Change for life

Service Manual

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Sayfa 2

Table of Contents

Part I : Technical Information...................................... 1

1. Summary......................................................................... 1

2. Specifications............................................................... 3

2.1 Specification Sheet..................................................................................................3

2.2 Capacity Variation Ratio According to Temperature..................................15

2.3 Cooling and Heating Data Sheet in Rated Frequency...............................15

3. Outline Dimension Diagram.................................. 16

3.1 Indoor Unit.................................................................................................................16

3.2 Outdoor Unit.............................................................................................................18

4. Refrigerant System Diagram................................ 20

5. Electrical Part.............................................................. 22

5.1 Wiring Diagram........................................................................................................22

5.2 PCB Printed Diagram.............................................................................................27

6. Function and Control............................................... 32

6.1 Remote Controller Introduction of YAP1F7(WiFi).......................................32

6.2 GREE+ App Operation Manual...........................................................................37

6.3 Ewpe Smart App Operation Manual.................................................................38

6.4 Brief Description of Models and Functions...................................................39

Part II : Installation and Maintenance ................... 44

7. Notes for Installation and Maintenance........... 44

8. Installation.................................................................... 47

8.1 Installation Dimension Diagram........................................................................47

8.2 Installation Parts-checking ................................................................................49

8.3 Selection of Installation Location.....................................................................49

8.4 Electric Connection Requirement.....................................................................49

8.5 Installation of Indoor Unit....................................................................................50

Table of Contents

Sayfa 3

8.6 Installation of Outdoor unit.................................................................................52

8.7 Vacuum Pumping and Leak Detection............................................................53

8.8 Check after Installation and Test operation..................................................54

9. Maintenance................................................................. 55

9.1 Error Code List........................................................................................................55

9.2 Procedure of Troubleshooting...........................................................................60

9.3 Troubleshooting for Normal Malfunction.......................................................74

10. Exploded View and Parts List............................ 76

10.1 Indoor Unit..............................................................................................................76

10.2 Outdoor Unit...........................................................................................................84

11. Removal Procedure................................................ 92

11.1 Removal Procedure of Indoor Unit.................................................................92

11.2 Removal Procedure of Outdoor Unit...........................................................102

Appendix.......................................................................... 120

Appendix 1: Reference Sheet of Celsius and Fahrenheit.............................120

Appendix 2: Configuration of Connection Pipe................................................120

Appendix 3: Pipe Expanding Method...................................................................121

Appendix 4: List of Resistance for Temperature Sensor..............................122

Table of Contents

Sayfa 4

1. Summary

Indoor Unit:

A1 panel
A2 panel

B4 panel

Outdoor Unit:

GWC12AGC-S3DTA1C/O     GWH12AGC-S3DTA1C/O

GWC30AGEXH-S3DTA1A/O	 GWH30AGEXH-S3DTA1A/O	
GWC30AGEXH-S3DTA1C/O	 GWC36QF-S3DTB4A/O	
GWH36QF-S3DTB4A/O

1
Technical Information

GWC18AGD-S3DTA1A/O	
GWH18AGD-S3DTA1A/O
GWC24AGE-S3DTA1F/O	
GWH24AGE-S3DTA1F/O

Remote Controller:

YAP1F7(WiFi)

ON/OFF

TURBO

MODE

FAN

I FEEL
T-ON  T-OFF

TEMP
CLOCK

LIGHT
WiFi
SLEEP

Sayfa 5

Model list:

Remote 
Controller
1
GWC12AGC-S3DTA1C
CB385009400
GWC12AGC-S3DTA1C/I
CB385N09400
GWC12AGC-S3DTA1C/O 
CB385W09400

No
Model
Product code
Indoor model
Indoor product 

2
GWC12AGCXD-S3DTA2C CB543005100 GWC12AGCXD-S3DTA2C/I CB543N05100
3
GWH12AGC-S3DTA1C
CB385009500
GWH12AGC-S3DTA1C/I
CB385N09500
GWH12AGC-S3DTA1C/O 
CB385W09500
4
GWH12AGCXD-S3DTA2C CB543002800 GWH12AGCXD-S3DTA2C/I CB543N02800
5
GWC18AGD-S3DTA1A
CB385010100 
GWC18AGD-S3DTA1A/I
CB385N10100
GWC18AGD-S3DTA1A/O
CB385W10100
6
GWC18AGD-S3DTA2A
CB543001700
GWC18AGD-S3DTA2A/I
CB543N01700
7
GWH18AGD-S3DTA1A
CB385010000  
GWH18AGD-S3DTA1A/I
CB385N10000
GWH18AGD-S3DTA1A/O
CB385W10000
8
GWH18AGD-S3DTA2A
CB543001500
GWH18AGD-S3DTA2A/I
CB543N01500
9
GWC24AGE-S3DTA1F
CB385008700
GWC24AGE-S3DTA1F/I 
CB385N08700
GWC24AGE-S3DTA1F/O 
CB385W08700
10
GWC24AGE-S3DTA2F
CB543001300
GWC24AGE-S3DTA2F/I
CB543N01300
11
GWH24AGE-S3DTA1F 
CB385008800
GWH24AGE-S3DTA1F/I 
CB385N08800
GWH24AGE-S3DTA1F/O 
CB385W08800
12
GWH24AGE-S3DTA2F
CB543001400
GWH24AGE-S3DTA2F/I
CB543N01400
13 GWC30AGEXH-S3DTA1A CB385011000 GWC30AGEXH-S3DTA1A/I CB385N11000 GWC30AGEXH-S3DTA1A/O CB385W11000
14 GWC30AGEXH-S3DTA2A CB543001600 GWC30AGEXH-S3DTA2A/I CB543N01600
15 GWH30AGEXH-S3DTA1A CB385011100 GWH30AGEXH-S3DTA1A/I CB385N11100 GWH30AGEXH-S3DTA1A/O CB385W11100
16 GWH30AGEXH-S3DTA2A CB543001800 GWH30AGEXH-S3DTA2A/I CB543N01800
17 GWC30AGEXH-S3DTA1C CB385019100 GWC30AGEXH-S3DTA1C/I CB385N19100 GWC30AGEXH-S3DTA1C/O CB385W19100
18
GWC36QF-S3DTB4A
CB434021200
GWC36QF-S3DTB4A/I
CB434N21200
GWC36QF-S3DTB4A/O 
CB434W21200
19
GWH36QF-S3DTB4A
CB434021100
GWH36QF-S3DTB4A/I
CB434N21100
GWH36QF-S3DTB4A/O 
CB434W21100

2
Technical Information

code
Outdoor model
Outdoor 
product code

YAP1F7

(WiFi)

Sayfa 6

2. Specifications

2.1 Specification Sheet

Model 
GWC12AGC-S3DTA1C
GWC12AGCXD-S3DTA2C

Product Code
CB385009400
CB543005100

Rated Voltage 
V~
220-240
220-240

Power 
Supply

Rated Frequency
Hz
50/60
50/60

Phases
1
1

Power Supply Mode
Indoor
Indoor

Cooling Capacity
Btu/h
T1:11700 T3:11300
T1:11700 T3:11300

Heating Capacity
W
/
3700

Cooling Power Input
W
T1:877 T3:1294
T1:877 T3:1294

Heating Power Input
W
/
974

Cooling Current Input
A
T1:3.93 T3:5.8
T1:3.931 T3:5.8

Heating Current Input
A
/
4.35

Rated Input
W
1400
1400

Rated Cooling Current
A
6.28
6.28

Rated Heating Current
A
/
6.23

Air Flow Volume
m

3/h
680/620/560/490/450/420/390
680/620/560/490/450/420/390

Dehumidifying Volume
L/h
1.4
1.4

EER 
(Btu/h)/W
T1:13.35 T3:8.75
T1:13.35 T3:8.75

COP 
W/W
/
3.8

SEER 
/
/

HSPF 
/
/

Application Area
m

2
16-24
16-24

Model
GWC12AGC-S3DTA1C/I
GWC12AGCXD-S3DTA2C/I

CB385N09500
CB543N02800
Fan Type
Cross-flow
Cross-flow

Product Code
CB385N09400
CB543N05100

Fan Diameter Length(DXL) 
mm
Ф98×630
Ф98×630

Cooling Speed
r/min
1450/1200/1120/1050/980/920/750
1450/1200/1120/1050/980/920/750

Heating Speed
r/min
/
1450/1200/1140/1080/1020/960/900

Fan Motor Power Output
W
15
15

Fan Motor RLA
A
0.2
0.2

Fan Motor Capacitor 
μF
/
/

Evaporator Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Φ5
Φ7

Indoor

Evaporator Row-fin Gap
mm
2-1.4
2-1.4

Unit 

Evaporator Coil Length (LXDXW)  
mm
634×22.8×304.8
634×25.4×304.8

Swing Motor Model
MP24BA/MP24AK/MP24HF
MP24BA/MP24AK/MP24HF

Swing Motor Power Output
W
1.5/1.5/1.5
1.5/1.5/1.5

Fuse Current
A
3.15
3.15

Sound Pressure Level 
dB (A) 
44/39/37/35/33/31/27
Cooling:44/39/37/35/33/31/27
Heating:44/38/36/34/32/30/28

Sound Power Level
dB (A) 
54/49/47/45/43/41/37
Cooling:54/49/47/45/43/41/37
Heating:54/48/46/44/42/40/38
Dimension (WXHXD) 
mm
825X293X196
825X293X196

Dimension of Carton Box (LXWXH)
mm
870X349X257
870X349X257

Dimension of Package (LXWXH) 
mm
875X365X268
875X365X268

Net Weight  
kg
9.5
10.5

Gross Weight
kg
11.5
12.5

3
Technical Information

GWH12AGC-S3DTA1C
GWH12AGCXD-S3DTA2C

CB385009500
CB543002800

GWH12AGC-S3DTA1C/I
GWH12AGCXD-S3DTA2C/I

Sayfa 7

Outdoor Unit Model
GWC12AGC-S3DTA1C/O
GWH12AGC-S3DTA1C/O

Outdoor Unit Product Code
CB385W09400
CB385W09500

ZHUHAI LANDA 
COMPRESSOR CO., LTD
Compressor Model
QXFa-M111zE170
QXFa-M111zE170

Compressor Manufacturer
ZHUHAI LANDA 
COMPRESSOR CO., LTD

Compressor Oil
FW68DA or equivalent
FW68DA or equivalent

Compressor Type
Rotary
Rotary

Compressor LRA.  
A
/
/

Compressor RLA  
A
4.35
4.35

Compressor Power Input
W
950
950

Compressor Overload Protector
/
/

Throttling Method
Electron expansion valve
Electron expansion valve

Set Temperature Range 
ºC
16~30
16~30

Cooling Operation  Ambient Temperature Range 
ºC
18~60
18~60

Heating Operation  Ambient Temperature Range 
ºC
/
-7~24

Condenser  Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Φ7
Φ7.94

Condenser  Rows-fin Gap
mm
2-1.4
2-1.4

Condenser  Coil Length (LXDXW)  
mm
895×38.1×528
895×38.1×528

Fan Motor Speed
rpm
850
850

Fan Motor Power Output
W
30
30

Outdoor 

Fan Motor RLA  
A
0.4
0.4

Unit

Fan Motor Capacitor 
μF
/
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow
Axial-flow

Fan Diameter
mm
420
420

Defrosting Method
/
Automatic Defrosting

Climate Type
T3
T3

Isolation
I
I

Moisture Protection
IPX4
IPX4
Permissible Excessive Operating Pressure for 
the Discharge Side
MPa
4.3
4.3

Permissible Excessive Operating Pressure for 
the Suction Side
MPa
2.5
2.5

Sound Pressure Level
dB (A) 
53
53

Sound Power Level
dB (A) 
63
63

Dimension(WXHXD) 
mm
802X555X350
802X555X350

Dimension of Carton Box (LXWXH)
mm
869X395X594
869X395X594

Dimension of Package(LXWXH)
mm
872X398X620
872X398X620

Net Weight  
kg
31
31

Gross Weight
kg
33.5
33.5

Refrigerant 
R410A
R410A

Refrigerant Charge
kg
1.2
1.2

Connection Pipe Length
m
5
5

Connection Pipe Gas Additional Charge
g/m
15
20

Outer Diameter Liquid Pipe
inch
1/4
1/4

Connection 

Outer Diameter Gas Pipe
inch
3/8
3/8

Pipe

Max Distance Height
m
10
10

Max Distance Length
m
20
20

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

4
Technical Information

3/h
2200
2200

Sayfa 8

Model 
GWC18AGD-S3DTA1A
GWC18AGD-S3DTA2A

Product Code
CB385010100
CB543001700

Rated Voltage 
V~
220-240
220-240

Power 
Supply

Rated Frequency
Hz
50/60
50/60

Phases
1
1

Power Supply Mode
Indoor
Indoor

Cooling Capacity
Btu/h
T1:18000 T3:16900
T1:18000 T3:16900

Heating Capacity
W
/
5600

Cooling Power Input
W
T1:1350 T3:1855
T1:1350 T3:1855

Heating Power Input
W
/
1473

Cooling Current Input
A
T1:6.3 T3:8.5
T1:6.3 T3:8.5

Heating Current Input
A
/
6.8

Rated Input
W
2500
2500

Rated Cooling Current
A
11
11

Rated Heating Current
A
/
11

Air Flow Volume
m

3/h
1150/910/870/830/770/660/600
1150/910/870/830/770/660/600

Dehumidifying Volume
L/h
1.8
1.8

EER 
(Btu/h)/W
T1:13.35 T3:9.10
T1:13.35 T3:9.10

COP 
W/W
/
3.80

SEER 
/
/

HSPF 
/
/

Application Area
m

2
23-34
23-34

Model
GWC18AGD-S3DTA1A/I
GWC18AGD-S3DTA2A/I

CB385N10000
CB543N01500
Fan Type
Cross-flow
Cross-flow

Product Code
CB385N10100
CB543N01700

Fan Diameter Length(DXL) 
mm
Φ106×739
Φ106×739

Cooling Speed
r/min
1450/1200/1120/1050/980/860/750
1450/1200/1120/1050/980/860/750

Heating Speed
r/min
/
1370/1200/1120/1050/950/850/750

Fan Motor Power Output
W
50
50

Fan Motor RLA
A
0.24
0.24

Fan Motor Capacitor 
μF
/
/

Evaporator Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Φ7
Φ7

Indoor

Evaporator Row-fin Gap
mm
2-1.3
2-1.3

Unit 

Evaporator Coil Length (LXDXW)  
mm
745×22.8×342.9
745×22.8×342.9

Swing Motor Model
MP24AK/MP24BA/MP24HF
MP24AK/MP24BA/MP24HF

Swing Motor Power Output
W
1.5/1.5/1.5
1.5/1.5/1.5

Fuse Current
A
3.15
3.15

Sound Pressure Level 
dB (A) 
48/42/40/38/36/32/28
Cooling:48/42/40/38/36/32/28
Heating:48/43/41/39/35/32/29

Sound Power Level
dB (A) 
58/52/50/48/46/42/38
Cooling:58/52/50/48/46/42/38
Heating:58/53/51/49/45/42/39
Dimension (WXHXD) 
mm
982X311X221
982X311X221

Dimension of Carton Box (LXWXH)
mm
1039X377X287
1039X377X287

Dimension of Package (LXWXH) 
mm
1044X385X297
1044X385X297

Net Weight  
kg
13.5
13.5

Gross Weight
kg
16
16

5
Technical Information

GWH18AGD-S3DTA1A
GWH18AGD-S3DTA2A

CB385010000
CB543001500

GWH18AGD-S3DTA1A/I
GWH18AGD-S3DTA2A/I

Sayfa 9

Outdoor Unit Model
GWC18AGD-S3DTA1A/O
GWH18AGD-S3DTA1A/O

Outdoor Unit Product Code
CB385W10100
CB385W10000

ZHUHAI LANDA 
COMPRESSOR CO., LTD
Compressor Model
QXFa-M125zE170
QXFa-M125zE170

Compressor Manufacturer
ZHUHAI LANDA 
COMPRESSOR CO., LTD

Compressor Oil
FW68DA or equivalent
FW68DA or equivalent

Compressor Type
Rotary
Rotary

Compressor LRA.  
A
/
/

Compressor RLA  
A
5
5

Compressor Power Input
W
1085
1085

Compressor Overload Protector
/
/

Throttling Method
Electron expansion valve
Electron expansion valve

Set Temperature Range 
ºC
16~30
16~30

Cooling Operation  Ambient Temperature Range 
ºC
18~60
18~60

Heating Operation  Ambient Temperature Range 
ºC
/
-7~24

Condenser  Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Φ7
Φ7

Condenser  Rows-fin Gap
mm
2-1.4
2-1.4

Condenser  Coil Length (LXDXW)  
mm
935×38.1×616
935×38.1×616

Fan Motor Speed
rpm
820
820

Fan Motor Power Output
W
60
60

Outdoor 

Fan Motor RLA  
A
0.65
0.65

Unit

Fan Motor Capacitor 
μF
/
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow
Axial-flow

Fan Diameter
mm
520
520

Defrosting Method
/
Automatic Defrosting

Climate Type
T3
T3

Isolation
I
I

Moisture Protection
IPX4
IPX4
Permissible Excessive Operating Pressure for 
the Discharge Side
MPa
4.3
4.3

Permissible Excessive Operating Pressure for 
the Suction Side
MPa
2.5
2.5

Sound Pressure Level
dB (A) 
58
60

Sound Power Level
dB (A) 
68
70

Dimension(WXHXD) 
mm
958X660X402
958X660X402

Dimension of Carton Box (LXWXH)
mm
1029X453X715
1029X453X715

Dimension of Package(LXWXH)
mm
1032X456X737
1032X456X737

Net Weight  
kg
41.5
42.5

Gross Weight
kg
46
47

Refrigerant 
R410A
R410A

Refrigerant Charge
kg
1.6
1.6

Connection Pipe Length
m
5
5

Connection Pipe Gas Additional Charge
g/m
50
50

Outer Diameter Liquid Pipe
inch
1/4
1/4

Connection 

Outer Diameter Gas Pipe
inch
5/8
5/8

Pipe

Max Distance Height
m
10
10

Max Distance Length
m
25
25

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

6
Technical Information

3/h
3600
3600

Sayfa 10

Model 
GWC24AGE-S3DTA1F
GWC24AGE-S3DTA2F

Product Code
CB385008700
CB543001300

Rated Voltage 
V~
220-240
220-240

Power 
Supply

Rated Frequency
Hz
50/60
50/60

Phases
1
1

Power Supply Mode
Indoor
Indoor

Cooling Capacity
Btu/h
T1:22000 T3:22000
T1:22000 T3:22000

Heating Capacity
W
/
7350

Cooling Power Input
W
T1:1654 T3:2471
T1:1654 T3:2471

Heating Power Input
W
/
1885

Cooling Current Input
A
T1:7.5 T3:11
T1:7.5 T3:11

Heating Current Input
A
/
8.5

Rated Input
W
2550
3050

Rated Cooling Current
A
13.5
13.5

Rated Heating Current
A
/
11

Air Flow Volume
m

3/h
1450/1100/1050/950/900/850/800
1450/1100/1050/950/900/850/800

Dehumidifying Volume
L/h
2.5
2.5

EER 
(Btu/h)/W
T1:13.3 T3:8.9
T1:13.3 T3:8.9

COP 
W/W
/
3.9

SEER 
/
/

HSPF 
/
/

Application Area
m

2
32-50
32-50

Model
GWC24AGE-S3DTA1F/I
GWC24AGE-S3DTA2F/I

CB385N08800
CB543N01400
Fan Type
Cross-flow
Cross-flow

Product Code
CB385N08700
CB543N01300

Fan Diameter Length(DXL) 
mm
Φ108×830
Φ108×830

Cooling Speed
r/min
1500/1150/1100/1000/950/900/850
1500/1150/1100/1000/950/900/850

Heating Speed
r/min
/
1500/1200/1100/1050/1000/950/900

Fan Motor Power Output
W
60
60

Fan Motor RLA
A
0.28
0.28

Fan Motor Capacitor 
μF
/
/

Evaporator Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Φ7
Φ7

Indoor

Evaporator Row-fin Gap
mm
2-1.4
2-1.4

Unit 

Evaporator Coil Length (LXDXW)  
mm
850×25.4×342.9
850×25.4×342.9

Swing Motor Model
MP24AK/MP24HF
MP24AK/MP24HF

Swing Motor Power Output
W
1.5/1.5
1.5/1.5

Fuse Current
A
3.15
3.15

Sound Pressure Level 
dB (A) 
53/46/44/41/40/38/36
Cooling:53/46/44/41/40/38/36
Heating:52/44/42/41/39/37/36

Sound Power Level
dB (A) 
63/56/54/51/50/48/46
Cooling:63/56/54/51/50/48/46
Heating:62/54/52/51/49/47/46
Dimension (WXHXD) 
mm
1075X333X246
1075X333X246

Dimension of Carton Box (LXWXH)
mm
1128X406X323
1128X406X323

Dimension of Package (LXWXH) 
mm
1133X414X333
1133X414X333

Net Weight  
kg
16
16

Gross Weight
kg
19
19

7
Technical Information

GWH24AGE-S3DTA1F
GWH24AGE-S3DTA2F

CB385008800
CB543001400

GWH24AGE-S3DTA1F/I
GWH24AGE-S3DTA2F/I

Sayfa 11

Outdoor Unit Model
GWC24AGE-S3DTA1F/O
GWH24AGE-S3DTA1F/O

Outdoor Unit Product Code
CB385W08700
CB385W08800

ZHUHAI LANDA 
COMPRESSOR CO., LTD
Compressor Model
QXFb-M180zX170
QXFb-M180zX170

Compressor Manufacturer
ZHUHAI LANDA 
COMPRESSOR CO., LTD

Compressor Oil
FW68DA or equivalent
FW68DA or equivalent

Compressor Type
Rotary
Rotary

Compressor LRA.  
A
24
24

Compressor RLA  
A
3.5
3.5

Compressor Power Input
W
1350
1350

Compressor Overload Protector
HPC 115/95U1 KSD115

Throttling Method
Electron expansion valve
Electron expansion valve

Set Temperature Range 
ºC
16~30
16~30

Cooling Operation  Ambient Temperature Range 
ºC
18~60
18~60

Heating Operation  Ambient Temperature Range 
ºC
/
-7~24

Condenser  Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Φ7
Φ7

Condenser  Rows-fin Gap
mm
2-1.4
2-1.4

Condenser  Coil Length (LXDXW)  
mm
839×38.1×616
839×38.1×616

Fan Motor Speed
rpm
800
800

Fan Motor Power Output
W
60
60

Outdoor 

Fan Motor RLA  
A
0.65
0.65

Unit

Fan Motor Capacitor 
μF
/
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow
Axial-flow

Fan Diameter
mm
520
520

Defrosting Method
/
Automatic Defrosting

Climate Type
T3
T3

Isolation
I
I

Moisture Protection
IPX4
IPX4
Permissible Excessive Operating Pressure for 
the Discharge Side
MPa
4.3
4.3

Permissible Excessive Operating Pressure for 
the Suction Side
MPa
2.5
2.5

Sound Pressure Level
dB (A) 
60
60

Sound Power Level
dB (A) 
70
70

Dimension(WXHXD) 
mm
958X660X402
958X660X402

Dimension of Carton Box (LXWXH)
mm
1029X453X715
1029X453X715

Dimension of Package(LXWXH)
mm
1032X456X737
1032X456X737

Net Weight  
kg
42
43.5

Gross Weight
kg
46.5
48

Refrigerant 
R410A
R410A

Refrigerant Charge
kg
1.9
1.9

Connection Pipe Length
m
5
5

Connection Pipe Gas Additional Charge
g/m
15
50

Outer Diameter Liquid Pipe
inch
1/4
1/4

Connection 

Outer Diameter Gas Pipe
inch
5/8
5/8

Pipe

Max Distance Height
m
10
10

Max Distance Length
m
25
25

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

8
Technical Information

oC
HPC 115/95U1 KSD115

oC

3/h
3600
3600

Sayfa 12

Model 
GWC30AGEXH-S3DTA1A
GWC30AGEXH-S3DTA2A

Product Code
CB385011000
CB543001600 

Rated Voltage 
V~
220-240
220-240

Power 
Supply

Rated Frequency
Hz
50/60
50/60

Phases
1
1

Power Supply Mode
Outdoor
Outdoor

Cooling Capacity
Btu/h
T1:27400 T3:24000
T1:27400 T3:24000

Heating Capacity
W
/
8600

Cooling Power Input
W
T1:2236 T3:2682
T1:2236 T3:2682

Heating Power Input
W
/
2440

Cooling Current Input
A
T1:10.5 T3:12.3
T1:10.5 T3:12.3

Heating Current Input
A
/
11.3

Rated Input
W
3500
3500

Rated Cooling Current
A
16
16

Rated Heating Current
A
/
/

Air Flow Volume
m

3/h
1500/1100/1050/950/900/850/800
1500/1100/1050/950/900/850/800

Dehumidifying Volume
L/h
3
3

EER 
(Btu/h)/W
T1:12.25 T3:8.95
T1:12.25 T3:8.95

COP 
W/W
/
3.50

SEER 
/
/

HSPF 
/
/

Application Area
m

2
35-52
35-52

Model
GWC30AGEXH-S3DTA1A/I
GWC30AGEXH-S3DTA2A/I

Product Code
CB385N11000
CB543N01600

CB385N11100
CB543N01800
Fan Type
Cross-flow
Cross-flow

Fan Diameter Length(DXL) 
mm
Φ108×830
Φ108×830

Cooling Speed
r/min
1500/1150/1100/1000/950/900/850
1500/1150/1100/1000/950/900/850

