xe7c-24hc-owner-s-manual

Bu sayfa, kılavuzun PDF dosyasındaki metnin tamamıdır (sayfa sayfa). Görseller ve çizimler için PDF'i açın. — sibastore.com

Sayfa 1

 
Owner's Manual 

Original Instructions 
 
Wired Controller XE7C-24/HC 
Wired Controller XE7C-24/H 

GREE+ 
 

Sayfa 2

To Users 

Thank you for selecting Gree product. Please read this 
instruction manual carefully before installing and using the product, 
so as to master and correctly use the product. In order to guide you 
to correctly install and use our product and achieve expected 
operating effect, we hereby instruct as below: 
(1) 
This appliance is not intended for use by persons (including 
children) with reduced physical, sensory or mental capabilities, 
or lack of experience and knowledge, unless they have been 
given supervision or instruction concerning use of the 
appliance by a person responsibility for their safety. Children 
should be supervised to ensure that they do not play with the 
appliance. 
(2) 
This instruction manual is a universal manual; some functions 
are only applicable to particular product. All the illustrations and 
information in the instruction manual are only for reference, 
and control interface should be subject to actual operation. 
(3) 
In order to make the product better, we will continuously 
conduct improvement and innovation. If there is adjustment in 
the product, please subject to actual product. 
(4) 
If the product needs to be installed, moved or maintained, 
please contact our designated dealer or local service center for 
professional support. Users should not disassemble or 
maintain the unit by themselves, otherwise it may cause 
relative damage, and our company will bear no responsibilities. 

Sayfa 3

This marking indicates that this 
product should not be disposed 
with other household wastes 
throughout the EU. To prevent 
possible harm to the environment 
or 
human 
health 
from 
uncontrolled 
waste 
disposal, 
recycle it responsibly to promote 
the sustainable reuse of material 
resources. To return your used 
device, please use the return and 
collection systems or contact the 
retailer where the product was 
purchased. They can take this 
product for environmental safe 
recycling. 
 
 
 
 
 
 
 
 
 

Sayfa 4

1 Safety Notices (Please be sure to abide them) ....... 1 

2 Operation Notices...................................................... 1 

3 Display ........................................................................ 3 

3.1 LCD of Wired Controller ....................................... 4 

3.2 LCD Display Instruction ........................................ 4 

3.3 Instruction of Status Column Icons ....................... 5 

4 Button ......................................................................... 7 

4.1 Button Silk Screen ................................................ 7 

4.2 Buttons Function Instruction ................................. 8 

5 Installation and Commissioning .............................. 9 

5.1 Instruction of Wired Controller ............................ 10 

5.2 Engineering Debugging ...................................... 16 

6 Operation Instruction .............................................. 30 

Contents 

Sayfa 5

6.1 ON/OFF .............................................................. 30 

6.2 Mode Setting ...................................................... 31 

6.3 Temperature Setting ........................................... 32 

6.4 Fan Setting ......................................................... 34 

6.5 Swing Setting ..................................................... 35 

6.6 Function Setting ................................................. 36 

6.7 Universal Setting ................................................ 54 

6.8 Timer Setting ...................................................... 58 

7 Error Display ............................................................ 64 

7.1 Table of Error Codes for VRF and Big Duct Unit 65 

7.2 Table of Display Codes for U-Match Unit ............ 76 

Sayfa 6

Owner’s Manual 

1 Safety Notices (Please be sure to abide them) 

 
WARNING: If not abide them strictly, it may cause severe damage 
to the unit or the people. 

 
NOTE: If not abide them strictly, it may cause slight or medium 
damage to the unit or the people. 

 
This sign indicates that the items must be prohibited. Improper 
operation may cause severe damage or death to people. 

 
This sign indicates that the items must be observed. Improper 
operation may cause damage to people or property. 
 
   WARNING! 
This product can’t be installed at corrosive, inflammable or 
explosive environment or the place with special requirements, such 
as kitchen. Otherwise, it will affect the normal operation or shorten 
the service life of the unit, or even cause fire hazard or serious injury. 
As for the above special places, please adopt special air conditioner 
with anti-corrosive or anti-explosion function.  
2 Operation Notices 
 The power supply for all indoor units must be unified. 
 Prohibit installing the wired controller at wet or sunshine places. 
 Do not knock, throw or frequently disassemble the wired controller. 
 Do not operate the wired controller with wet hands.  
 This product is applicable to VRF unit, Big Duct Type unit, Air-

cooled Packaged unit and U-Match unit whose outdoor unit and 
indoor unit communicate with each other by live line and neutral 
line. 

1 

Sayfa 7

 When two wired controllers control one (or more) indoor unit(s), the 

address of wired controller should be different. 
 Functions with “*” are optional for indoor units. If a function is not 

included in an indoor unit, wired controller can’t set the function, or 
setting of this function is invalid to the indoor unit. 
 Please pay attention to below items when matching with VRF unit: 

 
When the system mode priority is the master-slave mode, in 
one system network, you must set one indoor unit as the 
master indoor unit, other indoor units are slave indoor units.  
 
When the system mode priority is the master-slave mode, 
the operation mode of the system is basing on that of the 
master indoor unit. The master indoor unit can be set to any 
mode (including auto mode), while the slave indoor unit can’t 
set to the mode that conflicts with the system mode. 
 
When the system mode priority is: Cooling mode is 
prioritized, heating mode is prioritized, first-set mode is 
prioritized, or last-set mode is prioritized. The indoor unit can 
be set to any mode (excluding auto mode). The indoor unit 
will automatically switch to the system mode, when the 
operation mode of the indoor unit conflicts with the system 
operation mode.  
 
When the system mode priority is the voting mode (indoor 
unit’s capacity is prioritized / number of indoor units is 
prioritized). The indoor unit can be set to any mode 
(excluding the auto mode). The indoor unit will be stopped, 
when the operation mode of the indoor unit conflicts with the 

Owner’s Manual 

2 

Sayfa 8

Owner’s Manual 

system operation mode after voting. 
 
System mode priority defaults to master-slave mode, and 
only certain units have other system mode priorities. 
 Hereby, Our company, declares that this product is in compliance 

with the essential requirement and other relevant provisions of RE 
Directive 2014/53/EU. Wireless frequency range: 2412MHz - 
2472MHz. Maximum Transmit Power: 18dBm. 
3 Display  

Fig. 3.1 Appearance of wired controller  

3 

Sayfa 9

3.1 LCD of Wired Controller  

Fig. 3.2 LCD graphics of wired controller 
3.2 LCD Display Instruction  
Table 3.1 LCD display instruction 
No. 
Name 
Instruction 

1 
Status column 
Display the icon of function that is turned on 

2 
Fan speed 
It is for displaying the fan speed 

3 
Swing 
It is for displaying the current swing status 

4 
Button prompt 
Display the function of menu/ok button at the 

current page and the settable cursor  

It shows the value of temperature (If the wired 

5 
Temperature 

controller is controlling a fresh air indoor unit, 

display  

it will display FAP). 

6 
Mode 
It shows the operating mode 

4 

Owner’s Manual 

Sayfa 10

Owner’s Manual 

No. 
Name 
Instruction 

7 
Clock display  

No. of current indoor unit.  
NOTE: When wired controller is connected with different indoor units, some 
functions will be different. 
3.3 Instruction of Status Column Icons  
Table 3.2 Instruction of Status Column Icon 
No. 
Symbols 
Name 
Instructions 

1 
 
Air * 
Air status(indoor unit optional 

2 
 
Remove card 
The card for access control is 

3 
 
Clean 
Remind to clean the filter 

4 
 
Child lock 
Child lock status 

5 
 
Error 
There are errors for the unit 

6 
 
Health * 
Health function (indoor unit optional 

7 
 
Defrosting 
Defrosting status of outdoor unit 

8 
 
Master 
Current wired controller connects the 

9 
 
Power off 

It display the date and the time. When it’s 
locating the indoor unit, it displays the project 

function) 

removed 

function) 

master indoor unit. 

Memory status (when power 
recovered, indoor unit will resume 

memory 

previous setting status) 

5 

Sayfa 11

No. 
Symbols 
Name 
Instructions 

10 
 
Absence 
Absence is displayed when this 

11 
 

12 
 
Energy-

13 
 
Shield 
Shielding status 

14 
 
Slave wired 

15 
 
Sleep 
Sleep status 

16 
 
Time 
Timer status is displayed 

17 
 
X-fan 
X-fan is displayed when this function 

18 
 
Group control 
One wired controller controls multiple 

19 
 
Valid 
operation 
It’s displayed for valid operation 

20 
 
WiFi 

21 
 
Independent 

Owner’s Manual 

function is turned on. 

Quiet status 
Quiet status (including quiet and auto 

quiet modes) 

saving 
Energy-saving status of indoor unit 

Slave wired controller (address of 

controller 

wired controller is 02). 

is set. 

indoor units. 

WiFi status(If the wired controller has 
no WiFi function, it displays only when 

the unit connected to “G-Cloud”). 

swing* 
Independent swing status 

6 

Sayfa 12

Owner’s Manual 

No. 
Symbols 
Name 
Instructions 

22 
 
Auto clean * 
Auto clean status 

23 
 
I-DEMAND* 
I-DEMAND function, Indoor unit 

24 
 
 
DRED* 
DRED gear control status 

25 
 
Setback 
Setback function status 

NOTE: When wired controller is connected with different indoor units, some 
functions will be different. 
4 Button  
4.1 Button Silk Screen 

Fig. 4.1 Button silk screen  
 

optional function. 

7 

Sayfa 13

4.2 Buttons Function Instruction  
Table 4.1 Buttons function instruction 
No. 
Name 
Function 

1 
Fan 
Switch fan speeds: auto, low, medium-low, medium, 
Medium-high and high 

2 
 
(1) Set operation temperature for the indoor unit. 
(2) Move cursor. 
(3) Set and check parameters. 
7 
 

3 
 
On/off button for turn on or turn off the unit; back 
button for return to previous page. 

