To Users 

Thank you for selecting Gree product. Please read this 
instruction manual carefully before installing and using the product, 
so as to master and correctly use the product. In order to guide you 
to correctly install and use our product and achieve expected 
operating effect, we hereby instruct as below: 
(1) 
This appliance is not intended for use by persons (including 
children) with reduced physical, sensory or mental capabilities, 
or lack of experience and knowledge, unless they have been 
given supervision or instruction concerning use of the 
appliance by a person responsibility for their safety. Children 
should be supervised to ensure that they do not play with the 
appliance. 
(2) 
This instruction manual is a universal manual; some functions 
are only applicable to particular product. All the illustrations and 
information in the instruction manual are only for reference, 
and control interface should be subject to actual operation. 
(3) 
In order to make the product better, we will continuously 
conduct improvement and innovation. If there is adjustment in 
the product, please subject to actual product. 
(4) 
If the product needs to be installed, moved or maintained, 
please contact our designated dealer or local service center for 
professional support. Users should not disassemble or 
maintain the unit by themselves, otherwise it may cause 
relative damage, and our company will bear no responsibilities. 

Sayfa 3

This marking indicates that this product 
should not be disposed with other 
household wastes throughout the EU. To 
prevent possible harm to the environment 
or human health from uncontrolled waste 
disposal, recycle it responsibly to promote 
the 
sustainable 
reuse 
of 
material 
resources. To return your used device, 
please use the return and collection 
systems or contact the retailer where the 
product was purchased. They can take this 
product for environmental safe recycling. 
Special Functions and Instructions 

Sensor 
Function 

Temperature sensor 
Detect the indoor ambient temperature. 

Humidity sensor 
Detect the indoor ambient humidity. 

Infrared receive 
Receive the infrared signal sent from the remote 
controller. 
 
 
 

Sayfa 4

1 Safety Notices (Please be sure to abide them) ....... 1 

2 Operation Notices...................................................... 1 

3 Display ........................................................................ 3 

3.1 LCD of Wired Controller ....................................... 4 

3.2 LCD Display Instruction ........................................ 4 

3.3 Instruction of Status Column Icons ....................... 5 

4 Button ......................................................................... 7 

4.1 Button Silk Screen ................................................ 7 

4.2 Buttons Function Instruction ................................. 8 

5 Installation and Commissioning .............................. 9 

5.1 Instruction of Wired Controller ............................ 10 

5.2 Engineering Debugging ...................................... 16 

6 Operation Instruction .............................................. 18 

Contents 

Sayfa 5

6.1 ON/OFF .............................................................. 18 

6.2 Mode Setting ...................................................... 19 

6.3 Temperature Setting ........................................... 20 

6.4 Fan Setting ......................................................... 22 

6.5 Swing Setting ..................................................... 22 

6.6 Function Setting ................................................. 23 

6.7 Universal Setting ................................................ 31 

6.8 Timer Setting ...................................................... 35 

7 Error Display ............................................................ 41 

7.1 Table of Error Codes for VRF and Big Duct Unit 42 

7.2 Table of Display Codes for Packaged Unit ......... 52 

Sayfa 6

Owner’s Manual 

1 Safety Notices (Please be sure to abide them) 

 
WARNING: If not abide them strictly, it may cause severe damage 
to the unit or the people. 

 
NOTE: If not abide them strictly, it may cause slight or medium 
damage to the unit or the people. 

 
This sign indicates that the items must be prohibited. Improper 
operation may cause severe damage or death to people. 

 
This sign indicates that the items must be observed. Improper 
operation may cause damage to people or property. 
 
   WARNING! 
This product can’t be installed at corrosive, inflammable or 
explosive environment or the place with special requirements, such 
as kitchen. Otherwise, it will affect the normal operation or shorten 
the service life of the unit, or even cause fire hazard or serious injury. 
As for the above special places, please adopt special air conditioner 
with anti-corrosive or anti-explosion function.  
2 Operation Notices 
 The power supply for all indoor units must be unified. 
 Prohibit installing the wired controller at wet or sunshine places. 
 Do not knock, throw or frequently disassemble the wired controller. 
 Do not operate the wired controller with wet hands.  
 When two wired controllers control one (or more) indoor unit(s), the 

address of wired controller should be different. 
 Functions with “*” are optional for indoor units. If a function is not 

included in an indoor unit, wired controller can’t set the function, or 

1 

Sayfa 7

setting of this function is invalid to the indoor unit. 
 Please pay attention to below items when matching with VRF unit: 

 
When the system mode priority is the master-slave mode, in 
one system network, you must set one indoor unit as the 
master indoor unit, other indoor units are slave indoor units.  
 
When the system mode priority is the master-slave mode, 
the operation mode of the system is basing on that of the 
master indoor unit. The master indoor unit can be set to any 
mode (including auto mode), while the slave indoor unit can’t 
set to the mode that conflicts with the system mode. 
 
When the system mode priority is: Cooling mode is 
prioritized, heating mode is prioritized, first-set mode is 
prioritized, or last-set mode is prioritized. The indoor unit can 
be set to any mode (excluding auto mode). The indoor unit 
will automatically switch to the system mode, when the 
operation mode of the indoor unit conflicts with the system 
operation mode.  
 
When the system mode priority is the voting mode (indoor 
unit’s capacity is prioritized / number of indoor units is 
prioritized). The indoor unit can be set to any mode 
(excluding the auto mode). The indoor unit will be stopped, 
when the operation mode of the indoor unit conflicts with the 
system operation mode after voting. 
 
System mode priority defaults to master-slave mode, and 
only certain units have other system mode priorities. 
 

Owner’s Manual 

2 

Sayfa 8

Owner’s Manual 

 Hereby, Our company, declares that this product is in compliance 

with the essential requirement and other relevant provisions of RE 
Directive 2014/53/EU. Wireless frequency range: 2412MHz - 
2472MHz. Maximum Transmit Power: 18dBm. 
3 Display  

Fig. 3.1 Appearance of wired controller  
 
 

3 

Sayfa 9

3.1 LCD of Wired Controller  

Fig. 3.2 LCD graphics of wired controller 
3.2 LCD Display Instruction  
Table 3.1 LCD display instruction 

No. 
Name 
Instruction 
1 
Status column 
Display the icon of function that is turned on 
2 
Fan speed 
It is for displaying the fan speed 
3 
Swing 
It is for displaying the current swing status 

4 
Button prompt 
Display the function of MENU/OK button at 

the current page and the settable cursor  

It shows the value of temperature (If the wired 

5 
Temperature 

controller is controlling a fresh air indoor unit, 

display  

it will display FAP). 
6 
Mode 
It shows the operating mode 

It display the date and the time. When it’s 
locating the indoor unit, it displays the project 

7 
Clock display  

No. of current indoor unit.  

4 

Owner’s Manual 

Sayfa 10

Owner’s Manual 

No. 
Name 
Instruction 
NOTE: When wired controller is connected with different indoor units, some 
functions will be different. 
3.3 Instruction of Status Column Icons  
Table 3.2 Instruction of Status Column Icon 
No. 
Symbols 
Name 
Instructions 

1 
 
Air * 
Air status(indoor unit optional 
function) 

2 
 
Remove card 
The card for access control is 
removed 

3 
 
Clean 
Remind to clean the filter 

4 
 
Child lock 
Child lock status 

5 
 
Error 
There are errors for the unit 

6 
 
Health * 
Health function (indoor unit optional 
function) 

7 
 
Defrosting 
Defrosting status of outdoor unit 

8 
 
Master 
Current wired controller connects the 
master indoor unit. 