Heating Speed
r/min
/
1500/1200/1100/1050/1000/950/900

Fan Motor Power Output
W
60
60

Fan Motor RLA
A
0.28
0.28

Fan Motor Capacitor 
μF
/
/

Evaporator Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Φ7
Φ7

Indoor

Evaporator Row-fin Gap
mm
2-1.3
2-1.3

Unit 

Evaporator Coil Length (LXDXW)  
mm
850×25.4×342.9
850×25.4×342.9

Swing Motor Model
MP24AK/MP24HF
MP24AK/MP24HF

Swing Motor Power Output
W
1.5/1.5
1.5/1.5

Fuse Current
A
3.15
3.15

Sound Pressure Level 
dB (A) 
53/45/44/41/40/38/36
Cooling:53/45/44/41/40/38/36
Heating:52/44/42/41/39/37/36

Sound Power Level
dB (A) 
63/55/54/51/50/48/46
Cooling:63/55/54/51/50/48/46
Heating:62/54/52/51/49/47/46
Dimension (WXHXD) 
mm
1075X333X246
1075X333X246

Dimension of Carton Box (LXWXH)
mm
1128X406X323
1128X406X323

Dimension of Package (LXWXH) 
mm
1133X414X333
1133X414X333

Net Weight  
kg
16
16

Gross Weight
kg
19
19

9
Technical Information

GWH30AGEXH-S3DTA1A
GWH30AGEXH-S3DTA2A

CB385011100
CB543001800

GWH30AGEXH-S3DTA1A/I
GWH30AGEXH-S3DTA2A/I

Sayfa 13

Outdoor Unit Model
GWC30AGEXH-S3DTA1A/O
GWH30AGEXH-S3DTA1A/O

Outdoor Unit Product Code
CB385W11000
CB385W11100

ZHUHAI LANDA 
COMPRESSOR CO., LTD
Compressor Model
QXFb-B238zX070
QXFb-B238zX070

Compressor Manufacturer
ZHUHAI LANDA 
COMPRESSOR CO., LTD

Compressor Oil
/
/

Compressor Type
Rotary
Rotary

Compressor LRA.  
A
/
/

Compressor RLA  
A
/
/

Compressor Power Input
W
/
/

Compressor Overload Protector
/
/

Throttling Method
Electron expansion valve
Electron expansion valve

Set Temperature Range 
ºC
16~30
16~30

Cooling Operation  Ambient Temperature Range 
ºC
18~60
18~60

Heating Operation  Ambient Temperature Range 
ºC
/
-7~24

Condenser  Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Φ7
Φ7

Condenser  Rows-fin Gap
mm
3-1.4
3-1.4

Condenser  Coil Length (LXDXW)  
mm
955X57.15X704
955X57.15X704

Fan Motor Speed
rpm
850
850

Fan Motor Power Output
W
90
90

Outdoor 

Fan Motor RLA  
A
0.65
0.65

Unit

Fan Motor Capacitor 
μF
/
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow
Axial-flow

Fan Diameter
mm
570
570

Defrosting Method
/
Automatic Defrosting

Climate Type
T3
T3

Isolation
I
I

Moisture Protection
IPX4
IPX4
Permissible Excessive Operating Pressure for 
the Discharge Side
MPa
4.3
4.3

Permissible Excessive Operating Pressure for 
the Suction Side
MPa
2.5
2.5

Sound Pressure Level
dB (A) 
62
62

Sound Power Level
dB (A) 
72
72

Dimension(WXHXD) 
mm
1000X746X427
1000X746X427

Dimension of Carton Box (LXWXH)
mm
1077X480X785
1077X480X785

Dimension of Package(LXWXH)
mm
1080X483X810
1080X483X810

Net Weight  
kg
56
57

Gross Weight
kg
61
62

Refrigerant 
R410A
R410A

Refrigerant Charge
kg
2.1
2.1

Connection Pipe Length
m
5
5

Connection Pipe Gas Additional Charge
g/m
15
50

Outer Diameter Liquid Pipe
inch
1/4
1/4

Connection 

Outer Diameter Gas Pipe
inch
5/8
5/8

Pipe

Max Distance Height
m
25
25

Max Distance Length
m
40
40

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

10
Technical Information

3/h
4000
4000

Sayfa 14

Model 
GWC30AGEXH-S3DTA1C

Product Code
CB385019100

Rated Voltage 
V~
220-240

Power 
Supply

Rated Frequency
Hz
50/60

Phases
1

Power Supply Mode
Outdoor

Cooling Capacity
Btu/h
T1:27400 T3:24000

Heating Capacity
W
/

Cooling Power Input
W
T1:2236 T3:2682

Heating Power Input
W
/

Cooling Current Input
A
T1:10.5 T3:12.3

Heating Current Input
A
/

Rated Input
W
3500

Rated Cooling Current
A
16

Rated Heating Current
A
/

Air Flow Volume
m

Dehumidifying Volume
L/h
3

EER 
(Btu/h)/W
T1:12.25 T3:8.95

COP 
W/W
/

SEER 
15

HSPF 
/

Application Area
m

Model
GWC30AGEXH-S3DTA1C/I

Product Code
CB385N19100

Fan Type
Cross-flow

Fan Diameter Length(DXL) 
mm
Φ108×830

Cooling Speed
r/min
1500/1150/1100/1000/950/900/850

Heating Speed
r/min
/

Fan Motor Power Output
W
60

Fan Motor RLA
A
0.28

Fan Motor Capacitor 
μF
/

Evaporator Form 
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Φ7

Indoor

Evaporator Row-fin Gap
mm
2-1.3

Unit 

Evaporator Coil Length (LXDXW)  
mm
850×25.4×342.9

Swing Motor Model
MP24AK/MP24HF

Swing Motor Power Output
W
1.5/1.5

Fuse Current
A
3.15

Sound Pressure Level 
dB (A) 
53/45/44/41/40/38/36

Sound Power Level
dB (A) 
63/55/54/51/50/48/46

Dimension (WXHXD) 
mm
1075X333X246

Dimension of Carton Box (LXWXH)
mm
1128X406X323

Dimension of Package (LXWXH) 
mm
1133X414X333

Net Weight  
kg
16

Gross Weight
kg
19

11
Technical Information

3/h
1500/1100/1050/950/900/850/800

2
35-52

Sayfa 15

Outdoor Unit Model
GWC30AGEXH-S3DTA1C/O

Outdoor Unit Product Code
CB385W19100

Compressor Manufacturer
ZHUHAI LANDA COMPRESSOR CO., LTD

Compressor Model
QXFb-B238zX070

Compressor Oil
/

Compressor Type
Rotary

Compressor LRA.  
A
/

Compressor RLA  
A
/

Compressor Power Input
W
/

Compressor Overload Protector
/

Throttling Method
Electron expansion valve

Set Temperature Range 
ºC
16~30

Cooling Operation  Ambient Temperature Range 
ºC
18~60

Heating Operation  Ambient Temperature Range 
ºC
/

Condenser  Form 
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Φ7

Condenser  Rows-fin Gap
mm
3-1.4

Condenser  Coil Length (LXDXW)  
mm
955X57.15X704

Fan Motor Speed
rpm
850

Fan Motor Power Output
W
90

Outdoor 

Fan Motor RLA  
A
0.7

Unit

Fan Motor Capacitor 
μF
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow

Fan Diameter
mm
570

Defrosting Method
/

Climate Type
T3

Isolation
I

Moisture Protection
IPX4
Permissible Excessive Operating Pressure for 
the Discharge Side
MPa
4.3

Permissible Excessive Operating Pressure for 
the Suction Side
MPa
2.5

Sound Pressure Level
dB (A) 
62

Sound Power Level
dB (A) 
72

Dimension(WXHXD) 
mm
1000X746X427

Dimension of Carton Box (LXWXH)
mm
1077X480X785

Dimension of Package(LXWXH)
mm
1080X483X810

Net Weight  
kg
56

Gross Weight
kg
61

Refrigerant 
R410A

Refrigerant Charge
kg
2.1

Connection Pipe Length
m
5

Connection Pipe Gas Additional Charge
g/m
15

Outer Diameter Liquid Pipe
inch
1/4

Connection 

Outer Diameter Gas Pipe
inch
5/8

Pipe

Max Distance Height
m
25

Max Distance Length
m
40

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

12
Technical Information

3/h
4500

Sayfa 16

Model 
GWC36QF-S3DTB4A
GWH36QF-S3DTB4A

Product Code
CB434021200
CB434021100

Rated Voltage 
V~
220-240
220-240

Power 
Supply

Rated Frequency
Hz
50/60
50/60

Phases
1
1

Power Supply Mode
Outdoor
Outdoor

Cooling Capacity
Btu/h
T1:32400 T3:29600
T1:32400 T3:29600

Heating Capacity
W
/
9550

Cooling Power Input
W
T1:2645 T3:3326
T1:2645 T3:3326

Heating Power Input
W
/
2691

Cooling Current Input
A
T1:12 T3:14.8
T1:12 T3:14.8

Heating Current Input
A
/
12

Rated Input
W
3700
3750

Rated Cooling Current
A
17
17

Rated Heating Current
A
/
15

Air Flow Volume
m

Dehumidifying Volume
L/h
3.5
3.5

EER 
(Btu/h)/W
T1:12.25 T3:8.9
T1:12.25 T3:8.9

COP 
W/W
/
3.55

SEER 
/
/

HSPF 
/
/

Application Area
m

Model
GWC36QF-S3DTB4A/I
GWH36QF-S3DTB4A/I

Product Code
CB434N21200
CB434N21100

Fan Type
Cross-flow
Cross-flow

Fan Diameter Length(DXL) 
mm
Φ108×522.7×2
Φ108×522.7×2

Cooling Speed
r/min
1650/1300/1250/1150/1050/950/850
1650/1300/1250/1150/1050/950/850

Heating Speed
r/min
/
1500/1300/1250/1150/1100/1050/950

Fan Motor Power Output
W
70
70

Fan Motor RLA
A
0.3
0.3

Fan Motor Capacitor 
μF
/
/

Evaporator Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Φ7
Φ7

Evaporator Row-fin Gap
mm
2-1.3
2-1.3

Indoor

Unit 

Evaporator Coil Length (LXDXW)  
mm
1074×25.4×381
1074×25.4×381

Swing Motor Model
MP24CE MP24CC MP24BA
MP24CE MP24CC MP24BA

Swing Motor Power Output
W
1.5/1.5 /1.5
1.5/1.5 /1.5

Fuse Current
A
5
5

Sound Pressure Level 
dB (A) 
58/50/49/46/44/40/37
Cooling:58/50/49/46/44/40/37
Heating:57/52/50/47/46/44/41

Sound Power Level
dB (A) 
68/60/59/56/54/50/47
Cooling:68/60/59/56/54/50/47
Heating:67/62/60/57/56/54/51
Dimension (WXHXD) 
mm
1350X326X253
1350X326X253

Dimension of Carton Box (LXWXH)
mm
1438X418X352
1438X418X352

Dimension of Package (LXWXH) 
mm
1441X421X367
1441X421X367

Net Weight  
kg
19.5
19.5

Gross Weight
kg
24
24

13
Technical Information

3/h
1600/1250/1200/1100/1000/900/800
1600/1250/1200/1100/1000/900/800

2
46-70
46-70

Sayfa 17

Outdoor Unit Model
GWC36QF-S3DTB4A/O
GWH36QF-S3DTB4A/O

Outdoor Unit Product Code
CB434W21200
CB434W21100

Compressor Manufacturer
ZHUHAI LANDA 
COMPRESSOR CO., LTD.

ZHUHAI LANDA 
COMPRESSOR CO., LTD.
Compressor Model
QXFb-D280zX070
QXFb-D280zX070

Compressor Oil
FW68DA or equivalent
FW68DA or equivalent

Compressor Type
Rotary
Rotary

Compressor LRA.  
A
40
40

Compressor RLA  
A
5.5
5.5

Compressor Power Input
W
2475
2475

Compressor Overload Protector
HPC115/95U1 KSD115

Throttling Method
Capillary
Capillary

Set Temperature Range 
ºC
16~30
16~30

Cooling Operation  Ambient Temperature Range 
ºC
18~60
18~60

Heating Operation  Ambient Temperature Range 
ºC
/
-7~24

Condenser  Form 
Aluminum Fin-copper Tube
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Φ7.94
Φ7.94

Condenser  Rows-fin Gap
mm
3 - 1.4
3 - 1.4

Condenser  Coil Length (LXDXW)  
mm
955X57.15X704
955X57.15X704

Fan Motor Speed
rpm
850
850

Fan Motor Power Output
W
90
90

Outdoor 

Fan Motor RLA  
A
0.7
0.7

Unit

Fan Motor Capacitor 
μF
/
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow
Axial-flow

Fan Diameter
mm
570
570

Defrosting Method
/
Automatic Defrosting

Climate Type
T3
T3

Isolation
I
I

Moisture Protection
IPX4
IPX4
Permissible Excessive Operating Pressure for 
the Discharge Side
MPa
4.3
4.3

Permissible Excessive Operating Pressure for 
the Suction Side
MPa
2.5
2.5

Sound Pressure Level
dB (A) 
62
62

Sound Power Level
dB (A) 
72
72

Dimension(WXHXD) 
mm
1000X746X427
1000X746X427

Dimension of Carton Box (LXWXH)
mm
1077X480X785
1077X480X785

Dimension of Package(LXWXH)
mm
1080X483X810
1080X483X810

Net Weight  
kg
61
62

Gross Weight
kg
66
67

Refrigerant 
R410A
R410A

Refrigerant Charge
kg
2.7
2.7

Connection Pipe Length
m
5
5

Connection Pipe Gas Additional Charge
g/m
15
50

Outer Diameter Liquid Pipe
inch
1/4
1/4

Connection 

Outer Diameter Gas Pipe
inch
3/4
3/4

Pipe

Max Distance Height
m
25
25

Max Distance Length
m
40
40

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

14
Technical Information

oC
HPC115/95U1 KSD115

oC

3/h
4500
4500

Sayfa 18

2. Specifications

2.2 Capacity Variation Ratio According to Temperature

Cooling

Heatling

140

120

120

100

100

80

Capacity ratio(%)

Capacity ratio(%)

80

60

Conditions
Indoor:DB20°C
Indoor air flow:Super High
Pipe length:5m

60

Condition Cooling
Indoor:DB27°C/WB19°C

40

40

Indoor air flow:Super High

Pipe length:5m
 

20

20

0

0

-7
-5
0
5
10
15
20
24

1820
25
30
35
40
45
50
55
60

Outdoor Temp.(°C)

Outdoor Temp.(°C)

18K
12K
24/30K
36K
18K
12K
24/30K
36K

2.3 Cooling and Heating Data Sheet in Rated Frequency

Cooling:

Pressure of gas 
pipe connecting 
indoor and outdoor 

Inlet and outlet pipe 
temperature of heat 

Rated cooling condition(°C) 

Fan speed of 

Fan speed of 

(DB/WB) 
Model

exchanger

indoor unit

outdoor unit

unit

Indoor 
Outdoor 
P (MPa) 
T1 (°C) 
T2 (°C) 

27/19
35/24
12K ~ 24K
0.9 ~ 1.1
in:12
out:14

in:75
out:37
Super High
High

27/19
35/24
30K
0.8 ~ 1.0
in:8 ~ 11
out:11 ~ 14

in:75 ~ 85
out:37 ~ 43
Super High
High

27/19
35/24
36K
0.7 ~ 0.9
in:10
out:12

in:78
out:37
Super High
High

Heating:

Pressure of gas 
pipe connecting 
indoor and outdoor 

Inlet and outlet pipe 
temperature of heat 

Rated heating condition(°C) 

Fan speed of 

Fan speed of 

(DB/WB)
Model

exchanger

indoor unit

outdoor unit

unit 

Indoor 
Outdoor 
P (MPa) 
T1 (°C) 
T2 (°C) 

20/-
7/6
12K ~ 24K
2.2 ~ 2.4
in:70
out:35

in:2
out:4
Super High
High

20/-
7/6
30K
2.2 ~ 2.4
in:75 ~ 85
out:37 ~ 43

in:1 ~ 3
out:2 ~ 5
Super High
High

20/-
7/6
36K
2.4 ~ 2.7
in:71
out:36

in:1
out:7
Super High
High

Instruction:
T1: Inlet and outlet pipe temperature of evaporator  
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve 
Connection pipe length: 5 m.

15
Technical Information

Sayfa 19

3. Outline Dimension Diagram

3.1 Indoor Unit

W

D

H

AGC

W3
W2
W1

Φ55

43

116

155

AGD

W3
W2
W1

Φ55

40

40

178
89

AGE

W3
W2
W1

Φ70

43

175
60

Model
W
H
D
W1
W2
W3

AGC
825
293
196
113
542
170

AGD
982
311
221
122.5
707.5
152

AGE
1075
333
246
184
707.5
183.5

* Recommended distance

16
Technical Information

Sayfa 20

QF

1350

350
254
746

Φ70
Φ70

40

295
90

17
Technical Information

326

253

Unit: mm

Sayfa 21

3.2 Outdoor Unit

GWC12AGC-S3DTA1C/O   GWH12AGC-S3DTA1C/O

300

555

350

Unit:mm

GWC18AGD-S3DTA1A/O  GWH18AGD-S3DTA1A/O  GWC24AGE-S3DTA1F/O   GWH24AGE-S3DTA1F/O

340

660

402

Unit:mm

18
Technical Information

745

802

332

512

889

958

371

570

Sayfa 22

GWC30AGEXH-S3DTA1A/O	
GWH30AGEXH-S3DTA1A/O	
GWC30AGEXH-S3DTA1C/O	
GWC36QF-S3DTB4A/O	
GWH36QF-S3DTB4A/O

369

746

427

Unit:mm

395

19
Technical Information

923

1000

610

Sayfa 23

4. Refrigerant System Diagram

Cooling only model(12~24K)

INDOOR UNIT
UTDOOR UNIT
O

HEAT
EXCHANGE
(EVAPORATOR)

Cooling only model(30K/36K)

INDOOR UNIT
UTDOOR UNIT
O

HEAT
EXCHANGE
(EVAPORATOR)

20
Technical Information

GAS SIDE

3-WAY VALVE

Discharge

Accumlator

Suction

COMPRESSOR

HEAT

EXCHANGE

(CONDENSER)

Intercooler

LIQUID SIDE

Strainer
Electron
expansion 

Capillary

2-WAY VALVE

valve 

COOLING

GAS SIDE

3-WAY VALVE

Discharge

Accumlator

Suction

COMPRESSOR

HEAT

EXCHANGE

(CONDENSER)

Intercooler

LIQUID SIDE

Throttling device *

Strainer

2-WAY VALVE

COOLING

*  Electron expansion valve(30K)  or Capillary(36K)

Sayfa 24

Heat pump model(12K)

INDOOR UNIT
UTDOOR UNIT
O

HEAT
EXCHANGE
(EVAPORATOR)

Heat pump model(18~36K)

INDOOR UNIT
UTDOOR UNIT
O

HEAT
EXCHANGE
(EVAPORATOR)

Connection pipe specification:
Liquid pipe:1/4" 
Gas pipe:   3/8" (12K)     5/8"(18~36K) 

21
Technical Information

GAS SIDE

3-WAY VALVE

4-Way valve

Discharge

Accumlator

Suction

COMPRESSOR

HEAT

EXCHANGE
(CONDENSER)

Intercooler

LIQUID SIDE

Electron
expansion 

Throttle Valve

Strainer

2-WAY VALVE

valve 

COOLING
HEATING

GAS SIDE

3-WAY VALVE

4-Way valve

Discharge

Accumlator

Suction

COMPRESSOR

HEAT

EXCHANGE
(CONDENSER)

Intercooler

LIQUID SIDE

Strainer
Strainer

Capillary
Throttling device *

2-WAY VALVE

COOLING
HEATING

*  Electron expansion valve(18~30K)  or Capillary(36K)

Sayfa 25

5. Electrical Part

5.1 Wiring Diagram

●Instruction

Symbol
Symbol Color 
Symbol
Symbol Color 
Symbol
Name

WH
White
GN
Green
CAP
Jumper cap

YE
Yellow
BN 
Brown
COMP
Compressor

RD
Red
BU
Blue
Grounding wire

YEGN
Yellow/Green
BK 
Black
/
/

VT
Violet
OG
Orange
/
/

Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.

● Indoor Unit

GWC12AGC-S3DTA1C/I	
GWH12AGC-S3DTA1C/I	
GWC12AGCXD-S3DTA2C/I	
GWH12AGCXD-S3DTA2C/I

ROOM
TUBE

TEMP.
SENSOR

TEMP.
SENSOR

RECEIVER AND
DISPLAY BOARD

OPTIONAL

POWER

BU(WH)

FAN MOTOR

N

ION
PLASMACLUSTER

BN(BK)

DISPLAY

M1

AP1

L

θ

θ

YEGN(GN)

RT1

RT2

BLOCK
TERMINAL

HEALTH

DC-MOTOR

T-SENSOR

DISP

N(N1)

BU

BU

OUTDOOR UNIT

N(1)

CAP

AP2

BK

BK

COM-OUT

2

PRINTED CIRCUIT BOARD

JUMP

BN

BN

L-OUT

3

AC-L
K3(K1)

YEGN

SWING-UD1

SWING-UD2

(DRY-C)

YEGN

SWING-LR

COM-MANUAL

XT
PE
EVAPORATOR

DOOR-C

CONNECTING

CABLE

M4

M2

M3

UP-DOWN

UP-DOWN

LEFT-RIGHT

AP3
WIRED
CONTROLLER

AP4

STEPPING

STEPPING

STEPPING

GATE
CONTROL

MOTOR

MOTOR

MOTOR

OPTIONAL

OPTIONAL

OPTIONAL

60000706326803 

22
Technical Information

Sayfa 26

GWC18AGD-S3DTA1A/I	 GWC18AGD-S3DTA2A/I	 GWH18AGD-S3DTA1A/I	 GWH18AGD-S3DTA2A/I	
GWC24AGE-S3DTA1F/I	 GWC24AGE-S3DTA2F/I	 GWH24AGE-S3DTA1F/I	 GWH24AGE-S3DTA2F/I

TUBE 
ROOM

BN(BK)

OPTIONAL 
OPTIONAL 

L

TEMP.
SENSOR

TEMP.
SENSOR

RECEIVER AND
DISPLAY BOARD

FAN 
MOTOR

LEFT-RIGHT

BU(WH)

WIRED
 CONTROLLER

MOTOR
STEPPING

N

DISPLAY
AP1

YEGN(GN)

M1

θ
θ

POWER

M4

RT1
RT2

DISP

TERMINAL

T-SENSOR

DC-MOTOR

SWING-LR

COM-MANUAL

BLOCK

BU
N

BU
CAP

N(1)

OUTDOOR  UNIT

AP2

BK

COM-OUT

BK

2

JUMP

PRINTED CIRCUIT BOARD

BN

BN

K1
AC-L
L-OUT

3

YEGN

HEALTH
DOOR-C
(DRY-C)

SWING-UD1
SWING-UD2

E

CONNECTING

YEGN

YEGN

XT

CABLE

PE
EVAPORATOR

M2

M3

ION
PLASMACLUSTER

UP-DOWN

UP-DOWN

DRY

STEPPING

STEPPING

CONTACT

MOTOR

MOTOR

OPTIONAL
OPTIONAL 

600007065110

GWC30AGEXH-S3DTA1A/I	
GWC30AGEXH-S3DTA2A/I	
GWH30AGEXH-S3DTA1A/I	
GWH30AGEXH-S3DTA2A/I	
GWC30AGEXH-S3DTA1C/I

TUBE 
ROOM

TEMP.
SENSOR

TEMP.
SENSOR

OPTIONAL 

RECEIVER AND
DISPLAY BOARD

LEFT-RIGHT

MOTOR
STEPPING

FAN MOTOR

WIRED
 CONTROLLER

DISPLAY
AP1

M1

θ
θ

M4

RT1
RT2

TERMINAL

BLOCK

DC-MOTOR

COM-MANUAL

T-SENSOR

DISP

SWING-LR

BU
CAP

BU
N

OUTDOOR  UNIT

N(1)

BK

BK

COM-OUT

AP2

2

JUMP

3
BN

PRINTED CIRCUIT BOARD

BN

AC-L

YEGN

YEGN
E

YEGN

CONNECTING

(DRY-C)

SWING-UD2

SWING-UD1

XT

CABLE

DOOR-C

HEALTH

PE
EVAPORATOR

M3

M2

ION
PLASMACLUSTER

UP-DOWN

UP-DOWN

DRY

STEPPING

CONTACT

STEPPING

MOTOR

MOTOR

OPTIONAL
OPTIONAL 

60000706411701

23
Technical Information

Sayfa 27

GWC36QF-S3DTB4A/I    GWH36QF-S3DTB4A/I

WARNING

OPTIONAL 

OPTIONAL 

ROOM TEMP.