9 
 
(1) Turn pages, and switch and select the target; 
(2) Move the cursor; 
(3) Set and check parameters. 
4 
 

5 
Mode 
Switch operating modes: Auto, Cool, Dry, Fan, Heat, 
Floor, 3D Heat, etc. 
6 
Menu/OK 
Select mode and confirm parameters. 
8 
Swing 
Set the swing status of central air conditioners. 
 
 
 
 
 
 

Owner’s Manual 

8 

Sayfa 14

Owner’s Manual 

5 Installation and Commissioning 
Unit: mm 

Fig. 5.1 Dimension of Wired Controller 

Fig. 5.2 Parts and Components of Wired Controller 

9 

Sayfa 15

No. 
1 
2 
3 
4 

Panel of 

Self-tapping screw 

of wired 
controller 
QTY 
1 
4 
2 
1 
5.1 Instruction of Wired Controller 
5.1.1 Requirements for Model Selection of Communication Wire 

Name 

wired 
controller 

ST3.9×25 MA 

Fig. 5.3 Length of communication wire 

10 

Owner’s Manual 

Soleplate 

Screw 
M4×25 

Sayfa 16

Owner’s Manual 

Wire 
material 

Total 
length L 
(m/feet) 

Wire size  

Material 
standard 
Remarks 

(mm2/AW

type 

G) 

(1) Total length of 

communication 
line can't exceed 
250m (820-
1/5feet). 
(2) The cord shall be 

Light/ 
Ordinary 
Polyvinyl 

2×0.75 
mm2~2× 
1.25 mm2 
(2×AWG

chloride 
sheathed 

L≤250m 
(L≤820-

circular cord (the 
cores shall be 
twisted together).  
(3) If unit is installed in 

IEC 
60227-
5:2007 

cord. 
(60227 
IEC 52 
/60227 
IEC 53) 

1/5 
feet) 

18~ 
2×AWG1
6) 

places with intense 
magnetic field or 
strong 
interference, it is 
necessary to use 
shielded wire. 

5.1.2 Requirements for Installation 
(1) 
It is not allowed to install the wired controller in the wet place. 
(2) 
It is not allowed to install the wired controller in the place with 
direct sunlight. 
(3) 
It is not allowed to install the wired controller near the high-
temperature object or the place is likely to be spattered with 
water. 

11 

Sayfa 17

5.1.3 Requirements for Wired Connection 
Network connecting methods between wired controller and 
indoor unit are as below: 

Fig. 5.4 One wired controller controls one indoor unit        

Owner’s Manual 

12 

Sayfa 18

Owner’s Manual 

Fig. 5.5 One wired controller controls multiple VRF indoor units simultaneously 

Fig. 5.6 One wired controller controls multiple U-Match simultaneously 

13 

Sayfa 19

Instruction for wire connection: 
(1) 
The wiring methods in fig. 5.4 and fig. 5.6 can be adopted for 
the wired controller connecting U-Match unit. 
(2) 
The wiring methods in fig. 5.4 and fig. 5.5 can be adopted for 
the wired controller connecting VRF unit. 
(3) 
Only the wiring methods in fig. 5.4 can be adopted for the wired 
controller connecting Big Duct Type unit or Air-cooled 
Packaged unit, that is, one wired controller can control only one 
indoor unit, cannot control multiple indoor units of different 
systems. 
(4) 
When one wired controller controls multiple indoor units 
simultaneously, the wired controller can connect to any one 
indoor unit, but the connected indoor unit must be the same 
series indoor unit. The total quantity of indoor unit controlled by 
wired controller can't exceed 16 sets, and the connected indoor 
unit must be within the same indoor unit's network. Wire 
controller must set quantity of group control indoor units. 
Please refer to 5.2.2 Parameter Setting. 
(5) 
The terminal of the wire controller is non-polarized and cannot 
be connected to strong electric. 
NOTE: Wired controller XE7C-24/HC only supports one (or more) 

indoor unit(s) controlled by one wired controller. 
 
 
 
 

Owner’s Manual 

14 

Sayfa 20

Owner’s Manual 

5.1.4 Installation 

Fig. 5.7 Installation of Wired Controller 
 
 
 
 
 
 
 
 

15 

Sayfa 21

Fig. 5.7 shows a simple installation course of wired controller, 
and the following points should be noted: 
(1) 
Before installation, please cut off the power supply of indoor 
unit, it is not allowed to operate with power supply; 
(2) 
Pull out the 2-core twisted pair inside the installation hole in the 
wall, and thread the wire through the hole in the back of 
soleplate of wired controller; 
(3) 
Stick the soleplate of wired controller on the wall, and use Self-
tapping Screw ST3.9×25 MA or screw M4×25 to fix the 
soleplate with the installation hole of wall; 
(4) 
Connect the 2-core twisted pair to wiring terminal H1 and H2, 
and then tighten the screw; 
(5) 
Arrange the wires in the back of panel, and then buckle the 
panel of wired controller with the soleplate of wired controller. 
5.1.5 Disassembly 

Fig. 5.8 Disassembly of wired controller 
5.2 Engineering Debugging  
5.2.1 Parameter View 
Under on or off status, view unit’s parameters.  
Press “Menu/OK” button on the home page to enter into the 
menu page to select “View” to go to view page shown as below:  

Owner’s Manual 

16 

Sayfa 22

Owner’s Manual 

(1) 
View and locate indoor unit project No.  
Select “IDU Project No. View and Locating” on the view page to 
go to indoor unit project No. view and locating page shown as below. 
Indoor unit project No. and error codes will be displayed on this page.   

If there are multiple indoor units, press “◀” or “▶” button to switch 
the indoor unit. Corresponding indoor unit project No. and current 
errors will be displayed. When one indoor unit has multiple errors, the 
error codes will be displayed circularly at the interval of 3s. If there is 
no error, “none” will be displayed.  

17 

Sayfa 23

After entering indoor unit project No. View and locating page, the 
buzzer of selected indoor unit gives out sound until exit from the view 
page or switch to the next indoor unit.  
(2) 
One button to view all indoor units’ project No. (only for VRF 
unit)  
Select “View All IDU Project No.” on the view page, move the 
cursor left and right to turn on or turn off this function. Press 
“Menu/OK” button to confirm it.   

After turning on “View All IDU Project No.” function, all indoor 
units and wired controllers (the wired controller displays indoor units’ 
project No. every 3s in turn, and the project No. are displayed from 
smallest to biggest) in the internet display their project series No.  

After turning on “View All IDU Project No.” function, this function 
can be selected on the view page. Move the cursor to select “off” 
status, press “Menu/OK” button to turn off this function or press  
“
” on the connected wired controller to cancel the display of all 
indoor units’ project series No.  

Owner’s Manual 

18 

Sayfa 24

Owner’s Manual 

(3) 
Parameter View  
Select “parameter view” at the view page to enter into paremeter 
view page shown as below. As for the parameters, please refer to 
table 5.1 “Unit parameters view list”.   

When viewing the indoor unit, if there are multiple indoor unit, 
press “◀” or “▶” button to switch indoor units. Corresponding indoor 
unit’s parameters will be displayed on the page. See the figure as 
below:  

When viewing the outdoor unit, if there are multiple outdoor unit, 

19 

Sayfa 25

press “◀” or “▶” button to switch outdoor units. Corresponding outdoor 
unit’s parameters will be displayed on the page. See the figure as 
below:  

Table 5.1 Unit parameters view list 
Parameter 

Name 
Range 
Parameter 

Wired 
Controller’s 

Address 

Master IDU’s 

Project No. 
0,1~255 
Time Left to 
Clean Filter 
0~416 days 

Online IDUs of 

CAN1 
1~100 
CAN2 address 
1~255 

Max Distribution 

Ratio 

IDU Error Log 
5 historical 
errors 
Prior Operation 
Yes, No 

Owner’s Manual 

Name 
Range 

1,2 
Number of IDUs 
1~16 

110% 
135% 
150% 

Cool Only, Heat 

Cool & Heat 

Only, Cool & 

Modes 

Heat, Fan 

20 

Sayfa 26

Owner’s Manual 

Parameter 

Name 
Range 
Parameter 

Name 
Range 

Indoor Temp 
-30°C -139°C 
Relative 
Humidity / RH 
 0%~100% 

Inlet Temp 1 
-30°C -139°C 
Outlet Temp 1 
-30°C -139°C 
Inlet Temp 2* 
-30°C -139°C 
Outlet Temp 2* 
-30°C -139°C 

IDU capacity 
and capacity 
after adjustment 

IDU Capacity 

IDU EXV Status 
0~20 

Fresh Air IDU 
Output Temp* 
-30°C -139°C 
ODU Static 

Pressure 
0~4 

Duct Network 
Static Pressure 
0~999 
ODU Error Log 
5 historical 
errors 
 

The following parameters can only be viewed from the master wired 

controller, they cannot be viewed from the slave wired controller 
Parameter 

Name 
Range 
Parameter 

Name 
Range 

Unit Code 
0~9, A~Z, a~z, - 
Board Code 
0~9, A~Z, a~z,- 

Outdoor Temp 
-30~139°C 
Comp1 
Operation Freq. 
0~200Hz 

Comp 2 
Operation Freq. 
0~200Hz 
ODU Fan 
Operation Freq. 
0~100Hz 

Module High 

Pressure 
-40~70°C 
Module Low 

Pressure 
-69~38°C 

Comp 2 
Discharge 

Comp1 
Discharge Temp 
-30~150°C 

Temp. 