9 
 
Power off 

10 
 
Absence 
Absence is displayed when this 
function is turned on. 

Memory status (when power 
recovered, indoor unit will resume 
previous setting status) 

memory 

5 

Sayfa 11

No. 
Symbols 
Name 
Instructions 

11 
 
 
Quiet status 
Quiet status (including quiet and auto 
quiet modes) 

12 
 
Energy-

13 
 
Shield 
Shielding status 

14 
 
Slave wired 

15 
 
Sleep 
Sleep status 

16 
 
Time 
Timer status is displayed 

17 
 
X-fan 
X-fan is displayed when this function 
is set. 

18 
 
Group 
control 

19 
 
Valid 
operation 
It’s displayed for valid operation 

20 
 
WiFi 

21 
 
Independent 

22 
 
Auto clean * 
Auto clean status 

Owner’s Manual 

saving 
Energy-saving status of indoor unit 

Slave wired controller (address of 
wired controller is 02). 

controller 

One wired controller controls multiple 
indoor units. 

WiFi status(If the wired controller has 
no WiFi function, it displays only 
when the unit connected to “Unit 
WiFi”). 

swing* 
Independent swing status 

6 

Sayfa 12

Owner’s Manual 

No. 
Symbols 
Name 
Instructions 

23 
 
Setback 
Setback function status 

24 
 
Warning 
Warning status 

25 
 

26 
 
Aux. Heat operating 

NOTE: When wired controller is connected with different indoor units, some 
functions will be different. 
4 Button  
4.1 Button Silk Screen 

Fig. 4.1 Button silk screen  
 
 

Aux. Heat is available 

Aux. Heat* 

7 

Sayfa 13

4.2 Buttons Function Instruction  
Table 4.1 Buttons function instruction 

No. 
Name 
Function 

1 
FAN 
Switch fan speeds: auto, low, medium-low, medium, 
Medium-high and high 
2 
 
(1) Set operation temperature for the indoor unit. 
(2) Move cursor. 
(3) Set and check parameters. 
7 
 

3 
 
On/off button for turn on or turn off the unit; back 
button for return to previous page. 

9 
 
(1) Turn pages, and switch and select the target; 
(2) Move the cursor; 
(3) Set and check parameters. 
4 
 

5 
MODE 
Switch operating modes: Auto, Cool, Dry, Fan, Heat, 
Floor, 3D Heat, etc. 
6 
MENU/OK 
Select mode and confirm parameters. 

8 
SWING 
Set the swing status of central air conditioners. 
 
 
 
 
 

Owner’s Manual 

8 

Sayfa 14

Owner’s Manual 

5 Installation and Commissioning 
Unit: mm 

Fig. 5.1 Dimension of Wired Controller 

Fig. 5.2 Parts and Components of Wired Controller 

9 

Sayfa 15

No. 
1 
2 
3 
4 

Panel of 

Self-tapping screw 

of wired 
controller 
QTY 
1 
4 
2 
1 
5.1 Instruction of Wired Controller 
5.1.1 Requirements for Model Selection of Communication Wire 

Name 

wired 
controller 

ST3.9×25 MA 

Fig. 5.3 Length of communication wire 

10 

Owner’s Manual 

Soleplate 

Screw 
M4×25 

Sayfa 16

Owner’s Manual 

Wire 
material 

Total 
length L 
(m/feet) 

Wire size  
(mm2/AWG) 

Material 
standard 
Remarks 

type 

(1) Total length of 

communication 
line can't 
exceed 250m 
(820-1/5feet). 
(2) The cord shall 

Light/ 
Ordinary 
Polyvinyl 

be circular cord 
(the cores shall 
be twisted 
together).  
(3) If unit is 

chloride 
sheathed 

L≤250m 

2×0.75mm2 

IEC 
60227-
5:2007 

~2×1.25mm2 

(L≤820-

cord. 
(60227 
IEC 52 
/60227 
IEC 53) 

1/5 
feet) 

(2×AWG18~ 

2×AWG16) 

installed in 
places with 
intense 
magnetic field or 
strong 
interference, it is 
necessary to 
use shielded 
wire. 

5.1.2 Requirements for Installation 
(1) 
It is not allowed to install the wired controller in the wet place. 
(2) 
It is not allowed to install the wired controller in the place with 
direct sunlight. 
(3) 
It is not allowed to install the wired controller near the high-

11 

Sayfa 17

temperature object or the place is likely to be spattered with 
water. 
5.1.3 Requirements for Wired Connection 
Network connecting methods between wired controller and 
indoor unit are as below: 

Fig. 5.4 One wired controller controls one indoor unit        

Owner’s Manual 

12 

Sayfa 18

Owner’s Manual 

Fig. 5.5 One wired controller controls multiple VRF indoor units simultaneously 

Fig. 5.6 One wired controller controls multiple Packaged Unit simultaneously 

13 

Sayfa 19

Owner’s Manual 

Instruction for wire connection: 
(1) 
The wiring methods in fig. 5.4 and fig. 5.6 can be adopted for 
the wired controller connecting Packaged Unit. It's suggested 
that the length of communication wire between devices should 
be 8m. 
(2) 
The wiring methods in fig. 5.4 and fig. 5.5 can be adopted for 
the wired controller connecting VRF unit. It's suggested that the 
average length of communication wire between devices should 
be 15m. 
(3) 
Only the wiring methods in fig. 5.4 can be adopted for the wired 
controller connecting Big Duct Type unit or Air-cooled 
Packaged unit, that is, one wired controller can control only one 
indoor unit, cannot control multiple indoor units of different 
systems. 
(4) 
When one wired controller controls multiple indoor units 
simultaneously, the wired controller can connect to any one 
indoor unit, but the connected indoor unit must be the same 
series indoor unit. The total quantity of indoor unit controlled by 
wired controller can't exceed 16 sets, and the connected indoor 
unit must be within the same indoor unit's network. Wire 
controller must set quantity of group control indoor units. 
Please refer to 5.2.2 Parameter Setting. 
(5) 
The terminal of the wire controller is non-polarized and cannot 
be connected to strong electric. 
 
 

14 

Sayfa 20

Owner’s Manual 

NOTE: Wired controller XE7C-23/HC and wired controller XE7C-

23/HC1 only supports one (or more) indoor unit(s) controlled 
by one wired controller. 
5.1.4 Installation 

Fig. 5.7 Installation of Wired Controller 
Fig. 5.7 shows a simple installation course of wired controller, 
and the following points should be noted: 
(1) 
Before installation, please cut off the power supply of indoor 
unit, it is not allowed to operate with power supply; 
(2) 
Pull out the 2-core twisted pair inside the installation hole in the 

15 

Sayfa 21

wall, and thread the wire through the hole in the back of 
soleplate of wired controller; 
(3) 
Stick the soleplate of wired controller on the wall, and use Self-
tapping Screw ST3.9×25 MA or screw M4×25 to fix the 
soleplate with the installation hole of wall; 
(4) 
Connect the 2-core twisted pair to wiring terminal H1 and H2, 
and then tighten the screw; 
(5) 
Arrange the wires in the back of panel, and then buckle the 
panel of wired controller with the soleplate of wired controller. 
5.1.5 Disassembly 

Fig. 5.8 Disassembly of wired controller 
5.2 Engineering Debugging  
5.2.1 Parameter View 
Under on or off status, view unit’s parameters.  
Press “MENU/OK” button on the home page to enter into the 
menu page to select “View” to go to view page shown as below:  

Owner’s Manual 

16 

Sayfa 22

Owner’s Manual 

Select “Parameter View” at the view page to enter into parameter 
view page shown as below.  

