, it may cause the terminal to overheat and result in equipment damage. Do not connect the same battery pack to multiple inverters; otherwise, it may cause inverter damage. • When a 25-30kW inverter is used with the BAT series 61.4kWh commercial & industrial battery system, connecting two BAT ports is required to achieve full load operation. Battery System Wiring Diagram Lynx C Series 60kWh Commercial & Industrial Battery System • WARNING NOTICE 136
BAT-S Series 15.3-56.3kWh High Voltage Battery • 137
BAT-C Series 61.4-112.6kWh Commercial & Industrial Battery System • 138
5.6.1 Paired with Lynx C Series 60kWh Commercial & Industrial Battery System 5.6.1.1 Battery Wire Feedthrough Introduction 139
No. Description No. Description 1 Battery power cable pass- through hole 3 Communication cable pass- through hole 5 Reserved pass-through hole - - 5.6.1.2 Connecting the Power Cable between the Inverter and Battery 2 Emergency stop button control cable pass-through hole 4 Air conditioning cable pass-through hole 140
• Use a multimeter to measure the positive and negative poles of the DC cable to ensure correct polarity, with no reverse connection; and that the voltage is within the allowable range. • During wiring, ensure the battery cables match the "BAT+", "BAT-", and grounding ports on the battery terminals exactly. Incorrect cable connection will cause equipment damage. Ensure the wire core is fully inserted into the terminal connection hole with no exposed part. • Ensure the cable connections are tight. Otherwise, during equipment operation, the terminal may overheat, causing equipment damage. • Do not connect the same battery bank to multiple inverters, as this may cause inverter damage. • • The battery system comes with power cables for connecting to the inverter in the box. If the inverter accessories include type one terminals, cut off the terminals on the power cable from the battery accessories that connect to the inverter, and use the battery connectors provided with the inverter to remake the power cable. ○ If the inverter accessories include type two terminals, you can directly use the power cable from the battery accessories. ○ If there are no terminals on the power cable from the battery accessories for connecting to the inverter, use the connectors from the inverter accessories to make the power cable. ○ Power cables for parallel clustering between battery systems need to be prepared by yourself. • Please connect the battery system to the BAT1 port of the inverter. • WARNING NOTICE 141
Inverter End Cable Fabrication Method 142
Battery System Cluster Power Cable Fabrication Method 143
5.6.1.3 Connecting the Battery Communication Cable Do not omit the battery system terminal resistor, otherwise communication between battery systems will fail. • The battery system is shipped with a BMS battery communication cable. It is recommended to use the provided cable. If the supplied communication cable does not meet the requirements, please prepare your own shielded network cable and shielded RJ45 connector. Please connect the battery system to the BMS1 communication port of the inverter; otherwise, normal communication may not be possible. • • The emergency stop switch communication cable is pre-installed on the cabinet. If the supplied communication cable does not meet the requirements, please prepare your own communication cable. • For parallel communication cables between battery systems, please prepare shielded network cables and shielded RJ45 connectors that meet the EIA/TIA- 568B standard. • PIN4 and PIN5 are only for connecting to the inverter communication. There is no need to crimp PIN4 and PIN5 for the parallel communication cables between battery systems. When connecting battery systems in parallel, connect the inverter remote shutdown port to the main battery system. • WARNING NOTICE 144
Explanation of BMS Communication Connection between Inverter and Battery: Device port Definition Description 4:CAN_H 5:CAN_L CAN communication between the Inverter and the Battery BMS1 Inverter 7:GND Connected to the battery system to control the emergency shutdown of the battery Remote Shutdown 8:Remote Shutdown Battery 7:CAN_H 8:CAN_L Parallel cluster CAN communication between batteries Slave1 Master 1:RS485_A1 2:RS485_B1 Reserved for communication with the Inverter 145
Device port Definition Description 4:CAN_H 5:CAN_L Communication with the Inverter 7:CAN_H 8:CAN_L Parallel cluster CAN communication between batteries 7:CAN_H 8:CAN_L Parallel cluster CAN communication between batteries Slave2 Connected to the Inverter to control the emergency shutdown of the battery Emergency Stop Switch 1: NC 2: COM 5.6.1.4 Connecting Internal Power Busbars in Battery Systems NOTICE If the aluminum busbars in the battery system have been installed at the factory, please use tools to recheck the torque. Scenario with partially installed inter-cell aluminum busbars before shipment: Scenario with uninstalled inter-cell aluminum busbars before shipment: 146
5.6.1.5 Connecting Battery System AC Power Cables • The air conditioner power cord is pre-installed on the cabinet. If the provided power cord does not meet the requirements, please prepare an extension cable yourself. It is recommended to connect the air conditioner power cord to the power distribution cabinet for power supply. • • If the air conditioner needs to be used for emergency power supply, the air conditioner power cord can be connected to the inverter BACK UP side for power. • To ensure that the air conditioner can be safely disconnected from the power distribution cabinet in case of abnormalities, please install an AC switch between the air conditioner and the power distribution cabinet. The AC switch specification should be no less than 16A. To ensure heat dissipation performance, do not arbitrarily modify the default temperature parameter settings of the air conditioner. • NOTICE 147
5.6.1.6 Connecting the Battery System Air Conditioning Drain Pipe 5.6.1.7 Open the Fire Switch 148
The "open" (turn on) and "close" (turn off) functions of the firefighting equipment can only be activated during professional maintenance or replacement of the temperature-sensitive activation component. Scenario for operating the fire equipment switch: If a 'Do Not Touch' tag is present, no action is required. • • If no tag is present, please refer to the following steps to open the fire switch. Use a 14mm wrench to rotate the screw behind the pressure gauge counterclockwise approximately 1.5 turns until it is fully tightened, and the fire system will be successfully opened. NOTICE 149
5.6.1.8 Install Baffle After the cables are connected, install the bottom baffle. 150
5.6.2 Paired with BAT-S Series 15.3-56.3kWh High-Voltage Battery Inverter GW12KL -ET GW18KL -ET GW15K -ET GW20 K-ET GW25 K-ET GW29.9K -ET GW30K -ET Number of BAT Ports 1 2 1 1 2 2 2 Minimum PACKs Required for BAT-S Series Battery (Operational) 3PACK 3PACK 5PACK 5PACK 5PACK 5PACK 5PACK Minimum PACKs Required for BAT-S Series Battery (Full Load) 5PACK 4PACK 6PACK 8PACK 5PACK 6PACK 6PACK 5.6.2.1 Connecting the Power Cable between the Inverter and Battery NOTICE The BAT-S series 15.3-56.3kWh high-voltage battery supports up to 6 battery cabinets in parallel. Wiring Overview The 15-20kW inverter has only one BAT port; connect one when used with a battery. • 151
The 25-30kW inverter has two BAT ports; both need to be connected when used with a battery. • 152
Inverter-end Cable Manufacturing Method Battery-end Cable Manufacturing Method (Including Parallel Cluster Wiring) 153
5.6.2.2 Connecting Power Cables Between Batteries 5.6.2.3 Connecting Communication Cables 154
The battery system includes a communication cable with the package. Please use the included communication cable. Instructions for BMS Communication Connection between Inverter and Battery: port Definition Description 1: RS485_A1 2: RS485_B1 Communicate with inverter (reserved). COM1, COM2 4: CAN_H 5: CAN_L Inverter to Battery Communication Wiring NOTICE Communicate with inverter or parallel cluster communication. 155
Communication Wiring between Battery PACKs When connecting communication cables between battery PACKs, the COM OUT port of the bottommost PACK should not be connected, and there is no need to connect a terminal resistor! 5.6.3 BAT-C Series 61.4-112.6kWh Commercial & Industrial Battery System Inverter GW15K- ET Number of BAT Ports 1 1 2 2 2 NOTICE GW20K- ET GW25K- ET GW29.9K- ET GW30K -ET 156
Inverter GW15K- ET GW20K- ET GW25K- ET GW29.9K- ET GW30K -ET With BAT 61.4kWh Battery System Connec t to 2 BAT ports Connect to 1 BAT port Connect to 1 BAT port Connect to 2 BAT ports Connect to 2 BAT ports Wiring Method Can it be fully loaded? Yes No Yes Yes Yes Connec t to 2 BAT ports Connect to 1 BAT port Connect to 1 BAT port Connect to 2 BAT ports Connect to 2 BAT ports Wiring Method With BAT 92.1kWh Battery System Can it be fully loaded? Yes Yes Yes Yes Yes Connec t to 2 BAT ports Connect to 1 BAT port Connect to 1 BAT port Connect to 1 BAT port Connect to 2 BAT ports Wiring Method With BAT 102.4kWh Battery System Can it be fully loaded? Yes Yes Yes Yes Yes Connec t to 2 BAT ports Connect to 1 BAT port Connect to 1 BAT port Connect to 1 BAT port Connect to 2 BAT ports Wiring Method With BAT 112.6kWh Battery System Can it be fully loaded? Yes Yes Yes Yes Yes 5.6.3.1 Battery Wiring Port and System Wiring Introduction WARNING All cut wire holes must be sealed with fireproof putty. 157
5.6.3.3 Connecting the Battery Communication Cable The battery system is shipped with a communication cable. Please use the communication cable provided in the package. • • The external communication port of the battery system is pre-installed with a terminal resistor upon factory shipment. If you need to connect a communication cable, please remove the terminal resistor. Retain the terminal resistor on any port not connected to a communication cable. NOTICE 158
Instructions for BMS Communication Connection Between Inverter and Battery: Port Definition Description 1-3,6-8 - - 4 CAN_H 5 CAN_L Communicate with inverter 159
5.6.3.4 Connecting Battery Air Conditioning Cables Wiring Steps: Step 1: Make the air conditioning cable. Step 2: Connect the cable to the air conditioning switch on the battery. Step 3: Connect the cable directly to the distribution board or to the inverter's BACKUP port via the distribution board. Please ensure that the voltage of the air conditioner power cord is 220V±15%, and the rated current is 12A. 5.6.3.5 Install Base Plate and Release Emergency Stop Switch After wiring is complete, please reinstall the battery bottom cover along the original path, and rotate right to release the emergency stop switch. NOTICE 160
5.7 Connecting the AC Cable • The inverter internally integrates a Residual Current Monitoring Unit (RCMU) to prevent residual current from exceeding the specified value. When the inverter detects a leakage current greater than the allowable value, it will quickly disconnect from the grid or generator. • During wiring, ensure that the AC wires match the “L1”, “L2”, “L3”, “N”, and “PE” ports of the AC terminals exactly. If the cables are connected incorrectly, it may cause equipment damage. Ensure that the wire cores are fully inserted into the terminal connection holes without exposure. • Ensure that the insulation plate at the AC terminals is tightly secured without looseness. • • Ensure that the cable connections are tight; otherwise, during equipment operation, it may cause the terminal blocks to overheat and result in equipment damage. Type one: WARNING 161
Type two: 5.8 Connecting the Meter Cable 162
• The meter shipped with the unit is for use with a single inverter only. Do not connect one meter to multiple inverters. If you have multiple inverters, please consult the manufacturer to purchase additional meters separately. Ensure the CT connection direction and phase sequence are correct; otherwise, it may lead to incorrect monitoring data. • Ensure all cable connections are correct, secure, and not loose. Improper wiring may cause poor contact or damage the meter. • • In areas with lightning risk, if the meter cable length exceeds 10m and the cable is not routed using a grounded metal conduit, it is recommended to install an external lightning protection device. GM3000 Meter Wiring The outer diameter of the AC power line must be smaller than the aperture of the CT to ensure the AC power line can pass through the CT. • To ensure the current detection accuracy of the CT, the recommended length of the CT cable does not exceed 30m. • Do not use network cable as the CT cable, as excessive current may cause damage to the meter. • • The size and appearance of the CT provided by the equipment manufacturer may vary slightly depending on the model, but the installation and wiring methods are the same. NOTICE NOTICE 163
Wiring Steps GM330&GMK330 Meter Wiring 164
©l) i IN} 08000008 ' [3 NE == = L<100m 7.RS485-B1 4 Sğeesro) 8.RS485-A1 = şe 8 İN Ly} a (a) BL EO. METER | | ET3010ELCOO17 GMK330 7.RS485-B1 ————— — B.RS485-A1] _ = 5363 Öneş Mei ET3010ELCO0026 Wiring Steps 165
Install CT (Type 1) Install CT (Type 2) 166
5.9 Connecting the Inverter Communication Cable • To ensure the meter and CT can function properly, please ensure the following: Ensure the CT is connected to the matching phase line: CT1 to L1, CT2 to L2, CT3 to L3. ○ Connect according to the direction indicated on the CT; otherwise, it may cause a CT reverse fault. ○ When replacing or maintaining the CT later, use the "Meter/CT - Auxiliary Detection" function in the SolarGo APP to allow the Inverter to readapt to the CT sampling current direction. ○ To use the DRED, RCR, or remote shutdown function, please enable this function in the SolarGo APP after wiring is completed. • • If the Inverter is not connected to a DRED device or remote shutdown device, do not enable this function in the SolarGo APP; otherwise, the Inverter will not be able to operate in grid-connected mode. In a parallel system, to implement DRED or RCR functions, only connect the DRED/RCR communication cable to the master Inverter. • The Inverter's DO signal communication port can connect to dry contact signals with specifications: Max≤24Vdc, 1A. • • The Inverter supports connecting to a mobile phone or WEB interface via 4G, Bluetooth, WiFi, or LAN communication methods to set device parameters, view device operation information and error messages, and stay informed of the system status in a timely manner. In a single-unit system, the installation of a WiFi/LAN Kit-20 or 4G Kit-CN-G20 • NOTICE 167
smart communication stick is supported. In a parallel system, both the master and slave Inverters require the installation of a WiFi/LAN Kit-20 smart communication stick for networking. • • When using the 4G Kit-CN-G20: If parallel unit networking is required, please contact GoodWe to purchase the WiFi/LAN Kit-20. ○ In China, a standard Micro-SIM card is provided, with China Mobile as the carrier. Please confirm the device is installed in an area with carrier signal coverage. If local China Mobile signal is not covered, please contact the carrier to optimize the signal. ○ Supports connection to third-party monitoring platforms via the MQTT communication protocol. ○ The 4G Kit-CN-G20 is an LTE single-antenna device suitable for application scenarios with lower requirements for data transmission rates. • • To use dual meters for grid-connected unit generation monitoring and load consumption monitoring, please use an RJ45 splitter for connection. Prepare the RJ45 splitter yourself or contact GoodWe to purchase one. To maintain the Inverter's waterproof rating, do not remove the waterproof plugs from unused communication ports on the Inverter. • The Inverter's communication functions are optional; please select according to the actual usage scenario. • Type One NOTICE 168
Type Two 169 Type Two Slave inverter 1 Slave inverter n İrt EV Charger CAT 5E and higer categories 2 [LRS485_A2) CAT 5ERLAE .RS485 B2 Master inverter 12V Power supply ov ikea | Smart Meter/SREER METER Remote Shutdown G t / NS Protection -B.d0-_]- 5 -Seperenor DERM NS Protection RJ45 5 4e88 Only for single RJ45 Splitter ||7.RS485_B1 inverter/ (LERİN Adapter 8.RS485 A1 Battery (CAN2) 4.CAN H FB 3th (CAN2) 5.CAN_L Battery (CAN1) 4.CAN H FB te (CANI) 5.CAN L When S1, S2, and W3 are disconnected at the same time, the nominal output power is 100%. RCR&ENWG 14a — S1,S2,W3 IETF, Bie İMLHYEEİN1000 (11 REF_1) —w3>0% —K4—>0% —K 330% — s2 330% —s1—60% —K2—60% —W4-EnWG 14a —K1—100% ET3010ELCO012 169
Only for single inverter/仅单机 EMS 充电桩 EV Charger 1.RS485-A 2.RS485-B 5.CAN-L 6.CAN-H Slave inverter 1 从逆变器1 Slave inverter n 从逆变器n n≤3 PAR OFF ON 1.LOAD-NO 3.LOAD-COM 4.DI-2 5.DI-1 BMS1 BMS2 Generator 发电机 Only for single inverter/仅单机 Battery (CAN2) 电池(CAN2) 4.CAN-H 5.CAN-L Battery (CAN1) 电池(CAN1) 4.CAN-H 5.CAN-L DRM 6 1/5 5 2/6 4 3/7 3 4/8 2 RG/0 1 CL/0 10R S5a S5 S1 S6 S2 S7 S3 S8 S4 15K RCR (1 CL/0) 2 RG/0 3 4/8 4 3/7 5 2/6 6 1/5 K 4→0% K 3→30% K 2→60% K 1→100% RCR&EnWG 14a (1 CL/0) 2 RG/0 3 4/8 4 3/7 5 2/6 6 1/5 W3→0% S2→30% S1→60% W4→EnWG 14a ET3010ELC0033
Silkscreen Function Description DO / LOAD load control(SG Ready) GND 12V RSD 12V Power Supply The inverter provides a 12V power supply port, supporting devices up to 5W. This port has short-circuit Protection Function. Remote Shutdown/NS Protection DI • Supports connection of dry contact signals to achieve functions like load control. The DO contact capacity is 24V DC@1A, NO/COM normally open contact. • Supports SG Ready heat pump connection, controlling the heat pump via dry contact signals. • Supported operating modes: Operating mode 2 (Signal: 0:0 ): Energy- saving Mode, in this mode, the heat pump operates in energy-saving mode. ○ Operating mode 3 (Signal: 0:1 ): Activation suggestion, in this mode, the heat pump increases hot water reserve to store heat while maintaining current operation. ○ Provides a signal control port for Remote Shutdown of the device or to implement NS Protection Function. Remote Shutdown function: Can control the device to stop working when an unexpected event occurs. • The remote shutdown device must be a normally closed type switch. • • When the inverter uses the RCR or DRED function, ensure the remote shutdown device is connected, or the remote shutdown port is short-circuited. 171
Silkscreen Function Description Generator Start/Stop Control Port DO2 / GEN RCR, DRED, or EnWG 14a Function Connection Port DRM&RCR / EMS/PAR/PA R- 1/PAR1&EM S • EMS Communication or Charging Pile Communication Port • Parallel Communication Port Only supports connection of generator control signals in single inverter scenarios. • • The generator control mode is off by default, with the dry contact signal open; after enabling the control mode, the dry contact signal becomes shorted. • RCR (Ripple Control Receiver): Provides an RCR signal control port to meet grid dispatch requirements in regions like Germany. • DRED (Demand Response Enabling Device): Provides a DRED signal control port to meet DERD certification requirements in regions like Australia. • EnWG (Energy Industry Act) 14a: All controllable loads must accept emergency dimming from the grid. Grid operators can temporarily reduce the maximum grid purchase power of controllable loads to 4.2kW. • CAN and BUS port: Parallel communication port. CAN communication is used to connect to other inverters in parallel networking; the BUS bus is used to control the on-grid/off- grid status of each inverter in the parallel system. • RS485 port: Used to connect third-party EMS devices and charging piles. Connecting third-party EMS devices and charging piles is not supported in parallel scenarios. 172
Silkscreen Function Description EMS/PAR / PAR1&EMS / PAR2&EMS Parallel Communication Port S1 Parallel DIP Switch Inverter parallel DIP switch, factory default is set to the ON position. In multi-unit parallel scenarios, the parallel DIP switches of the first and last inverters must be set to the ON position, and the others to the 1 position. METER Smart Meter Connection Port Battery Communication Connection Port BMS1 / BMS2 Method for Connecting the Communication Cable • CAN and BUS port: Parallel communication port. CAN communication is used to connect to other inverters in parallel networking; the BUS bus is used to control the on-grid/off- grid status of each inverter in the parallel system. Connects to a smart meter to achieve output power control, load monitoring, and other functions. Connects to batteries using CAN communication. GW12KL-ET, GW15K-ET, GW20K-ET: 1 GW18KL-ET, GW25K-ET, GW29.9K-ET, GW30K- ET: 2 173
5.10 Connecting the Smart Communication Stick 174
