Change for life Service Manual GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Table of Contents Part Ⅰ: Technical Information.......................................................................1 1. Summary.......................................................................................................................1 2. Specifications...........................................................................................................2 2.1 Specification Sheet..................................................................................................2 2.2 Capacity Curve in Different Outdoor Temperature.......................................4 2.3 Cooling Data Sheet in Rated Frequency..........................................................4 2.4 Noise Curve.................................................................................................................5 3. Outline Dimension Diagram........................................................................6 3.1 Indoor Unit...................................................................................................................6 3.2 Outdoor Unit...............................................................................................................7 4. Refrigerant System Diagram.......................................................................9 5. Electrical Part.........................................................................................................10 5.1 Wiring Diagram........................................................................................................10 5.2 PCB Printed Diagram.............................................................................................13 6. Function and Control.......................................................................................17 6.1 Function Buttons of Air Conditioner................................................................17 6.2 Remote Control Operations................................................................................19 6.3 Description of Each Control Operation...........................................................23 6.4 GREE+ App Operation Manual...........................................................................25 6.5 Ewpe Smart App Operation Manual.................................................................26 Part Ⅱ: Installation and Maintenance ..................................................27 7. Notes for Installation and Maintenance..........................................27 8. Installation.................................................................................................................32 8.1 Installation Dimension Diagram........................................................................32 8.2 Installation Parts-checking ................................................................................35 8.3 Selection of Installation Location.....................................................................35 8.4 Requirements for electric connection ............................................................35 Service Manual Table of Contents
Service Manual 8.5 Installation of Indoor Unit....................................................................................35 8.6 Installation of Outdoor Unit.................................................................................37 8.7 Vacuum Pumping and Leak Detection............................................................39 8.8 Check after Installation and Test Operation..................................................39 9.Troubleshooting....................................................................................................40 9.1 Judgement by Flashing LED of Indoor...........................................................40 9.2 How to Check Simply the Main Part of Indoor ............................................43 9.3 How to Check Simply the Main Part of Outdoor..........................................53 9.4 Maintenance Method for Normal Malfunction..............................................55 10. Exploded View and Parts List...............................................................57 10.1 Indoor Unit..............................................................................................................57 10.2 Outdoor Unit...........................................................................................................61 11. Removal Procedure........................................................................................65 11.1 Removal Procedure of Indoor Unit.................................................................65 11.2 Removal Procedure of Outdoor Unit.............................................................80 Appendix:.........................................................................................................................90 Appendix 1: Reference Sheet of Celsius and Fahrenheit...............................90 Appendix 2: Configuration of Connection Pipe..................................................90 Appendix 3: Pipe Expanding Method.....................................................................91 Appendix 4: List of Resistance for Temperature Sensor................................92 Table of Contents
Service Manual Part Ⅰ: Technical Information 1. Summary Indoor Unit: GVH24AM-K6DNC7A/I GVH48AL-K6DNC7A/I Model List: No Model Product code Indoor model Indoor product code Outdoor model Outdoor product code 1 GVH24AM-K6DNC7A CH156002400 GVH24AM-K6DNC7A/I CH156N02400 GVH24AM-K6DNC7A/O CH156W02400 2 GVH48AL-K6DNC7A CH156002500 GVH48AL-K6DNC7A/I CH156N02500 GVH48AL-K6DNC7A/O CH156W02500 1 Technical Information Outdoor Unit: GVH24AM-K6DNC7A/O GVH48AL-K6DNC7A/O Remote Controller: YAP1F4(WiFi)
2. Specifications 2.1 Specification Sheet Parameter Unit Value Model GVH24AM-K6DNC7A GVH48AL-K6DNC7A Product Code CH156002400 CH156002500 Rated Voltage V~ 220-240 220-240 Power Supply Rated Frequency Hz 50 50 Phases 1 1 Power Supply Mode Outdoor outdoor Cooling Capacity W 7200 12500 Heating Capacity W 7900 13500 Cooling Power Input W 2050 4200 Heating Power Input W 2330 4200 Cooling Power Current A 10 19 Heating Power Current A 11 19 Rated Input W 3900 5400 Rated Current A 18 22 Air Flow Volume(SH/H/M/L/SL) m 3/h 1250/950/850/750/- 2000/1850/1700/1580/- Dehumidifying Volume L/h 2 5 EER W/W 3.51 2.98 COP W/W 3.39 3.21 SEER W/W 6.10 5.6 SCOP W/W 4.0 3.7 2 27-42 55-85 Application Area m Model of indoor unit GVH24AM-K6DNC7A/I GVH48AL-K6DNC7A/I Product Code CH156N02400 CH156N02500 Fan Type Centrifugal Centrifugal Diameter Length(DXL) mm Φ350X130.5 Φ379X180.5 Fan Motor Cooling Speed(SH/H/M/L/SL) r/min 470/420/380/330/- 600/560/530/500/- Fan Motor Heating Speed(SH/H/M/L/SL) r/min 470/420/380/330/- 600/560/530/500/- Output of Fan Motor W 65 220 Fan Motor RLA A / / Fan Motor Capacitor μF / / Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube Pipe Diameter mm Φ7 Φ7 Indoor Unit Row-fin Gap mm 2-1.3 2-1.4 Coil Length (LXDXW) mm 724X25.4X392 876X25.4X472 Swing Motor Model MP35AA/MP24TA MP35AB/MP24TA Output of Swing Motor W 2.5/1.5 2.5/1.5 Fuse A 5 5 Sound Pressure Level (SH/H/M/L/SL) dB (A) 45/41/38/35/- 53/51/50/48/- Sound Power Level (SH/H/M/L/SL) dB (A) 60/51/48/45/- 66/-/-/-/- Dimension (WXHXD) mm 507X1770X320 587X1882X394 Dimension of Carton Box (LXWXH) mm 1985X620X425 2150X735X530 Dimension of Package(LXWXH) mm 1988X623X440 2153X738X545 Net Weight kg 38 55 Gross Weight kg 50 77.5 2 Technical Information Service Manual
Service Manual Model of Outdoor Unit GVH24AM-K6DNC7A/O GVH48AL-K6DNC7A/O Product Code CH156W02400 CH156W02500 Compressor Manufacturer/Trademark ZHUHAI LANDA COMPRESSOR CO., LTD Compressor Model QXFS-D25zX090H QXFS-F428zX450E Compressor Oil R68EP FW68DA or equivalent Compressor Type Rotary Rotary L.R.A. A 24 38 Compressor RLA A 11 21 Compressor Power Input W 2420 4580 Overload Protector 1NT11L 6233/KSD115℃/ HPC115/95U1 / Throttling Method Electron expansion valve Electron expansion valve Operation Temp ºC 16~30 16~30 Ambient Temp (Cooling) ºC -15~43 -15~43 Ambient Temp (Heating) ºC -15~24 -15~24 Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube Pipe Diameter mm Φ7 Φ7 Rows-fin Gap mm 2-1.4 2-1.4 Coil Length (LXDXW) mm 935X38.1X660 1052X38X792 Fan Motor Speed rpm 800 880 Output of Fan Motor W 60 150 Outdoor Unit Fan Motor RLA A 0.58 0.95 Fan Motor Capacitor μF / / Air Flow Volume of Outdoor Unit m Fan Type Axial-flow Axial-flow Fan Diameter mm Φ520 Φ550 Defrosting Method Automatic Defrosting Automatic Defrosting Climate Type T1 T1 Isolation I I Moisture Protection IPX4 IPX4 Permissible Excessive Operating Pressure for the Discharge Side MPa 4.3 4.3 Permissible Excessive Operating Pressure for the Suction Side MPa 2.5 2.5 Sound Pressure Level (H/M/L) dB (A) 61/-/- 64/-/- Sound Power Level (H/M/L) dB (A) 70/-/- 74/-/- Dimension (WXHXD) mm 965X700X396 1010X820X460 Dimension of Carton Box (LXWXH) mm 1026X455X735 1070X560X853 Dimension of Package(LXWXH) mm 1029X458X750 1083X573X973 Net Weight kg 53.5 89 Gross Weight kg 58 100 Refrigerant R32 R32 Refrigerant Charge kg 1.6 2.6 Length m 5 5 Gas Additional Charge g/m 40 40 Outer Diameter Liquid Pipe mm Φ6 Φ9.52 Connection Outer Diameter Gas Pipe mm Φ16 Φ16 Pipe Max Distance Height m 10 20 Max Distance Length m 25 30 Note: The connection pipe applies metric diameter. The above data is subject to change without notice; please refer to the nameplate of the unit. 3 Technical Information ZHUHAI LANDA COMPRESSOR CO,LTD. 3/h 3200 6000
Service Manual 2.2 Capacity Curve in Different Outdoor Temperature Cooling Heating 120 120 110 110 Capacity ratio(%) Capacity ratio(%) 100 100 90 90 80 80 Conditions Indoor: DB20°C/WB15°C Indoor air flow: High Pipe length: 5m 70 70 Conditions Indoor: DB27°C/WB19°C Indoor air flow: High Pipe length: 5m 60 60 50 50 40 33 38 43 10 23 28 10 8 - 0 7 -20 -30 -15 Outdoor Temp.(°C) Outdoor Temp.(°C) 2.3 Cooling Data Sheet in Rated Frequency Cooling: Pressure of gas pipe connecting indoor and Rated cooling condition(°C) Inlet and outlet pipe temperature of heat exchanger Fan speed Fan speed Compressor (DB/WB) Model of indoor of outdoor frequency outdoor unit (Hz) Indoor Outdoor P (MPa) T1 (°C) T2 (°C) unit unit 27/19 35/24 24K 0.9 to 1.1 in:8~11 out:11~14 in:65~75 out:37~43 Super High High 48 48K 0.9 to 1.1 in:8~11 out:11~14 in:75~85 out:37~43 Super High High 48 Heaing: Pressure of gas pipe connecting indoor and Rated cooling condition(°C) Inlet and outlet pipe temperature of heat exchanger Fan speed Fan speed Compressor (DB/WB) Model of indoor of outdoor frequency outdoor unit (Hz) Indoor Outdoor P (MPa) T1 (°C) T2 (°C) unit unit 20/- 7/6 24K 2.0 to 2.3 in:1~3 out:4~8 in:75~85 out:33~48 Super High High 56 48K 2.5 to 3.0 in:75~85 out:37~43 in:1~3 out:3~5 Super High High 68 Instruction: T1: Inlet and outlet pipe temperature of evaporator T2: Inlet and outlet pipe temperature of condenser P: Pressure at the side of big valve Connection pipe length: 5 m. 4 Technical Information
Service Manual 2.4 Noise Curve Indoor side noise when blowing 60 65 50 55 40 Noise/dB(A) 30 35 20 10 0 0 low Middle Indoor fan motor rotating speed 24K 48K 5 Technical Information Outdoor side noise when blowing ) A ( B d / e sio N 45 25 20 40 60 80 100 High Super High Compressor frequency/Hz
3. Outline Dimension Diagram 3.1 Indoor Unit + : ' Model W H D 24K 507 1770 320 48K 587 1882 394 6 Technical Information Service Manual Unit:mm
Service Manual 3.2 Outdoor Unit GVH24AM-K6DNC7A/O 7 Technical Information 897 340 0 0 7 965 396 560 4 6 3 Unit:mm
GVH48AL-K6DNC7A/O 944 1010 610 8 Technical Information Service Manual 460 820 530 490 Unit:mm
Service Manual 4. Refrigerant System Diagram Indoor unit Outdoor unit Suction Heat exchanger (evaporator) Heat exchanger (condenser) Connection pipe specification: Liquid : 1/4" (6 mm)24K Liquid : 3/8" (9.52 mm)48K Gas : 5/8" (16mm) 9 Technical Information Gas pipe side Valve 4-Way valve Discharge Accumlator Compressor Liquid pipe side Valve Strainer Electronic expansion Strainer COOLING HEATING
Service Manual 5. Electrical Part 5.1 Wiring Diagram ● Instruction Symbol Symbol Color Symbol Symbol Color Symbol Name YE Yellow BN Brown COMP Compressor RD Red BU Blue Grounding wire YEGN Yellow/Green BK Black / / ● Indoor Unit GVH24AM-K6DNC7A/I <(*1 57 3( 52207(03 6(1625 3( &176(1625 57 6(1625 78%(7(03 $30$,1%2$5' 7(50,1$/ &211(&725 %2$5' 287'22581,7 &1&20',63/$< %8 %8 1; 1 $3φ %. %. &20 5(&(,9(5 $1' &200$,1 / %1 %1 %1 $&/; ',63/$< &1 <(*1 5($&725 %2$5' ;7 &1 &1 &1 )$1 6:,1*8'6:,1*/5 3( :,),02'8/( $3 237,21$/ / 5,1* 0$*1(7,& 0 0 / 0 <(*1 1RWH0RWRUJURXQG RQO\DSSOLHVWRWKH LURQVKHOOPRWRU 83'2:1 67(33,1* 02725 67(33,1* /()75,*+7 3( )$102725 600007060138 02725 10 Technical Information
Service Manual
GVH48AL-K6DNC7A/I
11
Technical Information
'&02725
6(1625
7(03
78%(
7(03
5220
67(33,1*
6(1625 83'2:1
/()75,*+7
0
<(*1
67(33,1*
02725
237,21$/
02725
3(
57
57
0
0
/
5,1*
0$*1(7,&
0$*1(7,&
5,1*
;7
/
1
6:,1*8'
6:,1*/5
'&02725
%8
287'22581,7
76(1625
%8
1
/
$3
%.
%.
&20
35,17('&,5&8,7%2$5'
&20287
/
$&/
%1
%1
&20',63/$<
7(50,1$/
%/2&.
<(*1
<(*1
3(
237,21$/
3(
3(
:,),
&217$&7
$3
&1
&200$,1
$3
600007063417
',63/$<Service Manual
● Outdoor Unit
GVH24AM-K6DNC7A/O
:$51,1*
3OHDVHGRQ
WWRXFKDQ\
HOHFWURQLFFRPSRQHQWRU
WHUPLQDOZKHQWKHPDFKLQHLV
UXQQLQJVWRSSLQJRUKDV
7(036(1625
28778%(
7(036(1625
7(036(1625
(;+$867
29(5/2$'3527(&725
6$7
2875220
&203
:
9
8
:+
:+
&203
EHHQSRZHUHGRIIIRUOHVV
WKDQPLQXWHVWRSUHYHQW
WKHULVNRIHOHFWULFVKRFN
5,1*
0$*1(7,&
57
57
57
/
/
/
;
<(
%8
5'
.
.
.
<(*1
%8
%/2&.
7(50,1$/
0$*1(7,&
:+
%.
3(
8%8 9<( :5'
<(
%8
5'
,1'22581,7
5,1*
%1
%.
%8
1
/
%.
76(1625
29&&203
&20,11(5
%1
$3
35,17('&,5&8,7%2$5'
%1%.
/
/
%1
/
$&B/
%8
/
/
1
%8
1
:$<
2)$1
)$
;7
3(
<(*1
3(
<(*1
97
97
32:(5
0
3(
/
1
(.9
3(
<(*1
)$102725
<9
:$<
(OHFWURQLF
([SDQVLRQ
9DOYH
3(
127(0RWRUJURXQG
600007061708
9$/9(
LURQVKHOOPRWRU
RQO\DSSOLHVWRWKH
GVH48AL-K6DNC7A/O
:$51,1*
5($&725
7(036(1625
28778%(
2875220
7(036(1625
7(036(1625
(;+$867
/2:35(6685( +,*+35(6685(
3OHDVHGRQ
WWRXFKDQ\HOHFWURQLF
FRPSRQHQWRUWHUPLQDOZKHQWKH
PDFKLQHLVUXQQLQJVWRSSLQJRU
KDVEHHQSRZHUHGRIIIRUOHVV
WKDQPLQXWHVWRSUHYHQWWKH
ULVNRIHOHFWULFVKRFN
/$
3527(&7,21
3527(&7,21
6:,7&+
6:,7&+
/%
0$*1(7,&
5,1*
/
/
/
/
/36
+36
.