21 

-30~150°C 

Sayfa 27

The following parameters can only be viewed from the master wired 

controller, they cannot be viewed from the slave wired controller 
Parameter 

Name 
Range 
Parameter 

Comp 3 
Discharge Temp 
-30~150°C 

Comp 5 
Discharge Temp 
-30~150°C 

Comp 3 
Operation Freq. 
0~200Hz 
ODU Heating 

ODU Heating 

EXV2 
0~48 
Subcooler EXV 
0~48 

Defrosting Temp 
-30~139°C 
Subcooler 
Liquid Temp 
-30~139°C 

Separator Outlet 

Temp 
-30~139°C 
Oil Return Temp 
-30~139°C 

Condenser Inlet 

Temp 
-30~139°C 
Condenser 
Outlet Temp 
-30~139°C 

NOTES: 
① Under parameter viewing status, the signal from remote 

controller is invalid. 
② When the parameter is invalid, it will display “--”. 
5.2.2 Parameters Setting  
Parameters can be set under on or off status.  
Press “Menu/ok” button on the homepage to enter into menu 
page to select “set” to go to set page. Select “parameter setting” at 

Owner’s Manual 

Name 
Range 

Comp 4 
Discharge 

-30~150°C 

Temp. 

Comp 6 
Discharge 

-30~150°C 

Temp. 

EXV1 
0~48 

22 

Sayfa 28

Owner’s Manual 

the set page to go into parameter setting page. See the figure as 
below.   

Select user parameter, project parameter and U-Match 
parameter to enter into corresponding parameter setting. See the 
figure as below: 

After that, press “▲” or “▼” button to switch the items. Hold it can 
switch it quickly. 

When selecting the parameter, press “◀” or “▶” to switch the 
setting value. Press “menu/ok” button to save corresponding setting 

23 

Sayfa 29

items. If the setting can’t be confirmed, switching the item can restore 
the previous setting value.  

Please refer to table 5.2 for the settable parameters.  

Table 5.2 Unit’s parameters setting list  
Item 
Settable range 
Default  
Remarks  

Master 

Wired 
Controller 

Yes, No 
Yes 

Owner’s Manual 

When it is set as no, this 
wired controller is slave wired 
controller. Status column of 
the homepage displays the 
icon of slave wired controller 
“
” . The wired controller 
can only activate the master 
wired controller. It does not 
have the function of setting 
parameters for other units. 

24 

Sayfa 30

Owner’s Manual 

Item 
Settable range 
Default  
Remarks  

Master IDU 
Yes, No 
No 

Use 
Remote 
Yes, No 
Yes 

Prior 
Operation 
Yes, No 
No 

High 
Ceiling 
Installation* 

Yes, No 
No 
Only applicable to cassette 
type IDU 

Once it is activated, the 
current IDU is set to be the 
master IDU. When the setting 
is Yes, if the system mode 
priority is the master-slave 
mode, the status column in 
homepage will display the 
icon of master IDU “
”; 
when the setting is off, master 
and slave status of the current 
IDU will not be changed. 

When it is set as no, the wired 
controller cannot receive the 
remote control signal. It can 
only be operated with buttons. 

When the power supply is 
insufficient, it is allowed to 
turn on the designated IDU as 
preferential operation; other 
IDUs should be forced to be 
off. 

25 

Sayfa 31

Item 
Settable range 
Default  
Remarks  

Link with 
Fresh Air 

Yes, No 
No 

IDU* 

PM2.5 

Filter* 
Yes, No 
No 

Yes: Temp and 
humidity correction 

Temp and 

RH 
Correction 

control  
No: Ambient 
temperature 

Control 

control  

Owner’s Manual 

After setting the linkage 
function, the fresh air IDU will 
automatically turn on or turn 
off along with the on and off of 
general IDU. Meanwhile, 
users can manually turn on or 
turn off the unit. 
It only applicable to fresh air 
IDU. 

After it is successfully set, 
adjust the revolving speed to 
ensure the air volume is close 
to or the same as the previous 
air volume. 
It is only applicable to the unit 
with PM2.5 filter. 

Refer to 

indoor 
unit for 

It can be set only when it’s 
supported by the indoor unit.  
 

the 
defaulted 

value  

26 

Sayfa 32

Owner’s Manual 

Item 
Settable range 
Default  
Remarks  

Yes: Humidity 

Dry Mode 

control 
No: Temperature 

Humidity 

Control 

control 

Clear Filter 

Cleaning 

Yes, No 
No 
— 

Time 

Indoor Fan 

Static 
Pressure 

1~9 
5 
 

0: This function is 
unavailable 
1-16: quantity of 
IDU 

Number of 

IDUs 

Angle of 
Air-return 

Angle 1 
Angle 2 
Angle 3 

Board* 

Cooling 
temp of 
Auto Mode 

25°C 
(77°F) 
Cooling temperature of auto 
mode – heating temperature 
of auto mode≥1°C. 
Heating 
temp of 
Auto Mode 

17°C~30°C 
(63°F~86°F) 

16°C ~29°C 
(61°F~84°F) 

If select “yes”, set humidity is 
displayed under dry mode. 
Otherwise, set temperature is 
displayed. It can only be set 
when it’s supported by the 
indoor unit.  

No 

1 
Set corresponding value 
according to the connected 
quantity of IDU. 

Angle 2 
Only applicable to the model 
with air-return plate. 

20°C 
(68°F) 

27 

Sayfa 33

Item 
Settable range 
Default  
Remarks  

Resume 

After 
Inserting 

Yes, No 
Yes 

Card 

Time for 
IDU Cold 

180s, 300s,  
420s, 600s 
180s 

Air 
Prevention* 

Set Temp 

of RH 
Control 

10°C ~30°C 
(50°F~86°F) 

Mode 

Owner’s Manual 

When it is set as No, it will 
keep the status after inserting 
the gate control card. If it is at 
OFF status when pulling out 
the card, when inserting the 
card, it is still at OFF status. 

Cold air prevention time is the 
max waiting time from the 
time turning on the heating 
mode to the time blowing out 
the hot wind. The actual 
waiting time is related to the 
outdoor ambient temperature. 
If there is cold air after turning 
on the heating mode in the 
actual operation, please 
consult the professional 
person to adjust this 
parameter. 

Note: It’s only applicable for 
the units whose dry mode is 
with humidity control function.  

16°C 
(61°F) 

28 

Sayfa 34

Owner’s Manual 

Item 
Settable range 
Default  
Remarks  

01: Normal  
02: Quick  
03: Deep 
1 

Auto Clean 

Mode 

Cooling 
Temp of 
Fresh Air 

16°C ~30°C 
(61°F~86°F) 

IDU* 

Heating 
Temp of 
Fresh Air 

16°C ~30°C 
(61°F~86°F) 

IDU* 

Setback 
Yes, No 
No 
-- 

Upper 
Temp Limit 
of Setback 

20~30°C 
(68~86°F) 

Lower 
Temp Limit 
of Setback 

16~26°C 
(61~79°F) 

Reset G-

Cloud 
Yes, No 
No 
Only applicable to Wired 
Controller XE7C-24/HC. 

NOTE: Only applicable to the 
unit with auto clean function. 
 If “0” is displayed, this 
function is not available for 
this unit.  

18°C 
(64°F) 

Only applicable to fresh air 
IDU. 

22°C 
(71°F) 

Only applicable to fresh air 
IDU. 

When temperature unit 
is °C, temperature upper 
limit – temperature lower 
limit ≥ 4°C; 
When temperature unit is °F, 
temperature upper limit – 
temperature lower limit ≥7°F. 

26°C 
(79°F) 

20°C 
(68°F) 

29 

Sayfa 35

Item 
Settable range 
Default  
Remarks  

No 
Occupancy 

Energy-

-40~40 
0 
Only applicable after installing 
Smart Sensor. 

saving 
Time of I 

SENSE 

NOTES: 
① Except for the above parameters, setting interface for other 

parameter can only be accessed by inputting password. 
② Under parameter setting status, the signal from remote controller 

is invalid. 
③ Under some circumstances, invalid parameters setting is in grey. 

Press “▲” or “▼”button to skip this parameter setting.  
6 Operation Instruction  
6.1 ON/OFF 
Press “
” button to turn on the air conditioner. 
Press “
” button again to stop operation.  
ON and OFF interfaces are shown as below:   

30 

Owner’s Manual 

Sayfa 36

Owner’s Manual 

   Fig. 6.1 ON interface                Fig. 6.2 OFF interface  
6.2 Mode Setting 
Under On status, pressing “MODE” button can set modes 
circularly: 

OR 

31 

Sayfa 37

NOTES: 
① The available modes are different for different models. The wired 

controller will automatically select mode setting range according 
to the model of indoor unit. 
② When the wired controller controls VRF unit and the system 

mode priority is the master-slave mode, only the master indoor 
unit can set the auto mode. 
③ Under Auto mode, if the indoor unit is cooling, the icons “
” 

and “
” will light up; if the indoor unit is Heating, the icons “
” 

and “
” will light up. 
6.3 Temperature Setting 
Press “▲” or “▼”button under on status to increase or decrease 
set temperature by 0.5°C/1°C or 1°F; hold “▲” or “▼”button to increase 
or decrease set temperature by 0.5°C/1°C or 1°F every 0.3s. Please 
refer to 6.7.4 for the setting method of the temperature setting interval 
in Celsius. 

Under Dry mode, when temperature is 16°C or 61°F, 
continuously press “▼”button twice to decrease temperature to 12°C 
or 54°F (when save function is activated, the temperature under Dry 
mode can’t be adjusted to 12°C or 54°F). 

When the control method under Dry mode is humidity control, 
press “▲” or “▼”button to adjust the set humidity at 5% intervals. The 
humidity setting range is 45%~75%, and the default value is 65%. 
The humidity control method under Dry mode can only be set for the 

Owner’s Manual 

32 

Sayfa 38

Owner’s Manual 

unit with this function. Please refer to 5.2.2 Parameter Setting for the 
setting method. 
NOTES: 
① Only when the wired controller controls U-Match indoor units,  

the setting temperature can be adjusted by pressing “▲” or “▼”  
under Auto mode. 
② When Absence function is activated, the setting temperature 

cannot be adjusted by pressing “▲” or “▼”.  
③ When the wired controller is connected with a Fresh Air Indoor 

Unit, fresh air indoor unit code “FAP” will be displayed as shown 
below. Setting temperature won’t be displayed and can’t be 
adjusted via “▲” or “▼”button. The air outlet temperature in cooling 
or heating can only be set in the parameter setting status. 