• The inverter supports connection via Bluetooth, 4G, WiFi, LAN smart dongle to a mobile phone or WEB interface for setting device parameters, viewing device operation information and error messages, and staying updated on system status. When multiple inverters are networked in a system, the master inverter requires the installation of an Ezlink3000 smart dongle for networking. • For an energy storage system with a single inverter, you can use a WiFi-Kit, WiFi/LAN Kit-20, or 4G smart dongle. • When using the WiFi communication method to connect the inverter to a router, you can install a WiFi-Kit, WiFi/LAN Kit-20, or Ezlink3000 smart dongle. • When using the LAN communication method to connect the inverter to a router, you can install a WiFi/LAN Kit-20 or Ezlink3000 smart dongle. • • When using the 4G communication method to upload energy storage system operation information to the monitoring platform, you can install an LS4G Kit- CN, 4G Kit-CN, 4G Kit-CN-G20, or 4G Kit-CN-G21 smart dongle. When using LS4G Kit-CN or 4G Kit-CN, you need to use the smart dongle shipped with the inverter to configure the parameters of the energy storage system. After configuration is complete, replace it with the LS4G Kit-CN or 4G Kit-CN for data transmission. When using 4G Kit-CN-G20 or 4G Kit-CN-G21, please use the Bluetooth signal emitted by the module for local device configuration. The 4G module is an LTE single-antenna device, suitable for application scenarios with low data transmission rate requirements. • • The built-in SIM card in the 4G module is a mobile communication card. Please confirm whether the device is installed in an area covered by China Mobile's 4G signal. • After installing the 4G Kit-CN-G20 or 4G Kit-CN-G21 communication dongle, please contact the after-sales service center to bind the inverter with the communication dongle. After binding, if you need to install the communication dongle on another inverter, please contact the after-sales service center to unbind it first. To ensure 4G signal communication quality, do not install the device indoors or in areas with metal interference signals. • NOTICE 175
ET3010ELC0034 ETSO010ELCO034 176
6 System Commissioning 6.1 Check Before Power ON No. Check Item 1 The equipment is installed securely, the installation location facilitates operation and maintenance, the installation space allows for ventilation and heat dissipation, and the installation environment is clean and tidy. 2 PE cable, DC cable, AC cable, Communication cable, and terminal resistor connections are correct and secure. 3 Cable bundling meets wiring requirements, is reasonably distributed, and shows no damage. 4 For unused cable entry holes and ports, ensure they are reliably connected using the terminals provided with the accessories and have been sealed. 5 Ensure used cable entry holes have been sealed. 6 The voltage and frequency at the inverter grid connection point meet the grid connection requirements. 6.2 Power ON • When multiple inverters are connected in parallel, ensure that the AC power is turned on for all slave inverters within one minute after the AC power is turned on for the master inverter. • When multiple battery systems are connected in a cluster, ensure that the QF2 switches for all battery systems are closed within five minutes. When multiple battery systems are connected in a cluster, before closing QF1, ensure that the SolarGo App correctly displays the number of battery systems in the cluster; otherwise, it may cause damage to the battery system. WARNING 177
When there is no PV power generation in the photovoltaic system and the grid is abnormal, if the inverter cannot operate normally, the battery black start function can be used to force the battery to discharge and start the inverter. The inverter can then enter off-grid mode, with the battery supplying power to the loads. BAT series 92.1-112.6kWh commercial & industrial battery system black start procedure, refer to the power on/off steps. • The black start procedure for other batteries is the same as the power-on steps. • BAT series 92.1-112.6kWh commercial & industrial battery system: Before performing the power-on operation, ensure the battery's emergency stop switch is in the released state. Release procedure: Rotate the emergency stop switch to the right. NOTICE 178
⑤ : Optional based on local laws and regulations. 6.3 Indicators 6.3.1 Inverter Indicators Indicator Status Description The inverter is powered on and in standby mode. The inverter is starting up and in self-test mode. The inverter is operating normally in grid- connected power generation or off-grid mode. BACK-UP output overload. 179
Indicator Status Description 6.3.2 Battery Indicators Lynx C Series 60kWh Commercial & Industrial Battery System • indicato r Status Description Two green blinks: Device in standby Run System fault. The inverter is powered off. Grid abnormal, inverter BACK-UP port power supply normal. Grid normal, inverter BACK-UP port power supply normal. No power supply at the BACK-UP port. Inverter monitoring module is resetting. No connection established between the inverter and the communication terminal. Communication failure between the communication terminal and the cloud server. Inverter monitoring is normal. Inverter monitoring module is not started. Steady green: Device operating normally Single green blink: Battery operating normally, not communicating with inverter Green off, steady yellow: Device alarm Green off, Steady red: Device fault Green, yellow, and red all off: Device not powered on 180
indicato r Status Description Warning Off: No device alarm Fault Off: No device fault BAT-S Series 15.3-56.3kWh High Voltage Battery • Indicator Status Description Single green flash: Battery operating normally, not communicating with the inverter RUN Single red flash: System undervoltage level 3~4 FAULT BAT-C Series 61.4-112.6kWh Commercial & Industrial Battery System • Steady on: Device alarm Steady on: Device fault Solid green light: Device operating normally Two green flashes: Device in standby Solid light: Device fault Two red flashes: SN abnormality 181
Indicato r Status Description Double flash of green light: Device in standby Run Warning Off: No device warning Off: No device fault Fault 6.3.3 Smart Meter Indicator GM330&GMK330 Type Status Description Power Light Off The meter is powered off Off Reserved Communication Light Steady green light: Device operating normally Single flash of green light: Battery operating normally, not communicating with inverter Green light off, steady yellow light: Device warning Green light off, steady red: Device fault Green, yellow, and red lights all off: Device not powered on Steady light: Device warning Steady light: Device fault Single red flash: Sleep (under-voltage) Constantly lit The meter is powered on, no RS485 communication Flashing The meter is powered on, RS485 communication is normal Flashing Press the Reset button for ≥5s, Power Light and Buy/Sell Power Light flash: Meter reset Constantly lit buy power from the grid Flashing Selling power to the grid 182
Type Status Description Buy/Sell Power Light Off Not buying or selling power Reserved GM3000 Type Status Description Constantly lit The meter is powered on Power Light Off The meter is powered off Constantly lit buy power from the grid Buy/Sell Light Flashing Selling power to the grid Flashing Normal communication Communication Light Flashes 5 times continuously Off No communication from the meter 6.3.4 Smart Dongle Indicator Wi-Fi Kit • Indicato r Color State Description On Wi-Fi Kit is powered on. Green Press the Reset button for <3s: Meter reset • • Press the Reset button for 5s: Meter parameters restored to factory settings • Press the Reset button for >10s: Meter parameters restored to factory settings, and energy data cleared 183
Power indicato r Off Wi-Fi Kit is not powered on or is rebooting. On WiFi AP hotspot is connected. Commu nication indicato r Blue Off WiFi/LAN Kit-20 • • After double-clicking the Reload button to turn on Bluetooth, the communication indicator will switch to a single-flash state. Please connect to the SolarGo APP within 5 minutes, otherwise Bluetooth will automatically turn off. The single-flash state of the communication indicator only occurs after double- clicking the Reload button to turn on Bluetooth. • Indicat or Status Description Steady on: The Smart Communication Stick is powered on. Power Light Commu nication Light Wi-Fi Kit communication is abnormal. • Wi-Fi Kit is rebooting. • NOTICE Off: The Smart Communication Stick is not powered on. Steady on: Communication is normal in WiFi mode or LAN mode. Single flash: The Smart Communication Stick's Bluetooth signal is on, waiting to connect to the SolarGo app. Double flash: The Smart Communication Stick has not connected to the router. 184
Indicat or Status Description Quadruple flash: The Smart Communication Stick communicates normally with the router but has not connected to the server. Sextuple flash: The Smart Communication Stick is identifying connected devices. Off: The Smart Communication Stick is undergoing a software reset or is not powered on. Indicator Color Status Description Steady on 100Mbps wired network connection is normal. The network cable is not connected. • Green LAN port communica tion light 100Mbps wired network connection is abnormal. • Off 10Mbps wired network connection is normal. • 10/100Mbps wired network connection is normal, with no communication data being sent or received. Flashin g Communication data is being sent or received. Steady on Yellow Off The network cable is not connected. Button Description Hold for 0.5 to 3 seconds, the smart communication stick will reset. Hold for 6 to 20 seconds, the smart communication stick will restore factory settings. Reload Quick double-click to enable Bluetooth signal (only lasts for 5 minutes). 4G Kit-CN-G20 & 4G Kit-CN-G21 • Indicator Status Description Steady on: The smart communication stick is powered on. 185
Indicator Status Description Off: The smart communication stick is not powered on. Steady on: The smart communication stick is connected to the server, communication is normal. Double flash: The smart communication stick is not connected to the communication base station. Quadruple flash: The smart communication stick is connected to the communication base station but not connected to the server. Sextuple flash: Communication between the smart communication stick and the inverter is disconnected. Off: The smart communication stick is undergoing a software reset or is not powered on. Button Description Hold for 0.5~3 seconds, the Smart Communication Bar will restart. RELOAD Hold for 6~20 seconds, the Smart Communication Bar will restore factory settings. LS4G Kit-CN, 4G Kit-CN • indicator Color Status Description On Module is secured and powered on Power Light Green Off Module is not secured or not powered on Blue slow blinking (0.2s on, 1.8s off) Inverter communication light 2 blinks: Dialing, searching for network Communi • cation Light • Inverter communication light 4 blinks: Connection to cloud failed due to no data flow 186
slow blinking (1.8s on, 0.2s off) Inverter communication light 2 blinks: Dialing successful • fast blinking (0.125s on, 0.125s off) Inverter is communicating with the cloud via the module 0.2s on, 8s off SIM card not installed or poor SIM card contact Ezlink3000 • indicator/Sil Color Status Description kscreen Power light Blue Green Communicatio n light RELOAD - - Short press for 1-3 seconds to restart the 6.4 Close Cabinet Door • Inverter communication light steady on: Cloud connection successful • Inverter communication light 4 blinks: Connection to cloud failed due to no data flow Flashing: The communication stick is operating normally. Off: The communication stick is powered off. Steady on: The communication stick is connected to the server. Double flash: The communication stick is not connected to the router. Quadruple flash: The communication stick is connected to the router but not to the server. communication stick. Long press for 6-10 seconds to restore factory settings. Quick double-click to enable Bluetooth signal (only lasts for 5 minutes). 187
Lynx C Series 60kWh Commercial & Industrial Battery System • BAT-CSeries 61.4-112.6kWh Commercial & Industrial Battery System • 188
Front door Back door BAT10INT0007
7 System Debugging and Power Station Monitoring 7.1 Device debugging and power plant monitoring via SEMS+ App SEMS+ App is a software for remote power plant monitoring or local device debugging. It supports installers or owners: Remotely monitor the operation of the power plant and set the operation parameters of the power plant and devices. • Locally connect to devices, view device operation status, and set device parameters. • Download and Install SEMS+ App Mobile phone requirements: Mobile operating system requirements: Android 7.0 and above, iOS 15.1 and above. • Mobile phone supports a web browser and connects to the Internet. • Mobile phone supports WLAN/Bluetooth functionality. • Download methods: Method 1: Search for SEMS+ in Google Play, App Store, Huawei, Honor, Xiaomi, OPPO, vivo app stores to download and install. Method 2: Scan the QR code below to download and install. 190
For detailed functions, please refer to the SEMS+ App User Manual. The user manual can be obtained from the official website or by scanning the QR code below. 7.2 Device Debugging and Power Plant Monitoring via SEMS+ WEB SEMS+ WEB is a monitoring platform that communicates via WiFi or LAN. The following are common functions of SEMS+ WEB: Manage organization or user information, etc. 1. Add and monitor power plant information, etc. 2. Maintain devices. 3. For detailed functions, please refer to the SEMS+ WEB User Manual. 191
SEMS+ WEB User Manual 192
8 Maintenance 8.1 Power OFF the System • When performing operation or maintenance on equipment within the system, please power down the system. Operating equipment while energized may cause equipment damage or risk of electric shock. • After the equipment is powered off, internal components require a certain amount of time to discharge. Please wait according to the label's time requirement until the equipment is completely discharged. Restarting the battery should be performed using the air switch power-on method. • When shutting down the battery system, strictly adhere to the battery system power-down requirements to prevent damage to the battery system. • When there are multiple batteries in the system, powering down any one battery will power down all batteries. • The circuit breakers between the inverter and the battery, and between battery systems, must be installed in accordance with local laws and regulations. • • To ensure effective protection of the battery system, keep the cover plate of the battery system switch in a closed state. The protective cover should automatically close after being opened. If the battery system switch will not be used for an extended period, secure it with screws. Power-Off Procedure DANGER NOTICE 193
❺: Optional based on local laws and regulations. 8.2 Removing the Equipment Ensure the device is powered off. • Wear personal protective equipment when operating the device. • Use proper disassembly tools when removing wiring terminals to avoid damaging the terminals or the device. • Unless otherwise specified, the device disassembly sequence is the reverse of the installation sequence, which will not be reiterated in this document. • DANGER 194
Power down the system. 1. Use labels to mark the cable types for the cables connected in the system. 2. Disconnect the connection cables of the Inverter, Battery, and smart meter in the system, such as: DC cable, AC cable, Communication cable, PE cable. 3. Remove devices such as the smart communication stick, Inverter, Battery, smart meter, etc. 4. Store the equipment properly. If it needs to be put into use later, ensure that the storage conditions meet the requirements. 5. 8.3 Disposing of the Equipment When the equipment can no longer be used and needs to be disposed of, please dispose of it according to the electrical waste disposal requirements of the regulations in the country/region where the equipment is located. The equipment must not be disposed of as general household waste. 8.4 Routine Maintenance • If any issues that may affect the battery or energy storage inverter system are found, contact after-sales personnel. Disassembly by unauthorized personnel is prohibited. • If exposed internal copper wires are found in the conductive cables, do not touch them. High voltage danger. Contact after-sales personnel. Disassembly by unauthorized personnel is prohibited. • In case of other emergencies, contact after-sales personnel immediately. Operate only under the guidance of after-sales personnel, or wait for on-site operation by after-sales personnel. WARNING 195
Maintenan ce Item Maintenance Method Maintenanc e Cycle Check for foreign objects or dust on the heat sink, fan, and air inlet/outlet. Check if the installation space meets requirements, and if there is any debris accumulation around the equipment. System Cleaning Check if the equipment installation is secure and if fastening screws are loose. Check for any damage or deformation on the equipment exterior. System Installation Check for loose electrical connections, damaged cable sheaths, or exposed copper wires. Electrical Connection s Check if the sealing of the equipment's cable entry holes meets requirements. Re-seal if gaps are too large or unblocked. Sealing If the battery has been unused or not fully charged for an extended period, regular charging is recommended. Battery Maintenanc e 8.5 fault The fault content in the manual is updated irregularly, and there may be slight variations across different models. Please refer to the real-time display on your device for specific details. Maintenance Purpose Once every 6 months Prevent cooling failures. Once every 6 months to once a year Confirm equipment installation stability. Once every 6 months to once a year Confirm reliability of electrical connections. Confirm machine sealing and intact waterproof performance. Once a year Once every 15 days Protect battery service life. NOTICE 196
8.5.1 Viewing Fault/Alarms Information All detailed information on faults and alarms in the energy storage system is displayed in the [SEMS+ App] and [SEMS+ WEB]. If your product experiences an abnormality and you do not see related fault information in [SEMS+ App] or [SEMS+ WEB], please contact the after-sales service center. SEMS+ App • Open the SEMS+ App and log in using any account. 1. Go to [power station] > [Alarms] to view all power station fault information. 2. Click on a specific fault name to view details such as the time of occurrence, possible causes, and solutions. 3. SEMS+ WEB • Open SEMS+ WEB and log in using any account. 1. On the power station details interface, click [Alarms] to view all alarm information for the current power station. 2. 8.5.2 Fault Information and Troubleshooting Please perform troubleshooting according to the following methods. If the troubleshooting methods cannot help you, please contact the after-sales service center. When contacting the after-sales service center, please collect the following information to facilitate a quick resolution. Product information, such as: serial number, software version, device installation time, fault occurrence time, fault occurrence frequency, etc. 1. 2. Device installation environment, such as: weather conditions, whether components are obstructed or shaded, etc. It is recommended to provide photos, videos, and other files of the installation environment to assist in problem analysis. Grid conditions. 3. 8.5.2.1 System Malfunction If the system experiences an unlisted issue, or if following the instructions does not prevent the problem or abnormality, immediately stop operating the system and 197
contact your dealer at once. No. fault Solution Unable to search for the Smart Comm Stick wireless signal 1 Unable to connect to the Smart Comm Stick wireless signal 2 3 Unable to find the router SSID After all configuration is complete, the Smart Comm Stick fails to connect to the router 4 Ensure no other devices are connected to the Smart Comm Stick's wireless signal. 1. Ensure the App is upgraded to the latest version. 2. Ensure the Smart Comm Stick is powered normally, with the blue signal light blinking or steadily on. 3. Ensure the smart device is within the communication range of the Smart Comm Stick. 4. Refresh the device list in the App. 5. Restart the inverter. 6. Ensure no other devices are connected to the Smart Comm Stick's wireless signal. 1. 2. Restart the inverter or the Comm Stick, then try connecting to the Smart Comm Stick wireless signal again. Ensure Bluetooth encryption pairing is successful. 3. Place the router closer to the Smart Comm Stick, or add a WiFi repeater to enhance the WiFi signal. 1. Reduce the number of devices connected to the router. 2. Restart the inverter. 1. 2. Check if the network name, encryption method, and password in the WiFi configuration match those of the router. Restart the router. 3. Place the router closer to the Smart Comm Stick, or add a WiFi repeater to enhance the WiFi signal. 4. 198