TUBE TEMP.

FAN

Please don't touch any electronic 
component or terminal when the 
machine is running,stopping or has 
been powered off for less than 3 
minutes to prevent electric shock !

RECEIVER AND

WIRED
 CONTROLLER

SENSOR

SENSOR

MOTOR

WIFI MODULE

DISPLAY BOARD

M1

AP3

AP4

AP1

θ
θ

RT2
RT1

TERMINAL

BLOCK

TUBE
ROOM

DISP2
DISP1

DC-MOTOR

WIFI

COM-MANUAL

L2

BU

BU 

N(1)

OUTDOOR UNIT

BK
N

L2

BK

COM-OUT

2

CAP
AP2

L2

BN

BN

MAIN BOARD
JUMP

AC-L

3

MAGNETIC
RING

YEGN

YEGN

DRY-C
(DOOR-C)

L1

SWING-UD

SWING-LR1

SWING-LR2

PE YEGN

XT1

HEALTH-L HEALTH-N

PE

EVAPORATOR

M2

M3

M4

BU
RD

INDOOR UNIT

COLD PLASMA

AP5

MOTOR
STEPPING
LEFT-RIGHT 
LEFT-RIGHT 
UP-DOWN 

GENERATOR

MOTOR
STEPPING

MOTOR
STEPPING

DRY
CONTACT

OPTIONAL 

60000700043606

OPTIONAL 

OPTIONAL 

These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.

24
Technical Information

Sayfa 28

● Outdoor Unit

GWC12AGC-S3DTA1C/O   GWH12AGC-S3DTA1C/O

OPTIONAL OPTIONAL
OPTIONAL

WARNING

Bottom

VALVE
4-WAY

EXHAUST
TEMP.
OUTROOM
TEMP.
OUTTUBE

ELECTRONIC
EXPANSION 

Please don't touch any terminal when the 
machine is running ,stopping or has been 
powered off for less than 30 minutes to 
prevent the risk of electric shock !

Band
Heater

TEMP.
SENSOR SENSOR
SENSOR

VALVE

4YV

EKV

EH1

15K
20K
50K
RT1

VT

(YE)

RT3
RT2

VT(YE)

T-SEN

4WAY

HEAT-B

FA

XT

L2

BU

BU

INDOOR UNIT

N(1)

N

L2

BK

BK
BN

Main Board
AP:

COMU(COM-IN)

2

L2

BN

3

AC_L(AC-L)

CN2

YEGN

OFAN

TERMINAL

YEGN

LX1-2
LX1-1

E

BLOCK

MAGNETIC

PE

RING

L1
L1
L1

OG
WH

M

RD
YE
BU

L

REACTOR

V
W

FAN

U

MOTOR

OPTIONAL

COMP

600007065257

COMP.

GWC18AGD-S3DTA1A/O   GWH18AGD-S3DTA1A/O   GWC24AGE-S3DTA1F/O   GWH24AGE-S3DTA1F/O

OPTIONAL
OPTIONAL

WARNING

BOTTOM
BAND
HEATER

EXHAUST
TEMP.
OUTROOM
TEMP.
OUTTUBE

ELECTRONIC

Please don't touch any terminal when the machine is
running ,stopping or has been powered off for less 
than 30 minutes to prevent the risk of electric shock !

EXPANSION 

TEMP.
SENSOR
SENSOR
SENSOR

VALVE

EKV

EH1

15K
20K
50K

RT3
RT2

RT1

MAGNETIC RING

XT

BU

L2

BU

INDOOR UNIT

T-SENSOR

(T-SEN)

HEAT-B

N(1)

FA

N

L2

BK
BN

BK

PRINTED CIRCUIT BOARD
AP1:

(COM-IN)

2

COM-INNER

L2

BN

3

AC-L

OVC-COMP

OFAN

YEGN

4WAY

YEGN

CN2

E

TERMINAL

PE

BLOCK

PE

MAGNETIC

VT
VT

WH

WH

RING

L1
L1
L1

M

4YV

SAT

BU

YE
RD

VALVE
4-WAY

FAN

V
W

MOTOR

U

COMP

OVERLOAD

OPTIONAL

PROTECTOR

600007064965 

OPTIONAL

COMP.

25
Technical Information

Sayfa 29

GWC30AGEXH-S3DTA1A/O	
GWH30AGEXH-S3DTA1A/O	
GWC30AGEXH-S3DTA1C/O	
GWC36QF-S3DTB4A/O	
GWH36QF-S3DTB4A/O

OPTIONAL
OPTIONAL

WARNING

BOTTOM
BAND
HEATER

EXHAUST
TEMP.
OUTROOM
TEMP.
OUTTUBE

ELECTRONIC

Please don't touch any terminal when the 
machine is running ,stopping or has been 
powered off for less than 30 minutes to 
prevent the risk of electric shock !

TEMP.
SENSOR
SENSOR
SENSOR

EXPANSION 

VALVE

EKV

15K
20K
50K

EH1

RT3
RT2

RT1

MAGNETIC RING

XT

BU

L2

BU

INDOOR UNIT

T-SENSOR

(T-SEN)

HEAT-B

N(1)

FA

N

L2

BK

BK
BN

PRINTED CIRCUIT BOARD
AP1:

(COM-IN)

2

COM-INNER

L2

BN

L(3)

AC-L
E

OVC-COMP

OFAN

YEGN

4WAY

CN2

YEGN

TERMINAL

PE

BLOCK

PE

BU
BN(BK)

L
N

MAGNETIC

VT
VT

OPTIONAL

WH

WH

RING

L1
L1
L1

YEGN

YEGN

4YV

M

PE

PE

POWER

SAT

BU

YE
RD

VALVE
4-WAY

FAN

PE

V
W

MOTOR

U

OPTIONAL

OVERLOAD

COMP

PROTECTOR

OPTIONAL

600007065386

COMP.

These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.

26
Technical Information

Sayfa 30

5.2 PCB Printed Diagram

Indoor Unit

12-30K

7
5

8
6
9

4

3

2

1

15

No.
Name 
No.
Name 

1
Earthing wire 
9
Up & down swing 2

2
DC fan
10
Up & down swing 1

3
Terminal of live wire
11
Display board 

4
Fuse
12
Temperature sensor

5
Dommunication wire 
13
Door control 

6
Neutral wire
14
Wired controller

7
Cold plasma
15
Jumper

8
Left & right swing 

27
Technical Information

10

11

12

13

14

Sayfa 31

36K

1
2
3
4
5
6
7

19

18

17

16

15

14

No.
Name 
No.
Name 

1
Neutral wire
11
Ambient temperature sensor

2
Live wire
12
Tube temperature sensor

3
Fuse
13
Display board 

4
Door control 
14
Jumper cap

5
Wired controller
15
DC fan

6
Auto button
16
Earthing wire 

7
Up&down swing
17
Communication wire

8
Left&right swing 2
18
Live line for AC contactor

9
Left&right swing 1
19
Cold plasma

10
WiFi

28
Technical Information

8

9

10

11

12

13

Sayfa 32

Outdoor Unit

GWC12AGC-S3DTA1C/O    GWH12AGC-S3DTA1C/O

1

2

3

4

5
6
7

No.
Name 

1
Earthing wire 

2
Neutral wire, live wire and communication cable

3
4-way valve

4
Electric heating belt of chassis

5
Outdoor fan

6
Electronic expansion valve

7
Temperature sensor 

8
Three-phase terminal of compressor

29
Technical Information

8

Sayfa 33

GWC18AGD-S3DTA1A/O    GWH18AGD-S3DTA1A/O    GWC24AGE-S3DTA1F/O    GWH24AGE-S3DTA1F/O

5
6
7
8

9
10
11
12
13
14

4

3

2

1

No.
Name 
No.
Name 

1
Terminal of electronic expansion valve
9
4-way valve

2
E disk(Reserved)
10
Electric heating belt of chassis

3
Computer monitoring interface
11
2-way valve

4
EE flash drive
12
DC motor 

5
Grounding wire
13
Temperature sensor 

6
Live wire 
14
Overload interface of compressor

7
Neutral wire
15
Terminal of compressor

8
Communication wire
16
Interface of program debugs

30
Technical Information

15

16

Sayfa 34

GWC30AGEXH-S3DTA1A/O	
GWH30AGEXH-S3DTA1A/O	
GWC30AGEXH-S3DTA1C/O	
GWC36QF-S3DTB4A/O 
GWH36QF-S3DTB4A/O

1

2

3

4

5

6

7

8

9

10

11

12

13
14

No.
Name 
No.
Name 

1
Neutral wire
8
Terminal of high pressure protection

2
Grounding wire
9
Temperature sensor 

3
Live wire
10
Overload interface of compressor

4
Communication wire
11
Terminal of electronic expansion valve

5
4-way valve
12
Terminal of DRED

6
Electric heating belt of chassis
13
E disk(Reserved)

7
Outdoor fan
14
Terminal of compressor wire

31
Technical Information

Sayfa 35

6. Function and Control

6.1 Remote Controller Introduction of YAP1F7(WiFi)

Notice:

1.This is a general use remote controller. It could be used for the air conditioner with multifunction. For the functions which the 
model doesn't have, if press the corresponding button on the remote controller, the unit will keep the original running status.

2.After putting through the power, the air conditioner will give out a sound. Operation indicator " 
 " is ON (red indicator, the 
colour is different for different models). After that, you can operate the air conditioner by using remote controller.

3.Under on status, pressing the button on the remote controller, the signal icon " 
 " on the display of remote controller will 
blink once and the air condition-er will give out a “ di ” sound, which means the signal has been sent to the air conditioner.

4.As for the models with functions of WiFi or wired controller, the indoor unit must has been controlled by standard remote 
controller under auto mode first, and then the function of adjustable temperature under auto mode can be realized by APP or 
the wired controller.

5.This remote controller can adjust the temperature under auto mode. When matching with the unit which is without the 
function of adjustable temperature under auto mode, the set temperature under auto mode may be invalid, or the displayed set 
temperature on the unit is not same as that on the remote controller under auto mode.

P

P

ON/OFF

ON/OFF

TURBO

TURBO

MODE

MODE

FAN

FAN

I FEEL
T-ON  T-OFF

I FEEL
T-ON  T-OFF

TEMP
CLOCK

TEMP
CLOCK

LIGHT
WiFi
SLEEP

LIGHT
WiFi
SLEEP

 button

Press this button to turn on the unit. Press this button again to 

turn off the unit.

 button

Press this button to select your required operation mode :

● When selecting auto mode, air conditioner will operate 

automatically according to the ex-factory setting. Press "FAN" 

button can adjust fan speed. Press " 
 " / " 
 " button can adjust 

fan blowing angle.

● After selecting cool mode, air conditioner will operate under 

cool mode. Press " " or "  " button to adjust set temperature. 

Press "FAN" button to adjust fan speed. Press" 
 " / "  " button 

to adjust fan blowing angle.

32
Technical Information

● When selecting dry mode, the air conditioner operates at low 

speed under dry mode. Under dry mode, fan speed can't be 

adjusted. Press " 
 " / " 
 " button to adjust fan blowing angle.

● When selecting fan mode, the air conditioner will only blow 

fan, no cooling and no heating. Press "FAN" button to adjust fan 

speed. Press" 
  " / "  " button to adjust fan blowing angle.  

When selecting heat mode, the air conditioner operates under 

heat mode. Press "▲" or "▼" button to adjust set temperature. 

Press "FAN" button to adjust fan speed. Press " 
 " / "  " button 

to adjust fan blowing angle. 

● When selecting heating mode, the air conditioner operates 

under heat mode. Press " 
 " or " 
 " button to adjust set 

temperature. Press "FAN" button to adjust fan speed. Press " 
 " 

/ "  " button to adjust fan blowing angle. (Cooling only unit won't 

receive heating mode signal. If setting heat mode with remote 

controller, press ON/OFF button can’t start up the unit).

Note:

● For preventing cold air, after starting up heat mode,indoor unit 

will delay 1~5 minutes to blow air (Actual delay time depends on 

indoor ambient temperature).

● Set temperature range from remote controller: 16~30
oC 

oF).

(61~86

● Under auto mode, temperature can be displayed;Under auto 

mode, set temperature can be adjusted.

● This mode indicator is not available for some models.

 button

This button is used for setting Fan Speed in the sequence that 

goes from AUTO, 
 ,  , 
 , 
 , 
 , 
 , then back to 

Auto.
Note: 

● Under AUTO speed, air conditioner will select proper fan speed 

automatically according to factory default setting.

● It's low fan speed under dry mode.

● X-FAN function Hold fan speed button for 2s in cool or dry 

mode, the icon " 
 " is displayed and the indoor fan will continue 

Sayfa 36

operation for a few minutes in order to dry the indoor unit even 

though you have turned off the unit. After energization, X-FAN 

OFF is defaulted. X-FAN is not available in auto, fan or heat 

mode.

● This function indicates that moisture on evaporator of indoor 

unit will be blowed after the unit is stopped to avoid mould.

● Having set X-FAN function on: After turning off the unit by 

pressing " ON/OFF " button indoor fan will continue running for a 

few minutes. at low speed. In this period, Hold fan speed button 

for 2s to stop indoor fan directly.

● Having set X-FAN function off: After turning off the unit by 

pressing " ON/OFF " button, the complete unit will be off directly.

 
TURBO button

Under COOL or HEAT mode, press this button to turn to quick 

COOL or quick HEAT mode. " 
 " icon is displayed on remote 

controller. Press this button again to exit turbo function and 

" 
 " icon will disappear. If start this function, the unit will run at 

super-high fan speed to cool or heat quickly so that the ambient 

temperature approaches the preset temperature as soon as 

possible. 

 / 
 button

● Press " 
 " or " 
 " button once increase or d ecrease set 

temperature 1°C (°F). Holding " 
 " or " 
 " button, 2s later, 

set temperature on remote controller will change quickly. On 

releasing button after setting is finished, temperature indicator on 

indoor unit will change accordingly.

● When setting T-ON, T-OFF or CLOCK, press " 
 " or " 
 " 

button to adjust time. (Refer to CLOCK, T-ON,T-OFF buttons)

 button

Press this button can select left & right swing angle. Fan blow 

angle can be selected circularly as below:

Note:

● Press this button continuously more than 2s, the main unit will 

swing back and forth from left to right, and then loosen the button, 

the unit will stop swinging and present position of guide louver 

will be kept immediately.

● Under left and right swing mode, when the status is switched 

from off to  
 , if press this button again 2s later, 
 status 

will switch to off status directly; if press this button again within 

2s, the change of swing status will also depend on the circulation 

sequence stated above.

● The function is only available for some models.

 button

Press this button can select left & right swing angle.  Fan blow 

angle can be selected circularly as below:

33
Technical Information

no display
(horizontal louvers stops

at current position)

● When selecting " 
 ", air conditioner is blowing fan 

automatically. Horizontal louver will automatically swing up & 

down at maximum angle.  

●When selecting " 
 ,      ,      ,      ,     ,  ", air conditioner is 

blowing fan at fixed position. Horizontal louver will stop at the 

fixed position.

● When selecting " 
 ,     , 
 ", air conditioner is blowing fan at 

fixed angle. Horizontal louver will send air at the fixed angle.

● Hold " 
 " button above 2s to set your required swing angle. 

When reaching your required angle, release the button.   
Note:

● " 
 ,     , 
 " may not be available. When air conditioner 

receives this signal, the air conditioner will blow fan automatically.

● Press this button continuously for more than 2s, the main 

unit will swing back and forth from up to down, and then loosen 

the button, the unit present position of guide louver will be kept 

immediately.

● Under up and down swing mode, when the status is switched 

from off to 
 , if press this button again 2s later, 
 status will 

switch to off status directly; if press this button again within 2s, 

the change of swing status will also depend on the circulation 

sequence stated above.  

T-ON  T-OFF button

● T-ON button

"T-ON" button can set the time for timer on. After pressing this 

button, " 
 " icon disappears and the word "ON" on remote 

controller blinks. Press "▲" or " ▼ " button to adjust T-ON 

setting. After each pressing "▲" or " ▼ " button, T-ON setting will 

increase or decrease 1min. Hold "▲" or " ▼ " button, 2s later, the 

time will change quickly until reaching your required time. Press 

"T-ON" to confirm it. The word "ON" will stop blinking. " 
 " icon 

resumes displaying. Cancel T-ON: Unde the condition that T-ON 

is started up, press "T-ON " button to cancel it.

● T-OFF button

"T-OFF" button can set the time for timer off. After pressing this 

button, " 
 " icon disappears and the word "OFF" on remote 

controller blinks. Press "▲" or " ▼ " button to adjust T-OFF 

setting. After each pressing "▲" or " ▼ " button, T-OFF setting 

will increase or decrease 1min. Hold "▲" or " ▼ " button, 2s later, 

the time will change quickly until reaching your required time. 

Press "T-OFF" word "OFF" will stop blinking. " 
 " icon resumes 

displaying. Cancel T-OFF. Under the condition that T-OFF is 

started up, press "T-OFF" button to cancel it.
Note:

● Under on and off status, you can set T-OFF or T-ON 

simultaneously.

Sayfa 37

● Before setting T-ON or T-OFF, please adjust the clock time.

● After starting up T-ON or T-OFF, set the constant circulating 

valid.

● After that, air conditioner will be turned on or turned off 

according to setting time.ON/OFF button has no effect on setting.

If you don’t need this function, please use remote controller to 

cancel it.

I FEEL button

Press this button to start I FEEL function and " 
 " will be 

displayed on the remote controller. After this function is set, the 

remote controller will send the detected ambient temperature 

to the controller and the unit will automatically adjust the indoor 

temperature according to the detected temperature. Press this 

button again to cancel I FEEL function and " 
 " will disappear.

● Please put the remote controller near user when this function 

is set. Do not put the remote contro ller near the object of high 

temperature or low temperature in order to avoid detecting 

inaccurate amb ient temperature. When I FEEL function is turned 

on, the remote controller should be put within the area where 

indoor unit can receive the signal sent by the remote controller.

CLOCK button

Press this button to set clock time. " 
 " icon on remote controller 

will blink. Press " ▲ " or " ▼ " button within 5s to set clock time. 

Each pressing of "▲" or " ▼ " button, clock time will increase or 

decrease 1 minute. If hold "▲" or " ▼ " button, 2s later, time will 

change quickly. Release this button when reaching your required 

time. Press "CLOCK" button to confirm the time. " 
 " icon stops 

blinking.
Note:

● Clock time adopts 24-hour mode.

● The interval between two operations can't exceed 5s. 

Otherwise, remote controller will quit setting status. Operation for 

TIMER ON/TIMER OFF is the same.

SLEEP button

● Press this button, can select Sleep 1 (
 1), Sleep 2 (
 2), 

Sleep 3 (
 3) and cancel the Sleep, circulate between these, 

after electrified, Sleep Cancel is defaulted.

● Sleep 1 is Sleep mode 1, in Cool modes; sleep status after run 

for one hour, the main unit setting temperature will increase 1 , 

two hours, setting temperature increased 2℃, then the unit will 

run at this setting temperature; In Heat mode: sleep status after 

run for one hour, the setting temperature will decrease 1 , two 

hours, setting temperature will decrease 2 , then the unit will run 

at this setting temperature.

● Sleep 2 is sleep mode 2, that is air conditioner will run 

according to the presetting a group of sleep temperature curve.

● Sleep 3-the sleep curve setting under Sleep mode by DIY;

34
Technical Information

(1) Under Sleep 3 mode, press “Turbo” button for a long 

time, remote controller enters into user individuation sleep 

setting status, at this time, the time of remote controller will 

display “1hour”, the setting temperature “88” will display the 

corresponding temperature of last setting sleep curve and blink 

(The first entering will display according to the initial curve setting 

value of original factory);

(2) Adjust " ▲ " and " ▼ " button, could change the corresponding 

setting temperature, after adjusted, press "Turbo" button for 

confirmation;

(3) At this time, 1hour will be automatically increased at the timer 

position on the remote control, (that are "2hours" or "3hours" or 

"8hours"), the place of setting temperature "88" will display the 

corresponding temperature of last setting sleep

curve and blink;

(4) Repeat the above step (2)~(3) operation, until 8 hours 

temperature setting finished, sleep,curve setting finished, at this 

time, the remote controller will resume the original timer display; 

temperature display will resume to original setting temperature.

● Sleep3- the sleep curve setting under Sleep mode by DIY could 

be inquired:

The user could accord to sleep curve setting method to inquire 

the presetting sleep curve, enter into user individuation sleep 

setting status, but do not change the temperature, press "Turbo" 

button directly for confirmation. Note: In the above presetting or 

enquiry procedure, if continuously within 10s, there is no button 

pressed, the sleep curve setting within 10s, there is no button 

pressed, the sleep curve setting status will be automatically quit 

and resume to display the original displaying. In the presetting 

or enquiry procedure, press "ON/OFF" button, "Mode" button, 

"Sleep" button, the sleep curve setting or enquiry status will quit 

similarly.

WiFi
 button

Press " WiFi "  button to turn on WiFi function, "WiFi " icon will be 

displayed on the remote controller; Hold " WiFi "  button for 5s to 

turn off WiFi function and " WiFi " icon will disappear. 

Under off status, press " MODE " and " WiFi " buttons 

simultaneously for 1s, WiFi module will restore factory settings.

● This function is only available for some models.

 button

Press this button to achieve the on and off of health and 

scavenging functions in operation station. Press this button 

for the first time to start scavenging function; LCD displays

" 
 ". Press the button for the second time to start health and 

scavenging functions simultaneously; LCD displays " 
 " and " 
 ". 

Press this button for the third time to quit health and scavenging 

functions simultaneously. Press the button for the fourth time to 

start health function; LCD display " 
 ". Press this button again to 

Sayfa 38

repeat the operation above.

● This function is applicable to partial of models .

LIGHT button

Press this button to turn off display light on indoor unit. " 
 " icon 

on remote controller disappears. Press this button again to turn 

on display light. " 
 " icon is displayed.

TEMP button

Press this button, you can see indoor set temperature, indoor 

ambient temperature on indoor unit' s display. The setting on 

remote controller is selected circularly as below:

no display

Introduction for icons on display screen

I feel

Set fan speed

Turbo mode

Send signal

Auto mode

Operation mode

Cool mode

Dry mode
Fan mode
Heat mode

Sleep mode

 8℃ heating function
Power limiting operation

P

Health mode 
Scavenging function

X-FAN function

Set temp.

temp.
Outdoor ambient 
temp.
Indoor ambient 

Temp. 

display type

Clock

Set temperature

WiFi function

Set time
TIMER ON / TIMER OFF

Left & right swing
Up & down swing

Child lock

Quiet

Function introduction for combination buttons

Energy-saving function

Under cooling mode, press "TEMP" and "CLOCK" buttons 

simultaneously to start up or turn off energysaving function. 

When energy-saving function is started up, "SE" will be shown 

on remote controller, and air conditioner will adjust the set 

35
Technical Information

temperature automatically according to ex-factorysetting to reach 

to the best energy-saving effect. Press "TEMP" and "CLOCK" 

buttons simultaneously again to exit energysaving function.
Note:

● Under energy-saving function, fan speed is defaulted at auto 

speed and it can't be adjusted.

● Under energy-saving function, set temperature can't be 

adjusted. Press "TURBO" button and the remote controller won't 

send signal.

● Sleep function and energy-saving function can't operate at the 

same time. If energy-saving function has been set under cool 

mode, press sleep button will cancel energy-saving function. If 

sleep function has been set under cool mode, start up the energy-

saving function will cancel sleep function.

8°C heating function

Under heat mode, press "TEMP" and "CLOCK" buttons 

simultaneously to start up or turn off 8°C heating function. When 

this function is started up, "
" and "8°C" will be shown on remote 

controller, and the air conditioner keep the heating status at 8°C.

Press "TEMP" and "CLOCK" buttons simultaneously again to exit 

8°C heating function.
Note:

● Under 8°C heating function, fan speed is defaulted at auto 

speed and it can't be adjusted.

● Under 8°C heating function, set temperature can't be adjusted.

Press "TURBO" button and the remote controller won't send 

signal.

● Sleep function and 8°C heating function can't operate at the 

same time. If 8°C heating function has been set under heat 

mode, press sleep button will cancel 8°C heating function. If 

sleep function has been set under heat mode, start up the 8°C 

heating function will cancel sleep function.

● Under °F temperature display, the remote controller will display 

46°F heating.

Child lock function

Press "▲" and "▼" simultaneously to turn on or turn off child lock 

function. When child lock function is on, " " icon is displayed on 

remote controller. If you operate the remote controller, the " " 

icon will blink three times without sending signal to the unit.

Temperature display switchover function

Under OFF status, press "▼" and "MODE" buttons 

simultaneously to switch temperature display between °C and °F.

Auto clean function

Under unit off status, hold "MODE" and "FAN" buttons 

simultaneously for 5s to turn on or turn off the auto clean function. 