33 

Sayfa 39

6.4 Fan Setting 
Under On status, pressing “FAN” button can set fan speeds 
circularly as: 

NOTES:  
① Under Dry mode, fan speed is low and can’t be adjusted. 
② When the wired controller is connected with a Fresh Air Indoor 

Owner’s Manual 

34 

Sayfa 40

Owner’s Manual 

Unit, fan speed of indoor unit will be high fan speed only. Fan 
speed of indoor unit can’t be adjusted via “FAN” button. 
③ If indoor unit’s fan speed is set auto, indoor unit will change fan 

speed automatically according to room temperature in order to 
make the room temperature more stable and comfortable. 
6.5 Swing Setting 
(1) 
Up&down Swing : 
The up&down swing has two modes: simple swing and fixed-
angle swing. Select the fixed-angle swing on the function page, and 
press “◀” and “▶” buttons to turn on or turn off the fixed-angle swing. 
Simple swing and fixed-angle swing can be switched.  

Under on status, press “Swing” button on the homepage to enter 
into swing setting:  
1)When the simple swing is set, press “Swing” button to turn on or 
turn off the up&down swing.  
2)When the fixed-angle swing is set, press “Swing” button to switch 
swing statuses circularly as below:  

(2) 
Left&right swing*: 
The left&right swing has two modes: simple swing and fixed-
angle swing. Select the fixed-angle swing on the function page, and 
press “◀” and “▶” buttons to turn on or turn off the fixed-angle swing. 
Simple swing and fixed-angle swing can be switched.  

Under on status, press “Swing” button on the homepage to enter 

35 

Sayfa 41

into swing setting, and then press “◀” and “▶” button to switch to the 
left&right swing setting:  
1)When the simple swing is set, press “Swing” button to turn on or 
turn off the left&right swing.  
2)When the fixed-angle swing is set, press “Swing” button to switch 
swing statuses circularly as below:  

6.6 Function Setting  
Press “Menu/OK” button on the homepage to enter menu page 
and then select “Function” to go to function page. See the figure as 
below.   

Fig. 6.3 Function page  
Press “▲” or “▼”button to switch the items; press “◀” and “▶” button 
to turn on or turn off corresponding function. “ON” indicates the 
function is turned on; “OFF” indicates the function turned off; press 
“Back” button to turn back to previous page.  

Owner’s Manual 

36 

Sayfa 42

Owner’s Manual 

Some functions are with more parameters and “Menu/OK” button 
can be used for setting detailed parameters. 

Fig. 6.4 Function with detailed setting 
As for some functions, only the on/off status is displayed at the 
switch button. It needs to press “Menu/OK” button to enter into 
detailed setting:  

Fig. 6.5 Functions whose on/off status is only displayed  
NOTES:  

The function under some circumstances is invalid and displayed 
in grey. Press “▲” or “▼”button to skip this function.  

37 

Sayfa 43

6.6.1 Turbo Setting 
Turbo fan Function: Turn on the highest fan speed, and then 
turbo fan will be displayed on the homepage.  

Turn on turbo fan Function: Under on status, select turbo fan on 
the function page and press “◀” or “▶” button to turn on or turn off the 
turbo fan. When turbo fan is turned on, “turbo fan” will be displayed 
at the fan speed area on the homepage. 

Cancel turbo fan Function: Same as the method used for turning 
on the turbo Fan Function.  

You can also press “Fan” button on the home page to cancel the 
turbo fan and then switch to the auto fan.  
NOTES:  
① Under Dry mode, fan speed is low and can’t be adjusted. 
② When the wired controller is connected with a Fresh Air Indoor 

Unit, fan speed of indoor unit will be high fan speed only. Fan 
speed of indoor unit can’t be adjusted via “FAN” button. 
③ If indoor unit’s fan speed is set auto, indoor unit will change fan 

speed automatically according to room temperature in order to 
make the room temperature more stable and comfortable. 
6.6.2 Air Setting* 
Air Function: Adjust the amount of indoor fresh air to improve air 
quality and keep indoor air fresh. 

Turn on air function: Under on or off status, select the air function 
on the function page and then press “◀” or “▶” button to turn on or turn 
off the air function.  

Owner’s Manual 

38 

Sayfa 44

Owner’s Manual 

Cancel air function: Same as the method used for turning on the 
air function.  

When selecting the air function on the function page, press 
“Menu/OK” button to go air level setting. The display is as below:  

Fig. 6.6 Air level setting  
Press “▲” or “▼”button can adjust the air level in the range of level 
1~10. Press “Menu/OK” button to save the setting. 
NOTES: 
① Air function is only effective for units with air function and fresh 

air motorized air valve (abbr. fresh air valve). 
② The following table indicates the opening time of fresh air valve 

per unit of time (60 min) corresponding to the level of air setting. 
Opening time of fresh air valve is the initial N minutes per unit of 
time. Example: The level of air setting is set to 1, and then unit 
starts timing and fresh air valve is open. 6 minutes later, fresh air 
valve is closed and the unit keeps running. After timing for 60 
minutes, unit restarts timing and fresh air valve is open again. 6 
minutes later, the valve is closed and the cycle repeats. 

39 

Sayfa 45

Owner’s Manual 

Level of Air 

setting 
1 
2 
3 
4 
5 
6 
7 
8 
9 
10 

Opening time 

60 
/6 

60 
/12 

60 
/18 

60 
/24 

60 
/30 

60 
/36 

60 
/42 

60 
/48 

60 
/54 

Always 

of fresh air 

on 

valve 

NOTE: Time indicated in the table: unit’s operating time (min) / opening time of 
fresh air valve per operating time (min). 
6.6.3 Sleep Setting 
Sleep Function: The unit will operate according to the preset 
sleep curve to provide comfortable sleep environment. 

Turn on sleep function: Under on status, select sleep function on 
the function page and then press “◀” or “▶” to turn on or turn off the 
sleep function.  

Cancel sleep function: Same as the method used for turning on 
the sleep function.  

When sleep function is activated, “
” icon is bright; quiet or auto 
quiet mode is also activated. 

Under Auto, Fan or Floor Heating mode, the sleep function is not 
available.  
6.6.4 Health Setting* 
Health function: Control the air purification module which can 
purify the air. This function cannot be used under Floor Heating mode. 

Turn on health function: Under on status, select the health 
function on the function page and then press “◀” or “▶” to turn on or 
turn off the health function.  

Cancel health function: Same as the method used for turning on 

40 

Sayfa 46

Owner’s Manual 

the health function.  
6.6.5 I-Demand Setting* 
I-DEMAND function: The unit operates in the SE mode to save 
energy. I-DEMAND function can only be used under cooling mode.  

Turn on I-Demand function: When the unit is turned on, under 
cooling mode, select I-Demand on the function page, and then press  
“◀” or “▶” button to turn on or turn off I-Demand function.  

Cancel I-Demand function: Same as the method used for turning 
on the I-Demand function.  
NOTE: It is only applicable to U-Match unit. 
6.6.6 Absence Setting 
Absence function: This is used to maintain indoor temperature 
so that unit can realize fast heating after it is turned on. This function 
can only be used under heating mode. 

Turn on absence function: Under heating mode, select absence 
function on the function page and then press “◀” or “▶” button to turn 
on or turn off the absence function.  

Cancel absence function: Same as the method used for turning 
on the absence function.  
6.6.7 Save Setting 
Save function: Air conditioner can be operated in small 
temperature range by setting the minimum temperature under 
Cooling and Dry modes and setting maximum temperature under 
Heating, 3D Heating and Space Heating modes. Thus, energy saving 
can be realized. 

41 

Sayfa 47

Turn on save mode: Under on status, select save function on the 
function page and press “◀” or “▶” button to turn on or turn off the save 
function.  

Cancel save mode: Same as the method used for turning on the 
save function.  

When selecting save function on the function page, press 
“Menu/OK” button to set temperature for save function. The display 
is as below:  

Fig. 6.7 Temperature setting for save function 
Press “▲” or “▼”button to switch items. When selecting the first 
item, press “◀” or “▶” button to switch modes; when selecting the 
second item, press “◀” or “▶” button to switch temperature lower limit 
and upper limit value. Press “Menu/OK” button to save the setting and 
then turn back to the previous page.  

 When save function is turned on, icon “
” is displayed under 
all modes at on and off statuses.  

Owner’s Manual 

42 

Sayfa 48

Owner’s Manual 

NOTE: 

When the save function is turned on and then set temperature 
exceeds the limit value for save function, “
” icon blinks three times 
and then buzzer will give out two sounds successively.  
6.6.8 X-FAN Setting 
X-fan function: If the unit is turned off under Cooling or Dry mode, 
the evaporator of indoor unit will be dried off automatically to prevent 
bacteria and mould from gathering. 

Turn on X-fan function: When the unit is turned on, select X-fan 
function on the function page under cooling or dry mode and press  
“◀” or “▶” button to turn on or turn off X-fan function.  

Cancel X-fan: Same as the method used for turning on the X-fan 
function.  
6.6.9 Filter Clean Reminder Setting 
Filter Clean Reminder Function: The unit will remember its own 
operating time. When the setting time is over, this function will remind 
you to clean the filer. A dirty filter will result in bad heating and cooling 
performance, abnormal protection, bacteria gathering, etc. 

Select “Clean Remind” on the function page and press 
“Menu/OK” button to go to filter clean reminder setting page. Refer 
to the figure as below:  

43 

Sayfa 49

Fig 6.8 Filter clean reminder setting 
Press “▲” or “▼”button to switch items. When selecting the first 
item, press “◀” or “▶” button to turn on or turn off this function; when 
selecting the second item, press “◀” or “▶” button to switch current 
environmental cleanliness (switch among level 1, level 2 and level 3. 
There are for good, general and bad cleanliness); when selecting 
the third item, press “◀” or “▶” button to adjust the cleaning period . 
Press “Menu/OK” button to save the setting and then turn back to the 
previous page. 