No. fault Solution After all configuration is complete, the Smart Comm Stick fails to connect to the server 5 Restart the router and the inverter. 8.5.2.2 Inverter Fault 8.5.2.2.1 Troubleshooting (Fault Codes F01-F40) Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions 1. Grid power outage. 2. AC line or AC switch is disconnected. 1. The alarm will disappear automatically after grid power supply is restored. 2. Check if the AC line or AC switch is disconnected. F01 Grid Power Outage 199
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Grid voltage is higher than the allowable range, or the duration of high voltage exceeds the HVRT set value. Grid Overvoltage Protection F02 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid voltage is within the allowable range. If not, contact the local power operator. If yes, also modify the grid overvoltage protection point after obtaining consent from the local power operator. 3. If normal operation cannot be restored for a long time, check if the AC side circuit breaker and output cables are properly connected. 200
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Grid voltage is lower than the allowable range, or the duration of low voltage exceeds the LVRT set value. Grid Undervoltag e Protection F03 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid voltage is within the allowable range. If not, contact the local power operator. If yes, also modify the grid undervoltage protection point after obtaining consent from the local power operator. 3. If normal operation cannot be restored for a long time, check if the AC side circuit breaker and output cables are properly connected. 201
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Abnormal grid voltage detection or extremely high voltage triggers the fault. Grid Rapid Overvoltage Protection F04 The moving average of grid voltage within 10min exceeds the range specified by safety regulations. 10min Overvoltage Protection F05 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid voltage is within the allowable range. If not, contact the local power operator. If yes, also modify the grid undervoltage protection point after obtaining consent from the local power operator. 3. If normal operation cannot be restored for a long time, check if the AC side circuit breaker and output cables are properly connected. Check if the grid voltage has been operating at a high level for a long time. If it occurs frequently, check if the grid frequency is within the allowable range. If not, contact the local power operator. If yes, also modify the grid 10min overvoltage protection point after obtaining consent from the local power operator. 202
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Grid anomaly: The actual grid frequency is higher than the local grid standard requirements. Grid Overfrequen cy F06 Grid anomaly: The actual grid frequency is lower than the local grid standard requirements. Grid Underfreque ncy F07 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid frequency is within the allowable range. If not, contact the local power operator. If yes, also modify the grid overfrequency protection point after obtaining consent from the local power operator. 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid frequency is within the allowable range. If not, contact the local power operator. If yes, also modify the grid overfrequency protection point after obtaining consent from the local power operator. 203
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Grid anomaly: The rate of change of the actual grid frequency does not comply with the local grid standard. Grid Frequency Instability F08 The grid has been disconnected, but grid voltage is maintained due to the presence of loads. Grid connection is stopped according to safety protection requirements. Anti- islanding Protection F09 Grid anomaly: The duration of abnormal grid voltage exceeds the time specified for high/low voltage ride-through. LVRT Undervoltag e F10 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid frequency is within the allowable range. If not, contact the local power operator. 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid frequency is within the allowable range. If not, contact the local power operator. 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid voltage and frequency are within the allowable range and stable. If not, contact the local power operator. 204
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Grid anomaly: The duration of abnormal grid voltage exceeds the time specified for high/low voltage ride-through. F11 HVRT Overvoltage The insulation resistance to ground of the input decreases during inverter operation. F12 30mA GFCI Protection The insulation resistance to ground of the input decreases during inverter operation. F13 60mA GFCI Protection 1. If it occurs occasionally, it may be a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, check if the grid voltage and frequency are within the allowable range and stable. If not, contact the local power operator. 1. If it occurs occasionally, it may be caused by occasional external line anomalies. It will resume normal operation after the fault is cleared, requiring no manual intervention. 2. If it occurs frequently or cannot be restored for a long time, check if the PV string's impedance to ground is too low. 1. If it occurs occasionally, it may be caused by occasional external line anomalies. It will resume normal operation after the fault is cleared, requiring no manual intervention. 2. If it occurs frequently or cannot be restored for a long time, check if the PV string's impedance to ground is too low. 205
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions The insulation resistance to ground of the input decreases during inverter operation. F14 150mA GFCI Protection The insulation resistance to ground of the input decreases during inverter operation. GFCI Gradual Change Protection F15 The DC component of the inverter output current is higher than the safety regulation or the machine's default allowable range. F16 DCI Level 1 Protection 1. If it occurs occasionally, it may be caused by occasional external line anomalies. It will resume normal operation after the fault is cleared, requiring no manual intervention. 2. If it occurs frequently or cannot be restored for a long time, check if the PV string's impedance to ground is too low. 1. If it occurs occasionally, it may be caused by occasional external line anomalies. It will resume normal operation after the fault is cleared, requiring no manual intervention. 2. If it occurs frequently or cannot be restored for a long time, check if the PV string's impedance to ground is too low. 1. If it is caused by an external fault, the inverter will automatically resume normal operation after the fault disappears, requiring no manual intervention. 2. If this alarm occurs frequently, affecting the normal power generation of the power station, contact the dealer or after-sales service center. 206
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions The DC component of the inverter output current is higher than the safety regulation or the machine's default allowable range. F17 DCI Level 2 Protection 1. If it is caused by an external fault, the inverter will automatically resume normal operation after the fault disappears, requiring no manual intervention. 2. If this alarm occurs frequently, affecting the normal power generation of the power station, contact the dealer or after-sales service center. 207
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions 1. PV string shorted to protective earth. 2. The PV string is installed in a humid environment for a long time and the line has poor insulation to ground. 3. Low insulation impedance of the battery port line to ground. Low Insulation Resistance F18 1. Check the impedance of the PV string/battery port to protective earth. A value greater than 80kΩ is normal. If the checked value is less than 80kΩ, locate and rectify the short circuit point. 2. Check if the inverter's protective earth wire is correctly connected. 3. If it is confirmed that the impedance is indeed below the default value in rainy/overcast environments, please reset the inverter's "Insulation Impedance Protection Point" via the App. For inverters in the Australia and New Zealand markets, the insulation impedance fault can also be alerted in the following ways: 1. The inverter is equipped with a buzzer. When a fault occurs, the buzzer sounds continuously for 1 minute; if the fault is not resolved, the buzzer sounds again every 30 minutes. 2. If the inverter is added to the monitoring platform and alarm notification methods are set, alarm information can be sent to customers via email. 208
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions 1. The inverter's protective earth wire is not connected. 2. When the PV string output is grounded, the inverter output side is not connected to an isolation transformer. F19 Grounding Abnormal Hard Anti- reverse Power Flow Protection Load abnormal fluctuation F20 1. Please confirm if the inverter's protective earth wire is not properly connected. 2. In scenarios where the PV string output is grounded, please confirm if the inverter output side is connected to an isolation transformer. 1. If it is caused by an external fault, the inverter will automatically resume normal operation after the fault disappears, requiring no manual intervention. 2. If this alarm occurs frequently, affecting the normal power generation of the power station, contact the dealer or after-sales service center. 209
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions F21 Internal Comm Loss Slave DSP1 communication timeout - Master DSP, Slave DSP2 communication timeout - Master DSP, Slave DSP2 communication timeout - Slave DSP1, Master DSP communication timeout - Slave DSP1, Master DSP communication timeout - Slave DSP2 or Slave DSP1 communication timeout - Slave DSP2: 1. Chip not powered on 2. Chip firmware version error Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. 210
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Master DSP CAN module error, Slave DSP1 CAN module error or Slave DSP2 CAN module error: 1. Frame format error 2. Parity error 3. CAN bus offline 4. Hardware CRC error 5. Control bit is receive (transmit) when transmitting (receiving) 6. Transmission to a disallowed unit Generator Waveform Detection Fault 1. This fault will always be displayed when a generator is not connected; 2. When the generator is operating, failure to meet generator safety regulations will trigger this fault. F22 Generator Abnormal Connection F23 F24 Generator Voltage Low F25 Generator Voltage High Generator Frequency Low F26 1. Ignore this fault when a generator is not connected; 2. When this fault occurs due to a generator fault, it is normal. Wait for a period after the generator recovers, and the fault will clear automatically; 3. This fault will not affect the normal operation of the off-grid mode. 4. When both the generator and grid are connected and meet safety requirements, the grid has priority for grid connection, and the system will operate in grid-connected state. 211
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions Generator Frequency High F27 Parallel communication cable not securely connected or parallel IO chip damaged Parallel I/O Self-check Abnormal F28 Paralell Grid Line Reversed Some machines have grid lines reversed with others F29 AC HCT check Abnormal AC sensor has sampling abnormality F30 GFCI HCT Check Abnormal Leakage current sensor has sampling abnormality F31 Inverter Internal Failure F32 Inverter has a fault Possible causes: Flash content changed; Flash lifespan exhausted; Flash Read/Write Error F33 Check if the parallel communication cable is securely connected, then check if the IO chip is damaged. If yes, replace the IO chip. Reconnect the grid lines. Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. 1. Upgrade to the latest firmware. 2. Contact the dealer or after-sales service center. 212
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions The arc fault module did not detect an arc fault during the arc self-check process. F34 AFCI Check Failure Cabinet temperature is too high, possible causes: 1. Poor ventilation at the inverter installation location. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. Cabinet Overtemper ature F35 Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. 1. Check if the ventilation at the inverter installation location is good and if the ambient temperature exceeds the maximum allowable ambient temperature range. 2. If ventilation is poor or ambient temperature is too high, improve its ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, contact the dealer or after-sales service center. 213
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions BUS overvoltage, possible causes: 1. PV voltage is too high; 2. Inverter BUS voltage sampling abnormality; 3. Poor isolation effect of the dual- split transformer at the inverter output side, causing mutual interference when two inverters are connected in parallel, with one inverter reporting DC overvoltage during grid connection; F36 Bus Overvoltage Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. 214
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions PV input voltage is too high, possible cause: PV array configuration error, too many PV panels connected in series in a string, causing the string's open- circuit voltage to be higher than the inverter's maximum operating voltage. F37 PV Input Overvoltage 1. Unreasonable component configuration. 2. Hardware damage. PV Continuous Hardware Overcurrent F38 1. Unreasonable component configuration. 2. Hardware damage. PV Continuous Software Overcurrent F39 Check the series configuration of the corresponding PV array string to ensure the string's open-circuit voltage is not higher than the inverter's maximum operating voltage. After the PV array is correctly configured, the inverter alarm will disappear automatically. Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, contact the dealer or after-sales service center. 215
Faul t Cod e Fault Name Possible Cause Troubleshooting Suggestions String Reverse Connection (String 1-n) n: Determined based on the actual number of inverter strings. F40, F98 PV string reverse connection 8.5.2.2.2 Troubleshooting (Fault Codes F41-F80) Fault Code Fault Name Fault Cause Troubleshooting Suggestions 1. Off-grid side output exceeds specifications. 2. Off-grid side short circuit. 3. Off-grid terminal voltage is too low. 4. When used as a heavy load port, the heavy load exceeds specifications. Generator Port Overload F41 Check if the string is reverse connected. Confirm the off-grid side output voltage, current, power and other data to identify the cause of the problem. 216
Fault Code Fault Name Fault Cause Troubleshooting Suggestions DC Arcing Failure(Strin g1-n) n: Determined based on the actual number of inverter strings. 1. DC side connection terminals are loose. 2. DC side connection terminals have poor contact. 3. DC cable core is damaged or has poor contact. F42 Utility grid abnormality: Anomaly in grid voltage detection triggers the fault. Grid Waveform Abnormal F43 Utility grid abnormality: Single- phase voltage drop in the grid. F44 Grid Phase Loss 1. After the machine reconnects to the grid, check if the voltage and current of each circuit show abnormal reduction or drop to zero. 2. Check if the DC side terminals are firmly connected. 1. If it occurs occasionally, it may be due to a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, please check if the grid voltage and frequency are within the allowable range and stable. If not, contact the local power operator. 1. If it occurs occasionally, it may be due to a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, please check if the grid voltage and frequency are within the allowable range and stable. If not, contact the local power operator. 217
Fault Code Fault Name Fault Cause Troubleshooting Suggestions Grid Voltage Imbalance Excessive difference in grid phase voltages. F45 Inverter and grid wiring abnormality: Wiring is not in positive sequence. Grid Phase Sequence Failure F46 Rapidly shuts down output after detecting a grid power outage condition. Grid Rapid Shutdown Protection F47 Grid Neutral Wire Loss (Split Grid) Neutral wire loss in a split-phase grid. F48 Low impedance or short circuit between output phase line and PE. F49 L-PE Short Circuit 1. If it occurs occasionally, it may be due to a short-term grid anomaly. The inverter will resume normal operation after detecting a normal grid, requiring no manual intervention. 2. If it occurs frequently, please check if the grid voltage and frequency are within the allowable range and stable. If not, contact the local power operator. 1. Check if the inverter and grid wiring are in positive sequence. The fault will disappear automatically after correct wiring (e.g., swapping any two live wires). 2. If the wiring is correct but the fault persists, contact the dealer or after- sales service center. The fault disappears automatically after grid power supply is restored. 1. The alarm disappears automatically after grid power supply is restored. 2. Check if the AC line or AC switch is disconnected. Measure the impedance between the output phase line and PE, locate the position with low impedance and repair it. 218
Fault Code Fault Name Fault Cause Troubleshooting Suggestions F50 DCV Level 1 Protection Abnormal load fluctuation. F51 DCV Level 2 Protection Abnormal load fluctuation. North American safety regulations require manual recovery or waiting 24h after multiple faults; automatic recovery is not allowed. Leakage current (GFCI) Multiple Fault Shutdown F52 North American safety regulations require manual recovery or waiting 24h after multiple faults; automatic recovery is not allowed. DC Arcing (AFCI) Multiple Fault Shutdown F53 1. If it is caused by an external fault, the inverter will automatically resume normal operation after the fault disappears, requiring no manual intervention. 2. If this alarm occurs frequently and affects normal power generation of the plant, contact the dealer or after- sales service center. Please check if the PV string's impedance to ground is too low. 1. After the machine reconnects to the grid, check if the voltage and current of each circuit show abnormal reduction or drop to zero. 2. Check if the DC side terminals are firmly connected. 219
Fault Code Fault Name Fault Cause Troubleshooting Suggestions Communication loss with external devices of the inverter, possibly due to peripheral power issues, communication protocol mismatch, or lack of configuration for the corresponding peripheral. External Communica tion Link Break F54 Back-up Port Overload Fault Prevents the inverter from continuously outputting overload. F55 Back-up Port Overvoltage Fault Prevents damage to loads caused by inverter output overvoltage. F56 Waiting time for the Box to switch relays is too long during grid-to-off-grid transition. F57 External Box Fault CT connection wire disconnected (Japanese safety regulation requirement). F58 CT Loss Fault Judgment is based on the actual model and detection enable bits. Peripherals not supported by some models will not be detected. Turn off some off-grid loads to reduce the inverter's off-grid output power. 1. If it occurs occasionally, it may be caused by load switching and requires no manual intervention. 2. If it occurs frequently, contact the dealer or after-sales service center. 1. Check if the Box is working normally. 2. Check if the Box communication wiring is correct. Check if the CT wiring is correct. 220