.
.
3
3
57
57
57
:+ :+
5'
5'
1
;7
%8
%.
:+
2*
2*
:+
:+
%8
,1'22581,7
/; /; /; /;
%.
%1
<(*1
%.
&20,11(5
%1
76(1625
/33
+33
7(50,1$/
%/2&.
%8
$&1
$30$,1%2$5'
0$*1(7,&
5,1*
0$*1(7,&
5,1*
/
;7
$&1
%1%.
/
%1
%1
%8
/
)$
$&/
$&/
$&/
%8
/
/
:$<
%8
<(*1
2)$1
1
$&1
$&1
$&1
<(*1
8%8 9<( :5'
$3
),/7(5%2$5'
7(50,1$/
%/2&.
/
0$*1(7,&
5,1*
97
97
5'
<(
%8
3(
32:(5
/ 1
(.9
0
3(
&203
8
9
<9
:$<
3(
<(*1
:
(/(&7521,&
9$/9(
(;3$16,21
)$102725
&203
9$/9(
LURQVKHOOPRWRU
RQO\DSSOLHVWRWKH
127(0RWRUJURXQG
600007063756
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
12
Technical InformationService Manual 5.2 PCB Printed Diagram Indoor unit 24K ● Top view 7 8 9 10 6 ● Bottom view 5 13 Technical Information 1 Copper pin terminal of communication wire 2 Needle stand of display board 3 Needle stand of up&down swing 4 Needle stand of left&right swing 1 5 Needle stand of temperature sensor 6 Needle stand of DC fan 7 Earthing wire terminal 8 Fuse 9 Copper pin terminal of live wire 2 10 Copper pin terminal of neutral wire 3 4
48K ● Top view 1 2 3 4 5 6 ● Bottom view 14 Technical Information Service Manual 1 Interface of live wire 2 Fuse 3 Interface of communication wire for outdoor unit 4 Interface of netural wire 5 Motor interface of indoor unit 6 Interface of earthing wire 7 Connection needle stand of display board 8 Left&right swing interface 9 Up&down swing interface 10 Needle stand of temperature sensor 10 8 7 9
Service Manual Outdoor unit 24K Top View 2 3 4 5 6 7 8 9 10 1 NO. Name NO. Name NO. Name 1 Compressor three phase input interface 6 Terminal of high pressure protection 11 Terminal of chassis electric heating 2 Terminal of low ambient temperature cooling temperature sensor 7 Terminal of low pressure protection 12 Terminal of live wire 3 Terminal of electronic expansion valve 8 Terminal of outdoor fan 13 Terminal of communication 4 Terminal of outdoor temperature sensor 9 Terminal of compressor electric heating 14 Terminal of grounding wire 5 Terminal of compressor overload protection 10 Terminal of 4-way valve 15 Terminal of neutral wire Bottom View 15 Technical Information 11 12 13 14 15
48K ● Top view 1 2 3 4 9 10 11 12 ● Bottom view 16 Technical Information Service Manual 1 Compressor wiring terminal 2 Wiring terminal of PFC inductance 3 Neutral terminal 4 Live wire terminal 5 4-way valve terminal 6 Terminal of communication wire 7 Terminal of communication neutral wire 8 Terminal for high pressure protection 5 9 Terminal for low pressure protection 10 Terminal of temperature sensor 6 7 11 Terminal of electronic expansion valve 12 Terminal of fan 8
Service Manual
6. Function and Control
6.1 Function Buttons of Air Conditioner
Button’s Name and Function
1
ON/OFF button
2
MODE button
3
FAN button
5
4
FUNCTION button
3
ON/OFF
5
▼/▲ button
1
FAN
6
button
/
2
4
MODE
FUNC.
6
Introduction for icons on display screenof air conditioner
Ambient temperature
or set temperature
display or others
Timer
display
Operation
display
E-Heater display
Cooling display
Defrosting display
Dry display
Heating display
Fan display
Fan speed display
Note:
This series unit adopts touch buttons. You only need to touch the buttons slightly.
1
ON/OFF button
●
Press this button to turn on or turn off the unit.(Note: Under X-FAN mode, press this button to turn on the unit directly.)
2
MODE button
● Every time press this button, the mode will switchover in cycle among.
COOLING
DRY
HEATING
FAN
(Note: Cooling only unit won’t accept heating operation signal. For cooling only unit, pressing MODE button under FAN mode will
skip heating mode and enter cooling mode.)
FAN button
3
● Press this button and then fan speed can be selected and displayed in the
sequence as below:
(low)
(medium)
(high)
(turbo)
(Note:Only low fan speed is available for dry mode. Fan speed can't be adjusted
under dry mode. Turbo cannot be set in FAN mode.)
FUNCTION button
4
●
Under on status, press Function button to switch between timer and auxiliary heating function setting (auxiliary heating
can be set only in heating mode). When timer or auxiliary heating icon is blinking, it means this function can be set. Press
"▲" or "▼" button to set function. If there’s no operation change within 5s after setting is finished, the function setting will be
confirmed. Or press Function button again to exit or confirm the function.When the function is selected through Function
button, if the unit is not turned off and no remote control signal is received within 2min, pressing Function button again to
circulate from the previous set function.After 2min or the unit is turned off or remote control signal is received, pressing
Function button again to circulate from timer icon. (Note: Only when the unit is under heating mode and with auxiliary heating
function, auxiliary heating function can be turned on or off through Function button.)
Under off status, if the unit is in X-FAN status, press Function button to turn off the unit directly; if the unit is not in X-FAN status,
press Function button to set timer ON.
●
17
Technical InformationButton’s introduction
▼/▲ button
5
● After each pressing of "▲" or "▼" button, set temperature will increase or decrease
1ć. Temperature adjustment range is
ć~30 ć. This button is invalid under
16
auto mode. Timer setting can be set in 1h increment among 0~24h. When it is adjusted to
auxiliary heating function setting through Function button,press this button to turn on or turn off auxiliary heating. (Note: auxiliary
heating is valid only for the model with this function.)
● Hold "▲" and "▼" buttons for 3s and the air conditioner will display "LC", which indicates buttons are locked. Any button
under on status or ON/OFF button and function buttons under off status are all invalid. Hold these two button for 3s
again to release the lock.
button
6
● Left and right swing: this button controls the left and right swing motor, single pressit to switchover between ON and OFF.
● Up and down swing: this button controls the up and down swing motor, single pressit to switchover between ON and OFF.
/
Icon function introduction
Operation display
●It indicates the air conditioner is
put through the power. Under on
status, this indicator is on; under
off status, this indicator is off.
Timer display
ƽ When this indicator is on, it
indicates the timer function
is turned on.
Heating display
●When this indicator is on, it
indicates the heating mode is
turned on.
Fan speed display
Defrosting display
●When this indicator is on, it
indicates the defrosting function
is turned on.
18
Technical Information
Service Manual
Dry display
When this indicator is on, it indicates
the dry mode is turned on.
ƽ
E-Heater display
●
When this indicator is on, it indicates
the E-heater function is turned on.
Cooling display
●
When this indicator is on, it indicates
the cooling mode is turned on.
Fan display
●When this indicator is on, it indicates
the fan mode is turned on.
●Displays the fan speed. The fan speed
is displayed as below:
(low) → (medium) →
(high) → (turbo)Service Manual
6.2 Remote Control Operations
Buttons on remote controller
1
ON/OFF button
2
SAVE button
3
FAN button
4
MODE button
5
▲/ button
▲
HEAT button
6
7
COOL button
1
8
button
2
button
9
3
4
10
SLEEP button
5
11
WiFi button
12
X-FAN/E-HEATER button
7
6
13
QUIET button
8
9
10
14
LIGHT button
13
11
14
15
TIMER button
12
15
Introduction for icons on display screen
Set fan speed
(No
fan speed. It’s displayed
only after turning it on.)
{
Operation mode
Send signal
battery power
Cool mode
Auto mode
This is a general remote controller.Some
models have this function while some
do not. Please refer to the actual models.
{
WiFi
Dry mode
Child lock
Fan mode
Switch temperature displaying type on
the unit’s display
Heat mode
I feel function
Up & down swing
Left & right swing
Set time
TIMER ON/TIMER OFF
Sleep mode
Turbo fan speed
Quiet mode
X-FAN function
Introduction for buttons on remote controller
This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the
model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
● After putting through the power, the air conditioner will give out a sound.
Operation indicator " " is ON.
After that, you can operate the air
(This indicator is not available for some models).
conditioner by using remote controller.
● Under on status, pressing the button on the remote controller, the signal icon " " on the display of remote controller will
blink once and the air conditioner will give out a “di” sound, which means the signal has been sent to the air conditioner.
19
Technical InformationON/OFF button
1
Press this button can turn on or turn off the air conditioner. After turning on the air conditioner, indoor unit will give out a sound.
SAVE button
2
Under cooling mode, press this button to start up or turn off energy-saving function.When energy-saving function is started up,
"SE" will be shown on remote controller, and air conditioner will adjust the set temperature automatically according to
ex-factory setting to reach to the best energy-saving effect. Press this button again to exit energy-saving function.
FAN button
3
Pressing this button can set fan speed circularly as: auto (AUTO), low( ), medium ( ), high( ), turbo( ).
Auto
● Under AUTO speed, air conditioner will select proper fan speed automatically according to ex-factory setting.
Note:
● It’s Low fan speed under Dry mode.
● Turbo cannot be set in FAN mode.
MODE button
4
Press this button to select your required operation mode.
AUTO
COOL
FAN
DRY
HEAT
● When selecting auto mode, air conditioner will operate automatically according to the sensed temperature. Set temperature
can’t be adjusted and will not be
displayed as well. Press "FAN" button can adjust fan speed. Press " " / " " button can adjust
fan blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Cool indicator " " on indoor unit is ON.
(This indicator is not available for some models).
FAN" button to adjust fan speed. Press " " / " " button to adjust fan blowing angle.
● When selecting dry mode, the air conditioner operates at low speed under dry mode. Dry indicator " " on indoor unit is ON.
button to adjust set temperature. Press "
Press
"▲" or " "
▲
(This indicator is not available for some models).
Under dry mode, fan speed can’t be adjusted. Press " " / " " button to adjust fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and
no heating. Fan indicator " " on indoor unit is ON.
(This indicator is not available for some models).
Press "FAN" button to adjust fan speed. Press" " / " " button to adjust fan blowing angle.
● When selecting heating mode, the air conditioner operates under heat mode.
Heat indicator " " on indoor unit is ON.
(This indicator is not available for some models).
"▲" or " "
Press
(Cooling only
▲
button to adjust set temperature. Press " FAN" button to adjust fan speed. Press " " / " " button to adjust fan blowing angle.
unit won’t receive heating mode signal. If setting heat mode with remote controller, press ON/OFF button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend on indoor
ambient temperature).
● Set temperature range from remote controller: 16~30ć (61-86°F);
Fan speed: auto, low speed, medium speed, high speed, turbo speed.
▲/ button
5
▲
● Press "▲" or " " button once increase or decrease set temperature 1ć (°F).
Holding "▲" or " " button, 2s later, set temperature
on remote controller will change quickly . On releasing button after setting is finished, temperature indicator
on indoor unit will change
accordingly. (Temperature can’t be adjusted under
▲
▲
auto mode)
● When setting TIMER ON, TIMER OFF, press "▲" or " " button to adjust time.
(Refer to TIMER button for details)
▲
Cool button
6
● Press this button, unit will operate in cool mode.
Heat button
7
● Press this button, unit will operate in heat mode.
20
Technical Information
Service ManualService Manual
8
button
● Under simple swing mode, press this button can turn on (" " icon is displayed) or
turn off (" " icon is not displayed)
the left&right swing function.
● When the unit is turned off by remote controller, press "▲" button and " "
button can switch between single swing mode
" " on the remote controller will flash twice.
and fixed-angle swing mode.
Under fixed-angle swing mode, press this button and then left&right swing status will circulate as shown in the right figure:
no display
● This remote controller is the general type remote controller. When remote controller receives the signal of " " , swing
status is same as " " ; when remote controller
receives " " , swing status is same as left&right swing OFF.
9
button
● Under simple swing mode, press this button can turn on (" " icon is displayed)
lor turn off (" " icon is not displayed) the
up&down swing function.
● When the unit is turned off by remote controller, press "▲" button and " " button can switch between single swing mode and
" " on the remote controller will flash twice. Under fixed-angle swing mode, press this button and
the up&down swing status will circulate as shown in the right figure:
fixed-angle swing mode.
no display
10 SLEEP button
Under COOL, or HEAT mode, press this button to start up sleep function. " " icon is displayed on remote controller. Press this
button again to cancel sleep function and " " icon will disappear.After powered on, Sleep Off is defaulted. After the unit is
turned off, the Sleep function is canceled.
In this mode, set temperature will be adjusted with the change of time. Under Fan、DRY and Auto modes, this function is not
available.
WiFi button
11
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on
remote controller; Under status of remote controller off, press "MODE" and " WiFi " buttons simultaneously for 1s,WiFi module
will restore to factory default setting.
● This function is only available for some models.
12
Pressing this button in COOL or DRY mode, the icon " " is displayed and the
X-FAN/E-HEATER button
indoor fan will continue operation for a few
minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted.
X-FAN is not available in AUTO, FAN or HEAT mode.This function indicates that moisture on evaporator of indoor unit will be
blowed after the unit is stopped to avoid mould.
button indoor fan will continue running for
In this period, press X-FAN button to stop indoor fan directly.
●
●Having set X-FAN function on: After turning off the unit by pressing ON/OFF
about a few minutes. at low speed.
Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
●
Only under cooling mode and dry mode, press this button can turn on (characters
(characters of “X-FAN” are not displayed)
of “X-FAN” are displayed) or turn off
X-FAN function.
Under heating mode, press this button and the E-HEATER status will changed circularly as below:
●
Auto E-HEATER (no display)
E-HEATER OFF
( is displayed)
E-HEATER ON
( is displayed)
21
Technical Information●This function is not available for this unit.
Press this button can turn on or turn off QUIET function.
13
QUIET button
LIGHT button
14
Press this button to turn off display light on indoor unit. Press this button again to turn on display light.
TIMER button
15
● At ON status, press this button once can set TIMER OFF. The character of HOUR
TIMER ON. After each pressing of " " or " " button, time will increase or
decrease half an
hour. When holding " " or " " button, 2s later, the time will change quickly until to
▲
▲
Cancel TIMER OFF: Press "TIMER" button again under TIMER OFF status.
● At OFF status, press this button once can set TIMER ON. Please refer to TIMER off for detailed operation.
Cancel TIMER ON: Press "TIMER" button again under TIMER ON status.
Note:
● Time setting range: 0.5-24 hours.
● Time interval between two operations can’t exceed 5s. Otherwise, remote
controller will exit the setting status automatically.
Function introduction for combination buttons
Child lock function
Press "▲" and " " simultaneously to turn on or turn off child lock function. When
on remote controller. If you operate the remote controller, the " " icon will blink three times without sending signal to the unit.
▲
Temperature display switchover function
Under OFF status, press " " and "MODE" buttons simultaneously to switch temperature display between ć and ̧
.
▲
If “H1” is displayed on the remote controller while it’s not operated by the professional person/after-sales person, it belongs to the misoperation.
Please operate it as below to cancel it.Under the OFF status of remote controller, hold the “MODE” button and “X-FAN” buttons simultaneously
for 5s to cancel “H1” display.
Note:
● If remote controller displays “H1”, it belongs to the normal function reminder. If the unit is defrosting under heating mode, it operates accord-
ing to H1 defrosting mode. “H1” won’t be displayed on the panel of indoor unit;
● Once you set H1 mode, if you turn off unit by remote controller, H1 will display 3 times on the remote controller and then disappear;
● Also, when you set H1 mode, when you change to heating mode, H1 will display 3 times on the remote controller and then disappear.
Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to
turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN,
HEAT.