There are four circumstances while cleaning period Setting: 

Turn off clean reminder; 
Light pollution: When current cleanliness is “1”, the setting range 
for the clean cycle is 5500h-10000h. After each pressing of “▶” button, 
the accumulated time will increase 500h. When the time exceeds the 
maximum value, it will turn back to the minimum value.  

Medium pollution: When current cleanliness is “2”, the setting 
range for the clean cycle is 1400h-5000h. After each pressing of “▶” 

Owner’s Manual 

44 

Sayfa 50

Owner’s Manual 

button, the accumulated time will increase 400h. When the time 
exceeds the maximum value, it will turn back to the minimum value.  

Serious pollution: When current cleanliness is “3”, the setting 
range for the clean cycle is 100h-1000h. After each pressing of “▶” 
button, the accumulated time will increase 100h. When the time 
exceeds the maximum value, it will turn back to the minimum value.  
NOTES:  

When clean time is reached, icon“
”at the status column will 
be displayed. The reminding will pop up at the home page to remind 
users to clean the filter. Click “Done” or “Skip” to cancel the display. 
At the same time, the accumulated time for “filter clean reminder” will 
be cleared and the time will be counted again.  
6.6.10 Quiet Setting 
Quiet function: Decrease the noise of indoor unit and achieve the 
quiet effect. Quiet function has two modes: quiet mode and auto quiet 
mode. It is available only in Auto, Cooling, Dry, Fan, Heating, 3D 
heating and Space heating modes. 

Turn on quiet function: Under on status, select the quiet function 
on the function page and press “◀” or “▶” button to turn on or turn off 
the quiet function.  

Cancel quiet function: Same as the method used for turning on 
the quiet function.  

When selecting quiet function on the function page, press 
“Menu/OK” button to set the quiet mode. The display is as below:  

45 

Sayfa 51

Fig. 6.9 Quiet mode setting  
Press“▲”or “▼” button can adjust the quiet mode (quiet mode and 
auto quiet mode). Press “Menu/OK” button to save the setting.  
NOTES:  
① When quiet function is enabled, indoor unit will operate at quiet 

fan speed. Fan speed is lowered so as to reduce the noise of 
indoor fan motor. 
② When auto quiet function is enabled, indoor unit will change fan 

speed automatically according to room temperature. After room 
temperature reaches a set point, the unit will operate at quiet fan 
speed.  
6.6.11 Low-temperature Dry Function Setting  
Low-temperature dry function: It can be turned on under the dry 
mode. When the dry function is turned on, the set temperature is 
changed to12°C.  

Turn on low-temperature dry function: When the unit is turned on, 
under dry mode, select the “12-Drying” function at the function page 

Owner’s Manual 

46 

Sayfa 52

Owner’s Manual 

and then press “◀” or “▶” button to turn it on or turn it off.  

Cancel low-temperature dry function: Same as the method of 
turning on the low-temperature dry function.  
6.6.12 Setback Function 
In unit off status with setback function activated, the unit will 
operate in heating mode automatically when indoor temperature is 
lower than temperature lower limit for setback function and operate 
in cooling mode automatically when indoor temperature is higher than 
temperature upper limit for setback function, so as to keep indoor 
temperature within the temperature upper and lower limit range for 
setback function.  

When turning on the setback function, the icon“
”will be 
displayed on the homepage.  

Under off status, when setback function is operating, the icon 
“
”blinks.  
As for setting related parameters of setback, it needs to go to 
user parameters page. Please refer to 5.2.2 parameters setting for 
the method.  

Turn on setback function: Under on or off status, select setback 
function on the user parameter page, and press “◀” or “▶” button to 
turn on or turn off the setback function. Press “Menu/OK” button to 
save the setting.    

Cancel setback function: Same as the method used for turning 
on the setback.  

47 

Sayfa 53

Set setback temperature: 
Setback Upper Temp Limit: select “Upper Temp Limit of Setback” 
on the user parameters page, and press “◀” or “▶” button to adjust the 
upper temperature limit of setback function. Press “Menu/OK” button 
to save the setting. 

Setback Lower Temp Limit: select “Lower Temp Limit of Setback” 
on the user parameter page, and press “◀” or “▶” button to adjust the 
lower temperature limit of setback function. Press “Menu/OK” button 
to save the setting. 
NOTES:  
① Setback function is forbidden as defaulted;  
② When the slave indoor unit is operating in setback function, it 

cannot operate in the mode which is in conflict with that of master 
indoor unit. 
③ If you want to activate setback function, you cannot use the wired 

controllers of other models as the master wired controller or 
slave master controller. 
④ When all shield function of remote monitor or central controller is 

turned on, the wired controller can’t enter or exits from the 
setback function. 
⑤ When the unit is operating at setback function, the slave wired 

controller cannot set save function and doesn’t display or receive 
save setting. 
6.6.13 DRED Function Setting *   
DRED function: The unit operates under save mode. This 

Owner’s Manual 

48 

Sayfa 54

Owner’s Manual 

function can be turned on under cooling, heating, auto and dry modes.  

Turn on DRED function: Under on status, select DRED on the 
function page and then press “◀” or “▶” button to turn on or turn off 
DRED function.  

Cancel DRED: Same as the method used for turning on DRED 
function.  

When selecting DRED on the function page, press “Menu/OK” 
button to go to DRED mode setting. The display is as below:  

Figure 6.10 DRED mode setting 
Press “▲” or “▼”button to switch between DRED mode 2 and 
DRED mode 3. Press “Menu/OK” button to save the setting.  
NOTE: It is only applicable to U-Match unit. 
6.6.14 Independent Swing Function Setting*  
Turn on independent swing function: Select the independent 
swing on the function page under on status, and press “◀” or “▶” button 
to turn on or turn off the independent swing function.  

Cancel independent swing: Same as the method used for turning 

49 

Sayfa 55

on the independent swing function.  

When turning on the independent swing, select the independent 
swing on the function page and press “Menu/OK: button to go to the 
independent swing setting. The display is as below:  

Fig 6.11 Independent swing setting 
Press “▲” or “▼”button to select the air outlet (air outlet 1, air outlet 
2, air outlet 3 and air outlet 4). Press “◀” or “▶” button to switch the 
swing status of corresponding air outlet. Press “Menu/OK” button to 
save the setting.  

The swing status is shown as blow:  

Fig. 6.12 Swing status  
NOTES:  
① This function is only applicable to cassette type unit.  
② Up&down swing is only applicable for independent swing 

function.  

Owner’s Manual 

50 

Sayfa 56

Owner’s Manual 

③ As for the independent swing, one air outlet at the most can be 

set closed. When the air outlet is closed, it can’t supply the air 
outlet.  
④ Turning off the independent swing can restore to the original 

up&down swing setting.   
When independent swing function is turned on, independent 
swing icon “
 ” will be displayed at the status column on the 
homepage.  
6.6.15 Auto Clean Function* 
Turn on auto clean function: Select auto clean function on the 
function page and then press “◀” or “▶” button to turn on or turn off the 
auto clean function. When turning on the auto clean function, press 
other buttons to turn back to the homepage.   

Cancel auto clean:  
Function page: Same as the method used for turn on the auto 
clean function.  

Homepage: Press any buttons and a pop-up window will appear 
and then press “
” button.  
When auto clean function is turned on while the unit hasn’t enter 
into auto clean operation, “
”is bright; when the unit has officially 
entered into auto clean status, “
” blinks. The remaining time of 
auto clean mode is displayed at the temperature area.  

When existing the auto clean function, the remaining time for 
auto clean mode won’t be displayed at the temperature area. Some 
time later, icon“
”will be off and the auto clean is existed.  

51 

Sayfa 57

NOTES:  
① This function is only applicable to the unit with auto clean function.  
② When the unit is faulty, auto clean function cannot be turned on.  
③ When auto clean function is turned on, there will be some 

phenomenons, such as frosting of evaporator of indoor unit, 
sound of liquid flow, and fluctuation of indoor temperature and 
humidity, which will affect the comfort. Auto clean function is 
recommended to be used when there are no people in the room. 
In order to ensure the cleaning effect, it is recommended to turn 
on auto clean function every three months. 
④ The auto clean effect will be weakened if indoor environment 

humidity is low. 
⑤ It is recommended to use auto clean function at the outdoor 

ambient temperature of 10 ℃~40 ℃. Otherwise, auto clean 
function will exit in advance, which is the normal phenomenon.  
⑥ When an indoor unit in VRF system has entered into the auto 

clean mode, all other units in the system will operate under the 
auto clean mode. 
⑦ When the wired controller controls U-Match unit, auto clean 

function can only be turned on under OFF status. The remaining 
time of the auto clean mode won’t be displayed at the timer zone. 

 
6.6.16 Remote Shield Function 
Remote shield function: Remote monitor or central controller can 
disable the relevant functions of wired controller so as to realize the 
function of remote control. 

Owner’s Manual 

52 

Sayfa 58

Owner’s Manual 

When the remote monitor or central controller activates remote 
shield on the wired controller, icon “
” will show. If user wants to 
control it through the wired controller, icon “
”  will blink to remind 
that these controls are disabled. 
6.6.17 Gate-Control Function 
When there is gate-control system, user can insert a card to turn 
on the unit or pull off a card to turn off the unit. When the card is re-
inserted, the unit will recover the operation as state in memory. When 
the card is pulled off (or improperly inserted), icon “
” will show. 
Neither remote control nor operation of wired controller will be 
effective and icon “
” will blink.  
NOTE: This model cannot be connected with gate control system on 
its own because it cannot detect gate control signal directly. To 
realize gate control display and gate control function, it has to be used 
with the wired controller that includes gate control signal detecting 
function (used as master and salve wired controllers). 
6.6.18 I-SENSE Function Setting* 
I-SENSE function:After setting I-SENSE function, I-SENSE 
device is automatically turned on for detection. The air conditioner will 
automatically detect the perceived temperature and then the 
comfortable status will be realized rapidly. The air conditioner 
automatically control the angle of air guide louver as well as the swing 
angle. After I-SENSE has been set, when the air conditioner detected 
that there is no people in the room, it will automatically go to the save 
mode. 