Fault Code Fault Name Fault Cause Troubleshooting Suggestions Parallel communication cable is not securely connected or some machines are offline. Parallel CAN Communica tion Abnormal F59 Parallel Back-up Connection Reversed Backup lines of some machines are reversed with others. F60 Inverter Soft Start Failure Inverter soft start failure during off- grid cold start. F61 F62 AC HCT Failure HCT sensor abnormality. F63 GFCI HCT Failure Leakage current sensor abnormality. Inverter Internal Failure F64 Inverter has a fault. Check if all machines are powered on and if the parallel communication cable is securely connected. Reconnect the backup lines. Check if the inverter module is damaged. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. 221
Fault Code Fault Name Fault Cause Troubleshooting Suggestions AC terminal temperature is too high, possible causes: 1. Inverter installation location lacks ventilation. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. AC Terminal Overtemper ature F65 Inverter module temperature is too high, possible causes: 1. Inverter installation location lacks ventilation. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. INV Module Overtemper ature F66 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or ambient temperature is too high, improve the ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, contact the dealer or after-sales service center. 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or ambient temperature is too high, improve the ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, contact the dealer or after-sales service center. 222
Fault Code Fault Name Fault Cause Troubleshooting Suggestions Boost module temperature is too high, possible causes: 1. Inverter installation location lacks ventilation. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. Boost Module Overtemper ature F67 Output filter capacitor temperature is too high, possible causes: 1. Inverter installation location lacks ventilation. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. AC Capacitor Overtemper ature F68 Possible causes: 1. IGBT short circuit. 2. Inverter sampling circuit abnormality. PV IGBT Short Circuit Fault F69 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or ambient temperature is too high, improve the ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, contact the dealer or after-sales service center. 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or ambient temperature is too high, improve the ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. 223
Fault Code Fault Name Fault Cause Troubleshooting Suggestions 1. Software issue causing no PWM generation. 2. Drive circuit abnormality. 3. IGBT open circuit. PV IGBT Open Circuit Fault F70 F71 NTC Abnormal NTC temperature sensor abnormality. F72 PWM Abnormal Abnormal PWM waveform. CPU Interrupt Abnormal CPU interrupt abnormality. F73 Functional safety detection detected an abnormality. F74 Microelectr onics Fault F75 PV HCT Fault Boost current sensor abnormality. 1.5V Reference Abnormal Reference circuit fault. F76 Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. 224
Fault Code Fault Name Fault Cause Troubleshooting Suggestions 0.3V Reference Abnormal Reference circuit fault. F77 CPLD Version Identificatio n Error CPLD version identification error. F78 Communication content error or timeout between CPLD and DSP. CPLD Communica tion Fault F79 Model Identificatio n Fault Fault related to model identification error. F80 8.5.2.2.3 Troubleshooting (Fault Codes F81-F121) Faul t Cod e Fault Name Possible Cause Recommended Action F81 P-Bus Overvoltage Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Turn off the AC output side switch and DC input side switch, wait 5 minutes, then turn them on. If the fault persists, contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 225
Faul t Cod e Fault Name Possible Cause Recommended Action BUS overvoltage, possible causes: 1. PV voltage too high; 2. Inverter BUS voltage sampling abnormal; 3. Poor isolation effect of the split- phase transformer behind the inverter, causing mutual interference when two inverters are grid-connected, with one inverter reporting DC overvoltage during grid connection; F82 N-Bus Overvoltage Bus Overvoltage (Sub CPU1) F83 P-Bus Overvoltage (Sub CPU1) F84 Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 226
Faul t Cod e Fault Name Possible Cause Recommended Action BUS overvoltage, possible causes: 1. PV voltage too high; 2. Inverter BUS voltage sampling abnormal; 3. Poor isolation effect of the split- phase transformer behind the inverter, causing mutual interference when two inverters are grid-connected, with one inverter reporting DC overvoltage during grid connection; N-Bus Overvoltage (Sub CPU1) F85 Bus Overvoltage (Sub CPU2) F86 P-Bus Overvoltage (Sub CPU2) F87 Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 227
Faul t Cod e Fault Name Possible Cause Recommended Action BUS overvoltage, possible causes: 1. PV voltage too high; 2. Inverter BUS voltage sampling abnormal; 3. Poor isolation effect of the split- phase transformer behind the inverter, causing mutual interference when two inverters are grid-connected, with one inverter reporting DC overvoltage during grid connection; N-Bus Overvoltage (Sub CPU2) F88 P-Bus Overvoltage (CPLD) F89 Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 228
Faul t Cod e Fault Name Possible Cause Recommended Action BUS overvoltage, possible causes: 1. PV voltage too high; 2. Inverter BUS voltage sampling abnormal; 3. Poor isolation effect of the split- phase transformer behind the inverter, causing mutual interference when two inverters are grid-connected, with one inverter reporting DC overvoltage during grid connection; N-Bus Overvoltage (CPLD) F90 FlyCap Software Overvoltage FlyCap overvoltage, possible causes: 1. PV voltage too high; 2. Inverter FlyCap voltage sampling abnormal; F91 FlyCap Hardware Overvoltage F92 Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 229
Faul t Cod e Fault Name Possible Cause Recommended Action FlyCap undervoltage, possible causes: 1. PV energy insufficient; 2. Inverter FlyCap voltage sampling abnormal; FlyCap Undervoltag e F93 FlyCap precharge failure, possible causes: 1. PV energy insufficient; 2. Inverter FlyCap voltage sampling abnormal; FlyCap Precharge Failure F94 1. Control loop parameters unreasonable 2. Hardware damage FlyCap Precharge Abnormal F95 String Overcurrent( String 1-n) n: Determined by the actual number of inverter strings Possible causes: 1. String overcurrent; 2. String current sensor abnormal F96, F97 Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 230
Faul t Cod e Fault Name Possible Cause Recommended Action String Missing(Stri ng 1-n) n: Determined by the actual number of inverter strings F99, F100 String fuse open (if present) Check if the fuse is open. Battery 1 precharge circuit fault (precharge resistor burnt, etc.) Battery 1 Precharge Fault F101 Battery 1 relay cannot operate normally F102 Battery 1 Relay Failure Battery 1 connection voltage exceeds the machine's rated range Battery 1 Connection Overvoltage F103 Battery 2 precharge circuit fault (precharge resistor burnt, etc.) Battery 2 Precharge Fault F104 Check if the precharge circuit is in good condition, and whether the battery voltage matches the bus voltage after only the battery is powered on. If not consistent, please contact the dealer or after-sales service center. After powering on the battery, check if the battery relay is working, and if a closing sound is heard. If not operating, please contact the dealer or after-sales service center. Confirm if the battery voltage is within the machine's rated range. Check if the precharge circuit is in good condition, and whether the battery voltage matches the bus voltage after only the battery is powered on. If not consistent, please contact the dealer or after-sales service center. 231
Faul t Cod e Fault Name Possible Cause Recommended Action Battery 2 relay cannot operate normally F105 Battery 2 Relay Failure Battery 2 connection voltage exceeds the machine's rated range Battery 2 Connection Overvoltage F106 Abnormal during carrier synchronization grid connection On-grid PWM Sync Failure F107 DSP Communicat ion Fault F108 - - Abnormal cable connection between inverter and STS F109 External STS Fault After powering on the battery, check if the battery relay is working, and if a closing sound is heard. If not operating, please contact the dealer or after-sales service center. Confirm if the battery voltage is within the machine's rated range. 1. Check if the sync cable connection is normal 2. Check if the master/slave settings are normal; 3. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Check if the wiring sequence of the harness between the inverter and the STS corresponds one by one in order. 232
Faul t Cod e Fault Name Possible Cause Recommended Action 1. Inverter reports error and disconnects from grid 2. Meter communication unstable 3. Reverse power flow condition occurs F110 Export Limit Protection F111 Bypass Overload - - F112 Black Start Failure - - F113 Offgrid AC Ins Volt High - - Relay abnormal, reasons: 1. Relay abnormal (relay short circuit) 2. Relay sampling circuit abnormal. 3. AC side wiring abnormal (possible loose connection or short circuit) F114 Relay Failure 2 SVG Precharge Disabled SVG precharge hardware failure F115 Nighttime SVG PID Prevention Fault PID prevention hardware abnormal F116 1. Check if the inverter has other error messages. If yes, handle them accordingly; 2. Check if the meter connection is reliable; 3. If this alarm occurs frequently, affecting normal power generation of the plant, please contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Contact the dealer or after-sales service center. 233
Faul t Cod e Fault Name Possible Cause Recommended Action DSP Version Identificatio n Error DSP software version identification error F117 1. Software issue causing inverter drive to turn off earlier than flyback drive: 2. Inverter drive circuit abnormal causing failure to turn on: 3. PV voltage too high; 4. Mos voltage sampling abnormal; MOS Continuous Overvoltage F118 F119 Bus Short Circuit Fault Hardware damage Bus Sampling Abnormal 1. BUS voltage sampling hardware fault F120 Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. If the BUS short circuit fault occurs and the inverter remains offline, please contact the dealer or after- sales service center. Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 234
Faul t Cod e Fault Name Possible Cause Recommended Action 1. BUS voltage sampling hardware fault 2. Battery voltage sampling hardware fault 3. Dcrly relay fault DC Side Sampling Abnormal F121 8.5.2.2.4 Troubleshooting (Fault Codes F122-F163) Disconnect the AC output side switch and DC input side switch, wait for 5 minutes, then close the AC output side switch and DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 235
Faul t Cod e Fault Name Possible Cause Recommended Action There are three PV Access Modes, taking a four- channel MPPT as an example: 1. Parallel Mode: i.e., AAAA mode (same- source mode), PV1- PV4 are from the same source, all 4 PV channels are connected to the same solar panel. 2. Partial Parallel Mode: i.e., AACC mode, PV1 and PV2 are connected from the same source, PV3 and PV4 are connected from the same source. 3. Independent Mode: i.e., ABCD mode (different- source), PV1, PV2, PV3, PV4 are connected independently, each of the 4 PV channels connects to one solar panel. This fault is reported PV Access Mode Setting Error F122 Check if the PV Access Mode is set correctly (ABCD, AACC, AAAA), and reconfigure the PV Access Mode correctly. 1. Confirm that all actual PV channels are correctly connected. 2. If the PV connections are correct, use the APP or the screen to check if the currently set "PV Access Mode" corresponds to the actual connection mode. 3. If the currently set "PV Access Mode" does not match the actual connection mode, use the APP or the screen to set the "PV Access Mode" to the mode consistent with the actual situation. After setting, disconnect and restart the PV and AC power supply. 4. After configuration, if the current "PV Access Mode" matches the actual connection mode but the fault persists, contact the dealer or the after-sales service center. 236
Faul t Cod e Fault Name Possible Cause Recommended Action if the actual PV connection mode does not match the PV Access Mode configured on the device. Multi- channel PV Phase Error PV Input Mode Setting Error F123 Check if the PV Access Mode is set correctly (ABCD, AACC, AAAA), and reconfigure the PV Access Mode correctly. 1. Confirm that all actual PV channels are correctly connected. 2. If the PV connections are correct, use the APP or the screen to check if the currently set "PV Access Mode" corresponds to the actual connection mode. 3. If the currently set "PV Access Mode" does not match the actual connection mode, use the APP or the screen to set the "PV Access Mode" to the mode consistent with the actual situation. After setting, disconnect and restart the PV and AC power supply. 4. After configuration, if the current "PV Access Mode" matches the actual connection mode but the fault persists, contact the dealer or the after-sales service center. 237
Faul t Cod e Fault Name Possible Cause Recommended Action Battery 1 Reverse Connection fault Battery 1 positive and negative terminals are reversed F124 Battery 2 Reverse Connection fault Battery 2 positive and negative terminals are reversed F125 Abnormal Battery Connection Abnormal Battery Connection F126 High battery temperature, possible causes: 1. Inverter is installed in a poorly ventilated location. 2. Ambient temperature is too high. BAT Overtemper ature F127 3. Internal fan is malfunctioning. F128 Ref Voltage Abnormal Reference circuit fault Check if the polarities of the battery and the machine's terminals are consistent. Check if the polarities of the battery and the machine's terminals are consistent. Check if the battery is working normally. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If the fault persists, contact the dealer or the after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If the fault persists, contact the dealer or the after-sales service center. 238
Faul t Cod e Fault Name Possible Cause Recommended Action Cabinet temperature is too low, possible cause: ambient temperature is too low. Cabinet Under Temperatur e F129 AC side surge protection device failure F130 AC Side SPD fault DC side surge protection device failure F131 DC Side SPD fault Internal fan abnormal, possible causes: 1. Fan power supply abnormal; 2. Mechanical fault (locked rotor); 3. Fan aging or damage. F132 Internal Fan Abnormal External fan abnormal, possible causes: 1. Fan power supply abnormal; 2. Mechanical fault (locked rotor); 3. Fan aging or damage. F133 External Fan Abnormal Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If the fault persists, contact the dealer or the after-sales service center. Replace the AC side surge protection device. Replace the DC side surge protection device. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If the fault persists, contact the dealer or the after-sales service center. 239
Faul t Cod e Fault Name Possible Cause Recommended Action PID hardware fault or PV voltage too high causing PID suspension PID Diagnosis Abnormal F134 Possible causes: Overcurrent or PV reverse connection caused the trip- switch to open; Trip-Switch Trip Warning F135 Possible causes: Overcurrent caused the trip-switch to open; Historical PV IGBT Short Circuit Warning F136 No action required for PID suspension warning caused by high PV voltage. For PID hardware fault, clear the PID fault by turning the PID switch off and then on. Replace the PID device. Contact the dealer or the after-sales service center; The reason for tripping is a PV short circuit or reverse connection. Check if there is a historical PV short circuit warning or a historical PV reverse connection warning. If present, a technician needs to inspect the corresponding PV condition. After checking and confirming no fault, manually close the trip-switch and clear this warning via the "Clear Historical Faults" operation in the APP interface. Contact the dealer or the after-sales service center; The technician needs to check the Boost hardware and the external string for faults according to the historical PV short circuit warning sub-code. After checking and confirming no fault, clear this warning via the "Clear Historical Faults" operation in the APP interface. 240
Faul t Cod e Fault Name Possible Cause Recommended Action Historical PV Reverse Connection Warning (String 1-n) (n: determined by the actual number of inverter strings) Possible causes: PV reverse connection caused the trip-switch to open; F137 , F138 Possible causes: 1. Flash content changed; 2. Flash end of life; Flash Read/Write Error Warning F139 This warning may only be reported after anti-backfeed function is enabled. Possible causes: 1. Meter not connected; 2. Communication cable connection between the meter and the inverter is incorrect. F140 Meter Comm Loss PV Panel Type Identificatio n Failure PV panel identification hardware abnormal F141 Contact the dealer or the after-sales service center; The technician needs to check the corresponding string for reverse connection and check for voltage differences in the PV panel configuration according to the historical PV reverse connection warning sub-code. After checking and confirming no fault, clear this warning via the "Clear Historical Faults" operation in the APP interface. 1. Upgrade to the latest firmware; 2. Contact the dealer or the after- sales service center. Check the meter wiring, connect the meter correctly. If the fault persists after checking, contact the dealer or the after-sales service center. Contact the dealer or the after-sales service center. 241
Faul t Cod e Fault Name Possible Cause Recommended Action PV string mismatch, two strings under the same MPPT channel have different open- circuit voltage configurations F142 PV String Mismatch F143 CT Not Connected CT not connected Check CT wiring. F144 CT Reverse Connection CT reverse connection Check CT wiring. F145 PE Loss Ground wire not connected Check the ground wire. High String Terminal Temperatur e (String 1~8) Bit 1 of the PV terminal temperature alarm sub-code in register 37176 is set F146 High String Terminal Temperatur e (String 9~16) Bit 2 of the PV terminal temperature alarm sub-code in register 37177 is set F147 High String Terminal Temperatur e (String 17~20) Bit 3 of the PV terminal temperature alarm sub-code in register 37178 is set F148 Check the open-circuit voltages of the two strings, configure strings with the same open-circuit voltage under the same MPPT channel. Prolonged string mismatch poses a safety risk. - - - 242
Faul t Cod e Fault Name Possible Cause Recommended Action Historical PV Reverse Connection Warning (String 33~48) Possible causes: PV reverse connection caused the trip-switch to open; F149 F150 Battery 1 Low Voltage Battery voltage is below the set value - F151 Battery 2 Low Voltage Battery voltage is below the set value - Battery is not in charging mode, voltage is below the shutdown voltage Low Voltage of Battery Power F152 F153 Battery 1 High Voltage - - F154 Battery 2 High Voltage - - Contact the dealer or the after-sales service center; The technician needs to check the corresponding string for reverse connection and check for voltage differences in the PV panel configuration according to the historical PV reverse connection warning sub-code. After checking and confirming no fault, clear this warning via the "Clear Historical Faults" operation in the APP interface. - 243
Faul t Cod e Fault Name Possible Cause Recommended Action 1. PV string shorted to protective earth. 2. PV string installed in a long-term humid environment with poor line-to- ground insulation. Online Low Insulation Resistance F155 Micro-grid Overload Warning backup port input current is too high F156 F157 Manual Reset - - Generator Phase Sequence Abnormal F158 - - The multiplexed (generator) port is configured for micro-grid or large load, but a generator is actually connected Multiplexed Port Configuratio n Abnormal F159 EMS issued a forced off-grid command, but the off-grid function is not enabled F160 EMS Forced Off-grid 1. Check the impedance of the PV string to protective earth. If a short circuit is found, rectify the short circuit point. 2. Check if the inverter's protective earth wire is correctly connected. 3. If it is confirmed that the impedance is indeed below the default value in rainy/cloudy conditions, reconfigure the "Insulation Resistance Protection Point". No action required if it occurs occasionally; If this warning appears frequently, contact the dealer or the after-sales service center. Use the APP to change the multiplexed (generator) port configuration. Enable the off-grid function. 244