3. Press "▲" or " " button to set your required temperature. (Temperature can’t be adjusted under auto mode).
4. Press "FAN" button to set your required fan speed: auto, low speed, medium
speed, high speed, turbo speed.
▲
5. Press " " button to select fan blowing angle.
Replacement of batteries in remote controller
1. Lift the cover along the direction of arrow (as shown in Fig 1 ǐ).
2. Take out the original batteries (as shown in Fig 1 Ǒ).
3. Place two 7# (AAA 1.5V) dry batteries, and make sure the position of “+”
polar and “-” polar is correct (as shown in Fig 2ǒ).
4. Reinstall the cover (as shown in Fig 2 Ǔ).
NOTICE
● During operation, point the remote control signal sender at the receiving
window on indoor unit.
● The distance between signal sender and receiving window should be no
more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp
or wireless telephone; remote controller should be close to indoor unit during
operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the
batteries.
22
Technical Information
Service Manual
▲
▲
▲
▲
child lock function is on, " " icon is displayed
Fig.1
Fig.2 Service Manual 6.3 Description of Each Control Operation Note:Heating function is not available for this model. 1.Basic Functions 1.1 Cooling Mode When Tamb.≥Tpreset+1ć, the unit will run in cooling mode. Meanwhile, compressor and outdoor fan will run. Indoor fan will run at setting fan speed; When Tamb.≤Tpreset-1ć, the unit will stop running in cooling mode. Compressor and outdoor fan will stop running, while indoor fan is still running at setting fan speed; When Tpreset-1ć<Tamb.<Tpreset+1ć, the unit will keep previous running status; 1.2 Dry Mode When Tamb>Tpreset+2ćˈthe unit will run at cooling mode. Meanwhile, compressor and outdoor fan will run. Indoor fan will run at low fan speed. When Tpreset-2ć≤Tamb. ≤Tpreset+2ć, compressor and outdoor fan will run for 6mins and then stop running for 4mins and they will run like that circularly. Indoor fan will run at low fan speed; When Tamb.<Tpreset-2ć, compressor and outdoor fan will stop running. Indoor fan will run at low fan speed. 1.3 Heating Mode When Tamb≤Tpreset-1ć, the unit will run in heating mode and the corresponding load will start running. Indoor fan will run at the condition of anti cold wind. When Tamb.≥Tpreset+1ć, the corresponding load will be stopped. Indoor fan will run at setting fan speed and the condition of blowing residual heat. When Tpreset<Tamb<Tpreset+1ć, the unit will keep previous running status. 1.4 Fan Mode Indoor fan will run at setting fan speed. Compressor, outdoor fan and reversing valve will stop running. 1.5 Auto Mode In this mode, the unit will decide its running mode according to the ambient temperature. When Tamb>26ć, the unit will run in cooling mode. Internal setting temperature is 26ć; When 20ć≤Tamb. ≤26ć, the unit will run in dry mode. Internal setting temperature is 24ć; When Tamb.<20ć, the unit will run in heating mode. Internal setting temperature is 20ć. When Tamb.≥24ć, the unit will quit from the heating mode. As for the cooling only unit, when Tamb.<20ć, the unit will run at fan mode and the internal setting temperature is 20ć. When Tamb≥24ć, the unit will quit from the fan mode. 2. Protection Function 2.1 Indoor Antifreezing Protection When antifreezing protection is detected, the corresponding load will be stopped. After the antifreezing protection is released, controller will run at setting mode. Buttons won’t be shielded during the antifreezing protection. 2.2 High Pressure Protection of System When high pressure protection is detected, the corresponding load will be stopped. All button and remote control signal will be shielded and E1 will be displayed; after high pressure protection of compressor is released, all buttons and remote control signal will become normal. 2.3 Low Pressure Protection of System When low pressure protection is detected for the first time, the corresponding load will be stopped and the indicator will blink. If the low pressure protection is detected for twice successively, the corresponding load will be stopped and E3 will be displayed. They can’t resume automatically. 2.4 High Temperature Protectionfor Discharge Pipe When high temperature protection for discharge pipe is detected, the corresponding load will be stopped. E4 will be displayed. 2.5 Indoor High Temperature Resistant Protection When high temperature resistant protection is detected, the corresponding load will be stopped. 2.6 Overcurrent Protection When overcurrent protection is detected, the corresponding load will be stopped and E5 will be displayed. 3. Other Function 3.1 Defrosting The unit will judge according to the tube temperature and ambient temperature, when it’s detected that the outdoor condenser is frosting, the unit will start defrosting. Indoor fan and four-way valve will stop running. After defrosting is finished, the unit will start heating normally. During the time of defrosting,Defrosting indicator is on. 3.2 Swing Function Users can start up or stop the function of up&down swing, right&left swing. 23 Technical Information
3.3 Sleep ķ If the controller is in cooling or dry mode, after the sleep function is started, Tpreset will be increased but it won’t increase over 3ć. Then the unit will run at the increased temperature. ĸ If the controller is in heating mode, after the sleep function is started, Tpreset will be decreased and it won’t decrease over 3ć. Then the unit will run at the decreased temperature. 3.4 Timer Timer ON and timer OFF can be set by remote controller or buttons and the setting range is 0.5~24hrs. 3.5 Buzzer Upon energization and operation, the buzzer will give out a beef. 3.6 Power-off Memory Function Memory content: mode, up&dwon swing (7 statuses), right&left swing (ON/OFF), setting temperature, setting fan speed, health, light, timer. After power failure, the unit will run according to the memory content automatically when power recovered. If energize the unit after power failure and the unit is turned on before power failure, the compressor will be delayed for 3mins for protection; if the unit is turned off before power failure, the compressor won’t be delayed for 3mins for protection. If the timer is reached before power failure, the unit will run according to the mode before power failure after power recovered; if the timer isn’t reached, the timer will be continued and time will be recalculated. 3.7 LED Display Module Control 1. Indicator control 2. Use the light button on r Indicator will be displayed according to current operation function. emote controller to turn off the LED display: When cancel the “light” by remote controller, the complete display screen will go out except the running indicator. 3.8 Buttons ķ ON/OFF button: This button is used for control the on/off of controller. After each pressing of this button, the on/off status will be changes for once. ĸ Mode button: After pressing the mode button, it will be selected and display as: auto—cooling—drying—fan—heating (not available for cooling only unit). Ĺ +and – buttons: This two buttons are used for adjusting temperature and timer; ĺ Up&down button: This button is used for control the up&down swing motor and it will be selected and displayed as: angle 1→angle 2→angle 3 →angle 4→angle 5→to-and-fro swing →stop swing. Ļ Fan speed button: fan speed will be selected as: auto—low—medium—high—super-high; ļ Right&left swing button: This button is used for control the on/off of right&left swing motor. After each pressing this button, the on/off status of the right&left swing motor will be changed for once. 24 Technical Information Service Manual
Service Manual 6.4 GREE+ App Operation Manual Control Flow Chart Home Wi-Fi Gree intelligent home appliances Home wireless router Operating Systems Requirement for User's smart phone: iOS system Support iOS7.0 and above version Download and installation GREE+ App Download Linkage Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the account and add the device to achieve long-distance control and LAN control of Gree smart home appliances. For more information, please refer to "Help" in App. 25 Technical Information Internet Gree Cloud Cellular/ Other Wi-FI Home Wi-Fi GREE+ APP Android system Support Android 4.4 and above version
6.5 Ewpe Smart App Operation Manual Control Flow Chart intelligent Home Wi-Fi home appliances Home wireless router Operating Systems Requirement for User's smart phone: iOS system Support iOS7.0 and above version Download and installation App Download Linkage Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed, register the account and add the device to achieve long-distance control and LAN control of smart home appliances. For more information, please refer to "Help" in App. 26 Technical Information Service Manual Internet Cloud Cellular/ Other Wi-FI Home Wi-Fi APP Android system Support Android 4.4 and above version
Service Manual Part Ⅱ: Installation and Maintenance 7. Notes for Installation and Maintenance Safety Precautions: Important! Please read the safety precautions carefully before installation and maintenance. The following contents are very important for installation and maintenance. Please follow the instructions below. ●The installation or maintenance must accord with the instructions. ●Comply with all national electrical codes and local electrical codes. ●Pay attention to the warnings and cautions in this manual. ●All electric work must be performed by a licensed technician according to local regulations and the instructions given in this manual. ●Be caution during installation and maintenance. Prohibit incorrect operation to prevent electric shock, casualty and other accidents. 1. Select the installation location according to the requirement of this manual.(See the requirements in installation part) 2. Handle unit transportation with care; the unit should not be carried by only one person if it is more than 20kg. 3. When installing the indoor unit and outdoor unit, a sufficient fixing bolt must be installed; make sure the installation support is firm. 4. Ware safety belt if the height of working is above 2m. 5. Use equipped components or appointed components during installation. 6. Make sure no foreign objects are left in the unit after finishing installation. Electrical Safety Precautions: Warnings 1. Cut off the power supply of air conditioner before checking and maintenance. 2. The air condition must apply specialized circuit and prohibit share the same circuit with other appliances. 3. The air conditioner should be installed in suitable location and ensure the power plug is touchable. 4. Make sure each wiring terminal is connected firmly during installation and maintenance. 5. Have the unit adequately grounded. The grounding wire can’t be used for other purposes. 6. Must apply protective accessories such as protective boards, cable-cross loop and wire clip. 7. The live wire, neutral wire and grounding wire of power supply must be corresponding to the live wire, neutral wire and grounding wire of the air conditioner. 8. The power cord and power connection wires can’t be pressed by hard objects. 9. If power cord or connection wire is broken, it must be replaced . 27 Installation and Maintenance 10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire from the manufacture or distributor. Prohibit prolong the wire by yourself. 11. For the air conditioner without plug, an air switch must be installed in the circuit. The air switch should be all-pole parting and the contact parting distance should be more than 3mm. 12. Make sure all wires and pipes are connected properly and the valves are opened before energizing. 13. Check if there is electric leakage on the unit body. If yes, please eliminate the electric leakage. 14. Replace the fuse with a new one of the same specification if it is burnt down; don’t replace it with a cooper wire or conducting wire. 15. If the unit is to be installed in a humid place, the circuit breaker must be installed. Installation Safety Precautions: When refrigerant leaks or requires discharge during installation, maintenance, or disassembly, it should be handled by certified professionals or otherwise in compliance with local laws and regulations. Refrigerant Safety Precautions: 1. Avoid contact between refrigerant and fire as it generates poisonous gas; Prohibit prolong the connection pipe by welding. 2. Apply specified refrigerant only. Never have it mixed with any other refrigerant. Never have air remain in the refrigerant line as it may lead to rupture or other hazards. 3. Make sure no refrigerant gas is leaking out when installation is completed. 4. If there is refrigerant leakage, please take sufficient measure to minimize the density of refrigerant. 5. Never touch the refrigerant piping or compressor without wearing glove to avoid scald or frostbite. Improper installation may lead to fire hazard, explosion, electric shock or injury.
To ensure safety, please be mindful of the following precautions. ●When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the specified refrigerant. Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in injury. ●When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or unqualified refrigerant.Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident. ●When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling mode. Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery should not exceed 1 minute. If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury. ●During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe. If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury. ●When installing the unit, make sure that connection pipe is securely connected before the compressor starts running. If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury. ●Prohibit installing the unit at the place where there may be leaked corrosive gas or flammable gas. If there leaked gas around the unit, it may cause explosion and other accidents. ●Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service center authorized and ask for a proper electric wire. Poor connections may lead to electric shock or fire. ●Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so that their terminals receive no external stresses. Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire. 28 Installation and Maintenance Service Manual
Service Manual Safety Precautions for Installing and Relocating the Unit: To ensure safety, please be mindful of the following precautions. Warnings 1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the specified refrigerant. Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in injury. 2.When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or unqualified refrigerant. Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident. 3.When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling mode.Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery should not exceed 1 minute. If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury. 4.During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe. If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury. 5.When installing the unit, make sure that connection pipe is securely connected before the compressor starts running. If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure rise or compressor rupture, resulting in injury. 6.Prohibit installing the unit at the place where there may be leaked corrosive gas or flammable gas. If there leaked gas around the unit, it may cause explosion and other accidents. 7.Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service center authorized and ask for a proper electric wire. Poor connections may lead to electric shock or fire. 8.Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so that their terminals receive no external stresses. Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire. Safety Precautions for Refrigerant ●To realize the function of the air conditioner unit, a special refrigerant circulates in the system. The used refrigerant is the fluoride R32,which is specially cleaned. The refrigerant is flammable and inodorous. Furthermore, it can leads to explosion under certain conditions. But the flammability of the refrigerant is very low. It can be ignited only by fire. ●Compared to common refrigerants, R32 is a nonpolluting refrigerant with no harm to the ozonosphere. The influence upon the greenhouse effect is also lower. R32 has got very good thermodynamic features which lead to a really high energy efficiency. The units therefore need a less filling. WARNING: ●Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture. Should repair be necessary,contact your nearest authorized Service Centre. Any repairs carried out by unqualified personnel may be dangerous. The appliance shall be stored in a room without continuously operating ignition sources. (for example:open flames , an operating gas appliance or an operating electric heater.) ●Do not pierce or burn. ●Appliance shall be installed, operated and stored in a room with a floor area larger than 4m 2 (or 6m 2 ). ●Appliance filled with flammable gas R32. For repairs, strictly follow manufacturer’s instructions only.Be aware that refrigrants not contain odour. ●Read specialist’s manual. 29 Installation and Maintenance
Safety Operation of Flammable Refrigerant Qualification requirement for installation and maintenance man ●All the work men who are engaging in the refrigeration system should bear the valid certification awarded by the authoritative organization and the qualification for dealing with the refrigeration system recognized by this industry. If it needs other technician to maintain and repair the appliance, they should be supervised by the person who bears the qualification for using the flammable refrigerant. ●It can only be repaired by the method suggested by the equipment’s manufacturer. Installation notes ●The air conditioner is not allowed to use in a room that has running fire (such as fire source,working coal gas ware, operating heater). ●It is not allowed to drill hole or burn the connection pipe. ●The air conditioner must be installed in a room that is larger than the minimum room area. The minimum room area is shown on the nameplate or following table a. ●Leak test is a must after installation. table a - Minimum room area(m 2) Charge amount (kg) ≤1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5 4 14.5 16.8 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6 floor location Minimum room window mounted 4 5.2 6.1 7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3 2 area( m ) 4 4 4 4 4 4 4 4 wall mounted 4 4.2 4.6 5 5.5 6 4 4 4 4 4 ceiling mounted 4 4 4 4 4 4 4 4 4 Maintenance notes ●Check whether the maintenance area or the room area meet the requirement of the nameplate. — It’s only allowed to be operated in the rooms that meet the requirement of the nameplate. ●Check whether the maintenance area is well-ventilated. — The continuous ventilation status should be kept during the operation process. ●Check whether there is fire source or potential fire source in the maintenance area. — The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged. ●Check whether the appliance mark is in good condition. — Replace the vague or damaged warning mark. Welding ●If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below: a. Shut down the unit and cut power supply b. Eliminate the refrigerant c. Vacuuming d. Clean it with N2 gas e. Cutting or welding f. Carry back to the service spot for welding ●Make sure that there isn’t any naked flame near the outlet of the vacuum pump and it’s well-ventilated. ●The refrigerant should be recycled into the specialized storage tank. Filling the refrigerant ●Use the refrigerant filling appliances specialized for R32. Make sure that different kinds of refrigerant won’t contaminate with each other. ●The refrigerant tank should be kept upright at the time of filling refrigerant. ●Stick the label on the system after filling is finished (or haven’t finished). ●Don’t overfilling. ●After filling is finished, please do the leakage detection before test running; another time of leak detection should be done when it’s removed. Safety instructions for transportation and storage ●Please use the flammable gas detector to check before unload and open the container. ●No fire source and smoking. ●According to the local rules and laws. 30 Installation and Maintenance Service Manual
Service Manual Main Tools for Installation and Maintenance 1. Measuring tape 4. Electroprobe 7. Electronic leakage detector 10. Pipe pliers, pipe cutter 31 Installation and Maintenance 2. Screw driver 3. Impact drill, drill head, electric drill 5. Universal meter 6. Torque wrench, open-end wrench, inner hexagon spanner 8. Vacuum pump 9. Pressure meter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container 13. Electronic scale
8. Installation 8.1 Installation Dimension Diagram GVH24AM-K6DNC7A Away from wall (30cm at least for piping side) Away from 10cm above ceiling 30cm 200cm above Away from obstacles Away from wall (30cm at 10cm above least for piping side) Away from back side 5cm above Space to the obstruction At least 19 2/3 inch Space to the obstruction At least 11 4/5 inch Space to the wall At least 11 4/5 inch Drainage pipe Space to the obstructio At least 78 3/5 inch Space to the obstruction At least 19 2/3 inch 32 Installation and Maintenance Service Manual
Service Manual GVH48AL-K6DNC7A Away from wall (30cm at least for piping side) ceiling Away from 10cm above 30cm 200cm above Away from obstacles FAN ON/OFF FUNC. MODE Away from wall (30cm at least for piping side) 10cm above from back side Away 5cm above Away from obstacled Away from obstacles 50cm above 30cm above Away from wall 30cm above Away from obstacles Away from obstacles 50cm above 200cm above 33 Installation and Maintenance
Installation procedures Start installation Preparation before installation Prepare tools Read the requirements for electric connection select installation location Select indoor unit installation location Select outdoor unit installation location Install the support of outdoor unit (select it according to the actual situation) Drill wall holes Connect pipes of indoor unit and drainage pipe Fix outdoor unit Install drainage joint of outdoor unit (only for cooling and heating unit) Connect wires of indoor unit Bind up pipes Connect pipes of outdoor unit Make the bound pipes pass through the wall hole and then connect outdoor unit Connect wires of outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installation Note: this flow is only for reference; please find the more detailed installation steps in this section. 34 Installation and Maintenance Service Manual
Service Manual
8.2 Installation Parts-checking
No.