When the auto clean function is turned on, indoor unit displays 

"CL" . During the auto clean process of evaporator, the unit will 

Sayfa 39

perform fast cooling or fast heating. There may be some noise, 

which is the sound of flowing liquid or thermal expansion or cold 

shrinkage. The air conditioner may blow cool or warm air, which 

is a normal phenomenon. During cleaning process, please make 

sure the room is well ventilated to avoid affecting the comfort.
Note:

● The auto clean function can only work under normal ambient 

temperature. If the room is dusty, clean it once a month; if not, 

clean it once every three months. After the auto clean function is 

turned on,you can leave the room. When auto clean is finished, 

the air conditioner will enter standby status.

● This function is only available for some models.

function

Press "MODE" and "SLEEP" buttons simultaneously to start 
 

function.

 function is for limiting power of the whole unit. Press this button, 

the remote controller will circu-larly display as the following:

blank
No Setting

● Maximum power limited under the  mode is lower than that of 

mode.

● If you want to cancel the power limiting function, press the 

button  till the icon in remote controller is not displayed.

● When the remote controller is turned off, power limiting function 

is cancelled. If you want to activatethe function, please repress 

this button.

● If the current power is lower than the maximum power of 
 

mode, then the power will not be limited after entering into such 

mode.

● For the model with one outdoor unit and two indoor units, if any 

one of indoor units enters into power limiting function, the outdoor 

unit will enter into the set limiting power mode of indoor unit; 

when two indoor units enter into power limiting mode, then the 

power of outdoor unit will be limited according to the lower power 

of the two indoor units.
Note:

● This function is only available for some models.

Replacement of batteries in remote controller

36
Technical Information

1. Lift the cover along the direction of arrow (as shown in Fig 1① ).

2.Take out the original batteries (as shown in Fig 1 ② ).

3.Place two 7# (AAA 1.5V) dry batteries, and make sure the 

position of “ + ” polar and “ - ” polar is correct (as shown in Fig 2 

③ ).

4.Reinstall the cover (as shown in Fig 2 ④ ).

①

④

②

③

Fig.1
Fig.2 

NOTICE:

● During operation, point the remote control signal sender at 

the receiving window on indoor unit.

● The distance between signal sender and receiving 

window should be no more than 8m, and there should be no 

obstacles between them.

● Signal may be interfered easily in the room where there is 

fluorescent lamp or wireless telephone; remote controller 

should be close to indoor unit during operation.

● Replace new batteries of the same model when 

replacement is required.

● When you don’t use remote controller for a long time, 

please take out the batteries.

● If the display on remote controller is fuzzy or there’s no 

display, please replace batteries.
Emergency operation
If remote controller is lost or damaged, please use aux.

button to turn on or turn off the air conditioner. The 

operation in details is as below: As shown in the figure, open 

panel and press aux.button to turn off the air conditioner. 

When the air conditioner is turned on, it will operate under 

auto mode.

aux. button

Sayfa 40

6.2 GREE+ App Operation Manual

Control Flow Chart

Home Wi-Fi
Gree

intelligent

home
appliances

Home wireless router

Operating Systems

Requirement for User's smart phone:

iOS system
Support iOS7.0 and 
above version 

Download and installation

GREE+ App Download Linkage 

Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the 
account and add the device to achieve long-distance control and LAN control of Gree smart home appliances. 
For more information, please refer to "Help" in App.

37
Technical Information

Internet

Gree Cloud

Cellular/
Other Wi-FI

Home Wi-Fi

GREE+ APP

Android system
Support Android 4.4 and 
above version

Sayfa 41

6.3 Ewpe Smart App Operation Manual

Control Flow Chart

intelligent

Home Wi-Fi

home
appliances

Home wireless router

Operating Systems

Requirement for User's smart phone:

iOS system
Support iOS7.0 and 
above version 

Download and installation

App Download Linkage 

Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed, 
register the account and add the device to achieve long-distance control and LAN control of smart home appliances. 
For more information, please refer to "Help" in App.

38
Technical Information

Internet

Cloud

Cellular/
Other Wi-FI

Home Wi-Fi

APP

Android system
Support Android 4.4 and 
above version

Sayfa 42

6.4 Brief Description of Models and Functions

●Indoor Unit
1.Basic function of system

(1)Cooling mode
(1) Under this mode, fan and swing operates at setting status. 
Temperature setting range is 16~30

OC. 
(2) During malfunction of outdoor unit or the unit is stopped 
because of protection, indoor unit keeps original operation status.
(2)Drying mode
(1) Under this mode, fan operates at low speed and swing 
operates at setting status. Temperature setting range is 16~30

OC. 
(2) During malfunction of outdoor unit or the unit is stopped 
because of protection, indoor unit keeps original operation status. 
(3) Protection status is same as that under cooling mode.
(4) Sleep function is not available for drying mode.
(3)Heating mode
(1) Under this mode, Temperature setting range is 16~30

OC. 
(2) Working condition and process for heating mode:
When turn on the unit under heating mode, indoor unit enters into 
cold air prevention status. When the unit is stopped or at OFF 
status, and indoor unit has been started up just now, the unit 
enters into residual heat-blowing status.
(4)Working method for AUTO mode:
1.Working condition and process for AUTO mode:
a.Under AUTO mode, standard heating Tpreset=20

OC and 
standard cooling Tpreset=25

OC. The unit will switch mode 
automatically according to ambient temperature.
2.Protection function
a. During cooling operation, protection function is same as that 
under cooling mode.
b. During heating operation, protection function is same as that 
under heating mode.
3. Display: Set temperature is the set value under each condition. 

Ambient temperature is (Tamb.-Tcompensation) for heat pump 
unit and Tamb. for cooling only unit. 
4. If theres I feel function, Tcompensation is 0. Others are same 
as above.
(5)Fan mode
Under this mode, indoor fan operates at set fan speed. 
Compressor, outdoor fan, 4-way valve and electric heating tube 
stop operation. Indoor fan can select to operate at high, medium, 

low or auto fan speed. Temperature setting range is 16~30

2. Other control 

(1) Buzzer
Upon energization or availably operating the unit or remote 
controller, the buzzer will give out a beep.

(2) Auto button

If press this auto button when turning off the unit, the complete 
unit will operate at auto mode. Indoor fan operates at auto fan 
speed and swing function is turned on. Press this auto button at 
ON status to turn off the unit.

(3) Auto fan

39
Technical Information

Heating mode: During auto heating mode or normal heating ode, 
auto fan speed will adjust the fan speed automatically according 
to ambient temperature and set temperature.

(4) Sleep

After setting sleep function for a period of time, system will adjust 
set temperature automatically.

(5) Timer function:

General timer and clock timer functions are compatible by 
equipping remote controller with different functions.

(6) Memory function

memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, 
set fan speed, general timer (clock timer cant be memorized).
After power recovery, the unit will be turned on automatically 
according to memory content.
(7) Health function
During operation of indoor fan, set health function by remote 
controller. Turn off the unit will also turn off health function.
Turn on the unit by pressing auto button, and the health is 
defaulted ON.
(8)I feel control mode
After controller received I feel control signal and ambient 
temperature sent by remote controller, controller will work 
according to the ambient temperature sent by remote controller.
(9)Entry condition for compulsory defrosting function
When turn on the unit under heating ode and set temperature is 
16
OC (or 16.5

OC by remote controller), press “ , 
, 
, 
, 
, 
” 
button successively within 5s and then indoor unit will enter into 
compulsory defrosting setting status:
(1) If theres only indoor units controller, it enters into indoor normal 
defrosting mode.
(2) If theres indoor units controller and outdoor units controller, 
indoor unit will send compulsory defrosting mode signal to outdoor 
unit and then outdoor unit will operate under normal defrosting 
mode. After indoor unit received the signal that outdoor unit has 
entered into defrosting status, indoor unit will cancel to send 
compulsory mode to outdoor unit. If outdoor unit hasnt received 
feedback signal from outdoor unit after 3min, indoor unit will also 
cancel to send compulsory defrosting signal.
(10)Refrigerant recovery function: 
Enter into Freon recovery mode actively: Within 5min after 
energization, turn on the unit at 16

OC.

OC under cooling mode, and 
press light button for 3 times within 3s to enter into Freon recovery 
mode. Fo is displayed and Freon recovery mode will be sent to 
outdoor unit.
(11)Ambient temperature display control mode
1. When user set the remote controller to display set temperature 
(corresponding remote control code: 01), current set temperature 
will be displayed. 
2. Only when remote control signal is switched to indoor ambient 
temperature display status (corresponding remote control code: 

Sayfa 43

10) from other display status (corresponding remote control code: 
00, 01,11),controller will display indoor ambient temperature for 3s 
and then turn back to display set temperature.
Under this mode, indoor fan operates at set fan speed. 
Compressor, outdoor fan, 4-way valve and electric heating tube 
stop operation. Indoor fan can select to operate at high, medium, 

(3) Protection function: same as in cooling mode.

3. Fan mode
(1) Under this mode, indoor fan can select different fan speed 
(except Turbo) or auto fan speed. Compressor, outdoor fan and 
4-way valve all stop operation.
(2) In fan mode, temperature setting range is 16~30

oC.

4. Heating mode
Working condition and process of heating mode:
① W h e n T p r e s e t - ( Ti n d o o r a m b i e n t t e m p e r a t u r e -
Tcompensation)≥1

low or auto fan speed. Temperature setting range is 16~30

OC.

(12)Off-peak energization function:

oC, unit enters into heating mode. Compressor, 
outdoor fan and 4-way valve start operation.
② When -2

Adjust compressors minimum stop time. The original minimum 
stop time is 180s and then we change to: 
The time interval between two start-ups of compressor cant be 
less than 180+Ts(0≤T≤15). T is the variable of controller. Thats to 
say the minimum stop time of compressor is 180s~195s. Read-
in T into memory chip when refurbish the memory chip each time. 
After power recovery, compressor can only be started up after 
180+T s at least.

oC <Tpreset-(Tindoor ambient temperature-
Tcompensation) <1

oC, unit operates according to the previous
status.
③ When Tpreset-(Tindoor ambient temperature-Tcompensation)≤-
2
oC, compressor stops operation and outdoor fan will stop 30s 
later. Indoor fan will be in residual-heat blowing status.
④ When unit is turned off under heating mode or changed to other 
modes from heating mode, 4-way valve will be power-off 2min 
after compressor stops working (compressor is in operation status 
under heating mode).
⑤ When Toutdoor ambient temperature >30

(13) SE control mode

The unit operates at SE status. 

oC, compressor 
stops operation immediately. Outdoor fan will stop 30s later.
⑥ Under the condition that compressor is turned on, when unit 
is changed to heating mode from cooling or drying mode, 4-way 
valve will be energized in 2~3mins delay.
Note: Tcompensation is determined by IDU and ODU. If IDU 
controls the compensation temperature, then Tcompensation is
determined according to the value sent by IDU to ODU; If 
IDU does not control the compensation temperature, then 
Tcompensation will default to 3

(14) X-fan mode

When X-fan function is turned on, after turn off the unit, indoor fan 
will still operate at low speed for 2min and then the complete unit 
will be turned off. When x-fan function is turned off, after turn off 
the unit, the complete unit will be turned off directly.

OC heating function

(15) 8

Under heating mode, you can set 8

oCheating function by remote 
controller. The system will operate at 8

oC by the ODU.

oC set temperature. 

5. Freon recovery mode
After the Freon recovery signal from IDU is received, cooling at 
rated frequency will be forcibly turned on to recover Freon.
Indoor unit will display Fo. If any signal from remote controller is 
received, unit will exit from Freon recovery mode and indoor unit 
stops displaying Fo.

(16)Turbo function

Turbo function can be set under cooling and heating modes. 
Press Fan Speed button to cancel turbo setting. Turbo function is 
not available under auto, drying and fan modes.
●Outdoor Unit
12-30K:
1. Cooling mode:
Working condition and process of cooling mode:
① When Tindoor ambient temperature≥Tpreset, unit enters into 
cooling mode. Indoor fan, outdoor fan and compressor start 
operation. Indoor fan operates according to set fan speed.
② When Tindoor ambient temperature≤Tpreset-2

6. Compulsory defrosting
If unit is turned on under heating mode and set temperature is 
16OC (by remote controller), press “ , , 
, , 
, ” within 5s, 
unit will enter into compulsory defrosting mode and send the 
signal to ODU. When the compulsory defrosting signal from ODU 
is received, IDU will exit from the compulsory defrosting mode and 
stop sending the signal to ODU.
After ODU receives the compulsory defrosting code, it will start 
compulsory defrosting. Defrosting frequency and opening
angle will be the same as in normal defrosting mode. When 
compulsory defrosting is finished, the complete unit resumes
original status.

oC, compressor 
stops operation and outdoor fan will stop 30s later. Indoor fan 
operates according to set fan speed.
③ When Tpreset-2

oC <Tindoor ambient temperature <Tpreset, 
unit operates according to the previous status.
Under cooling mode, 4-way valve is not energized. Temperature 
setting range is 16~30

7. Auto mode
Auto mode is determined by controller of IDU. See IDU logic for 
details.

oC. If compressor stops because of 
malfunction in cooling mode, indoor fan and swing motor will work 
according to the original status.

8. 8
oC heating
Set temperature is 8

2. Drying mode
(1) Working condition and process of drying mode
① When Tindoor ambient temperature >Tpreset, unit will be in 
drying mode. Outdoor fan and compressor start operation while 
indoor fan will operate at low fan speed.
② When Tpreset-2

oC. Under 
this mode, “Cold air prevention” function is shielded.
If compressor is operating under this mode, fan speed will adjust 
according to auto fan speed; if compressor stops operation
under this mode, indoor fan will be in residual-heat blowing status.

oC. Display board of IDU displays 8

oC≤Tindoor ambient temperature≤Tpreset, unit 
operates according to the previous status.
③ When Tindoor ambient temperature <Tpreset-2

When power on, communication light will be blinking in a 
normal way (after receiving a group of correct signals,
blinking stops for 0.2s~0.3s). If theres no communication, 
communication light will be always on. If other ODU has

oC, 
compressor stops operation and outdoor fan will stop 30s later.
(2) Under drying mode, 4-way valve is not energized. Temperature 
setting range is 16~30

oC.

40
Technical Information

Sayfa 44

malfunction, communication light will be on for 1s and off for 
1s in a circular way.

36K:
1. Basic Functions
(1) Cooling Mode
1. Conditions and processes of cooling operation:
(1) If the compressor is shut down, and [Tsetup – (Tindoor ambient temperature 
– 
 Tcooling indoor ambient temperature compensation)] < 0ºC , start up the machine 
for cooling, the cooling operation will start;
(2) During operations of cooling, if 0ºC ≤ [Tsetup – (Tindoor ambient temperature 
– 
 Tcooling indoor ambient temperature compensation)] < 2ºC , the cooling operation
will be still running;
(3) During operations of cooling, if 2ºC ≤ [Tsetup – (Tindoor ambient temperature 
– 
 Tcooling indoor ambient temperature compensation)], the cooling operation will
stop after reaching the temperature point.
2. Temperature setting range
(1) If Toutdoor ambient temperature ≥ [Tlow-temperature cooling temperature], the 
temperature can be set at: 16~30ºC (Cooling at room 
temperature);
(2) If Toutdoor ambient temperature < [Tlow-temperature cooling temperature], the 
temperature can be set at: 25~30ºC (Cooling at low temperature), 
that is, the minimum setting temperature for outer units judgment 
is 25ºC .
(2) Dehumidifying Mode
1. Conditions and processes of dehumidifying operations: Same 
as the cooling mode;
2. The temperature setting range is: 16~30ºC ;
(3) Air-supplying Mode
1. The compressor, outdoor fans and four-way valves are switched 
off;
2. The temperature setting range is: 16~30ºC.
(4) Heating Mode
1. Conditions and processes of heating operations: 
(Tindoor ambient temperature is the actual detection temperature of indoor 
environment thermo-bulb, Theating indoor ambient temperature compensation is 
the indoor ambient temperature compensation during heating 
operations)
(1) If the compressor is shut down, and [(Tindoor ambient temperature – 
 
Theating indoor ambient temperature compensation) –Tsetup] < 0

oC , start the machine 
to enter into heating operations for heating;
(2) During operations of heating, if 0

oC ≤ [(Tindoor ambient temperature – 
  Theating indoor ambient temperature compensation) –Tsetup] < 2

oC, the heating 
operation will be still running;
(3) During operations of heating, if 2ºC ≤ [(Tindoor ambient temperature – 
 
Theating indoor ambient temperature compensation) –Tsetup], the heating operation will
stop after reaching the temperature point.
2. The temperature setting range in this mode is: 16~30
oC .
3. Special Functions
Defrosting Control
①Conditions for starting defrosting
After the time for defrosting is judged to be satisfied, if the 
temperature for defrosting is satisfied after detections for 
continuous 3minutes,
the defrosting operation will start.
② Conditions of finishing defrosting
The defrosting operation can exit when any of the conditions 
below is satisfied:
③ Toutdoor pipe temperature ≥ (Toutdoor ambient temperature – [Ttemperature 1 of finishing 

defrosting];
④ The continuous running time of defrosting reaches [tmax. defrosting 

time].
4. Control Logic
(1) Compressor Control
Start the compressor after starting cooling, heating, dehumidifying 

41
Technical Information

operations, and the outer fans start for 5s; When the machine is
shutdown, in safety stops and when switching to air-supplying 
mode, the compressor will stop immediately. In all modes: once 
the compressor starts up, it will not be allowed to stop until having 
run for the [tmin. compressor running time] (Note: including cases 
of shutdown when the temperature point is reached; except the 
cases requiring stopping the compressor such as fault protection, 
remote shutdown, mode switching etc.); In all modes: once the 
compressor stops, it will be allowed be restart after 3-minute delay 
(Note: The indoor units have a function of power memory, the 
machine can be restarted after remote shutdown and powering up 
again without delay).
1. Cooling mode
Start the machine to enter into cooling operation for cooling, the 
compressor is switched on.
2. Dehumidifying mode
Same as the cooling mode.
3. Air-supplying mode
The compressor is switched off.
4. Heating mode
(1) Start the machine to enter into heating operation for heating, 
the compressor is switched on.
(2) Defrosting:
a. Defrosting starts: the compressor is shut down, and restarts it 
after 55-second delay.
b. Defrosting ends: the compressor stops, then starts it after 
55-second delay.
(2) Outer Fans Control
Notes:
Only the outer fans run for at least 80s in each air flow speed can 
the air flow be switched;
After the outer fans run compulsively in high speed for 80s when 
the machine starts up, control the air flow according to the logic.
After remote shutdown, safety stops, and when the machine 
stops after reaching the temperature point, as well as after the 
compressor stops, extend 1 minute, the outer fans will stop 
(During the period in the 1 minute, the air flow of outer fans can be 
changed according to the outdoor ambient temperature changes); 
When running with force, the outdoor fans shall run in the highest 
air flow.
(3) 4-way valve control
1. The 4-way valve control under the modes of Cooling, 
dehumidification and supplying air: closing;
2. The status of 4-way valve control under the heating mode: 
getting power;
(1) 4-way valve power control under heating mode
a. Starts the machine under heating mode, the 4-way valve will get 
power immediately.
(2) 4-way valve power turn-off control under heating mode
a. When you should turn off the power or switch to other mode 
under heating mode, the power of 4-way valve will be cut after 2 
minutes of the compressor stopped.
b. When all kinds of protection stops, the power of 4-way valve will 
be cut after delaying 4 minutes.
(3) Defrosting control under heating mode:
a. Defrosting begins: The power of 4-way valve will be cut after 
50s of entering into the defrosting compressor.
b. Defrosting stops: The 4-way valve will get power after 50s of 
exiting the defrosting compressor.
(4) Evaporatorrozen-preventing protection function
1. Starting estimation:
When the indoor unit is running 6 minutes (the compressor 
is turned on), the Tinner pipe≤[Tfrozen-preventing stop(the temperature of 
hysteresis is 2 )] is detected in 3 minutes., then enter the frozen-
preventing protection.
2. Frequency limited
When the indoor unit enters frozen-preventing protection, 

Sayfa 45

according to cooling reaches temperature point stop.

(5) Compressor overloads protection
If you measure the compressor overload switch action in 3s, the 
compressor should be stopped for overloading. The machine 
should be allowed to operate after overload protection was 
measured to resume. If the overloading protection continuously 
occurs for three times, it should not be resumed automatically, and 
you should press the ON/OFF button to resume. The protection 
times of compressor is allowed to clear after the compressor run [t 

Protection times clearing of compressor overloading] 30 minutes.

(6)Communication fault

When you have not received any correct signal from the inner 
machine in three minutes, the machine will stop for communication 
fault. When you have not received any correct signal from driver 
IC (aim to the controller for the  separating of main control IC and 
driver IC), and the machine will stop for communication fault. If 
the communication is resumed, the machine will be allowed to 
operate.
(7) Module protection
Testing the module protective signal immediately after started, 
once the module protective signal is measured, stop the machine 
with module protection immediately. If the module protection is 
resumed, the machine will be allowed to operate. If the module 
protection continuously occurs for three times, it should not be 
resumed automatically, and you should press the ON/OFF button 
to resume. If the running time of compressor exceeds the [tProtection 

times clearing of module] , the module protection is cleared to recount.
(9) Module overheating protection
1. Starting estimation:
After the compressor stopped working for 180s, if TModule<[TModule 

frequency limited temperature], the machine is allowed to start, otherwise it 
should not be started, and should be stopped to treat according 
to the module overheating protection: The machine should be 
stopped or transferred to supply air, the trouble should be cleared 
immediately, and the protection times are not counted.
2. Frequency limited
If [TLimited frequency temperature of module] ≤TModule <[Tfrequency reducing temperature at normal 

speed of module] , you should limit the frequency raising of compressor.
3. Reducing frequency at normal speed and power turn-off:
If [Tfrequency reducing temperature at normal speed of module] ≤TModule<[Tfrequency reducing 

temperature at high speed of module], you should adjust the compressor 
frequency by reducing 8Hz/90s till the lower limit; After it was 
running 90s at the lower limit, if [Tfrequency reducing temperature at normal speed of 

module] ≤TModule, you should stop the machine for module overheating 
protection;
4. Reducing frequency at high speed and power turn-off:
If [Tfrequency reducing temperature at high speed of module]≤TModule <[TPower turn-off temperature 

of module] you should adjust the compressor frequency by reducing 
30Hz/90s till the lower limit; After it was running 90s at the lower 
limit, if [Tfrequency reducing temperature at normal speed of module] ≤TModule, you should 
stop the machine for module overheating protection;
5. Power turn-off:
If the [TPower turn-off temperature of module] ≤TModule, you should stop the 
machine for module overheating protection; If TModule <[TLimited 

frequency temperature of module] and the compressor has been stopped for 3 
minutes, the machine should be allowed to operate.
6. If protection continuously occurs for six times, it should not 
be resumed automatically, and you should press the ON/OFF 
button to resume.During the process of running, if the running 
time of compressor exceeds the [t Protection times clearing of 
module] , the discharge protection is cleared to recount. Stopped 
or transferred to supply air mode will clear the trouble times 
immediately (if the trouble can not be resumed, mode transferring 
also will not clear it).
(10)Phase current overcurrent protection of compressor

42
Technical Information

During the running process of compressor, you could measure the 
phase current of the compressor, and control it according to the 
following steps:
1. Frequency limited
If [ILimited frequency phase current] ≤[IPhase current T frequency reducing phase current] , you 
should limit the frequency raising of compressor.
2. Reducing Frequency
If [IFrequency Reducing Phase Current]≤IPhase Current<[IPower Turn-Off Phase Current], the 
compressor shall continue to reduce frequency till the lowest 
frequency limit or out of the condition of reducing frequency;
3. Power turn-off
If [I Phase Current]≥[I Power Turn-Off Phase Current], the compressor phase current 
shall stop working for overcurrent protection; if [I Phase Current]≤[I 

Frequency Reducing Phase Current], and the compressor have stopped working 
for 3 min, the machine shall be allowed to operate;
4. If the overcurrent protection of compressor phase current 
continuously occurs for six times, it should not be resumed 
automatically, and you should press the ON/OFF button to 
resume. During the process of running, if the running time of 
compressor exceeds the [t Clearing Time of Compressor Phase 
Current Times] , the overcurrent protection is cleared to recount.
(11) Starting-up Failure Protection for Compressor
Stop the compressor after its starting-up fails, restart it after 20s if 
the fault doesn’t shows, and if they are all failing for the successive 
start 3 times, it shall be reported as Starting-up Failure, and then 
restart up it after 3 min. When it still not be able to operate through 
carry out the above process for 5 times, it is available if press ON/
OFF. And the compressor should be cleared the times after it run 
2 min.
(12) Out-of-Step Protection for Compressor
The out-of-step protection signal should be detected immediately 
after starting-up compressor, and once find the out-of-step 
protection signal, the out-of-step protection shall be stopped; if 
it can run for lasting power turn-off 3 min, the machine shall be 
allowed to operate. If it still can’t run automatically when the out-
of-step protection for compressor happens to stop working for 6 
times in succession, it needs to press ON/OFF to operate. And if 
the running time is more than 10 min, the power turn-off times for 
out-of-step protection shall be cleared and recounted.
(13) Voltage Abnormity Protection for DC Bus
To detect voltage abnormity protection for dc bus after completing 
the pre-charge:
1. Over-Low Voltage Protection for DC Bus:
When the compressor is running, the DC bus voltage is detected. 
If the PFC is not opened, the bus voltage is smaller than the 
VPFC does not open the undervoltage protection valuetime, if the 
PFC is turned on, the bus voltage is smaller than the VPFC Open 
undervoltage protection value Times Under voltage protection, 
under pressure protection, the compressor is closed, and the 
PFC is closed, and the compressor will clear the fault sign after 3 
minutes.
2.Over-High Voltage Protection for DC Bus
When the compressor is running, if the DC bus voltage is detected 
is greater than the VPFC output protection value, the voltage 
protection is reported, the stopper, the PFC, and the compressor 
will clear the fault flag after 3 minutes.
(14) Abnormity Protection for Four-way Valve
Under the model of heating operation in good condition: the 
compressor is detected [TInner Tube <(TInner Ring-T Abnormity Temperature Difference 