53 

Sayfa 59

Turn on I-SENSE function: Turn on the unit, when it is in cooling 
or heating mode, select I-SENSE in the function page, and then press 
“◀” or “▶” to turn on or turn off I-SENSE function. 

Cancel I-SENSE: Same as the method used for turning on I-
SENSE function. 

When selecting I-SENSE in the function page, press “Menu/OK” 
button to enter the setting of I-SENSE mode, it will display as below: 

Fig. 6.13 Setting of I-SENSE mode 
Press “▲” or “▼” button to switch I-SENSE mode. It can 
switch to Smart, Follow, Avoid, and Surround. After selecting the 
proper mode, press “Menu/OK” button to save the setting. 
NOTE: 
① This function can only be set after installing Smart Sensor. 
② Only version 3 and above version support this function. 
6.7 Universal Setting  
Press “Menu/OK” button on the homepage to go to the menu 
page and then select “set’ to enter into set page; please refer to the  

Owner’s Manual 

54 

Sayfa 60

Owner’s Manual 

figure as below: 

Fig. 6.14 Set page  
Below parameters can be set on the set page.  
6.7.1 WiFi Function Setting 
"GREE+" App can be used to control wired controller XE7C-
24/HC. Please scan the QR code or search "GREE+" in the 
application market to download and install it. When "GREE+" App is 
installed, register the account and add the device to achieve long-
distance control and LAN control of Gree smart home appliances. 

App can only set some common functions of wired controller: 
ON/OFF, mode, set temperature, fan speed, etc. 

When using the App for the first time, please reset the WiFi 
function of wired controller (reset WiFi to ex-factory setting):  

Reset WiFi: 
Press “Menu/OK” button on the homepage to go to menu page 
to select “set” to go to the set page; Select “reset WiFi” on the set 
page to go to WiFi reset page. Please refer to the figure as below:  

55 

Sayfa 61

Fig. 6.15 WiFi set page  
Press “◀” or “▶” button to select it: “yes” indicates WiFi resetting. 
When “reset WiFi” on the setting page has changed to “reset 
succeeded” or WiFi icon on the homepage flashes at the interval of 
0.5s, WiFi resetting is succeeded. After that, add devices to the App.  
NOTES:  
① This function is only applicable to wired controller XE7C-24/HC. 
② If the device is offline or router’s name and password have been 

changed, please reset WiFi and add the device again. 
③ WiFi networking performance is related to the distance between 

the wired controller and the router and the obstacles between 
them. During the installation process, the distance between the 
wired controller and the router should be as close as possible, 
and the obstacles should be as little as possible. If the WiFi signal 
is not good, use the WiFi signal enhanced router. The specific 
situation depends on the actual installation. 
④ For more information, please refer to "Help" in App. 

Owner’s Manual 

56 

Sayfa 62

Owner’s Manual 

6.7.2 Time Format Setting  
Users can set 12-hour time format or 24-hour time format. Press   
“▲” or “▼”button on the setting page to select “time format” and then 
press “◀” or “▶” button to select 12-hour time format or 24-hour time 
format.  
6.7.3 System Time Setting  
Select “clock” item on the setting page and then press “Menu/OK” 
button to go to time setting page. See the figure as below:  

Fig. 6.16 Clock setting page  
Press “◀” or “▶” button to select setting items: hour, minute, year, 
month and day; press “▲” or “▼”button to set the value. When setting 
is finished, press “Menu/OK” button to save the setting.  
6.7.4 Temperature Precision Setting 
Users can set the temperature precision as 0.5°C or 1°C. Press  
“▲” or “▼” button to select “set temperature precision” on the setting 
page and then press “ ◀” or “ ▶” button to select two different 
temperature precision.  

57 

Sayfa 63

Owner’s Manual 

6.7.5 Temperature Unit Setting  
Users can set the temperature unit on the wired controller as °C 
or℉. Press “▲” or “▼”button to select “In℉” on the setting page; press 
“◀” or “▶” button to select whether use℉. If not, the temperature unit 
on the wired controller will switch to °C.  
6.7.6 Child Lock Setting  
Users can set the child lock on the setting page. When child lock 
is turned on, other buttons are all invalid. At the same time, LCD 
flashes to display the icon“
”for three times. Users need to unlock 
it according to the instruction in the pop-up widow. Press “▲” or “▼”to 
select “ lock” on the setting page and then press “◀” or “▶” button to 
turn on the child lock or not.  
6.7.7 Display Language Setting  
Users can select the language on the setting page. Press  “▲” 
or “▼”button to select “language selection”; press “menu/OK” button 
to go to language setting page. Press “▲” or “▼” button to select the 
required language item. Finally, press “menu/OK” button to save the 
setting.  
6.8 Timer Setting  
The wired controller can set four times of timer: daily timer, 
weekly timer, two-week timer and timer off. Users select the timer icon 
on the menu page and then press “▲” or “▼”button to select the timer. 
Press “◀” or “▶” button to turn on or turn off this timer. Press “Menu/OK” 
button to go to corresponding timer setting page. The figure is as 
below:  

58 

Sayfa 64

Owner’s Manual 

Fig. 6.17 Timer setting page  
6.8.1 Daily Timer Setting  
As for the daily timer setting, users can set four independent 
timer periods. Only when the timer period is turned on, it is valid. As 
for each timer period, it can set time, on/off, working mode, set 
temperature and fan speed. See the figure as below:   

Fig. 6.18 Daily timer setting page  
When entering to daily timer setting page, press “◀” or “▶”  
button to select the setting item, press “▲” or “▼”button to set the value 
and then press “Menu/OK” button to save the setting.   

59 

Sayfa 65

Owner’s Manual 

6.8.2 Weekly Timer Setting  
Users can set the timer for each day in a week, and they can also 
set 4 timer periods for each day. The unit will execute corresponding 
timer setting on weekly basis circularly. When entering weekly timer 
setting page, press “◀” or “▶” button to select one day in a week, press 
“Menu/OK” button to go to its timer setting, press “◀” or “▶” button to 
select the item, press “▲” or “▼”button again to adjust the setting 
content and then press “Menu/OK” button to save the setting. When 
all timer settings have been saved, press “
”button to exit from 
this page. Please refer to the figure as below:  

60 

Sayfa 66

Owner’s Manual

Weekly
Week SUN MON TUE WED THU FRI SAT
Sch Time On/Off Mode Temp Fan
1 Off 0:00 Off Cool 20℃ Auto
2 Off 0:00 Off Cool 20℃ Auto
3 Off 0:00 Off Cool 20℃ Auto
4 Off 0:00 Off Cool 20℃ Auto
Menu/OK Back
FAN
MENU
OK
SWING
MODE

Enter weekly timer setting page

Press "▲"button or"▼"button to select one day in a week to set timer

Press "▲"button or"▼"button to adjust the setting content

Press "Menu/OK" button to enter timer setting of this day

61

Sayfa 67

Owner’s Manual 

Fig. 6.19 Weekly timer setting  
When entering to weekly timer setting page, press “◀” or “▶”  
button to select the setting item, press “▲” or “▼”button to set the value 
and then press “Menu/OK” button to save the setting.   
6.8.3 Two-week Timer Setting  
Users can set the timer for each day in two weeks and they can 
also set 4 timer periods for each day. The unit will execute 
corresponding timer setting on two-week circularly. Select “two week” 
on the timer interface and then press “Menu/OK” button to enter into 
two-week timer menu. Please refer to the figure as below.  

62 

Sayfa 68

Owner’s Manual 

Fig. 6.20 Two-week timer menu  
Select the item of “two week schedule”, press “Menu/OK” button 
to enter into its setting page, select the item of “current week” and 
then press “◀” or “▶” button can set the current week as the first week 
or the second week.  

When entering two-week timer page, users can press “ ▲” or 
“▼”button to select the setting items for two-week time, and then press 
“Menu/OK” button to go to two-week timer setting page. When 
entering two-week timer setting page, press “◀” or “▶” button to select 
one day in two weeks, press “Menu/OK” button to go to its timer 
setting, press “◀” or “▶” button to select the item, press “▲” or “▼”button 
again to adjust the setting content and then press “Menu/OK” button 
to save the setting. Press “
” button to exit from this page. Please 
refer to the figure as the Fig. Weekly timer setting. 
6.8.4 Timer OFF Setting  
As for timer OFF, the unit will be turned off after operating for“x” 
hours. If the timer off has been set, when the unit has been turned on 

63 

Sayfa 69

every time, it will be turned off automatically after operation for “x” 
hours.  

When entering timer OFF page, press “▲” or “▼”button to set the 
time for timer OFF, set the time change at the interval of 0.5h and 
then press “Menu/OK” button to save the setting. If not save the 
setting, press “
” button turn it back. Please refer to the figure as 
below. 

Fig. 6.21 Timer OFF Setting Page 
NOTE: The time is 12-hour format. The time on the timer setting 
page is displayed by 12-hour format.  
7 Error Display 
When there is error during operation, the temperature display 
zone on the wired controller will show the error code. If several errors 
happen at the same time, error codes will show on the display 
repeatedly.  

NOTE: If error occurs, please turn off the unit and ask for 
professionals to repair it.  

Owner’s Manual 

64 

Sayfa 70

Owner’s Manual 

Fig.7.1shows the display of outdoor unit high pressure protection 
when unit is on. 