Name
No.
Name
1
Indoor unit
7
Sealing gum
2
Outdoor unit
8
Wrapping tape
3
Connection pipe
9
Support of outdoor
unit
4
Drainage pipe
10
Fixing screw
5
Connecting
cable(power cord)
11
Drainage plug(cooling
and heating unit)
6
Wall pipe
12
Owner’s manual,
remote controller
Note:
1.Please contact the local agent for installation.
2.Don't use unqualified power cord.
8.3 Selection of Installation Location
Basic Requirement:
Installing the unit in the following places may cause
malfunction. If it is unavoidable, please consult the local dealer:
1.The place with strong heat sources, vapors, flammable or
explosive gas, or volatile objects spread in the air.
2.The place with high-frequency devices (such as welding
machine, medical equipment).
3.The place near coast area.
4.The place with oil or fumes in the air.
5.The place with sulfureted gas.
6.Other places with special circumstances.
7. Please try your best to keep way from fluorescent lamp.
8.It’s not allowed to be installed on the unstable or motive base
structure (such as truck) or in the corrosive environment
(such as chemical factory).
Indoor Unit:
1. Avoid installing the indoor unit in a place where generated or
leaked inflammable gas will stay.
2. Avoid installing the indoor unit in a moist place or in a place
where oil may be splashed on the unit.
3. Select a location where outlet air may reach each corner of
the room.
4. Select a location where connection pipe can be led to
outdoor conveniently.
5. Select a location where air inlet and outlet won't be blocked.
6. Select a location with least affection of outdoor air.
7. Select a location with firm and flat floor.
8. Retain sufficient space for maintenance and installation.
9. Ensure the installation meets the requirement of installation
dimension diagram.
10.Do not use the unit in the immediate surroundings of a
laundry a bath a shower or a swimming pool.
Outdoor Unit:
1. Select a location where the noise and outflow air emitted by
the outdoor unit will not affect neighborhood.
2. The location should be well ventilated and dry, in which the
outdoor unit won't be exposed directly to sunlight or strong
wind.
3. The location should be able to withstand the weight of
outdoor unit.
4. Make sure that the installation follows the requirement of
installation dimension diagram.
5. Select a location which is out of reach for children and far
away from animals or plants. If it is unavoidable, please add
fence for safety purpose.
6. The height difference between indoor unit and outdoor unit
should be within 5m. The length of connection pipe should be
within 10m.
35
Installation and Maintenance
8.4 Requirements for electric connection
Safety Precaution:
1.Must follow the electric safety regulations when installing the unit.
2.If the supply cord is damaged, it must be replaced by the
manufacturer or its
service agent or a similarly qualified person in order to avoid a
hazard.
3.According to the local safety regulations, use qualified power
supply circuit and air switch
4.A air switch having a contact separation of at least 3mm in all
poles should be fixed in fixed wiring.
5.The appliance shall be installed in accordance with national wiring
regulation.
6.The air switch must have the functions of magnetic tripping and
heat tripping in order to prevent short circuit or overload. Please
install the air switch with suitable capacity according to the sheet
below.
7.Make sure the power supply matches with the requirement of air
conditioner.Unstable power supply or incorrect wiring may result
in electric shock, fire hazard or malfunction. Please install proper
power supply cables before using the air conditioner.
8.Properly connect the live wire, neutral wire and grounding wire of
power socket.
9.Be sure to cut off the power supply before proceeding any work
related to electric safety.
10.Do not put through the power before finishing installation.
11.To be in compliance with IEC/EN 61000-3-11, impedance value
of power-supply system connected to product must be less than
or equal to the allowable maximum value of |Zsys| in the following
sheet:
Model
max |Zsys| unit:ohm
GVH48AL-K6DNC7A
0.356
Grounding Requirement:
1. The air conditioner is first class electric appliance. It must
be properly grounded with specialized grounding device by a
professional. Please make sure it is always grounded effectively,
otherwise it may cause electric shock.
2. The yellow-green wire in air conditioner is grounding wire, which
can't be used for other purposes.
3. The grounding resistance should comply with national electric
safety regulations.
Model
Capacity of air switch
Power cord specifications
24K
25A
4G0.75
48K
32A
4G0.75
8.5 Installation of Indoor Unit
Step one: choosing installation Iocation
Recommend the installation location to the client and then
confirm it with the client.
Step two: open piping hole
1.Choose the position of piping hole according to the direction of
outlet pipe.
2.Open a piping hole with the diameter of Φ70mm on the selected
outlet pipe position. In order to drain smoothly, slant the piping hole
on the wall slightly downward to the outdoor side with the gradient
of 5-10°. (As show in Fig.1)
Indoor
Outdoor
Model
Piping hole
24K
Φ70mm
Fig.1
Φ70mm
5-10°Service Manual Note: 1.Pay attention to dust prevention and take relevant safety measures when opening the hole. 2.The plastic expansion particles are not provided and should be bought locally. Refer to the following table for wrench moment of force: . Hex nut diameter(mm) Tightening torque(N m) Φ6.35(1/4") 15.7(1.6kg.m) Φ9.52(3/8") 29.4(3.0kg.m) Φ12.70(1/2") 49.0(5.0kg.m) Φ15.88(5/8") 73.6(7.5kg.m) Step three: outlet pipe 1. The pipe can be led out in the direction of left, right or rear. (As show in Fig.2) 2. After confirming the direction of outlet pipe, loosen the Step five: install drain hose 1. Connect the drain hose to the outlet pipe of indoor unit.(As screws at the upper and lower adjusting baffle to let the connection pipe/drain pipe connects the indoor unit. (As show show in Fig.8) in Fig.3) 2. Bind the joint with tape.(As show in Fig.8) 3. Add insulating pipe in the indoor drain hose in order to prevent condensation.(As show in Fig.10) drain hose outlet pipe left back right Fig.2 left back right drain hose tape outlet pipe Fig.9 Fig.8 drain hose Fig.3 upper and lower adjusting baffle insulating pipe Step four: connect the pipe of indoor unit 1. Take out the left and right screw cover and then remove Fig.10 the screws on air-inlet panel to remove the panel.(As show in Step six: connect wire of indoor unit 1. Make the power connection wire go through the cable- Fig.4) 2. Aim the pipe joint at the corresponding bellmouth.(As show cross hole of indoor unit(As show in Fig.11) in Fig.5) 3. Pretightening the union nut with hand. 4. Adjust the torque force by referring to the following sheet. Place the open-end wrench on the pipe joint and place the power connection wire cable-cross hole torque wrench on the union nut. Tighten the union nut with torque wrench.(As show in Fig.6) 5. Wrap the indoor pipe and joint of connection pipe with Fig.11 insulating pipe, and then wrap it with tape. (As show in Fig.7) 2. Remove the wire clip; connect the power connection wire screw to the wiring terminal according to the color; tighten the screw and then fix the power supply wire,power connection wire with union nut pipe joint pipe wire clip.(As show in Fig.12) air-inlet panel Fig.12 Fig.4 Fig.5 3 N(1) 2 open-end wrench blue black yellow- green brown union nut pipe torque wrench insulating pipe indoor pipe Outdoor unit connection Fig.6 Fig.7 36 Installation and Maintenance
Service Manual 3. Adjust the position of upper and lower adjusting baffle; clamp the connection pipe and drain pipe as firm as possible. 4. Tighten the screws. Note: All wires of indoor unit and outdoor unit should be connected by a professional. 1.If the length of power connection wire is insufficient, please contact the supplier for a new one. Avoid extending the wire by yourself. 2.For the air conditioner with plug, the plug should be reachable after finishing installation. 3.For the air conditioner without plug, an air switch must be installed in the line. The air switch should be all-pole parting and the contact parting distance should be more than 3mm. Step seven: bind up pipe 1. Bind up the connection pipe, power cord and drain hose with the band.(As show in Fig.13) 2.Reserve a certain length of drain hose and power cord for installation when binding them. When binding to a certain degree, separate the indoor power and then separate the drain hose.(As show in Fig.14) 3. Bind them evenly. 4. The liquid pipe and gas pipe should be bound separately at the end. indoor and outdoor power cord indoor unit gas pipe liquid pipe drain hose band Fig.13 drain hose band connection pipe indoor power cord Fig.14 Note: 1.The power cord and control wire can't be crossed or winding. 2.The drain hose should be bound at the bottom. 37 Installation and Maintenance Step Eight: place the indoor unit 1.Put the bound pipes in the wall pipe and then make them pass through the wall hole. 2. Stuff the gap between pipes and wall hole with sealing gum. (As show in Fig.15) 3. Fix the wall pipe. 4.Check if the indoor unit is installed firmly. indoor outdoor wall pipe sealing gum Fig.15 Note: Do not bend the drain hose too excessively in order to prevent blocking. 8.6 Installation of Outdoor Unit Step one: fix the support of outdoor unit (select it according to the actual installation situation) 1. Select installation location according to the house structure. 2. Fix the support of outdoor unit on the selected location with expansion screws. Note: 1.Take sufficient protective measures when installing the outdoor unit. 2.Make sure the support can withstand at least four times the unit weight. 3.The outdoor unit should be installed at least 3cm above the floor in order to install drain joint.(As show in Fig.16) 4.For the unit with cooling capacity of 2300W~5000W, 6 expansion screws are needed; for the unit with cooling capacity of 6000W~8000W, 8 expansion screws are needed; for the unit with cooling capacity of 10000W~16000W, 10 expansion screws are needed. At least 3cm above the floor Fig.16
Service Manual Handle Step two: install drain joint (only for cooling and heating unit) 1. Connect the outdoor drain joint into the hole on the chassis, 24K N(1) 2 3 L N as shown in the picture below. (black) yellow- green blue black brown brown blue yellow- green 2. Connect the drain hose into the drain vent.(As show in L N Fig.17) POWER Indoor unit connection NOTE: As for the shape of drainage joint,please refer to 48K : the current product.Do not install the drainage joint in the N(1) 2 3 N L severe cold area. Otherwise,it will be frosted and then cause blue brown black yellow- green blue yellow- green (black) brown malfunction L N POWER Indoor unit connection Fig.21 2. Fix the power connection wire with wire clip (only for cooling and heating unit). drain vent chassis Note: outdoor drain joint drain hose Fig.17 1.After tightening the screw, pull the power cord slightly to check if it is firm. 2. Never cut the power connection wire to prolong or shorten the distance. Step three: fix outdoor unit 1. Place the outdoor unit on the support. 2. Fix the foot holes of outdoor unit with bolts.(As show in Step six: neaten the pipes 1. The pipes should be placed along the wall, bent reasonably Fig.18) foot holes and hidden possibly. Min. semidiameter of bending the pipe is 10cm. 2. If the outdoor unit is higher than the wall hole, you must set handle a U-shaped curve in the pipe before pipe goes into the room, foot holes in order to prevent rain from getting into the room. (As show in valve cover Fig.18 Fig.23) Fig.19 Step four: connect indoor and outdoor pipes 1. Remove the screw on the right handle of outdoor unit and the drain hose can't raise upwards. then remove the handle.(As show in Fig.19) 2. Remove the screw cap of valve and aim the pipe joint at the bellmouth of pipe.(As show in Fig.20) Wall Fig.23 pipe joint gas pipe liquid pipe U-shaped curve gas valve Fig.22 union nut Drain hose Note: liquid valve Fig.20 1.The through-wall height of drain hose shouldn't be higher 3. Pretightening the union nut with hand. than the outlet pipe hole of indoor unit.(As show in Fig.23) 4. Tighten the union nut with torque wrench by referring to the 2.Slant the drain hose slightly downwards. The drain hose sheet below. can't be curved, raised and fluctuant, etc. (As show in Fig.24) Hex nut diameter(mm) Tightening torque(N m) Φ6.35(1/4") 15.7(1.6kg.m) Φ9.52(3/8") 29.4(3.0kg.m) Φ12.70(1/2") 49.0(5.0kg.m) Φ15.88(5/8") 73.6(7.5kg.m) 3.The water outlet can't be placed in water in order to drain . smoothly.(As show in Fig.25) The drain hose can't be fluctuant Step five: connect outdoor electric wire 1. Remove the wire clip; connect the power connection wire to The water outlet can't be placed in water the wiring terminal according to the color; fix them with screws. (As show in Fig.21) The drain hose can't be fluctuant Fig.25 The water outlet can't be fluctuant Fig.24 38 Installation and Maintenance
Service Manual 8.7 Vacuum Pumping and Leak Detection Use Vacuum Pump 1. Remove the valve caps on the liquid valve and gas valve and the nut of refrigerant charging vent. 2. Connect the charging hose of piezometer to the refrigerant charging vent of gas valve and then connect the other charging hose to the vacuum pump. 3. Open the piezometer completely and operate for 10-15min to check if the pressure of piezometer remains in -0.1MPa. 4. Close the vacuum pump and maintain this status for 1-2min to check if the pressure of piezometer remains in -0.1MPa. If the pressure decreases, there may be leakage. 5. Remove the piezometer, open the valve core of liquid valve and gas valve completely with inner hexagon spanner. 6. Tighten the screw caps of valves and refrigerant charging vent. (As show in Fig.26) piezometer Lo Hi liquid valve gas valve valve cap vacuum pump refrigerant charging vent valve cap nut of refrigerant charging vent inner hexagonspanner close open Fig.26 Leakage Detection 1. With leakage detector: Check if there is leakage with leakage detector. 2. With soap water: If leakage detector is not available, please use soap water for leakage detection. Apply soap water at the suspected position and keep the soap water for more than 3min. If there are air bubbles coming out of this position, there's a leakage. 39 Installation and Maintenance 8.8 Check after Installation and Test Operation 1. Check After Installation Check according to the following requirement after finishing installation. NO. Items to be checked Possible malfunction 1 Has the unit been installed firmly? The unit may drop, shake or emit noise. 2 Have you done the refrigerant leakage test? It may cause insufficient cooling (heating) capacity. 3 Is heat insulation of pipeline sufficient? It may cause condensation and water dripping. 4 Is water drained well? It may cause condensation and water dripping. Is the voltage of power supply according to the voltage marked on the nameplate? It may cause malfunction or damage the parts. 5 6 Is electric wiring and pipeline installed correctly? It may cause malfunction or damage the parts. 7 Is the unit grounded securely? It may cause electric leakage. 8 Does the power cord follow the specification? It may cause malfunction or damage the parts. 9 Is there any obstruction in air inlet and air outlet? It may cause insufficient cooling (heating) capacity. The dust and sundries caused during installation are removed? It may cause malfunction or damaging the parts. 10 11 The gas valve and liquid valve of connection pipe are open completely? It may cause insufficient cooling (heating) capacity. 12 Is the inlet and outlet of piping hole been covered? It may cause insufficient cooling (heating) capacity or waster eletricity. 2. Test Operation (1) Preparation of test operation The client approves the air conditioner installation. Specify the important notes for air conditioner to the client. (2) Method of test operation Put through the power, press ON/OFF button on the remote controller to start operation.Press MODE button to select AUTO, COOL, DRY, FAN and HEAT to check whether the operation is normal or not.If the ambient temperature is lower than 16 ℃, the air conditioner can’t start cooling.