Faul t Cod e Fault Name Possible Cause Recommended Action Passive Anti- islanding Protection F161 - - Actual grid type (two-phase or split- phase) does not match the set safety standard F162 Grid Type Fault Grid abnormal: The rate of change of grid voltage phase does not comply with local grid standards. F163 Grid Phase Instability 8.5.2.2.5 Fault Phenomenon Handling Switch to the corresponding safety standard according to the actual grid type. 1. If it occurs occasionally, it may be a temporary grid abnormality. The inverter will resume normal operation after detecting a normal grid, no manual intervention is required. 2. If it occurs frequently, check if the grid frequency is within the allowable range. If not, contact the local power operator. 245
Fault Name Fault Cause Fault Handling Suggestions 1. This fault will be displayed continuously when no generator is connected. 2. When the generator is operating, if it does not meet the generator safety regulations, this fault will be triggered. Generator Failure BMS Status Bit Error BMS module failure 1. Poor ventilation of the machine 2. Hot air flows back to the ambient temperature sampling point Ambient Overtemperat ure 1. If the generator is not connected, ignore this fault. 2. If this fault appears when the generator has a fault, it is normal. Wait for a period after the generator recovers, and the fault will clear automatically. 3. This fault will not affect the normal operation of the off-grid mode. 4. When both the generator and the grid are connected and meet safety requirements, the grid has priority for grid connection, and the system will operate in grid-tied mode. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If the fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If the fault persists, please contact the dealer or after-sales service center. 246
Fault Name Fault Cause Fault Handling Suggestions PV terminal overtemperature, possible causes: 1. Poor ventilation at the inverter installation location. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. PV Terminal Overtemperat ure BAT terminal overtemperature, possible causes: 1. Poor ventilation at the inverter installation location. 2. Ambient temperature is too high. BAT Terminal Overtemperat ure AC terminal overtemperature, possible causes: 1. Poor ventilation at the inverter installation location. 2. Ambient temperature is too high. 3. Internal fan operation is abnormal. AC Terminal Overtemperat ure Warning 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or the ambient temperature is too high, please improve its ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, please contact the dealer or after-sales service center. 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or the ambient temperature is too high, please improve its ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, please contact the dealer or after-sales service center. 247
Fault Name Fault Cause Fault Handling Suggestions BAT terminal overtemperature, possible causes: 1. Poor ventilation at the inverter installation location. 2. Ambient temperature is too high. BAT Terminal Overtemperat ure Warning Three-phase external wiring error Three-phase on-grid fault Abnormal cable connection between the inverter and the STS External STS Failure Fault Name Possible Cause Recommended Action In a parallel system, if a slave unit has not communicated with the master for more than 400 seconds. Parallel Comm Timeout Shutdown Three-phase off-grid phase loss fault Phase loss in a three-phase system. 1. Check if the ventilation at the inverter installation location is adequate and if the ambient temperature exceeds the maximum allowable range. 2. If ventilation is poor or the ambient temperature is too high, please improve its ventilation and heat dissipation conditions. 3. If both ventilation and ambient temperature are normal, please contact the dealer or after-sales service center. Re-wire the connections. Check if the wiring sequence of the harness between the inverter and the STS corresponds one-to-one in order. Check if the parallel communication cable harness is securely connected. Check if the slave unit addresses are duplicated. Check if all inverters are powered on. 1. Check if each phase of the three-phase system is connected to an inverter. 2. 248
Fault Name Possible Cause Recommended Action Externally triggered hardware EPO button or remotely triggered EPO command. EPO Automatically triggered when the combustible gas device detects a concentration of 20% LEL or higher. High Combustible Gas Concentration Mismatch Between Combustible Gas Device Air Damper Open Command and Feedback Signal Mismatch between the control signal to open the air damper and the feedback signal. Check via the App if the one-key shutdown function is enabled. One-Key Shutdown If it was actively triggered by a remote shutdown command, it can be ignored. 1. 2. If not actively triggered, please contact the distributor or after-sales service center. 1. After the fault occurs, the unit will automatically open the air damper to exhaust and reduce the concentration. The fault will clear automatically after the concentration remains below 5% LEL for 15 minutes. 2. If the fault triggers a cluster-level fire protection fault, the air damper will automatically close. Confirm the damper status within 30s to ensure the cluster- level fire protection operates in an enclosed space. 3. Please contact the distributor or after- sales service center. Check the cable harness signal connection for issues. 1. Please contact the distributor or after- sales service center. 2. Disable the one-key shutdown function. 249
Fault Name Possible Cause Recommended Action Offline Shutdown - - Remote Shutdown - - On-Grid SPD Fault - Off-Grid SPD Fault - Child Node Communicati on Failure Internal Comm Abnormal Communication link abnormality between the dehumidifier and the LC control box. Dehumidifier Communicati on Fault Try restarting the unit and observe if the fault clears. 1. 2. If the fault persists after restart, please contact the distributor or after-sales service center. Try restarting the unit and observe if the fault clears. 1. 2. If the fault persists after restart, please contact the distributor or after-sales service center. Try restarting the unit and observe if the fault clears. 1. 2. If the fault persists after restart, please contact the distributor or after-sales service center. Check the communication cable harness for the link and observe if the fault clears. 1. Try restarting the unit and observe if the fault clears. 2. 3. If the fault persists after restart, please contact the distributor or after-sales service center. 250
Fault Name Possible Cause Recommended Action 1. The combustible gas device left the factory without the 485 address properly configured to 2. Combustible Gas Detection Device Communicati on Fault 2. Communication link abnormality between the combustible gas device and the LC control box. Communication link abnormality between the control board and the diesel generator (DG). DG Communicati on Failure 1. Individual cell voltage too high. 2. Voltage sensing line abnormality. Battery Over Voltage 1. Total battery voltage too high. 2. Voltage sensing line abnormality. Battery Undervoltage 1. Individual cell voltage too low. 2. Voltage sensing line abnormality. Check the communication cable harness for the link and observe if the fault clears. 1. Try restarting the unit and observe if the fault clears. 2. 3. Use the method provided by the combustible gas device manufacturer to check if the device address is 2. If not, modify it. 4. If the fault persists after restart, please contact the distributor or after-sales service center. 1. Check the communication cable harness for the link and observe if the fault clears. 2. Try restarting the unit and observe if the fault clears. 3. If the fault persists after restart, please contact the distributor or after-sales service center. Record the fault phenomenon, restart the battery, wait a few minutes, and confirm if the fault disappears. If the problem persists after restart, please contact the after-sales service center. 251
Fault Name Possible Cause Recommended Action 1. Total battery voltage too low. 2. Voltage sensing line abnormality. 1. Charging current too high, battery current limiting abnormality: sudden changes in temperature and voltage values. 2. Inverter response abnormal. Battery Overcurrent Battery discharge current too high. 1. Ambient Overtemperature. 2. Temperature sensor abnormality. Battery Overtemperat ure 1. Ambient temperature too low. 2. Temperature sensor abnormality. Battery Undertemper ature Battery Terminal Overtemperat ure Terminal temperature too high. 252
Fault Name Possible Cause Recommended Action Battery Imbalance 1. Large temperature difference. At different stages, the battery will limit its power, i.e., limit charge/discharge current. Therefore, this issue is generally difficult to occur. 2. Cell capacity degradation leads to excessive internal resistance, causing large temperature rise during overcurrent and thus a large temperature difference. 3. Poor welding of cell tabs leads to rapid cell temperature rise during overcurrent. 4. Temperature sampling issue. 5. Loose power cable connections. 253
Fault Name Possible Cause Recommended Action 1. Inconsistent cell aging levels. 2. Slave board chip issues can also cause excessive cell voltage difference. 3. Slave board balancing issues can also cause excessive cell voltage difference. 4. Caused by wiring harness issues. Insulation resistance damaged. Insulation Resistance Pre-charging Failure Pre-charging Failure Sensing Line Fault Battery sensing line poor contact or disconnected. Cell voltage sensing line poor contact or disconnected. Cell temperature sensing line poor contact or disconnected. Check if the ground wire is properly connected, restart the battery. If the problem persists after restart, please contact the after-sales service center. Indicates that during pre-charging, the voltage across the pre-charge MOS always exceeds the specified threshold. Power off and restart, then observe if the fault persists. Check if the wiring is correct and if the pre-charge MOS is damaged. Check the wiring, restart the battery. If the problem persists after restart, please contact the after-sales service center. Check the wiring, restart the battery. If the problem persists after restart, please contact the after-sales service center. 254
Fault Name Possible Cause Recommended Action Dual-channel current comparison error too large, or current sensing line circuit abnormal. Dual-channel voltage comparison error too large, or MCU vs. AFE voltage comparison error too large, or voltage sensing line circuit abnormal. Temperature sensing line circuit abnormal, poor contact, or disconnected. Overvoltage level 5 or overtemperature level 5, tripping the three-terminal fuse. Relay or MOS Overtemperat ure Relay or MOS overtemperature. Shunt Overtemperat ure Shunt overtemperature. The three-terminal fuse is blown. Please contact the after-sales service center to replace the main control board. This fault indicates the MOS tube temperature exceeds the specified threshold. Power off and let it sit for 2 hours for temperature recovery. This fault indicates the shunt temperature exceeds the specified threshold. Power off and let it sit for 2 hours for temperature recovery. 255
Fault Name Possible Cause Recommended Action BMS1 Other Faults 1 (Residential Storage) Relay or MOS open circuit. Relay or MOS short circuit. Communication abnormality between main cluster and slave cluster, or cell inconsistency between clusters. Battery system loop wiring harness abnormal, causing the interlock signal not to form a loop. BMS and PCS communication abnormal. BMS master and slave control communication cable harness abnormal. 1. Upgrade software, power off and let it sit for 5 minutes, restart and see if the fault persists. 2. If it persists, replace the battery pack. 1. Upgrade software, power off and let it sit for 5 minutes, restart and see if the fault persists. 2. If it persists, replace the battery pack. 1. Check the slave unit's battery information and software version, and if the communication cable connection to the master unit is normal. 2. Upgrade software. Check if the termination resistor is installed correctly. 1. Confirm if the communication cable interface definitions between the inverter and the connected battery are correct. 2. Please contact the after-sales service center to check backend data and observe if the inverter and battery software match correctly. 1. Check wiring, restart the battery. 2. Upgrade the battery firmware. If the problem persists after restart, please contact the after-sales service center. 256
Fault Name Possible Cause Recommended Action Communication loss between main negative chips. Circuit breaker, shunt trip abnormality. MCU self-test failure. 1. Software version too low or BMS board damaged. 2. Large number of parallel inverters, causing excessive inrush current during battery pre- charging. MCU internal fault. Total control current exceeds the specified threshold. 1. Power off and let it sit for 5 minutes, restart and see if the fault persists. 2. Check if the communication pins on the PACK and PCU bottom blind-mate connectors are loose or misaligned. Upgrade software, restart the battery. If the problem persists after restart, please contact the after-sales service center. 1. Upgrade software, observe if the fault persists. 2. For parallel systems, perform a black start of the battery first, then start the inverters. Upgrade software, restart the battery. This usually indicates MCU or external component damage. If the problem persists after restart, please contact the after-sales service center. Power off and let it sit for 5 minutes, restart and see if the fault persists. 1. Check if the inverter power setting is too high, exceeding the bus load capacity. 2. 257
Fault Name Possible Cause Recommended Action Inconsistent cells in parallel battery clusters. Reverse polarity connection of parallel battery clusters. Severe overtemperature/ov ervoltage etc., triggering the fire protection system. Air conditioner abnormal failure. Cabinet door not closed. Check if the cabinet door is properly closed. Supply voltage too high. Insufficient supply voltage. Air Conditioner Failure No voltage input. Unstable supply voltage. Compressor voltage unstable. Sensor poor contact or damaged. Air conditioner fan abnormal. Confirm if the cells in the parallel battery clusters are consistent. Check if the positive and negative terminals of the parallel battery clusters are reversed. Contact the after-sales service center. Try restarting the system. If the fault is not resolved, please contact the after-sales service center. Confirm if the supply voltage meets the air conditioner input voltage requirements. Re- power on after confirmation. Try restarting the system. If the fault is not resolved, please contact the after-sales service center. 258
Fault Name Possible Cause Recommended Action BMS1 Other Faults 2 (Residential Storage) Internal voltage or current abnormality in DCDC. DCDC overload or heatsink overtemperature, etc. Cell sensing abnormality or inconsistent aging levels. Fan operation not executed normally. Please contact the after-sales service center. Output terminal screws loose or poor contact. Battery used for too long or cells severely damaged. 1. Software version too low or BMS board damaged. 2. Large number of parallel inverters, causing excessive inrush current during battery pre- charging. Heating film damaged. Please contact the after-sales service center. Refer to specific DC fault content. Please contact the after-sales service center. 1. Power off the battery, check wiring and output terminal screw condition. 2. After confirmation, restart the battery, observe if the fault persists. If it persists, please contact the after-sales service center. Please contact the after-sales service center to replace the pack. 1. Upgrade software, observe if the fault persists. 2. For parallel systems, perform a black start of the battery first, then start the inverters. 259
Fault Name Possible Cause Recommended Action Heating film three- terminal fuse blown, heating function unavailable. Software model, Cell Type, hardware model mismatch. Thermal management board communication cable disconnected. Pack fan fault signal triggered. DCDC Fault Output port voltage too high. DCDC module detects battery voltage exceeding maximum charging voltage. Heatsink temperature too high. Battery discharge current too high. Please contact the after-sales service center. Check if the software model, SN, Cell Type, and hardware model are consistent. If not, please contact the after-sales service center. 1. Power off and let it sit for 5 minutes, restart and see if the fault persists. 2. If the fault does not recover, contact after-sales to replace the pack. Check the output port voltage. If the output port voltage is normal and the fault does not clear itself after restarting the battery, please contact the after-sales service center. Stop charging, discharge to below 90% SOC or let it sit for 2 hours. If ineffective and the fault persists after restart, please contact the after-sales service center. Let the battery sit for 1 hour for heatsink temperature to drop. If ineffective and the fault persists after restart, please contact the after-sales service center. Check if the load exceeds the battery's discharge capability. Turn off the load or stop PCS operation for 60s. If ineffective and the fault persists after restart, please contact the after-sales service center. 260
Fault Name Possible Cause Recommended Action Output port power cable positive/negative reversed with parallel cluster battery or PCS. Output power relay cannot close. Power device temperature too high. Relay welded/stuck. If the fault persists after restart, please contact the after-sales service center. Battery Rack Circulating Current Failure 1. Cell imbalance. 2. First power-on without full charge calibration. BMS1 Other Faults 3 (Large-scale Storage) Communication abnormal with Linux module. Cell temperature rise too fast. SOC below 10%. Charge the battery. Turn off the battery manual switch, check if the output port wiring is correct, restart the battery. Check if the output port wiring is correct and if there is a short circuit. If ineffective and the fault persists after restart, please contact the after-sales service center. Let the battery sit for 1 hour for internal power device temperature to drop. If ineffective and the fault persists after restart, please contact the after-sales service center. Record the fault phenomenon, restart the battery, wait a few minutes, and confirm if the fault disappears. If the problem persists after restart, please contact the after-sales service center. 1. Check if the communication cable connection is normal. 2. Upgrade software, restart the battery and observe if the fault persists. If it persists, please contact the after-sales service center. Cell abnormal, contact after-sales to replace the pack. 261
Fault Name Possible Cause Recommended Action SN written does not comply with rules. 1. Communication abnormal within battery cluster daisy chain. 2. Inconsistent cell aging levels between battery clusters. High humidity inside pack. - Fuse blown. Contact after-sales to replace the pack. Battery low power. Charge the battery. Circuit breaker abnormal. Contact after-sales to replace the pack. BMS1 Other Faults 4 (Large-scale Storage) External device abnormal. Contact after-sales to replace the pack. Contactor Failure 1 - - Contactor Failure 2 - - Overload Protection (Ksic) Sustained overload (exceeding 690KVA) for 10s. Overload Protection (Smart Port) Sustained overload (exceeding 690KVA) for 10s. Check if the SN digit count is normal. If abnormal, please contact the after-sales service center. 1. Check the pack contact condition within a single cluster battery. 2. Confirm the usage of each cluster battery, such as accumulated charge/discharge capacity, cycle count, etc. 3. Please contact the after-sales service center. Please contact the after-sales service center. Please contact the after-sales service center. 262