NOTES: 
① Under parameter viewing status, the signal from remote 

controller is invalid. 
② When the parameter is invalid, it will display “--”. 
5.2.2 Parameters Setting  
Parameters can be set under on or off status.  
Press “MENU/OK” button on the homepage to enter into menu 

17 

Sayfa 23

page to select “Set” to go to set page. Select “Parameter Setting” at 
the set page to go into parameter setting page. See the figure as 
below.   

After that, press “
” or “
” button to switch the items. Hold it 
can switch it quickly. 

When selecting the parameter, press “ ” or “ ” to switch the 
setting value. Press “MENU/OK” button to save corresponding setting 
items. If the setting can’t be confirmed, switching the item can restore 
the previous setting value.  
NOTES: 

Under parameter setting status, the signal from remote controller 
is invalid. 
6 Operation Instruction  
6.1 ON/OFF 
Press “
” button to turn on the air conditioner. 

Press “
” button again to stop operation.  

Owner’s Manual 

18 

Sayfa 24

Owner’s Manual 

ON and OFF interfaces are shown as below:   

   Fig. 6.1 ON interface                Fig. 6.2 OFF interface  
6.2 Mode Setting 
Under On status, pressing “MODE” button can set modes 
circularly: 

NOTES: 
① The available modes are different for different models. The wired 

controller will automatically select mode setting range according 
to the model of indoor unit. 
② When the wired controller controls VRF unit and the system 

19 

Sayfa 25

mode priority is the master-slave mode, only the master indoor 
unit can set the auto mode. 
③ Under Auto mode, if the indoor unit is cooling, the icons “
” 

and “
” will light up; if the indoor unit is Heating, the icons “
” 

and “
” will light up. 
6.3 Temperature Setting 
Press “
 ” or “
 ” button under on status to increase or 
decrease set temperature by 0.5°C/1°C or 1°F; hold “
 ” or “
 ” 
button to increase or decrease set temperature by 0.5°C/1°C or 1°F 
every 0.3s. Please refer to 6.7.4 for the setting method of the 
temperature setting interval in Celsius. 

Under Dry mode, when temperature is 16°C or 61°F, 
continuously press “
 ” button twice to decrease temperature to 
12°C or 54°F (when save function is activated, the temperature under 
Dry mode can’t be adjusted to 12°C or 54°F). 

When the control method under Dry mode is humidity control, 
press “
” or “
” button to adjust the set humidity at 5% intervals. 
The humidity setting range is 45%~75%, and the default value is 65%. 
The humidity control method under Dry mode can only be set for the 
unit with this function. Please refer to 5.2.2 Parameter Setting for the 
setting method. 
NOTES: 
① Only when the wired controller controls Packaged Unit indoor 

units, the setting temperature can be adjusted by pressing “
” 

Owner’s Manual 

20 

Sayfa 26

Owner’s Manual 

or “
” under Auto mode. 
② When Absence function is activated, the setting temperature 

cannot be adjusted by pressing “
” or “
”.  
③ When the wired controller is connected with a Fresh Air Indoor 

Unit, fresh air indoor unit code “FAP” will be displayed as shown 
below. Setting temperature won’t be displayed and can’t be 
adjusted via “
” or “
” button. The air outlet temperature in 
cooling or heating can only be set in the parameter setting status. 

21 

Sayfa 27

6.4 Fan Setting 
Under On status, pressing “FAN” button can set fan speeds 
circularly as: 

NOTES:  
① Under Dry mode, fan speed is low and can’t be adjusted. 
② When the wired controller is connected with a Fresh Air Indoor 

Unit, fan speed of indoor unit will be high fan speed only. Fan 
speed of indoor unit can’t be adjusted via “FAN” button. 
③ If indoor unit’s fan speed is set auto, indoor unit will change fan 

speed automatically according to room temperature in order to 
make the room temperature more stable and comfortable. 
6.5 Swing Setting 
(1) 
Up&down Swing : 
The up&down swing has two modes: simple swing and fixed-
angle swing. Select the fixed-angle swing on the function page, and 
press “ ” or “ ” buttons to turn on or turn off the fixed-angle swing. 
Simple swing and fixed-angle swing can be switched.  

Under on status, press “SWING” button on the homepage to 
enter into swing setting:  
1)When the simple swing is set, press “SWING” button to turn on or 
turn off the up&down swing.  

Owner’s Manual 

22 

Sayfa 28

Owner’s Manual 

2)When the fixed-angle swing is set, press “SWING” button to 
switch swing statuses circularly as below:  

(2) 
Left&right swing*: 
The left&right swing has two modes: simple swing and fixed-
angle swing. Select the fixed-angle swing on the function page, and 
press “ ” and “ ” buttons to turn on or turn off the fixed-angle swing. 
Simple swing and fixed-angle swing can be switched.  

Under on status, press “SWING” button on the homepage to 
enter into swing setting, and then press “ ” and “ ” button to switch 
to the left&right swing setting:  
1)When the simple swing is set, press “SWING” button to turn on or 
turn off the left&right swing.  
2)When the fixed-angle swing is set, press “SWING” button to 
switch swing statuses circularly as below:  

 
6.6 Function Setting  
Press “MENU/OK” button on the homepage to enter menu page 
and then select “Function” to go to function page. See the figure as 
below.   

23 

Sayfa 29

Fig. 6.3 Function page  
Press “
” or “
” button to switch the items; press “ ” and “ ” 
button to turn on or turn off corresponding function. “ON” indicates 
the function is turned on; “OFF” indicates the function turned off; 
press “
” button to turn back to previous page.  
Some functions are with more parameters and “MENU/OK” 
button can be used for setting detailed parameters. 

Fig. 6.4 Function with detailed setting 
 

Owner’s Manual 

24 

Sayfa 30

Owner’s Manual 

As for some functions, only the on/off status is displayed at the 
switch button. It needs to press “MENU/OK” button to enter into 
detailed setting:  

Fig. 6.5 Functions whose on/off status is only displayed  
NOTE:  

The function under some circumstances is invalid and displayed 
in grey. Press “
” or “
” button to skip this function.  
6.6.1 Turbo Setting 
Turbo fan Function: Turn on the highest fan speed, and then 
turbo fan will be displayed on the homepage.  

Turn on turbo fan Function: Under on status, select turbo fan on 
the function page and press “ ” or “ ” button to turn on or turn off the 
turbo fan. When turbo fan is turned on, “turbo fan” will be displayed 
at the fan speed area on the homepage. 