9.Troubleshooting 9.1 Judgement by Flashing LED of Indoor No. Malfunction Error Code A/C Status Possible Causes Name 1. The main board and the display panel are not connected well. 2. The OVC terminal on main board is not connected well with the high pressure switch on the complete unit. 3. The wiring of high pressure switch is loosened. 4. Refrigerant is superabundant. 5. Poor heat exchange (including blocked heat exchanger and bad radiating environment ). 6. Ambient temperature is too high.(if it is 3-phase unit, the high pressure protection may be caused by overcurrent protection due to this reason) 7. The supply voltage is abnormal.(if it is 3-phase unit, the high pressure protection may be caused by overcurrent protection due to this reason) 8. The air intake and air discharge at indoor / outdoor heat exchanger are not smooth. The air cycle is short circuited. 9. Filter and heat exchange fins of indoor/outdoor units are blocked. 10. The system pipeline is blocked. 11. The gas valve and liquid valve for outdoor unit are not completely opened. 12. The OVC input is at high level. During cooling and drying operation, except indoor fan operates, all loads stop operation. During heating operation, if it is inverter unit, the complete unit stops; if it is floor standing unit, the complete unit stops and operation of remote controller or controller is unavailable. 1 High pressure protection E1 1. Poor air-return in indoor unit. 2. Abnormal fan speed. 3. Dirty evaporator. 4. System is normal, but the indoor tube temperature sensor is abnormal, or the tube temperature sensor is not connected well. During cooling and drying operation,compressor and outdoor fan stop while indoor fan operates. 2 Freeze protection E2 1. The main board and display panel are not connected well. 2. The LPP terminal on the main board is not connected well with the high pressure switch on the complete unit. 3. The wiring of the high pressure switch is loosened. High pressure switch is damaged or poorly contacted. 4. Insufficient or leaking out refrigerant. 5. The LPP input is at high level. 3 Low pressure protection of compressor E3 The complete unit stops During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation,all loads stop. 1. Abnormal system (e.g.: blockage, etc) 2. Abnormal rotation speed of outdoor motor (cooling ) 3. Abnormal air intake (cooling) 4. System is normal, but the compressor discharge temperature sensor is abnormal or poorly contacted. High discharge temperature protection of compressor 4 E4 1. Unstable supply voltage. Normal fluctuation shall be within 10% of the rated voltage on the nameplate. 2. Supply voltage is too low and load is too high. 3. Measure the current of live wire on main board. If the current isn’t higher than the overcurrent protection value, please check the controller. 4. The indoor and outdoor heat exchangers are too dirty, or the air inlet and air outlet are blocked. 5. The fan motor is not running. Abnormal fan speed: fan speed is too low or the fan doesn’t run. 6. The compressor is not running normally. There is abnormal sound, oil leakage or the temperature of the shell is too high, etc. 7. There’s blockage in the system. (filth blockage, ice plug, greasy blockage, Y-valve hasn’t beenopened completely) During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating operation, all loads stop. 5 Overcurrent protection E5 Heating indicator off for 0.5s and Not the error code. It’s the status code for the operation 6 Defrosting then blinks for 10s 40 Installation and Maintenance Service Manual
Service Manual No. Malfunction Error Code A/C Status Possible Causes Name 7 WIFI communication JF Loads operate normally, while the unit can’t be normally controlled by APP. malfunction During cooling operation, compressor stops while indoor fan motor operates. During heating operation, the complete unit stops. 8 Communication malfunction E6 9 Overload malfunction E8 The entire unit stops. During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation. 10 Overload protection for compressor H3 11 In defect of refrigerant F0 The Dual-8 Code Display will show F0 and the complete unit stops. The unit will stop operation as it reaches the temperature point. During cooling and drying Indoor ambient operation, except IDU fan motor operates, temperature 12 F1 other loads stop operation; During heating sensor is open/ operation, the heating fan motor operates short-circuited according to the conditions of blowing residual heat. The unit will stop operation as it reaches the Indoor temperature point. During cooling and drying evaporator operation, except IDU fan motor operates, 13 temperature F2 other loads stop operation; During heating sensor is open/ operation, the heating fan motor operates short-circuited according to the conditions of blowing residual heat. The unit will stop operation as it reaches Outdoor the temperature point. During cooling and ambient drying operation, the compressor stops 14 temperature F3 operation while IDU fan motor operates; sensor is open/ During heating operation, the heating fan short-circuited motor operates according to the conditions of blowing residual heat. The unit will stop operation as it reaches the temperature point. During cooling and drying operation, the compressor stops operation while IDU fan motor operates; During heating operation, the heating fan motor operates according to the conditions of blowing residual heat. Outdoor condenser temperature sensor is open/ 15 F4 short-circuited 41 Installation and Maintenance 1. Main board of indoor unit is damaged; 2. Detection board is damaged; 3. The connection between indoor unit and detection board is not good; Refer to the corresponding malfunction analysis. 1. Indoor and outdoor heat exchanger is too dirty? Or air inlet/outlet is blocked? 2. Fan motor doesn't work at a normal fan speed;fan speed is too low or the fan doesn't run. 3. Compressor operates normally or not? Is there any abnormal noise or oil leak? Casing is too hot? 4. System is blocked inside? (Dirt blockage? Ice blockage? Oil blockage? Y-valve is not fully open?) 5. Main board temperature sensor detects wrongly. 1. Wiring terminal OVC-COMP is loosened. In normal state, the resistance for this terminal should be less than 1ohm. 2.Refer to the malfunction analysis ( discharge protection, overload) 1. In defect of refrigerant; 2. Indoor evaporator temperature sensor works abnormally; 3. The unit has been plugged up somewhere. 1. The wiring terminal between indoor ambient temperature sensor and maiboard is loosened or poorly contacted; 2. There’s short circuit due to trip-over of the parts on maiboard; 3. Indoor ambient temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor); 4. Mainboard is broken. 1. The wiring terminal between indoor evaporator temperature sensor and maiboard is loosened or poorly contacted; 2. There’s short circuit due to trip-over of the parts on maiboard; 3. Indoor evaporator temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor); 4. Mainboard is broken. 1. The wiring terminal between outdoor ambient temperature sensor and maiboard is loosened or poorly contacted; 2. There’s short circuit due to trip-over of the parts on maiboard; 3. Outdoor ambient temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor); 4. Mainboard is broken. 1. The wiring terminal between outdoor condenser temperature sensor and maiboard is loosened or poorly contacted; 2. There’s short circuit due to trip-over of the parts on maiboard; 3. Outdoor condenser temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor); 4. Mainboard is broken.
No. Malfunction Error Code A/C Status Possible Causes Name 1. The wiring terminal between outdoor discharge temperature sensor and maiboard is loosened or poorly contacted; 2. There’s short circuit due to trip-over of the parts on maiboard; 3. Outdoor discharge temperature sensor is damaged (Please check it by referring to the resistance table for temperature sensor); 4. Mainboard is broken. The unit will stop operation as it reaches the temperature point. During cooling and drying operation, the compressor stops operation while IDU fan motor operates; During heating operation, the heating fan motor operates according to the conditions of blowing residual heat. Outdoor discharge temperature sensor is open/ 16 F5 short-circuited "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 1. The compressor wiring connection is not well connected; 2. The compressor is damaged; 3. The Outdoor mainboard is damaged. 17 IPM protection H5 "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation" 1. The unit voltage input is abnormal; 2. The inductance wire is not well connected; 3. The Outdoor mainboard is damaged. 18 PFC protection HC "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 1. The system pressure is too high; 2. The unit voltage input is too low; 3. The compressor wiring connection is not well connected; 4. The Outdoor mainboard is damaged. 19 Compressor loss step protection H7 "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 1. The compressor wiring connection is not well connected; 2. There’s too much refrigerant; 3. The compressor is damaged; 4. The Outdoor mainboard is damaged. 20 Startup failure LC "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 1. The unit voltage input is within abnormal range; 2. The electric reactor connection wiring is not well connected; 3. The Outdoor mainboard is damaged. 21 Capacitor charge malfunction PU "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 22 IPM sensor circuit malfunction P7 The Outdoor mainboard is damaged. "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 23 IPM high temperature 1. The temperature of IPM module is too high; 2.The Outdoor mainboard is damaged. P8 protection "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 24 Over voltage protection for 1. The input voltage is too high; 2. The Outdoor mainboard is damaged. PH PN "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 25 Low PN voltage 1. The input voltage is too low; 2. The Outdoor mainboard is damaged. protection PL "During cooling and drying operation, compressor will stop while indoor fan will operate; During heating operation, the complete unit will stop operation." 1. The electric reactor connection wiring is not well connected; 2.The Outdoor mainboard is damaged. 26 Charging Circuit Malfunction PU 42 Installation and Maintenance Service Manual
Service Manual 9.2 How to Check Simply the Main Part of Indoor 1. High pressure protection (E1) Start Are the display panel and main board Connect the display panel with the main board well no Malfunction is eliminated. connected tightly? yes no Are the OVC terminal on the main board connected Connect the OVC terminal on the main board with the high pressure switch on the complete unit well no Malfunction is eliminated. well with the high pressure switch on the complete unit? yes no Is the wiring of high pressure If the wire of high pressure switch is loosened, please connect the wires according to the circuit diagram. If the high pressure switch is broken or poorly contacted, please replace it. yes Malfunction is eliminated. switch loosened? Is the high pressure switch broken or poorly contacted? no no Adjust the volume of refrigerant according to the requirement of the system yes Malfunction is eliminated. Is the refrigerant superabundant? no no Is there poor heat exchange? (Including filth blockage of heat Adjust the unit to improve the heat exchange of unit yes Malfunction is eliminated. exchanger and bad radiating environment ); no no Is the ambient temperature too high?(If it is a 3-phase unit, high pressure Decrease the ambient temperature yes Malfunction is eliminated. protection may be caused by overcurrent protection due to this) no no Is the supply voltage normal? The normal voltage is lower than 90% of the rated no Malfunction is eliminated. voltage on the nameplate (If it is a 3-phase unit, high pressure protection may be caused by overcurrent protection due to this) no yes Are the air intake and air discharge at indoor / outdoor heat Adjust the system to make the air intake and air discharge of indoor and outdoor heat exchangers smooth no Malfunction is eliminated. exchanger smooth? yes no Is there filth blockage on the filter or on the heat exchanger fins of indoor / outdoor unit? no Remove the blockage. Malfunction is eliminated. no no Is there blockage inside the pipeline of the system Remove the blockage inside the pipeline of the system yes Malfunction is removed. no no Are the gas valve and liquid valve for Open the outdoor gas valve and liquid valve completely no Malfunction is eliminated. outdoor unit opened completely? yes no Replace the controller End 43 Installation and Maintenance yes yes yes yes yes yes yes yes yes yes yes
2. Freeze protection(E2) Start Poor air return in indoor unit no no The fan speed is abnormal no no Evaporator is dirty System is normal, but resistance value of indoor tube temperature sensor is abnormal no Replace control panel End 44 Installation and Maintenance Service Manual Clean the filter, check Is the problem h g u o n e s'e r e h t r e h t e h w yes yes space at the top of indoor unit solved? Check whether jumper cap and motor is Is the problem yes yes solved? normal Is the problem Clean the evaporator yes yes solved? no Replace temperature sensor Is the problem yes yes solved? no
Service Manual 3. Low pressure protection of compressor (E3) 45 Installation and Maintenance “E3" is displayed on the unit. Is the terminal of low pressure switch Re-insert it tightly to ensure reliable No inserted well? contact. Is the malfunction eliminated? Yes No Is the system pressure higher than the acting value of the low pressure Yes Add refrigerant. switch? Is the malfunction eliminated? No No Yes Test when denergized: is it a closed circuit between the two Replace the low pressure switch. No terminals led out from the switch? Is the malfunction eliminated? Yes No Yes Yes The controller is defined abnormal; replace it. Yes End
4. High discharge temperature protection of compressor (E4)
Start
Abnormal system (blockage)
no
Motor speed of
outdoor unit is abnoral
(under cooling mode)
no
Abnormal air in for
outdoor unit (under cooling
mode)
no
Normal syste, but resistance
value of discharge temperature sensor
for compressor is abnormal
no
Replace control
panel
End
46
Installation and Maintenance
Service Manual
Check the system;
eliminate the
Problem is
solved
yes
yes
blockage
no
Check wiring and
fan capacitor,
replace motor
Problem is
solved
yes
yes
no
Check the unit to
let the air come in
and come out
smoothly
Problem is
solved
yes
yes
no
Replace tempera-
ture sensor
Problem is
solved
yes
yes
noService Manual
5. Overcurrent protection (E5)
Start
nameplate
yes
Normal fluctuation is within 10% of the rated voltage on the
Is the supply voltage unstable with big fluctuation?
no
no
Adjust the supply voltage to maintain it within normal range
yes
Is the supply voltage too low with overload?
no
no
the blockage of air inlet and outlet
yes
Is the indoor / outdoor heat exchanger too dirty,
Clean the indoor and outdoor heat exchangers and remove
or are the air inlet and outlet blocked?
no
no
normally
yes
Check the motor and reinstall the motor to have the fan run
Is the fan motor running abnormally; is the fan speed too
low or does it fail to run?
no
no
Measure the current of live wire
on the main board with a clamp ampere meter. Is the
Replace the controller
no
Malfunction is eliminated.
current higher than the value of the overcurrent
protection?
yes
no
Is there blockage inside the system?
(Filth blockage, ice plug, greasy blockage, the Y-valve hasn’ t
Flush the heat exchangers with high pressure nitrogen
yes
been opened completely)
no
no
Replace the compressor
yes
Is the compressor running
abnormally? Is there abnormal sound or oil leakage; is
the temperature of the shell too high, etc.?
no
no
Replace the control
panel
End
47
Installation and Maintenance
yes
Malfunction is eliminated.
yes
Malfunction is eliminated.
yes
Malfunction is eliminated.
yes
Malfunction is eliminated.
yes
yes
Malfunction is eliminated.
yes
Malfunction is eliminated.6. Malfunction of Temperature Sensor (F1, F2, F3, F4, F5) 48 Installation and Maintenance Service Manual Troubleshooting for F1,F2 malfunction Is the wiring terminal between the temperature sensor and the controller yes loosened or poorly contacted? Insert the temperature sensor tightly no Is malfunction no eliminated Is there short circuit due to trip-over of yes the parts? Make the parts upright no Is malfunction no yes eliminated Is the temperature sensor normal according no to the Resistance Table? Replace it with a temperature sensor with the same model yes yes Is malfunction removed no Replace the mainboard with the same model. yes End
Service Manual
7. Communication malfunction(E6)
E6
If the unit operates normally
before malfunction
Check built-in wiring
of indoor and outdoor
unit
If the wiring is
damaged?