Fault Name Possible Cause Recommended Action Overcurrent Protection (Ksic) - - Overcurrent Protection (Smart Port) - - 1. Possibly the meter is not connected to the master. 2. Possibly the meter communication cable is loose. 1. Check if the meter is connected to the master. 2. Check if the meter communication cable is loose. Master AC On Meter Comm Error Parallel Slave Meter Error Meter connected to a slave unit. Set the unit with the meter connected as the master. 1. Slave address setting error. 2. Slave communication cable loose. 1. Check if the slave addresses are duplicated. 2. Check if the parallel communication cable is loose. Slave AC On Timeout with Master 8.5.2.3 Battery Fault Lynx C Series 60kWh Commercial & Industrial Battery System • No. Fault Name Possible Cause Troubleshooting Continuing to charge when the battery is fully charged Stop charging. If not automatically restored, contact a professional technician to restart the system. 1 Battery Over Voltage 263
No. Fault Name Possible Cause Troubleshooting 2 Battery Undervoltage 3 Battery Overcurrent 4 Battery Overtemperatu re 5 Battery Undertemperature 6 Battery Terminal Overtemperature 7 Battery Imbalance 8 Insulation Resistance 9 Precharge Failure 10 Harness Fault 11 Relay Open Circuit Relay Failure Replace the relay. Continuing to discharge when the battery is fully discharged Stop discharging. If not automatically restored, contact a professional technician to restart the system. Current exceeding the system's maximum current during charge/discharge Reduce power. If not automatically restored, contact a professional technician to restart the system. Perform cooling. If not automatically restored, contact a professional technician to restart the system. Temperature too high during charge/discharge Perform heating. If not automatically Temperature too low restored, contact a professional technician during charge/discharge to restart the system. Perform cooling. If not automatically Temperature too high restored, contact a professional technician during charge/discharge to restart the system. Excessive temperature or Stop charge/discharge to allow voltage difference temperature recovery. Perform balancing between individual cells if voltage difference is excessive. System insulation Check grounding condition. resistance is low Precharge circuit Check precharge circuit components. component damage Abnormal voltage, temperature, or current Check the corresponding harness. sensing harness 264
No. Fault Name Possible Cause Troubleshooting 12 Relay Short Circuit Relay Failure Replace the relay. 13 Cluster Parallel Fault 14 PCS Comm Loss 15 BMU Communication Fault 16 Circuit Breaker Sticking Fault 17 Fire Protection System Triggered 18 Air Conditioner Failure BAT-S Series 15.3-56.3kWh High Voltage Battery • No. Fault Name Possible Causes Troubleshooting 1 Charging Overvoltage2 Slave cluster loss of Check the reliability of the master-slave communication harness connection. Abnormal communication harness with PCS Check the reliability of the harness connection. Abnormal communication harness between BCU and BMU Check the reliability of the harness connection. Molded case circuit breaker failure Replace the molded case circuit breaker. Thermal runaway inside the system Please contact the after-sales service center. Abnormal fault occurred within the air conditioning system Please contact the after-sales service center. 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; Cell voltage/total voltage too high • Voltage sampling line abnormal • 2. If the fault is not resolved, contact GoodWe after-sales service. 265
No. Fault Name Possible Causes Troubleshooting 2 Charging Overvoltage3 3 Discharge Undervoltage3 4 Discharge Undervoltage2 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; Cell voltage/total voltage too high • Voltage sampling line abnormal • 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; 2. Determine the inverter's working status, check if it is not charging the battery due to working mode or other issues. Try charging the battery via the inverter and observe if the fault is resolved. Cell voltage/total voltage too low • Voltage sampling line abnormal • 3. If the fault is not resolved, contact GoodWe after-sales service. 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; 2. Determine the inverter's working status, check if it is not charging the battery due to working mode or other issues. Try charging the battery via the inverter and observe if the fault is resolved. Cell voltage/total voltage too low • Voltage sampling line abnormal • 3. If the fault is not resolved, contact GoodWe after-sales service. 266
No. Fault Name Possible Causes Troubleshooting 5 Cell Overvoltage2 6 Cell Undervoltage2 Cell undervoltage 7 Significant Cell Voltage Variation2 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; Cell voltage/total voltage too high • Voltage sampling line abnormal • If the fault is not resolved, contact GoodWe after-sales service. 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; 2. Determine the inverter's working status, check if it is not charging the battery due to working mode or other issues. Try charging the battery via the inverter and observe if the fault is resolved. 3. If the fault is not resolved, contact GoodWe after-sales service. Restart the battery and wait for 12 hours. 1. Significant cell voltage variation 2. If the fault is not resolved, contact GoodWe after-sales service. 267
No. Fault Name Possible Causes Troubleshooting 8 Charging Overcurrent2 9 Discharge Overcurrent2 10 Battery Cell High Temperature2 • Charging current too high, battery current limiting abnormal: sudden changes in temperature and voltage values 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; 2. Check if the inverter power setting is too high, causing it to exceed the battery's rated operating current; Inverter response abnormal • 3. If the fault is not resolved, contact GoodWe after-sales service. • Discharge current too high, battery current limiting abnormal: sudden changes in temperature and SOC values Inverter response abnormal • 1. Power off and let it sit for 30 minutes, then restart to see if the fault persists; Cell temperature too high • Temperature sensor abnormal • 2. If the fault is not resolved, contact GoodWe after-sales service. 268
No. Fault Name Possible Causes Troubleshooting 11 Battery Cell Low Temperature2 12 Charging Overtemperatu re2 13 Charging Low Temperature2 14 Discharge Overtemperatu re2 1. Power off and let it sit for 30 minutes, then restart to see if the fault persists; • Ambient temperature too low 2. If the fault is not resolved, contact GoodWe after-sales service. Temperature sensor abnormal • 1. Power off and let it sit for 30 minutes; then restart to see if the fault persists; Cell temperature too high • Temperature sensor abnormal • 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Power off and let it sit for 30 minutes; then restart to see if the fault persists; • Ambient temperature too low 2. If the fault is not resolved, contact GoodWe after-sales service. Temperature sensor abnormal • 1. Power off and let it sit for 30 minutes; then restart to see if the fault persists; Cell temperature too high • Temperature sensor abnormal • 2. If the fault is not resolved, contact GoodWe after-sales service. 269
No. Fault Name Possible Causes Troubleshooting 15 Discharge Low Temperature2 16 Significant Cell Temperature Variation2 17 Precharge Disabled 18 Battery Tripping Battery Trip 1. Power off and let it sit for 30 minutes; then restart to see if the fault persists; • Ambient temperature too low 2. If the fault is not resolved, contact GoodWe after-sales service. Temperature sensor abnormal • 1. Power off and let it sit for 30 minutes; then restart to see if the fault persists; Significant cell temperature variation 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Power off and let it sit for 5 minutes, then restart to see if the fault persists; Precharge MOS closure failure 2. If the fault is not resolved, contact GoodWe after-sales service. Let it sit for 10 minutes, then re- close to recover; 1. 2. If the fault is not resolved, contact GoodWe after-sales service. 270
No. Fault Name Possible Causes Troubleshooting 19 Battery and Inverter Comm Failure 20 Specific Failures 21 Cluster Parallel Fault 22 Application Software Fault 23 Microelectronic s Fault 24 Master Control Overload 25 SN Abnormal Batteries with identical SN exist 26 Circuit Breaker Abnormal BAT-C Series 61.4-112.6kWh Commercial & Industrial Battery System • 1. Confirm the communication cable wiring sequence and DC cable are correct, and check for continuity. Battery and Inverter Comm Failure Restart the inverter and battery. 2. 3. If the fault is not resolved, contact GoodWe after-sales service. Battery specific failure Please contact the after-sales service center. Check the reliability of the master- slave harness communication connection; Please contact the after-sales service center. Slave cluster loss of communication Cluster parallel failure Software self-test failure Please contact the after-sales service center. Electronic component failure Please contact the after-sales service center. Stop charging. If it does not recover automatically, please contact a professional technician to restart the system. Exceeds power line capacity range Please contact the after-sales service center. Molded case circuit breaker abnormal trip Replace the molded case circuit breaker. 271
No. Fault Name Possible Cause Troubleshooting 1 Charging Overvoltage2 2 Charging Overvoltage3 3 Discharge Undervoltage3 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; • Excessive cell voltage/total voltage 2. If the fault is not resolved, contact GoodWe after-sales service. Abnormal voltage sensing line • 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; • Excessive cell voltage/total voltage 2. If the fault is not resolved, contact GoodWe after-sales service. Abnormal voltage sensing line • 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; 2. Determine the inverter's working status, check if it is not charging the battery due to issues like working mode, and try charging the battery via the inverter to observe if the fault is resolved. • Insufficient cell voltage/total voltage Abnormal voltage sensing line • 3. If the fault is not resolved, contact GoodWe after-sales service. 272
No. Fault Name Possible Cause Troubleshooting 4 Discharge Undervoltage2 5 Cell Overvoltage2 6 Cell Undervoltage2 Cell undervoltage 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; 2. Determine the inverter's working status, check if it is not charging the battery due to issues like working mode, and try charging the battery via the inverter to observe if the fault is resolved. • Insufficient cell voltage/total voltage Abnormal voltage sensing line • 3. If the fault is not resolved, contact GoodWe after-sales service. 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; • Excessive cell voltage/total voltage Abnormal voltage sensing line • If the fault is not resolved, contact GoodWe after-sales service. 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; 2. Determine the inverter's working status, check if it is not charging the battery due to issues like working mode, and try charging the battery via the inverter to observe if the fault is resolved. 3. If the fault is not resolved, contact GoodWe after-sales service. 273
No. Fault Name Possible Cause Troubleshooting 7 Significant Cell Voltage Variation2 8 Charging Overcurrent2 9 Discharge Overcurrent2 10 Battery Cell High Temperature2 Restart the battery and wait for 12 hours. 1. Significant cell voltage variation 2. If the fault is not resolved, contact GoodWe after-sales service. • Excessive charging current, abnormal battery current limiting: Sudden changes in temperature and voltage values 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; Abnormal inverter response • 2. Check if the inverter is set to an excessive power level, causing it to exceed the battery's rated operating current; • Excessive discharge current, abnormal battery current limiting: Sudden changes in temperature and SOC values 3. If the fault is not resolved, contact GoodWe after-sales service. Abnormal inverter response • 1. Leave the unit powered off and idle for 30 minutes, then restart and check if the fault persists; Excessive cell temperature • • Abnormal temperature sensor 2. If the fault is not resolved, contact GoodWe after-sales service. 274
No. Fault Name Possible Cause Troubleshooting 11 Battery Cell Low Temperature2 12 Charging Overtemperatu re2 13 Charging Low Temperature2 14 Discharge Overtemperatu re2 • Excessively low ambient temperature 1. Leave the unit powered off and idle for 30 minutes, then restart and check if the fault persists; • Abnormal temperature sensor 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Leave the unit powered off and idle for 30 minutes; then restart and check if the fault persists; Excessive cell temperature • • Abnormal temperature sensor 2. If the fault is not resolved, contact GoodWe after-sales service. • Excessively low ambient temperature 1. Leave the unit powered off and idle for 30 minutes; then restart and check if the fault persists; • Abnormal temperature sensor 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Leave the unit powered off and idle for 30 minutes; then restart and check if the fault persists; Excessive cell temperature • • Abnormal temperature sensor 2. If the fault is not resolved, contact GoodWe after-sales service. 275
No. Fault Name Possible Cause Troubleshooting 15 Discharge Low Temperature2 16 Significant Cell Temperature Variation2 17 Precharge Disabled 18 Battery Tripping Battery Trip • Excessively low ambient temperature 1. Leave the unit powered off and idle for 30 minutes; then restart and check if the fault persists; • Abnormal temperature sensor 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Leave the unit powered off and idle for 30 minutes; then restart and check if the fault persists; Significant cell temperature variation 2. If the fault is not resolved, contact GoodWe after-sales service. 1. Leave the unit powered off and idle for 5 minutes, then restart and check if the fault persists; Precharge MOS closing failure 2. If the fault is not resolved, contact GoodWe after-sales service. Leave idle for 10 minutes, then re-close to recover; 1. 2. If the fault is not resolved, contact GoodWe after-sales service. 276
No. Fault Name Possible Cause Troubleshooting 19 Battery and Inverter Comm Failure 20 Specific Failures 21 Cluster Parallel Failure 22 Application Software Failure 23 Microelectronic Failure 24 Main Control Overload 25 SN Anomaly Existence of batteries with identical SN 26 Circuit Breaker Anomaly 1. Confirm the communication cable wiring sequence and DC cable are correct, and check for continuity. Battery and Inverter Comm Failure Restart the inverter and the battery. 2. 3. If the fault is not resolved, contact GoodWe after-sales service. Battery specific failure Please contact the after-sales service center. Check the reliability of the master- slave harness communication connection Please contact the after-sales service center. Slave cluster loss of communication Cluster parallel failure Software self-test failure Please contact the after-sales service center Electronic component failure Please contact the after-sales service center Stop charging. If it does not recover automatically, please contact a professional technician to restart the system. Exceeding the power line's load capacity Please contact the after-sales service center Molded case circuit breaker abnormal trip Replace the molded case circuit breaker 277
No. Fault Name Possible Cause Troubleshooting 27 Circuit Breaker Welding Fault 28 Fire Suppression System Triggered 29 Air Conditioner Fault 30 Door Access Fault 31 Emergency Stop Triggered 32 PACK Fan Fault PACK fan locked rotor or unable to operate 8.5.3 Post-Fault Clearance Processing In an energy storage system, after certain faults are handled, additional processing is required for the system to resume normal operation. 8.5.3.1 Clear AFCI Fault Warning Molded case circuit breaker fault or auxiliary circuit breaker fault Replace the molded case circuit breaker or replace the auxiliary circuit breaker Internal system thermal runaway or accidental fire suppression trigger Please contact the after-sales service center Abnormal fault occurred within the air conditioning system Please contact the after-sales service center Door abnormally opened or door access sensor damaged Close the door or replace the door access sensor Emergency stop pressed or emergency stop button damaged Replace the emergency stop button Replace the corresponding PACK fan 278
Software Used: SolarGo APP Clear Method: Via [Home] > [Settings] > [Advanced Settings] > [DC Arc Detection]. 1. Click the [Clear AFCI Fault Alarm] button. 2. 279
9 technical parameter 9.1 Inverter Parameters Technical Data GW15K- ET Battery Input Data Battery Type Li-Ion Li-Ion Li-Ion Li-Ion Li-Ion Nominal Battery Voltage (V) 500 500 500 500 500 Battery voltage range (V) 200~800 200~800 200~800 200~800 200~800 Start-up Voltage (V) 200 200 200 200 200 Number of Battery Input 1 1 2 2 2 Max. Continuous Charging Current (A) 50 50 50×2 50×2 50×2 Max. Continuous Discharging Current (A) 50 50 50×2 50×2 50×2 Max Charge Power (W) 15000 20000 25000 30000 30000 Max Discharge Power (W) 15000 20000 25000 30000 30000 PV String Input Data Max. Input Power (W)*1 22500 30000 37500 45000 45000 Max. Input Voltage (V)*2 1000 1000 1000 1000 1000 MPPT Operating Voltage Range (V) 200~850 200~850 200~850 200~850 200~850 MPPT Voltage Range at Nominal Power (V) 400~850 400~850 450~850 450~850 450~850 Start-up Voltage (V) 200 200 200 200 200 GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET 280
Technical Data GW15K- ET Nominal Input Voltage (V) 620 620 620 620 620 Max. Input Current per MPPT (A) 30 30 30 30 30 Max. Short Circuit Current per MPPT (A) 38 38 38 38 38 Max. Backfeed Current to The Array (A) 0 0 0 0 0 Number of MPPT 2 2 3 3 3 Number of Strings per MPPT 2/2 2/2 2/2/2 2/2/2 2/2/2 AC Output Data (On-grid) Nominal Output Power (W) 15000 20000 25000 29900 30000 Max. Output Power (W) 15000 20000 25000 29900 30000 Nominal Output Power at 40 ℃(W) *14 15000 20000 25000 29900 30000 Max. Output Power at 40 ℃ (W)*14 15000 20000 25000 29900 30000 Nominal Apparent Power Output to Utility Grid (VA) 15000 20000 25000 29900 30000 Max. Apparent Power Output to Utility Grid (VA)*3 *15 16500 22000 27500 29900 33000 Nominal Apparent Power from Utility Grid(VA) 15000 20000 25000 30000 30000 Max. Apparent Power from Utility Grid (VA) *12 15000 20000 25000 30000 30000 GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET 281
Technical Data GW15K- ET Nominal Output Voltage (V) 380/400, 3L/N/PE 380/400, 3L/N/PE 380/400, 3L/N/PE 380/400, 3L/N/PE 380/400, 3L/N/PE Output Voltage Range (V)*4 0~300 0~300 0~300 0~300 0~300 Nominal AC Grid Frequency (Hz) 50/60 50/60 50/60 50/60 50/60 AC Grid Frequency Range (Hz) 45~65 45~65 45~65 45~65 45~65 Max. AC Current Output to Utility Grid (A) *11 23.9 31.9 39.9 43.3 47.8 Max. AC Current From Utility Grid (A) *13 22.7 30.3 37.9 45.3 45.5 Nominal AC Current From Utility Grid (A) Max. Output Fault Current (Peak and Duration) (A) Inrush Current (Peak and Duration) (A) Nominal Output Current (A)*5 21.7 29 36.2 43.3 43.5 GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET 21.7 @230V 22.7 @220V 29.0 @230V 30.3 @220V 36.2 @230V 37.9 @220V 43.3 @230V 45.3 @220V 43.5 @230V 45.5 @220V 241.5A@ 126ms 241.5A@ 126ms 241.5A@ 126ms 241.5A@ 126ms 241.5A@ 126ms 264A@5 3us 264A@5 3us 264A@5 3us 264A@5 3us 264A@5 3us 282
Technical Data GW15K- ET Power Factor Max. Total Harmonic Distortion ≤3.05% ≤3.05% ≤3.05% ≤3.05% ≤3.05% Maximum Output Overcurrent Protection (A) 94 94 94 94 94 AC Output Data (Back-up) Back-up Nominal Apparent Power (VA) 15000 20000 25000 29900 30000 Max. Output Apparent Power without Grid(VA)*6 Max. Output Apparent Power with Grid (VA) 15000 20000 25000 29900 30000 Nominal Output Current (A) 22.7 30.3 37.9 45.5 45.5 Max. Output Current (A) Max. Output Fault Current (Peak and Duration) (A) 94 94 94 94 94 GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET ~1 (Adjusta ble from0.8 leading~ 0.8 lagging ) ~1 (Adjusta ble from0.8 leading~ 0.8 lagging ) ~1 (Adjusta ble from0.8 leading~ 0.8 lagging ) ~1 (Adjusta ble from0.8 leading~ 0.8 lagging ) ~1 (Adjusta ble from0.8 leading~ 0.8 lagging ) 15,000(1 8,000@6 0s , 24,000@ 3s) 20,000(2 4,000@6 0s , 32,000@ 3s) 25,000(3 0,000@6 0s) 30,000(3 6,000@6 0s) 30,000(3 6,000@6 0s) 22.7(27.3 @60s, 36.4@3s) 30.3(36.4 @60s, 48.5@3s) 37.9(45.5 @60s) 45.5(54.5 @60s) 45.5(54.5 @60s) 283