Cancel turbo fan Function: Same as the method used for turning 
on the turbo Fan Function.  

You can also press “FAN” button on the home page to cancel the 
turbo fan and then switch to the auto fan.  

25 

Sayfa 31

NOTES:  
① Under Dry mode, fan speed is low and can’t be adjusted. 
② When the wired controller is connected with a Fresh Air Indoor 

Unit, fan speed of indoor unit will be high fan speed only. Fan 
speed of indoor unit can’t be adjusted via “FAN” button. 
③ If indoor unit’s fan speed is set auto, indoor unit will change fan 

speed automatically according to room temperature in order to 
make the room temperature more stable and comfortable. 
6.6.2 Save Setting 
Save function: Air conditioner can be operated in small 
temperature range by setting the minimum temperature under 
Cooling and Dry modes and setting maximum temperature under 
Heating, 3D Heating and Space Heating modes. Thus, energy saving 
can be realized. 

Turn on save mode: Under on status, select save function on the 
function page and press “ ” or “ ” button to turn on or turn off the 
save function.  

Cancel save mode: Same as the method used for turning on the 
save function.  

When selecting save function on the function page, press 
“MENU/OK” button to set temperature for save function. The display 
is as below:  

Owner’s Manual 

26 

Sayfa 32

Owner’s Manual 

Fig. 6.6 Temperature setting for save function 
Press “
” or “
” button to switch items. When selecting the 
first item, press “ ” or “ ” button to switch modes; when selecting the 
second item, press “ ” or “ ” button to switch temperature lower limit 
and upper limit value. Press “MENU/OK” button to save the setting 
and then turn back to the previous page.  

 When save function is turned on, icon “
” is displayed under 
all modes at on and off statuses.  

 
NOTE: 

When the save function is turned on and then set temperature 
exceeds the limit value for save function, “
” icon blinks three times 
and then buzzer will give out two sounds successively.  
6.6.3 Filter Clean Reminder Setting 
Filter Clean Reminder Function: The unit will remember its own 
operating time. When the setting time is over, this function will remind 
you to clean the filer. A dirty filter will result in bad heating and cooling 

27 

Sayfa 33

performance, abnormal protection, bacteria gathering, etc. 

Select “Clean Remind” on the function page and press 
“MENU/OK” button to go to filter clean reminder setting page. Refer 
to the figure as below:  

Fig. 6.7 Filter clean reminder setting 
Press “
” or “
” button to switch items. When selecting the 
first item, press “ ” or “ ” button to turn on or turn off this function; 
when selecting the second item, press “ ” or “ ” button to switch 
current environmental cleanliness (switch among level 1, level 2 and 
level 3. There are for good, general and bad cleanliness); when 
selecting the third item, press “ ” or “ ” button to adjust the cleaning 
period . Press “MENU/OK” button to save the setting and then turn 
back to the previous page. 

There are four circumstances while cleaning period Setting: 

Turn off clean reminder; 
Light pollution: When current cleanliness is “1”, the setting range 
for the clean cycle is 5500h-10000h. After each pressing of “ ” button, 

Owner’s Manual 

28 

Sayfa 34

Owner’s Manual 

the accumulated time will increase 500h. When the time exceeds the 
maximum value, it will turn back to the minimum value.  

Medium pollution: When current cleanliness is “2”, the setting 
range for the clean cycle is 1400h-5000h. After each pressing of “ ” 
button, the accumulated time will increase 400h. When the time 
exceeds the maximum value, it will turn back to the minimum value.  

Serious pollution: When current cleanliness is “3”, the setting 
range for the clean cycle is 100h-1000h. After each pressing of “ ” 
button, the accumulated time will increase 100h. When the time 
exceeds the maximum value, it will turn back to the minimum value.  
NOTE:  

When clean time is reached, icon “
” at the status column will 
be displayed. The reminding will pop up at the home page to remind 
users to clean the filter. Click “Done” or “Skip” to cancel the display. 
At the same time, the accumulated time for “filter clean reminder” will 
be cleared and the time will be counted again.  
6.6.4 Setback Function 
In unit off status with setback function activated, the unit will 
operate in heating mode automatically when indoor temperature is 
lower than temperature lower limit for setback function and operate 
in cooling mode automatically when indoor temperature is higher than 
temperature upper limit for setback function, so as to keep indoor 
temperature within the temperature upper and lower limit range for 
setback function.  

When turning on the setback function, the icon “
 ” will be 

29 

Sayfa 35

displayed on the homepage.  

Under off status, when setback function is operating, the icon 
“
” blinks.  

As for setting related parameters of setback, it needs to go to 
user parameters page. Please refer to 5.2.2 parameters setting for 
the method.  

Turn on setback function: Under on or off status, select setback 
function on the user parameter page, and press “ ” or “ ” button to 
turn on or turn off the setback function. Press “MENU/OK” button to 
save the setting.    

Cancel setback function: Same as the method used for turning 
on the setback.  

Set setback temperature: 
Setback Upper Temp Limit: select “Upper Temp Limit of Setback” 
on the user parameters page, and press “ ” or “ ” button to adjust 
the upper temperature limit of setback function. Press “MENU/OK” 
button to save the setting. 

Setback Lower Temp Limit: select “Lower Temp Limit of Setback” 
on the user parameter page, and press “ ” or “ ” button to adjust the 
lower temperature limit of setback function. Press “MENU/OK” button 
to save the setting. 
NOTES:  
① Setback function is forbidden as defaulted;  
② When the slave indoor unit is operating in setback function, it 

cannot operate in the mode which is in conflict with that of master 

Owner’s Manual 

30 

Sayfa 36

Owner’s Manual 

indoor unit. 
③ If you want to activate setback function, you cannot use the wired 

controllers of other models as the master wired controller or 
slave master controller. 
④ When all shield function of remote monitor or central controller is 

turned on, the wired controller can’t enter or exits from the 
setback function. 
⑤ When the unit is operating at setback function, the slave wired 

controller cannot set save function and doesn’t display or receive 
save setting. 
6.7 Universal Setting  
Press “MENU/OK” button on the homepage to go to the menu 
page and then select “Set” to enter into set page; please refer to the  
figure as below: 

Fig. 6.8 Set page  
Below parameters can be set on the set page.  
 
 

31 

Sayfa 37

6.7.1 WiFi Function Setting 
“GREE+” App can be used to control wired controller XE7C-
23/HC and wired controller XE7C-23/HC1. Please scan the QR code 
or search “GREE+” in the application market to download and install 
it. When “GREE+” App is installed, register the account and add the 
device to achieve long-distance control and LAN control of Gree 
smart home appliances. 

App can only set some common functions of wired controller: 
ON/OFF, mode, set temperature, fan speed, etc. 

When using the App for the first time, please reset the WiFi 
function of wired controller (Reset WiFi to ex-factory setting):  

Reset WiFi: 
Press “MENU/OK” button on the homepage to go to menu page 
to select “Set” to go to the set page; Select “Reset WiFi” on the set 
page to go to WiFi reset page. Please refer to the figure as below:  

Fig. 6.9 WiFi set page  
Press “ ” or “ ” button to select it: “yes” indicates WiFi resetting. 