Replace the
wire
Check the malfunction
type with communication
malfunction detector
Is the malfunction
eliminated?
Replace outdoor
mainboard AP1
Malfunction of outdoor
communication circuit
Replace indoor
mainboard AP2
Is the malfunction
eliminated?
End
49
Installation and Maintenance
Check the connection
wire according to the
wiring diagram.
If the connection wire
is connected well?
Reconnect the wire or
replace the connection
wire according to the
wiring diagram.
Is the malfunction
eliminated?8. High temperature and overload protection (AP1 below means control board of outdoor unit) E8 Main detection points: ● If the outdoor ambient temperature is in normal range; ● If the indoor and outdoor fan are running normally; ● If the radiating environment of indoor and outdoor unit is good. Malfunction diagnosis process: Start If the outdoor ambient temperature is higher than 53°C? No is good? No If the indoor and outdoor fan are running normally? Yes Replace outdoor mainboard End 50 Installation and Maintenance Service Manual Normal protection, please use it after improving the outdoor ambient Yes Unit restarts Yes normally temperature No Improve the radiating environment of Yes Unit restarts unit (clean the heat exchanger and normally remove surrounding obstacles) No Yes Connect normally? Adjust the connection Yes Replace fan Yes Fan capacitor is broken? capacitor No Yes Motor is broken? Replace motor No Replace mainboard
Service Manual 9 Troubleshooting for F0 malfunction Heat exchangers are too dirty or the air inlet/outlet Clean the heat exchangers and remove Yes blockage of air inlet/outlet. is blocked. No No Compressor doesn't work normally. Strange noise or leakage occurs. Make compressor run normally. Casing is too hot. Yes No No Remove blockage in the system System is blocked inside (dirt block, ice block, oil block, Y-valve no Yes fully open). No No The refrigerant is leaking Check the leaking status of refrigerant and charge refrigerant Yes No No Replace a main board with the same model. End 51 Installation and Maintenance Malfunction is Yes eliminated. Malfunction is Yes eliminated. Malfunction is Yes eliminated. Malfunction is Yes eliminated.
10. Malfunction of detecting plate(WIFI) JF Start check if the connection wire are correctly connected Yes Replace the detecting plate with the same model Is malfunction eliminated Replace the mainboard No Yes with the same model The end 52 Installation and Maintenance Service Manual
Service Manual 9.3 How to Check Simply the Main Part of Outdoor 1. E1: High pressure protection Malfunction description: The pressure of ODU high pressure side is too high. Main check points: a. Is the system pressure is normal; b. Is the pressure switch is normal; c. If above two issues are normal, the mainboard circuit is with malfunction, please replace mainboard. 2. E2: Freeze protection Malfunction description: Too low tube temperature of IDU under cooling mode. Main check point: a. Check if the IDU fan speed is normal, if the air inlet/outlet is smooth; b. Check if the IDU, ODU heat exchanger is too dirty that affect the heat exchanging effect. 3. E3: Low pressure protection Malfunction description: The pressure of ODU low pressure side is too low Main check points: a. Is the system pressure is normal; b. Is the pressure switch is normal; c. If above two issues are normal, the mainboard circuit is with malfunction, please replace mainboard. 4. E4: The air discharging temperature is too high Main check points: a. Pull off the ODU air discharging temp. sensor, check if the temp. sensor resistance value match with present temperature; b. Check if the refrigerant is too much or too little; c. Check if the IDU, ODU heat exchanger is too dirty that affect the heat exchanging effect. 5. E6: IDU, ODU communication malfunction Main check points: a. Check if the wiring connection if IDU and ODU is correct; b. Check if the communication power supply voltage is normal, if the DC voltage is more than 56±15%, please replace the ODU mainboard. 6. F4: Outdoor condenser temperature sensor open or short circuit Malfunction description: The ODU condenser temp. sensor temperature value is too high or too low that out of the normal range. Main check points: a. Pull off the ODU condenser temp. sensor, check if the temp. sensor resistance value match with present temperature; b. If the temp. sensor resistance is normal, please replace ODU mainboard; 7. F3: ODU ambient temp. sensor open/short circuit Malfunction description: The ODU ambient temp. sensor temperature value is too high or too low that out of the normal range. Main check points: a. Pull off the ODU ambient temp. sensor, check if the temp. sensor resistance value match with present temperature; b. If the temp. sensor resistance is normal, please replace ODU mainboard; 8. F5:ODU air discharging temp. sensor open, short circuit Malfunction description: The ODU air discharging temp. sensor temperature value is too high or too low that out of the normal range. Main check points: a. Pull off the ODU air discharging temp. sensor, check if the temp. sensor resistance value match with present temperature; b. If the temp. sensor resistance is normal, please replace ODU mainboard; 9. H3: Compressor overload protection Malfunction description: Temperature of top compressor is over than the limit value Main check points: a. Normally the compressor overload protection switch is always on, check if the switch is normal. 10. H5: IPM module protection Main check points: a. Check if the compressor wiring connection is well connected, if the compressor wiring sequence is correct. The correct wiring sequence is yellow, blue, red in anticlockwise direction. b. Pull off the compressor connection wire, measure the impedance between phase U/V/W and P/N, if any of them is short circuit, please replace the ODU mainboard; c. Check if the compressor is damaged, measure the resistance between any two phases of the compressor three phases. 53 Installation and Maintenance
They should be almost the same, if they’re with big difference, the compressor is damaged, please check the insulation condition of three phases to the case. 11. HC: PFC protection Main check points: a. Check if the unit voltage input is normal; b. Check if the inductance wire is well connected; c. If the above two issues are normal, please replace the ODU mainboard. 12. H7: Compressor out-of-step malfunction Main check points: a. Check if the system pressure is too high? b. Check if the working voltage is too low? 13. Lc; Compressor startup failure Main check points: a. Check if the compressor wiring connection is well connected; b. Check if the compressor startup interval is over 3 minutes, if not, please water for 3 minutes than turn on the unit; c. Check if there’s too much refrigerant. d. Check if the compressor is damaged, measure the resistance between any two phase of the three phases, they should be almost the same, if they’re with big difference, the compressor is damaged, please check the insulation condition of three phases to the case. 14. PU: ODU capacitor charging malfunction Malfunction description: after the unit is energized, before the compressor starting operation, the electrolytic capacitor on mainbiard should be charging. After the charging command is received, if it is detected by chip that the voltage of electrolytic capacitor is low, it is ODU capacitor charging malfunction. Main check points: a. Check if the unit voltage input is within normal range. b. Check if the electric reactor connection wiring and capacitor connection wiring is well connected, if the electric reactor is open circuit. c. If above two issues are normal, please replace ODU mainboard. 15. P7: Module temp. sensor circuit malfunction Malfunction description: There’s a thermal resistance on top of IPM module, for detecting the module surface temperature, if it is detected by chip that the temperature is over the normal range. Main check points: a. The circuit on mainboard is damaged, please replace the ODU mainboard. 16. P8: Module temperature too high protection Main check points: a. After daubing radiating glue on IPM module, fix it with screw, if the glue is aging or the fixing screw is loosened, please daub the glue again or fix the screw and test again, if the malfunction still exist, please replace the mainboard. 17. PH: ODU DC bus bar voltage too high Malfunction description: When it is detected the voltage of DC bus bar on electrolytic capacitor is over 420V. Main check points: a. Check if the input voltage is too high that out of normal power supply voltage range. 18. PL: ODU DC bus bar voltage too low Malfunction description: When it is detected the voltage of DC bus bar on electrolytic capacitor is less than 200V. Main check points: a. Check if the input voltage is too low that out of normal power supply voltage range. 19. PU: Charging circuit malfunction Malfunction description: The DC bus bar voltage is less than 100V during charging. Main check points: Check if the circuit wiring connection is loosened or correct as wiring diagram, well connect the wire, if the malfunction still exist, please replace the mainboard. 54 Installation and Maintenance Service Manual
Service Manual 9.4 Maintenance Method for Normal Malfunction 1. Air Conditioner Can't be Started Up Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Confirm whether it's due to power failure. If yes, wait for power recovery. If not, check power supply circuit and make sure the power plug is connected well. Wrong wire connection between indoor unit and outdoor unit, or poor connection for wiring terminals No power supply, or poor connection for power plug After energization, operation indicator isn’t bright and the buzzer can't give out sound Under normal power supply circumstances, operation indicator isn't bright after energization Make sure the air conditioner is grounded reliably Make sure wires of air conditioner is connected correctly Check the wiring inside air conditioner. Check whether the insulation layer of power cord is damaged; if yes, place the power cord. Model selection for air switch is improper After energization, air switch trips off Select proper air switch Electric leakage for air conditionerAfter energization, room circuit breaker trips off at once After energization, operation indicator is bright, while no display on remote controller or buttons have no action. Malfunction of remote controller 2. Poor Cooling (Heating) for Air Conditioner Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Set temperature is improper Observe the set temperature on remote controller Adjust the set temperature Rotation speed of the IDU fan motor is set too low Small wind blow Set the fan speed at high or medium Filter of indoor unit is blocked Check the filter to see it's blocked Clean the filter Check whether the installation postion is proper according to installation requirement for air conditioner Installation position for indoor unit and outdoor unit is improper Discharged air temperature during cooling is higher than normal discharged wind temperature; Discharged air temperature during heating is lower than normal discharged wind temperature; Unit's pressure is much lower than regulated range Refrigerant is leaking Malfunction of 4-way valve Blow cold wind during heating Replace the 4-way valve Discharged air temperature during cooling is higher than normal discharged wind temperature; Discharged air temperature during heating is lower than normal discharged wind temperature; Unit't pressure is much lower than regulated range. If refrigerant isn’t leaking, part of capillary is blocked Malfunction of capillary Flow volume of valve is insufficient The pressure of valves is much lower than that stated in the specification Open the valve completely Malfunction of horizontal louver Horizontal louver can’t swing Refer to point 3 of maintenance method for details Malfunction of the IDU fan motor The IDU fan motor can’t operate Refer to troubleshooting for H6 for maintenance method in details Malfunction of the ODU fan motor The ODU fan motor can't operate Refer to point 4 of maintenance method for details Malfunction of compressor Compressor can't operate Refer to point 5 of maintenance method for details 3. Horizontal Louver Can't Swing Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Connect wires according to wiring diagram to make sure all wiring terminals are connected firmly Stepping motor is damaged Stepping motor can't operate Repair or replace stepping motor Wrong wire connection, or poor connection Check the wiring status according to circuit diagram Main board is damaged Others are all normal, while horizontal louver can't operate Replace the main board with the same model 55 Installation and Maintenance Check the circuit according to circuit diagram and connect wires correctly. Make sure all wiring terminals are connected firmly Replace batteries for remote controller Repair or replace remote controller Adjust the installation position, and install the rainproof and sunproof for outdoor unit Find out the leakage causes and deal with it. Add refrigerant. Replace the capillary
4. ODU Fan Motor Can't Operate Possible causes Discriminating method (air conditioner status) Troubleshooting Wrong wire connection, or poor connection Check the wiring status according to circuit diagram Measure the capacity of fan capacitor with an universal meter and find that the capacity is out of the deviation range indicated on the nameplate of fan capacitor. Capacity of the ODU fan motor is damaged Power voltage is a little low or high Use universal meter to measure the power supply voltage. The voltage is a little high or low Suggest to equip with voltage regulator When unit is on, cooling/heating performance is bad and ODU compressor generates a lot of noise and heat. Motor of outdoor unit is damaged 5. Compressor Can't Operate Possible causes Discriminating method (air conditioner status) Troubleshooting Wrong wire connection, or poor connection Check the wiring status according to circuit diagram Measure the capacity of fan capacitor with an universal meter and find that the capacity is out of the deviation range indicated on the nameplate of fan capacitor. Capacity of compressor is damaged Power voltage is a little low or high Use universal meter to measure the power supply voltage. The voltage is a little high or low Suggest to equip with voltage regulator Coil of compressor is burnt out Use universal meter to measure the resistance between compressor terminals and it's 0 Repair or replace compressor Cylinder of compressor is blocked Compressor can't operate Repair or replace compressor 6. Air Conditioner is Leaking Possible causes Discriminating method (air conditioner status) Troubleshooting Drain pipe is blocked Water leaking from indoor unit Eliminate the foreign objects inside the drain pipe Drain pipe is broken Water leaking from drain pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 7. Abnormal Sound and Vibration Possible causes Discriminating method (air conditioner status) Troubleshooting When turn on or turn off the unit, the panel and other parts will expand and there's abnormal sound There's the sound of "PAPA" Normal phenomenon. Abnormal sound will disappear after a few minutes. When turn on or turn off the unit, there's abnormal sound due to flow of refrigerant inside air conditioner Water-running sound can be heard Normal phenomenon. Abnormal sound will disappear after a few minutes. Foreign objects inside the indoor unit or there're parts touching together inside the indoor unit Remove foreign objects. Adjust all parts' position of indoor unit, tighten screws and stick damping plaster between connected parts Foreign objects inside the outdoor unit or there're parts touching together inside the outdoor unit There's abnormal sound fro indoor unit Remove foreign objects. Adjust all parts' position of outdoor unit, tighten screws and stick damping plaster between connected parts Short circuit inside the magnetic coil There's abnormal sound fro outdoor unit During heating, the way valve has abnormal electromagnetic sound Replace magnetic coil Abnormal shake of compressor Outdoor unit gives out abnormal sound Adjust the support foot mat of compressor, tighten the bolts Abnormal sound inside the compressor Abnormal sound inside the compressor 56 Installation and Maintenance Service Manual Connect wires according to wiring diagram to make sure all wiring terminals are connected firmly Replace the capacity of fan Change compressor oil and refrigerant. If no better, replace the compressor with a new one Connect wires according to wiring diagram to make sure all wiring terminals are connected firmly Replace the compressor capacitor If add too much refrigerant during maintenance, please reduce refrigerant properly. Replace compressor for other circumstances.