Technical Data GW15K- ET Inrush Current (Peak and Duration) (A) Maximum Output Overcurrent Protection (A) 94 94 94 94 94 Nominal Output Voltage (V) 380/400 380/400 380/400 380/400 380/400 Nominal Output Frequency (Hz) 50/60 50/60 50/60 50/60 50/60 Output THDv (@Linear Load) <3% <3% <3% <3% <3% Efficiency Max. Efficiency 98.0% 98.0% 98.0% 98.0% 98.0% European Efficiency 97.5% 97.5% 97.5% 97.5% 97.5% Max. Battery to AC Efficiency 97.5% 97.5% 97.5% 97.5% 97.5% MPPT Efficiency 99.9% 99.9% 99.9% 99.9% 99.9% Protection PV String Current Monitoring PV Insulation Resistance Detection Residual Current Monitoring PV Reverse Polarity Protection Battery Reverse Polarity Protection GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET 264@53 us 264@53 us 264@53 us 264@53 us 264@53 us Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed 284
Technical Data GW15K- ET Anti-islanding Protection Integrat ed AC Overcurrent Protection Integrat ed AC Short Circuit Protection Integrat ed AC Overvoltage Protection Integrat ed DC Switch*7 Integrat ed DC Surge Protection Type II Type II Type II Type II Type II AC Surge Protection Type III Type III Type III Type III Type III AFCI*16 Optional Optional Optional Optional Optional Rapid Shutdown Optional Optional Optional Optional Optional Remote Shutdown Integrat ed General Data Operating Temperature Range (℃) -35~+60 -35~+60 -35~+60 -35~+60 -35~+60 Operating Environment Outdoor Outdoor Outdoor Outdoor Outdoor Relative Humidity 0~95% 0~95% 0~95% 0~95% 0~95% Max. Operating Altitude (m) 4000 4000 4000 4000 4000 Cooling Method GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Integrat ed Smart Fan Cooling Smart Fan Cooling Smart Fan Cooling Smart Fan Cooling Smart Fan Cooling 285
Technical Data GW15K- ET Display Communication with BMS RS485 / CAN Communication with Meter RS485 RS485 RS485 RS485 RS485 Communication with Portal Weight (kg) 48 48 54 54 54 Dimension W×H×D (mm) 520×660 ×220 Noise Emission (dB) <45 <45 <45 <60 <60 Topology Non- isolated Self-consumption at Night (W) *8 <15 <15 <15 <15 <15 Ingress Protection Rating IP66 IP66 IP66 IP66 IP66 DC Connector AC Connector OT OT OT OT OT Environmental Category 4K4H 4K4H 4K4H 4K4H 4K4H Pollution Degree III III III III III Overvoltage Category DC II / AC III GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET LED, WLAN+A PP LED, WLAN+A PP LED, WLAN+A PP LED, WLAN+A PP LED, WLAN+A PP RS485 / CAN RS485 / CAN RS485 / CAN RS485 / CAN WiFi+LA N+Bluet ooth WiFi+LA N+Bluet ooth WiFi+LA N+Bluet ooth WiFi+LA N+Bluet ooth WiFi+LA N+Bluet ooth 520×660 ×220 520×660 ×220 520×660 ×220 520×660 ×220 Non- isolated Non- isolated Non- isolated Non- isolated Stäubli Electrical Connect ors AG Stäubli Electrical Connect ors AG Stäubli Electrical Connect ors AG Stäubli Electrical Connect ors AG Stäubli Electrical Connect ors AG DC II / AC III DC II / AC III DC II / AC III DC II / AC III 286
Technical Data GW15K- ET Protective Class I I I I I Storage Temperature (℃) -45~+85 -45~+85 -45~+85 -45~+85 -45~+85 The Decisive Voltage Class (DVC) Mounting Method Active Anti-islanding Method Type of Electrical Supply System Country of Manufacture China China China China China *1: In Australia, for most PV modules, the max. input power can achieve 2*Pn. For example, the max. input power of the GW15K-ET can achieve 30000W. Additionally, the Max. Input Power is not continuous for 1.5*normal power. *2: For a 1000V system, the maximum operating voltage is 950V. *3: According to local grid regulations. *4: Output Voltage Range: phase voltage. *5: For a 380V grid, the Nominal Output Current is 22.7A for GW15K-ET, 30.3A for GW20K-ET, 37.9A for GW25K-ET, 45.3A for GW29.9K-ET, and 45.5A for GW30K-ET. *6: Can only be reached if PV and battery power are sufficient. *7: DC Switch: GHX6-55P (for Australia). *8: No Backup Output. *9: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive Feedback. *10: Not all certifications & standards are listed; check the official website for details. GW20K- ET GW25K- ET GW29.9 K-ET GW30K- ET Battery :C PV:C AC:C Com:A Battery :C PV:C AC:C Com:A Battery :C PV:C AC:C Com:A Battery :C PV:C AC:C Com:A Battery :C PV:C AC:C Com:A Wall Mounted Wall Mounted Wall Mounted Wall Mounted Wall Mounted AFDPF + AQDPF *9 AFDPF + AQDPF *9 AFDPF + AQDPF *9 AFDPF + AQDPF *9 AFDPF + AQDPF *9 Three phase Grid Three phase Grid Three phase Grid Three phase Grid Three phase Grid 287
*11: For a 380V grid, the Max. AC Current Output to Utility Grid is 25A for GW15K-ET, 33.3A for GW20K-ET, 41.7A for GW25K-ET, 49.8A for GW29.9K-ET, and 50A for GW30K- ET. *12: When the load is connected to the inverter's backup port, the Max. Apparent Power from Utility Grid can reach 22.5kVA for GW15K-ET, 30kVA for GW20K-ET, 33kVA for GW25K-ET, 33kVA for GW29.9K-ET, and 33kVA for GW30K-ET respectively. *13: When the load is connected to the inverter's backup port, the Max. AC Current From Utility Grid can reach 34A for GW15K-ET, 45A for GW20K-ET, 50A for GW25K-ET, 50A for GW29.9K-ET, and 50A for GW30K-ET respectively. *14: Nominal Output Power at 40℃(W) and Max. Output Power at 40℃(W) are only for Brazil. *15: For Austria, Max. Output Power (W) is 15K for GW15K-ET, 20K for GW20K-ET, 25K for GW25K-ET, 29.9K for GW29.9K-ET, and 30K for GW30K-ET. *16: For Brazil, AFCI is integrated. Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Battery Input Data Battery Type Li-Ion Li-Ion Li-Ion Li-Ion Nominal Battery Voltage (V) 500 500 500 500 Battery Voltage Range (V) 112~650 112~650 200~800 200~800 Start-up Voltage (V) 112 112 180 180 Number of Battery Input 1 2 1 2 Max. Continuous Charging Current (A) 50 50*2 50 50*2 Max. Continuous Discharging Current (A) 50 50*2 50 50*2 Max Charge Power (kW) 12 18 20 30 Max Discharge Power (kW) 12 18 20 30 PV String Input Data 288
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Max. Input Power (kW) 24 36 30 45 Max. Input Voltage (V)*1 800 800 1000 1000 MPPT Operating Voltage Range (V) 200~650 200~650 200~850 200~850 MPPT Voltage Range at Nominal Power (V) 260~650 260~650 400~850 450~850 Start-up Voltage (V) 200 200 200 200 Nominal Input Voltage (V) 380 380 620 620 Max. Input Current per MPPT (A) 30 30 30 30 Max. Short Circuit Current per MPPT (A) 38 38 38 38 Max. Backfeed Current to The Array (A) 0 0 0 0 Number of MPPT Trackers 2 3 2 3 Number of Strings per MPPT 2/2 2/2/2 2/2 2/2/2 AC Output Data (On-grid) Nominal Output Power (kW) 12 18 20 30 Max. Output Power (kW) 12 18 20 30 Nominal Output Power at 40 ℃(kW) *8 12 18 20 30 Max. Output Power at 40 ℃ (kW)*8 12 18 20 30 289
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Nominal Apparent Power Output to Utility Grid (kVA) Max. Apparent Power Output to Utility Grid (kVA) 13.2 19.8 22 33 Nominal Apparent Power from Utility Grid(kVA) 12 18 20 30 Max. Apparent Power from Utility Grid (kVA) *6 12 18 20 30 Nominal Output Voltage (V) Output Voltage Range (V)*2 0~165 0~165 0~300 0~300 Nominal AC Grid Frequency (Hz) 60 60 60 60 AC Grid Frequency Range (Hz) 55~65 55~65 45~65 45~65 Max. AC Current Output to Utility Grid (A) 34.6 52 33.3 50 Max. AC Current From Utility Grid (A) *7 31.5 47 30.3 45.5 Nominal AC Current From Utility Grid (A) 31.5 47 30.3 45.5 Max. Output Fault Current (Peak and Duration) (A) Inrush Current (Peak and Duration) (A) 264A@53us 264A@53us 264A@53us 264A@53us Nominal Output Current (A) 31.5 47 30.3 45.5 12 18 20 30 220, 3L/N/PE 220, 3L/N/PE 380, 3L/N/PE 380, 3L/N/PE 241.5A@126 ms 241.5A@126 ms 241.5A@126 ms 241.5A@126 ms 290
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Power Factor Max. Total Harmonic Distortion <3% <3% <3% <3% Maximum Output Overcurrent Protection (A) AC Output Data (Back-up) Back-up Nominal Apparent Power (kVA) 12 18 20 30 Max. Output Apparent Power without Grid(kVA)*3 Max. Output Apparent Power with Grid (kVA) 12 18 20 30 Nominal Output Current (A) 31.5 47 30.3 45.5 Max. Output Current (A) 31.5(37.8@6 0s, 50.4@3s) 47(56.4@60 s) Max. Output Fault Current (Peak and Duration) (A) 94 94 94 94 Inrush Current (Peak and Duration) (A) 264@53us 264@53us 264@53us 264@53us Maximum Output Overcurrent Protection (A) ~1 (Adjustable from0.8 leading~0.8 lagging) ~1 (Adjustable from0.8 leading~0.8 lagging) ~1 (Adjustable from0.8 leading~0.8 lagging) ~1 (Adjustable from0.8 leading~0.8 lagging) 94 94 94 94 12.0(14.4@6 0s , 19.2@3s) 20.0(24.0@6 0s , 32.0@3s) 18.0(21.6@6 0s) 30.0(36.0@6 0s) 30.3(36.4@6 0s, 48.5@3s) 45.5(54.5@6 0s) 94 94 94 94 291
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Nominal Output Voltage (V) Nominal Output Frequency (Hz) 60 60 60 60 Output THDv (@Linear Load) <3% <3% <3% <3% Switching from Grid Connected Mode to Standalone Mode Switching from standalone mode to Grid connected mode Efficiency Max. Efficiency 98.0% 98.0% 98.0% 98.0% European Efficiency 97.5% 97.5% 97.5% 97.5% Max. Battery to AC Efficiency 97.5% 97.5% 97.5% 97.5% Protection PV String Current Monitoring Integrated Integrated Integrated Integrated PV Insulation Resistance Detection Integrated Integrated Integrated Integrated Residual Current Monitoring Integrated Integrated Integrated Integrated PV Reverse Polarity Protection Integrated Integrated Integrated Integrated Battery Reverse Polarity Protection Integrated Integrated Integrated Integrated 220, 3L/N/PE 220, 3L/N/PE 380, 3L/N/PE 380, 3L/N/PE 20ms 20ms 20ms 20ms 20ms 20ms 20ms 20ms 292
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Anti-islanding Protection Integrated Integrated Integrated Integrated AC Overcurrent Protection Integrated Integrated Integrated Integrated AC Short Circuit Protection Integrated Integrated Integrated Integrated AC Overvoltage Protection Integrated Integrated Integrated Integrated DC Switch Integrated Integrated Integrated Integrated DC Surge Protection Type II Type II Type II Type II AC Surge Protection Type III Type III Type III Type III AFCI Integrated Integrated Integrated Integrated Rapid Shutdown Optional Optional Optional Optional Remote Shutdown Integrated Integrated Integrated Integrated General Data Operating Temperature Range (℃) -35~+60 -35~+60 -35~+60 -35~+60 Storage Temperature (℃) -45~+85 -45~+85 -45~+85 -45~+85 Relative Humidity 0~95% 0~95% 0~95% 0~95% Max. Operating Altitude (m) 4000 4000 4000 4000 Cooling Method Smart Fan Cooling User Interface LED, WLAN+APP Communication with BMS RS485 / CAN RS485 / CAN RS485 / CAN RS485 / CAN Smart Fan Cooling Smart Fan Cooling Smart Fan Cooling LED, WLAN+APP LED, WLAN+APP LED, WLAN+APP 293
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET Communication Communication Protocols Weight (kg) 48 54 48 54 Dimension W×H×D (mm) 520×660×22 0 520×660×22 0 520×660×22 0 520×660×22 0 Noise Emission (dB) <45 <60 <45 <60 Topology Non- isolated Self-consumption at Night (W) *4 <15 <15 <15 <15 Ingress Protection Rating IP66 IP66 IP66 IP66 Anti-corrosion Class C4 C4 C4 C4 DC Connector MC4 MC4 MC4 MC4 AC Connector OT OT OT OT Environmental Category 4K4H 4K4H 4K4H 4K4H Pollution Degree III III III III Overvoltage Category DC II / AC III DC II / AC III DC II / AC III DC II / AC III Protective Class I I I I RS485, WiFi+LAN+B luetooth, 4G+Bluetoo th(Optional) RS485, WiFi+LAN+B luetooth, 4G+Bluetoo th(Optional) RS485, WiFi+LAN+B luetooth, 4G+Bluetoo th(Optional) RS485, WiFi+LAN+B luetooth, 4G+Bluetoo th(Optional) Modbus- RTU (SunSpec Compliant), Modbus- TCP Modbus- RTU (SunSpec Compliant), Modbus- TCP Modbus- RTU (SunSpec Compliant), Modbus- TCP Modbus- RTU (SunSpec Compliant), Modbus- TCP Non- isolated Non- isolated Non- isolated 294
Technical Data GW12KL-ET GW18KL-ET GW20K-ET GW30K-ET The Decisive Voltage Class (DVC) Mounting Method Wall Mounted Active Anti-islanding Method Type of Electrical Supply System Country of Manufacture China China China China *1: For a 1000V system, the maximum operating voltage is 950V. *2: Output Voltage Range: phase voltage. *3: Can only be reached if PV and battery power are sufficient. *4: No Backup Output. *5: AFDPF: Active Frequency Drift with Positive Feedback, AQDPF: Active Q Drift with Positive Feedback. *6: When the load is connected to the inverter's backup port, the Max. Apparent Power from Utility Grid can reach 18kVA for GW12KL-ET, 19.8kVA for GW18KL-ET, 30kVA for GW20K-ET, and 33kVA for GW30K-ET respectively. *7: When the load is connected to the inverter's backup port, the Max. AC Current From Utility Grid can reach 47.2A for GW12KL-ET and 52A for GW18KL-ET; and can reach 45A for GW20K-ET and 50A for GW30K-ET respectively. *8: Nominal Output Power at 40℃(W) and Max. Output Power at 40℃(W) are only for Brazil. 9.2 Battery Parameters 9.2.1 Lynx C Series 60kWh C&l Battery System Battery:C PV:C AC:C Com:A Battery:C PV:C AC:C Com:A Battery:C PV:C AC:C Com:A Battery:C PV:C AC:C Com:A Wall Mounted Wall Mounted Wall Mounted FDPF + AQDPF *5 FDPF + AQDPF *5 AFDPF + AQDPF *5 AFDPF + AQDPF *5 Three phase Grid Three phase Grid Three phase Grid Three phase Grid 295
Technical Parameters GW60KWH-D-10 GW60KWH-D- 10(EXTENSION) Battery Data Usable Energy (kWh)*1 60 Cell Type LFP (LiFePO4) Cell Capacity (Ah) 100 Pack Nominal Energy (kWh) 5.76 Number of Packs 11 Nominal Voltage (V) 633.6 Operating Voltage Range (V) 554.4~712.8 Max. Charge/ Discharge Current (A)*2 96 Max. Charge/ Discharge Rate*2 0.96C Cycle Life*3 ≥5000 Depth of Discharge 100% Efficiency Round-trip Efficiency 95% General Data Operating Temperature Range (℃) Charge: 0~+55; Discharge: -25~+55 Storage Temperature (℃) Relative Humidity 0~95% Max. Operating Altitude (m) 3000 Heating & Cooling Air Conditioner User Interface LED indicator Communication Interface CAN Communication Protocol CAN Weight (kg) appro.1029.5 appro.972 Dimension (W×H×D mm) 1108×2050× 1111.5 808×2050× 1111.5 Ingress Protection Rating IP55(Battery Cabinet) Anti-Corrosion*4 C4 (Optional upgrade to C5) Fire Suppression Perfluoro Certification*5 0~+35(<One Year);-20~0(≤One Month);+35~+40(≤One Month) 296
Technical Parameters GW60KWH-D-10 GW60KWH-D- 10(EXTENSION) Safety Regulation IEC62619/63056, IEC60730-1, IEC/EN62477-1, IEC62040-1 EMC EN IEC61000-6-1, EN IEC61000-6-2, EN IEC61000-6- 3, EN IEC61000-6-4 *1: Test conditions, 100% DOD, 0.5C charge & discharge at +25±2 °C for battery system at beginning life. System Usable Energy may vary with different Inverter. *2: Actual Dis-/Charge Current and power derating will occur related to Cell Temperature and SOC.And, Max C-rate continuous time is affected by SOC, Cell Temperature, Atmosphere environment temperature ,Air-conditioner refrigeration capacity. *3: Based on Cell test condition of 25±2℃, 0.5C/0.5C and 80% EOL. *4: Excluding locks. *5: Not all certifications & standards listed, check the official website for detail. 9.2.2 BAT-S Series 15.3-56.3kWh High Voltage Battery Technical Data GW15.3-BAT-I-G11 GW20.4-BAT-I-G11 Battery System Cell Type LFP (LiFePO4) Capacity (Ah) 100 Pack Type/model GW5.1-PACK-I-G10 Pack Nominal Energy (kWh) 5.12 Pack Configuration 1P48S 1P64S Pack Weight(kg) 42.5 Number of Packs 3 4 Nominal Energy (kWh) 15.3 20.4 Usable Energy (kWh) *1 15 20 297
Technical Data GW15.3-BAT-I-G11 GW20.4-BAT-I-G11 Nominal Voltage (V) 153.6 204.8 Operating Voltage Range (V) 137.76~173.28 183.68~231.04 Charging Operating Temperature Range(℃) 0~+55 Discharging Operating Temperature Range(℃) -20~+55 Max. Charge/ Disharge Current (A) *2 100/110 Max. Charge/ Discharge Rate *2 1C/1.1C Max. Charge/ Discharge power (kW) *2 15.3/16.8 20.4/22.4 Cycle Life 6000 (25±2°C, 0.5C, 90%DOD, 70%EOL) Depth of Discharge 100% Efficiency Round-trip Efficiency 96%@100%DOD, 0.2C, 25±2℃ General Data Operating Temperature Range (℃) 0~40℃ Storage Temperature (℃) +35~+45 (<6 Months);-20~+35 (<1 Year) Relative Humidity 5~85%, No condensation Max. Operating Altitude (m) 3000 Cooling Method Natural Cooling User Interface LED Communication CAN (RS485 Optional) 298
Technical Data GW15.3-BAT-I-G11 GW20.4-BAT-I-G11 Weight-stacked(kg) 158 203 Dimension-stacked (W×H×D mm) 481*649*552 481*787*552 Ingress Protection Rating IP20 Fire safety equipment Aerosol, Pack Level Certification*3 Safety Regulation For details, please visit our official website EMC For details, please visit our official website Note: Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system at beginning life. System Usable Energy may vary with system configuration. 1. 2. Actual Dis-/Charge Current and power derating will occur related to Cell Temperature and SOC. And, Max C-rate continuous time is affected by SOC, Cell Temperature, Atmosphere environment temperature . Not all certifications & standards listed, check the official website for detail. 3. GW25.6 -BAT-I- G10 GW30.7 -BAT-I- G10 GW35.8 -BAT-I- G10 GW40.9 -BAT-I- G10 GW46.0- BAT-I- G10 GW51.2- BAT-I- G10 GW56. 3-BAT- I-G10 Technical Data Battery System Cell Type LFP (LiFePO4) Capacity (Ah) 100 Pack Type/model GW5.1-PACK-I-G10 299
GW25.6 -BAT-I- G10 GW30.7 -BAT-I- G10 GW35.8 -BAT-I- G10 GW40.9 -BAT-I- G10 GW46.0- BAT-I- G10 GW51.2- BAT-I- G10 GW56. 3-BAT- I-G10 Technical Data Pack Nominal Energy (kWh) 5.12 Pack Configuratio n 1P80S 1P96S 1P112S 1P128S 1P144S 1P160S 1P176S Pack Weight (kg) 42.5 Number of Packs 5 6 7 8 9 10 11 Nominal Energy (kWh) 25.6 30.7 35.8 40.9 46 51.2 56.3 Usable Energy (kWh) *1 25 30 35 40 45 50 55 Nominal Voltage (V) 256 307.2 358.4 409.6 460.8 512 563.2 Operating Voltage Range (V) 505.12 ~635.3 6 229.6~2 88.8 275.52~ 346.56 321.44~ 404.32 367.36~ 462.08 413.28~ 519.84 459.2~5 77.6 Charging Operating Temperatur e Range (℃) 0~+55 300
GW25.6 -BAT-I- G10 GW30.7 -BAT-I- G10 GW35.8 -BAT-I- G10 GW40.9 -BAT-I- G10 GW46.0- BAT-I- G10 GW51.2- BAT-I- G10 GW56. 3-BAT- I-G10 Technical Data Discharging Operating Temperatur e Range (℃) -20~+55 Max. Charge/Disc harge Current (A) *2 100/110 Max. Charge/Disc harge Rate *2 1C/1.1C Max. Charge/Disc harge Power (kW) *2 25.6/28. 1 30.7/33. 7 35.8/39. 4 40.9/44. 9 46.0/50. 6 51.2/56. 3 56.3/61 .9 Cycle Life 6000 (25±2°C, 0.5C, 90% DOD, 70% EOL) Depth of Discharge 1 Efficiency Round-trip Efficiency 96%@100%DOD, 0.2C, 25±2℃ General Data Operating Temperatur e Range (℃) 0~40℃ 301
GW25.6 -BAT-I- G10 GW30.7 -BAT-I- G10 GW35.8 -BAT-I- G10 GW40.9 -BAT-I- G10 GW46.0- BAT-I- G10 GW51.2- BAT-I- G10 GW56. 3-BAT- I-G10 Technical Data Storage Temperatur e (℃) +35°C to +45°C (<6 Months); -20°C to +35°C (<1 Year) Relative Humidity 5-85%, no condensation Max. Operating Altitude (m) 3000 Cooling Method Natural Cooling User Interface LED Communicat ion CAN (RS485 Optional) Weight-rack mounted (kg) - - - - - 495 540 Weight- stacked (kg) 248 293 338 383 428 472 517 Dimension- rack mounted (W×H×D mm) - - - - - 543*1815*520 Dimension- stacked (W×H×D mm) 481*92 5*552 481*10 63*552 481*120 1*552 481*133 9*552 481*147 7*552 481*161 5*552 481*17 53*552 302
GW25.6 -BAT-I- G10 GW30.7 -BAT-I- G10 GW35.8 -BAT-I- G10 GW40.9 -BAT-I- G10 GW46.0- BAT-I- G10 GW51.2- BAT-I- G10 GW56. 3-BAT- I-G10 Technical Data Ingress Protection Rating IP20 Fire safety equipment Aerosol, Pack Level Certification *3 Safety Regulation For details, please visit our official website EMC For details, please visit our official website Note: 1. Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system at beginning life. System Usable Energy may vary with system configuration. 2. Actual Dis-/Charge Current and power derating will occur related to Cell Temperature and SOC. And, Max C-rate continuous time is affected by SOC, Cell Temperature, Atmosphere environment temperature . Not all certifications & standards listed, check the official website for detail. 3. 9.2.3 BAT-C Series 61.4-112.6kWh C&I Battery System GW92.1-BAT- AC-G10 GW102.4-BAT- AC-G10 GW112.6-BAT- AC-G10 Technical Data GW61.4-BAT- AC-G10 Battery System Cell Type LFP (LiFePO4) Cell Capacity (Ah) 100 303
Technical Data GW61.4-BAT- AC-G10 Rated Capacity (Ah) 200 Pack Type/model GW10.2-PACK-ACI-G10 Pack Nominal Energy (kWh) 10.24 Pack Configuration 2P96S 2P144S 2P160S 2P176S Pack Weight(kg) <90 Number of Packs 6 9 10 11 Nominal Energy (kWh) 61.4 92.1 102.4 112.6 Usable Energy (kWh) *1 60 90 100 110 Nominal Voltage (V) 307.2 460.8 512 563.2 Operating Voltage Range (V) Charging Operating Temperature Range(℃) Discharging Operating Temperature Range(℃) GW92.1-BAT- AC-G10 GW102.4-BAT- AC-G10 GW112.6-BAT- AC-G10 275.52~346.5 6 413.28~519.8 4 459.2~577.6 505.12~635.36 -20~+55 -20~+55 304
Technical Data GW61.4-BAT- AC-G10 Max. Charge/ Discharge Current (A) *2 Rated Charge/ Discharge Current (A) *2 Max. Charge/ Discharge Rate *2 0.9C/1.1C Max. Charge/ Discharge power (kW) *2 Rated Charge/ Discharge power (kW) *2 Cycle Life*3 ≥6000 times until 70% SOH under 25±2°C.0.5C and 100% DOD Depth of Discharge 100% Efficiency Round-trip Efficiency*3 96%@100%DOD, 0.2C, 25±2℃ General Data Operating Temperature Range (℃) Storage Temperature (℃) +35~+45 (<6 Months); -20~+35 (<1) Relative Humidity 0~100%(Condensationless) GW92.1-BAT- AC-G10 GW102.4-BAT- AC-G10 GW112.6-BAT- AC-G10 180/220 100/100 55.2/67.5 82.9/101.3 92.1/112.6 101.3/123.9 30.7 46.0 51.2 56.3 -20~+55 305