Owner’s Manual 

32 

Sayfa 38

Owner’s Manual 

When “Reset WiFi” on the setting page has changed to “reset 
succeeded” or WiFi icon on the homepage flashes at the interval of 
0.5s, WiFi resetting is succeeded. After that, add devices to the App.  
NOTES:  
① This function is only applicable to wired controller XE7C-23/HC 

and wired controller XE7C-23/HC1. 
② If the device is offline or router’s name and password have been 

changed, please reset WiFi and add the device again. 
③ WiFi networking performance is related to the distance between 

the wired controller and the router and the obstacles between 
them. During the installation process, the distance between the 
wired controller and the router should be as close as possible, 
and the obstacles should be as little as possible. If the WiFi signal 
is not good, use the WiFi signal enhanced router. The specific 
situation depends on the actual installation. 
④ For more information, please refer to “Help” in App. 
⑤ This function only supports 2.4GHz frequency WiFi. 
6.7.2 Time Format Setting  
Users can set 12-hour time format or 24-hour time format. Press 
“
”or “
” button on the setting page to select “Time Format” and 
then press “ ” or “ ” button to select 12-hour time format or 24-hour 
time format.  
 
 

33 

Sayfa 39

6.7.3 System Time Setting  
Select “Clock” item on the setting page and then press 
“MENU/OK” button to go to time setting page. See the figure as below:  

Fig. 6.10 Clock setting page  
Press “ ” or “ ” button to select setting items: hour, minute, year, 
month and day; press “
 ” or “
 ” button to set the value. When 
setting is finished, press “MENU/OK” button to save the setting.  
6.7.4 Temperature Setting Precision(°C) 
Users can set the temperature precision as 0.5°C or 1°C. Press  
“
 ”or “
 ” button to select “Temp Setting Precision(°C)” on the 
setting page and then press “ ” or “ ” button to select two different 
temperature precision.  
6.7.5 Temperature Unit Setting  
Users can set the temperature unit on the wired controller as °C 
or °F. Press “
”or “
” button to select “°C/°F” on the setting page; 
press “ ” or “ ” button to select °C or °F.  
 
 

Owner’s Manual 

34 

Sayfa 40

Owner’s Manual 

6.7.6 Display Language Setting  
Users can select the language on the setting page. Press “
” 
or “
 ” button to select “Language Selection”; press “MENU/OK” 
button to go to language setting page. Press “
”or “
” button to 
select the required language item. Finally, press “MENU/OK” button 
to save the setting.  
6.8 Timer Setting  
The wired controller can set four times of timer: daily timer, 
weekly timer, two-week timer and timer off. Users select the timer icon 
on the menu page and then press “
” or “
” button to select the 
timer. Press “ ” or “ ” button to turn on or turn off this timer. Press 
“MENU/OK” button to go to corresponding timer setting page. The 
figure is as below:  

Fig. 6.11 Timer setting page  
6.8.1 Daily Timer Setting  
As for the daily timer setting, users can set four independent 
timer periods. Only when the timer period is turned on, it is valid. As 

35 

Sayfa 41

for each timer period, it can set time, on/off, working mode, set 
temperature and fan speed. See the figure as below:   

Fig. 6.12 Daily timer setting page  
When entering to daily timer setting page, press “ ” or “ ”  
button to select the setting item, press “
” or “
” button to set the 
value and then press “MENU/OK” button to save the setting.   
6.8.2 Weekly Timer Setting  
Users can set the timer for each day in a week, and they can also 
set 4 timer periods for each day. The unit will execute corresponding 
timer setting on weekly basis circularly. When entering weekly timer 
setting page, press “ ” or “ ” button to select one day in a week, 
press “MENU/OK” button to go to its timer setting, press “ ” or “ ” 
button to select the item, press “
” or “
” button again to adjust the 
setting content and then press “MENU/OK” button to save the setting. 
When all timer settings have been saved, press “
” button to exit 
from this page. Please refer to the figure as below:  

Owner’s Manual 

36 

Sayfa 42

Owner’s Manual

Weekly
Week SUN MON TUE WED THU FRI SAT
Sch Time On/Off Mode Temp Fan
1 Off 0:00 Off Cool 20°C Auto
2 Off 0:00 Off Cool 20°C Auto
3 Off 0:00 Off Cool 20°C Auto
4 Off 0:00 Off Cool 20°C Auto

Menu/OK Back
FAN
MENU
OK
SWING
MODE

Enter weekly timer setting page

Press " < "button or" > "button
to select one day in a week to set timer

Press " ^ "button or" \ " button to
adjust the setting content

Press "MENU/OK" button to enter
timer setting of this day

37

Sayfa 43

Owner’s Manual 

Fig. 6.13 Weekly timer setting  
When entering to weekly timer setting page, press “ ” or “ ”  
button to select the setting item, press “
” or “
” button to set the 
value and then press “MENU/OK” button to save the setting.   
6.8.3 Two-week Timer Setting  
Users can set the timer for each day in two weeks and they can 
also set 4 timer periods for each day. The unit will execute 
corresponding timer setting on two-week circularly. Select “two week” 
on the timer interface and then press “MENU/OK” button to enter into 
two-week timer menu. Please refer to the figure as below.  

38 

Sayfa 44

Owner’s Manual 

Fig. 6.14 Two-week timer menu  
Select the item of “two week schedule”, press “MENU/OK” button 
to enter into its setting page, select the item of “current week” and 
then press “ ” or “ ” button can set the current week as the first week 
or the second week.  

When entering two-week timer page, users can press “
” or “
” 
button to select the setting items for two-week time, and then press 
“MENU/OK” button to go to two-week timer setting page. When 
entering two-week timer setting page, press “ ” or “ ” button to select 
one day in two weeks, press “MENU/OK” button to go to its timer 
setting, press “ ” or “ ” button to select the item, press “
” or “
” 
button again to adjust the setting content and then press “MENU/OK” 
button to save the setting. Press “
” button to exit from this page. 
Please refer to the figure as the Fig. Weekly timer setting. 
 
 

39 

Sayfa 45

6.8.4 Timer OFF Setting  
As for timer OFF, the unit will be turned off after operating for “x” 
hours. If the timer off has been set, when the unit has been turned on 
every time, it will be turned off automatically after operation for “x” 
hours.  

When entering timer OFF page, press “
” or “
” button to set 
the time for timer OFF, set the time change at the interval of 0.5h and 
then press “MENU/OK” button to save the setting. If not save the 
setting, press “
” button turn it back. Please refer to the figure as 
below. 

Fig. 6.15 Timer OFF Setting Page 
NOTE: The time is 12-hour format. The time on the timer setting 
page is displayed by 12-hour format.  
 
 

Owner’s Manual 

40 

Sayfa 46

Owner’s Manual 

7 Error Display 
When there is error during operation, the temperature display 
zone on the wired controller will show the error code. If several errors 
happen at the same time, error codes will show on the display 
repeatedly.  

NOTE: If error occurs, please turn off the unit and ask for 
professionals to repair it.  

Fig.7.1 shows the display of outdoor unit high pressure 
protection when unit is on. 