Fig. 7.1 Display of Outdoor Unit High Pressure Protection 
7.1 Table of Error Codes for VRF and Big Duct Unit 
7.1.1 Table of Error Codes for Outdoor Unit 

Error Code 
Content 
Error 
Code 
Content 

E0 
Outdoor Unit Error 
J9 
System Pressure Under-

Ratio Protection 

65 

Sayfa 71

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

E1 
High Pressure 

Protection 
JA 
Protection of Abnormal 

Pressure 

E2 
Discharge Low 
Temperature Protection 
JC 
Protection of Water Flow 

Switch 

E3 
Low Pressure 

Protection 
JL 
Protection of Low High-

pressure 

Excess Discharge 
Temperature Protection 

JE 
Oil Return Pipe is 

E4 

Blocked 

of Compressor 

Low Temperature 
Protection of Driver 

Ed 

JF 
Oil Return Pipe is Leaking 

Module 

F0 
Bad Performance of the 

Outdoor Mainboard 
JJ 
Low Water-in 
Temperature Protection 

F1 
High Pressure Sensor 

Error 
b1 
Outdoor Ambient 
Temperature Sensor Error 

Inlet Tube Temperature 

b2 
Defrosting Temperature 

F2 

Sensor Error of Plate 
Type Heat Exchanger 

Sensor 1 Error 

F3 
Low Pressure Sensor 

Error 
b3 
Defrosting Temperature 

Sensor 2 Error 

Outlet Tube 
Temperature Sensor 

b4 
Subcooler Liquid-out 
Temperature Sensor Error 

F4 

Error of Plate Type 

Heat Exchanger 

66 

Sayfa 72

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

Compressor 1 
Discharge Temperature 

F5 

Sensor Error 

Compressor 2 
Discharge Temperature 

F6 

Sensor Error 

Compressor 3 
Discharge Temperature 

F7 

Sensor Error 

Compressor 4 
Discharge Temperature 

F8 

Sensor Error 

Compressor 5 
Discharge Temperature 

F9 

Sensor Error 

Compressor 6 
Discharge Temperature 

FA 

Sensor Error 

FC 
Compressor 2 Current 

Sensor Error 
bH 
System Clock Malfunction 

FL 
Compressor 3 Current 

Sensor Error 
bE 

FE 
Compressor 4 Current 

Sensor Error 
bF 

b5 
Subcooler Gas-out 
Temperature Sensor Error 

b6 
Gas-liquid Separator Inlet 
Temperature Sensor Error 

Gas-liquid Separator 

b7 

Outlet Temperature 

Sensor Error 

b8 
Outdoor Humidity Sensor 

Error 

b9 
Heat Exchanger Gas-out 
Temperature Sensor Error 

bA 
Oil-return Temperature 

Sensor Error 

Malfunction of Entry Tube 

Temperature Sensor of 

Condenser 

Malfunction of Exit Tube 

Temperature Sensor of 

Condenser 

67 

Sayfa 73

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

High and Low Pressure 
Sensors are Connected 

FF 
Compressor 5 Current 

Sensor Error 
bJ 

Inversely 

FJ 
Compressor 6 Current 

Sensor Error 
bP 
Oil-return 2 Temperature 

Sensor Error 

FP 
Malfunction of DC 

motor 
bU 
Oil-return 3 Temperature 

Sensor Error 

Compressor 1 Top 
Temperature Sensor 

bb 
Oil-return 4 Temperature 

FU 

Sensor Error 

Error 

Compressor 2 Top 
Temperature Sensor 

bd 
Air-in Temperature 
Sensor Error of Subcooler 

Fb 

Error 

Mode Exchanger Outlet 

bn 
Liquid-in Temperature 
Sensor Error of Subcooler 

Fd 

Pipe Temperature 

Sensor Error 

Mode Exchanger Inlet 

by 
Water-out Temperature 

Fn 

Pipe Temperature 

Sensor Error 

Sensor Error 

Fy 
Water-in Temperature 

Sensor Error 
P0 
Compressor Drive Board 

Error 

J1 
Compressor 1 Over-

current Protection 
P1 
Compressor Drive Board 

Malfunction 

Protection of Compressor 

J2 
Compressor 2 Over-

current Protection 
P2 

Drive Board Power 

Supply 

68 

Sayfa 74

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

J3 
Compressor 3 Over-

current Protection 
P3 

J4 
Compressor 4 Over-

current Protection 
H0 
Error of Fan Drive Board 

J5 
Compressor 5 Over-

current Protection 
H1 
Malfunction of Fan Drive 

J6 
Compressor 6 Over-

current Protection 
H2 
Protection of Fan Drive 

J7 
4-way Valve Blow-by 
Protection 
GH 
PV DC/DC Protection 

J8 
System Pressure Over-

Ratio Protection 
— 
— 

7.1.2 Table of Error Codes for Indoor Unit 

Error Code 
Content 
Error 
Code 
Content 

L0 
Indoor Unit Error 
dL 
Outlet Air Temperature 
Sensor Error 

L1 
Indoor Fan Protection 
dE 
Indoor Unit CO2 Sensor 
Error 

L2 
E-heater Protection 
db 
Special Code: Field 
Debugging Code 
L3 
Water Full Protection 
dn 
Swing Assembly Error 

L4 
Wired Controller Power 
Supply Error 
dy 
Water Temperature 
Sensor Error 

L5 
Anti-Frosting Protection 
y1 
Inlet Pipe Temperature 
Sensor 2 Error 

Protection of Compressor 

Drive Board Module 

Reset 

Board 

Board Power Supply 

69 

Sayfa 75

Error Code 
Content 
Error 
Code 
Content 

L6 
Mode Conflict 
y2 
Outlet Pipe Temperature 
Sensor 2 Error 

L7 
No Master Indoor Unit 
Error 
y3 
Middle Tube Temperature 
Sensor 2 Error 

L8 
Power Insufficiency 
Protection 
y7 
Fresh Air Inflow 
Temperature Sensor Error 

Quantity Of Group 
Control Indoor Units 
Setting Error 

L9 

LA 
Indoor Units 
Incompatibility Error 
y9 
Outdoor Air Box Sensor 
Error 

LH 
Low Air Quanlity 
Warning 
yA 
IFD error 

LC 
Outdoor-Indoor 
Incompatibility Error 
yH 
Fresh Air-out Sensor 
Error 

LF 
Shunt Valve Setting 
Error 
yC 
Air-return Inlet Sensor 
Error 

LJ 
Wrong Setting of 
Function DIP Switch 
yL 
Air-return Outlet 
Temperature Sensor Error 

Zero-crossing 
Malfunction of PG 
Motor 

LP 

Inconsistent Branch of 
Group-controlled Indoor 
Units in Heat Recovery 
System 

LU 

Owner’s Manual 

y8 
Indoor Air Box Sensor 
Error 

yE 
High Liquid Level Switch 
Error 

yF 
Low Liquid Level Switch 
Error 

70 

Sayfa 76

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

Inconsistency of Group-
controlled Indoor Units 
in Reheat 
Dehumidification 
System 

Lb 

Ld 
Indoor Fan 2 Error 
o1 
Low Voltage of IDU Bus 
Bar 

Ln 
Lift Panel Return Air 
Frame Reset Exception 
o2 
High Voltage of IDU Bus 
Bar 

d1 
Indoor Unit PC-Board 
Error 
o3 
IDU IPM Module 
Protection 

d3 
Ambient Temperature 
Sensor Error 
o4 
IDU Startup Failure 

d4 
Inlet Pipe Temperature 
Sensor Error 
o5 
IDU Overcurrent 
Protection 

Malfunction of Middle 
Tube Temperature 
Sensor 

d5 

Outlet Pipe 
Temperature Sensor 
Error 

d6 

d7 
Humidity Sensor Error 
o8 
IDU Driver 
Communication Error 

d8 
Water Temperature 
Abnormality 
o9 

o0 
Motor Drive Error 

o6 
IDU Current Detective 
Electric Circuit Error 

o7 
IDU Losing Step 
Protection 

Communication Error 
between IDU Main 
Control and IDU Drive 
Board 

71 

Sayfa 77

Error Code 
Content 
Error 
Code 
Content 

d9 
Jumper Cap Error 
oA 
High Temperature of IDU 
Module  

dA 
Indoor Unit Hardware 
Address Error 
oC 
IDU Charging Circuit 
Error 

dH 
Wired Controller PC-
Board Error 
ob 
Temperature Sensor Error 
of IDU Module 

dC 
Capacity DIP Switch 
Setting Error 
— 
— 

7.1.3 Table of Debugging Codes 

Error Code 
Content 
Error 
Code 
Content 

Outdoor Unit Capacity 
Code/Jumper Cap 
Setting Error 

U2 

Phase Sequence 
Protection of Power 
Supply 

U3 

U4 
Protection of Lack of 
Refrigerant 
C2 

Owner’s Manual 

Communication between 
indoor unit and outdoor 
unit and the 
communication between 
indoor unit and wired 
controller have 
malfunction 

C0 

C1 
Communication error of 
expansion board 

Communication error 
between master control 
and inverter compressor 
drive 

72 

Sayfa 78

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

Wrong Address of 
Compressor Drive 
Board 

U5 

U6 
Valve Abnormal Alarm 
C4 
Error of Lack of Indoor 
Unit 

U7 
Grid DRED0 Response 
Protection 
C5 
Alarm of Indoor Unit 
Project Number Collision 

U8 
Indoor Unit Tube 
Malfunction 
C6 
Alarm of Wrong Number 
of Outdoor Unit 

U9 
Outdoor Unit Tube 
Malfunction 
C7 
Mode Exchanger 
Communication Error 

Overvoltage Protection 
of DC Bus Bar in Power 
Grid Side 

UA 

Under voltage 
Protection of DC Bus 
Bar in Power Grid Side 

UH 

UC 
Master indoor unit is 
successfully set 
CL 
Rated capacity is too low 

Emergency Operation 
DIP switch setting of 
the compressor is 
wrong 

UL 

UE 
Refrigerant Charging is 
ineffective 
CF 
Error of Multiple Master 
Indoor Unit 

Communication error 
between master control 
and inverter fan motor 
drive 

C3 

CH 
Rated capacity is too high 

CC 
No master control unit 
error 

Communication Failure 
Between Mode 
Exchanger and Indoor 
Unit 

CE 

73 

Sayfa 79

Error Code 
Content 
Error 
Code 
Content 

Indoor Unit 
Identification Error of 
Mode Exchanger 

UF 

UJ 
PV module F0 
protection 
CP 
Error of Multiple Master 
Wired Controller 

Protection shutdown 
error of thermal storage 
module 

UP 

Electronic expansion 
valve leak error of 
thermal storage module 

UU 

Protection without 
shutdown error of 
thermal storage module 

Ub 

Ud 
Grid-connection driver 
board error 
Cn 

Communication error 
between grid-
connection driver board 
and master controller 