Service Manual 10. Exploded View and Parts List 10.1 Indoor Unit 24K The component picture is only for reference; please refer to the actual product. 57 Installation and Maintenance
NO. Description Part Code Product Code CH156N02400 1 Baffle Plate 2611454401 3 2 Left Side Plate Sub-Assy 00013100003 1 3 Top Cover Sub-Assy 20906900008 1 4 Rear Plate Sub-Assy 01304364 1 5 Right Side Plate Sub-Assy 00013000005 1 6 Breakwater Sub-Assy 01364069P 1 7 Evaporator Assy 01100100218 1 8 Protection Cover 20124112 1 9 Air Guard Sub-Assy / / 10 SteppingMotor 1521210104 1 11 Air Louver 1 10514120 1 12 Air Louver 2 10514121 5 13 Stepping Motor 15214211 1 14 Guide Louver 1 10514167 6 15 Guide Louver 2 / / 16 Guide Louver 3 / / 17 Air Outlet Panel Assy 00801400056 1 18 Big Front Panel-Assy 000055060001 1 19 Display Board 300001000195 1 20 Display Sub-Assy 000057000031 1 21 Air Intake Panel Assy 0000410001901 1 22 Filter Sub-Assy 1112423502 4 23 Temperature Sensor 390001379 1 24 Chassis 22224474 1 25 Propeller HousingPress Plate 01364215 1 26 Diversion Circle 10374006 1 27 Propeller Housing Sub-assy 12104226 1 28 Fan Motor 1501403301 1 29 Centrifugal Fan 10314075 1 30 Drainage Pipe Sub-assy 0523543401 1 31 Water Tray Sub-Assy 209041060005 1 32 Terminal Board 420001000002 1 33 Main Board 300002000765 1 34 Electric Box Cover Sub-Assy 01404922 1 35 Electric Box Assy 100002067408 1 36 Cover of pass 01254012 1 37 Connecting Cable 4002052318 1 38 Connecting Cable 4002054026 1 39 Remote Controller 305001000125 1 Above data is subject to change without notice.。 58 Installation and Maintenance Service Manual Qty GVH24AM-K6DNC7A/I
Service Manual 48K 34 7 8 1 2 4 6 3 5 30 31 33 32 27 29 26 24 25 28 37 21 36 35 22 23 38 39 41 40 16 17 18 19 20 9 10 11 12 13 15 14 42 43 The component picture is only for reference; please refer to the actual product. 59 Installation and Maintenance
NO. Description Part Code Product Code CH156N02500 1 Right Side Plate Sub-Assy 0130451801 1 2 Rear Plate Sub-Assy 01304290 1 3 Right Air Guard 01364507 1 4 Top Cover Sub-Assy 000051000034 1 5 Left Air Guard 01364506 1 6 Left Side Plate Sub-Assy 0130451901 1 7 Evaporator Assy 01100100275 1 8 Air Guard Assy 01364509 1 9 Chassis 200148000005 1 10 Wire Clamp 01384201 1 11 Fan Motor 150104060057 1 12 Water Tray Sub-Assy 12314811 1 13 Breakwater Sub-Assy 01364154P 1 14 Protection Cover 20124062 1 15 Remote Control Panel Sub-assy 20903400001 3 16 Propeller Housing Sub-assy 12104058 1 17 Centrifugal Fan 10314401 1 18 Diversion Circle 10374435 1 19 Gasket 70414201 1 20 Electric Box Cover Sub-Assy 01404388 1 21 Electric Box Assy 100002069209 1 22 Main Board 300002061447 1 23 Terminal Board 420001000002 1 24 Motor Cover 22244170 1 25 Stepping Motor 1521210104 1 26 Air Guide Bushing 1054420302 6 27 Guide Blade Lever 200235000004 1 28 Stepping Motor 15212115 1 29 Crank 1 10564204 1 30 Air Louver 1 200007000028 1 31 Air Louver 2 200007000029 5 32 Guide Louver 200004000023 6 33 Crankshaft of Guide Louver 1056420502 6 34 Air Outlet Panel Assy 000039000017 1 35 Display Sub-Assy 000057000046 1 36 Display Board 300001000195 1 37 Remote Controller 305001000125 1 38 Screw Cover 200005000006 2 39 Air Intake Panel Assy 209006000002 1 40 Filter (lower) 11124012 1 41 Filter Sub-assy(Upper) 111001000032 1 42 Connecting Cable 4002052319 1 43 Connecting Cable 4002054015 1 Above data is subject to change without notice. 60 Installation and Maintenance Service Manual Qty GVH48AL-K6DNC7A/I
Service Manual 10.2 Outdoor Unit GVH24AM-K6DNC7A/O 7 8 9 10 11 12 13 14 16 6 5 4 3 2 1 22 23 24 25 26 27 28 15 The component picture is only for reference; please refer to the actual product. 61 Installation and Maintenance 17 18 19 20 21
NO. Description Part Code Qty GVH24AM-K6DNC7A/O Product Code CH156W02400 1 Front Grill 22413045 1 2 Front Panel 01535013P 1 3 Axial Flow Fan 10335008 1 4 Fan Motor 1501506402 1 5 Electric Box Assy 100002066933 1 6 Main Board 300027060927 1 7 Terminal Board 422000060009 1 8 Handle 26233053 1 9 Left Side Plate 01305093P 1 10 Supporting Board(Condenser) 01795031 1 11 Coping 012049000007P 1 12 Motor Support Sub-Assy 01705067 1 13 Condenser Assy 011002000244 1 14 Rear Grill 01475020 1 15 Drainage Connecter 06123401 1 16 Temperature Sensor 3900030902 1 17 Electronic Expansion Valve assy 030174000041 1 18 4-Way Valve Assy 030152000318 1 19 Right Side Plate 0130509001P 1 20 Valve Support Sub-Assy 01705046P 1 21 Handle 26233053 1 22 Valve Cover 22245002 1 23 Cut off Valve 07130239 1 24 Cut off Valve 07133844 1 25 Compressor and Fittings 009001000195 1 26 Clapboard Sub-Assy 01235081 1 27 Drainage hole Cap 06813401 1 28 Chassis Sub-assy 01205816P 1 Above data is subject to change without notice. 62 Installation and Maintenance Service Manual
Service Manual GVH48AL-K6DNC7A/O The component picture is only for reference; please refer to the actual product. 63 Installation and Maintenance
NO. Description Part Code Qty GVH48AL-K6DNC7A/O Product Code CH156W02500 1 Front Grill 01572800003 1 2 Cabinet 012022000003 1 3 Diversion Circle 10474100003 1 4 Axial Flow Fan 1043410000801 1 5 Front Side Plate 012050000007 1 6 Drainage hole Cap 76715005 3 7 Drainage Joint 26113009 1 8 Compressor and Fittings 009001060077 1 9 Motor Support Sub-Assy 017012060034 1 10 Motor Support 012048060023 1 11 Brushless DC Motor 150104060013 1 12 4-Way Valve Assy 030152060458 1 13 Pressure Protect Switch 46020007 1 14 Pressure Protect Switch 4602000603 1 15 Valve Support Sub-Assy 017104000021 1 16 Cut-off valve 5/8 07103030 1 17 Cut off Valve 3/8 07130209 1 18 Handle 2690410001603 2 19 Rear Side Plate 012076000021 1 20 Electric Expand Valve Fitting 072002060023 1 21 Electric Expansion Valve Sub-Assy 030026060232 1 22 Chassis Sub-assy 017000060533 1 23 Clapboard 012051060978 1 24 Condenser Assy 011002061095 1 25 Rear Grill 01574100014 1 26 Mounting Plate 200139060032 1 27 Electric Box Assy 100002067267 1 28 Electric Box Cover 012020060532 1 29 Main Board 300027060925 1 30 Coping 01264100052 1 31 Electric Box Sub-Assy 017007062069 1 32 Module Support 200145060004 1 33 Radiator 430034060083 1 34 Electric Box Assy 2 100002068603 1 35 Mounting Plate 200139060031 1 36 Filter Board 300020060064 1 37 Electric Component Mounting Plate 012064060815 1 38 Terminal Board 420001000002 1 39 Terminal Board 422000060003 1 40 Cover of Reactor Box 012120060010 1 41 Left Side Plate 012055000007 1 42 PFC Inductance 34003206000402 1 43 Reactor Box 012119060019 1 Above data is subject to change without notice. 64 Installation and Maintenance Service Manual
Service Manual 11. Removal Procedure Caution: discharge the refrigerant completely before removal. 11.1 Removal Procedure of Indoor Unit 24K Procedure Step 1.Outside view of indoor unit 2.Remove the big front panel sub-assy Open the screw cover, use screwdriver to remove the screws at both side of big front panel sub-assy air-in panel, push the big front panel upwards and then separate the connector connected to the connection wire of display and then remove the big front panel. 65 Installation and Maintenance screw cover screw
Procedure Step 3.Remove display box sub-assy screw Take out the connection wire of display from the wire groove, remove the fixing screws of display box sub-assy, and then remove the display box sub-assy. 4. Remove air-in panel sub-assy Remove two screws on the air-in panel sub-assy. Open the air-in panel along the arrow direction and then remove the air-in panel. 5.Remove filter sub-assy Extend your hands into grooves at both sides, pull it outwards and then draw out 4 filters. 66 Installation and Maintenance Service Manual display box sub-assy big front panel sub-assy screw air-in panel sub-assy filter sub-assy
Service Manual Procedure Step 6.Remove electric box and wire-passing groove sub-assy Remove the four screws fixing the electric box cover and then remove the electric box cover; disconnect the wiring terminal of each electronic components and then remove related electronic components according to your requirements; 1.Remove the two screws fixing the electric box assy and then lift the electric box assy outwards to remove it; 2.Remove the four screws fixing the cover of wire-crossing groove and then remove the cover of wire-crossing groove; 3.Remove the four screws fixing the wire- crossing groove and then remove the wire- crossing groove sub-assy. 7.Remove air-outlet panel Remove the three screws at the top and two screws at the lower part of air outlet panel and screws in the screw covers at two sides; push the air outlet panel upwards slightly to remove the air outlet panel assy. 67 Installation and Maintenance electric box assy electric box cover screws wire-crossing groove cover wire-crossing groove screws screws air-outlet panel screws
Procedure Step 8.Remove upper cover, horizontal louver, swing board a.Remove 2 screws at the upper part of the upper cover and two screws at the back side of the air-outlet panel. b.After removing the air-guiding connecting robe, and then pull the horizontal louver outwards to remove it. c.After removing the air swing connection rod, pull the swing board inwards to remove it. 9.Remove swing motor and air-guide motor a.Remove screws used for fixing the air- guide motor and the remove the air-guide motor. b.Remove screws used for fixing the motor cover, remove the motor cover and then remove the swing motor. 10.Remove wind board Remove 11 screws used for fixing the wind board and then remove the wind board. 68 Installation and Maintenance Service Manual swing board upper cover screw horizontal louver air swing connecting rod air-guiding connecting rod swing motor screw air-guide motor motor cover screw wind board
Service Manual Procedure Step 11.Remove top cover Remove 5 screws used for fixing the top cover, pull it upwards and then remove the top cover. top cover 12.Remove evaporator Remove 4 screws used for fixing the top connection board and lower connection board of evaporator and 2 screws used for fixing the side plate, pull left and right side plates outwards slightly and take out evaporator, baffle board and water tray. After the evaporator is removed, remove left and right wind boards on the evaporator and the baffle board. 69 Installation and Maintenance screw screw screw evaporator
Procedure Step 13.Remove propeller housing, centrifugal blade and motor a.Remove 3 screws used for fixing the press plate of propeller housing, and then take out the pressure plate of propeller housing. b.Rotate the diversion loop to a certain position in the clockwise direction and then take out the diversion loop, c.Remove 9 screws used for fixing the propeller housing and then take out the propeller housing. d.Use wrench to remove the nuts used for fixing the centrifugal blade and then pull the centrifugal blade outwards. e.Take out the centrifugal blade. f.Remove 4 screws fixing the motor and 2 screws fixing the wire-pressing late, and then remove the motor. 14.Remove chassis Remove 9 screws, pull it downwards and then remove the chassis. 70 Installation and Maintenance Service Manual propeller housing diversion loop press plate of propeller housing motor centrifugal blade wire-pressing plate chassis
Service Manual Procedure Step 15. Remove left and right side plates sub-assy Remove screws on both plates, pull it to both sides respectively and then remove left and right side plates sub-assy. right side plate left side plate sub-assy 71 Installation and Maintenance sub-assy
48K Procedure Step 1.Outside view of indoor unit 2.Remove air-in panel Open the screw cover, use screwdriver to remove screws used for fixing the air-in panel at both sides, and then remove the air-in panel. 72 Installation and Maintenance Service Manual Screw cover Air - in panel
Service Manual Procedure Step 3.Remove filter, middle air-in panel Hold the buckle position at the upper part of the filter, and pull it upwards to draw out the filter. a b Remove 2 screws at top part of the air- in panel, pull the middle air-in panel upwards and then remove the middle air-in panel. 4.Remove electric box and wire-passing groove sub-assy Remove 4 screws used for fixing the electric box cover, remove the electric box cover and then pull out the wiring terminals for each component. At this time, you can remove related electriccomponents according to the needs; Remove 9 screws used for fixing the electric box, pull the electric box outwards to remove it. Remove 3 screws used for fixing the wirepassing groove, and then remove the wirepassing groove cover. Remove 3 screws used for fixing the wirepassing groove and then remove the wirepassing groove sub-assy 73 Installation and Maintenance Buckle Filter Middle air-in panel Electric box Electric box cover Screw Wire-passing groove cover Wire-passing groove Screw
Procedure Step 5.Remove air-out panel Screw Remove 3 screws at the top part of the air-out panel, 2 screw at the lower part and screws under the screw cover, push the air-output panel upwards slightly and then remove the air-output panel. 6.Remove big front panel sub-assy Remove 2 screws at the lower part, and then pull the big front panel sub-assy downwards slightly to remove it. 74 Installation and Maintenance Service Manual Air-out panel Screw Big front panel sub-assy
Service Manual Procedure Step 7.Remove display box Big front panel sub-assy Display box sub-assy Take out the display connection wire from the wire groove, remove 2 screw at the back of the display cover and then remove the display cover sub-assy. 8.Remove upper cover, air-outlet foam, guide louver, swing blade Hold both end of the foam, and then remove the air-outlet foam; Remove 2 screws at the upper part of the upper cover and 2 screws at the back side,and then the upper cover can be removed. Remove the air-guide connection rod and then pull the guide louver outwards to remove it. When the swing connection rod is removed, pull the swing blade outwards to remove it. a b c d 9.Remove swing motor and air-guide motor Remove screws used for fixing the air guide motor, and then the air guide motor can be removed. a Remove screws used for fixing the motor cover, remove the motor cover and then the swing motor can be removed. b 75 Installation and Maintenance Upper cover Swing blade Air-out foam Swing Lever Guide louver Air-guide connection rod Swing motor Air-guide louver Screw Motor cover Screw
Procedure Step 10.Remove air damper Remove 10 screws used for fixing the air damper, and then the air damper can be removed. 11.Remove electric heating part Remove 4 screws on the protective grille and then remove the protective grille; Remove 4 screws on the electric heating part and then remove the electric heating part. 76 Installation and Maintenance Service Manual Air damper Air damper Air damper
Service Manual Procedure Step 12.Remove top cover Remove 7 screws on the top cover, and then pull the top cover upwards to remove it. 13.Remove evaporator Remove 3 screws on the evaporator, 2 screw at the middle part and 2 screws at the lower part. Pull left and right side plates outwards slightly and then take out the evaporator, baffle board and water tray. When the evaporator is removed, the left and the right air damper and the baffle board of the evaporator can be removed. 77 Installation and Maintenance Screw Top cover Screw Water tray Evaporator
Procedure Step 14.Remove propeller housing, centrifugal blade and motor Remove 3 screws used for fixing the press plate of propeller housing and then remove the press plate of propeller housing; a Rotate the guide loop to a certain position along the clockwise direction, and then remove the guide loop; b Remove 9 screws used for fixing the propeller housing, and then remove the propeller housing; c Use wrench to twist off the nuts used for fixing the centrifugal chiller and then pull the centrifugal blade outwards; d e Remove the centrifugal blade; Remove 4 nuts used for fixing the motor and 2 screws used for fixing the wire- pressing plate, and the remove the motor. f 15.Remove chassis After 9 screws are removed, pull the chassis downwards to remove it. 78 Installation and Maintenance Service Manual Propeller housing Guide loop Motor Centrifugal blade Press plate of propeller housing Wire-pressing plate Chassis
Service Manual Procedure Step 16.Remove left and right side plate sub-assys Remove screws at both sides, pull them to both sides respectively and then left and right plate sub-assys can be removed. 79 Installation and Maintenance Right side plate sub-assy Left side plate sub-assy
11.2 Removal Procedure of Outdoor Unit
Warning Be sure to wait for a minimum of 10 minutes after
turning off all power supplies before disassembly.
24K
Steps
Procedure
1. Remove big handle,valve cover and top cover
Remove the screw connecting the big handle and
right side plate, and then remove the big handle.
Remove the screw connecting the valve cover and
right side plate, and then remove the valve cover.
Remove the screws connecting the top cover with
outer case, right side plate and left side plate; lift
the top cover upwards to remove it.
2. Remove grille and outer case
grille
Remove the 4 screws connecting the grille and
outer case, and then remove the panel grille.
80
Installation and Maintenance
Service Manual
handle
valve
top panelService Manual Steps Procedure Remove the screws connecting the outer case with motor support, isolation plate and chassis; lift the outer case upwards; loosen the clasps of outer case with right side plate and left side plate, and then remove the outer case. 3. Remove right&left side plate Remove the screws connecting the right side plate with electric box assy, valve support, chassis and condenser side plate, and then remove the right side plate. Remove the screws connecting the left side plate with chassis, and then remove the left side plate. 81 Installation and Maintenance outer case right side plate left side plate
Steps Procedure 4. Remove axial flow blade Remove the nut fixing axial flow blade and then remove the blade. Remove the 6 screws fixing the motor and then remove the motor. Remove the 2 screws connecting the motor support and chassis, and then loosen the stopper to remove the motor support. 5. Remove electric box Remove the screws fixing the electric box sub-assy; loosen the wire bundle; pull out the wiring terminals and then pull the electric box upwards to remove it. 82 Installation and Maintenance Service Manual axial flow fan motor support fan motor electric box
Service Manual Steps Procedure 6. Remove the soundproof sponge Tear off the sticking stripe and then remove the soundproof sponge. 7. Remove isolation plate Remove the 2 screws connecting the isolation plate and condenser side plate; remove the 3 screws connecting the isolation plate and chassis, and then remove the isolation plate. 8. Remove 4-way valve assy Unsolder the welding joints connecting the 4-way valve assy with capillary sub-assy, compressor and condenser; remove the 4-way valve. Note: Before unsoldering the welding joint, wrap the 4-way valve with a wet cloth completely to avoid damage to the valve caused by high temperature. 83 Installation and Maintenance soundproof sponge isolation plate 4-way valve assy
Steps Procedure 9. Remove compressor Remove the 3 foot nuts fixing compressor and then lift the compressor upwards to remove the compressor and damping cushion. Note: Keep the ports of discharge pipe and suction pipe from foreign objects. 10. Remove condenser sub-assy Remove the screws connecting the support (condenser) and condenser assy,and then remove the support(condenser). Remove the 2 screws fixing the condenser and chassis, and then lift the condenser upwards to remove it. 84 Installation and Maintenance Service Manual compressor support condenser sub-assy chassis subassy
Service Manual 48K Steps Procedure 1. Remove top cover Outside view of oudoor unit Remove the screws connecting the top cover with outer case, right side plate and left side plate; lift the top cover upwards to remove it. 2. Remove the rear grille Remove the tapping screws connecting the back grille with the back-side plate, the front case and the chassis. Remove the back grille. 85 Installation and Maintenance top panel rear grille screws screws
Steps Procedure 4. Remove the front side plate ate Remove the 2 tapping screws fixing the front side plate. Take the front side plate outward to remove it. 5. Remove the electric box assy 2 Remove the 2 screws connecting the electric box assy 2 and then remove the electric box assy 2 . 6. Remove the rear side plate sub-assy Remove the screws connecting the rear side plate sub-assy and then remove the rear side plate sub -assy . 86 Installation and Maintenance Service Manual front side pl screws screws electric box assy 2 rear side plate sub-assy screws screws
Service Manual Steps Procedure 7. Remove the electric box assy and electric box cover a.Open the screws fixing the electric box cover and then remove the electric box cover. b.Disconnect the connection wire of motor, compre- ssor, temperature sensor and PFC inductor; remove the ground wire screw in the wiring board and the screws fixing the electric box, and then remove the electric box assy. c.Remove the screws fixing the electric box cover and then remove the electric box cover. d.Disconnect the connection wire of PFC inductor and then remove the reactor box sub-assy. 8. Remove grille and outer case Remove the 4 screws connecting the grille and outer case, and then remove the panel grille. Remove the screws connecting the outer case with motor support, isolation plate and chassis; lift the outer case upwards; loosen the clasps of outer case with right side plate and left side plate, and then remove the outer case. 9. Remove axial flow blade Remove the nut fixing axial flow blade and then remove the blade. 87 Installation and Maintenance electric box cover reactor sub-assy cover of reactor box electric box assy outer case screws grille screws screws axial flow fan
Steps Procedure 10. Remove the fan motor and motor support motor support Remove the screws fixing the fan motor and then remove the fan moto. Remove the 2 screws connecting the motor support and chassis, and then loosen the stopper to remove the motor support. 11. Remove 4-way valve assy and electric expansion valve sub-assy Unsolder the welding joints connecting the 4-way valve assy with electric expansion valvesub-assy, compressor and condenser; remove the 4-way valve. Note: Before unsoldering the welding joint, wrap the 4-way valve with a wet cloth completely to avoid damage to the valve caused by high temperature. 12. Remove valve support sub-assy Twist off the screws connecting valve support sub-assy and chassis and then remove the valve support sub-assy. 88 Installation and Maintenance Service Manual fan motor screws 4-way valve assy electric expansion valve sub-assy valve valve support sub-assy
Service Manual Steps Procedure 13. Remove compressor Remove the 3 foot nuts fixing compressor and then lift the compressor upwards to remove the compressor and damping cushion. Note: Keep the ports of discharge pipe and suction pipe from foreign objects. 89 Installation and Maintenance compressor
Appendix: Appendix 1: Reference Sheet of Celsius and Fahrenheit Set temperature Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Fahrenheit Fahrenheit display temperature Fahrenheit display temperature Fahrenheit (℉) Celsius(℃) (℉) Celsius(℃) (℉) (℉) 61 60.8 16 69/70 69.8 21 78/79 78.8 26 62/63 62.6 17 71/72 71.6 22 80/81 80.6 27 64/65 64.4 18 73/74 73.4 23 82/83 82.4 28 66/67 66.2 19 75/76 75.2 24 84/85 84.2 29 68 68 20 77 77 25 86 86 30 Ambient temperature Fahrenheit Fahrenheit display temperature Fahrenheit display temperature Fahrenheit (℉) Celsius(℃) (℉) Celsius(℃) (℉) (℉) 32/33 32 0 55/56 55.4 13 79/80 78.8 26 34/35 33.8 1 57/58 57.2 14 81 80.6 27 36 35.6 2 59/60 59 15 82/83 82.4 28 37/38 37.4 3 61/62 60.8 16 84/85 84.2 29 39/40 39.2 4 63 62.6 17 86/87 86 30 41/42 41 5 64/65 64.4 18 88/89 87.8 31 43/44 42.8 6 66/67 66.2 19 90 89.6 32 45 44.6 7 68/69 68 20 91/92 91.4 33 46/47 46.4 8 70/71 69.8 21 93/94 93.2 34 48/49 48.2 9 72 71.6 22 95/96 95 35 50/51 50 10 73/74 73.4 23 97/98 96.8 36 52/53 51.8 11 75/76 75.2 24 99 98.6 37 54 53.6 12 77/78 77 25 Appendix 2: Configuration of Connection Pipe 1.Standard length of connection pipe(More details please refer to the specifications.) 2.Min. length of connection pipe is 3m. 3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications.) 4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe ● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each additional 5m of connection pipe. ● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe): ● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet. ● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter Additional refrigerant charging amount for R22, R407C, R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe(mm) Gas pipe(mm) Cooling only(g/m) Cooling and heating(g/m) Ф6 Ф9.5 or Ф12 15 20 Ф6 or Ф9.5 Ф16 or Ф19 15 50 Ф12 Ф19 or Ф22.2 30 120 Ф16 Ф25.4 or Ф31.8 60 120 Ф19 / 250 250 Ф22.2 / 350 350 90 Installation and Maintenance Service Manual Fahrenheit display temperature Fahrenheit (℉) Celsius(℃) (℉) Fahrenheit display temperature Fahrenheit (℉) Celsius(℃) (℉)
Service Manual Appendix 3: Pipe Expanding Method Note: Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps: A:Cut the pip ● Confirm the pipe length according to the distance of indoor unit and outdoor unit. ● Cut the required pipe with pipe cutter. B:Remove the burrs ● Remove the burrs with shaper and prevent the burrs from getting into the pipe. C:Put on suitable insulating pipe D:Put on the union nut ● Remove the union nut on the indoor connection pipe and outdoor valve; install the union nut on the pipe. E:Expand the port ● Expand the port with expander. Note: ● "A" is different according to the diameter, please refer to the sheet below: Outer diameter(mm) A(mm) Max Min Ф6 - 6.35 (1/4") 1.3 0.7 Ф9.52 (3/8”) 1.6 1.0 Ф12 - 12.70 (1/2”) 1.8 1.0 Ф16 - 15.88 (5/8”) 2.4 2.2 F:Inspection ● Check the quality of expanding port. If there is any blemish, expand the port again according to the steps above. 91 Installation and Maintenance Pipe Pipe cutter Leaning Uneven Burr Pipe Shaper Downwards Union pipe Pipe Hard mold Expander Pipe Smooth surface Improper expanding leaning damaged crack uneven thickness surface The length is equal
Appendix 4: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K) Temp( oC) Resistance(kΩ) Temp( -19 138.1 20 18.75 59 3.848 98 1.071 -18 128.6 21 17.93 60 3.711 99 1.039 -17 121.6 22 17.14 61 3.579 100 1.009 -16 115 23 16.39 62 3.454 101 0.98 -15 108.7 24 15.68 63 3.333 102 0.952 -14 102.9 25 15 64 3.217 103 0.925 -13 97.4 26 14.36 65 3.105 104 0.898 -12 92.22 27 13.74 66 2.998 105 0.873 -11 87.35 28 13.16 67 2.896 106 0.848 -10 82.75 29 12.6 68 2.797 107 0.825 -9 78.43 30 12.07 69 2.702 108 0.802 -8 74.35 31 11.57 70 2.611 109 0.779 -7 70.5 32 11.09 71 2.523 110 0.758 -6 66.88 33 10.63 72 2.439 111 0.737 -5 63.46 34 10.2 73 2.358 112 0.717 -4 60.23 35 9.779 74 2.28 113 0.697 -3 57.18 36 9.382 75 2.206 114 0.678 -2 54.31 37 9.003 76 2.133 115 0.66 -1 51.59 38 8.642 77 2.064 116 0.642 0 49.02 39 8.297 78 1.997 117 0.625 1 46.6 40 7.967 79 1.933 118 0.608 2 44.31 41 7.653 80 1.871 119 0.592 3 42.14 42 7.352 81 1.811 120 0.577 4 40.09 43 7.065 82 1.754 121 0.561 5 38.15 44 6.791 83 1.699 122 0.547 6 36.32 45 6.529 84 1.645 123 0.532 7 34.58 46 6.278 85 1.594 124 0.519 8 32.94 47 6.038 86 1.544 125 0.505 9 31.38 48 5.809 87 1.497 126 0.492 10 29.9 49 5.589 88 1.451 127 0.48 11 28.51 50 5.379 89 1.408 128 0.467 12 27.18 51 5.197 90 1.363 129 0.456 13 25.92 52 4.986 91 1.322 130 0.444 14 24.73 53 4.802 92 1.282 131 0.433 15 23.6 54 4.625 93 1.244 132 0.422 16 22.53 55 4.456 94 1.207 133 0.412 17 21.51 56 4.294 95 1.171 134 0.401 18 20.54 57 4.139 96 1.136 135 0.391 19 19.63 58 3.99 97 1.103 136 0.382 92 Installation and Maintenance Service Manual oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ)
Service Manual Resistance Table of Tube Temperature Sensors for Outdoor and Indoor(20K) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( -19 181.4 20 25.01 59 5.13 98 1.427 -18 171.4 21 23.9 60 4.948 99 1.386 -17 162.1 22 22.85 61 4.773 100 1.346 -16 153.3 23 21.85 62 4.605 101 1.307 -15 145 24 20.9 63 4.443 102 1.269 -14 137.2 25 20 64 4.289 103 1.233 -13 129.9 26 19.14 65 4.14 104 1.198 -12 123 27 18.13 66 3.998 105 1.164 -11 116.5 28 17.55 67 3.861 106 1.131 -10 110.3 29 16.8 68 3.729 107 1.099 -9 104.6 30 16.1 69 3.603 108 1.069 -8 99.13 31 15.43 70 3.481 109 1.039 -7 94 32 14.79 71 3.364 110 1.01 -6 89.17 33 14.18 72 3.252 111 0.983 -5 84.61 34 13.59 73 3.144 112 0.956 -4 80.31 35 13.04 74 3.04 113 0.93 -3 76.24 36 12.51 75 2.94 114 0.904 -2 72.41 37 12 76 2.844 115 0.88 -1 68.79 38 11.52 77 2.752 116 0.856 0 65.37 39 11.06 78 2.663 117 0.833 1 62.13 40 10.62 79 2.577 118 0.811 2 59.08 41 10.2 80 2.495 119 0.77 3 56.19 42 9.803 81 2.415 120 0.769 4 53.46 43 9.42 82 2.339 121 0.746 5 50.87 44 9.054 83 2.265 122 0.729 6 48.42 45 8.705 84 2.194 123 0.71 7 46.11 46 8.37 85 2.125 124 0.692 8 43.92 47 8.051 86 2.059 125 0.674 9 41.84 48 7.745 87 1.996 126 0.658 10 39.87 49 7.453 88 1.934 127 0.64 11 38.01 50 7.173 89 1.875 128 0.623 12 36.24 51 6.905 90 1.818 129 0.607 13 34.57 52 6.648 91 1.736 130 0.592 14 32.98 53 6.403 92 1.71 131 0.577 15 31.47 54 6.167 93 1.658 132 0.563 16 30.04 55 5.942 94 1.609 133 0.549 17 28.68 56 5.726 95 1.561 134 0.535 18 27.39 57 5.519 96 1.515 135 0.521 19 26.17 58 5.32 97 1.47 136 0.509 93 Installation and Maintenance oC) Resistance(kΩ)
Resistance Table of Discharge Temperature Sensor for Outdoor(50K) oC) Resistance(kΩ) Temp( Temp( -29 853.5 10 98 49 18.34 88 4.75 -28 799.8 11 93.42 50 17.65 89 4.61 -27 750 12 89.07 51 16.99 90 4.47 -26 703.8 13 84.95 52 16.36 91 4.33 -25 660.8 14 81.05 53 15.75 92 4.20 -24 620.8 15 77.35 54 15.17 93 4.08 -23 580.6 16 73.83 55 14.62 94 3.96 -22 548.9 17 70.5 56 14.09 95 3.84 -21 516.6 18 67.34 57 13.58 96 3.73 -20 486.5 19 64.33 58 13.09 97 3.62 -19 458.3 20 61.48 59 12.62 98 3.51 -18 432 21 58.77 60 12.17 99 3.41 -17 407.4 22 56.19 61 11.74 100 3.32 -16 384.5 23 53.74 62 11.32 101 3.22 -15 362.9 24 51.41 63 10.93 102 3.13 -14 342.8 25 49.19 64 10.54 103 3.04 -13 323.9 26 47.08 65 10.18 104 2.96 -12 306.2 27 45.07 66 9.83 105 2.87 -11 289.6 28 43.16 67 9.49 106 2.79 -10 274 29 41.34 68 9.17 107 2.72 -9 259.3 30 39.61 69 8.85 108 2.64 -8 245.6 31 37.96 70 8.56 109 2.57 -7 232.6 32 36.38 71 8.27 110 2.50 -6 220.5 33 34.88 72 7.99 111 2.43 -5 209 34 33.45 73 7.73 112 2.37 -4 198.3 35 32.09 74 7.47 113 2.30 -3 199.1 36 30.79 75 7.22 114 2.24 -2 178.5 37 29.54 76 7.00 115 2.18 -1 169.5 38 28.36 77 6.76 116 2.12 0 161 39 27.23 78 6.54 117 2.07 1 153 40 26.15 79 6.33 118 2.02 2 145.4 41 25.11 80 6.13 119 1.96 3 138.3 42 24.13 81 5.93 120 1.91 4 131.5 43 23.19 82 5.75 121 1.86 5 125.1 44 22.29 83 5.57 122 1.82 6 119.1 45 21.43 84 5.39 123 1.77 7 113.4 46 20.6 85 5.22 124 1.73 8 108 47 19.81 86 5.06 125 1.68 9 102.8 48 19.06 87 4.90 126 1.64 94 Installation and Maintenance Service Manual oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ)
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: gree@gree.com.cn www.gree.com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add: Unit 2612,26/F.,Miramar Tower 132 Nathan Road,TST,Kowloon,HK Tel: (852) 31658898 Fax: (852) 31651029 For product improvement, specifications and appearance in this manual are subject to change without prior notice. JF00304138