Fig. 7.1 Display of Outdoor Unit High Pressure Protection 

41 

Sayfa 47

7.1 Table of Error Codes for VRF and Big Duct Unit 
7.1.1 Table of Error Codes for Outdoor Unit 
Error 
Code 
Content 
Error 
Code 
Content 

E0 
Outdoor Unit Error 
J9 
System Pressure Under-
Ratio Protection 

E1 
High Pressure Protection 
JA 
Protection of Abnormal 
Pressure 

E2 
Discharge Low 
Temperature Protection 
JC 
Protection of Water Flow 
Switch 

E3 
Low Pressure Protection 
JL 
Protection of Low High-
pressure 

Excess Discharge 
Temperature Protection of 
Compressor 

E4 

Low Temperature 
Protection of Driver 
Module 

Ed 

F0 
Bad Performance of the 
Outdoor Mainboard 
JJ 
Low Water-in Temperature 
Protection 

F1 
High Pressure Sensor 
Error 
b1 
Outdoor Ambient 
Temperature Sensor Error 

Inlet Tube Temperature 
Sensor Error of Plate Type 
Heat Exchanger 

F2 

F3 
Low Pressure Sensor 
Error 
b3 
Defrosting Temperature 
Sensor 2 Error 

Owner’s Manual 

JE 
Oil Return Pipe is Blocked 

JF 
Oil Return Pipe is Leaking 

b2 
Defrosting Temperature 
Sensor 1 Error 

42 

Sayfa 48

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

Outlet Tube Temperature 
Sensor Error of Plate Type 
Heat Exchanger 

F4 

F5 
Compressor 1 Discharge 
Temperature Sensor Error 
b5 
Subcooler Gas-out 
Temperature Sensor Error 

F6 
Compressor 2 Discharge 
Temperature Sensor Error 
b6 
Gas-liquid Separator Inlet 
Temperature Sensor Error 

F7 
Compressor 3 Discharge 
Temperature Sensor Error 
b7 

F8 
Compressor 4 Discharge 
Temperature Sensor Error 
b8 
Outdoor Humidity Sensor 
Error 

F9 
Compressor 5 Discharge 
Temperature Sensor Error 
b9 
Heat Exchanger Gas-out 
Temperature Sensor Error 

FA 
Compressor 6 Discharge 
Temperature Sensor Error 
bA 
Oil-return Temperature 
Sensor Error 

FC 
Compressor 2 Current 
Sensor Error 
bH 
System Clock Malfunction 

FL 
Compressor 3 Current 
Sensor Error 
bE 

FE 
Compressor 4 Current 
Sensor Error 
bF 

FF 
Compressor 5 Current 
Sensor Error 
bJ 

b4 
Subcooler Liquid-out 
Temperature Sensor Error 

Gas-liquid Separator 
Outlet Temperature Sensor 
Error 

Malfunction of Entry Tube 
Temperature Sensor of 
Condenser 

Malfunction of Exit Tube 
Temperature Sensor of 
Condenser 

High and Low Pressure 
Sensors are Connected 
Inversely 

43 

Sayfa 49

Error 
Code 
Content 
Error 
Code 
Content 

FJ 
Compressor 6 Current 
Sensor Error 
bP 
Oil-return 2 Temperature 
Sensor Error 

FP 
Malfunction of DC motor 
bU 
Oil-return 3 Temperature 
Sensor Error 

FU 
Compressor 1 Top 
Temperature Sensor Error 
bb 
Oil-return 4 Temperature 
Sensor Error 

Fb 
Compressor 2 Top 
Temperature Sensor Error 
bd 
Air-in Temperature Sensor 
Error of Subcooler 

Mode Exchanger Outlet 
Pipe Temperature Sensor 
Error 

Fd 

Mode Exchanger Inlet 
Pipe Temperature Sensor 
Error 

Fn 

Fy 
Water-in Temperature 
Sensor Error 
P0 
Compressor Drive Board 
Error 

J1 
Compressor 1 Over-
current Protection 
P1 
Compressor Drive Board 
Malfunction 

J2 
Compressor 2 Over-
current Protection 
P2 
Protection of Compressor 
Drive Board Power Supply 

J3 
Compressor 3 Over-
current Protection 
P3 
Protection of Compressor 
Drive Board Module Reset 

J4 
Compressor 4 Over-
current Protection 
H0 
Error of Fan Drive Board 

J5 
Compressor 5 Over-
current Protection 
H1 
Malfunction of Fan Drive 
Board 

Owner’s Manual 

bn 
Liquid-in Temperature 
Sensor Error of Subcooler 

by 
Water-out Temperature 
Sensor Error 

44 

Sayfa 50

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

J6 
Compressor 6 Over-
current Protection 
H2 
Protection of Fan Drive 
Board Power Supply 

J7 
4-way Valve Blow-by 
Protection 
GH 
PV DC/DC Protection 

J8 
System Pressure Over-
Ratio Protection 
― 
― 

7.1.2 Table of Error Codes for Indoor Unit 
Error 
Code 
Content 
Error 
Code 
Content 

L0 
Indoor Unit Error 
dL 
Outlet Air Temperature 
Sensor Error 

L1 
Indoor Fan Protection 
dE 
Indoor Unit CO2 Sensor 
Error 

L2 
E-heater Protection 
db 
Special Code: Field 
Debugging Code 
L3 
Water Full Protection 
dn 
Swing Assembly Error 

L4 
Wired Controller Power 
Supply Error 
dy 
Water Temperature 
Sensor Error 

L5 
Anti-Frosting Protection 
y1 
Inlet Pipe Temperature 
Sensor 2 Error 

L6 
Mode Conflict 
y2 
Outlet Pipe Temperature 
Sensor 2 Error 

L7 
No Master Indoor Unit 
Error 
y3 
Middle Tube Temperature 
Sensor 2 Error 

L8 
Power Insufficiency 
Protection 
y7 
Fresh Air Inflow 
Temperature Sensor Error 

45 

Sayfa 51

Error 
Code 
Content 
Error 
Code 
Content 

Quantity Of Group 
Control Indoor Units 
Setting Error 

L9 

LA 
Indoor Units 
Incompatibility Error 
y9 
Outdoor Air Box Sensor 
Error 
LH 
Low Air Quanlity Warning 
yA 
IFD error 

LC 
Outdoor-Indoor 
Incompatibility Error 
yH 
Fresh Air-out Sensor Error 

LF 
Shunt Valve Setting Error 
yC 
Air-return Inlet Sensor 
Error 

LJ 
Wrong Setting of 
Function DIP Switch 
yL 
Air-return Outlet 
Temperature Sensor Error 

LP 
Zero-crossing 
Malfunction of PG Motor 
yE 
High Liquid Level Switch 
Error 

Inconsistent Branch of 
Group-controlled Indoor 
Units in Heat Recovery 
System 

LU 

Inconsistency of Group-
controlled Indoor Units in 
Reheat Dehumidification 
System 

Lb 

Ld 
Indoor Fan 2 Error 
o1 
Low Voltage of IDU Bus 
Bar 

Ln 
Lift Panel Return Air 
Frame Reset Exception 
o2 
High Voltage of IDU Bus 
Bar 