Un 

Uy 
PV module overheating 
protection 
— 
— 

Owner’s Manual 

CJ 
System addresses is 
incompatible 

Communication Error 
between Indoor Unit and 
Remote Receiver 

CU 

Cb 
Outflow of Units IP 
Address 

Communication Failure 
Between Mode 
Exchanger and Outdoor 
Unit 

Cd 

Indoor and Outdoor 
Network Error of Mode 
Exchanger 

Communication Error of 
No Master in Mode 
Exchanger 

Cy 

74 

Sayfa 80

Owner’s Manual 

7.1.4 Table of Status Codes 

Error Code 
Content 
Error 
Code 
Content 

A0 
Unit is waiting for 
debugging 
Ay 
Shielding status 

A1 
Check the compressor 
operation parameters 
n3 
Compulsory defrosting 

A2 
After-sales Refrigerant 
Reclaim 
q5 

A3 
Defrosting 
q7 
Select degree Celsius or 
Fahrenheit 

A4 
Oil return 
q8 

A5 
Online Testing 
q9 
Setting of defrosting 
mode 
A8 
Vacuum-pumping Mode 
qL 
Setting of static pressure 

A9 
Operate in Setback 
Function 
qE 
EVI Operating Mode 

AH 
Heating 
qF 
System compulsory 
cooling mode 

AC 
Cooling 
qP 
PV GMV Unit  export 
area setting 

AF 
Fan 
qU 
Grid voltage system 
configuration 

AJ 
Filter Clean Reminder 
qb 
Anti-condensation 
temperature setting 

Setting of ordinary units 
and high sensible heat 
units 

Discharge low 
temperature protection 
revision value b 

75 

Sayfa 81

Error Code 
Content 
Error 
Code 
Content 

AU 
Remote Urgent Stop 
qd 
Setting of target degree 
of super-cooling of ODU 

Ab 
Emergency Stop 
qn 
PV grid-connected 
settings 

Ad 
Operation Restriction 
qy 
Working mode of 
compressor heating belt 
An 
Lock status 
— 
— 
7.2 Table of Display Codes for U-Match Unit 
7.2.1 Table of Error Codes of Outdoor Unit 

Error Code 
Content 
Error 
Code 
Content 

E4 
Discharge Protection 
LA 
Outdoor Fan 2 Error 
H4 
Overload Protection 
L3 
Outdoor Fan 1 Error 

PA 
ODU AC Current 
Protection 
E3 
System Low Pressure 
Protection 

H5 
Module Current 
Protection 
E1 
System High Pressure 
Protection 

P8 
Module Temperature 
Protection 
U3 
DC Bus Voltage Drop 
Error 

E2 
Freeze Protection 
U5 
Current Detecting Error of 
Complete Unit 
L9 
High Power Protection 
PU 
Capacitor Charging Error 

Compressor Phase 
Loss/Phase 
Reversal/Out of Phase 

U2 

Owner’s Manual 

Compressor Phase 
Current Circuit Detecting 
Error 

U1 

76 

Sayfa 82

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

HC 
PFC Overcurrent Error 
H7 
Compressor Non-
synchronism 

PH 
High Voltage Protection 
of DC Bus 
HE 

PL 
Low Voltage Protection 
of DC Bus 
LE 
Compressor Stalling 

Lc 
Startup Failure 
P6 
Drive Board 
Communication Error 

Overcurrent of 
Compressor Phase 
Current 
LF 
Overspeed 
PP 
DC Input Voltage Error 

P0 
Drive Module Reset  
P5 

Compressor DIP 
Switch/Jumper Cap 
Error 

C8 

Drive Board Ambient 
Temperature Sensor 
Error 

PF 

P9 
AC Contactor Protection 
b7 
Gas Valve Temperature 
Sensor Error 

PE 
Temperature Shifting 
Protection 
A5 

Compressor 
Demagnetization 
Protection 

Abnormal Outdoor 
Ambient Temperature 
(heating at too high 
ambient temperature or 
cooling at too low 
ambient temperature) 

Uo 

b5 
Liquid Valve Temperature 
Sensor Error 

Outdoor Condenser Inlet 
Pipe Temperature Sensor 
Error 

77 

Sayfa 83

Error Code 
Content 
Error 
Code 
Content 

Sensor Connection 

Protection (current 
sensor hasn’t been 
connected to 
corresponding U phase 
or V phase) 

Pd 

e3 
Low Pressure Sensor 
Error 
A4 
Refrigerant Temperature 
Sensor Error 

C7 
Outdoor Pipe Middle 
Sensor Error 
A3 
ODU Refrigerant Heater 
Failure 

E1 
High Pressure Switch 2 
Error 
A2 
ODU Refrigerant Heater 
Relay Adhesion Error 

C9 
Compressor Drive 
Storage Chip Error 
E6 
Communication Error 
between ODU and IDU  

Ad 
Outdoor Fan Out-of-
phase Protection 
C4 
ODU Jumper Cap Error 

AE 
Outdoor Fan Current 
Detecting Circuit Error 
dJ 

Ac 
Outdoor Fan Startup 
Failure 
e1 
High Pressure Sensor 
Error 

AJ 
Outdoor Fan Non-
synchronism Protection 
UL 
Outdoor Fan Overcurrent 
Protection 

EL 
Emergency Operation 
Stop 
A1 
Outdoor Fan IPM Module 
Protection 

oE 
Other Error of 
Compressor 
C6 
Discharge Temperature 
Sensor Error 

Owner’s Manual 

Outdoor Condenser 
Outlet Pipe Temperature 
Sensor Error 

A7 

AC Phase Sequence 
Protection (phase loss or 
phase reversal) 

78 

Sayfa 84

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

Compressor Suction 
Temperature Sensor 
Error 

dc 

P7 
Module Temperature 
Sensor Circuit Error  
U7 
4-way Valve 
Commutation Error 

U8 
Zero-crossing Signal 
Error 
Cd 
Abnormal Electrical Level 
of Selected Port 

Outdoor Ambient 
Temperature Sensor 
Error 

F3 

E3 
Refrigerant Lacking 
Protection 
— 
— 

7.2.2 Table of Error Codes of Indoor Unit 

Error Code 
Content 
Error 
Code 
Content 

E0 
Indoor Fan Error 
L1 
Indoor Humidity Sensor 
Error 

Inverter Indoor Fan 
Drive Current Detecting 
Circuit Error 

qA 

Indoor Ambient 
Temperature Sensor 
Error 

C1 

Indoor Evaporator 
Middle Temperature 
Sensor Error 

C2 

Outdoor Condenser 
Middle Pipe Temperature 
Sensor Error 

C3 

EE 
Memory Chip Read and 
Write Error 

Main Control and 
Inverter Indoor Fan Drive 
Communication Error 

qC 

Inverter Indoor Fan Drive 
Module High 
Temperature Protection 

qd 

Inverter Indoor Fan Drive 
Module Temperature 
Sensor Error 

qE 

79 

Sayfa 85

Error Code 
Content 
Error 
Code 
Content 

E9 
IDU Water Full 
Protection 
qF 
Inverter Indoor Fan Drive 
Storage Chip Error 

CJ 
IDU Jumper Cap Error 
qH 
Inverter Indoor Fan Drive 
Charging Circuit Error 

Inverter Indoor Fan 
Drive IPM Module 
Protection 

q3 

Low Voltage Protection 
or Voltage Drop Error of 
Inverter Indoor Fan 
Drive DC Bus 

q0 

High Voltage Protection 
of Inverter Indoor Fan 
Drive DC Bus 

q1 

Inverter Indoor Fan AC 
Current Protection 
(input side) 

q2 

q4 
Inverter Indoor Fan 
Drive PFC Protection 
qb 
Inverter Indoor Fan Non-
synchronism Protection 

q5 
Inverter Indoor Fan 
Startup Failure 
CP 
Multiple Master Wired 
Controllers Error 

q6 
Inverter Indoor Fan 
Out-of-phase Protection 
L5 

q7 
Inverter Indoor Fan 
Drive Module Reset  
L7 
Group-controlled IDU 
Series Inconsistency 

Owner’s Manual 

Inverter Indoor Fan Drive 
AC Input Voltage 
Abnormal Protection 

qL 

Inverter Indoor Fan Drive 
Electric Box 
Temperature Sensor 
Error 

qo 

Inverter Indoor Fan Drive 
AC Input Zero-crossing 
Protection 

qp 

Communication Error 
between Indoor Unit and 
Wired Controller 

C0 

Wired Controller Power 
Supply Overcurrent 
Protection 

80 

Sayfa 86

Owner’s Manual 

Error Code 
Content 
Error 
Code 
Content 

q8 
Inverter Indoor Fan 
Overcurrent Protection 
CE 

q9 
Inverter Indoor Fan 
Power Protection 
dH 
Wired Controller Circuit 
Board Error 

L4 
Wired Controller Power 
Supply Circuit Failure 
Lb 

L6 
Group-controlled IDU 
Quantity Inconsistency 
— 
— 

7.2.3 Table of Status Codes 

Status Code 
Content 
Status 

CL 
Auto clean 
d1 
DRED operation mode 1 

Fo 
Refrigerant recycle 
mode 
d2 
DRED operation mode 2 

H1 
Ordinary defrosting 
status 
d3 
DRED operation mode 3 

Wired Controller 
Temperature Sensor 
Error 

Group-controlled IDU 
Inconsistency of Reheat 
Dehumidification System 

Code 
Content 

81 

Sayfa 87

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070
Tel: (+86-756) 8522218
Fax: (+86-756) 8669426
E-mail: global@cn.gree.com www.gree.com

600005067336