Technical Data GW61.4-BAT- AC-G10 Max. Operating Altitude (m) 4000 Cooling Method Air Conditioner User Interface LED Communication CAN (RS485 Optional) Weight (kg) <950 <1220 <1310 <1400 Dimension (W×H×Dmm) 1055*2000*1055 Noise Emission (dB) ≤70 Ingress Protection Rating IP55 IP55 IP55 IP55 Anti-corrosion Class C4(C5-M Optional) Fire safety equipment*4 Aerosol (Pack&Cabinet Level) Certification *5 Safety Regulation IEC62619/IEC63056/IEC60730/IEC62477/VDE2510/ISO13849 IEC62040/N140/EU 2023/1542/UN38.3 EMC IEC/EN61000-6-1/2/3/4 GW92.1-BAT- AC-G10 GW102.4-BAT- AC-G10 GW112.6-BAT- AC-G10 306
GW92.1-BAT- AC-G10 GW102.4-BAT- AC-G10 Technical Data GW61.4-BAT- AC-G10 Note: 1. Test conditions, 100% DOD, 0.2C charge & discharge at +25±2 °C for battery system at beginning life. System Usable Energy may vary with system configuration. 2. Actual Dis-/Charge Current and power derating will occur related to Cell Temperature and SOC. And, Max C-rate continuous time is affected by SOC, Cell Temperature, Atmosphere environment temperature. Rated Charge/ Discharge Current & Rated Charge/ Discharge power only for Australia. For Australian DOD is 98%. 3. Aerosol (Cabinet Level) before May 30th,Aerosol (Pack&Cabinet Level) after May 30th. 4. Not all certifications & standards listed, check the official website for detail. 5. 9.3 Smart Meter Technical Data 9.3.1 GM330 technical parameter GM330 Supported Grid Type Three-phase, split-phase, single-phase voltage Range L-L (Vac) 172~817 voltage Range L-N (Vac) 100~472 Nominal Frequency (Hz) 50/60 Measurement Range CT ratio nA:5A Communication Method RS485 Communication Parameters Communication Distance (m/ft) 1000/3280 voltage/current Class 0.5 Active Energy Class 0.5 Accuracy Parameters Reactive Energy Class 1 307 GW112.6-BAT- AC-G10
technical parameter GM330 Dimensions(WxHxDmm/in) 72x85x72/2.83x3.35×2.83 General Parameters Housing 4-module Weight (g/Ib) 240/0.53 Mounting Method DIN rail User Interface 4 LEDs, Reset Button Power Consumption (W) ≤5 IP Rating IP20 Operating Temperature Range (℃/°F) -30~+70/-22~+158 Storage Temperature Range(℃/°F) -30~70/-22~+158 Environmental Parameters Relative Humidity (non- condensing) 0~95% Max. Operating Altitude (m/ft) 3000/9842 Certification Parameters Certification UL1741/ANSI 9.3.2 GM3000 Technical Parameter GM3000 Application Three-phase Voltage Nominal Voltage 3L+N/400V Voltage Range 100V~240V Frequency 50Hz/60Hz Rated Current CT in: 120A/40mA; Current Current Range 0.48A~120A Power Consumption <3W Data Detection Voltage/Current/Active Power/Reactive Power/Power Energy Calculation Active/Reactive Power Voltage/Current Class I Accuracy Factor/Frequency 308
Active Class I Reactive Class II Communication RS485 (Max. Speed 9600/ModBus Protocol/Max. Cable Display LED, USB, Reset Button Device Dimensions (L x W x H mm) Weight (g) 450 Ingress Protection Rating Mounting Method Back Plate Mounting Operating Temperature -25 ~ +60° C Storage Temperature -25 ~ +60° C Humidity <95% Non-condensing Operating Altitude(m) < 2000m Safe Service Life (Years) ≥25 9.3.3 GMK330 model GMK330 Measurement Range Supported Grid Type 1P2W/3P3W/3P4W Operating voltage (Vac)* 3P4W:90~264 L-N 3P3W:90~264 L-L Frequency (Hz) 50/60 CT ratio 120A: 40mA 200A: 50mA* Number of CTs 3 Accuracy Parameters voltage/current Class 0.5 Active Energy Class 0.5 Length 100m) 36 x 85 x 66.5 IP20(Indoor) 309
model GMK330 Reactive Energy Class 1 Communication Parameters Communication Method RS485 Communication Distance (m) 1000 General Parameters Dimensions (W*H*D mm) 72*85*72 Housing 4模 Weight (g) 240 Mounting Method DIN Rail User Interface 4 LEDs, Reset Button Power Consumption (W) <5 Environmental Parameters IP Rating IP20 Operating Temperature Range (℃) -30-+70 Storage Temperature Range (℃) -30-+70 Relative Humidity (non- condensing) 0-95% Max. Operating Altitude (m) 3000 *Supports 1.1 times rated voltage input. *The standard CT for the meter has been uniformly updated to the 120A:40mA specification. Meters equipped with the 200A:50mA CT will no longer be sold after June 2026. 310
9.4 Smart Dongle Technical Data 9.4.1 4G Kit-CN-G21 Product Model 4G Kit-CN-G21 Device Management Max. Supported Inverter Quantity 1 Electrical Specifications Input Voltage (V) 5 Power Consumption (W) ≤4 Interface Type USB Communication Specifications 4G/3G/2G LTE-FDD:B1/B3/B5/B8 LTE-TDD:B34/B39/B40/B41 GNSS Positioning BeiDou, GPS Bluetooth Bluetooth V5.0 Mechanical Specifications Dimensions (W×H×D mm) 48.3*95.5*32.1 Weight (g) 87 indicator LED* 2 Mounting Method Plug and Play SIM Card Size Micro sim, 15mm*12mm Environmental Specifications Operating Temperature Range (℃) -30~+65 Storage Temperature Range (℃) -40~+70 Relative Humidity 0-100% IP Rating IP66 Max. Operating Altitude (m) 4000 311
Product Model 4G Kit-CN-G21 Compliance Standards Certification SRRC、CTA 9.4.2 4G Kit-CN-G20 Product Model 4G Kit-CN-G20 Device Management Max. Supported Inverter Quantity 1 Power Parameters Input Voltage (V) 5 Power Consumption (W) ≤4 Interface Method USB Communication Parameters 4G/3G/2G LTE-FDD:B1/B3/B5/B8 LTE-TDD:B34/B39/B40/B41 GNSS Positioning / Bluetooth Bluetooth V5.0 Mechanical Parameters Dimensions (Width×Height×Thick ness mm) Weight (g) 87 indicator LED* 2 Mounting Method Plug and Play SIM Card Size Micro sim, 15mm*12mm Environmental Parameters Operating Temperature Range (℃) Storage Temperature Range (℃) Relative Humidity 0-100% 48.3*95.5*32.1 -30~+65 -40~+70 312
Product Model 4G Kit-CN-G20 IP Rating IP66 Max. Operating Altitude (m) 4000 Compliant Standards Certification SRRC, CTA 9.4.3 WiFi/LAN Kit-20 technical parameter WiFi/LAN Kit-20 Output Voltage (V) 5 Power Consumption (W) ≤2 Communication Interface USB Ethernet 10M/100Mbps Auto-negotiation Wireless IEEE 802.11 b/g/n @2.4 GHz Communication Parameters Bluetooth Bluetooth V4.2 BR/EDR and Bluetooth LE Standard Dimensions (W×H×D mm) 48.3*159.5*32.1 Mechanical Parameters Weight (g) 82 Ingress Protection Rating IP65 Mounting Method USB Port Plug/Unplug Operating Temperature Range (℃) -30~+60 Storage Temperature Range (℃) -40~+70 Relative Humidity 0-95% Max. Operating Altitude (m) 4000 9.4.4 Ezlink3000 Indicator /Silkscre en Color Status Description Flashing = The communication stick is operating normally. Blue 313
Indicator /Silkscre en Color Status Description Power Light Communi cation Light Green RELOAD - - Off = The communication stick is powered off. Steady on = The communication stick is connected to the server. Double flash = The communication stick is not connected to the router. Quadruple flash = The communication stick is connected to the router but not connected to the server. Press and hold for 1-3 seconds to restart the communication stick. • Press and hold for 6-10 seconds to restore factory settings. • Double-click quickly to enable Bluetooth signal (only maintained for 5 minutes). 314
10 Appendix 10.1 FAQ 10.1.1 How to conduct auxiliary detection for smart meters/CT? The meter detection function can check whether the meter CT is connected correctly and the current operating status of the meter and CT. Method 1: • Go to [Home] > [Settings] > [Meter/CT Auxiliary Detection] to access the detection page. 1. Click Start Detection, wait for the detection to complete, and then view the results. 2. Method 2: • Click > [System Setup] > [Quick Setting] > [Meter/CT Assisted Test] to access the detection page. 1. Click Start Detection, wait for the detection to complete, and then view the results. 2. 10.1.2 How to Upgrade the Device Version Through the firmware information, you can view or upgrade: The inverter's DSP version, ARM version, communication module software version, battery's BMS version, DCDC version, etc. Prompted Upgrade: • When the user opens the App, an upgrade prompt pops up on the home page. The user can choose whether to upgrade. If they choose to upgrade, they can complete the upgrade by following the on-screen instructions. Regular Upgrade: • Go to [Home] > [Settings] > [Firmware Information] to enter the firmware information viewing interface. Click "Check for Updates". If a new version is available, complete the upgrade by 315
following the on-screen instructions. Forced Upgrade: • The App pushes an upgrade notification. The user must upgrade as prompted; otherwise, the App cannot be used. Complete the upgrade by following the on- screen instructions. Inverter Software Version Upgrade The inverter supports software upgrade via a USB drive. • Before using a USB drive to upgrade the device, please contact the after-sales service center to obtain the software upgrade package and upgrade method. • 10.2 Abbreviations Abbreviation English Description Chinese Description Ubatt Battery Voltage Range Battery voltage range Ubatt,r Nominal Battery Voltage Nominal battery voltage Ibatt,max (C/D) Max. Charging Current Max. Discharging Current EC,R Rated Energy Rated Energy UDCmax Max.Input Voltage Max. Input Voltage UMPP MPPT Operating Voltage Range MPPT Voltage Range IDC,max Max. Input Current per MPPT Max. Input Current per MPPT ISC PV Max. Short Circuit Current per MPPT Max. Short Circuit Current per MPPT PAC,r Nominal Output Power Nominal output power Sr (to grid) Nominal Apparent Power Output to Utility Grid Smax (to grid) Max. Apparent Power Output to Utility Grid Sr (from grid) Nominal Apparent Power from Utility Grid Smax (from grid) Max. Apparent Power from Utility Grid Max. Apparent Power from Utility Grid UAC,r Nominal Output Voltage Nominal output voltage Max. Charging/Discharging Current Nominal Apparent Power Output to Utility Grid Max. Apparent Power Output to Utility Grid Nominal Apparent Power from Utility Grid 316
Abbreviation English Description Chinese Description fAC,r Nominal AC Grid Frequency Nominal AC Grid Frequency IAC,max(to grid) Max. AC Current Output to Utility Grid Max. AC Current Output to Utility Grid IAC,max(from grid) Max. AC Current From Utility Grid Max. Current from Grid P.F. Power Factor Power Factor Sr Back-up Nominal apparent power Max. Output Apparent Power (VA) Max. Output Apparent Power without Grid Smax IAC,max Max. Output Current Max. Current to Grid UAC,r Nominal Output Voltage Max. Output Voltage fAC,r Nominal Output Freqency Nominal Output Voltage Frequency Toperating Operating Temperature Range Operating Temperature Range IDC,max Max. Input Current Max. Input Current UDC Input Voltage Input Voltage UDC,r DC Power Supply DC Input UAC Power Supply/AC Power Supply Input Voltage Range/AC Input UAC,r Power Supply/Input Voltage Range Input Voltage Range/AC Input Toperating Operating Temperature Range Operating Temperature Range Pmax Max Output Power Maximum Power PRF TX Power Transmit Power PD Power Consumption Power Consumption PAC,r Power Consumption Power Consumption F (Hz) Frequency Frequency ISC PV Max. Input Short Circuit Current Udcmin-Udcmax Range of input Operating Voltage Operating Voltage range UAC,rang(L-N) Power Supply Input Voltage Adapter Input Voltage Range Off-grid Nominal Apparent Power Max. Apparent Power to Grid Max. Input Short Circuit Current 317
Abbreviation English Description Chinese Description Usys,max Max System Voltage Max. System Voltage Haltitude,max Max. Operating Altitude Max. Operating Altitude PF Power Factor Power Factor THDi Total Harmonic Distortion of Current Current Harmonic Distortion THDv Total Harmonic Distortion of Voltage Voltage Harmonic Distortion C&I Commercial & Industrial Commercial & Industrial SEMS Smart Energy Management System MPPT Maximum Power Point Tracking PID Potential-Induced Degradation Potential-Induced Degradation Voc Open-Circuit Voltage open-circuit voltage Anti PID Anti-PID Anti-PID PID Recovery PID Recovery PID Recovery PLC Power-line Commucation Power Line Carrier Communication Modbus TCP/IP Modbus Transmission Control / Internet Protocol Modbus over TCP/IP Modbus RTU Modbus Remote Terminal Unit Modbus over Serial Link SCR Short-Circuit Ratio Short-Circuit Ratio UPS Uninterruptable Power Supply Uninterruptible Power Supply ECO mode Economical Mode Economic Mode TOU Time of Use Time of Use ESS Energy Stroage System energy storage system PCS Power Conversion System Power Conversion System RSD Rapid shutdown Rapid Shutdown EPO Emergency Power Off Emergency Poweroff SPD Surge Protection Device Surge Protection zero injection/zero export Power Limit / Export Power Limit ARC DRED Demand Response Enabling Device Smart Energy Management System Maximum Power Point Tracking Power Limit Demand Response Enabling Device 318
Abbreviation English Description Chinese Description RCR Ripple Control Receiver - AFCI AFCI AFCI DC Arc Fault Protection GFCI Ground Fault Circuit Interrupter GFCI RCMU Residual Current Monitioring Unit Residual Current Monitoring Unit FRT Fault Ride Through Fault Ride Through HVRT High Voltage Ride Through High Voltage Ride Through LVRT Low Voltage Ride Through Low Voltage Ride Through EMS Energy Management System Energy Management System BMS Battery Management System Battery Management System BMU Battery Measure Unit Battery Measurement Unit BCU Battery Control Unit Battery Control Unit SOC State of Charge State of Charge SOH State of Health State of Health SOE State Of Energy State Of Energy SOP State Of Power State Of Power SOF State Of Function State Of Function SOS State Of Safety State Of Safety DOD Depth of discharge depth of discharge 10.3 Explanation of Terms • Explanation of Overvoltage Categories Overvoltage Category I: Equipment connected to circuits with measures to limit transient overvoltages to a relatively low level. ○ Overvoltage Category II: Energy-consuming equipment supplied by fixed distribution installations. This category includes appliances, portable tools, and other household and similar loads. If special requirements for reliability and suitability are imposed on such equipment, Overvoltage Category III is adopted. ○ Overvoltage Category III: Equipment in fixed distribution installations where reliability and suitability must meet special requirements. This includes switching devices in fixed distribution installations and industrial equipment permanently connected to fixed distribution installations. ○ Overvoltage Category IV: Equipment used in the power supply of distribution installations, including measuring instruments and pre-overcurrent protection devices, etc. ○ 319
Explanation of Damp Location Categories • Environmental Parameter Level 3K3 4K2 4K4H Temperature Range 0~+40℃ -33~+40℃ -33~+40℃ Humidity Range 5% to 85% 15% to 100% 4% to 100% • Explanation of Environmental Categories: Outdoor Inverter: Ambient air temperature range from -25 to +60°C, suitable for environments with Pollution Degree 3; ○ Indoor Type II Inverter: Ambient air temperature range from -25 to +40°C, suitable for environments with Pollution Degree 3; ○ Indoor Type I Inverter: Ambient air temperature range from 0 to +40°C, suitable for environments with Pollution Degree 2; ○ • Explanation of Pollution Degree Categories Pollution Degree 1: No pollution or only dry, non-conductive pollution; ○ Pollution Degree 2: Generally only non-conductive pollution, but occasional temporary conductive pollution due to condensation must be considered; ○ Pollution Degree 3: Conductive pollution exists, or non-conductive pollution becomes conductive due to condensation; ○ Pollution Degree 4: Persistent conductive pollution, such as pollution caused by conductive dust or rain/snow. ○ 10.4 Meaning of Battery SN Code Digits 11-14 of the product SN code represent the production date code. The production date in the image above is 2023-08-08. 320
Digits 11 and 12 represent the last two digits of the production year, e.g., 2023 is represented as 23; • Digit 13 represents the production month, e.g., August is represented as 8; Details are as follows: • Month Jan-Sep Oct Nov Dec Month Code 1~9 A B C • Digit 14 represents the production day, e.g., the 8th is represented as 8; Numbers are used preferentially, e.g., 1~9 represent the 1st~9th day, A represents the 10th day, and so on. The letters I and O are not used to avoid confusion. Details are as follows: Production Day 1 2 3 4 5 6 7 8 9 Code 1 2 3 4 5 6 7 8 9 Production Date 10 11 12 13 14 15 16 17 18 Code A B C D E F G H J Production Date 21 22 23 24 25 26 27 28 29 Code M N P Q R S T U V 10.5 Safety Compliance Countries No. Safety Regulation Name No. Safety Regulation Name Europe 1 IT-CEI 0-21 56 IE-LV-72A 2 IT-CEI 0-16 57 IE-ESB-C&D(<110kV) 3 DE LV with PV 58 IE-EirGrid-110kV 4 DE LV without PV 59 PT-D 5 DE-MV 60 EE 321
No. Safety Regulation Name No. Safety Regulation Name 6 ES-A 61 NO 7 ES-B 62 FI-A 8 ES-C 63 FI-B 9 ES-D 64 FI-C 10 ES-island 65 FI-D 11 BE 66 UA-A1 12 FR-LV 67 UA-A2 13 FR-island-50Hz 68 EN 50549-1 14 FR-island-60Hz 69 EN 50549-2 15 type A-PL_V.1.1 70 DK-West-B-MVHV 16 type B-LV-PL_V.1.1 71 DK-East-B-MVHV 17 type C-PL_V.1.1 72 DK-West-C-MVHV 18 type D-PL_V.1.1 73 DK-East-C-MVHV 19 NL-16/20A 74 DK-West-D-MVHV 20 NL-A 75 DK-East-D-MVHV 21 NL-B 76 FR-Reunion 22 NL-C 77 BE-LV(>30kVA) 23 NL-D 78 BE-HV 24 SE-A 79 CH-B 25 SE MV 80 NI-G99-A 26 SK-A 81 NI-G99-B 27 SK-B 82 NI-G99-C 28 SK-C 83 NI-G99-D 322
No. Safety Regulation Name No. Safety Regulation Name 29 HU 84 IE-LV-170kVA 30 CH-A 85 IE-MV&HV-200kVA 31 CY 86 DE-HV 32 GR 87 FR-MV 33 DK-West-A 88 CZ-A1/A2-09 34 DK-East-A 89 DE-EHV 35 DK-West-B 90 IE-EirGrid-400KV 36 DK-East-B 91 IE-EirGrid-220KV 37 AT<1kV 92 IE-EirGrid-66KV 38 AT>1kV 93 IE-ESB-B 39 BG 94 IE-ESB-D(≥110kV) 40 Czech 95 type B-MV-PL_V.1.1 41 CZ-A1-09 96 GB-G99-A HV 42 CZ-A2-09 97 GB-G99-B LV 43 CZ-B1/B2-09 98 GB-G99-C LV 44 CZ-C 99 UA-B 45 CZ-D 100 UA-C 46 RO-A 101 UA-D 47 RO-B 102 UK-G98 48 RO-D 103 UK-G99-A LV 49 GB-G98 104 UK-G99-B LV 50 GB-G99-A LV 105 UK-G99-C LV 51 GB-G99-B HV 106 CZ-A1 323
No. Safety Regulation Name No. Safety Regulation Name 52 GB-G99-C HV 107 UK-A-MV 53 GB-G99-D 108 UK-B-MV 54 NI-G98 109 UK-C-MV 55 IE-LV-16/25A - - Global 1 60Hz-Default 6 IEC 61727-60Hz 2 50Hz-Default 7 Warehouse 3 127Vac-60Hz-Default 8 IEC61727-480Vac-60Hz 4 127Vac-50Hz-Default 9 IEC61727-480Vac-50Hz 5 IEC 61727-50Hz Americas 1 Argentina-220V-LV 38 LUMAPR-2024-220Vac-3P 2 US-208Vac 39 LUMAPR-2024-240Vac-3P 3 US-240Vac 40 Cayman 4 Mexico-220Vac 41 Brazil-220Vac 5 Mexico-440Vac 42 Brazil-208Vac 6 US-480Vac 43 Brazil-230Vac 7 US-208Vac-3P 44 Brazil-240Vac 8 US-220Vac-3P 45 Brazil-254Vac 9 US-240Vac-3P 46 Brazil-127Vac 10 US-CA-208Vac 47 Brazil-ONS 11 US-CA-240Vac 48 Barbados 12 US-CA-480Vac 49 Chile-BT 13 US-CA-208Vac-3P 50 Chile-MT-A 324
No. Safety Regulation Name No. Safety Regulation Name 14 US-CA-220Vac-3P 51 Chile MT-B 15 US-CA-240Vac-3P 52 Colombia 16 US-HI-208Vac 53 Colombia<0.25MW-208Vac-1P 17 US-HI-240Vac 54 Colombia<0.25MW-120Vac-3P 18 US-HI-480Vac 55 IEEE 1547-208Vac 19 US-HI-208Vac-3P 56 IEEE 1547-220Vac 20 US-HI-220Vac-3P 57 IEEE 1547-240Vac 21 US-HI-240Vac-3P 58 IEEE 1547-230Vac 22 US-Kauai-208Vac 59 Colombia<0.25MW-127Vac-3P 23 US-Kauai-240Vac 60 Colombia>5MW 24 US-Kauai-480Vac 61 Mexico-127V 25 US-Kauai-208Vac-3P 62 Mexico-240V 26 US-Kauai-220Vac-3P 63 US-O&R-208Vac 27 US-Kauai-240Vac-3P 64 US-O&R-240Vac 28 US-ISO-NE-208Vac 65 US-O&R-480Vac 29 US-ISO-NE-240Vac 66 US-O&R-208Vac-3P 30 US-ISO-NE-480Vac 67 US-O&R-220Vac-3P 31 US-ISO-NE-208Vac-3P 68 US-O&R-240Vac-3P 32 US-ISO-NE-220Vac-3P 69 Brazil-277Vac 33 US-ISO-NE-240Vac-3P 70 Chile-BT ≤9MW 34 LUMAPR-2024-208Vac 71 Chile-MT ≤9MW 35 LUMAPR-2024-240Vac 72 Chile>9MW 36 LUMAPR-2024-480Vac 73 Mexico-277Vac 325
No. Safety Regulation Name No. Safety Regulation Name 37 LUMAPR-2024-208Vac-3P Oceania 1 Australia-A 4 Newzealand 2 Australia-B 5 Newzealand:2015 3 Australia-C 6 NZ-GreenGrid Asia 1 China A 33 Israel-MV 2 China B 34 Israel-HV 3 China Higher Voltage 35 Vietnam 4 China Highest Voltage 36 Malaysia-LV 5 China Power Station 37 Malaysia-MV 6 China Shandong 38 DEWA-LV 7 China Hebei 39 DEWA-MV 8 China PCS 40 Saudi Arabia-220V-LV 9 Taiwan 41 JP-690Vac-50Hz 10 Hong Kong 42 JP-690Vac-60Hz 11 China Northeast 43 Srilanka-MV/HV 12 Thailand-MEA 44 IEC 61727-127Vac-50Hz 13 Thailand-PEA 45 IEC 61727-127Vac-60Hz 14 Mauritius 46 JP-550Vac-50Hz 15 Korea 47 JP-550Vac-60Hz 16 India 48 India-Higher 17 India-CEA 49 JP-220Vac-50Hz 18 Pakistan 50 JP-220Vac-60Hz 326
No. Safety Regulation Name No. Safety Regulation Name 19 Philippines 51 Saudi Arabia-127V-LV 20 Philippines-127Vac 52 Srilanka-LV >1MW 21 JP-200Vac-50Hz 53 China-YN 22 JP-200Vac-60Hz 54 GB/T 29319-LV 23 JP-440Vac-50Hz 55 GB/T 29319-MV 24 JP-440Vac-60Hz 56 Philippines-277Vac 25 JP-420Vac-50Hz 57 JP-360Vac-50Hz 26 JP-420Vac-60Hz 58 JP-360Vac-60Hz 27 JP-480Vac-50Hz 59 JP-320Vac-50Hz 28 JP-480Vac-60Hz 60 JP-320Vac-60Hz 29 Srilanka-LV<1MW 61 JP-340Vac-50Hz 30 Singapore 62 JP-340Vac-60Hz 31 Israel-OG 63 JP-380Vac-50Hz 32 Israel-LV 64 JP-380Vac-60Hz Africa 1 Mauritius 5 Ghana-LV 2 South Africa-LV 6 Ghana-HV 3 South Africa-B-MV 7 South Africa-A3-LV 4 South Africa-C-MV 8 Nigeria 327