Owner’s Manual 

y8 
Indoor Air Box Sensor 
Error 

yF 
Low Liquid Level Switch 
Error 

o0 
Motor Drive Error 

46 

Sayfa 52

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

d1 
Indoor Unit PC-Board 
Error 
o3 
IDU IPM Module 
Protection 

d3 
Ambient Temperature 
Sensor Error 
o4 
IDU Startup Failure 

d4 
Inlet Pipe Temperature 
Sensor Error 
o5 
IDU Overcurrent 
Protection 

Malfunction of Middle 
Tube Temperature 
Sensor 

d5 

d6 
Outlet Pipe Temperature 
Sensor Error 
o7 
IDU Losing Step 
Protection 

d7 
Humidity Sensor Error 
o8 
IDU Driver 
Communication Error 

d8 
Water Temperature 
Abnormality 
o9 

d9 
Jumper Cap Error 
oA 
High Temperature of IDU 
Module  

dA 
Indoor Unit Hardware 
Address Error 
oC 
IDU Charging Circuit Error 

dH 
Wired Controller PC-
Board Error 
ob 
Temperature Sensor Error 
of IDU Module 

dC 
Capacity DIP Switch 
Setting Error 
yb 
Refrigerant Leakage 

yd 
Malfunction of 
Refrigerant Sensor 
― 
― 

o6 
IDU Current Detective 
Electric Circuit Error 

Communication Error 
between IDU Main 
Control and IDU Drive 
Board 

47 

Sayfa 53

7.1.3 Table of Debugging Codes 
Error 
Code 
Content 
Error 
Code 
Content 

Outdoor Unit Capacity 
Code/Jumper Cap 
Setting Error 

U2 

Phase Sequence 
Protection of Power 
Supply 

U3 

U4 
Protection of Lack of 
Refrigerant 
C2 

U5 
Wrong Address of 
Compressor Drive Board 
C3 

U6 
Valve Abnormal Alarm 
C4 
Error of Lack of Indoor 
Unit 

U7 
Grid DRED0 Response 
Protection 
C5 
Alarm of Indoor Unit 
Project Number Collision 

U8 
Indoor Unit Tube 
Malfunction 
C6 
Alarm of Wrong Number 
of Outdoor Unit 

U9 
Outdoor Unit Tube 
Malfunction 
C7 
Mode Exchanger 
Communication Error 

Owner’s Manual 

Communication between 
indoor unit and outdoor 
unit and the 
communication between 
indoor unit and wired 
controller have 
malfunction 

C0 

C1 
Communication error of 
expansion board 

Communication error 
between master control 
and inverter compressor 
drive 

Communication error 
between master control 
and inverter fan motor 
drive 

48 

Sayfa 54

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

Overvoltage Protection of 
DC Bus Bar in Power 
Grid Side 

UA 

Under voltage Protection 
of DC Bus Bar in Power 
Grid Side 

UH 

UC 
Master indoor unit is 
successfully set 
CL 
Rated capacity is too low 

Emergency Operation 
DIP switch setting of the 
compressor is wrong 

UL 

UE 
Refrigerant Charging is 
ineffective 
CF 
Error of Multiple Master 
Indoor Unit 

UF 
Indoor Unit Identification 
Error of Mode Exchanger 
CJ 
System addresses is 
incompatible 

UJ 
PV module F0 protection 
CP 
Error of Multiple Master 
Wired Controller 

Protection shutdown 
error of thermal storage 
module 

UP 

Electronic expansion 
valve leak error of 
thermal storage module 

UU 

Protection without 
shutdown error of 
thermal storage module 

Ub 

CH 
Rated capacity is too high 

CC 
No master control unit 
error 

Communication Failure 
Between Mode Exchanger 
and Indoor Unit 

CE 

Communication Error 
between Indoor Unit and 
Remote Receiver 

CU 

Cb 
Outflow of Units IP 
Address 

Communication Failure 
Between Mode Exchanger 
and Outdoor Unit 

Cd 

49 

Sayfa 55

Error 
Code 
Content 
Error 
Code 
Content 

Ud 
Grid-connection driver 
board error 
Cn 

Communication error 
between grid-connection 
driver board and master 
controller 

Un 

Uy 
PV module overheating 
protection 
― 
― 

7.1.4 Table of Status Codes 
Error  
Code 
Content 
Error 
Code 
Content 

A0 
Unit is waiting for 
debugging 
Ay 
Shielding status 

A1 
Check the compressor 
operation parameters 
n3 
Compulsory defrosting 

A2 
After-sales Refrigerant 
Reclaim 
q5 

A3 
Defrosting 
q7 
Select degree Celsius or 
Fahrenheit 

A4 
Oil return 
q8 

A5 
Online Testing 
q9 
Setting of defrosting 
mode 

Owner’s Manual 

Indoor and Outdoor 
Network Error of Mode 
Exchanger 

Communication Error of 
No Master in Mode 
Exchanger 

Cy 

Setting of ordinary units 
and high sensible heat 
units 

Discharge low 
temperature protection 
revision value b 

50 

Sayfa 56

Owner’s Manual 

Error  
Code 
Content 
Error 
Code 
Content 

A8 
Vacuum-pumping Mode 
qL 
Setting of static pressure 

A9 
Operate in Setback 
Function 
qE 
EVI Operating Mode 

AH 
Heating 
qF 
System compulsory 
cooling mode 

AC 
Cooling 
qP 
PV GMV Unit  export 
area setting 

AF 
Fan 
qU 
Grid voltage system 
configuration 

AJ 
Filter Clean Reminder 
qb 
Anti-condensation 
temperature setting 

AU 
Remote Urgent Stop 
qd 
Setting of target degree 
of super-cooling of ODU 

Ab 
Emergency Stop 
qn 
PV grid-connected 
settings 

Ad 
Operation Restriction 
qy 
Working mode of 
compressor heating belt 

An 
Lock status 
― 
― 

51 

Sayfa 57

7.2 Table of Display Codes for Packaged Unit 
7.2.1 Table of Error Codes of Outdoor Unit 
Error 
Code 
Content 
Error 
Code 
Content 

E4 
Discharge Protection 
LA 
Outdoor Fan 2 Error 

H4 
Overload Protection 
L3 
Outdoor Fan 1 Error 

PA 
ODU AC Current 
Protection 
E3 

H5 
Module Current Protection 
E1 
System High Pressure 
Protection 

P8 
Module Temperature 
Protection 
U3 
DC Bus Voltage Drop 
Error 

E2 
Freeze Protection 
U5 
Current Detecting Error of 
Complete Unit 
L9 
High Power Protection 
PU 
Capacitor Charging Error 

Compressor Phase 
Loss/Phase Reversal/Out 
of Phase 

U2 

HC 
PFC Overcurrent Error 
H7 
Compressor Non-
synchronism 

PH 
High Voltage Protection of 
DC Bus 
HE 

PL 
Low Voltage Protection of 
DC Bus 
LE 
Compressor Stalling 

Owner’s Manual 

Refrigerant Lacking 
Protection or System Low 
Pressure Protection 

Compressor Phase 
Current Circuit Detecting 
Error 

U1 

Compressor 
Demagnetization 
Protection 

52 

Sayfa 58

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

Lc 
Startup Failure 
P6 
Drive Board 
Communication Error 

Overcurrent of 
Compressor Phase 
Current 
LF 
Overspeed 
PP 
DC Input Voltage Error 

P0 
Drive Module Reset  
P5 

C8 
Compressor DIP 
Switch/Jumper Cap Error 
Uo 

PF 
Drive Board Ambient 
Temperature Sensor Error 
b5 
Liquid Valve Temperature 
Sensor Error 