For Four-Way Valve Reversion)], during the running, it should be regarded as 
four-way valve reversion abnormity. And then it can run if stop the 
reversion abnormity protection for four-way valve 3 min; and if it 
still can’t run when the reversion abnormity protection for four-
way valve happens to stop working for 3 times in succession, it is 
available if presses ON/OFF.
Attention: the protection shall be shielded during the testing mode 
and defrosting process, and it shall be cleared out the failure and 

Sayfa 46

its times immediately when turning off or delivering wind / cooling / 
dehumidifying mode conversed (the inverted mode don’t clear out 
the failure when it can’t recover to operate).
(15) PFC Protection
1. After start up the PFC, it should detect the protection signal of 
PFC immediately; under the condition of PFC protection, it should 
turn off the PFC and compressor at one time;
2. It shows the failure is cleared out if PFC Protection stopped 
working 3 min and recovers to run automatically;
3. If it still can’t run when it occurs PFC protection for 3 times in 
succession, it is available if presses ON/OFF; and clear the PFC 
Protection times when start up PFC for 10min.
(16) Failure Detection for Sensor
1. Outdoor Ambient Sensor: detect the failure of sensor at all 
times.
2. Outdoor Tube Sensor: You should not detect the failure of 
outdoor tube sensor within 10 minutes heating
operation compressor except the defrosting, and you could detect 
it at other time.
3. Outdoor Exhaust Sensor:
(a) The compressor only detect the sensor failure after it start up 3 
min in normal mode;
(b) It should detect the exhaust sensor failure immediately in the 
testing mode.
4. Module Temperature Sensor:
(a) Short-Circuit Detection: the compressor should be detected 
immediately when the module temperature
sensor occurs short-circuits;
(b) Open-Circuit Detection: the compressor should be detected on 
open-circuit when it runs 3min (it needn’t 30s
avoiding the module over-heated).
(c) Detect the sensor failure at all times in the testing mode.
5. Disposal for Sensor Protection
(1) When the short-circuit of sensor is detected within 30s, It is 
regarded as the temperature of sensor over-high (or infinitely 
high), and now
according to the over-high sensor, the machine should carry 
out the corresponding protection to stop working, and show the 
corresponding
temperature shutdown protection and sensor failure at the same 
time (for example: the compressor stops immediately when the 
outdoor tube
sensor short-circuit, and the machine shall show the overload 
protection and outdoor tube sensor failure).
(2) When the open-circuit of sensor is detected within 30s, The 
protection shall be stopped and it shall show the corresponding 
sensor failure.
6. Electric Heating Function of Chassis
(1) When Toutdoor amb.≤0 , the electric heating of chassis will 
operate;
(2) When Toutdoor amb.>2 , the electric heating of chassis will 
stop operation;
(3)When 0 <Toutdoor amb.≤2 , the electric heating of chassis will 
keep original status.
7. Electric Heating Function of Compressor
(1) When Toutdoor amb.≤≤-5 , compressor stops operation, while 
the electric heating of compressor starts operation;
(2) When Toutdoor amb.>-2 , the electric heating of compressor 
stops operation;
(3) When -5 <Toutdoor amb.≤-2 , the electric heating of 
compressor will keep original status.

43
Technical Information

Sayfa 47

7. Notes for Installation and Maintenance

Safety Precautions: Important!

Please read the safety precautions carefully before 
installation and maintenance.

The following contents are very important for installation and 
maintenance.

Please follow the instructions below.

●The installation or maintenance must accord with the 
instructions.

●Comply with all national electrical codes and local electrical 
codes.

●Pay attention to the warnings and cautions in this manual.

●All installation and maintenance shall be performed by 
distributor or qualified person.

●All electric work must be performed by a licensed technician 
according to local regulations and the instructions given in 
this manual.

●Be caution during installation and maintenance. Prohibit 
incorrect operation to prevent electric shock, casualty and 
other accidents.

WARNINGS

Electrical Safety Precautions:

1. Cut off the power supply of air conditioner before checking 
and maintenance.

2. The air condition must apply specialized circuit and 
prohibit share the same circuit with other appliances.

3. The air conditioner should be installed in suitable location 
and ensure the power plug is touchable.

4. Make sure each wiring terminal is connected firmly during 
installation and maintenance.

5. Have the unit adequately grounded. The grounding wire 
cant be used for other purposes.

6. Must apply protective accessories such as protective 
boards, cable-cross loop and wire clip.

7. The live wire, neutral wire and grounding wire of power 
supply must be corresponding to the live wire, neutral wire 
and grounding wire of the air conditioner.  

8. The power cord and power connection wires cant be 
pressed by hard objects.

9. If power cord or connection wire is broken, it must be 
replaced by a qualified person.

10. If the power cord or connection wire is not long enough, 
please get the specialized power cord or connection wire 
from the manufacture or distributor. Prohibit prolong the wire 
by yourself.

44
Installation and Maintenance

11. For the air conditioner without plug, an air switch must 
be installed in the circuit. The air switch should be all-pole 
parting and the contact parting distance should be more than 
3mm.

12. Make sure all wires and pipes are connected properly and 
the valves are opened before energizing.

13. Check if there is electric leakage on the unit body. If yes, 
please eliminate the electric leakage.

14. Replace the fuse with a new one of the same specification 
if it is burnt down; dont replace it with a cooper wire or 
conducting wire.

15. If the unit is to be installed in a humid place, the circuit 
breaker must be installed.

Installation Safety Precautions:

1. Select the installation location according to the requirement 
of this manual.(See the requirements in installation part)

2. Handle unit transportation with care; the unit should not be 
carried by only one person if it is more than 20kg.

3. When installing the indoor unit and outdoor unit, a 
sufficient fixing bolt must be installed; make sure the 
installation support is firm.

4. Ware safety belt if the height of working is above 2m.

5. Use equipped components or appointed components 
during installation.

6. Make sure no foreign objects are left in the unit after 
finishing installation.

Refrigerant Safety Precautions:

1. When refrigerant leaks or requires discharge during 
installation, maintenance, or disassembly, it should be 
handled by certified professionals or otherwise in compliance 
with local laws and regulations.

2.Avoid contact between refrigerant and fire as it generates 
poisonous gas; Prohibit prolong the connection pipe by 
welding.

3. Apply specified refrigerant only. Never have it mixed with 
any other refrigerant. Never have air remain in the refrigerant 
line as it may lead to rupture or other hazards.

4. Make sure no refrigerant gas is leaking out when 
installation is completed.

5. If there is refrigerant leakage, please take sufficient 
measure to minimize the density of refrigerant.

6. Never touch the refrigerant piping or compressor without 
wearing glove to avoid scald or frostbite.

Improper installation may lead to fire hazard, 
explosion, electric shock or injury.

Sayfa 48

Safety Precautions for Installing and Relocating the Unit:

To ensure safety, please be mindful of the following precautions. 

WARNINGS

WARNINGS

1. When installing or relocating the unit, be sure to 
keep the refrigerant circuit free from air or substances 
other than the specified refrigerant.

Any presence of air or other foreign substance in the refrigerant 
circuit will cause system pressure rise or compressor rupture, 
resulting in injury.

2.When installing or moving this unit, do not charge 
the refrigerant which is not comply with that on the 
nameplate or unqualified refrigerant.

Otherwise, it may cause abnormal operation, wrong action, 
mechanical malfunction or even series safety accident.

3.When refrigerant needs to be recovered during 
relocating or repairing the unit, be sure that the unit is 
running in cooling mode.Then, fully close the valve at 
high pressure side (liquid valve).About 30-40 seconds 
later, fully close the valve at low pressure side (gas 
valve), immediately stop the unit and disconnect power. 
Please note that the time for refrigerant recovery 
should  not exceed 1 minute. 

If refrigerant recovery takes too much time, air may be sucked in 
and cause pressure rise or compressor rupture, resulting in injury. 

4.During refrigerant recovery, make sure that liquid 
valve and gas valve are fully closed and power is 
disconnected before detaching the connection pipe. 

If compressor starts running when stop valve is open and 
connection pipe is not yet connected, air will be sucked in and 
cause pressure rise or compressor rupture, resulting in injury.

45
Installation and Maintenance

5.When installing the unit, make sure that connection 
pipe is securely connected before the compressor 
starts running.

If compressor starts running when stop valve is open and 
connection pipe is not yet connected, air will be sucked in and 
cause pressure rise or compressor rupture, resulting in injury.

6.Prohibit installing the unit at the place where there 
may be leaked corrosive gas or flammable gas.

If there leaked gas around the unit, it may cause explosion and 
other accidents.

7.Do not use extension cords for electrical connections. 
If the electric wire is not long enough, please contact 
a local service center authorized  and ask for a proper 
electric wire.

Poor connections may lead to electric shock or fire.

8.Use the specified types of wires for electrical 
connections between the indoor and outdoor units. 
Firmly clamp the wires so that their terminals receive 
no external stresses.

Electric wires with insufficient capacity, wrong wire connections 
and insecure wire terminals may cause electric shock or fire.

Sayfa 49

Main Tools for Installation and Maintenance

Level meter
Measuring tape

Drill head
Electric drill

Torque wrench
Open-end wrench
Inner hexagon 

Vacuum pump

Pressure meter

Pipe cutter

Pipe bender
Pipe expander

Electronic scale
Refrigerant container

46
Installation and Maintenance

Screw driver

Impact drill

Electroprobe

Universal meter

Electronic 
leakage detector

spanner

Pipe pliers
Pipe pliers

Soldering appliance

Sayfa 50

8. Installation

8.1 Installation Dimension Diagram

Space to the ceiling

At least 15cm

Space to the wall

At least 15cm

At least 15cm
Space to the wall

At least 300cm
Space to the obstruction
Space to the floor

At least 250cm

Space to the obstruction

At least 50cm

Space to the obstruction

At least 30cm

Drainage pipe

Space to the wall

At least 30cm

Space to the obstruction

Space to the obstruction

At least 50cm

At least 200cm

47
Installation and Maintenance

Sayfa 51

Installation Procedures

48
Installation and Maintenance

 Start installation

Preparation before installation

Prepare tools
Read the requirements 
for electric connection

select installation 
location

Select indoor unit 
installation location

Select outdoor unit 
installation location

Install the support of outdoor unit
(select it according to the actual situation)

Install wall-mounting 
frame, drill wall holes

Connect pipes of indoor 
unit and drainage pipe

Fix outdoor unit

Install drainage joint of outdoor unit 
(only for cooling and heating unit)

Connect wires of indoor unit

Bind up pipes and 
hang the indoor unit

Make the bound pipes pass 
through the wall hole and then
 connect outdoor unit

Connect pipes of outdoor unit

Connect wires of outdoor unit

Neaten the pipes

Vacuum pumping and leakage detection

Check after installation and test operation

Finish installation

Note: this flow is only for reference; please find the more detailed installation steps in this section.

Sayfa 52

8.2 Installation Parts-checking 

No.
Name

1
Indoor unit

2
Outdoor unit

3
Connection pipe

4
Drainage pipe

5
Wall-mounting frame

6
Connecting cable(power cord)

7
Wall pipe

8
Sealing gum

9
Wrapping tape

10
Support of outdoor unit

11
Fixing screw

12
Drainage plug(cooling and heating unit)

13
Owners manual, remote controller

Note:

1.Please contact the local agent for installation.
2.Dont use unqualified power cord.

8.3 Selection of Installation Location

1. Basic Requirement:

Installing the unit in the following places may cause malfunction. If 
it is unavoidable, please consult the local dealer:

(1) The place with strong heat sources, vapors, flammable or 
explosive gas, or volatile objects spread in the air.

(2) The place with high-frequency devices (such as welding 
machine, medical equipment).

(3) The place near coast area.

(4) The place with oil or fumes in the air.

(5) The place with sulfureted gas.

(6) Other places with special circumstances.

(7) The appliance shall nost be installed in the laundry.

(8) It’s not allowed to be installed on the unstable or motive base 
structure(such as truck) or in the corrosive environment (such as 
chemical factory).

2. Indoor Unit:

(1)  There should be no obstruction near air inlet and air outlet.

(2) Select a location where the condensation water can be 
dispersed easily andwont affect other people.

(3) Select a location which is convenient to connect the outdoor 
unit and near the power socket.

(4)  Select a location which is out of reach for children.

(5) The location should be able to withstand the weight of indoor 
unit and wont increase noise and vibration.

(6) The appliance must be installed 2.5m above floor.

(7) Dont install the indoor unit right above the electric appliance.

(8) Please try your best to keep way from fluorescent lamp.

49
Installation and Maintenance

3. Outdoor Unit:

(1) Select a location where the noise and outflow air emitted by 
the outdoor unit will not affect neighborhood.

(2) The location should be well ventilated and dry, in which the 
outdoor unit wont be exposed directly to sunlight or strong wind.

(3) The location should be able to withstand the weight of outdoor 
unit.

(4) Make sure that the installation follows the requirement of 
installation dimension diagram.

(5) Select a location which is out of reach for children and far 
away from animals or plants.If it is unavoidable, please add fence 
for safety purpose.

8.4 Electric Connection Requirement

1. Safety Precaution

(1) Must follow the electric safety regulations when installing the 
unit.

(2) According to the local safety regulations, use qualified power 
supply circuit and air switch.

(3) Make sure the power supply matches with the requirement 
of air conditioner. Unstable power supply or incorrect wiring may 
result in electric shock,fire hazard or malfunction. Please install 
proper power supply cables before using the air conditioner.

(4) Properly connect the live wire, neutral wire and grounding wire 
of power socket.

(5) Be sure to cut off the power supply before proceeding any 
work related to electricity and safety.

(6) Do not put through the power before finishing installation.

(7) If the supply cord is damaged, it must be replaced by the 
manufacturer, its service agent or similarly qualified persons in 
order to avoid a hazard .

(8) The temperature of refrigerant circuit will be high, please keep 
the interconnection cable away from the copper tube.

(9) The appliance shall be installed in accordance with national 
wiring regulations.

2. Grounding Requirement:

(1) The air conditioner is the first class electric appliance.It must 
be properly grounding with specialized grounding device by a 
professional.

Please make sure it is always grounded effectively,otherwise it 
may cause electric shock.

(2) The yellow-green wire in air conditioner is grounding wire, 
which cant be used for other purposes.

(3) The grounding resistance should comply with national electric 
safety regulations.

(4) The appliance must be positioned so that the plug is 
accessible.

(5) An all-pole disconnection switch having a contact separation of 
at least 3mm in all poles should be connected in fixed wiring.

(6) Including an air switch with suitable capacity, please note 
the following table. Air switch should be included magnet buckle 
and heating buckle function, it can protect the circuit-short and 
overload. (Caution: please do not use the fuse only for protect the 
circuit)

Sayfa 53

4. Outlet Pipe

2)
12K
10A
3G1.0
18K
16A
3G1.5
24~36K
25A
3G2.5

Model
Air switch capacity
Power cord(mm

(1) The pipe can be led out in the direction of right, rear right, left 
or rear left.(As show in Fig.3)

(2) When selecting leading out the pipe from left or right, please 
cut off the corresponding hole on the bottom case.(As show in 
Fig.4)

8.5 Installation of Indoor Unit

1. Choosing Installation Iocation

Left
Right

Recommend the installation location to the client and then confirm 
it with the client.

Cut off
the hole

Left

Rear left

2. Install Wall-mounting Frame

Right
Rear right

(1) Hang the wall-mounting frame on the wall; adjust it in 
horizontal position with the level meter and then point out the 
screw fixing holes on the wall.

Fig.3
Fig.4

5. Connect the Pipe of Indoor Unit

(2) Drill the screw fixing holes on the wall with impact drill (the 
specification of drill head should be the same as the plastic 
expansion particle) and then fill the plastic expansion particles in 
the holes.

(1) Aim the pipe joint at the corresponding bellmouth.(As show in 
Fig.5)

(2) Pretightening the union nut with hand.

(3) Fix the wall-mounting frame on the wall with tapping screws 
and then check if the frame is firmly installed by pulling the frame. 
If the plastic expansion particle is loose, please drill another fixing 
hole nearby.

(3) Adjust the torque force by referring to the following sheet. 
Place the open-end wrench on the pipe joint and place the 
torque wrench on the union nut. Tighten the union nut with torque 
wrench.(As show in Fig.6) 

3. Install Wall-mounting Frame

(4) Wrap the indoor pipe and joint of connection pipe with 
insulating pipe, and then wrap it with tape.(As show in Fig.7)

(1) Choose the position of piping hole according to the direction of 
outlet pipe. The position of piping hole should be a little lower than 
the wall-mounted frame,shown as below.(As show in Fig.1)

Open-end 
wrench

Mark in the middle of it

Wall

Union nut
Union nut
Pipe joint
Pipe

Space

Pipe

Torque wrench

Wall

to the

Space

wall
above
150mm
Left

to the

wall
above
150mm

Indoor pipe

Fig.5
Fig.6

Right

Level meter

(Rear piping hole)

(For some models)
(Rear piping hole)

Fig.1

(2) Open a piping hole with the diameter of Φ55mm or Φ70mm on 
the selected outlet pipe position. In order to drain smoothly, slant 
the piping hole on the wall slightly downward to the outdoor side 
with the gradient of 5-10°.(As show in Fig.2)

Insulating pipe

Fig.7

Refer to the following table for wrench moment of force:

Indoor
Outdoor

Piping size(inch)
Tightening torque(N.m)

1/4
15~20

5-10°
Φ55/70mm 

3/8
30~40

Fig.2

1/2
45~55

5/8
60~65

Note:

3/4
70~75

Pay attention to dust prevention and take relevant safety 

measures when opening the hole.

50
Installation and Maintenance

Sayfa 54

6. Install Drain Hose

(1) Connect the drain hose to the outlet pipe of indoor unit.(As 
show in Fig.8)

N(1)
2
3

(2) Bind the joint with tape.(As show in Fig.9)

blue
black
brown yellow-

green

Outdoor unit connection

Drain hose

Outlet pipe

Fig.13

Note: The wiring connect is for reference only, please refer to 
the actual one.

Drain hose

Outlet

Tape

pipe

(4) Put wiring cover back and then tighten the screw.

Fig.8
Fig.9

(5) Close the panel.

Note:

WARNING

(1) All wires of indoor unit and outdoor unit should be connected 
by a professional.

(1) Add insulating pipe in the indoor drain hose in order to 

prevent condensation.

(2) If the length of power connection wire is insufficient, please 
contact the supplier for a new one. Avoid extending the wire by 
yourself. 

(2) The plastic expansion particles are not provided.

(As show in Fig.10)

(3) For the air conditioner with plug, the plug should be reachable 
after finishing installation.

Drain hose

(4) For the air conditioner without plug, an air switch must be 
installed in the line. The air switch should be all-pole parting and 
the contact parting distance should be more than 3mm.

Insulating pipe

8. Bind up Pipe

Fig.10

(1) Bind up the connection pipe, power cord and drain hose with 
the band.(As show in Fig.14)

7. Connect Wire of Indoor Unit

(2) Reserve a certain length of drain hose and power cord for 
installation when binding them. When binding to a certain degree, 
separate the indoor power and then separate the drain hose.(As 
show in Fig.15)

(1) Open the panel, remove the screw on the wiring cover and 
then take down the cover.(As show in Fig.11)

(3) Bind them evenly.

Panel
Screw

(4) The liquid pipe and gas pipe should be bound separately at the 
end.

Indoor and
outdoor power cord

Indoor unit
Gas
pipe

Wiring cover

Fig.11

(2) Make the power connection wire go through the cable-cross 
hole at the back of indoor unit and then pull it out from the front 
side.(As show in Fig.12)

Liquid 
pipe

Drain hose
Band

Fig.14

Cable-cross

hole

Drain hose
Band
Connection pipe

Power connection

wire

Fig.12

(3) Remove the wire clip; connect the power connection wiresignal 
control wire (only for cooling and heating unit) to the wiring 
terminal according to the color; tighten the screw and then fix the 
power connection wire with wire clip.(As show in Fig.13)

Indoor power cord

Fig.15

51
Installation and Maintenance

Sayfa 55

NOTICE:

(1) The power cord and control wire cant be crossed or winding.

(2) The drain hose should be bound at the bottom.

9. Hang the Indoor Unit

(1) Put the bound pipes in the wall pipe and then make them pass 
through the wall hole.

(2) Hang the indoor unit on the wall-mounting frame.

(3) Stuff the gap between pipes and wall hole with sealing gum.

(4) Fix the wall pipe.(As show in Fig.16)

(5) Check if the indoor unit is installed firmly and closed to the 
wall.(As show in Fig.17)

Indoor
Outdoor
Wall pipe
Sealing gum

Lower hook of
wall-mounting frame
Fig.16
Fig.17

NOTICE:

Do not bend the drain hose too excessively in order to prevent 

blocking.

8.6 Installation of Outdoor unit

1. Fix the Support of Outdoor Unit(Select it according 
to the actual installation situation)

(1) Select installation location according to the house structure.

(2) Fix the support of outdoor unit on the selected location with 
expansion screws.

NOTICE:

(1) Take sufficient protective measures when installing the outdoor 

unit.

(2) Make sure the support can withstand at least four times the 

unit weight.

(3) The outdoor unit should be installed at least 3cm above the 

floor in order to install drain joint.(As show in Fig.18)

(4) For the unit with cooling capacity of 2300W~5000W, 6 

expansion screws are needed; for the unit with cooling capacity of 

6000W~8000W, 8 expansion screws are needed; for the unit with 

cooling capacity of 10000W~16000W, 10 expansion screws are 

needed.

52
Installation and Maintenance

Drain vent

Chassis

Outdoor drain joint
Drain hose

At least 3cm above the floor

Fig.18
Fig.19

2. Install Drain Joint(Only for cooling and heating unit)

(1) Connect the outdoor drain joint into the hole on the chassis.

(2) Connect the drain hose into the drain vent.

(As show in Fig.19)

3. Fix Outdoor Unit

Upper hook

(1) Place the outdoor unit on the support.

(2) Fix the foot holes of outdoor unit with bolts.

(As show in Fig.20)

Foot holes

Handle

Foot holes

Valve cover

Fig.20
Fig.21

4. Connect Indoor and Outdoor Pipes

(1) Remove the screw on the handle and valve cover of outdoor 
unit, then remove them.(As show in Fig.21)

(2) Remove the screw cap of valve and aim the pipe joint at the 
bellmouth of pipe.(As show in Fig.22)

Liquid pipe

Pipe joint

Liquid
valve

gas pipe

Union nut

gas valve

Fig.22

(3) Pretightening the union nut with hand.

(4) Tighten the union nut with torque wrench .

Refer to the following table for wrench moment of force:

Piping size(inch)
Tightening torque(N.m)

1/4
15~20

3/8
30~40

1/2
45~55

5/8
60~65

3/4
70~75

Sayfa 56

5. Connect Outdoor Electric Wire

(1) Remove the wire clip; connect the power connection wire and 
signal control wire (only for cooling and heating unit) to the wiring 
terminal according to the color; fix them with screws.(As show in 
Fig.23)

The drain hose can't be fluctuant

12/18/24K

The water outlet 
can't be placed
in water

The drain 
hose can't 
be fluctuant
The water 
outlet can't 
be fluctuant

N(1)
2
3

blue
black
brown
yellow-
green

Fig.26
Fig.27

Indoor unit connection

30/36K

N(1)

2

L(3)

8.7 Vacuum Pumping and Leak Detection

yellow-
green

brown

yellow-
green

blue black brown blue

(black)

1. Use Vacuum Pump

N
Indoor unit connection

L

POWER

(1) Remove the valve caps on the liquid valve and gas valve and 
the nut of refrigerant charging vent.

Fig.23

*The wiring connect is for reference only, please refer to the actual one.

(2) Connect the charging hose of piezometer to the refrigerant 
charging vent of gas valve and then connect the other charging 
hose to the vacuum pump.

(2) Fix the power connection wire and signal control wire with wire 
clip (only for cooling and heating unit).

(3) Open the piezometer completely and operate for 10-15min to 
check if the pressure of piezometer remains in -0.1MPa.

NOTICE:

(4) Close the vacuum pump and maintain this status for 1-2min 
to check if the pressure of piezometer remains in -0.1MPa. If the 
pressure decreases, there may be leakage.

(1) After tightening the screw, pull the power cord slightly to check 

if it is firm.

(5) Remove the piezometer, open the valve core of liquid valve 
and gas valve completely with inner hexagon spanner.

(2) Never cut the power connection wire to prolong or shorten the 

distance.

(6) Tighten the screw caps of valves and refrigerant charging 
vent.(As show in Fig.28)

6. Neaten the Pipes

(1) The pipes should be placed along the wall, bent reasonably and 
hidden possibly. Min. semidiameter of bending the pipe is 10cm.

Liquid valve

Piezometer

Lo
Hi

Gas valve

(2) If the outdoor unit is higher than the wall hole, you must set 
a U-shaped curve in the pipe before pipe goes into the room, in 
order to prevent rain from getting into the room.(As show in Fig.24)

Valve cap

Refrigerant charging
vent

Nut of refrigerant

Charging vent

Vacuum pump

The drain hose
can't raise
upwards.

Inner hexagon
spanner

Wall

Open
Close

U-shaped curve

Drain hose

Fig.24
Fig.25

Fig.28

NOTICE:

2. Leakage Detection

(1) The through-wall height of drain hose shouldnt be higher than 
the outlet pipe hole of indoor unit.(As show in Fig.25)

(1) With leakage detector:

Check if there is leakage with leakage detector.

(2) Slant the drain hose slightly downwards. The drain hose cant 
be curved, raised and fluctuant, etc.(As show in Fig.26)

(2) With soap water:

If leakage detector is not available, please use soap water for 
leakage detection. Apply soap water at the suspected position and 
keep the soap water for more than 3min. If there are air bubbles 
coming out of this position, there's a leakage.

(3) The water outlet cant be placed in water in order to drain 
smoothly.(As show in Fig.27)

53
Installation and Maintenance

Sayfa 57

8.8 Check after Installation and Test operation

1. Check after Installation

Check according to the following requirement after finishing 
installation.

NO.
Items to be checked
Possible malfunction

1
Has the unit been installed 
firmly?

2
Have you done the 
refrigerant leakage test?

3
Is heat insulation of pipeline 
sufficient?

4
Is water drained well?
It may cause condensation 
and water dripping.

Is the voltage of power 
supply according to the 
voltage marked on the 
nameplate?

5

6
Is electric wiring and pipeline 
installed correctly?

7
Is the unit grounded 
securely?

8
Does the power cord follow 
the specification?

9
Is there any obstruction in 
air inlet and air outlet?

10
The dust and sundries 
caused during installation 
are removed?

11
The gas valve and liquid 
valve of connection pipe are 
open completely?

12
Is the inlet and outlet of 
piping hole been covered?

2. Test Operation

(1) Preparation of test operation

● The client approves the air conditioner installation.

● Specify the important notes for air conditioner to the client.

(2) Method of test operation

● Put through the power, press ON/OFF button on the remote 
controller to start operation.

● Press MODE button to select AUTO, COOL, DRY, FAN and 
HEAT to check whether the operation is normal or not.

● If the ambient temperature is lower than 16
oC, the air conditioner 
cant start cooling.

54
Installation and Maintenance

The unit may drop, shake or 
emit noise.

It may cause insufficient 
cooling (heating) capacity.

It may cause condensation 
and water dripping.

It may cause malfunction or 
damage the parts.

It may cause malfunction or 
damage the parts.

It may cause electric 
leakage.

It may cause malfunction or 
damage the parts.

It may cause insufficient 
cooling (heating) capacity.

It may cause malfunction or 
damaging the parts.

It may cause insufficient 
cooling (heating) capacity.

It may cause insufficient 
cooling(heating) capacity or 
waster eletricity.

Sayfa 58

9. Maintenance

9.1 Error Code List

Display Method 

Malfunction 

of Indoor Unit

A/C Status

Name

(Error Code)

During cooling and drying operation, 
except indoor fan operates, all loads 
stop operation.
During heating operation, the complete 
unit stops.

High pressure
protection of 
system

E1

1. Poor air-return in indoor unit;
2. Fan speed is abnormal;
3. Evaporator is dirty.
System block 
or refrigerant 
leakage

During cooling and drying operation, 
compressor and outdoor fan stop while 
indoor fan operates.

Antifreezing
protection
E2

The Dual-8 Code Display will show 
E3 until the low pressure switch stop 
operation.

E3

High discharge
temperature
protection of
compressor

During cooling and drying operation, 
compressor and outdoor fan stop while 
indoor fan operates. During heating 
operation, all loads stop.

E4

During cooling and drying operation, 
compressor and outdoor fan stop while 
indoor fan operates. During heating 
operation, all loads stop.

Overcurrent
protection
E5

During cooling operation, compressor 
stops while indoor fan motor operates. 
During heating operation, the complete 
unit stops.

Communi-
cation
Malfunction

E6

High
temperature
resistant
protection

During cooling operation: compressor 
will stop while indoor fan will operate. 
During heating operation, the complete 
unit stops.

E8

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop

EEPROM
malfunction
EE

Limit/decrease
frequency due 
to high
temperature of 
module

EU
All loads operate normally, while 
operation frequency for compressor is 
decreased

Malfunction
protection of
jumper cap

C5
Wireless remote receiver and button are 
effective, but can not dispose the related
command

When the outdoor unit receive signal of 
Gathering refrigerant ,the system will 
be forced to run under cooling mode for 
gathering refrigerant

Gathering 
refrigerant
F0

1. Loosening or bad contact of indoor ambient temp. sensor 
and mainboard terminal.
2. Components in mainboard fell down leads short circuit.
3. Indoor ambient temp. sensor damaged.(check with sensor
resistance value chart)
4. Mainboard damaged.
Indoor
evaporator
temperature
sensor is
open/short
circuited

Indoor ambient
temperature
sensor is
open/short 
circuited

During cooling and drying operation, 
indoor unit operates while other loads 
will stop; during heating operation, the 
complete unit will stop operation.

F1

AC stops operation once reaches the 
setting temperature. Cooling, drying: 
internal fan motor stops operation while 
other loads stop operation; heating: AC
stop operation

F2

55
Installation and Maintenance

Possible Causes(For specific maintenance 
method, please refer to the following procedure of 

troubleshooting)

Possible reasons: 
1. Refrigerant was superabundant; 
2. Poor heat exchange (including filth blockage of heat 
exchanger and bad radiating environment ); Ambient 
temperature is too high.

1.Low-pressure protection 
2.Low-pressure protection of system 
3.Low-pressure protection of compressor 

Please refer to the malfunction analysis (discharge 
protection, overload).

1. Supply voltage is unstable;
2. Supply voltage is too low and load is too high;
3. Evaporator is dirty.

Refer to the corresponding malfunction analysis.

Refer to the malfunction analysis (overload, high temperature 
resistant).

Replace outdoor control panel AP1

Discharging after the complete unit is de-energized for 
20mins, check whether the thermal grease on IPM Module 
of outdoor control panel AP1 is sufficient and whether the 
radiator is inserted tightly.
If its no use, please replace control panel AP1.

1. No jumper cap insert on mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of mainboard.

Nominal cooling mode

1. Loosening or bad contact of Indoor evaporator temp. 
sensor and mainboard terminal.
2. Components on the mainboard fall down leads short 
circuit.
3. Indoor evaporator temp. sensor damaged.(check temp. 
sensor value chart for testing)
4. Mainboard damaged.

Sayfa 59

During cooling and drying operating, 
compressor stops while indoor fan 
operates; During heating operation, the 
complete unit will stop operation

Outdoor ambient
temperature sensor is
open/short circuited

F3

During cooling and drying operation, 
compressor stops while indoor fan will 
operate; During heating operation, the 
complete unit will stop operation.

Outdoor condenser
temperature sensor is
open/short circuited

F4

During cooling and drying operation, 
compressor will sop after operating for 
about 3 mins, while indoor fan will operate;
During heating operation, the complete unit 
will stop after operating for about 3 mins.

Outdoor discharge
temperature sensor is
open/short circuited

F5

Limit/decrease
frequency due to
overload

F6
All loads operate normally, while operation 
frequency for compressor is decreased

Decrease frequency 
due to overcurrent
F8
All loads operate normally, while operation 
frequency for compressor is decreased

Decrease frequency 
due to high air 
discharge

F9
All loads operate normally, while operation 
frequency for compressor is decreased

Limit/decrease
frequency due to
antifreezing

FH
All loads operate normally, while operation 
frequency for compressor is decreased
Poor air-return in indoor unit or fan speed is too low

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate; During heating operation, the
complete unit will stop operation.

Voltage for DC bus-
bar is too high
PH

1. Measure the voltage of position L and N on wiring board 
(XT), if the voltage is higher than 150VAC, turn on the unit 
after the supply voltage is increased to the normal range.
2.If the AC input is normal, measure the voltage of electrolytic 
capacitor C on control panel (AP1), if its normal, theres 
malfunction for the circuit, please replace the control panel 
(AP1)
Compressor Min 
frequence in test state
P0
Showing during min. cooling or min. heating test

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop

Voltage of DC bus-bar 
is too low 
PL

Compressor rated 
frequence in test state
P1
Showing during nominal cooling or nominal heating test

Compressor maximum 
frequence in test state
P2
Showing during max. cooling or max. heating test

Compressor 
intermediate 
frequence in test state

P3
Showing during middle cooling or middle heating test

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop operation.

Overcurrent protection 
of phase current for 
compressor

P5

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop

Charging malfunction 
of capacitor
PU

56
Installation and Maintenance

Outdoor temperature sensor hasnt been connected well or is 
damaged. Please check it by referring to the resistance table 
for temperature sensor)

Outdoor temperature sensor hasnt been connected well or is 
damaged. Please check it by referring to the resistance table 
for temperature sensor)

1.Outdoor temperature sensor hasnt been connected well 
or is damaged. Please check it by referring to the resistance 
table for temperature sensor)
2.The head of temperature sensor hasnt been inserted into 
the copper tube

Refer to the malfunction analysis (overload, high temperature 
resistant)

The input supply voltage is too low; System pressure is too 
high and overload

Overload or temperature is too high;  Refrigerant is 
insufficient; Malfunction of electric expansion valve (EKV)

1. Measure the voltage of position L and N on wiring board 
(XT), if the voltage is higher than 265VAC, turn on the unit 
after the supply voltage is increased to the normal range.
2.If the AC input is normal, measure the voltage of electrolytic 
capacitor C on control panel (AP1), if its normal, theres 
malfunction for the circuit, please replace the control panel 
(AP1)

Refer to the malfunction  analysis (IPM protection, loss of 
synchronism protection and overcurrent protection of phase 
current for compressor.

Refer to the part three—charging malfunction analysis of 
capacitor

Sayfa 60

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop

Malfunction of module
temperature sensor 
circuit

P7

During cooling operation, compressor will 
stop while indoor fan will operate; During 
heating operation, the complete unit will 
stop

Module high 
temperature
protection

P8

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop operation.

Overload protection 
for compressor
H3

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop operation.

IPM protection
H5

Malfunction of zero-
cross detection circuit
U8
The complete unit stops
1.Power supply is abnormal;
2.Detection circuit of indoor control mainboard is abnormal.

Internal fan motor, external fan motor, 
compressor and electric heater stop 
operation,guide louver stops at present 
location.

Internal motor (fan 
motor) do not operate
H6

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop operation.

Desynchro-nizing of 
compressor
H7

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop operation.

PFC protection
HC

Outdoor DC fan motor 
malfunction
L3
Outdoor DC fan motor malfunction lead to 
compressor stop operation, 

compressor stop operation and Outdoor 
fan motor will stop 30s latter , 3 minutes 
latter fan motor and compressor will restart

power  protection
L9

Indoor unit and 
outdoor unit doesnt 
match

LP
compressor and Outdoor fan motor cant 
work 
Indoor unit and outdoor unit doesnt match

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop operation.

Failure start-up
LC

Heating 
indicator 

off for 
0.5s and 
then 
blinks 
for 10s

Defrosting will occur in heating mode. 
Compressor will operate while indoor fan 
will stop operation.

Defrosting

If this malfunction occurs during heating 
operation, the complete unit will stop 
operation.

The four-way valve is
abnormal
U7

57
Installation and Maintenance

Replace outdoor control panel AP1

After the complete unit is de-energized for 20mins, check 
whether the thermal grease on IPM Module  of outdoor 
control panel AP1 is sufficient and whether the radiator is 
inserted tightly. If its no use, please replace control panel 
AP1.

1. Wiring terminal OVC-COMP is loosened. In normal state, 
the resistance for this terminal should be less than 1ohm. 
2.Refer to the malfunction analysis ( discharge protection, 
overload)

Refer to the malfunction analysis (IPM protection, loss of 
synchronism protection and overcurrent protection of phase 
current for compressor.

1. Bad contact of DC motor feedback terminal.
2. Bad contact of DC motor control end.
3. Fan motor is stalling.
4. Motor malfunction.
5. Malfunction of mainboard revdetecting circuit.

Refer to the malfunction analysis (IPM protection, loss of 
synchronism protection and overcurrent protection of phase 
current for compressor.

Refer to the malfunction analysis

DC fan motor malfunction or system blocked or the connector 
loosed 

To protect the electronical components when detect high 
power 

Refer to the malfunction analysis

Not the error code. It’s the status code for the operation

1.Supply voltage is lower than AC175V;
2.Wiring terminal 4V is loosened or broken;
3.4V is damaged, please replace 4V.

Sayfa 61

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop

Malfunction of phase 
current detection 
circuit for compressor

U1

During cooling and drying operation, 
compressor will stop while indoor fan will 
operate;
During heating operation, the complete 
unit will stop

Malfunction of voltage
dropping for DC 
busbar

U3

During cooling and drying operation, the 
compressor will stop while indoor fan will 
operate; 
During heating operating, the complete 
unit will stop operation.

Malfunction of 
complete units current 
detection

U5

Malfunction of 
detecting plate(WIFI )
JF
Loads operate normally, while the unit 
can’t be normally controlled by APP.

Analysis or processing of some of the malfunction display:
1. Compressor discharge protection
Possible causes: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short pass for condenser; the sys­
tem has noncondensing gas (such as air, water etc.); blockage of capillary assy (including filter); leakage inside four-way 
valve causes incorrect operation; malfunction of compressor; malfunction of protection relay; malfunction of discharge sen­
sor; outdoor temperature too high.
Processing method: refer to the malfunction analysis in the above section.
2. Low voltage overcurrent protection
Possible cause: Sudden drop of supply voltage.
3.Communication malfunction
Processing method: Check if communication signal cable is connected reliably.
4. Sensor open or short circuit
Processing method: Check whether sensor is normal, connected with the corre sponding position on the controller and if 
damage of lead wire is found.
5. Compressor over load protection
Possible causes: insufficient or too much refrigrant; blockage of capillary and increase of suction temp.; improper running of 
compressor, burning in or stuck of bearing, damage of discharge valve; malfunction of protector.
Processing method: adjust refrigerant amount; replace the capillary; replace the compressor; use universal meter to check if 
the contactor of compress or is fine when it is not overheated, if not replace the protector.
6. System malfunction
i.e.overload protection.When tube temperature(Check the temperature of outdoor heat exchanger when cooling and check 
the temperatur e of indoor heat exchanger when heating) is too high, protection will be activated.
Possible causes: Outdoor temperature is too high when cooling; insufficient outdoor air circulation; refrigerant flow malfunc­
tion.
please refer to the malfunction analysis in the previous section for handling method .
7. IPM module protection
Processing method:Once the module malfunction happens,if it persists for a long time and can not be selfcanceled, cut off 
the power and turn off the unit,and then re-energize the unit again after about 10 min.After repeating the procedure for sever 
times, if the malfunction still exists,replace the module.

58
Installation and Maintenance

Replace outdoor control panel AP1

Supply voltage is unstable

Theres circuit malfunction on outdoor units control panel 
AP1, please replace the outdoor units control panel AP1.

1. Main board of indoor unit is damaged;
2. Detection board is damaged;
3. The connection between indoor unit and detection board is 
not good; 

Sayfa 62

If malfunction occurs,corresponding code will display and the unit will resume normal until protection or 
malfunction disappears.

59
Installation and Maintenance

Sayfa 63

9.2 Procedure of Troubleshooting

●Indoor unit:  

1. Malfunction of Temperature Sensor F1, F2

Main detection points:

● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?

● Is there short circuit due to trip-over of the parts?

● Is the temperature sensor broken?

● Is mainboard broken?

Malfunction diagnosis process:

60
Installation and Maintenance

Start

Is the wiring terminal between the 
temperature sensor and the controller 

Yes

loosened or poorly contacted?

Insert the temperature 

sensor tightly

No

No

Is malfunction 

eliminated

Yes

Is there short circuit due to trip-

over of the parts

Make the parts upright

No

No

Is malfunction 

Yes

eliminated

Is the temperature sensor normal 
according to the resistance table?

No

Yes

Replace it with a 
temperature sensor with 

the same model

Yes

Is malfunction 

No

eliminated

Replace the mainboard with 

the same model.

Yes

End

Sayfa 64

2. Malfunction of Blocked Protection of IDU Fan Motor H6
Main detection points:
● SmoothlyIs the control terminal of PG motor connected tightly?
● SmoothlyIs the feedback interface of PG motor connected tightly?
● The fan motor can't operate?
● The motor is broken?
● Detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:

Measure the voltage of this foot to 

neutral wire on the mainboard

61
Installation and Maintenance

Start

While power is off stir the blade 

No

with a tool to see whether the 

blade rotates  smoothly 

Tighten the screw; reassemble the blade, motor 
and shaft bearing rubber base sub-assy to make 

sure there is no foreign object between them
Yes

No

Yes

Is malfunction 

eliminated

Check if the connection of PG 
motor feedback terminal is firm

No

Insert the control terminal 

of PG motor tightly

Yes

No

Is malfunction 

Yes

eliminated

Check if the connection of PG 

No

motor control terminal is firm

Reinstall the blade 
and motor correctly

Yes

No

Is malfunction 

Yes

eliminated

Turn on the unit again; measure 

whether the output voltage on 
control terminal for PG motor is 
more than 50V  within 1 min after 

Yes

Yes

the louvers are opened

Yes

Is the motor started up

No

Replace PG motor

No

No

Yes

Is malfunction 

eliminated

Replace the mainboard 

with the same model

End

Sayfa 65

3. Malfunction of Protection of Jumper Cap C5

Main detection points:

● Is there jumper cap on the mainboard?

● Is the jumper cap inserted correctly and tightly?

● The jumper is broken?

● The motor is broken?

● Detection circuit of the mainboard is defined abnormal?

Malfunction diagnosis process:

62
Installation and Maintenance

Start

No

Appearance of the 

Is there jumper cap on the mainboard?

jumper cap

Assemble the jumper
cap with the same model

Yes

No

Is malfunction 

eliminated

No

Is the jumper cap inserted correctly 

and tightly?

Insert the jumper 

cap tightly

Yes

No

Is malfunction 

Yes

eliminated

Replace the jumper cap with 

the same model

Yes

Is malfunction 

eliminated

Yes

No

Replace the mainboard

with the same model

End

Sayfa 66

4. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8

Main detection points:

● Instant energization afte de-energization while the capacitordischarges slowly?

● The zero-cross detectioncircuit of the mainboard is defined abnormal?

Malfunction diagnosis process:

63
Installation and Maintenance

Start

Turn power off for 

1minute,the turn 
back on

The unit returns to normal. 
Conclusion:U8 is displayed due to 
power off/on while the
capacitor discharges slowly.

U8 is still 
displayed

No

Yes

The zero-cross detection circuit 

of the mainboard is defined 
abnormal.Replace the mainboard 

with the same model

End

Sayfa 67

5. High Temperature and Overload Protection (AP1 below means control board of outdoor unit) E8

Start

If the outdoor ambient temperature is 

higher than 53°C?

No

is good?

No

If the indoor and outdoor fan are 

running normally?

Yes

Replace outdoor 

mainboard

End

64
Installation and Maintenance

Normal protection, please use it 
after improving the outdoor ambient 

Yes

Unit restarts 

Yes

normally

temperature

No

Improve the radiating environment of 

Yes

Unit restarts 

unit (clean the heat exchanger and 

normally

remove surrounding obstacles)

No

Connect normally?
Adjust the 
connection

Yes

Yes

Replace fan

Yes

Fan capacitor is broken?

capacitor

No

Yes

Motor is broken?

Replace motor

No

Replace mainboard

Sayfa 68

6. Malfunction of detecting plate(WIFI) JF

65
Installation and Maintenance

Start

check if the connection wire

 are correctly connected

Yes

Replace the detecting 
 plate with the same model

Is malfunction 

eliminated

No

Yes

Replace the mainboard 

with the same model

The end

Sayfa 69

●Outdoor unit:  

1.Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit) 

Main detection point: 

● Detect if the voltage of L and N terminal of wiring board is between 210AC-240AC by alternating voltage meter; 
● Is reactor (L) well connected? Is connection wire loosened or pull-out? Is reactor (L) damaged?

Malfunction diagnosis process: 

Turn on the unit 
and wait 1 minute

Use DC voltmeter 
to measure the 
voltage on the two 
ends of electrolytic 

capacitor 

Fault with the 
voltage testing 
circuit on 
control panel AP1

Replace the 
control 
panel AP1

Voltage higher than 
200V?

Y

Measure the AC voltage 
between 
terminal L and and N on wiring 

board XT(power supply)

Shut down the
power and repair
the power supply 
to restore the range

power on and
restart the unit
If the fault is 
eliminated?

Voltage within 
210VAC~250VAC?

N
Y

210VAC~250VAC

Y

Shut down the power and wait 20 minutes; 
or use DC voltmeter to measure the voltage 

N

on the two ends of capacitor (test3), 

until the voltage  is lower than 20V

Check the 
connection of reactor 
(Lin the Electrical Wiring 

Diagram)

Connect the reactor 
Laccording to Elec-

Re-energize and
turn on the unit
If the fault is 
eliminated?

If the wiring of 
reactor Lis normal?

N

trical Wiring Diagr-

am correctly

Y

Replace the control 
panel AP1

N

End

66
Installation and Maintenance

Y

Sayfa 70

2.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit)

Main detection point:

● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan is running normal;
● If the radiating environment of indoor and outdoor unit is well.

Malfunction diagnosis process:

67
Installation and Maintenance

Anti-high temperature,
overload protection

Normal protection, please use 
it after improve the outdoor 

If the outdoor ambient temperature is 
higher than 53 °C?

Y

ambient temperature

N

After the unit de-
energized for 20min

Improve the
radiating 
environment of
unit 

If the radiating of outdoor 
and indoor unit is well?

Y

N

1. Check if fan terminal 
OFAN is connected well
2. Test if resistance value 
of any two terminals is less 
than 1kΩ with ohmic meter

If the indoor and outdoor 
fan work well?

N

Y

Replace fan 
capacitor C1

Replace
control board

AP1

Replace 
outdoorfan

End

Sayfa 71

3.IPM protection, phase current overcurrent (the control board as below indicates the control board 
    of outdoor unit) H5/P5
Mainly detect:
(1) Compressor COMP terminal  (2) voltage of  power supply (3) compressor 
(4) Refrigerant-charging volume  (5) air outlet and air inlet of outdoor/indoor unit 
 Troubleshooting:

Turn on the unit 
after energization

Check the connection 
between the control board 

Whether IPM 
protection occurs after the unit has 

N

and the compressor by 

referring to the electric 

operated for a while? 

wiring diagram

Y

Correctly connect the wires of 

Check whether wires 
of compressor (UVW) are connected 

Whether 
the voltage between 
terminal L and terminal N
 of XT is  within 210AVC~

Y

compressor according to the 

electric wiring diagram, and 

correctly

then turn on the unit

250VAC?

N

Measure the resistance value 
among three terminals (UVW) 
of compressor with a resistance 

Check the power 
supply voltage and 
make the power voltage 

measuring meter. 

Whether IPM 
protection occurs after the unit has 

N

operated for a while? 

resume to the range 
of 210VAC~250VAC

Whether the 
resistance value of three terminals 

are almost the same. 

Y

1. Whether the heat exchangers of indoor unit and outdoor unit are 
dirty? Whether the radiation is affected because the unit is 

Measure the resistance 
between three terminals (UVW) 
of compressor and the copper pipe 

covered by the objects? 
2. When indoor fan and outdoor unit are operate normally?
3. Whether the system pressure is too high?
4. Whether the pressure is because there's too much refrigerant? 

with resistance measuring meter

Whether the 
resistance value is more than 

500ohm?

Whether there's 
abnormal phenomenons 

Correct it one by one 
according to the Service 
Manual, and then turn on 

N

Y

described as above? 

Replace the 
compressor  

the unit. 

N

N

Y

Whether the unit 
can operate normally? 

N

Y

Replace control 

Y

board

End

68
Installation and Maintenance

Sayfa 72

4. Start-up failure (following AP1 for outdoor unit control board)

Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:

Power on the unit

Is stop time of the compressor 

longer than 3 minutes?

Yes

Does startup fail?

Yes

Are the wires for the compressor connected 

correctly? Is connection sequence right?

Yes

Replace the control panel AP1

No

If the fault is eliminated?

No

Replace the 
compressor

End

69
Installation and Maintenance

Restart it up after 
3 minutes

No

Connect the wires as 
per the connection 
diagram

No

Yes

Sayfa 73

5. Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)

Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:

unit is powered on.
Out of step occurs once the 

No

Is stop time of the 
compressor longer than 

3 minutes?

Yes

Are the wires for the compressor connected 

Is the connection made in clockwise 
correctly? Is connection sequence right?

direction?

No

Yes

Connect the 
wires correctly

Replace the 
control panel AP1

Yes

If the fault is eliminated?

No

Replace the 
compressor 

End

70
Installation and Maintenance

Out of step occurs in 

operation

capacitor C1
Check if the fan terminal 
OFAN is connected 
correctly

No

Replace the fan 

Is the outdoor fan working 

normally?

Yes

Replace the 
outdoor fan

Yes

Remove foreign 
objects

Is the outdoor unit blocked 

by foreign objects?

No

Replace the 

control panel AP1

Yes

If the fault is eliminated?

No

Replace the 
compressor 

End

Sayfa 74

6. Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)

Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:

71
Installation and Maintenance

20 minutes after the 
complete unit is 

powered off

Is the terminal FA for the 
electronic expansion valve 

Connect the 
wires correctly

No

connected correctly?

Yes

Resistances between the first four pins 
close to the terminal hole 
and the fifth 
pin are almost the same, less than 100 
ohm.

Replace the electronic 

expansion valve

Yes

If the fault is eliminated?

No

Replace the 

AP1
control panel 

Yes

If the fault is eliminated?

No

Coolant leakage, refilling 

the coolant

End

Sayfa 75

7. Communication malfunction: (following AP1 for outdoor unit control board)

Mainly detect:
●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is 
there any
damage?
Fault diagnosis process:

Start

Did the equipment operate 
normally before the failure 

No

Yes

occurs?

Check the wiring of the indoor and 

outdoor units with reference to the 

wiring diagram

Check wiring inside 
of the indoor and 

Yes

Is the connection right?

outdoor units

No
No

Correctly connect the 
corresponding wires for 

The AP1 voltage 
detection circuit 
is at fault

Yes

Are wires broken?

the indoor and outdoor 

units with reference to 

the wiring diagram

No

If the fault is eliminated?
Check the communication 

No

circuit of the outdoor unit

If the fault is eliminated?

Yes

Replace the main board 

The communication 

AP1
of the outdoor unit

circuit is abnormal

No

If the fault is eliminated?

No

Replace the main board 
of the indoor unit

Yes

Yes

Yes

End

72
Installation and Maintenance

Sayfa 76

8. Malfunction of Overcurrent Protection

Main detection points:

● Is the supply voltage unstable with big fluctuation?

● Is the supply voltage too low with overload?

● Hardware trouble?

Malfunction diagnosis process:

Start

Yes
Yes

Is the supply voltage unstable

of the rated voltage on the nameplate

No
No

Yes

Is the supply voltage too low

Adjust the supply voltage to maintain it 
within normal range

with overload?

No

No

Is the indoor / outdoor
heat exchanger dirty,or are the air inlet

Yes

Clean the indoor and outdoor heat 
exchangers and remove the blockage 
of air inlet and outlet

and outlet blocked?

No

No

The fan is abnormal? Fan
speed is too low or fan doesnt rotate

Yes

Check the motor and reinstall the 
motor to have the fan run normally

No
No

Measure the current of live wire on 
the main board with a clamp ampere 

No

Replace the mainboard with the same 
model

meter. Is the current higher than the 
value of the overcurrent protection?

No

Yes

Is there blockage inside the system? 

Yes

Flush the heat exchangers with high 
pressure nitrogen

(Filth blockage, ice plug, greasy 
blockage, the cut off valve hasnt been 

opened completely)

No

No

Is the compressor running abnormally? 
Is there abnormal sound or oil leakage; 
Is the temperature of the shell too high, 

Yes

Replace the compressor

etc.?

No

Replace the mainboard 

with the same model

End

73
Installation and Maintenance

eliminated
Is malfunction 

Yes

eliminated
Is malfunction 

Yes

Is malfunction 

eliminated

Is malfunction 

Yes

eliminated

eliminated
Is malfunction 

Yes

Yes

Is malfunction 

eliminated

eliminated
Is malfunction 

Yes

Sayfa 77

9.3 Troubleshooting for Normal Malfunction

1. Air Conditioner Cant be Started Up

Possible Causes 
Discriminating Method (Air conditioner Status)
Troubleshooting 

Confirm whether its due to power failure. If yes, 
wait for power recovery. If not, check power 
supply circuit and make sure the power plug is 
connected well. 
Wrong wire connection between 
indoor unit and outdoor unit, or poor 
connection for wiring terminals 

No power supply, or poor connection 
for power plug

After energization, operation indicator isnt bright 
and the buzzer cant give out sound 

Under normal power supply circumstances, 
operation indicator isnt bright after energization

Make sure the air conditioner is grounded reliably
Make sure wires of air conditioner is connected 
correctly
Check the wiring inside air conditioner. Check 
whether the insulation layer of power cord is 
damaged; if yes, place the power cord.
Model selection for air switch is 
improper
After energization, air switch trips off
Select proper air switch

Electric leakage for air conditioner
After energization, room circuit breaker trips off at 
once

After energization, operation indicator is bright, 
while no display on remote controller or buttons 
have no action. 

Malfunction of remote controller 

2. Poor Cooling (Heating) for Air Conditioner 

Possible Causes 
Discriminating Method (Air conditioner Status)
Troubleshooting 

Set temperature is improper
Observe the set temperature on remote controller  Adjust the set temperature

Rotation speed of the IDU fan 
motor is set too low
Small wind blow 
Set the fan speed at high or medium 

Filter of indoor unit is blocked 
Check the filter to see its blocked 
Clean the filter 

Check whether the installation postion is proper 
according to installation requirement for air 
conditioner 

Installation position for indoor unit 
and outdoor unit is improper 

Discharged air temperature during cooling is 
higher than normal discharged wind temperature; 
Discharged air temperature during heating is lower 
than normal discharged wind temperature; Units 
pressure is much lower than regulated range 

Refrigerant is leaking 

Malfunction of 4-way valve 
Blow cold wind during heating 
Replace the 4-way valve 

Discharged air temperature during cooling is 
higher than normal discharged wind temperature; 
Discharged air temperature during heating is lower 
than normal discharged wind temperature; Unitt 
pressure is much lower than regulated range. If 
refrigerant isnt leaking, part of capillary is blocked 

Malfunction of capillary

Flow volume of valve is insufficient The pressure of valves is much lower than that 

stated in the specification
Open the valve completely 

Malfunction of horizontal louver 
Horizontal louver cant swing 
Refer to point 3 of maintenance method for details 

Malfunction of the IDU fan motor 
The IDU fan motor cant operate 
Refer to troubleshooting for H6 for maintenance 
method in details 

Malfunction of the ODU fan motor The ODU fan motor cant operate 
Refer to point 4 of maintenance method for details 

Malfunction of compressor 
Compressor cant operate 
Refer to point 5 of maintenance method for details 

3. Horizontal Louver Cant Swing

Possible Causes 
Discriminating Method (Air conditioner Status)
Troubleshooting 

Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Stepping motor is damaged 
Stepping motor cant operate 
Repair or replace stepping motor 

Main board is damaged 
Others are all normal, while horizontal louver cant 
operate 
Replace the main board with the same model

74
Installation and Maintenance

Check the circuit according to circuit diagram 
and connect wires correctly. Make sure all wiring 
terminals are connected firmly

Replace batteries for remote controller
Repair or replace remote controller

Adjust the installation position, and install the 
rainproof and sunproof for outdoor unit

Find out the leakage causes and deal with it. Add 
refrigerant. 

Replace the capillary

Connect wires according to wiring diagram to make 
sure all wiring terminals are connected firmly

Sayfa 78

4. ODU Fan Motor Cant Operate

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 

Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Measure the capacity of fan capacitor with an 
universal meter and find that the capacity is out of 
the deviation range indicated on the nameplate of 
fan capacitor.

Capacity of the ODU fan motor is 
damaged 

Power voltage is a little low or high Use universal meter to measure the power supply 

voltage. The voltage is a little high or low 
Suggest to equip with voltage regulator 

When unit is on, cooling/heating performance is 
bad and ODU compressor generates a lot of noise 
and heat. 

Motor of outdoor unit is damaged

5. Compressor Cant Operate

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 
Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Measure the capacity of fan capacitor with an 
universal meter and find that the capacity is out of 
the deviation range indicated on the nameplate of 
fan capacitor.

Capacity of compressor is 
damaged 

Power voltage is a little low or high Use universal meter to measure the power supply 

voltage. The voltage is a little high or low 
Suggest to equip with voltage regulator 

Coil of compressor is burnt out
Use universal meter to measure the resistance 
between compressor terminals and its 0
Repair or replace compressor

Cylinder of compressor is blocked Compressor cant operate 
Repair or replace compressor 

6. Air Conditioner is Leaking 

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 

Drain pipe is blocked 
Water leaking from indoor unit
Eliminate the foreign objects inside the drain pipe

Drain pipe is broken 
Water leaking from drain pipe
Replace drain pipe 

Wrapping is not tight
Water leaking from the pipe connection place of 
indoor unit
Wrap it again and bundle it tightly 

7. Abnormal Sound and Vibration

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 

When turn on or turn off the unit, 
the panel and other parts will 
expand and theres abnormal sound 

Theres the sound of "PAPA"
Normal phenomenon. Abnormal sound will 
disappear after a few minutes. 

When turn on or turn off the unit, 
theres abnormal sound due to flow 
of refrigerant inside air conditioner

Water-running sound can be heard 
Normal phenomenon. Abnormal sound will 
disappear after a few minutes. 

Remove foreign objects. Adjust all parts position 
of indoor unit, tighten  screws and stick damping 
plaster between connected parts 
Foreign objects inside the outdoor 
unit or therere parts touching 
together inside the outdoor unit 

Foreign objects inside the indoor 
unit or therere parts touching 
together inside the indoor unit 

Theres abnormal sound fro indoor unit

Remove foreign objects. Adjust all parts position 
of outdoor unit, tighten  screws and stick damping 
plaster between connected parts 
Short circuit inside the magnetic 
coil 

Theres abnormal sound fro outdoor unit

During heating, the way valve has abnormal 
electromagnetic sound 
Replace magnetic coil 

Abnormal shake of compressor 
Outdoor unit gives out abnormal sound 
Adjust the support foot mat of compressor, tighten 
the bolts 

Abnormal sound inside the 
compressor 
Abnormal sound inside the compressor 

75
Installation and Maintenance

Connect wires according to wiring diagram to make 
sure all wiring terminals are connected firmly

Replace the capacity of fan

Change compressor oil and refrigerant. If no better, 
replace the compressor with a new one

Connect wires according to wiring diagram to make 
sure all wiring terminals are connected firmly

Replace the compressor capacitor

If add too much refrigerant during maintenance, 
please reduce refrigerant properly. Replace 
compressor for other circumstances. 

Sayfa 79

10. Exploded View and Parts List

10.1 Indoor Unit

GWC12AGC-S3DTA1C/I	
GWH12AGC-S3DTA1C/I	
GWH12AGCXD-S3DTA2C/I	
GWC12AGCXD-S3DTA2C/I

33
34
35

1
2
3
4
5
6
7
8
9

The component picture is only for reference; please refer to the actual product.

76
Installation and Maintenance

36

13

12

ON/OFF

TURBO

MODE

FAN

I FEEL
T-ON  T-OFF

11

TEMP
CLOCK

LIGHT
WiFi
SLEEP

10

14

16

15

17

18

19

20

24

25

21

26

22

27

23

28
29
30
32

31

Sayfa 80

NO.
Description

1
Front Panel

2
Guide Louver (upper)

3
Guide Louver (lower)

4
Screw Cover

5
Front Case

6
Filter Sub-Assy

7
Helicoid Tongue

8
Air Louver(left)

9
Left Axile Bush

10
Rear Case assy

11
Ring of Bearing

12
O-Gasket sub-assy of Bearing

13
Evaporator Support

14
Wall Mounting Frame

15
Evaporator Assy

16
Cross Flow Fan

17
Motor Press Plate

18
Fan Motor

Some models may not contain some parts,  please refer to the actual product.

77
Installation and Maintenance

NO.
Description

19
Connecting pipe clamp

20
Drainage Hose

21
Stepping  Motor

22
Stepping  Motor

23
Crank

24
Air Louver(auto)

25
Sweeping connecting rod

26
Stepping  Motor

27
Air Louver(right)

28
Main Board

29
Electric Box Assy

30
Terminal Board

31
Electric Box Cover

32
Display Board

33
Power Cord

34
Connecting Cable

35
Connecting Cable

36
Remote Controller

Sayfa 81

GWC18AGD-S3DTA1A/I	 GWC18AGD-S3DTA2A/I	 GWH18AGD-S3DTA1A/I	 GWH18AGD-S3DTA2A/I

34

30
31
32
33

12

ON/OFF

11

TURBO

MODE

FAN

13

I FEEL
T-ON  T-OFF

TEMP
CLOCK

LIGHT
WiFi
SLEEP

14

10

9

15

8

7
6

16

5

17

4

18

3

37

19

2

23

25
24

26
35

1

21

36

22

27

28

29

The component picture is only for reference; please refer to the actual product.

78
Installation and Maintenance

20

Sayfa 82

NO.
Description

1
Front Panel

2
Front Case Assy

3
Guide Louver Sub-assy 1

4
Guide Louver Sub-assy 2

5
Plug Pin

6
Left Axile Bush

7
Rear Case

8
Cross Flow Fan

9
Ring of Bearing

10
O-Gasket sub-assy of Bearing

11
Evaporator Support

12
Evaporator Assy

13
Fan Motor

14
Motor Press Plate

15
Wall Mounting Frame Sub-assy

16
Electric Box Assy

17
Connecting pipe clamp

18
Rubber Plug (Water Tray)

19
Supporter

Some models may not contain some parts,  please refer to the actual product.

79
Installation and Maintenance

NO.
Description

20
Electric Box

21
Main Board

22
Jumper

23
Stepping Motor

24
Stepping Motor

25
Crank

26
Drainage Hose

27
Filter Sub-Assy

28
Screw Cover

29
Electric Box Cover

30
Remote Controller

31
Connecting Cable

32
Connecting Cable

33
Power Cord

34
Temperature Sensor

35
Plasmacluster Ion

36
Stepping Motor

37
Teminal Board

Sayfa 83

GWC24AGE-S3DTA1F/I	
GWC24AGE-S3DTA2F/I	
GWH24AGE-S3DTA1F/I	
GWH24AGE-S3DTA2F/I	
GWC30AGEXH-S3DTA1A/I	 GWC30AGEXH-S3DTA2A/I	 GWC30AGEXH-S3DTA1C/I	 GWH30AGEXH-S3DTA1A/I	
GWH30AGEXH-S3DTA2A/I

40
41
42
43

1
2
3
4

The component picture is only for reference; please refer to the actual product.

80
Installation and Maintenance

17

16

18

ON/OFF

15

TURBO

MODE

FAN

I FEEL
T-ON  T-OFF

TEMP
CLOCK

LIGHT
WiFi
SLEEP

14

13

19

12

11

10

9

20

8

21

22

6
5

7

23

24

25

28

26

27
29

30

31

32

33

34

36
37
39
35
38

Sayfa 84

NO.
Description

1
Front Panel

2
Filter Sub-Assy

3
Screw Cover

4
Front Case

5
Plug Pin

6
Guide Louver Sub-assy 1

7
Guide Louver Sub-assy 2

8
Sweeping Connecting Rod

9
Air Louver(Automatic)

10
Helicoid Tongue

11
Left Axile Bush

12
Rear Case

13
Drainage Hose

14
Cross Flow Fan

15
O-Gasket sub-assy of Bearing

16
Ring of Bearing

17
Evaporator Support

18
Evaporator Assy

19
Wall Mounting Frame

20
Motor Press Plate

21
Fan Motor

22
Plasmacluster Ion

Some models may not contain some parts,  please refer to the actual product.

81
Installation and Maintenance

NO.
Description

23
Connecting pipe clamp

24
Rubber Plug (Water Tray)

25
Crank

26
Stepping  Motor

27
Stepping  Motor

28
Stepping  Motor

29
Sweep Blade

30
Air Louver(Automatic)

31
Electric Box

32
Display Board

33
Main Board

34
Jumper

35
Supporter

36
Terminal Board

37
Cable Clamp 

38
Electric Box Assy

39
Electric Box Cover

40
Connecting Cable

41
Power Cord

42
Temperature Sensor

43
Remote Controller

Sayfa 85

GWC36QF-S3DTB4A/I    GWH36QF-S3DTB4A/I

49

24

47
48
1
46

45

23

21
22

ON/OFF

TURBO

MODE

FAN

19
20

I FEEL
T-ON  T-OFF

TEMP
CLOCK

LIGHT
WiFi
SLEEP

18

17

14
16

15

1213

1011

25

9

8

26

5
6 7

27

4

28
29

3

2

30

31

32

37

33

35
34

38

36

40

39

41

44

43

42

The component picture is only for reference; please refer to the actual product.

82
Installation and Maintenance

Sayfa 86

NO.
Description

1
Detecting Plate

2
Front Panel

3
Stand Bar

4
Filter Sub-Assy

5
Front Case Sub-assy

6
Lower Guide Louver

7
Upper Guide Louver

8
Axile Bush

9
Air Louver 1

10
Air Louver 2

11
Connecting Rod

12
Louver Clamp

13
SteppingMotor

14
Water Tray

15
Water Tray Sub-Assy

16
Screw Cover

17
Rubber Plug (Water Tray)

18
Rear Case Sub-Assy

19
Cross Flow Fan 1

20
Bearing Holder Sub-assy

21
Cross Flow Fan 2

22
O-Gasket of Cross Fan Bearing

23
Left Evaporator Support

24
Evaporator Assy

25
Wall Mounting Frame

Some models may not contain some parts,  please refer to the actual product.

83
Installation and Maintenance

NO.
Description

26
Fan Motor

27
Pipe Clamp

28
Drainage Hose

29
Cover Plate

30
Motor Fixed Clip 1

31
SteppingMotor

32
Press Plate(Crank)

33
Crank-guide

34
Upper Crank

35
Lower crank

36
SteppingMotor

37
Electric Box Assy

38
Electric Box

39
Terminal Board

40
Jumper

41
Main Board

42
Display Board

43
Electric Box Cover 2

44
Electric Box Cover

45
Remote Controller

46
Connecting Cable

47
Temperature Sensor

48
Temperature Sensor

49
Cold Plasma Generator

Sayfa 87

10.2 Outdoor Unit

GWC12AGC-S3DTA1C/O

1

12
2
4
5
6

14

3

7

8

9
10

11

13

30
33
25

32

31
24

29
26

28

27

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Grill
16
Inhalation Tube Sub-assy

2
Front Panel
17
Discharge Tube Sub-assy

3
Axial Flow Fan
18
Flash Vaporizer Assy

4
Chassis Sub-assy
19
Clapboard Assy

5
Compressor and Fittings
20
Motor Support

6
Electronic Expansion Valve
21
Motor

7
Electric Expand Valve Fitting
22
Top Cover Assy

8
Right Side Plate
23
Left Side Plate

9
Valve Support
24
Condenser Left Border Plate

10
Cut off Valve
25
Electric Box Assy

11
Cut off Valve
26
Radiator

12
Valve Cover
27
Electric Box

13
Handle
28
Main Board

14
Terminal Board
29
Electric Box Cover

15
4-Way Valve Assy

Some models may not contain some parts, please refer to the actual product.

84
Installation and Maintenance

15

16

17

18

19

20

21

22

23

Sayfa 88

GWH12AGC-S3DTA1C/O

1

13
8
2
4
5
6

3

7

9

10
11

12

14

30
33
25

32

31
24

29
26

28

27

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Electric Box Assy
18
Electric Expansion Valve Sub-Assy

2
Radiator
19
4-Way Valve Assy

3
Electric Box
20
Right Side Plate

4
Main Board
21
Earthing Plate Sub-assy

5
Electric Box Cover
22
Handle (Right)

6
Terminal Board
23
Cut-off valve 1/4(N)

7
Left Side Plate
24
Valve Cover

8
Drainage Joint
25
Cut-off valve 3/8(N)

9
Clapboard
26
Silencer

10
Motor Support
27
Valve Support

11
Top Cover Assy
28
Compressor and Fittings

12
Condenser Assy
29
Chassis Sub-assy

13
Sponge(Condenser)
30
Brushless DC Motor

14
Rear Grill
31
Axial Flow Fan

15
Temp Sensor Sleeving
32
Cabinet

16
Sensor Insert
33
Front Grill

17
Flash Vaporizer Assy

Some models may not contain some parts, please refer to the actual product.

85
Installation and Maintenance

15

16

17

18

19

20

21

22

23

Sayfa 89

GWC18AGD-S3DTA1A/O   GWC24AGE-S3DTA1F/O

19
20
21
22
23
24
25

26

27

28

29

1
2
3
4
5
6
8
9 10 11

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Electric Box Assy
18
Inhalation Tube

2
Radiator
19
Electric Expansion Valve Sub-Assy

3
Electric Box
20
Right Side Plate

4
Main Board
21
Earthing Plate Sub-assy

5
Controller Cover
22
Handle (Right)

6
Terminal Board
23
Cut-off valve 1/4(N)

7
Left Side Plate
24
Valve Cover

8
Clapboard
25
Cut-off valve 3/8(N)

9
Motor Support
26
Silencer

10
Top Cover Assy
27
Valve Support

11
Condenser Assy
28
Compressor and Fittings

12
Sponge(Condenser)
29
Chassis Sub-assy

13
Rear Grill
30
Brushless DC Motor

14
Discharge Tube
31
Axial Flow Fan

15
Temp Sensor Sleeving
32
Cabinet

16
Sensor Insert
33
Front Grill

17
Flash Vaporizer Assy

Some models may not contain some parts, please refer to the actual product.

86
Installation and Maintenance

18

17
16

15

14

13

12

7

Sayfa 90

GWH18AGD-S3DTA1A/I   GWH24AGE-S3DTA1F/O

18
19
20
21
22
23
24

25

26

27

28

1
2
3
4
5
6
8
9 10 11

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Grill
15
4-Way Valve Assy

2
Front Panel
16
Condenser Assy

3
Axial Flow Fan
17
Flash Vaporizer Assy

4
Chassis Sub-assy
18
Clapboard Assy

5
Compressor and Fittings
19
Motor Support

6
Electronic Expansion Valve
20
Motor

7
Electric Expand Valve Fitting
21
Top Cover Assy

8
Right Side Plate
22
Left Side Plate

9
Valve Support
23
Condenser Left Border Plate

10
Cut off Valve
24
Electric Box Assy

11
Cut off Valve
25
Radiator

12
Valve Cover
26
Electric Box

13
Handle
27
Main Board

14
Terminal Board
28
Electric Box Cover

Some models may not contain some parts, please refer to the actual product.

87
Installation and Maintenance

17

16

15

14

13

12

7

Sayfa 91

GWC30AGEXH-S3DTA1A/O	
GWC30AGEXH-S3DTA1C/O

26
27
29
30
31
33
32
34
24

25
23
28
22

1
2
3
4
5
6
7
8
9
10
11
12
13

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Front Grill
18
Union Nut

2
Cabinet
19
Handle

3
Axial Flow Fan
20
Support

4
Brushless DC Motor
21
Valve Support Baffle

5
Chassis Sub-assy
22
Rear Grill

6
Cushioned Nut
23
Exhaust pipe Sub-assy

7
Clap Board Assy
24
Electronic Expansion Valve assy

8
Compressor and fittings
25
Electric Expand Valve Fitting

9
Inspiration tube Sub-assy
26
Condenser Assy

10
Right Side Plate Assy
27
Flash Vaporizer Assy

11
Valve Support Sub
28
Electric Box  Cover

12
Cut-off Valve
29
Main Board

13
Back Cover Nut
30
Electric box

14
Cut-off Valve
31
Top Cover-assy

15
Back Cover Nut
32
Motherboard radiator

16
Valve Cover
33
Motor Support Sub-Assy

17
Union Nut
34
Left Side Plate

Some models may not contain some parts, please refer to the actual product.

88
Installation and Maintenance

21

20

19

18

17

16

15

14

Sayfa 92

GWH30AGEXH-S3DTA1A/O

27
28
30
31
32
34
33
35
25

26
24
29

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Front Grill
19
Union Nut

2
Cabinet
20
Union Nut

3
Axial Flow Fan
21
Handle

4
Brushless DC Motor
22
Support

5
Chassis Sub-assy
23
Valve Support Baffle

6
Drainage Plug
24
Rear Grill

7
Drainage Connecter
25
Electronic Expansion Valve assy

8
Cushioned Nut
26
Electric Expand Valve Fitting

9
Clap Board Assy
27
Condenser Assy
10
Compressor and fittings
28
Flash Vaporizer Assy
11
4-way Valve Assy
29
Electric Box  Cover

12
Right Side Plate Assy
30
Main Board

13
Valve Support Sub
31
Electric box

14
Cut-off Valve
32
Top Cover-assy

15
Back Cover Nut
33
Motherboard radiator

16
Cut-off Valve
34
Motor Support Sub-Assy

17
Back Cover Nut
35
Left Side Plate

18
Valve Cover

Some models may not contain some parts, please refer to the actual product.

89
Installation and Maintenance

23

22

21

20

19

18

17

16

Sayfa 93

GWC36QF-S3DTB4A/O

29
30
32
33
34
36
35
37
27

28
26
31
25

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Front Grill
20
Union Nut

2
Cabinet
21
Handle

3
Axial Flow Fan
22
Supporter

4
Brushless DC Motor
23
Valve Support Block

5
Chassis Sub-assy
24
Flash Vaporizer Assy

6
Drainage hole Cap
25
Exhaust pipe Sub-assy

7
Drainage Joint
26
Rear Grill

8
Cushioned Nut
27
Capillary Sub-assy

9
Clap Board Assy
28
Temperature Sensor

10
Compressor and Fittings
29
Condenser Assy

11
Inspiration tube Sub-assy
30
Electric Box  Cover

12
Right Side Plate Assy
31
Tube Clip

13
Valve Support Sub
32
Main Board

14
Cut-off Valve
33
Electric box

15
Back Cover Nut
34
Top Cover-assy

16
Cut-off valve 1/4(N)
35
Motherboard radiator

17
Back Cover Nut
36
Motor Support Sub-Assy

18
Valve Cover
37
Left Side Plate

19
Union Nut

Some models may not contain some parts, please refer to the actual product.

90
Installation and Maintenance

24

23

22

21

20

19

18

17

16

Sayfa 94

GWH36QF-S3DTB4A/O

28
29
31
32
33
35
34
36
26

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

The component is only for rererence;please refer to the actual product

NO.
Description
NO.
Description

1
Front Grill
19
Union Nut

2
Cabinet
20
Union Nut

3
Axial Flow Fan
21
Handle

4
Brushless DC Motor
22
Supporter

5
Chassis Sub-assy
23
Valve Support Block

6
Drainage hole Cap
24
Flash Vaporizer Assy

7
Drainage Joint
25
Rear Grill

8
Cushioned Nut
26
Capillary Sub-assy

9
Clap Board Assy
27
Temperature Sensor
10
Compressor and Fittings
28
Condenser Assy
11
4-Way Valve Assy
29
Electric Box  Cover

12
Right Side Plate Assy
30
Tube Clip

13
Valve Support Sub
31
Main Board

14
Cut-off Valve
32
Electric box

15
Back Cover Nut
33
Top Cover-assy

16
Cut-off valve 1/4(N)
34
Motherboard radiator

17
Back Cover Nut
35
Motor Support Sub-Assy

18
Valve Cover
36
Left Side Plate

Some models may not contain some parts, please refer to the actual product.

91
Installation and Maintenance

30

27

25

24

23

22

21

20

19

18

17

16

Sayfa 95

11. Removal Procedure

11.1 Removal Procedure of Indoor Unit
Caution: discharge the refrigerant 
completely before removal.

12-30K 

Step
Procedure

    1.Remove filter

a
Open the panel.

b
Loosen the clasp shown in the fig and then pull the left 

filter and right filer outwards to remove them.

   2.Remove horizontal louver

Push out the axile bush on horizontal louver. Bend 

the horizontal louver with hand and then separate the 

horizontal louver from the crankshaft of step motor to 

remove it.

92
Installation and Maintenance

Panel

Clasps

Left filter and right filer

Horizontal louver

Location of step motor

Axile bush

Sayfa 96

Step
Procedure

    3.Remove panel

Open the front panel; separate the panel rotation shaft 

from the groove fixing the front panel and then removes 

the front panel.

Note:

The display of some models is fixed on the panel; 

unscrew the screws fixing the display on the panel 

before removing the panel.

   4.Remove electric box cover 2

Remove the screws on the electric box cover 2 to 

remove the electric box cover 2.

    5.Remove front case sub-assy

Remove the screws fixing front case.

Note:

a

(1) Open the screw caps before removing the screws 

around the air outlet.

(2) The quantity of screws fixing the front case sub-

assy is different for different models.

b

Loosen the clasps at left, middle and right sides of front 

case. Lift the front case sub-assy upwards to remove it.

93
Installation and Maintenance

Panel

Display

Front panel

Panel rotation

Groove

Screw

Front case subassy

Electric box cover 2

Screw

Front case sub-assy

Screw

Screw caps

Front case 
sub-assy

Right clasp
Middle clasp
Left clasp

Sayfa 97

Step
Procedure

     6.Remove electric box assy

Remove the screw fixing electric box assy.

a

①Cut off the wire binder and pull out the
indoor tube temperature sensor.
②Screw off one grounding screw.
③Remove the wiring terminals of motor, cold plasma 
generator and stepping motor.
④Remove the electric box assy.
⑤Screw off the screws that are locking each.

b

Rotate the electric box assy. Twist off the screws that 
are locking the wire clip and loosen the power cord. 
Remove the wiring terminal of power cord. Lift up the 
main board and take it off.

Instruction:Some wiring terminal of this products is with 

C

lock catch and other devices.The pulling method is as 

below:

1.Remove the soft sheath for some terminals at first, 

hold the circlip and then pull out the terminals,

2.Pull out the holder for some terminals at first(holder 

is not available for some wiring terminal).hold the 

connector and then pull the terminal.

94
Installation and Maintenance

electric box

Step motor
clasps

Indoor tube
temperature sensor
Electric box assy

Grounding 
screw

Main board

Wiring terminal 
 of motor

Wiring terminal 
 of stepping motor

Wire binder

Screw

Screw

Power cord

Wire clip

Circlip

Holder

Connector
Soft sheath

Sayfa 98

Step
Procedure 

   7.Remove evaporator assy

Remove 3 screws fixing evaporator assy.

a

At the back of the unit, Loosen the clasp,connection 

b

pipe clamp and then remove the connection pipe 

clamp.

First remove the left side of evaporator from the groove 

c

of bottom shell and then remove the right side from the 

clasp on the bottom shell.

Adjust the position of connection pipe on evaporator 

d

slightly and then lift the evaporator upwards to remove 

it.

95
Installation and Maintenance

Screw

Connection pipe clamp

Clasp

Groove
Rear Case assy

Evaporator assy

Connection pipe

Sayfa 99

Step
Procedure

   8.Remove motor and cross flow blade

Remove 3 screws fixing motor clamp and then remove 
the motor clamp.

a

Remove the at the connection place of cross flow blade 
and motor; lift the motor and cross flow blade upwards 
to remove them.

b

   9.Remove vertical louver

Loosen the connection clasps between vertical louver 

and bottom case to remove vertical louver.

96
Installation and Maintenance

Motor clasp

Screws

Motor
Cross flow

Vertical louver

Clasps

Clasps

Sayfa 100

36K 

Step
Procedure

    1.Remove filter

Open the pane,Push up and pull down the filter

   2.Remove panel

Remove screws fixing display, and then remove

the display.

Separate the panel rotation shaft from the groove 

fixing the front panel and then removes the front 

panel.

    3.Remove horizontal louver

Bend the horizontal louver with hand and 

then separate the horizontal louver from the 

crankshaft of step motor to remove it.

97
Installation and Maintenance

Caution: discharge the refrigerant 
completely before removal.

Panel

Left filter and right filer

Screws

Panel rotation

Horizontal louver

Sayfa 101

Step
Procedure

    3.Remove electric box cover 2

Remove the screws on the electric box cover 2 

to remove the electric box cover 2.

    4.Remove front case sub-assy

a

Open the screw caps on front case.

b

Remove the screws fixing front case.

c

Loosen the clasps of front case. Lift the front 

case sub-assy upwards to remove it.

    5.Remove electric box cover

Remove the screw fixing electric box cover to 

remove the electric box cover.

98
Installation and Maintenance

Electric box cover 2

Screw

Screws

Screw caps

Clasp
Front case sub-assy

Screw

Electric Box Cover

Sayfa 102

Step
Procedure

     6.Remove electric box assy

Remove the screw fixing electric box assy.

a

①Cut off the wire binder and pull out the
indoor tube temperature sensor.
②Screw off one grounding screw.
③Remove the wiring terminals of motor, cold plasma 
generator and stepping motor.
④Remove the electric box assy.
⑤Screw off the screws that are locking each.

b

Instruction:Some wiring terminal of this products is with 

lock catch and other devices.The pulling method is as 

below:

1.Remove the soft sheath for some terminals at first, 

hold the circlip and then pull out the terminals,

2.Pull out the holder for some terminals at first(holder 

is not available for some wiring terminal).hold the 

connector and then pull the terminal.

99
Installation and Maintenance

Electric box assy

Screws

Cold Plasma Generator

Grounding screws

Main board

Wiring terminal 
 of stepping motor

Indoor room
temperature sensor

Indoor tube
temperature sensor

Circlip

Holder

Connector
Soft sheath

Sayfa 103

Step
Procedure 

   7.Remove water tray sub-assy

Pull the water tray upwards, and then remove the 

water tray.

   8.Remove evaporator assy

a
Remove two screws on pipe clamp, and then 

remove the pipe clamp.

Remove two screws on cover plate, and then 

remove the cover plate.

Remove the screws fixing left and right 

b

evaporator support, then slightly adjust the 

pipeline. 

c

Extract the evaporator up.

100
Installation and Maintenance

Connection pipe clamp

Cover Plate

Screws

Screws

Evaporator assy

Connection pipe

Sayfa 104

Step
Procedure

   8.Remove motor and cross flow fan

Remove the screws fixing motor fixed clip 2 and then 
remove the motor fixed clip 2.

a

Remove the screw on the motor shaft and pull out the 
motor.
Remove the screw fixing cross flow fan, leave out of 
the cross flow fans.

b

101
Installation and Maintenance

Motor Fixed Clip 2

Screws

Screw
Motor
Cross flow fan

Screw

Sayfa 105

11.2 Removal Procedure of Outdoor Unit

12K :Take the heat pump for example

Step
Procedure

    1. Before disassembly

   2. Remove top cover

Remove the screws fixing top cover and then remove 
the top cover.

    3. Remove big handle and valve cover

Remove the screws fixing big handle, valve cover and 
then remove them.

102
Installation and Maintenance

Caution: discharge the refrigerant 
completely before removal.

top cover

big handle

valve cover

Sayfa 106

Step
Procedure

    4. Remove front panel assy

Remove connection screws connecting the front panel 
assy with the chassis and the motor support, and then 
remove the front panel assy.

   5. Remove rear grill

Remove the screws connecing the left side plate and 
right side plate and then remove rear grill.

   6. Remove right side plate assy

Rescrew the ground screws, remove the ground wires, 
loosen the screws fixing terminal board, remove the 
terminal board, rescrew the screws fixing the right 
plate, and remove the right side plate assy.

103
Installation and Maintenance

Front Panel Assy

Rear Grill

Right Side 
Plate Assy

Sayfa 107

Step
Procedure

    7. Remove valve suppprt

Remove the valve support bolck, remove the screws 
fixing valve support, remove the screws fixing the liquid 
valve and gas valve  then remove the valve support.

    8. Remove gas valve and liquid valve

Unsolder the welding joint connecting the gas valve 
and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; 
when unsoldering, wrap the gas valve with a wet cloth 
completely to avoid damage to the valve caused by 
high temperature.

    9. Remove electric box assy

Remove the terminals, lift up and rotate the electrical
box assy to the right so that the snaps on the clapboard
are removed and the electrical box assy are removed.

104
Installation and Maintenance

valve supprt

Valve Support Block

welding joint

liquid valve

gas valve

Electric Box Assy

Sayfa 108

Step
Procedure

    10. Remove 4-way valve assy

Unsolder the welding joints connecting the 4-way valve 
assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way 
valve with a wet cloth completely to avoid damage to 
the valve caused by high temperature.

  11. Remove electronic expansion valve

Rotate to remove the electronic expansion valve fitting.
Unsolder the welding joint connecting the electronic 
expansion Valve and then remove the electronic 
expansion valve.

  12. Remove flash vaporizer assy

Remove the screws fixing the tube clip of flash 
vaporizer assy, unsolder the welding joint connecting 
the flash vaporizer assy and remove the flash vaporizer 
assy.

105
Installation and Maintenance

4-way valve assy

electric expand 
valve fitting

electric expansion 
valve sub-Assy

welding joint

Flash Vaporizer Assy

welding joint

Tube Clip

Sayfa 109

Step
Procedure

    13. Remove axial flow fan

Remove the nut on the fan and then remove the axial 
flow fan.

   14. Remove motor

Remove the screws fixing the motor and then remove 
the motor.

    15. Remove motor support

Remove the screws fixing the motor support and lift the 
motor support to remove it.

106
Installation and Maintenance

axial flow fan

motor

motor support

Sayfa 110

Step
Procedure 

     16. Remove clapboard assy

Remove the screws fixing the clapboard assy and then 
remove the clapboard assy.

     17. Remove compressor

Remove the 3 foot nuts on the compressor and then 
remove the compressor.

107
Installation and Maintenance

clapboard assy

compressor

Sayfa 111

18K/24K :Take the heat pump for example

Step
Procedure

    1. Before disassembly

   2. Remove top cover

Remove the screws fixing top cover and then remove 
the top cover.

    3. Remove big handle and valve cover

Remove the screws fixing big handle, valve cover and 
then remove them.

108
Installation and Maintenance

Caution: discharge the refrigerant 
completely before removal.

top cover

big handle

valve cover

Sayfa 112

Step
Procedure

    4. Remove front panel assy

Remove connection screws connecting the front panel 
assy with the chassis and the motor support, and then 
remove the front panel assy.

   5. Remove rear grill

Remove the screws connecing the left side plate and 
right side plate and then remove rear grill.

   6. Remove right side plate assy

Rescrew the ground screws, remove the ground wires, 
loosen the screws fixing terminal board, remove the 
terminal board, rescrew the screws fixing the right 
plate, and remove the right side plate assy.

109
Installation and Maintenance

Front Panel Assy

Rear Grill

Right Side 
Plate Assy

Sayfa 113

Step
Procedure

    7. Remove valve suppprt

Remove the valve support bolck, remove the screws 
fixing valve support, remove the screws fixing the liquid 
valve and gas valve  then remove the valve support.

    8. Remove gas valve and liquid valve

Unsolder the welding joint connecting the gas valve 
and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; 
when unsoldering, wrap the gas valve with a wet cloth 
completely to avoid damage to the valve caused by 
high temperature.

    9. Remove electric box assy

Remove the terminals, lift up and rotate the electrical
box assy to the right so that the snaps on the clapboard
are removed and the electrical box assy are removed.

110
Installation and Maintenance

valve supprt

Valve Support Block

welding joint

liquid valve

gas valve

Electric Box Assy

Sayfa 114

Step
Procedure

    10. Remove 4-way valve assy

Unsolder the welding joints connecting the 4-way valve 
assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way 
valve with a wet cloth completely to avoid damage to 
the valve caused by high temperature.

  11. Remove electronic expansion valve

Rotate to remove the electronic expansion valve fitting.
Unsolder the welding joint connecting the electronic 
expansion Valve and then remove the electronic 
expansion valve.

  12. Remove flash vaporizer assy

Remove the screws fixing the tube clip of flash 
vaporizer assy, unsolder the welding joint connecting 
the flash vaporizer assy and remove the flash vaporizer 
assy.

111
Installation and Maintenance

4-way valve assy

electric expand 
valve fitting

electric expansion 
valve sub-Assy

welding joint

Flash Vaporizer Assy

Tube Clip

welding joint

Sayfa 115

Step
Procedure

    13. Remove axial flow fan

Remove the nut on the fan and then remove the axial 
flow fan.

   14. Remove motor

Remove the screws fixing the motor and then remove 
the motor.

    15. Remove motor support

Remove the screws fixing the motor support and lift the 
motor support to remove it.

112
Installation and Maintenance

axial flow fan

motor

motor support

Sayfa 116

Step
Procedure 

     16. Remove clapboard assy

Remove the screws fixing the clapboard assy and then 
remove the clapboard assy.

     17. Remove compressor

Remove the 3 foot nuts on the compressor and then 
remove the compressor.

113
Installation and Maintenance

clapboard assy

compressor

Sayfa 117

30K/36K :Take the heat pump for example

Step
Procedure

    1. Before disassembly

   2. Remove top cover

Remove the screws fixing top cover and then remove 
the top cover.

    3. Remove big handle and valve cover

Remove the screws fixing big handle, valve cover and 
then remove them.

114
Installation and Maintenance

Caution: discharge the refrigerant 
completely before removal.

top cover

big handle

valve cover

Sayfa 118

Step
Procedure

    4. Remove front panel assy

Remove connection screws connecting the front panel 
assy with the chassis and the motor support, and then 
remove the front panel assy.

   5. Remove rear grill

Remove the screws connecing the left side plate and 
right side plate and then remove rear grill.

   6. Remove right side plate assy

Rescrew the ground screws, remove the ground wires, 
loosen the screws fixing terminal board, remove the 
terminal board, rescrew the screws fixing the right 
plate, and remove the right side plate assy.

115
Installation and Maintenance

Front Panel Assy

Rear Grill

Right Side 
Plate Assy

Sayfa 119

Step
Procedure

    7. Remove valve suppprt

Remove the valve support bolck, remove the screws 
fixing valve support, remove the screws fixing the liquid 
valve and gas valve  then remove the valve support.

    8. Remove gas valve and liquid valve

Unsolder the welding joint connecting the gas valve 
and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; 
when unsoldering, wrap the gas valve with a wet cloth 
completely to avoid damage to the valve caused by 
high temperature.

    9. Remove electric box assy

Remove the terminals, lift up and rotate the electrical
box assy to the right so that the snaps on the clapboard
are removed and the electrical box assy are removed.

116
Installation and Maintenance

valve supprt

Valve Support Block

welding joint

liquid valve

gas valve

Electric Box Assy

Sayfa 120

Step
Procedure

    10. Remove 4-way valve assy

Unsolder the welding joints connecting the 4-way valve 
assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way 
valve with a wet cloth completely to avoid damage to 
the valve caused by high temperature.

  11. Remove Capillary Sub-assy

Unsolder the welding joint connecting the capillary 
subassy and then remove the capillary sub-assy.

  12. Remove flash vaporizer assy

Remove the screws fixing the tube clip of flash 
vaporizer assy, unsolder the welding joint connecting 
the flash vaporizer assy and remove the flash vaporizer 
assy.

117
Installation and Maintenance

4-way valve assy

Capillary Sub-assy

welding joint

Flash Vaporizer Assy

Tube Clip

welding joint

Sayfa 121

Step
Procedure

    13. Remove axial flow fan

Remove the nut on the fan and then remove the axial 
flow fan.

   14. Remove motor

Remove the screws fixing the motor and then remove 
the motor.

    15. Remove motor support

Remove the screws fixing the motor support and lift the 
motor support to remove it.

118
Installation and Maintenance

axial flow fan

motor

motor support

Sayfa 122

Step
Procedure 

     16. Remove clapboard assy

Remove the screws fixing the clapboard assy and then 
remove the clapboard assy.

     17. Remove compressor

Remove the 3 foot nuts on the compressor and then 
remove the compressor.

119
Installation and Maintenance

clapboard assy

compressor

Sayfa 123

Appendix

Appendix 1: Reference Sheet of Celsius and Fahrenheit

Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32

Set temperature

 Fahrenheit display 
temperature(℉)

Fahrenheit

Celsius

 Fahrenheit display 
temperature(℉)

Fahrenheit

Celsius

 Fahrenheit display 
temperature(℉)

Fahrenheit

Celsius

(℉)

(℃)

(℉)

(℃)

(℉)

(℃)

61
60.8
16
69/70
69.8
21
78/79
78.8
26

62/63
62.6
17
71/72
71.6
22
80/81
80.6
27

64/65
64.4
18
73/74
73.4
23
82/83
82.4
28

66/67
66.2
19
75/76
75.2
24
84/85
84.2
29

68
68
20
77
77
25
86
86
30

Ambient temperature

 Fahrenheit display 
temperature(℉)

Fahrenheit

Celsius

 Fahrenheit display 
temperature(℉)

Fahrenheit

Celsius

 Fahrenheit display 
temperature(℉)

Fahrenheit

Celsius

( ℉)

(℃)

(℉)

(℃)

(℉)

(℃)

32/33
32
0
55/56
55.4
13
79/80
78.8
26

34/35
33.8
1
57/58
57.2
14
81
80.6
27

36
35.6
2
59/60
59
15
82/83
82.4
28

37/38
37.4
3
61/62
60.8
16
84/85
84.2
29

39/40
39.2
4
63
62.6
17
86/87
86
30

41/42
41
5
64/65
64.4
18
88/89
87.8
31

43/44
42.8
6
66/67
66.2
19
90
89.6
32

45
44.6
7
68/69
68
20
91/92
91.4
33

46/47
46.4
8
70/71
69.8
21
93/94
93.2
34

48/49
48.2
9
72
71.6
22
95/96
95
35

50/51
50
10
73/74
73.4
23
97/98
96.8
36

52/53
51.8
11
75/76
75.2
24
99
98.6
37

54
53.6
12
77/78
77
25

Appendix 2: Configuration of Connection Pipe

1. Standard length of connection pipe (More details please refer to the specifications.)

2. Min length of connection pipe for the unit with standard connection pipe of 5m,  there is no limitation for themin length of connection 
pipe. For the unit with  standard connection pipe of 7.5m and 8m, the min length of connection pipe is 3m.

3. Max. length of connection pipe and max. high difference. (More details please refer to the specifications.)

4. The additional refrigerant oil and refrigerant charging required after prolonging connection pipe

● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each 
additional 5m of connection pipe.

● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):

● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant 
charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.

● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter.

Additional refrigerant charging amount for R410A

Diameter of connection pipe
Outdoor unit throttle

Liquid pipe
Gas pipe
Cooling only(g/m)
Cooling and heating(g/m)

1/4”
3/8” or 1/2”
15
20

1/4” or 3/8”
5/8” or 3/4”
15
50

1/2”
3/4” or 7/8”
30
120

5/8”
1" or 1 1/4”
60
120

3/4''
/
250
250

7/8''
/
350
350

120
Installation and Maintenance

Sayfa 124

Appendix

Appendix 3: Pipe Expanding Method

Note:

Improper pipe expanding is the main cause of refrigerant leakage.Please expand 

the pipe according to the following steps:

A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.

B:Remove the burrs
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.

C:Put on suitable insulating pipe.

D:Put on the union nut

● Remove the union nut on the indoor connection pipe and outdoor valve; install

the union nut on the pipe.

E:Expand the port
● Expand the port with expander.

Note:

● "A" is different according to the diameter, please refer to the sheet below:

Outer diameter(mm)
A(mm)
Max
Min
Ф6 - 6.35 (1/4")
1.3
0.7
Ф9 - Ф9.52 (3/8”)
1.6
1.0
Ф12 - 12.70 (1/2”)
1.8
1.0
Ф16 - 15.88 (5/8”)
2.4
2.2

F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the port 
again according to the steps above.

121
Installation and Maintenance

Pipe

Pipe cutter

Leaning
Uneven
Burr

Pipe

Shaper

Downwards

Union pipe

Pipe

Hard
mold

Expander

Pipe

Smooth surface

Improper expanding

leaning
damaged

crack
uneven
thickness

surface

The length is equal

Sayfa 125

Appendix

Appendix 4: List of Resistance for Temperature Sensor

Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K)

oC)
Resistance(kΩ)
Temp(

Temp(

-19
138.10 
0
49.02 
20
18.75 
40
7.97 

-18
128.60 
2
44.31 
22
17.14 
42
7.35 

-16
115.00 
4
40.09 
24
15.68 
44
6.79 

-14
102.90 
6
36.32 
26
14.36 
46
6.28 

-12
92.22 
8
32.94 
28
13.16 
48
5.81 

-10
82.75 
10
29.90 
30
12.07 
50
5.38 

-8
74.35 
12
27.18 
32
11.09 
52
4.99 

-6
66.88 
14
24.73 
34
10.20 
54
4.63 

-4
60.23 
16
22.53 
36
9.38 
56
4.29 

-2
54.31 
18
20.54 
38
8.64 
58
3.99 

Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)

oC)
Resistance(kΩ)
Temp(

Temp(

-19
181.40 
20
25.01 
60
4.95 
100
1.35 

-15
145.00 
25
20.00 
65
4.14 
105
1.16 

-10
110.30 
30
16.10 
70
3.48 
110
1.01 

-5
84.61 
35
13.04 
75
2.94 
115
0.88 

0
65.37 
40
10.62 
80
2.50 
120
0.77 

5
50.87 
45
8.71 
85
2.13 
125
0.67 

10
39.87 
50
7.17 
90
1.82 
130
0.59 

15
31.47 
55
5.94 
95
1.56 
135
0.52 

Resistance Table of Discharge Temperature Sensor for Outdoor(50K)

Temp(

oC)
Resistance(kΩ)
Temp(

-30
911.400 
10
98
50
17.65
90
4.469

-25
660.8
15
77.35
55
14.62
95
3.841

-20
486.5
20
61.48
60
12.17
100
3.315

-15
362.9
25
49.19
65
10.18
105
2.872

-10
274
30
39.61
70
8.555
110
2.498

-5
209
35
32.09
75
7.224
115
2.182

0
161
40
26.15
80
6.129
120
1.912

5
125.1
45
21.43
85
5.222
125
1.682

122
Installation and Maintenance

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)

Sayfa 126

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070
Tel: (+86-756) 8522219         
Fax: (+86-756) 8669426
E-mail: global@cn.gree.com

For product improvement, specifications and appearance in this manual are subject to change without prior notice.