P9 
AC Contactor Protection 
b7 
Gas Valve Temperature 
Sensor Error 

PE 
Temperature Shifting 
Protection 
A5 

Sensor Connection 

Protection (current sensor 
hasn’t been connected to 
corresponding U phase or 
V phase) 

Pd 

e3 
Low Pressure Sensor Error 
A4 
Refrigerant Temperature 
Sensor Error 

Abnormal Outdoor 
Ambient Temperature 
(heating at too high 
ambient temperature or 
cooling at too low 
ambient temperature) 

Outdoor Condenser Inlet 
Pipe Temperature Sensor 
Error 

Outdoor Condenser 
Outlet Pipe Temperature 
Sensor Error 

A7 

53 

Sayfa 59

Error 
Code 
Content 
Error 
Code 
Content 

C7 
Outdoor Pipe Middle 
Sensor Error 
A3 
ODU Refrigerant Heater 
Failure 

C9 
Compressor Drive Storage 
Chip Error 
A2 
ODU Refrigerant Heater 
Relay Adhesion Error 

Ad 
Outdoor Fan Out-of-phase 
Protection 
C4 
ODU Jumper Cap Error 

AE 
Outdoor Fan Current 
Detecting Circuit Error 
dJ 

Ac 
Outdoor Fan Startup 
Failure 
e1 
High Pressure Sensor 
Error 

AJ 
Outdoor Fan Non-
synchronism Protection 
UL 
Outdoor Fan Overcurrent 
Protection 

EL 
Emergency Operation Stop 
A1 
Outdoor Fan IPM Module 
Protection 

oE 
Other Error of Compressor 
C6 
Discharge Temperature 
Sensor Error 

dc 
Compressor Suction 
Temperature Sensor Error 
C3 

P7 
Module Temperature 
Sensor Circuit Error  
U7 
4-way Valve 
Commutation Error 

U8 
Zero-crossing Signal Error 
Cd 
Abnormal Electrical Level 
of Selected Port 

F3 
Outdoor Ambient 
Temperature Sensor Error 
EE 
Memory Chip Read and 
Write Error 

Owner’s Manual 

AC Phase Sequence 
Protection (phase loss or 
phase reversal) 

Outdoor Condenser 
Middle Pipe Temperature 
Sensor Error 

54 

Sayfa 60

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

b2 
Subcooler Gas Inlet 
Temperature Sensor Error 
b3 

b4 
Subcooler Liquid Outlet 
Temperature Sensor Error 
FJ 
Air Outlet Temperature 
Sensor Error 

EH 
Electric Heater Operation 
Error 
A6 

A8 
Overheat Protection of 
Fan Radiator 
A9 
Fan Radiator Sensor 
Malfunction 

AA 
Fan AC Current 
Protection (input side) 
Ab 
Fan Drive Board Module 
Reset 

AF 
Fan PFC Abnormality 
AH 
Fan DC Busbar over 
Voltage Protection 

AL 
Fan DC Busbar under 
Voltage Protection 
An 
Fan Drive Storage Chip 
Malfunction 

AP 
Fan AC Input Voltage 
Abnormality 
Ar 

Fan AC Contractor 
Protection or Input Zero 
Crossing Error 
UP 
Fan Power Protection 
― 
― 
 
 
 

AU 
Fan Charge Circuit 
Malfunction 
U9 

Subcooler Gas Outlet 
Temperature Sensor 
Error 

Malfunction from Fan 
Driving Part to Main-
control Communication 

Fan Driver Board 
Environment 
Temperature Sensor 
Malfunction 

55 

Sayfa 61

7.2.2 Table of Error Codes of Indoor Unit 
Error 
Code 
Content 
Error 
Code 
Content 

E0 
Indoor Fan Error 
L1 
Indoor Humidity Sensor 
Error 

Inverter Indoor Fan Drive 
Current Detecting Circuit 
Error 

qA 

C1 
Indoor Ambient 
Temperature Sensor Error 
qd 

C2 
Indoor Evaporator Middle 
Temperature Sensor Error 
qE 

E9 
IDU Water Full Protection 
qF 
Inverter Indoor Fan Drive 
Storage Chip Error 

CJ 
IDU Jumper Cap Error 
qH 
Inverter Indoor Fan Drive 
Charging Circuit Error 

q3 
Inverter Indoor Fan Drive 
IPM Module Protection 
qL 

Low Voltage Protection or 
Voltage Drop Error of 
Inverter Indoor Fan Drive 
DC Bus 

q0 

High Voltage Protection of 
Inverter Indoor Fan Drive 
DC Bus 

q1 

Owner’s Manual 

Main Control and 
Inverter Indoor Fan Drive 
Communication Error 

qC 

Inverter Indoor Fan Drive 
Module High 
Temperature Protection 

Inverter Indoor Fan Drive 
Module Temperature 
Sensor Error 

Inverter Indoor Fan Drive 
AC Input Voltage 
Abnormal Protection 

Inverter Indoor Fan Drive 
Electric Box 
Temperature Sensor 
Error 

qo 

Inverter Indoor Fan Drive 
AC Input Zero-crossing 
Protection 

qp 

56 

Sayfa 62

Owner’s Manual 

Error 
Code 
Content 
Error 
Code 
Content 

Inverter Indoor Fan AC 
Current Protection (input 
side) 

q2 

q4 
Inverter Indoor Fan Drive 
PFC Protection 
qb 
Inverter Indoor Fan Non-
synchronism Protection 

q5 
Inverter Indoor Fan 
Startup Failure 
CP 
Multiple Master Wired 
Controllers Error 

q6 
Inverter Indoor Fan Out-
of-phase Protection 
L5 

q7 
Inverter Indoor Fan Drive 
Module Reset  
L7 
Group-controlled IDU 
Series Inconsistency 

q8 
Inverter Indoor Fan 
Overcurrent Protection 
CE 

q9 
Inverter Indoor Fan Power 
Protection 
dH 
Wired Controller Circuit 
Board Error 

L4 
Wired Controller Power 
Supply Circuit Failure 
Lb 

L6 
Group-controlled IDU 
Quantity Inconsistency 
EA 
Refrigerant Leakage 

FE 
Malfunction of Refrigerant 
Sensor 
CA 

Communication Error 
between Indoor Unit and 
Wired Controller 

C0 

Wired Controller Power 
Supply Overcurrent 
Protection 

Wired Controller 
Temperature Sensor 
Error 

Group-controlled IDU 
Inconsistency of Reheat 
Dehumidification System 

Inlet Pipe Temperature 
Sensor of Evaporator 
Error 

57 

Sayfa 63

Error 
Code 
Content 
Error 
Code 
Content 

Outlet Pipe Temperature 
Sensor of Evaporator 
Error 

Cb 

7.2.3 Table of Status Codes 
Status 

Code 
Content 
Status 

CL 
Auto clean 
d1 
DRED operation mode 1 

Fo 
Refrigerant recycle mode 
d2 
DRED operation mode 2 

H1 
Ordinary defrosting status 
d3 
DRED operation mode 3 

Owner’s Manual 

― 
― 

Code 
Content 

58 

Sayfa 64

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI