gmv6-r32-indoor-units-service-manual

Bu sayfa, kılavuzun PDF dosyasındaki metnin tamamıdır (sayfa sayfa). Görseller ve çizimler için PDF'i açın. — sibastore.com

Sayfa 1

Multi Variable Air Conditioners  
Indoor Units 

(GC202506-II) 
Capacity: 5800Btu/h~60000Btu/h 
Rated Frequency: 60Hz 
Refrigerant Type: R32 

Sayfa 2

Thank you for choosing Gree air conditioners. In order to correctly install and use our units, and for 

the satisfactory operation effect, please read this manual carefully.  

This manual specifies safe operation requirements from perspectives of product introduction, control, 

troubleshooting and maintenance, as well as basic principles and implementation methods. Professional 

operators must abide by relevant national (local) safety requirements and technical specifications set 

forth in this manual during operations; otherwise, the air conditioning system may fail or be damaged, 

and personnel safety accident may also occur. 

 
Appliance filled with flammable gas R32. 

 
Before install the appliance, read the installation manual first. 

 
Before use the appliance, read the owner’s manual first. 

 
Before repair the appliance, read the service manual first. 

Foreword 

Sayfa 3

PRODUCT ........................................................................................................................... 4 

1 Product List ..................................................................................................................... 5 

1.1 High Static Pressure Duct Type Indoor Unit ....................................................................... 5 

1.2 Fresh Air Processing Duct Type Indoor Unit ...................................................................... 5 

1.3 High Pressure Air Handler Indoor Unit ................................................................................ 5 

1.4 360° Air Discharge Cassette Type Indoor Unit .................................................................... 6 

1.5 360°Air Discharge Compact Cassette Type Indoor Unit .................................................... 6 

1.6 1-way Cassette Type Indoor Unit ......................................................................................... 6 

1.7 Wall Mounted Type Indoor Unit ............................................................................................ 7 

2 Nomenclature .................................................................................................................. 8 

3 Specifications ................................................................................................................. 9 

3.1 High Static Pressure Duct Indoor Unit ................................................................................ 9 

3.2 Fresh Air Processing Indoor Unit ....................................................................................... 11 

3.3 Air Handler Indoor Unit ....................................................................................................... 12 

3.4 360°Air Discharge Cassette Indoor Unit ............................................................................ 14 

3.5 360°Air Discharge Compact Cassette Indoor Unit ........................................................... 17 

3.6 1-way Cassette Indoor Unit ................................................................................................ 18 

3.7 Wall Mounted Type Indoor Unit .......................................................................................... 19 

CONTROL ......................................................................................................................... 22 

1 Operation Flowchart ..................................................................................................... 23 

2 Wired Controller ............................................................................................................ 24 

2.1 Control Panel ....................................................................................................................... 24 

2.2 Installation and Removal .................................................................................................... 29 

3 Remote Controller ........................................................................................................ 32 

3.1 Remote Controller YAP1F ................................................................................................... 32 

4 Introduction to Unit Functions .................................................................................... 33 

4.1 Engineering Application Functions Operated through the XE7C-23/H Wired Controller
 ..................................................................................................................................................... 33 

4.2 Engineering Application Functions Operated through the YAP1F Remote Controller . 41 

INSTALLATION ................................................................................................................. 43 

1 Engineering Installation Preparation and Notice ....................................................... 44 

1.1 Installation Notice ................................................................................................................ 44 

1.2 Installation Key Points and Importance ............................................................................ 44 

2 Installation Materials Selection ................................................................................... 45 

2.1 Refrigerant Piping ............................................................................................................... 46 

2.2 Condensate Water Pipe ....................................................................................................... 46 

2.3 Insulation Material ............................................................................................................... 46 

CONTENTS 

Sayfa 4

2.4 Communication Cable and Control Cable ......................................................................... 47 

2.5 Power Cable ......................................................................................................................... 47 

2.6 Hanger Rod and Support .................................................................................................... 47 

3 Installation of Indoor Unit ............................................................................................ 48 

3.1Installation of High Static Pressure Duct Type Indoor Unit .............................................. 48 

3.2 Installation of Fresh Air Processing Indoor Unit .............................................................. 50 

3.3 Installation of Air Handler Type Indoor Unit ...................................................................... 51 

3.4 Installation of 360°Air Discharge Cassette Type Indoor Unit .......................................... 54 

3.5 Installation of 360°Air Discharge Compact Cassette Type Indoor Unit .......................... 56 

3.6 Installation of 1-way Cassette Type Indoor Unit ............................................................... 57 

3.7 Wall Mounted Type Indoor Unit .......................................................................................... 59 

4 Installation of Connection Pipe ................................................................................... 61 

4.1 Flaring Process .................................................................................................................... 61 

4.2 Pipe Bending ........................................................................................................................ 62 

4.3 Indoor Pipe Connection ...................................................................................................... 62 

5 Installation of Drain Pipe .............................................................................................. 63 

5.1 Precautions When Doing the Piping Work ........................................................................ 63 

5.2 Installing the Drain Pipes .................................................................................................... 64 

5.3 Precautions When Doing Riser Piping Work .................................................................... 66 

5.4 Testing of Drain Piping ....................................................................................................... 66 

6 Electrical Installation .................................................................................................... 66 

6.1 Locking Joint Installation of 360°Air Discharge Cassette Type Indoor Unit .................. 67 

6.2 Locking Joint Installation of 360°Air Discharge Compact Cassette Type Indoor Unit . 68 

MAINTENANCE ................................................................................................................ 69 

1 Malfunction List ............................................................................................................ 70 

1.1 Malfunction List for the Wired Controller .......................................................................... 70 

1.2 Display of Light Board (Only for Two-way Cassette Type Indoor Unit) .......................... 70 

1.3 Exception Analyzing and Troubleshooting ....................................................................... 71 

2 After-sales Emergency Masures .................................................................................. 83 

3 About the Refrigerant Leakage Sensor ....................................................................... 83 

4 Wiring Diagram ............................................................................................................. 85 

4.1 High Static Pressure Duct Type Indoor Unit ..................................................................... 85 

4.2 Fresh Air Processing Indoor Unit ...................................................................................... 86 

4.3 Air Handler Type Indoor Unit .............................................................................................. 86 

4.4 360°Air Discharge Casssette Type Indoor Unit ................................................................ 87 

4.5 360°Air Discharge Compact Casssette Type Indoor Unit ................................................ 87 

4.6 1-way Cassette Type Indoor Unit ....................................................................................... 88 

4.7 Wall Mounted Type Indoor Unit .......................................................................................... 88 

Sayfa 5

5 Disassembly and Assembly Procedure of Main Parts ............................................... 89 

5.1 High Static Pressure Duct Type Indoor Unit ..................................................................... 89 

5.2 Fresh Air Processing Indoor Unit ...................................................................................... 90 

5.3 Air Handler Type Indoor Unit .............................................................................................. 92 

5.4 360°Air Discharge Casssette Type Indoor Unit ................................................................ 98 

5.5 360°Air Discharge Compact Casssette Type Indoor Unit .............................................. 101 

5.6 1-way Cassette Type Indoor Unit ..................................................................................... 103 

5.7 Wall Mounted Type Indoor Unit ........................................................................................ 106 

6 Exploded Views and Part List .................................................................................... 108 

6.1 High Static Pressure Duct Type Indoor Unit ................................................................... 108 

6.2 Fresh Air Processing Type Indoor Unit ............................................................................ 112 

6.3 Air Handler Type Indoor Unit ............................................................................................. 114 

6.4 360°Air Discharge Casssette Type Indoor Unit ............................................................... 118 

6.5 360°Air Discharge Compact Casssette Type Indoor Unit .............................................. 122 

6.6 1-way Cassette Type Indoor Unit ..................................................................................... 124 

6.7 Wall Mounted Type Indoor Unit ........................................................................................ 126 

Sayfa 6

GREE                                                Multi Variable Air Conditioners Indoor Unit  

 PROHIBITED: 

(1)  Do not use means to accelerate the defrosting process or to clean, other than those recommended 

by the manufacturer. 

(2)  Do not pierce or burn. 

(3)  Please note that refrigerant may be odorless. 

(4)  The appliance shall be stored in a room without continuously operating ignition sources (For 

example: open flames, an operating gas appliance or an operating electric heater). 

(5)  Indoor unit adopts special joints that can’t be detached. The installation method is the same with 

the common joints. However, because the joint can’t be detached, if it is badly connected and 

causes leakage, it needs to be cut and replaced by a new one through welding. 

(6)  Using unsuitable parts or tools may lead to electric shock or fire hazard. 

(7)  If refrigerant leaks during maintenance, please ventilate the room immediately. Heavy leakage may 

lead to breathing difficulty, severe injury or death. 

(8)  Disconnect power before disassembling the appliance for maintenance. 

(9)  The appliance should be maintained and cared by authorized technical personnel with necessary 

qualifications. 

 WARNING: 

(1)  If the working place is more than 2m's high, please wear a safety helmet, gloves and a safety belt. 

(2)  Never mix any other substances except the specified refrigerant into the refrigerant circuit. 

(3)  When re-locating the appliance, check whether the new location is strong enough to withstand the 

weight of the appliance. 

(4)  If there is refrigerant leak, please fix the leak before charging in the refrigerant. After refrigerant is 

charged, check for refrigerant leaks. If you cannot spot the leak, stop the maintenance work. Please 

evacuate the system and close the service valve to prevent refrigerant leaking into the room. 

(5)  Prepare suitable tools and protectors. 

(6)  If you need to carry out maintenance or check the electric circuit without cutting off the power, 

please be careful not to touch the electrical parts. 

(7)  The appliance should be maintained and cared by authorized technical personnel with necessary 

qualifications. 

(8)  LEAK DETECTION SYSTEM installed. Unit must be powered except for service. 

(9)  Keep any required ventilation openings clear of obstruction. 

(10)  Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping. 

(11)  Protection devices, piping and fittings shall be protected as far as possible against adverse 

environmental effects, for example, the danger of water collecting and freezing in relief pipes or the 

accumulation of dirt and debris. 

(12)  Provision shall be made for expansion and contraction of long runs of piping. 

(13)  Piping in refrigerating systems shall be so designed and installed to minimize the likelihood 

hydraulic shock damaging the system. 

Safety Notice on Maintenance 

1 

Sayfa 7

GREE                                                Multi Variable Air Conditioners Indoor Unit  

(14)  Steel pipes and components shall be protected against corrosion with a rustproof coating before 

applying any insulation. 

(15)  Only auxiliary devices approved by the appliance manufacturer or declared suitable with the 

refrigerant shall be installed in connecting ductwork. 

 NOTICE: 

(1)  If the appliance is maintained at a humid place, it should be grounded to avoid electric shock. 

(2)  Never repair the unit with wet hands. Operating the unit with wet hands may lead to electric shock. 

(3)  If the unit is not correctly grounded, please check and fix it.  

(4)  Before cleaning the unit, please disconnect power to prevent the inner fan from starting up and 

running at high speed; Otherwise personal injury may occur. 

(5)  Measure the insulation resistance after maintenance. The resistance must be 1M or higher. Bad 

insulation may lead to electric shock. 

(6)  Welding and cutting work must be done in a well-ventilated place. 

(7)  Gas appliances, heaters and other fire sources should be kept away from the installation and 

maintenance site. 

(8)  Maintenance should be done according to suggestions of the manufacturer. 

(9)  Maintenance should be done only after the refrigerant is completely reclaimed from the unit. 

 OBSERVED: 

(1)  After the maintenance work is done, check the drainage of indoor unit. 

(2)  Do not tilt the unit, otherwise, water may spill out from the unit and make the floor and furniture wet. 

(3)  Disassembly of the unit, handling of the refrigerant, oil and accessories should all be done 

according to applicable local rules and regulations.  

2 

Sayfa 8

GREE                                                Multi Variable Air Conditioners Indoor Unit  

 PROHIBITED: 

(1)  Never try to modify the unit, otherwise, it may cause electric shock, overheat or fire hazard. 

(2)  If the power cord or conducting wires are scratched, please replace them. 

(3)  Never use connected or extended power cord or share the power socket with other appliances. 

(4)  Prepare a specialized power circuit for the appliance. 

 WARNING: 

(1)  If the power plug is dirty, please clean it before inserting it to the power socket. If the power plug is 

loose, please tighten it up. 

(2)  Do not damage the power cord. A damaged or refitted power cord may lead to electric shock or fire 

hazard. 

(3)  Check frequently whether the appliance is in good condition. 

 NOTICE: 

(1)  After changing the batteries of remote control, please discard them to avoid being swallowed by 

children. 

(2)  When the unit is working, do not remove the fan cover. 

(3)  Do not use organic solvents to wipe the controller operating panel. 

(4)  Before cleaning the unit, cut off the power supply. 

Safety Notice on Operation 

3 

Sayfa 9

GREE                                                Multi Variable Air Conditioners Indoor Unit  

PRODUCT 
 
 

4 

Sayfa 10

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1 Product List 

1.1 High Static Pressure Duct Type Indoor Unit 

Model 
Product 

GMV-ND07PHS/NhD-T(U) 
CM810N3040 
7500 
8500 

GMV-ND09PHS/NhD-T(U) 
CM810N3050 
9500 
10500 

GMV-ND12PHS/NhD-T(U) 
CM810N2990 
12000 
13500 

GMV-ND15PHS/NhD-T(U) 
CM810N3070 
15000 
17000 

GMV-ND18PHS/NhD-T(U) 
CM810N3060 
18000 
20000 

GMV-ND24PHS/NhD-T(U) 
CM810N2940 
24000 
27000 

GMV-ND30PHS/NhD-T(U) 
CM810N3080 
30000 
34000 

GMV-ND36PHS/NhD-T(U) 
CM810N3100 
36000 
40000 

GMV-ND42PHS/NhD-T(U) 
CM810N3090 
42000 
47000 

GMV-ND48PHS/NhD-T(U) 
CM810N3110 
48000 
54000 

GMV-ND54PHS/NhD-T(U) 
CM810N2930 
54000 
60000 

1.2 Fresh Air Processing Duct Type Indoor Unit 

Model 
Product 

GMV-NDX42P/NhD-T(U) 
CM810N3230 
42000 
29000 

208/230V 
~60Hz 
R32 
 
GMV-NDX48P/NhD-T(U) 
CM810N3220 
48000 
34000 

GMV-NDX54P/NhD-T(U) 
CM810N3120 
54000 
45000 

1.3 High Pressure Air Handler Indoor Unit 

Model 
Product Code 

GMV-ND12A/NhB-T(U) 
CM810N3290 
12000 
13500 

GMV-ND18A/NhB-T(U) 
CM810N3020 
18000 
20000 

GMV-ND24A/NhB-T(U) 
CM810N3370 
24000 
27000 

GMV-ND30A/NhB-T(U) 
CM810N3010 
30000 
34000 

GMV-ND36A/NhB-T(U) 
CM810N3360 
36000 
40000 

GMV-ND42A/NhB-T(U) 
CM810N3000 
42000 
47000 

GMV-ND48A/NhB-T(U) 
CM810N3340 
48000 
54000 

GMV-ND54A/NhB-T(U) 
CM810N3350 
54000 
60000 

GMV-ND60A/NhB-T(U) 
CM810N3030 
60000 
66000 

CHAPTER 1 PRODUCT 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

Code 

208/230V 
~60Hz 
R32 
 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

Code 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

208/230V 
~60Hz 
R32 
 

5 

Sayfa 11

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.4 360° Air Discharge Cassette Type Indoor Unit 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

Model 
Product 

Code 

GMV-ND07T/NhD-T(U) 
CM500N2470 
7500 
8500 

GMV-ND09T/NhD-T(U) 
CM500N2520 
9500 
10500 

GMV-ND12T/NhD-T(U) 
CM500N2440 
12000 
13500 

GMV-ND15T/NhD-T(U) 
CM500N2510 
15000 
17000 

GMV-ND18T/NhD-T(U) 
CM500N2430 
18000 
20000 

208/230V 
~60Hz 
R32 
 

GMV-ND24T/NhD-T(U) 
CM500N2500 
24000 
27000 

GMV-ND30T/NhD-T(U) 
CM500N2460 
30000 
34000 

GMV-ND36T/NhD-T(U) 
CM500N2490 
36000 
40000 

GMV-ND42T/NhD-T(U) 
CM500N2480 
42000 
47000 

GMV-ND48T/NhD-T(U) 
CM500N2420 
48000 
54000 

1.5 360°Air Discharge Compact Cassette Type Indoor Unit 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

Model 
Product 

Code 

GMV-ND05T/NhE-T(U) 
CM500N2550 
5800 
6200 

GMV-ND07T/NhE-T(U) 
CM500N2570 
7500 
8500 

GMV-ND09T/NhE-T(U) 
CM500N2580 
9500 
10500 

208/230V 
~60Hz 
R32 
 

GMV-ND12T/NhE-T(U) 
CM500N2560 
12000 
13500 

GMV-ND15T/NhE-T(U) 
CM500N2590 
15000 
17000 

GMV-ND18T/NhE-T(U) 
CM500N2450 
18000 
20000 

1.6 1-way Cassette Type Indoor Unit 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

Model 
Product 

Code 

GMV-ND07TD/NhA-T(U) 
CM502N0220 
7500 
8500 

208/230V 
~60Hz 
R32 
 
GMV-ND09TD/NhA-T(U) 
CM502N0230 
9500 
10500 

GMV-ND12TD/NhA-T(U) 
CM502N0210 
12000 
13500 

6 

Sayfa 12

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.7 Wall Mounted Type Indoor Unit 

Model 
Product 

GMV-ND06G/NhA1C-T(U) 
CM100N3560 
6000 
7500 

GMV-ND07G/NhA1C-T(U) 
CM100N3570 
7500 
8500 

GMV-ND09G/NhA1C-T(U) 
CM100N3410 
9500 
10500 

GMV-ND12G/NhA1C-T(U) 
CM100N3590 
12000 
13500 

GMV-ND14G/NhA1C-T(U) 
CM100N3430 
15000 
17000 

GMV-ND18G/NhA1C-T(U) 
CM100N3580 
18000 
20000 

GMV-ND24G/NhA1C-T(U) 
CM100N3420 
24000 
27000 

GMV-ND06G/NhA3C-T(U) 
CM100N3490 
6000 
7500 

GMV-ND07G/NhA3C-T(U) 
CM100N3510 
7500 
8500 

GMV-ND09G/NhA3C-T(U) 
CM100N3520 
9500 
10500 

GMV-ND12G/NhA3C-T(U) 
CM100N3500 
12000 
13500 

GMV-ND14G/NhA3C-T(U) 
CM100N3530 
15000 
17000 

GMV-ND18G/NhA3C-T(U) 
CM100N3550 
18000 
20000 

GMV-ND24G/NhA3C-T(U) 
CM100N3540 
24000 
27000 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 
Btu/h 
Btu/h 

Code 

208/230V 
~60Hz 
R32 
 

7 

Sayfa 13

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2 Nomenclature 

Nomenclature of Indoor Unit: 

GMV 
- 
N 
□ 
□ 
□ 
□ 
□ 
/ 
□ 
□ 
- 
□ 
□ 

1 
 
2 
3 
4 
5 
6 
7 
 
8 
9 
 
10 
11 
 

No. 
Description 
Options 

1 
Product code 
GMV-Gree Multi VRF Units 

2 
indoor unit code 
indoor unit-N 

3 
Motor type  
D-DC motor 
NULL-AC motor  

4 
Function code  
X-fresh air  

5 
Cooling capacity/air volume 
code  
Indoor unit: nominal cooling capacity /1000(Btu/h) 

6 
Unit type  

7 
With water pump or not  
With water pump-S 
(S is not displayed for the cassette unit with water pump)  

8 
Refrigerant code 
Nh-R32 

9 
Design serial No.  
Nominate by A, B, C or expand it by 1, 2, 3… 

10 
Power  
T-208/230V~,60Hz 

11 
Sale Area code 
(U)-North America 

P-standard static pressure duct type indoor unit 
PH-high static pressure duct type indoor unit 
T-360°Air Discharge type indoor unit 
A-Air handler type indoor unit 
TD-one-way cassette type indoor unit 

8 

Sayfa 14

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3 Specifications 

3.1 High Static Pressure Duct Indoor Unit 

Model 
GMV-ND07PHS/NhD-T(U) GMV-ND09PHS/NhD-T(U)GMV-ND12PHS/NhD-T(U) 

Cooling 
Btu/h 
7500 
9500 
12000 

Capacity 

Heating 
Btu/h 
8500 
10500 
13500 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
470/355/295 
470/355/295 
470/355/295 

Airflow volume(H/M/L) 

m3/h 
800/600/500 
800/600/500 
800/600/500 

Pa 
60/0~150 
60/0~150 
60/0~150 

ESP 

In.W.G 
0.24/0~0.6 
0.24/0~0.6 
0.24/0~0.6 

Sound pressure level(H/M/L) 
dB(A) 
33/30/27 
33/30/27 
35/32/29 

Liquid 
In. 
1/4 
1/4 
1/4 

Connecting pipe 

Gas 
In. 
3/8 
3/8 
3/8 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Connecting pipe 

Gas 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 

Dimension 

(WxDxH) 

Package 
In. 
47-7/16×32×14-3/16 
47-7/16×32×14-3/16 
47-7/16×32×14-3/16 

Outline 
mm 
1000×700×300 
1000×700×300 
1000×700×300 

Dimension 

(WxDxH) 

Package 
mm 
1205×813×360 
1205×813×360 
1205×813×360 

Net weight/Gross weight 
LBS 
94/108 
94/108 
94/108 

Net weight/Gross weight 
kg 
42.5/49 
42.5/49 
42.5/49 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.4 
1.4 
1.4 

Fuse Capacity 
A 
10 
10 
10 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 
 

Model 
GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U)GMV-ND24PHS/NhD-T(U) 

Cooling 
Btu/h 
15000 
18000 
24000 

Capacity 

Heating 
Btu/h 
17000 
20000 
27000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
590/470/410 
590/470/410 
735/620/560 

Airflow volume(H/M/L) 

m3/h 
1000/800/700 
1000/800/700 
1250/1050/950 

Pa 
90/0~200 
90/0~200 
90/0~200 

ESP 

In.W.G 
0.36/0~0.8 
0.36/0~0.8 
0.36/0~0.8 

Sound pressure level(H/M/L) 
dB(A) 
39/36/33 
39/36/33 
40/37/34 

Liquid 
In. 
1/4 
1/4 
1/4 

Connecting pipe 

Gas 
In. 
1/2 
1/2 
1/2 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Connecting pipe 

Gas 
mm 
Φ12.7 
Φ12.7 
Φ12.7 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 

Dimension 

(W×D×H) 

Package 
In. 
47-7/16×32×14-3/16 
47-7/16×32×14-3/16 
47-7/16×32×14-3/16 

Outline 
mm 
1000×700×300 
1000×700×300 
1000×700×300 

Dimension 

(W×D×H) 

Package 
mm 
1205×813×360 
1205×813×360 
1205×813×360 

9 

Sayfa 15

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U)GMV-ND24PHS/NhD-T(U) 

Net weight/Gross weight 
LBS 
95/109 
95/109 
95/109 

Net weight/Gross weight 
kg 
43/49.5 
43/49.5 
43/49.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.8 
1.8 
 2.2 

Fuse Capacity 
A 
10 
10 
10 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 
 

Model 
GMV-ND30PHS/NhD-T(U) GMV-ND36PHS/NhD-T(U) GMV-ND42PHS/NhD-T(U) 

Cooling 
Btu/h 
30000 
36000 
42000 

Capacity 

Heating 
Btu/h 
34000 
40000 
47000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
1175/940/825 
1175/940/825 
1175/940/825 

Airflow volume(H/M/L) 

m3/h 
2000/1600/1400 
2000/1600/1400 
2000/1600/1400 

Pa 
90/0~200 
90/0~200 
90/0~200 

ESP 

In.W.G 
0.36/0~0.8 
0.36/0~0.8 
0.36/0~0.8 
Sound pressure 

level(H/M/L) 
dB(A) 
44/40/37 
44/40/37 
44/40/37 

Liquid 
In. 
 3/8 
3/8 
3/8 

Connecting pipe 

Gas 
In. 
 5/8 
5/8 
5/8 

Liquid 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

Connecting pipe 

Gas 
mm 
Φ15.9 
Φ15.9 
Φ15.9 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
55-1/8×27-9/16×11-13/16 55-1/8×27-9/16×11-13/16 55-1/8×27-9/16×11-13/16 

Dimension 

(W×D×H) 

Package 
In. 
63-1/16×32×14-3/8 
63-1/16×32×14-3/8 
63-1/16×32×14-3/8 

Outline 
mm 
1400×700×300 
1400×700×300 
1400×700×300 

Dimension 

(W×D×H) 

Package 
mm 
1601×813×365 
1601×813×365 
1601×813×365 

Net weight/Gross weight 
LBS 
128/143 
128/143 
128/143 

Net weight/Gross weight 
kg 
58/65 
58/65 
58/65 

MOP (Max Fuse Size) 
A 
15 
15 
15 
MCA (Min. Circuit 

Ampacity) 
A 
2.7 
2.7 
2.7 

Fuse Capacity 
A 
10 
10 
10 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 
 

Model 
GMV-ND48PHS/NhD-T(U) 
GMV-ND54PHS/NhD-T(U) 

Cooling 
Btu/h 
48000 
54000 

Capacity 

Heating 
Btu/h 
54000 
60000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 

CFM 
1470/1175/1030 
1470/1175/1030 

Airflow volume(H/M/L) 

m3/h 
2500/2000/1750 
2500/2000/1750 

Pa 
90/0~200 
90/0~200 

ESP 

In.W.G 
0.36/0~0.8 
0.36/0~0.8 
Sound pressure 

level(H/M/L) 
dB(A) 
46/44/41 
46/44/41 

Liquid 
In. 
3/8 
3/8 

Connecting pipe 

Gas 
In. 
5/8 
5/8 

10 

Sayfa 16

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND48PHS/NhD-T(U) 
GMV-ND54PHS/NhD-T(U) 

Liquid 
mm 
Φ9.52 
Φ9.52 

Connecting pipe 

Gas 
mm 
Φ15.9 
Φ15.9 

In. 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 

Outline 
In. 
55-1/8×27-9/16×11-13/16 
55-1/8×27-9/16×11-13/16 

Dimension 

(W×D×H) 

Package 
In. 
63-1/16×32×14-3/8 
63-1/16×32×14-3/8 

Outline 
mm 
1400×700×300 
1400×700×300 

Dimension 

(W×D×H) 

Package 
mm 
1601×813×365 
1601×813×365 

Net weight/Gross weight 
LBS 
128/143 
128/143 

Net weight/Gross weight 
kg 
58/65 
58/65 

MOP (Max Fuse Size) 
A 
15 
15 
MCA (Min. Circuit 

Ampacity) 
A 
3.7 
3.7 

Fuse Capacity 
A 
10 
10 

Refrigeration Control Device 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 

3.2 Fresh Air Processing Indoor Unit 

Model 
GMV-NDX42P/NhD-T(U) GMV-NDX48P/NhD-T(U) GMV-NDX54P/NhD-T(U) 

Cooling 
Btu/h 
42000 
48000 
54000 

Capacity 

Heating*1 
Btu/h 
29000 
34000 
45000 

Heating*2 
Btu/h 
36000 
41000 
52000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
705/590~1175 
705/590~1175 
880/705~1470 

Airflow volume(H/M/L) 

m3/h 
1200/1000~2000 
1200/1000~2000 
1500/1200~2500 

Pa 
150/50~220 
150/50~220 
150/50~220 

ESP 

In.W.G 
0.6/0.2~0.88 
0.6/0.2~0.88 
0.6/0.2~0.88 

Sound pressure level(H/M/L) 
dB(A) 
45 
45 
46 

Liquid 
In. 
3/8 
3/8 
3/8 

Gas 
In. 
5/8 
5/8 
5/8 

Connecting pipe 

Liquid 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

Gas 
mm 
Φ15.9 
Φ15.9 
Φ15.9 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
55-1/8×27-9/16×11-
13/16 
55-1/8×27-9/16×11-
13/16 
55-1/8×27-9/16×11-
13/16 
Package 
In. 
63-1/16×32×14-3/8 
63-1/16×32×14-3/8 
63-1/16×32×14-3/8 

Dimension 

(W×D×H) 

Outline 
mm 
1400×700×300 
1400×700×300 
1400×700×300 

Package 
mm 
1601×813×365 
1601×813×365 
1601×813×365 

Net weight/Gross weight 
LBS 
126/141 
126/141 
126/141 

Net weight/Gross weight 
kg 
57/64 
57/64 
57/64 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
2.7 
2.7 
3.7 

Fuse Capacity 
A 
10 
10 
10 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

11 

Sayfa 17

GREE                                                Multi Variable Air Conditioners Indoor Unit  

 
① Rated cooling capacity test conditions: indoor 95.0°F DB/82.4°F WB, outdoor 95.0°F DB; 

connection pipe length: 24-5/8ft., without height difference between units. The default air outlet 

temperature of the unit is 64.4°F. 

② Rated heating capacity test conditions: *1. indoor 44.6°F DB, outdoor 44.6°F DB/42.8 °F WB, *2 

indoor 32°F DB, outdoor 32°F DB/26.8°F WB, connection pipe length: 24-5/8ft., without height 

difference between units. The default air outlet temperature of the unit is 71.6°F. 

③ The Sound Pressure Level will change with the External Static Pressure. 

VRF fresh air series indoor unit is a kind of air processing unit that inhales the fresh air from outdoor 

side and then processes it to provide for the user in the room. This product series can only connect to 

one VRF fresh air indoor unit when linking to the outdoor unit. 

Optional 
Indoor unit model 

Recommended 
capacity of outdoor unit 

Connected 
outdoor unit series 
Connection condition 

GMV-NDX42P/NhD-T(U) 
42000/48000Btu/h 
R32 GMV6 Mini 
R32 Ultra Heat GMV6 Mini 

GMV-NDX48P/NhD-T(U) 
48000Btu/h 

GMV-NDX54P/NhD-T(U) 
60000Btu/h 

 
Please match the outdoor unit in strict accordance with the above requirements, otherwise, the 

comfortableness will be affected or even the unit will be damaged. 

3.3 Air Handler Indoor Unit 

Model 
GMV-ND12A/NhB-T(U) GMV-ND18A/NhB-T(U) GMV-ND24A/NhB-T(U) 

Cooling 
Btu/h 
12000 
18000 
24000 

Capacity 

Heating 
Btu/h 
13500 
20000 
27000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
650/520/300 
650/520/300 
880/800/690 

Airflow volume(H/M/L) 

m3/h 
1105/884/510 
1105/884/510 
1495/1359/1172 

Pa 
50/0~250 
50/0~250 
50/0~250 

ESP 

In.W.G 
0.2/0~1.0 
0.2/0~1.0 
0.2/0~1.0 

Sound pressure level(H/M/L) 
dB(A) 
40/37/35 
40/37/35 
42/40/38 

Liquid 
In. 
1/4 
1/4 
1/4 

Gas 
In. 
3/8 
1/2 
1/2 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ12.7 
Φ12.7 

In. 
G1 
G1 
G1 

Drain pipe 

mm 
Φ25.4 
Φ25.4 
Φ25.4 

12 

The capacity of outdoor unit is 
not less than the recommended 
capacity and cannot exceed 10% 
of the recommended capacity. 

Sayfa 18

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND12A/NhB-T(U) GMV-ND18A/NhB-T(U) GMV-ND24A/NhB-T(U) 

Outline 
In. 
21-1/4×18-1/8×43-1/2 
21-1/4×18-1/8×43-1/2 
21-1/4×18-1/8×43-1/2 

Package 
In. 
26×20-9/16×46-1/4 
26×20-9/16×46-1/4 
26×20-9/16×46-1/4 

Dimension 

(W×D×H) 

Outline 
mm 
540×460×1105 
540×460×1105 
540×460×1105 

Package 
mm 
660×523×1175 
660×523×1175 
660×523×1175 

Net weight/Gross weight 
LBS 
126/139 
126/139 
130/143 

Net weight/Gross weight 
kg 
57/63 
57/63 
59/65 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
2.0 
2.0 
3.0 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 
 

Model 
GMV-ND30A/NhB-T(U) GMV-ND36A/NhB-T(U) GMV-ND42A/NhB-T(U) 

Cooling 
Btu/h 
30000 
36000 
42000 

Capacity 

Heating 
Btu/h 
34000 
40000 
47000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
910/820/710 
1230/1100/970 
1260/1120/1000 

Airflow volume(H/M/L) 

m3/h 
1546/1393/1206 
2090/1869/1648 
2141/1903/1699 

Pa 
50/0~250 
50/0~250 
50/0~250 

ESP 

In.W.G 
0.2/0~1.0 
0.2/0~1.0 
0.2/0~1.0 

Sound pressure level(H/M/L) 
dB(A) 
42/40/38 
48/46/44 
48/46/44 

Liquid 
In. 
3/8 
3/8 
3/8 

Gas 
In. 
5/8 
5/8 
5/8 

Connecting pipe 

Liquid 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

Gas 
mm 
Φ15.9 
Φ15.9 
Φ15.9 

In. 
G1 
G1 
G1 

Drain pipe 

mm 
Φ25.4 
Φ25.4 
Φ25.4 

Outline 
In. 
21-1/4×18-1/8×43-1/2 
21-1/4×21×1/4×48-1/4 
21-1/4×21×1/4×48-1/4 

Package 
In. 
26×20-9/16×46-1/4 
26×23-3/4×51 
26×23-3/4×51 

Dimension 

(W×D×H) 

Outline 
mm 
540×460×1105 
540×540×1224 
540×540×1224 

Package 
mm 
660×523×1175 
660×603×1295 
660×603×1295 

Net weight/Gross weight 
LBS 
130/143 
157/172 
157/172 

Net weight/Gross weight 
kg 
59/65 
71/78 
71/78 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
3.0 
4.0 
4.0 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) 

Cooling 
Btu/h 
48000 
54000 
60000 

Capacity 

Heating 
Btu/h 
54000 
60000 
66000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
1800/1600/1500 
1800/1600/1500 
1820/1650/1530 

Airflow volume(H/M/L) 

m3/h 
3059/2719/2549 
3059/2719/2549 
3093/2804/2600 

Pa 
50/0~250 
50/0~250 
50/0~250 

ESP 

In.W.G 
0.2/0~1.0 
0.2/0~1.0 
0.2/0~1.0 

Sound pressure level(H/M/L) 
dB(A) 
51/50/49 
51/50/49 
51/50/49 

13 

Sayfa 19

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) 

Liquid 
In. 
3/8 
3/8 
3/8 

Gas 
In. 
5/8 
5/8 
5/8 

Connecting pipe 

Liquid 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

Gas 
mm 
Φ15.9 
Φ15.9 
Φ15.9 

In. 
G1 
G1 
G1 

Drain pipe 

mm 
Φ25.4 
Φ25.4 
Φ25.4 

Outline 
In. 
24-13/16×21-1/4×51-
15/16 
24-13/16×21-1/4×51-
15/16 
24-13/16×21-1/4×51-
15/16 
Package 
In. 
27-5/16×26×54-13/16 
27-5/16×26×54-13/16 
27-5/16×26×54-13/16 

Dimension 

(W×D×H) 

Outline 
mm 
630×540×1320 
630×540×1320 
630×540×1320 

Package 
mm 
693×660×1392 
693×660×1392 
693×660×1392 

Net weight/Gross weight 
LBS 
194/212 
194/212 
194/212 

Net weight/Gross weight 
kg 
88/96 
88/96 
88/96 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
7.7 
7.7 
7.7 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

3.4 360°Air Discharge Cassette Indoor Unit 

Model 
GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) 

Cooling 
Btu/h 
7500 
9500 
12000 

Capacity 

Heating 
Btu/h 
8500 
10500 
13500 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
470/412/353 
470/412/353 
470/412/353 

Airflow volume(H/M/L) 

m3/h 
800/700/600 
800/700/600 
800/700/600 

Sound pressure level(H/M/L) 
dB(A) 
37/33/28 
37/33/28 
37/33/28 

Liquid 
In. 
 1/4 
 1/4 
 1/4 

Gas 
In. 
 3/8 
 3/8 
 3/8 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×9 7/16 

Package 
In. 
36 3/4×36 3/4×11 1/2 
36 3/4×36 3/4×11 1/2 
36 3/4×36 3/4×11 1/2 

Dimension 

(W×D×H) 

Outline 
mm 
840×840×240 
840×840×240 
840×840×240 

Package 
mm 
933×933×292 
933×933×292 
933×933×292 

Net weight/Gross weight 
LBS 
50/61 
50/61 
50/61 

Net weight/Gross weight 
kg 
22.5/27.5 
22.5/27.5 
22.5/27.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.9 
0.9 
0.9 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
TF06 
TF06 
TF06 

Outline 
In. 
37 3/8×37 3/8×2 9/16 
37 3/8×37 3/8×2 9/16 
37 3/8×37 3/8×2 9/16 

Decoration 

Dimension 

paneI 

Package 
In. 
40 5/8×40 1/8×4 3/8 
40 5/8×40 1/8×4 3/8 
40 5/8×40 1/8×4 3/8 

(W×D×H) 

Outline 
mm 
950×950×65 
950×950×65 
950×950×65 

14 

Sayfa 20

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) 

Dimension 

(W×D×H) 
Package 
mm 
1033×1020×110 
1033×1020×110 
1033×1020×110 

Decoration 

Net weight/Gross 

weight 
LBS 
13.2/20.9 
13.2/20.9 
13.2/20.9 

paneI 

Net weight/Gross 

weight 
kg 
6/9.5 
6/9.5 
6/9.5 

Model 
GMV-ND15T/NhD-T(U) GMV-ND18T/NhD-T(U) GMV-ND24T/NhD-T(U) 

Cooling 
Btu/h 
15000 
18000 
24000 

Capacity 

Heating 
Btu/h 
17000 
20000 
27000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
560/500/440 
560/500/440 
736/677/588 

Airflow volume(H/M/L) 

m3/h 
950/850/750 
950/850/750 
1250/1150/1000 

Sound pressure level(H/M/L) 
dB(A) 
40/37/34 
40/37/34 
40/37/34 

Liquid 
In. 
 1/4 
 1/4 
 1/4 

Gas 
In. 
 1/2 
 1/2 
 1/2 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ12.7 
Φ12.7 
Φ12.7 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×11 7/16 

Package 
In. 
36 3/4×36 3/4×11 1/2 
36 3/4×36 3/4×11 1/2 
36 3/4×36 3/4×13 9/16 

Dimension 

(W×D×H) 

Outline 
mm 
840×840×240 
840×840×240 
840×840×290 

Package 
mm 
933×933×292 
933×933×292 
933×933×345 

Net weight/Gross weight 
LBS 
50/61 
50/61 
56/67 

Net weight/Gross weight 
kg 
22.5/27.5 
22.5/27.5 
25.5/30.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.9 
0.9 
1.1 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
TF06 
TF06 
TF06 

Outline 
In. 
37 3/8×37 3/8×2 9/16 
37 3/8×37 3/8×2 9/16 
37 3/8×37 3/8×2 9/16 

Package 
In. 
40 5/8×40 1/8×4 3/8 
40 5/8×40 1/8×4 3/8 
40 5/8×40 1/8×4 3/8 

Dimension 

(W×D×H) 

Outline 
mm 
950×950×65 
950×950×65 
950×950×65 

Decoration 

paneI 

Package 
mm 
1033×1020×110 
1033×1020×110 
1033×1020×110 
Net weight/Gross 

weight 
LBS 
13.2/20.9 
13.2/20.9 
13.2/20.9 

Net weight/Gross 

weight 
kg 
6/9.5 
6/9.5 
6/9.5 

Model 
GMV-ND30T/NhD-T(U) 
GMV-ND36T/NhD-T(U) 

Cooling 
Btu/h 
30000 
36000 

Capacity 

Heating 
Btu/h 
34000 
40000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 

CFM 
883/706/588 
883/706/588 

Airflow volume(H/M/L) 

m3/h 
1500/1200/1000 
1500/1200/1000 

Sound pressure level(H/M/L) 
dB(A) 
44/39/34 
44/39/34 

Liquid 
In. 
 3/8 
 3/8 

Connecting pipe 

Gas 
In. 
 5/8 
 5/8 

Liquid 
mm 
Φ9.52 
Φ9.52 

15 

Sayfa 21

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND30T/NhD-T(U) 
GMV-ND36T/NhD-T(U) 

Connecting pipe 
Gas 
mm 
Φ15.9 
Φ15.9 

In. 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 

Outline 
In. 
33 1/16×33 1/16×11 7/16 
33 1/16×33 1/16×11 7/16 
Package 
In. 
36 3/4×36 3/4×13 9/16 
36 3/4×36 3/4×13 9/16 
Outline 
mm 
840×840×290 
840×840×290 
Package 
mm 
933×933×345 
933×933×345 
Net weight/Gross weight 
LBS 
56/67 
56/67 

Dimension 

(W×D×H) 

Net weight/Gross weight 
kg 
25.5/30.5 
25.5/30.5 

MOP (Max Fuse Size) 
A 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.2 
1.2 

Fuse Capacity 
A 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 

Model 
TF06 
TF06 

Outline 
In. 
37 3/8×37 3/8×2 9/16 
37 3/8×37 3/8×2 9/16 

Package 
In. 
40 5/8×40 1/8×4 3/8 
40 5/8×40 1/8×4 3/8 

Dimension 

Decoration 

(W×D×H) 

Outline 
mm 
950×950×65 
950×950×65 

paneI 

Package 
mm 
1033×1020×110 
1033×1020×110 

Net weight/Gross weight 
LBS 
13.2/20.9 
13.2/20.9 

Net weight/Gross weight 
kg 
6/9.5 
6/9.5 
 

Model 
GMV-ND42T/NhD-T(U) 
GMV-ND48T/NhD-T(U) 

Cooling 
Btu/h 
42000 
48000 

Capacity 

Heating 
Btu/h 
47000 
54000 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 

CFM 
1060/853/677 
1060/853/677 

Airflow volume(H/M/L) 

m3/h 
1800/1450/1150 
1800/1450/1150 

Sound pressure level(H/M/L) 
dB(A) 
45/40/35 
45/40/35 

Liquid 
In. 
 3/8 
 3/8 

Gas 
In. 
 5/8 
 5/8 

Connecting pipe 

Liquid 
mm 
Φ9.52 
Φ9.52 

Gas 
mm 
Φ15.9 
Φ15.9 

In. 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 

Outline 
In. 
33 1/16×33 1/16×11 7/16 
33 1/16×33 1/16×11 7/16 

Package 
In. 
36 3/4×36 3/4×13 9/16 
36 3/4×36 3/4×13 9/16 

Dimension 

(W×D×H) 

Outline 
mm 
840×840×290 
840×840×290 

Package 
mm 
933×933×345 
933×933×345 

Net weight/Gross weight 
LBS 
56/67 
56/67 

Net weight/Gross weight 
kg 
25.5/30.5 
25.5/30.5 

MOP (Max Fuse Size) 
A 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.3 
1.3 

Fuse Capacity 
A 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 

Model 
TF06 
TF06 

Decoration 

Outline 
In. 
37 3/8×37 3/8×2 9/16 
37 3/8×37 3/8×2 9/16 

Dimension 

paneI 

(W×D×H) 

Package 
In. 
40 5/8×40 1/8×4 3/8 
40 5/8×40 1/8×4 3/8 

16 

Sayfa 22

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND42T/NhD-T(U) 
GMV-ND48T/NhD-T(U) 

Outline 
mm 
950×950×65 
950×950×65 

Dimension 

(W×D×H) 

Package 
mm 
1033×1020×110 
1033×1020×110 

Decoration 

paneI 

Net weight/Gross weight 
LBS 
13.2/20.9 
13.2/20.9 

Net weight/Gross weight 
kg 
6/9.5 
6/9.5 

3.5 360°Air Discharge Compact Cassette Indoor Unit 

Model 
GMV-ND05T/NhE-T(U) GMV-ND07T/NhE-T(U) GMV-ND09T/NhE-T(U) 

Cooling 
Btu/h 
5800 
7500 
9500 

Capacity 

Heating 
Btu/h 
6200 
8500 
10500 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
290/270/220 
290/270/220 
360/320/280 

Airflow volume(H/M/L) 

m3/h 
500/460/370 
500/460/370 
620/550/480 

Sound pressure level(H/M/L) 
dB(A) 
33/30/28 
33/30/28 
37/35/30 

Liquid 
In. 
 1/4 
 1/4 
 1/4 

Gas 
In. 
 3/8 
 3/8 
 3/8 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 

Package 
In. 
27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 

Dimension 

(W×D×H) 

Outline 
mm 
570×570×265 
570×570×265 
570×570×265 

Package 
mm 
698×653×295 
698×653×295 
698×653×295 

Net weight/Gross weight 
LBS 
37.5/47.4 
37.5/47.4 
37.5/47.4 

Net weight/Gross weight 
kg 
17.0/21.5 
17.0/21.5 
17.0/21.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.5 
0.5 
0.5 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
TF05 
TF05 
TF05 

Outline 
In. 
24 3/8×24 3/8×1 7/8 
24 3/8×24 3/8×1 7/8 
24 3/8×24 3/8×1 7/8 

Package 
In. 
27 1/4×27 1/4×4 1/2 
27 1/4×27 1/4×4 1/2 
27 1/4×27 1/4×4 1/2 

Dimension 

(W×D×H) 

Outline 
mm 
620×620×47.5 
620×620×47.5 
620×620×47.5 

Decoration 

paneI 

Package 
mm 
693×693×115 
693×693×115 
693×693×115 
Net weight/Gross 

weight 
LBS 
6.6/10 
6.6/10 
6.6/10 

Net weight/Gross 

weight 
kg 
3/4.5 
3/4.5 
3/4.5 

Model 
GMV-ND12T/NhE-T(U) GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U) 

Cooling 
Btu/h 
12000  
15000  
18000  

Capacity 

Heating 
Btu/h 
13500  
17000  
20000  

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
360/320/280 
360/320/280 
430/385/330 

Airflow volume(H/M/L) 

m3/h 
620/550/480 
620/550/480 
730/650/560 

Sound pressure level(H/M/L) 
dB(A) 
37/35/30 
37/35/30 
43/40/38 

17 

Sayfa 23

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND12T/NhE-T(U) GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U) 

Liquid 
In. 
 1/4 
 1/4 
 1/4 

Gas 
In. 
 3/8 
 1/2 
 1/2 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ12.7 
Φ12.7 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 

Package 
In. 
27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 

Dimension 

(W×D×H) 

Outline 
mm 
570×570×265 
570×570×265 
570×570×265 

Package 
mm 
698×653×295 
698×653×295 
698×653×295 

Net weight/Gross weight 
LBS 
37.5/47.4 
37.5/47.4 
37.5/47.4 

Net weight/Gross weight 
kg 
17.0/21.5 
17.0/21.5 
17.0/21.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.5 
0.5 
0.5 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
TF05 
TF05 
TF05 

Outline 
In. 
24 3/8×24 3/8×1 7/8 
24 3/8×24 3/8×1 7/8 
24 3/8×24 3/8×1 7/8 

Package 
In. 
27 1/4×27 1/4×4 1/2 
27 1/4×27 1/4×4 1/2 
27 1/4×27 1/4×4 1/2 

Dimension 

(W×D×H) 

Outline 
mm 
620×620×47.5 
620×620×47.5 
620×620×47.5 

Decoration 

paneI 

Package 
mm 
693×693×115 
693×693×115 
693×693×115 

Net weight/Gross 

weight 
LBS 
6.6/10 
6.6/10 
6.6/10 

Net weight/Gross 

weight 
kg 
3/4.5 
3/4.5 
3/4.5 

3.6 1-way Cassette Indoor Unit 

Model 
GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) 

Cooling 
Btu/h 
7500 
9500 
12000 

Capacity 

Heating 
Btu/h 
8500 
10500 
13500 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
353/294/265 
353/294/265 
353/294/265 

Airflow volume(H/M/L) 

m3/h 
600/500/450 
600/500/450 
600/500/450 

Sound pressure level(H/M/L) 
dB(A) 
36/33/28 
36/33/28 
36/33/28 

Liquid 
In. 
 1/4 
 1/4 
 1/4 

Gas 
In. 
 3/8 
 3/8 
 3/8 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

In. 
Φ1 
Φ1 
Φ1 

Drain pipe 

mm 
Φ25 
Φ25 
Φ25 

Outline 
In. 
38 7/8×15 3/16×7 
38 7/8×15 3/16×7 
38 7/8×15 3/16×7 

Package 
In. 
51 1/2×19 3/4×12 3/16 
51 1/2×19 3/4×12 3/16 
51 1/2×19 3/4×12 3/16 

Dimension 

(W×D×H) 

Outline 
mm 
987×385×178 
987×385×178 
987×385×178 

Package 
mm 
1307×501×310 
1307×501×310 
1307×501×310 

Net weight/Gross weight 
LBS 
42/57 
42/57 
42/57 

18 

Sayfa 24

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) 

Net weight/Gross weight 
kg 
19/26 
19/26 
19/26 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.3 
0.3 
0.3 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
TD01 
TD01 
TD01 

Outline 
In. 
47 1/4×18 1/8×2 3/16 
47 1/4×18 1/8×2 3/16 
47 1/4×18 1/8×2 3/16 

Package 
In. 
49 13/16×21 1/8×4 3/4 
49 13/16×21 1/8×4 3/4 
49 13/16×21 1/8×4 3/4 

Dimension 

(W×D×H) 

Outline 
mm 
1200×460×55 
1200×460×55 
1200×460×55 

Decoration 

paneI 

Package 
mm 
1265×536×121 
1265×536×121 
1265×536×121 
Net weight/Gross 

weight 
LBS 
9.3/13.2 
9.3/13.2 
9.3/13.2 

Net weight/Gross 

weight 
kg 
4.2/6 
4.2/6 
4.2/6 

3.7 Wall Mounted Type Indoor Unit 

Model 
GMV-ND06G/NhA1C-T(U) GMV-ND07G/NhA1C-T(U) GMV-ND09G/NhA1C-T(U) 

Cooling 
Btu/h 
6000 
7500 
9500 

Capacity 

Heating 
Btu/h 
7500 
8500 
10500 

Power supply 
V/Ph/Hz 
208/230V ~ 60 
208/230V ~ 60 
208/230V ~ 60 

CFM 
265 
265 
265 

Airflow volume(H) 

m3/h 
450 
450 
450 

Sound pressure level(H/M/L) 
dB(A) 
36/34/31 
36/34/31 
36/34/31 

Liquid 
In. 
1/4 
1/4 
1/4 

Gas 
In. 
3/8 
3/8 
3/8 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

In. 
Φ13/16 
Φ13/16 
Φ13/16 

Drain pipe 

mm 
Φ20 
Φ20 
Φ20 

Outline 
In. 
34 1/8×8 1/8×10 7/8 
34 1/8×8 1/8×10 7/8 
34 1/8×8 1/8×10 7/8 

Package 
In. 
39 3/16×13 1/2×10 31/32 39 3/16×13 1/2×10 31/32 39 3/16×13 1/2×10 31/32 

Dimension 

(WxDxH) 

Outline 
mm 
867×206×276 
867×206×276 
867×206×276 

Package 
mm 
996×343×279 
996×343×279 
996×343×279 

Net weight/Gross weight 
LBS 
21/26 
21/26 
21/26 

Net weight/Gross weight 
kg 
9.5/12 
9.5/12 
9.5/12 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.9 
0.9 
0.9 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
GMV-ND12G/NhA1C-T(U) GMV-ND14G/NhA1C-T(U) GMV-ND18G/NhA1C-T(U) 

Cooling 
Btu/h 
12000 
15000 
18000 

Capacity 

Heating 
Btu/h 
13500 
17000 
20000 

Power supply 
V/Ph/Hz 
208/230V ~ 60 
208/230V ~ 60 
208/230V ~ 60 

CFM 
380 
380 
530 

Airflow volume(H) 

m3/h 
650 
650 
900 

Sound pressure level(H/M/L) 
dB(A) 
42/39/34 
42/39/34 
44/42/38 

19 

Sayfa 25

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND12G/NhA1C-T(U) GMV-ND14G/NhA1C-T(U) GMV-ND18G/NhA1C-T(U) 

Liquid 
In. 
1/4 
1/4 
1/4 

Gas 
In. 
3/8 
1/2 
1/2 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ12.7 
Φ12.7 

In. 
Φ13/16 
Φ13/16 
Φ13/16 

Drain pipe 

mm 
Φ20 
Φ20 
Φ20 

Outline 
In. 
38 1/2×9 3/4×13 1/8 
38 1/2×9 3/4×13 1/8 
43 15/16×9 3/4×13 1/8 

Package 
In. 
43 11/16×16 1/8×13 11/16 43 11/16×16 1/8×13 11/16 49 1/4×16 1/2×14 1/32 

Dimension 

(WxDxH) 

Outline 
mm 
978×248×333 
978×248×333 
1116×248×333 

Package 
mm 
1109×410×347 
1109×410×347 
1251×419×356 

Net weight/Gross weight 
LBS 
29/36 
29/36 
34/43 

Net weight/Gross weight 
kg 
13/16.5 
13/16.5 
15.5/19.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.1 
1.1 
1.1 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
GMV-ND24G/NhA1C-T(U) GMV-ND06G/NhA3C-T(U) GMV-ND07G/NhA3C-T(U) 

Cooling 
Btu/h 
24000 
6000 
7500 

Capacity 

Heating 
Btu/h 
27000 
7500 
8500 

Power supply 
V/Ph/Hz 
208/230V ~60 
208/230V ~60 
208/230V ~60 

CFM 
530 
265 
265 

Airflow volume(H) 

m3/h 
900 
450 
450 

Sound pressure level(H/M/L) 
dB(A) 
44/42/38 
36/34/31 
36/34/31 

Liquid 
In. 
1/4 
1/4 
1/4 

Gas 
In. 
1/2 
3/8 
3/8 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ12.7 
Φ9.52 
Φ9.52 

In. 
Φ13/16 
Φ13/16 
Φ13/16 

Drain pipe 

mm 
Φ20 
Φ20 
Φ20 

Outline 
In. 
43 15/16×9 3/4×13 1/8 
34 1/8×8 1/8×10 7/8 
34 1/8×8 1/8×10 7/8 

Package 
In. 
49 1/4×16 1/2×14 1/32 
39 3/16×13 1/2×10 31/32 39 3/16×13 1/2×10 31/32 

Dimension 

(WxDxH) 

Outline 
mm 
1116×248×333 
867×206×276 
867×206×276 

Package 
mm 
1251×419×356 
996×343×279 
996×343×279 

Net weight/Gross weight 
LBS 
34/43 
21/26 
21/26 

Net weight/Gross weight 
kg 
15.5/19.5 
9.5/12 
9.5/12 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.1 
0.9 
0.9 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
GMV-ND09G/NhA3C-T(U) GMV-ND12G/NhA3C-T(U) GMV-ND14G/NhA3C-T(U) 

Cooling 
Btu/h 
9500 
12000 
15000 

Capacity 

Heating 
Btu/h 
10500 
13500 
17000 

Power supply 
V/Ph/Hz 
208/230V ~ 60 
208/230V ~ 60 
208/230V ~ 60 

Airflow volume(H) 
CFM 
265 
380 
380 

20 

Sayfa 26

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND09G/NhA3C-T(U) GMV-ND12G/NhA3C-T(U) GMV-ND14G/NhA3C-T(U) 

Airflow volume(H) 
m3/h 
450 
650 
650 

Sound pressure level(H/M/L) 
dB(A) 
36/34/31 
42/39/34 
42/39/34 

Liquid 
In. 
1/4 
1/4 
1/4 

Gas 
In. 
3/8 
3/8 
1/2 

Connecting pipe 

Liquid 
mm 
Φ6.35 
Φ6.35 
Φ6.35 

Gas 
mm 
Φ9.52 
Φ9.52 
Φ12.7 

In. 
Φ13/16 
Φ13/16 
Φ13/16 

Drain pipe 

mm 
Φ20 
Φ20 
Φ20 

Outline 
In. 
34 1/8×8 1/8×10 7/8 
38 1/2×9 3/4×13 1/8 
38 1/2×9 3/4×13 1/8 

Package 
In. 
39 3/16×13 1/2×10 31/32 43 11/16×16 1/8×13 11/16 43 11/16×16 1/8×13 11/16 

Dimension 

(WxDxH) 

Outline 
mm 
867×206×276 
978×248×333 
978×248×333 

Package 
mm 
996×343×279 
1109×410×347 
1109×410×347 

Net weight/Gross weight 
LBS 
21/26 
29/36 
29/36 

Net weight/Gross weight 
kg 
9.5/12 
13/16.5 
13/16.5 

MOP (Max Fuse Size) 
A 
15 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
0.9 
1.1 
1.1 

Fuse Capacity 
A 
3.15 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
Fuse 

Model 
GMV-ND18G/NhA3C-T(U) 
GMV-ND24G/NhA3C-T(U) 

Cooling 
Btu/h 
18000 
24000 

Capacity 

Heating 
Btu/h 
20000 
27000 

Power supply 
V/Ph/Hz 
208/230V ~ 60 
208/230V ~ 60 

CFM 
530 
530 

Airflow volume(H) 

m3/h 
900 
900 

Sound pressure level(H/M/L) 
dB(A) 
44/42/38 
44/42/38 

Liquid 
In. 
1/4 
1/4 

Connecting pipe 

Gas 
In. 
1/2 
1/2 

Liquid 
mm 
Φ6.35 
Φ6.35 

Connecting pipe 

Gas 
mm 
Φ12.7 
Φ12.7 

In. 
Φ13/16 
Φ13/16 

Drain pipe 

mm 
Φ20 
Φ20 

Outline 
In. 
43 15/16×9 3/4×13 1/8 
43 15/16×9 3/4×13 1/8 

Package 
In. 
49 1/4×16 1/2×14 1/32 
49 1/4×16 1/2×14 1/32 

Dimension 

(WxDxH) 

Outline 
mm 
1116×248×333 
1116×248×333 

Package 
mm 
1251×419×356 
1251×419×356 

Net weight/Gross weight 
LBS 
34/43 
34/43 

Net weight/Gross weight 
kg 
15.5/19.5 
15.5/19.5 

MOP (Max Fuse Size) 
A 
15 
15 

MCA (Min. Circuit Ampacity) 
A 
1.1 
1.1 

Fuse Capacity 
A 
3.15 
3.15 

Refrigeration Control Device 
EXV 
EXV 

Protection Device 
Fuse 
Fuse 
 

21 

Sayfa 27

GREE                                                Multi Variable Air Conditioners Indoor Unit  

CONTROL 

22 

Sayfa 28

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1 Operation Flowchart 

CHAPTER 2 CONTROL 

23 

Sayfa 29

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2 Wired Controller 

2.1 Control Panel 

2.1.1 XE7C-23/H Wired Controller 

 Table LCD display instruction 

No. 
Name 
Instruction 
1 
Status column 
Display the icon of function that is turned on 
2 
Fan speed 
It is for displaying the fan speed 
3 
Swing 
It is for displaying the current swing status 

4 
Button prompt 
Display the function of MENU/OK button at the current page and the 
settable cursor  

5 
Temperature display  
It shows the value of temperature (If the wired controller is controlling a 
fresh air indoor unit, it will display FAP). 
6 
Mode 
It shows the operating mode 

7 
Clock display  
It display the date and the time. When it’s locating the indoor unit, it 
displays the project No. of current indoor unit.  
NOTE: When wired controller is connected with different indoor units, some functions will be different. 

Table Instruction of Status Column Icon 

No. 
Symbols 
Name 
Instructions 
1 
 
Air * 
Air status(indoor unit optional function) 

2 
 
Remove card 
The card for access control is removed 

3 
 
Clean 
Remind to clean the filter 

4 
 
Child lock 
Child lock status 

5 
 
Error 
There are errors for the unit 

6 
 
Health * 
Health function (indoor unit optional function) 

7 
 
Defrosting 
Defrosting status of outdoor unit 

8 
 
Main 
Current wired controller connects the main indoor unit. 

9 
 
Power off memory 
Memory status (when power recovered, indoor unit will 
resume previous setting status) 

10 
 
Absence 
Absence is displayed when this function is turned on. 

11 
 
 
Quiet status 
Quiet status (including quiet and auto quiet modes) 

12 
 
Energy-saving 
Energy-saving status of indoor unit 

Appearance of wired controller 

 LCD graphics of wired controller 

24 

Sayfa 30

GREE                                                Multi Variable Air Conditioners Indoor Unit  

No. 
Symbols 
Name 
Instructions 
13 
 
Shield 
Shielding status 

14 
 
Slave wired controller 
Slave wired controller (address of wired controller is 02). 

15 
 
Sleep 
Sleep status 

16 
 
Time 
Timer status is displayed 

17 
 
X-fan 
X-fan is displayed when this function is set. 

18 
 
Group control 
One wired controller controls multiple indoor units. 

19 
 
Valid operation 
It’s displayed for valid operation 

20 
 
WiFi 
WiFi status(If the wired controller has no WiFi function, it 
displays only when the unit connected to “G-Cloud”). 

21 
 
Independent swing* 
Independent swing status 

22 
 
Auto clean * 
Auto clean status 

23 
 
Setback 
Setback function status 

24 
 
Warning 
Warning status 

25 
 
Aux. Heat* 

26 
 
Aux. Heat operating 

NOTE: When wired controller is connected with different indoor units, some functions will be different. 

Table function instruction of buttons 

No. 
Name 
Function 
1 
FAN 
Switch fan speeds: auto, low, medium-low, medium, Medium-high and high 

2 
 
(1) Set operation temperature for the indoor unit. 

(3) Set and check parameters. 
7 
 

3 
 
On/off button for turn on or turn off the unit; back button for return to previous page. 

9 
 
(1) Turn pages, and switch and select the target; 

(3) Set and check parameters. 
4 
 

5 
MODE 
Switch operating modes: Auto, Cool, Dry, Fan, Heat, Floor, 3D Heat, etc. 

6 
MENU/OK 
Select mode and confirm parameters. 

8 
SWING 
Set the swing status of central air conditioners. 
 

Aux. Heat is available 

Button graphics 

(2) Move cursor. 

(2) Move the cursor; 

25 

Sayfa 31

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2.1.2 LE60-24/H1 Linkage Controller 

The linkage controller can detect strong or weak electric access control signals as well as passive 

dry contact signals (window switches, fire alarms, etc.), achieving linkage control of access, windows, fire 

alarms, etc., to turn off the indoor units and restoring the original on/off state. 

2.1.2.1 Description of Ports 

Diagram of Ports 
HBS communication port (H1, H2): It is connected to the indoor unit of air conditioner through a 2-

core communication wire. It is used for the indoor unit to supply power to linkage controller and 

communicate with linkage controller.  

Dry contact interface (I1 and O1, I2 and O2): Connect the dry contact signal to the I1, O1 (or I2, O2) 

ports to achieve linkage controller of window switches, fire alarms, etc., for unpowered signals to turn off 

the indoor units and restoring the original on/off state. Attention to the following items:  

(1) When any dry contact detects the following signal changes, linkage controller switches unit off. 

1) When the DIP switch function corresponding to the dry contact is set to “Dry contact 

disconnected for switching unit off”, the dry contact signal is changed from connection to 

disconnection and lasts for 5 seconds. 

Exterior Sketch of Linkage Controller 

26 

Sayfa 32

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2) When the DIP switch function corresponding to the dry contact is set to “Dry contact connected 

for switching unit off”, the dry contact signal is changed from disconnection to connection and 

lasts for 5 seconds. 

(2) After the unit is switched off in above way, it can be turned on by other devices (such as a wired 

controller). 

(3) After the signal recovers, the original startup or shutdown state of the unit will restore. However, if 

manual operation for unit startup is done before the signal recovers, the original startup or 

shutdown state of the unit will not restore after the signal recovers.  

Gate control interface (N and L, VCC and GND): The linkage controller has gate control interface, 

which can be connected with gate control system to achieve access control card removal to turn off the 

indoor units or access control card insertion to restore the original on/off state. If you want to control 

indoor unit’s functions through gate control, make sure the 4th lever of the DIP switch is turned to the “1” 

side, then connect the gate-control terminal to the N and L port or the VCC and GND port. Attention to 

the following items: 

1) The N and L port is the power supply interface of the 100-240V~50/60Hz gate control. 

2) The VCC and GND port is the power supply interface of the DC 5-24V gate control. 

3) Only one power input can be chosen between the 100-240V ~50/60Hz and the DC 5-24V. 

2.1.2.2 LED Indicator 

The following table is a detailed description about the LED indicator: 

The LED indicator lights up 
The linkage controller works. 

The LED indicator blinks 
The communication between the indoor unit and the linkage controller 
has malfunction. 
The LED indicator lights off 
The power supply of linkage controller is cut off. 

2.1.2.3 DIP Switch 

NOTE: 

If the setting is changed, it will take effect after the linkage controller is re-energized. 

(1) The 1st Lever of DIP Switch –Master/Slave HBS Device Setting 

The 1st lever of DIP switch is used for the setting of master/slave HBS device. The factory default 

setting is slave HBS device. 

In an HBS network, if the linkage controller is the only device that is connected to indoor units, it 

should be set as the master HBS device. Turn the 1st lever of DIP switch to 0.  

In an HBS network, if both the wired controller and linkage controller are connected to indoor units, 

the wired controller should be set as the master HBS device (i.e. master wired controller, please refer to 

the instruction manual of wired controller for the setting method). So the linkage controller should be set 

as the slave HBS device. Turn the 1st lever of DIP switch to 1. 

Diagram of DIP Switch 

27 

Sayfa 33

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Diagram of DIP Switch Setting for Master/Slave HBS Device: 

(2) The 2nd/3rd Lever of DIP Switch –Dry Contact 1/2 Signal Change Detection Setting 

The 2nd/3rd lever of DIP switch is used for the setting of dry contact 1/2 signal change detection 

respectively. The factory default setting is “dry contact 1/2 disconnected for switching unit off”. 

When dry contact 1(I1, O1) signal change detection shall be set to “Dry contact disconnected for 

switching unit off”, turn the 2nd lever of DIP switch to 1. 

When dry contact 1 signal change detection shall be set to “Dry contact connected for switching unit 

off”, turn the 2nd lever of DIP switch to 0. 

Similarly, the 3rd lever of DIP switch corresponds to dry contact 2(I2, O2) signal change detection. 

The setting method of dry contact 2 signal change detection is the same as that of dry contact 1 signal 

change detection.  

Diagram of DIP Switch Setting for dry contact 1/2 signal change detection: 

Dry contact 2 
connected for 
switching unit off 
 

(3) The 4th Lever of DIP Switch –Gate Control System Setting 

The 4th lever of DIP switch is used for the setting of Gate Control System. Factory default provided 

with Gate-control function. 

If the gate-control system is involved, turn the 4th lever of DIP switch to 1. 

If the gate-control system is not involved, turn the 4th lever of DIP switch to 0.  

Diagram of DIP Switch Setting for Gate Control System: 

Gate-control system is 
not connected 
 

 
 
Slave HBS 

Master HBS Device 

Device 

 
 Dry contact 1 

Dry contact 1 
connected for 
switching unit off 

disconnected for 
switching unit off 

 
 Dry contact 2 

disconnected for 
switching unit off 

 
 Gate-control system 

is connected 

28 

Sayfa 34

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2.2 Installation and Removal 

2.2.1 Installation Dimensions 

Unit: mm(inch) 

Dimension of XE7C-23/H 

Unit:mm(inch) 

Dimension of LE60-24/H1 

29 

Sayfa 35

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2.2.2 Installation Method 

(1) Wired Controller XE7C-23/H Installation Method: 

Installation diagram for wired controller XE7C-23/H 

The figure shows a simple installation course of wired controller, and the following points should 

be noted: 

① Before installation, please cut off the power supply of indoor unit, it is not allowed to operate with 

power supply; 

② Pull out the 2-core twisted pair inside the installation hole in the wall, and thread the wire through 

the hole in the back of soleplate of wired controller; 

③ Stick the soleplate of wired controller on the wall, and use Self-tapping Screw ST3.9×25 MA or 

screw M4×25 to fix the soleplate with the installation hole of wall; 

④ Connect the 2-core twisted pair to wiring terminal H1 and H2, and then tighten the screw; 

⑤ Arrange the wires in the back of panel, and then buckle the panel of wired controller with the 

soleplate of wired controller.  

If caliber of the communication cord is too large, which causes difficulty in leading or sticking the cord according to above 
point 2 and point 4, strip some of the sheath of the communication cable to meet the installation requirement. 

(2) Linkage Controller LE60-24/H1 Installation Method: 

According to actual condition, install the linkage controller in an appropriate place indoors, and 

secure it with 2 screws. If necessary, push plastic expansion tubes into the wall before secure it with 

screws. 

Installation Means 

30 

Sayfa 36

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2.2.3 Removal Method 

Wired Controller XE7C-23/H Disassembly diagram: 

Disassembly diagram of wired controller XE7C-23/H 

2.2.4 Connection of Communication Cord 

There are 2 ways to connect wired controller with indoor units’ network. 

Each indoor unit has to be connected with a R32 safety system compatible wired controller. These 

wired controllers have implemented safety measures that will warn the user visually and audibly in case 

of a leak. 

One wired controller                    Two wired controllers 

control one indoor unit                 controls one indoor unit 

31 

Sayfa 37

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3 Remote Controller 

3.1 Remote Controller YAP1F 

Button name and function introduction  

No. 
Button name 
Function 

1 
ON/OFF 
Turn on or turn off the unit 

2 
TURBO 
Set turbo function 

3 
MODE 
Set operation mode 

4 
 
Set up&down swing status 

5 
I FEEL 
Set I FEEL function 

6 
TEMP 
Switch temperature displaying type on the unit’s display 

7 
 
Set health function and air function 

8 
LIGHT 
Set light function 

9 
X-FAN 
Set X-FAN function 

10 
SLEEP 
Set sleep function 

11 
CLOCK 
Set clock of the system 

12 
T-OFF 
Set timer off function 

13 
T-ON 
Set timer on function 

14 
 
Set left&right swing status 

15 
FAN 
Set fan speed 

16 
/
 
Set temperature and time 
 

1

2
3

16
15

4

14
13
12

5
6
7

11

8

10
9

32 

Sayfa 38

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4 Introduction to Unit Functions 

Function Application of IDUs 

Indoor unit functions cover user operation functions and engineering application functions. For user 

operation functions, refer to operating instructions of the IDU, wired controller, and remote controller. 

Engineering application functions include: 

SN 
Function Name 

1 
Main IDU query and settings 

2 
Indoor unit project number query and settings 

3 
Parameter View 

4 
User parameter settings 

6 
Project parameter settings 

Engineering application functions can be operated through the IDU wired controller XE7C-23/H. 

4.1 Engineering Application Functions Operated through the XE7C-23/H 
Wired Controller 

4.1.1 Main IDU Settings 

The main IDU can be set through the wired controller or remote controller. The methods for setting 

the main IDU through the wired controller are as follows:  

Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. 

Press “
” or “
” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button 

to go into user parameter setting page. 

After that, press “
” or “
” button to select the item “Main IDU”.  

When selecting the parameter, press “ ” or “ ” button to select the setting value “Yes”. Press 

“MENU/OK” button to save corresponding setting item. If the setting can’t be confirmed, switching the 

item can restore the previous setting value.  

 If the main IDU setting is successful, "
" icon will display on the homepage of wired controller . 

4.1.2 Main IDU Display 

For IDUs connected with wired controllers, "
" on the wired controller connected with the main IDU 

will be on. 

For IDUs embedded or connected with LED panels, the operation LED on the LED panel of the main 

IDU will blink three times. 

After the main IDU is successfully set, stick the “

convenience of user operation and engineering maintenance. This flag is placed in the package bag of 

the ODU. 

4.1.3 Project Number Query and Settings 

(1) IDU Project Number View and Locating  

Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “View”, and then press “MENU/OK” button to enter into the view 

MASTER ” flag to the wired controller or unit panel for 

33 

Sayfa 39

GREE                                                Multi Variable Air Conditioners Indoor Unit  

page. 

Press “
” or “
” button to select “IDU Project No. View and Locating” at the view page. Then press 

“MENU/OK” button to enter into “IDU Project No. View and Locating” page to see IDU project number. 

Synchronously, the double-eight digital LED of the IDU embedded displays its own project number. If the 

current wired controller works in one-to-many mode, you can press the “ ” or “ ” button to switch indoor 

unit number, view each indoor unit corresponding project number.  

It is normal if the buzzer of the IDU operated by the wired controller rings. The purpose of ringing the 

buzzer is to facilitate engineering commissioning personnel to locate the IDU, especially for the IDU 

without any LED panel because it cannot display its project number. 

(2) View All IDU Project Number 

Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “View”, and then press “MENU/OK” button to enter into the view 

page. 

Press “
” or “
” button to select “View All IDU Project No.” at the view page. Then press “ ” or “ ” 

button to select turn on or turn off this function. And press “MENU/OK” button to confirm it. When turn on 

the “View All IDU Project No.”, the status column on the homepage of each wired controller in the entire 

network displays the project number of the corresponding IDU. Synchronously, the double-eight digital 

LED of each IDU embedded or connected with an LED panel displays its own project number. 

Method for quitting query: Press the “
” button on any wired controller in the network. 

(3) Project number settings of IDU 

Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. 

Press “
” or “
” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button 

for 5s to go into parameter setting page. 

Press “
” or “
” button to select “Project Parameter” at the parameter setting page, and then press 

“MENU/OK” button to enter into the project parameter setting page. 

After that, press “
” or “
” button to select the item “IDU Project No. Setting”. If the current wired 

controller works in one-to-many mode, you can press the “ ” or “ ” button to switch indoor unit number. 

When selecting the parameter, press “MENU/OK” button to enter into the IDU project No. setting 

page. Then press “
” or “
” or “ ” or “ ” button to switch the project number. Hold it can switch it quickly. 

Press “MENU/OK” button to save this setting. 

4.1.4 Parameter View 

Parameters can be queried in power-on or power-off status. 

Press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “View”, and then press “MENU/OK” button to enter into the view 

page. 

Press “
” or “
” button to select “Parameter View” at the view page. Then press “MENU/OK” button 

to enter into parameter view page. 

34 

Sayfa 40

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Press “
” or “
” button to switch the items.  

When viewing the indoor unit, if the current wired controller works in one-to-many mode, press “ ” 

or “ ” button to switch indoor units. Corresponding indoor unit’s parameters will be displayed on the page.  

When viewing the outdoor unit, if there are multiple outdoor unit, press “ ” or “ ” button to switch 

outdoor units. Corresponding outdoor unit’s parameters will be displayed on the page. 

The parameter view list is as follows: 

Parameter Name 
Range 
Parameter Name 
Range 

Wired Controller’s Address 
1,2 
No. of IDUs Wired to 

Main IDU’s Project No. 
0,1~255 
Time Left to Clean Filter 
0~416 days 
Online IDUs of CAN1 
1~100 
CAN2 address 
1~255 

Max Distribution Ratio 

IDU Error History 
5 historical errors 
Prior Operation 
Yes, No 
Indoor Temp 
-30°C -139°C 
Relative Humidity 
 0%~100% 
Inlet Temp 1 
-30°C -139°C 
Outlet Temp 1 
-30°C -139°C 
Inlet Temp 2* 
-30°C -139°C 
Outlet Temp 2* 
-30°C -139°C 

IDU Capacity 
IDU capacity and capacity 

Fresh Air IDU Output Temp* 
-30°C -139°C 
Indoor Unit Fan Static 

R32 Refrigerant 

Concentration 
0%~100% 
ODU Static Pressure 
0~4 

ODU Error History 
5 historical errors 
 
 
The following parameters can only be viewed from the master wired controller, they cannot be viewed from the slave 

wired controller 
Parameter Name 
Range 
Parameter Name 
Range 
Unit Code 
0~9, A~Z, a~z, - 
Board Code 
0~9, A~Z, a~z,- 
Outdoor Temp 
-30~139°C 
Comp1 Operation Freq. 
0~200Hz 
Comp 2 Operation Freq. 
0~200Hz 
ODU Fan Operation Freq. 
0~100Hz 
High Pressure Sat. Temp 
-40~70°C 
Low Pressure Sat. Temp 
-69~38°C 
Comp1 Discharge Temp 
-30~150°C 
Comp 2 Discharge Temp. 
-30~150°C 
Comp 3 Discharge Temp 
-30~150°C 
Comp 4 Discharge Temp. 
-30~150°C 
Comp 5 Discharge Temp 
-30~150°C 
Comp 6 Discharge Temp. 
-30~150°C 
Comp 3 Operation Freq. 
0~200Hz 
ODU Heating EXV1 
0~48 
ODU Heating EXV2 
0~48 
Subcooler EXV 
0~48 
Defrost Temp 
-30~139°C 
Subcooler Liquid Temp 
-30~139°C 
Separator Outlet Temp 
-30~139°C 
Oil Return Temp 
-30~139°C 
Condenser Inlet Temp 
-30~139°C 
Condenser Outlet Temp 
-30~139°C 

① Under parameter viewing status, the signal from remote controller is invalid. 

② When the parameter is invalid, it will display “--”. 

4.1.5 User Parameter Settings 
User parameters can be set in power-on or power-off status. 

Press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. 

Press “
” or “
” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button 

to go into user parameter setting page. 

After that, press “
” or “
” button to switch the items. Hold it can switch it quickly. 

When selecting the parameter, press “ ” or “ ” to switch the setting value. Press “MENU/OK” button 

to save corresponding setting items. If the setting can’t be confirmed, switching the item can restore the 

Parameter View List 

Controller 
1~16 

110% 
135% 
150% 
Cool & Heat Modes 
Cool Only, Heat Only, Cool 

& Heat, Fan 

after adjustment 
IDU EXV Status 
0~20 

Pressure 
0~999 

35 

Sayfa 41

GREE                                                Multi Variable Air Conditioners Indoor Unit  

previous setting value. 

The user parameter setting list is as follows: 

User Parameter Setting List 

Item 
Settable 

range 
Default  
Remarks  

When it is set as no, this wired controller is slave wired controller. Status 
column of the homepage displays the icon of slave wired controller “
” . 
The wired controller can only activate the main wired controller. It does not 
have the function of setting parameters for other units. 

Main Wired 

Controller 
Yes, No 
Yes 

Once it is activated, the current IDU is set to be the main IDU. When the 
setting is Yes, if the system mode priority is the master-slave mode, the 
status column in homepage will display the icon of main IDU “
”; when the 
setting is off, master and slave status of the current IDU will not be 
changed. 

Main IDU 
Yes, No 
No 

Use Remote 
Yes, No 
Yes 
When it is set as no, the wired controller cannot receive the remote control 
signal. It can only be operated with buttons. 

Prior 
Operation 
Yes, No 
No 
When the power supply is insufficient, it is allowed to turn on the designated 
IDU as preferential operation; other IDUs should be forced to be off. 

High Ceiling 

Installation* 
Yes, No 
No 
Only applicable to cassette type IDU 

After setting the linkage function, the fresh air IDU will automatically turn on 
or turn off along with the on and off of general IDU. Meanwhile, users can 
manually turn on or turn off the unit. 
It only applicable to fresh air IDU. 

Link with 
Fresh Air 

Yes, No 
No 

IDU* 

After it is successfully set, adjust the revolving speed to ensure the air 
volume is close to or the same as the previous air volume. 
It is only applicable to the unit with PM2.5 filter. 

PM2.5 Filter* 
Yes, No 
No 

Yes: Temp 
and humidity 

Refer to 

Temp and 

indoor 
unit for 

correction 

RH 
Correction 

control  
No: Ambient 
temperature 

It can be set only when it’s supported by the indoor unit.  

the 
defaulted 

Control 

value  

control  

Yes: 
Humidity 

Dry Mode 

If select “yes”, set humidity is displayed under dry mode. Otherwise, set 
temperature is displayed. It can only be set when it’s supported by the 
indoor unit.  

control 

Humidity 

No 

No: 
Temperature 

Control 

control 

Clear Filter 

Cleaning 

Yes, No 
No 
— 

Time 

Indoor Fan 

Static 
Pressure 

1~9 
5 
— 

0: This 
function is 
unavailable 

No. of IDUs 

Wired to 
Controller 

1 
Set corresponding value according to the connected quantity of IDU. 

1-16: 
quantity of 

IDU 

Angle 1 
Angle 2 
Angle 3 

Angle of Air-
return Board* 

Angle 2 
Only applicable to the model with air-return plate. 

25°C 
(77°F) 
Cooling temperature of auto mode – heating temperature of auto 
mode≥1°C. 
Heating temp 
of Auto Mode 

Cooling temp 
of Auto Mode 

17°C~30°C 
(63°F~86°F) 

16°C ~29°C 
(61°F~84°F) 

20°C 
(68°F) 

Resume 

When it is set as No, it will keep the status after inserting the gate control 
card. If it is at OFF status when pulling out the card, when inserting the 
card, it is still at OFF status. 

After 
Inserting 

Yes, No 
Yes 

Card 

36 

Sayfa 42

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Item 
Settable 

range 
Default  
Remarks  

Cold air prevention time is the max waiting time from the time turning on the 
heating mode to the time blowing out the hot wind. The actual waiting time 
is related to the outdoor ambient temperature. If there is cold air after 
turning on the heating mode in the actual operation, please consult the 
professional person to adjust this parameter. 

Time for IDU 

180s, 300s,  
420s, 600s 
180s 

Cold Air 
Prevention* 

Set Temp of 

10°C ~30°C 
(50°F~86°F) 

16°C 
(61°F) 

Note: It’s only applicable for the units whose dry mode is with humidity 
control function.  

RH Control 

Mode 

01: Normal  
02: Quick  
03: Deep 
1 
Note: Only applicable to the unit with auto clean function. 
 If “0” is displayed, this function is not available for this unit.  

Auto Clean 

Mode 

Cooling 
Temp of 
Fresh Air 

16°C ~30°C 
(61°F~86°F) 

18°C 
(64°F) 
Only applicable to fresh air IDU. 

IDU* 

Heating 
Temp of 
Fresh Air 

16°C ~30°C 
(61°F~86°F) 

22°C 
(71°F) 
Only applicable to fresh air IDU. 

IDU* 

Setback 
Yes, No 
No 
— 

Upper Temp 

26°C 
(79°F) 
When temperature unit is °C, temperature upper limit – temperature 
lower limit ≥ 4°C; 
When temperature unit is °F, temperature upper limit – temperature 
lower limit ≥7°F. 
Lower Temp 

20~30°C 
(68~86°F) 

Limit of 
Setback 

16~26°C 
(61~79°F) 

20°C 
(68°F) 

Limit of 
Setback 

0: Normal 
Auto Wind 
1: Heating 
Wind 
Sensing 

Auto Fan 

0 
— 

Setting 

Wind 

When Aux heating is available, the home status bar displays the “
” 
icon; when Aux heating is running, the home status bar displays the 
“
” icon.  
Note:This feature is only applicable to high static pressure air handler 
indoor units. 

Enable Aux. 

Heat* 
Yes, No 
Yes 

Setpoint-

When the temperature difference between the ambient temperature and the 
set temperature exceeds the opening temperature difference, AUX heating 
is allowed to start. 
Note:This feature is only applicable to high static pressure air handler 
indoor units. 

Space 
Temperature 

1~10 
3 

Differential 

for Aux. 

Heat* 

After the heat pump operation meets the start time, AUX heating is allowed 
to turn on. 
Note:This feature is only applicable to high static pressure air handler 
indoor units. 

Aux. Heat 
ON Timer * 
0min~60mins 2mins 

Satisfy Room 

Yes, No 
No 
Note:This feature is only applicable to high static pressure air handler 
indoor units. 

Temperature 

with AUX* 

In parameter setting status, signals of the remote controller are invalid. 

4.1.6 Project Parameter Settings 

Engineering parameters can be set in power-on or power-off status. 

Press “MENU/OK” button on the homepage to enter into the menu page.  

Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. 

Press “
” or “
” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button 

37 

Sayfa 43

GREE                                                Multi Variable Air Conditioners Indoor Unit  

for 5s to go into parameter setting page. 

Press “
” or “
” button to select “Project Parameter” at the parameter setting page, and then press 

“MENU/OK” button to enter into the project parameter setting page. 

After that, press “
” or “
” button to switch the items. Hold it can switch it quickly. 

When selecting the parameter, press “ ” or “ ” to switch the setting value. Press “MENU/OK” button 

to save corresponding setting items. If the setting can’t be confirmed, switching the item can restore the 

previous setting value. 

The project parameter setting list is as follows: 

Project Parameter Setting List 

Item 
Settable range 
Default  
Remarks  

No: standby after power-down recovery 
Yes: restoring the original status after power-down 
recovery 

Memory 
Yes、No 
Yes 

System Energy-

Saving 
Yes、No 
No 
— 

Constant Air Volume 

Debugging* 
Yes、No 
No 
— 

When the number of online indoor units is greater 
than 1, press “ ” or “ ” to switch indoor units, 
press the “MENU/OK” key to enter the project 
number setting of the selected indoor unit: press 
“ ” or “ ” to increase/decrease the project 
number by the unit digit. Press “ ” or “ ” to 
increase/decrease the project number by the tenth 
digit. 

IDU Project No. 

Setting 
1-255 
— 

Off、10s、
20s、30s、
40s、50s、
60s 

Prevent Heat 
Accumulation 

Off 
It indicates the number of seconds for enabling 
the low-level fan every 15min. 

ODU Quiet Mode 
Off、1~12 
— 
Top discharge outdoor unit defaults to Off, side 
discharge outdoor unit defaults to 12 

Capacity Upper Limit 
100%、90%、
80% 
100% 
— 

-40、-30、-
20、-10、0、
10、20、30、
40 

IDU Capacity 

0 
— 

Adjustment 

Press “ ” or “ ” to adjust the minimum opening 
degree. Press and hold “ ” or “ ” for 5 seconds, 
the minimum opening degree will increase or 
decrease by single digit. Press and hold for 5 to 
10 seconds, the minimum opening degree will 
increase or decrease by ten digits. 
After the default minimum opening degree for 
heating breakdown is manually modified, the 
opening degree remains unchanged upon heating 
breakdown. 

Min Pulse of EXV 
Auto、1~500 
Auto 

10mins、
15mins、
20mins 
15mins 
— 

Max Defrosting Time 

Standard、

Rapid Defrost Mode* 

Rapid1、

Standard 
— 

Rapid2 

Force Defrost 
Yes、No 
No 
— 

38 

Sayfa 44

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Item 
Settable range 
Default  
Remarks  

40mins、
50mins、
60mins 
50mins 
— 

Defrosting Cycle K1 

1:Return Air; 
2:Wired Controller; 
3:Cool:Return Air,  Heat:Wired Controller; 
4:Cool:Wired Controller,  Heat:Return Air 

Amb Temp Sensor 

Location 
1、2、3、4 
3  

Temperature sensor of 

Amb Temp Sensor 

unit: 0°C; temperature 

Cool Revise 
-15℃~+15℃ 

— 

sensor of wired 

controller: 0°C 

Temperature sensor of 
unit: -2°C; temperature 

Amb Temp Sensor 

Heat Revise 
-15℃~+15℃ 

— 

sensor of wired 

AHRI IDU Fan Speed* 
100~1800 
— 
— 

Heating to Temp Fan 

Status 
Stop、Breeze 
Breeze 
— 

Display Ambient 
Temp on Homepage 
Yes、No 
No 
— 

Function Setting of 

Lifting Panel* 
On、Off 
Off 
Only applicable for 360°air discharge cassette 
indoor unit. 

Cooling to Temp Fan 

Setting* 
Yes、No 
No 
This feature is only applicable to the indoor units 
that have this function set. 

IDU High and Low 

None、High、

Low 
None 
— 

Level Status* 

Control Method of 
Constant Temp Mode* 

Mode1、

Mode2 
Mode1 
— 

Fresh Air IDU Static 

Pressure* 
1~13 
8 
Only applicable to DC Fresh Air Indoor Unit. 

Lowest Air Outlet 
Temperature Can Be 

8℃~16℃ 
16℃ 
This setting can only be done when the indoor unit 
is a fresh air processing indoor unit.  

Set* 

Delayed Startup of 

0s、20s、
40s、60s、
80s 
0s 
This feature is only applicable to the indoor units 
that have this function set. 

Indoor Fan Under 

Cooling Mode* 

Default 0, indoor unit reports refrigerant leak fault, 

automatically changes to 1 after meeting the unit 

requirements, automatically changes to 0 after 

Locked Status of 
Refrigerant Leakage 
0、1 
0 

indoor unit refrigerant leak fault recovery. 

Manually set from 1 to 0, clear the indoor unit’s 

refrigerant leak fault. 

Item with “*” are reserved parameter. 

In parameter setting status, signals of the remote controller are invalid. 

4.1.7 Error Display 

When there is error during operation, the temperature display zone on the wired controller will show 

the error code. If several errors happen at the same time, error codes will show on the display repeatedly.  

If error occurs, please turn off the unit and ask for professionals to repair it.  

The following figure shows the display of outdoor unit high pressure protection when unit is on. 

39 

Sayfa 45

GREE                                                Multi Variable Air Conditioners Indoor Unit  

When the wired controller is connected with a Fresh Air Indoor Unit, fresh air indoor unit code “FAP” 

will be displayed as shown below. Setting temperature won’t be displayed and can’t be adjusted via “
” 

or “
” button. The air outlet temperature in cooling or heating can only be set in the parameter setting 

status. 

Display of Outdoor Unit High Pressure Protection 

40 

Sayfa 46

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4.2 Engineering Application Functions Operated through the YAP1F 
Remote Controller 

4.2.1 The method for setting the master IDU through the YAP1F remote controller is 
as follows 

No. 
Button name 
Function 

1 
ON/OFF 
Turn on or turn off the unit 

2 
TURBO 
Set turbo function 

3 
MODE 
Set operation mode 

4 
 
Set up&down swing status 

5 
I FEEL 
Set I FEEL function 

6 
TEMP 
Switch temperature displaying type on the unit’s display 

7 
 
Set health function and air function 

8 
LIGHT 
Set light function 

9 
X-FAN 
Set X-FAN function 

10 
SLEEP 
Set sleep function 

11 
CLOCK 
Set clock of the system 

12 
T-OFF 
Set timer off function 

13 
T-ON 
Set timer on function 

14 
 
Set left&right swing status 

15 
FAN 
Set fan speed 

16 
/
 
Set temperature and time 

For details about the above figures, refer to the instructions 66174100016. 

Perform settings by pressing “▲” and “▼” in air supply mode: 

(1) Set the temperature to 30°C. 

41 

Sayfa 47

GREE                                                Multi Variable Air Conditioners Indoor Unit  

(2) Press “▼” and then “▲” in five seconds. Repeat this operation for three times. 

After successful settings, “UC” is displayed on the receiving indicator panel of the remote controller 

for five seconds and “
” is displayed on the wired controller. 

4.2.2 IDU Project Number Query by Remote Controller YAP1F 

(1) Query method for project number of single IDU: 

Enter query: 

Under fan mode, set temperature in 16°C, press “Light” button for 5 times continuously within 5 

seconds and then the IDU light board will display its project number.  

Exit query: 

1) 
After entering query status, press “Light” button for 5 times continuously within 5 seconds 

to exit query status. 

2) 
After 30min, it will exit query status automatically and display normal status. 

(2) Query method for project numbers of all IDUs in a single system: 

Enter query: 

Under fan mode, set temperature in 30°C, press “Light” button for 5 times continuously within 5 

seconds and then the light boards of all indoor units will display their project numbers respectively. 

Exit query: 

1) 
After entering query status, press “Light” button for 5 times continuously within 5 seconds 

to exit query status. 

2) 
After 30min, it will exit query status automatically and display normal status. 

4.2.3 Common Remote controller recovery refrigerant leakage fault 

In the startup and Fan modes, the Remote controller shall operate the light key for 5 consecutive 

times within 5 seconds at the interface with the set temperature of 20 ℃(68℉) to clear the refrigerant 

leakage fault of the internal unit. 

42 

Sayfa 48

GREE                                                Multi Variable Air Conditioners Indoor Unit  

INSTALLATION 

43 

Sayfa 49

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1 Engineering Installation Preparation and Notice 

1.1 Installation Notice 

All phases of this installation must conform to NATIONAL, STATE AND LOCAL CODES. If it is 

required for additional information, please contact your local distributor. 

Personnel and property safety are highly concerned during the entire installation process. Installation 

implementation must abide by relevant national safety regulations to ensure personnel and property 

safety.  

All personnel involved in the installation must attend safety education courses and pass 

corresponding safety examinations before installation. Only qualified personnel can attend the installation. 

Relevant personnel must be held responsible for any violation of the regulation. 

1.2 Installation Key Points and Importance 

VRF air conditioning systems use refrigerant, instead of other agent, to directly evaporate to carry 

out the system heat. High level of pipe cleanness and dryness is required in the system. Since various 

pipes need to be prepared and laid out onsite, carelessness or maloperation during installation may leave 

impurities, water, or dust inside refrigerant pipes. If the design fails to meet the requirement, various 

problems may occur in the system or even lead to system breakdown. 

Problems that usually occur during installation are as follows: 

No. 
Installation Problem 
Possible Consequence 

1 
Dust or impurities enter into 
the refrigeration system. 

Nitrogen is not filled into the 
refrigerant pipe or 
insufficient Nitrogen is filled 
before welding. 

2 

3 
The vacuum degree in the 
refrigerant pipe is 
insufficient. 

4 
Water enters into the 
refrigeration system. 

The refrigerant pipe 
specifications do not meet 
the configuration 
requirements. 

5 

6 
Refrigerant pipe is blocked. 

7 
Refrigerant pipe exceeds 
the limit. 

8 
Incorrect amount of 
refrigerant is filled. 

9 
The refrigerant pipe leaks. 

CHAPTER 3 INSTALLATION 

Pipes are more likely to be blocked; air conditioning performance is reduced; 
compressor wear is increased or even hinder the normal operation of the system 
and burn the compressor. 

Pipes are more likely to be blocked; air conditioning performance is reduced; 
compressor wear is increased or even hinder the normal operation of the system 
and burn the compressor. 

The refrigeration performance is reduced. The system fails to keep normal operation 
due to frequent protection measures. When the problem getting serious, compressor 
and other major components can be damaged. 

Copper plating may appear on the compressor and reduce the compressor 
efficiency with abnormal noise generated; failures may occur in the system due to 
ice plug. 

Smaller configuration specifications can increase the system pipe resistance and 
affect the cooling performance; larger configuration specifications are waste of 
materials and can also reduce the cooling performance. 

The cooling performance is reduced; in certain cases, it may cause long-term 
compressor operating under overheat conditions; the lubricating effect can be 
affected and the compressor may be burnt if impurities were mixed with the 
lubricating oil. 

The loss in pipe is considerable and the unit energy efficiency decreases, which are 
harmful for long-term running of the system. 

The system cannot correctly control the flow allocation; the compressor may be 
operating under over-heating environment or running when the refrigerant flows 
back to the compressor. 

Insufficient refrigerant circulating in the system decreases the cooling performance 
of the air conditioner. Long-term operation under such circumstance may cause an 
overheating compressor or even damage the compressor. 

44 

Sayfa 50

GREE                                                Multi Variable Air Conditioners Indoor Unit  

No. 
Installation Problem 
Possible Consequence 

10 
Water drainage from the 
condensate water pipe is 
not smooth. 

The ratio of slop for 
condensate water pipe is 
insufficient or the 
condensate water pipe is 
incorrectly connected. 

11 

12 
The air channel is 
improperly fixed. 
The air channel will deform; vibration and noise occur during unit operating. 

13 
The guide vane of air 
channel is not reasonably 
manufactured. 

The refrigerant pipe or 
condensate water pipe does 
not meet the insulation 
requirement. 

14 

15 
The installation space for 
IDU is insufficient. 

The IDU or the location of 
the air outlet or return air 
inlet is not designed 
reasonably. 

16 

17 
The ODU is improperly 
installed. 

18 
Power cables are incorrectly 
provided. 
Unit components may be damaged and potential safety hazard may occur. 

Control communication 
cables are incorrectly 
provided or improperly 
connected. 

19 

20 
Control communication 
cables are not properly 
protected. 

Understand the special requirement (if any) for unit installation before implementation to ensure 

installation quality. Relevant installers must have corresponding engineering construction qualifications.   

Special type operators involved in the engineering implementation, such as welders, electricians, 

and refrigeration mechanics must have relevant operating licenses and are accredited with vocational 

qualification certification.   

2 Installation Materials Selection 

The materials, equipment and instruments used during air conditioning engineering construction 

must have certifications and test reports.  Products with fireproof requirements must be provided with 

fireproof inspection certificates and must meet national and relevant compulsory standards.  If 

environmentally-friendly materials are to be used as required by customers, all such materials must meet 

national environmental protection requirement and be provided with relevant certificates.   

(1) Only auxiliary devices approved by the appliance manufacturer or declared suitable with the 

refrigerant shall be installed in connecting ductwork;  

(2) Do NOT install operating ignition sources (example: open flames, an operating gas appliance or 

Residual water in IDUs can affect the normal operation of the system. The possible 
water leakage can damage the IDU's decoration. 

Reverse slop or inconsistent connection of condensate water pipe can hinder the 
smooth drainage and cause leakage of the IDU. 

Uneven air quantity allocation reduces the overall performance of the air conditioner. 

Water can easily condensate and drip to damage the indoor decoration, or even 
trigger the protection mode of system due to overheating operation. 

Since there is a lack of space for maintenance and checking, indoor decoration 
might need to be damaged during such operation. 

The air outlet or return air inlet may be short-circuited, thus affecting the air 
conditioning performance. 

The ODU is difficult to be maintained; unit exhaust is not smooth, which reduces the 
heat exchanging performance or even prevent the system from normal operation; in 
addition, the cold and hot air for heat exchange and the noise may annoy people in 
surrounding areas. 

The normal communication in the system fails or the control over IDUs and ODUs 
turn in a mess. 

The communication cables are short-circuited or disconnected, and the unit cannot 
be started up due to communication failure. 

45 

Sayfa 51

GREE                                                Multi Variable Air Conditioners Indoor Unit  

an operating electric heater) in the duct work.  

(3) Air inlet AND outlet are connected directly to the same room by ducting. Do NOT use spaces 

such as a false ceiling as a duct for the air inlet or outlet.  

(4) No auxiliary devices, which may be a potential ignition source, are installed in the duct work 

(example: hot surfaces with a temperature exceeding 700°C and electric switching device); 

2.1 Refrigerant Piping 

(1) Material requirement: Dephosphorization drawing copper pipe for air conditioners. 

(2) Appearance requirement: The inner and outer surface of pipe should be smooth without pinhole, 

crack, peeling, blister, inclusion, copper powder, carbon deposition, rust, dirt or severe oxide film, 

and without obvious scratch, pit, spot and other defects. 

(3) Test report: Certifications and quality test reports must be provided. 

(4) The tensile strength must be at least 240 kgf/mm². 

(5) After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed 

tightly by using pipe caps, plugs or adhesive tapes.  

2.2 Condensate Water Pipe 

(1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R 

pipe, PP-C pipe, and HDG steel pipe; 

(2) All relevant certificates and quality test reports are provided. 

(3) Requirements for specifications and wall thickness. 

Water supplying UPVC pipe:  

Φ32mm(1-1/4inch)×2mm(1/16inch), Φ40mm(1-3/4inch)×2mm(1/16inch), 

Φ50mm(1-15/16inch)×2.5mm(1/8inch). 

HDG steel pipe:  

Φ25mm(1inch)×3.25mm(1/8inch), Φ32mm(1-1/4inch)×3.25mm(1/8inch). 

Φ40mm(1-3/4inch)×3.5mm(1/8inch), Φ50mm(1-15/16inch)×3.5mm(1/8inch). 

2.3 Insulation Material 

(1) Rubber foam insulation material. 

(2) Flame retardancy level: B1 or higher. 

(3) Refractoriness: at least 120°C (248°F). 

(4) The insulation thickness of condensate water pipe: at least 10mm (3/8inch). 

(5) When the diameter of copper pipe is equal to or greater than Φ15.9mm(5/8inch), the thickness 

of insulation material should be at least 20mm(3/4inch); when the diameter of copper pipe is 

less than 15.9mm(5/8inch), the thickness of insulation material should be at least 15 

mm(5/8inch). 

46 

Sayfa 52

GREE                                                Multi Variable Air Conditioners Indoor Unit  

2.4 Communication Cable and Control Cable 

For air conditioning units installed in places with strong electromagnetic interference, 

shielded wire must be used as the communication cables of the IDU and wired controller, and shielded 

twisted pairs must be used as the communication cables between IDUs and between the IDU and ODU. 

Communication cable selection for ODU and IDUs 

Total Length L (m) of 
Communication Cable 
between Indoor Unit and 

Material Type 

Indoor (Outdoor) Unit 

Light/Ordinary 
polyvinyl chloride 

L≤1000m(L≤3280-5/6feet) 
≥2×0.75 
(2×AWG 18) 

sheathed cord. 

(60227 IEC 52 
/60227 IEC 53) 

Communication cable selection for IDU and wired controller 

Total length of 
communication line 
between indoor unit and 

Material type 

wired controller 

Light/Ordinary 
polyvinyl chloride 

sheathed cord. 

L≤100m(L≤328feet) 

(60227 IEC 52 
/60227 IEC 53) 

2.5 Power Cable 

Only copper conductors can be used as power cables. The copper conductors must meet relevant 

national standard and satisfy the carrying capacity of unit. 

2.6 Hanger Rod and Support 

(1) Hanger rod: M8 or M10. 

(2) U-steel: 14# or above. 

(3) Angle steel: 30mm (1-1/6inch)×30mm (1-1/6inch)×3mm (1/8inch) or above. 

Round steel: Φ10mm (4/10inch) or above. 
 
 

Wire size 
(mm2/AWG) 

Material 
Standard 
Remarks 

(1) If the wire diameter is enlarged to 2×1 

mm2 (2×AWG16), the total 
communication line length can reach 
1500 m (4921-1/4feet.). The average 
length of communication line between 
units is 12.5 m. 
(2) The cord shall be Circular cord (the 

IEC 60227-

5 

cores shall be twisted together). 
(3) If unit is installed in places with intense 

magnetic field or strong interference, it is 
necessary to use shielded wire. 

Wire 
size(mm2/A

Material 
Standard 
Remarks 

WG) 

(1) Total length of communication line can't 

exceed 100m(328feet.). The average 
length of the communication line 
between indoor unit and wired controller 
is 15m. 
(2) The cord shall be Circular cord (the 

2×0.75 
~2×1.25 
(2×AWG18 
~2×AWG16) 

IEC 
60227-5 

cores shall be twisted together). 
(3) If unit is installed in places with intense 

magnetic field or strong interference, it 
is necessary to use shielded wire. 

47 

Sayfa 53

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3 Installation of Indoor Unit 

3.1Installation of High Static Pressure Duct Type Indoor Unit 

3.1.1 Outline and Installation Dimension 

The following table lists the detailed dimensions. 

Model 
A 
B 
C 
D 
E 
F 
G 

GMV-ND07PHS/NhD-T(U) 
GMV-ND09PHS/NhD-T(U) 
GMV-ND12PHS/NhD-T(U) 
GMV-ND15PHS/NhD-T(U) 
GMV-ND18PHS/NhD-T(U) 
GMV-ND24PHS/NhD-T(U) 

1040 (40-
15/16) 
500 (19-
11/16) 
1130 (44-
1/2) 
300 (11-
13/16) 
754 (29-
11/16) 
1000 
(39-3/8) 

GMV-ND30PHS/NhD-T(U) 
GMV-ND36PHS/NhD-T(U) 
GMV-ND42PHS/NhD-T(U) 
GMV-ND48PHS/NhD-T(U) 
GMV-ND54PHS/NhD-T(U) 

1440 (56-
11/16) 
500 (19-
11/16) 
1540 (62-
5/8) 
300 (11-
13/16) 
754 (29-
11/16) 
1400 
(55-1/8) 

48 

Unit: mm(inch) 

700 (27-
9/16) 

700 (27-
9/16) 

Sayfa 54

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.1.2 Installation Space 

3.1.3 Installation Notice 

 
The unit shall be installed by the professional personnel according to this installation instruction 

to ensure proper use. 

 
Please contact the local Gree appointed service center before installation. Any malfunction 

caused by the unit that is not installed by the Gree appointed service center would probably not 

be dealt with on time because of the inconvenience of the business contact. 

 
It should be guided under the professional personnel when the air conditioner unit is moved to 

other place. 

 
Installation of the unit must be in accordance with National Electric Codes and local regulations. 

 
Improper installation will affect unit’s performance, so do not install the unit by yourself. Please 

contact local dealer to arrange professional technicians for the installation. 

 
Do not connect power until all installation work is finished. 

 
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a 

similarly qualified person in order to avoid a hazard. 

 
Air duct or grille fixed with screws must be installed at the air inlet or the air outlet of duct type 

unit. After installation, please make sure that human's hands are unable to touch inner parts of 

the unit. Installation and maintenance of the unit must be carried out by professionals. 

Unit: mm(inch) 

49 

Sayfa 55

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.2 Installation of Fresh Air Processing Indoor Unit 

3.2.1 Outline and Installation Dimension 

The following table lists the detailed dimensions. 

Model 
A 
B 
C 
D 
E 
F 
G 

GMV-NDX42P/NhD-T(U) 
GMV-NDX48P/NhD-T(U) 
GMV-NDX54P/NhD-T(U) 

1440 (56-
11/16) 
500 (19-
11/16) 
1540 (62-
5/8) 
300 (11-
13/16) 
754 (29-
11/16) 
1400 (55-
1/8) 
700 (27-
9/16) 

3.2.2 Installation Space 

 
3.2.3 Installation Notice 

(1) Installation of the unit must be in accordance with National Electric Codes and local safety 

regulations. 

(2) Improper installation will affect unit’s performance, so do not install the unit by yourself. Please 

50 

Unit: mm(inch) 

Unit: mm(inch) 

Sayfa 56

GREE                                                Multi Variable Air Conditioners Indoor Unit  

contact local dealer to arrange professional technicians for the installation. 

(3) Do not connect power until all installation work is finished.   

(4) Air duct or grille fixed with screws must be installed at the air inlet or the air outlet of duct type 

unit. After installation, please make sure that human's hands are unable to touch inner parts of 

the unit. Installation and maintenance of the unit must be carried out by professionals. 

3.3 Installation of Air Handler Type Indoor Unit 

3.3.1 Outline and Installation Dimension 

The following table lists the detailed dimensions. 

Unit: mm(inch)  

Model 
A 
B 
C 
D 
E 

GMV-ND60A/NhB-T(U) 
GMV-ND54A/NhB-T(U) 
GMV-ND48A/NhB-T(U) 

630 
(24-13/16) 

540 
(21-1/4) 

1320 
(51-15/16) 

295 
(11-5/8) 

508 
(20) 

508 
(20) 
GMV-ND30A/NhB-T(U) 
GMV-ND24A/NhB-T(U) 
GMV-ND18A/NhB-T(U) 
GMV-ND12A/NhB-T(U) 

540 
(21-1/4) 

540 
(21-1/4) 

1224 
(48-1/4) 

295 
(11-5/8) 

GMV-ND42A/NhB-T(U) 
GMV-ND36A/NhB-T(U) 

540 
(21-1/4) 

460 
(18-1/8 ) 

1105 
(43-1/2) 

295 
(11-5/8) 

508 
(20) 

3.3.2 Installation Notice 

When installing the air handler, take consideration to minimize the length of refrigerant tubing as 

much as possible. Do not install the air handler in a location either above or below the condenser that 

violates the instructions provided with the condenser. Service clearance is to take precedence. Allow a 

minimum of 24” in front of the unit for service clearance. When installing in an area directly over a finished 

ceiling (such as an attic), an emergency drain pan is required directly under the unit. See local and state 

codes for requirements. When installing this unit in an area that may become wet, elevate the unit with a 

sturdy, non-porous material. In installations that may lead to physical damage (i.e. a garage) it is advised 

to install a protective barrier to prevent such damage. 

This air handler is designed for a complete supply and return ductwork system. These duct type 

indoor units are used to supply conditioned air to one zone. Do not operate this product without all 

ductwork attached. 

Based upon the actual conditions, if air handler is installed as type (A), the air handler should be 

51 

Sayfa 57

GREE                                                Multi Variable Air Conditioners Indoor Unit  

concealed in a specific room or space and make sure the air handler is not accessible to the general 

public. 

Based upon the actual conditions, if air handler is installed as type (B), make sure that there is 

enough space for care and maintenance and the height between the air handler and ground is above 

2500mm. And the air handler is not accessible to the general public. 

       Type (A)                           Type (B) 

3.3.3 Electric Heater 

(1) The air handlers listed in this manual do not have factory installed electric heater. Electric heater 

is available as an accessory. Please refer to installation instructions provided with heater kit for 

the correct installation procedure. 

(2) Refer to the “installing electric heater” section of this manual and the instructions provided with 

the heater kit for the correct installation procedure. 

(3) The electrical characteristics of the air handler, the electric heater kit, and the supply power 

should be identical. This air handler does not have factory installed electric heater. Electric 

heater is available as an accessory. If installing this option, the only heater kits that can be used 

are the series as indicated below. It is forbidden to use the electric heater other than those 

recommended. 

(4) E-HEAT mode setting method: under off status, press “
” and “MENU/OK” button for 5s 

to turn on or turn off E-heat mode. After that, the wired controller control pop-up box shows 

"Enable Setting E-Heat Mode" or "Disable Setting E-Heat Mode" for 3s, and indoor unit can set 

“Electric heating mode”. When E-HEAT mode has been set and indoor unit operates under 

heating mode, if outdoor unit stops operation because of error, indoor unit will switch to operate 

under electric heating mode. 

(5) After the electric heater is shutdown, the fan of indoor unit will delay for a few minutes and then 

shut down so that the indoor unit can blow the waste heat and relieve the heat accumulation in 

the air duct. 

(6) During installation and debugging, pay attention to verify the switch sequence of electric heater 

and fan, ensure the fan must be turned on when electric heater operation and ensure the electric 

heater is turned off before the fan to avoid unsafe. 

52 

Sayfa 58

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.3.3.1 Electric heater kits available 

Model 
Electric heater 
Description 
Manufacturer of electric 

GMV-ND12A/NhB-T(U) 
GMV-ND18A/NhB-T(U) 
GMV-ND24A/NhB-T(U) 
GMV-ND30A/NhB-T(U) 

LYQ-08-A,21-4227-

01 
LYQ-08-C,21-4216-

Circuit breaker, 5 kW、10 kW electric 

heater 

03 

LYQ-08-A,21-4227-

01 
LYQ-08-C,21-4216-

GMV-ND36A/NhB-T(U) 
GMV-ND42A/NhB-T(U) 

Circuit breaker, 5 kW、10 kW、15 kW 

03 
LYQ-08-D,21-4217-

electric heater 

01 

LYQ-08-A,21-4227-

01 
LYQ-08-C,21-4216-

GMV-ND48A/NhB-T(U) 
GMV-ND54A/NhB-T(U) 
GMV-ND60A/NhB-T(U) 

Circuit breaker, 5 kW、10 kW、15 

03 
LYQ-08-D,21-4217-

kW、20 kW electric heater 

01 
LYQ-08-E,21-4228-

01 

3.3.3.2 Electric heater kits installation 

(1) Ensure that all power supply is disconnected prior to installing the heater kit.  

(2) A means of strain relief and conductor protection must be provided at the supply wire entrance 

into cabinet.  

(3) Use copper conductors only.  

(4) Installation must follow national electric code and other applicable codes.  

(5) If this appliance is installed in an enclosed area such as a garage or utility room with any carbon 

monoxide producing appliance, ensure the area is properly ventilated.  

1) Refer to the Table for appropriate heater kit. 

2) Check any physical damage, do not install damaged heater kit. 

3) Remove the upper access panel from air handler. 

4) Remove cover plate from air handler. 

5) Slide the heater kit in to the slot and secure element plate with previously removed screws. 

6) Before installing the electric heating, unplug the X1 terminal, and insert the plug-in terminals 

on the electric heating to the X1 and X2 terminals respectively. The power line of the unit is 

connected through an electrically heated circuit breaker. 

7) Insert power leads into the circuit breaker lugs or stripped red and black wires (for heater kit 

without circuit breaker) and tighten. 

8) Connect ground wire to ground lug; M6 screws are required for grounding screws when 

installing electric heating. 

9) Knock off appropriate area of the plastic circuit breaker cover on the access panel of the air 

handler. Knock off the holes according to the actual installation number and positions of circuit 

breakers. If circuit breaker is not installed, do not knock off the holes; otherwise, electric shock 

may occur. 

10) Replace access panel and check operation. 

53 

heater 

TUTCO 
Zhenjiang Dongfang 

Sayfa 59

GREE                                                Multi Variable Air Conditioners Indoor Unit  

11) Connection of power cords and thermostat wires. 

3.4 Installation of 360°Air Discharge Cassette Type Indoor Unit 

3.4.1 Outline and Installation Dimension 

The following table lists the detailed dimensions. 

Model 
A 
B 
C 
D 
E 

GMV-ND07T/NhD-T(U) 
GMV-ND09T/NhD-T(U) 
GMV-ND12T/NhD-T(U) 
GMV-ND15T/NhD-T(U) 
GMV-ND18T/NhD-T(U) 
GMV-ND24T/NhD-T(U) 
GMV-ND30T/NhD-T(U) 
GMV-ND36T/NhD-T(U) 
GMV-ND42T/NhD-T(U) 
GMV-ND48T/NhD-T(U) 

950(37-3/8) 
890(35) 
840(33-1/8) 
680(26-3/4) 
780(30-3/4) 

54 

Unit: mm(inch) 

Sayfa 60

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.4.2 Installation Space  

Model 
H 

GMV-ND07T/NhD-T(U) 
GMV-ND09T/NhD-T(U) 
GMV-ND12T/NhD-T(U) 
GMV-ND15T/NhD-T(U) 
GMV-ND18T/NhD-T(U) 

GMV-ND24T/NhD-T(U) 
GMV-ND30T/NhD-T(U) 
GMV-ND36T/NhD-T(U) 
GMV-ND42T/NhD-T(U) 
GMV-ND48T/NhD-T(U) 

3.4.3 Installation Notice 

 
The unit shall be installed in accordance with national standards or local regulations. 

 
Only qualified personnel can carry out installation work, please contact with local dealer before 

installation. 

 
Make sure all the installation work completed before energizing. 

 
The appliances are not accessible to general public. 

Unit: mm (inch) 

Unit: mm (inch) 

275(10-3/4) 

325(12-3/4) 

55 

Sayfa 61

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.5 Installation of 360°Air Discharge Compact Cassette Type Indoor Unit 

3.5.1 Outline and Installation Dimension 

Unit: mm (inch) 

Model 
A 
B 
C 
D 
E 
F 
G 

GMV-ND05T/NhE-T(U) 
GMV-ND07T/NhE-T(U) 
GMV-ND09T/NhE-T(U) 
GMV-ND12T/NhE-T(U) 
GMV-ND15T/NhE-T(U) 
GMV-ND18T/NhE-T(U) 

620 
(24-3/8) 

580 
(22-13/16) 

570 
(22-7/16) 

505 
(19-7/8) 

550 
(22-5/8) 

530 
(20-7/8) 

530 
(20-7/8) 

3.5.2 Installation Space  

Unit: mm (inch) 

56 

Sayfa 62

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
H 

GMV-ND18T/NhE-T(U) 
GMV-ND15T/NhE-T(U) 
GMV-ND12T/NhE-T(U) 
GMV-ND09T/NhE-T(U) 
GMV-ND07T/NhE-T(U) 
GMV-ND05T/NhE-T(U) 

3.5.3 Installation Notice 

 
The unit shall be installed by the professional personnel according to this installation instruction 

to ensure proper use. 

 
Please contact the local Gree appointed service center before installation. Any malfunction 

caused by the unit that is not installed by the Gree appointed service center would probably not 

be dealt with on time because of the inconvenience of the business contact. 

 
It should be guided under the professional personnel when the air conditioner unit is moved to 

other place. 

 
The unit shall be installed in accordance with national standards or local regulations. 

 
Only qualified personnel can carry out installation work, please contact with local dealer before 

installation. 

 
Make sure all the installation work completed before energizing. 

 
The appliances are not accessible to general public. 

3.6 Installation of 1-way Cassette Type Indoor Unit 

3.6.1 Outline and Installation Dimension 

Unit: mm (inch) 

305(12) 

Unit: mm (inch) 

57 

Sayfa 63

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.6.2 Installation Space 

Model 
H 

GMV-ND07TD/NhA-T(U) 
GMV-ND09TD/NhA-T(U) 
GMV-ND12TD/NhA-T(U) 

3.6.3 Drainage Pipe Installation 

The installation height of raising pipe for drainage should be lower than B. The gradient from 

raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe is vertical with the 

unit, the raising height should be less than C. 

Model 
A 
B 
C 
GMV-ND07TD/NhA-T(U) 
GMV-ND09TD/NhA-T(U) 
GMV-ND12TD/NhA-T(U) 

100(3-15/16) 
1100(43-5/16) 
1050(41-5/16) 

58 

Unit: mm (inch) 

Unit: mm (inch) 

207(8-1/8) 

Unit: mm (inch) 

Unit: mm (inch) 

Sayfa 64

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.6.4 Installation Notice 

 
The unit shall be installed by the professional personnel according to this installation instruction 

to ensure proper use. 

 
Please contact the local Gree appointed service center before installation. Any malfunction 

caused by the unit that is not installed by the Gree appointed service center would probably not 

be dealt with on time because of the inconvenience of the business contact. 

 
It should be guided under the professional personnel when the air conditioner unit is moved to 

other place. 

 
The unit shall be installed in accordance with national standards or local regulations. 

 
Only qualified personnel can carry out installation work, please contact with local dealer before 

installation. 

 
Make sure all the installation work completed before energizing. 

3.7 Wall Mounted Type Indoor Unit 

3.7.1 Outline and Installation Dimension 

Below are dimensions of W, H, D for different models:                                                   

        Item 
Model 
W 
H 
D 

GMV-ND06G/NhA1C-T(U)  
GMV-ND07G/NhA1C-T(U) 
GMV-ND09G/NhA1C-T(U) 
GMV-ND06G/NhA3C-T(U)  
GMV-ND07G/NhA3C-T(U) 
GMV-ND09G/NhA3C-T(U) 

867(34-1/8) 
276(10-7/8) 
206(8-1/8) 

GMV-ND12G/NhA1C-T(U) 
GMV-ND14G/NhA1C-T(U) 
GMV-ND12G/NhA3C-T(U) 
GMV-ND14G/NhA3C-T(U) 

978(38-1/2) 
333(13-1/8) 
248(9-3/4) 

GMV-ND18G/NhA1C-T(U) 
GMV-ND24G/NhA1C-T(U) 
GMV-ND18G/NhA3C-T(U) 
GMV-ND24G/NhA3C-T(U) 

1116(43-15/16) 
333(13-1/8) 
248(9-3/4) 

59 

Unit: mm (inch) 

Unit: mm(inch) 

Sayfa 65

GREE                                                Multi Variable Air Conditioners Indoor Unit  

3.7.2 Installation Space 

3.7.3 Installation Notice 

 
The unit shall be installed by the professional personnel according to this installation instruction 

to ensure proper use. 

 
Please contact the local Gree appointed service center before installation. Any malfunction 

caused by the unit that is not installed by the Gree appointed service center would probably not 

be dealt with on time because of the inconvenience of the business contact. 

 
It should be guided under the professional personnel when the air conditioner unit is moved to 

other place. 

 
Maintenance/service to be done by specialized personnel, mandated by the manufacturer or 

authorized representative. 

 
This appliance is intended to be used by expert or trained users in shops, in light industry and 

on farms or for commercial use by lay persons. 

 
This unit is a partial unit air conditioner, complying with partial unit requirements of this 

International standard and must only be connected to other units that have been confirmed as 

complying to corresponding partial unit requirements of this international standard. 

 
This unit shall only be connected to an appliance suitable for the same refrigerant. 

 
Make sure all the installation work completed before energizing. 

Unit: mm (inch) 

60 

Sayfa 66

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4 Installation of Connection Pipe 

① 
Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so 
is the height difference between indoor and outdoor units. Keep the number of bends as little as possible. 
Radius of curvature should be as large as possible. 
② 
Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for welding 
process. Rosin joint or pin hole is not allowed. 
③ 
When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm (8inch). Note 
that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch 
the pipe for more than 3 times at the same position. 

4.1 Flaring Process 

(1) Mechanical connectors used indoors shall comply with ISO 14903. When mechanical 

connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused 

indoors, the flare part shall be refabricated.  

(2) Pipework shall be protected from physical damage. 

(3) Installation of pipework shall be kept to a minimum space required.  

(4) Do NOT re-use joints and copper gaskets which have been used already.  

(5) Joints made in installation between parts of refrigerant system shall be accessible for 

maintenance purposes.  

(6) Install the refrigerant piping or components in a position where they are unlikely to be exposed 

to any substance which may corrode components containing refrigerant, unless the components 

are constructed of materials that are inherently resistant to corrosion or are suitably protected 

against corrosion.  

(7) After completion of field piping for split systems, the field pipework shall be pressure tested with 

an inert gas and then vacuum tested prior to refrigerant charging, according to the following 

requirements; field-made refrigerant joints indoors shall be tightness tested. The test method 

shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 

0.25 times the maximum allowable pressure. No leak shall be detected.  

(8) Use pipe cutter to cut the connection pipe in case it is unshaped. 

(9) Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after 

cutting. 

(10) Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use flaring tool 

to fix the flared nut into the pipe (as shown in Fig.4.1). 

(11) Check if the flared part is flaring evenly and if there is any crack.  

d2

d1

d2
90°±1°

d1

Fig. 4.1 

61 

Sayfa 67

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4.2 Pipe Bending 

(1) Reshape the pipe by hand. Be careful not to damage the pipe. 

(2) Do not bend the pipe over 90°. 

(3) If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch againch 

Therefore, do not bend or stretch the bend for over 3 times. 

(4) In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the insulating 

layer, as shown in Fig. 4.3. Do not bend the pipe until it is exposed. When bending is done, wrap 

the pipe with insulating layer and then secure it with adhesive tape. 

                 Fig. 4.2                                 Fig. 4.3 

4.3 Indoor Pipe Connection 

(1) Remove pipe cover and pipe plug. 

(2) Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut tightly 

by hand, as in Fig. 4.4 (Make sure indoor pipe is correctly connected. Improper location of the 

center will prevent flared nut from being securely twisted. Thread of nut will get damaged if the 

flared nut is twisted forcibly). 

(3) Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound (Hold 

the handle of wrench and make it at right angle to the pipe. as in Fig. 4.5). 

① 
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic tape. 

② 
Connection pipe should be supported by a bearer rather than the unit. 

③ 
The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use a pipe 
bender to bend the pipe. 
④ 
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case the 
capillary tube or other tubes have cracks and cause leakage. 

                              Fig. 4.4                   Fig. 4.5 

62 

Sayfa 68

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Pipe Diameter(mm/inch) 
Tightening Torque 

6.35(1/4) 
15-30N·m(11-22ft.-1b.) 

9.52(3/8) 
35-40N·m(26-29ft.-1b.) 

12.7(1/2) 
45-50N·m(33-37ft.-1b.) 

15.9(5/8) 
60-65N·m(44-48ft.-1b.) 

5 Installation of Drain Pipe 

5.1 Precautions When Doing the Piping Work 

 
Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that 

air may not remain trapped inside the pipe. 

For example: 

 
Keep pipe size equal to or greater than that of the connecting pipe.  

 
Install the drain piping as shown and take measures against condensation. Improperly rigged 

piping could lead to leaks and eventually wet furniture and belongings. 

 
When directly connecting a hard vinyl chloride pipe joint to the drain hose connected to the 

indoor unit, use a commercially available hard vinyl chloride pipe joint (nominal diameter 13mm 

(1/2 inch)).   

 
Drain hose connected to the indoor unit Commercially available hard vinyl chloride pipe joint 

(nominal diameter 13mm(1/2 inch)), Commercially available hard vinyl chloride pipe(nominal 

diameter 13mm(1/2 inch)) 

 
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia 

in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger. 

63 

Sayfa 69

GREE                                                Multi Variable Air Conditioners Indoor Unit  

5.2 Installing the Drain Pipes 

 
Insert the drain hose into the drain outlet, and tighten the clamp securely with tape. 

 
Tighten the clamp until the screw head is less than 4mm (3/16 inch) from the hose. 

 
Insulate the pipe clamp and the drain hose using heat insulation sponge. 

 
Install water trap as shown below. 

 
Install one water trap for each unit. 

 
Installation of water trap shall consider easy cleaning in the future. 

 
Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main pipe 

 
The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be 

connected in a manner as shown below: 

NO.1: 3-way connection of drainage pipe joint 

 Unit: mm (inch) 

64 

Sayfa 70

GREE                                                Multi Variable Air Conditioners Indoor Unit  

 
NO.2: Connection of drain elbow 

NO.3: Connection of horizontal pipe 

 
When unifying multiple drain pipes, install the pipes as shown below. Select converging drain 

pipes whose gauge is suitable for the operating capacity of the unit.(take the cassette type unit 

for example)  

Unit: mm (inch) 

65 

Sayfa 71

GREE                                                Multi Variable Air Conditioners Indoor Unit  

5.3 Precautions When Doing Riser Piping Work 

(1) Make sure that heat insulation work is executed on the following 2 spots to prevent any possible 

water leakage due to dew condensation. 

1) 
Connect the drain hose to the drain raiser pipe, and insulate them. 

2) 
Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp. 

(2) Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount 

supporting brackets at an interval of 1 -1.5 m (39-3/8~59in). 

5.4 Testing of Drain Piping  

 
After piping work is finished, check if drainage flows smoothly. 

 
Shown in the figure, add approximately 1liter of water slowly into the drain pan and check 

drainage flow during COOL running. 

6 Electrical Installation  

 
The wiring must be in accordance with the local rules. 

 
Rated supply voltage and special circuit for air conditioner must be used. 

 
Do not pull the power cord forcefully. 

 
All the electric installations must be carried out by specialist technicians in accordance with the 

local laws, rules and these instructions. 

 
The diameter of flexible wire should be wide enough. Replace the damaged power cord and 

connecting wire with special flexible wire. 

 
The earthing shall be reliable and connected to the special earthing device on the construction. 

The installation must be done by specialist technicians. The leak protection switch and air switch 

with enough capacity must be installed. The air switch shall have both the magnetic tripping and 

Unit: mm (inch) 

Unit: mm (inch) 

66 

Sayfa 72

GREE                                                Multi Variable Air Conditioners Indoor Unit  

thermal tripping functions to ensure protection against the short circuit and overload. 

 
The air conditioner belongs to I type electric appliances. The reliable earthed action is a must. 

 
The yellow and green wire inside the air conditioner is the earthed wire. Do not use it for other 

purpose or even cut off it. Do not fix it with tapping screw, Otherwise it may cause electric shock. 

 
There should be reliable earthed terminal for the power supply. Never connect the earth lead to 

the following articles: 

①water pipe; ②gas pipe; ③drain pipe; ④unreliable place considered by professionals. 

6.1 Locking Joint Installation of 360°Air Discharge Cassette Type Indoor 
Unit 

When the power cable and communication line of the unit are connected, the power cable and 

communication line need to be fixed through the side panel locking connector. The fixing process is as 

follows. 

(1) Attach the locking joint to the locking joint bracket. 

(2) Power cable (communication line) passes through the locking joint and the side plate engineering 

line over the wire crossing hole. 

(3) Finally, reattach the locking joint bracket to the side panel. 

67 

Sayfa 73

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.2 Locking Joint Installation of 360°Air Discharge Compact Cassette 
Type Indoor Unit 

When the power cord and communication cable of the unit are connected, the power cable and 

communication cable need to be fixed through the side panel locking connector. The fixing process is as 

follows. 

(1) Remove the locking joint bracket from the side panel. 

 
(2) Attach the locking joint to the locking joint bracket. 

(3) Power cable (communication line) passes through the locking joint and the side plate 

engineering line over the wire crossing hole. 

(4) Finally, reattach the locking joint bracket to the side panel. 

68 

Sayfa 74

GREE                                                Multi Variable Air Conditioners Indoor Unit  

MAINTENANCE 

69 

Sayfa 75

GREE                                                Multi Variable Air Conditioners Indoor Unit  

CHAPTER 4 MAINTENANCE 

1 Malfunction List  

1.1 Malfunction List for the Wired Controller  

Error 
Code 
Content 
Error 
Code 
Content 
Error 
Code 
Content 

L0 
Indoor Unit Error 
LA 
Indoor Units 
Incompatibility Error 
d9 
Jumper Cap Error 

L1 
Indoor Fan Protection 
LH 
Low Air Quality Warning 
dA 
Indoor Unit Network 
Address Error 

L2 
E-heater Protection 
LC 
ODU-IDU Incompatibility 
Error 
dH 
Wired Controller PCB 
Error 

L3 
Water Full Protection 
d1 
Indoor Unit PCB Error 
dC 
Capacity DIP Switch 
Setting Error. 

L4 
Wired Controller Power 
Supply Error 
d3 
Ambient Temperature 
Sensor Error 
dL 
Outlet Air Temperature 
Sensor Error 

L5 
Freeze protection 
d4 
Inlet Pipe Temperature 
Sensor Error 
dE 
Indoor Unit CO2 Sensor 
Error 

L7 
No Master Indoor Unit 
Error 
d6 
Outlet Pipe Temperature 
Sensor Error 
dy 
Water Temperature 
Sensor Error 

L8 
Power Insufficiency 
Protection 
d7 
Humidity Sensor Error 
C0 
Communication Error 

L9 
Quantity Of Group Control 
Indoor Units Setting Error 
d8 
Water Temperature Error 
AJ 
Filter Cleaning Reminder 

db 
Special Code: Field Debugging Code 

1.2 Display of Light Board (Only for Two-way Cassette Type Indoor Unit)  

The panel of this model is without nixie tube display. The error codes will be displayed through the 

power light, operation light and timer light; ○, ● and ◎ stand for on, off and blink respectively. 

Power light 
○ 
◎ 
◎ 
◎ 
◎ 

Operation light 
◎ 
● 
○ 
○ 
◎ 

Timer light 
● 
○ 
● 
○ 
● 

Error code display sheet 

Error code 
C0 
A0 
A3/A4 
L0 
L1 
L3 
L5 
d1 
d3 
d4 
d6 
d7 
E0 
db 

Power light 
◎ 
○ 
○ 
● 
● 
● 
○ 
◎ 
◎ 
◎ 
● 
○ 
● 
◎ 

Operation 

light 
◎ 
◎ 
○ 
● 
○ 
◎ 
● 
○ 
● 
◎ 
◎ 
◎ 
◎ 
● 

Timer light 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
○ 
○ 
○ 
● 
● 

Communicati
on error 

Ambient 
temperature 
sensor error

Inlet pipe 
temperature 
sensor error

Outlet pipe 
temperature 
sensor error

Humidity 
sensor error 

Outdoor unit 
error 

Defrosting/ 
oil return 

Indoor unit 
error 

Indoor unit 
PCB error 

Field 
debugging 
code

To be 
debugged 

Indoor fan 
protection 

Water full 
protection 

Freeze 
protection 

Error 
description 

70 

Sayfa 76

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.3 Exception Analyzing and Troubleshooting 

1.3.1 “d1” Indoor circuit board error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Check if the reading of address chip and memory chip of IDU mainboard is normal. If the data of 

address chip and memory chip cannot be read, it is abnormal 

Possible reason: 

 
Address chip is abnormal 

 
Memory chip is abnormal. Replace main control board directly 

Troubleshooting: 

Replace main control board directly 

1.3.2 “d3” Ambient temperature sensor error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 

the range of AD value, if the sampling AD value exceeds upper limit and lower limit in 5 seconds 

continuously, report the error 

Possible reason: 

 
Poor contact between ambient temperature sensor and terminal in mainboard interface 

 
Ambient temperature sensor is abnormal 

 
Detecting circuit is abnormal  

Troubleshooting: 

71 

Sayfa 77

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.3.3 “d4” Inlet pipe temperature sensor error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 

the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds 

continuously, report the error 

Possible reason: 

 
Poor contact between inlet pipe temperature sensor and terminal in mainboard interface 

 
Inlet pipe temperature sensor is abnormal 

 
Detecting circuit is abnormal 

Troubleshooting: 

1.3.4 “d6” Outlet pipe temperature sensor error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 

the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds 

continuously, report the error 

72 

Sayfa 78

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Possible reason: 

 
Poor contact between outlet pipe temperature sensor and terminal in mainboard interface 

 
Outlet pipe temperature sensor is abnormal 

 
Detecting circuit is abnormal 

1.3.5 “d7” Humidity sensor error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 

the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds 

continuously, report the error 

Possible reason: 

 
Poor contact between humidity sensor and terminal in mainboard interface 

 
Humidity sensor is abnormal 

 
Detecting circuit is abnormal 

73 

Sayfa 79

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Troubleshooting: 

 
1.3.6 “d9” Jumper cap error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Possible reason: 

 
If jumper cap model doesn’t match with mainboard, report the error 

 
Jumper cap is not installed 

 
Jumper cap model is wrong 

 
Detecting circuit is abnormal 

Troubleshooting: 

74 

Sayfa 80

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.3.7 “dA” IDU network address error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Through testing the IDU address chip and IP address, if address chip cannot be read, IDU IP is 0 or 

IP is in conflict, report the error. 

Possible reason: 

 
ODU allocated address is wrong 

 
IDU treatment is wrong 

 
Address chip is abnormal 

Troubleshooting: 

1.3.8 “dH” wired controller circuit board error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Wired controller IIC communication is abnormal 

Possible reason: 

 
Communication of wired controller touch button board and display board IIC is abnormal; 

 
Read and write of wired controller memory chip IIC is abnormal (when memory chip is existed); 

Troubleshooting: 

75 

Sayfa 81

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.3.9 “dC” Capacity DIP switch setting error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

If capacity DIP switch is set to the wrong position, report the error. 

Possible reason: 

 
Capacity DIP switch is set to the wrong position 

 
Detecting circuit is abnormal 

Troubleshooting: 

1.3.10 “dL” Air outlet temperature sensor error 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 

the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds 

continuously, report the error 

Possible reason: 

 
Poor contact between air outlet temperature sensor and terminal in mainboard interface 

 
Air outlet temperature sensor is abnormal 

 
Detecting circuit is abnormal 

76 

Sayfa 82

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Troubleshooting: 

1.3.11 “db” Project debugging 

Error display: ODU mainboard, IDU wired controller and IDU receive light board will display 

Error judgment condition and method: 

This is a status code of project debugging, not an error code. When IDU or ODU displays this code, 

it means the unit is under debugging status and the IDU cannot be operated.  

Troubleshooting: —— 

Possible reason:—— 

1.3.12 “L1” Indoor fan protection 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Check if the rotation speed of IDU is too slow, or it stops rotation, or protection signal of outdoor fan 

is transferred. If yes, it is judged that indoor fan protection occurs. 

Possible reason: 

 
Motor stops operation or it is blocked 

 
IDU mainboard is abnormal 

77 

Sayfa 83

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Troubleshooting: 

1.3.13 “L3” Water full protection  

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Check the status of IDU float switch. When water level is too high, float switch is activated, so water 

78 

Sayfa 84

GREE                                                Multi Variable Air Conditioners Indoor Unit  

full protection happens. 

Possible reason: 

 
IDU is installed improperly 

 
Drainage pump is broken 

 
Float switch operates abnormally 

 
IDU mainboard is abnormal 

Troubleshooting: 

79 

Sayfa 85

GREE                                                Multi Variable Air Conditioners Indoor Unit  

1.3.14 “L4” Power supply overcurrent protection 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Check if the power supply current from IDU to wired controller is normal. If power supply current is 

too big, it is judged that the current is abnormal. 

Possible reason: 

 
Power supply conducting wire of wired controller is short circuited 

 
IDU mainboard is abnormal 

 
Mainboard of wired controller is abnormal 

Troubleshooting: 

1.3.15 “L5” Freeze protection 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Check IDU pipe temperature. When pipe temperature is too low, freeze protection will be activated 

to prevent freezing damage of evaporator. 

Possible reason: 

 
IDU filter and evaporator are dirty 

 
IDU motor is blocked 

 
Refrigerant amount is insufficient 

 
Ambient temperature of IDU and ODU is too low 

80 

Sayfa 86

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Troubleshooting: 

1.3.16 “L7” No master IDU 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

No master IDU error will happen when there is no master IDU in the system 

Possible reason: 

 
Master IDU is offline 

 
The mainboard of master IDU is replaced 

 
The mainboard of master IDU has error 

81 

Sayfa 87

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Troubleshooting: 

1.3.17 “L9” Group-controlled IDU quantity inconsistency 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

If the IDU quantity connected with wired controller exceeds 16 sets or actually connected IDU 

quantity is inconsistent with the set group-controlled IDU quantity. 

Possible reason: 

 
IDU quantity connected with one wired controller exceeds 16 sets; 

 
Actually connected IDU quantity is inconsistent with the set group-controlled IDU quantity. 

Troubleshooting: 

1.3.18 “LA” Group-controlled IDU series inconsistency 

Error display: IDU wired controller and IDU receive light board will display 
 

Error judgment condition and method: 

Wired controller detects that the IDUs connected with itself belong to different series. 

Possible reason: 

 
IDUs connected with one wired controller belong to different series 

82 

Sayfa 88

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Troubleshooting: 

Make sure the IDUs connected with one wired controller belong to the same series. 

1.3.19 “LC” Mismatch of IDU and ODU models 

Error display: IDU wired controller and IDU receive light board will display
 

Error judgment condition and method: 

When some IDUs or devices which cannot be identified by some ODUs are installed in the system, 

mismatch error of IDU and ODU models will occur. 

Possible reason: 

 
Mismatch of IDU and ODU 

Troubleshooting: 

When some IDUs or devices which cannot be identified by some ODUs are installed in the system 

(E.g. floor heating device is installed in modular DC inverter multiple VRF system), the error will occur. 

Please remove the relevant IDU devices or replace the ODU with suitable model. 

2 After-sales Emergency Masures 

When some unrecoverable fault occurs to one module which is connected with several others in 

parallel, the following emergency measures are recommended to guarantee the heating or cooling 

capacity of the indoor units and the service life of modules except the faulted one are not affected. 

Step 1: set all indoor units under “Off” mode and cut off the power supply to the indoor and outdoor 

units. 

Step 2: shut off all cutoff valves of the faulted outdoor unit, including the cutoff valves of the liquid/gas 

pipe as well as the oil balancing valve. 

Step 3: cut off the air switch of the module. 

Step 4: remove the communication line between the faulted module and other modules which are 

still kept connected through the communication line. 

Step 5: readjust the address and quantity settings on the main board of the modules except the 

faulted one. 

Step 6: power and restart the unit. 

3 About the Refrigerant Leakage Sensor 

(1) The R32 refrigerant leakage sensor must be replaced after malfunction or at the end of its 

lifetime. ONLY authorized persons may replace the sensor. 

(2) The sensor has a lifetime of 15 years. At the end of sensor lifetime or when the sensor fault, the 

indoor unit or wired controller displays error code "yd", and emits an alarm sound. The alarm 

can be canceled by operating the “On/Off” button of the wired controller or remote control. The 

indoor unit fan will keep running and the system can not operate until the sensor is replaced. 

Please contact our designated dealer or local service center to replace the sensor. 

(3) The R32 refrigerant leakage sensor is a semiconductor detector which may incorrectly detect 

substances other than R32 refrigerant. Avoid using chemical substances (e.g. organic solvents, 

83 

Sayfa 89

GREE                                                Multi Variable Air Conditioners Indoor Unit  

hair spray, paint) in high concentrations, in the close proximity of the indoor unit because this 

may cause misdetection of the R32 refrigerant leakage sensor. 

(4) When the sensor detects refrigerant leak, the indoor unit or wired controller displays error code 

"yb", and emits an alarm sound. The alarm can be canceled by operating the “On/Off” button of 

the wired controller or remote control. The indoor unit fan will keep running and the system can 

not operate until the leakage is repaired. Please contact our designated dealer or local service 

center. 

(5) If the indoor unit report a refrigerant leak and returns to normal after a while, it may be a 

misdetection caused by other chemical substances. 

84 

Sayfa 90

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4 Wiring Diagram  

This drawing is just for reference; please always refer to the electric wiring stuck to the 

unit for actual wiring. 

4.1 High Static Pressure Duct Type Indoor Unit 

GMV-ND07~54PHS/NhD-T(U): 

85 

Sayfa 91

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4.2 Fresh Air Processing Indoor Unit 

GMV-NDX42~54P/NhD-T(U): 

4.3 Air Handler Type Indoor Unit 

GMV-ND12~60A/NhB-T(U):  

86 

Sayfa 92

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4.4 360°Air Discharge Casssette Type Indoor Unit 

GMV-ND07~48T/NhD-T(U): 

4.5 360°Air Discharge Compact Casssette Type Indoor Unit 

GMV-ND05~18T/NhE-T(U): 

87 

Sayfa 93

GREE                                                Multi Variable Air Conditioners Indoor Unit  

4.6 1-way Cassette Type Indoor Unit 

GMV-ND07~12TD/NhA-T(U): 

4.7 Wall Mounted Type Indoor Unit 

GMV-ND06~24G/NhA1C-T(U)、GMV-ND06~24G/NhA3C-T(U): 

88 

Sayfa 94

GREE                                                Multi Variable Air Conditioners Indoor Unit  

5 Disassembly and Assembly Procedure of Main Parts 

5.1 High Static Pressure Duct Type Indoor Unit 

The following steps are specific for GMV-ND18PHS/NhD-T(U) units. For other units, the 

assembly and disassembly procedure is similar except the specifications of centrifugal fans and motors.  

Motor and fan 

Precondition: The power supply has been disconnected. 

Step 
Diagram 
Operation Procedure 

1. Remove the line 
connecting to the motor. 
 

2. Remove the filter. 
 
 Remove the filter from the air 

3. Remove the air return 
cover plate. 
 
 Use a screwdriver to unscrew 

4. Remove the volute 
casing. 
 

5. Loosen the centrifugal fan 
and motor. 
 

89 

 Use a screwdriver to unscrew 

the electric box cover. 
 Remove from the master 

board the line connecting to 
the motor and remove the tie. 

return frame. 

the air return cover plate. 

 Loosen the fasteners that 

connect the rear volute casing 
with the front volute casing 
and remove the rear volute 
casing. 

 Use a hexagon to unscrew the 

centrifugal fan and loosen the 
fasteners of the motor. 

Sayfa 95

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Motor and fan 

Precondition: The power supply has been disconnected. 

Step 
Diagram 
Operation Procedure 

6. Remove the motor. 
 

7. Install a new motor. 
 

8. Remove the Refrigerant 
Sensor. 
 

5.2 Fresh Air Processing Indoor Unit 

Motor and fan 

Precondition: The power supply has been disconnected. 

Step 
Diagram 
Operation Procedure 

1. Remove the line 
connecting to the motor. 
 

2. Remove the filter. 
 
 Remove the filter from the air 

90 

 Remove the motor from the 

support and remove the 
centrifugal fan from the motor 
axle. Then, remove the motor. 
 For motors that are 

accompanied with supports, 
the supports need removing 
as well. 

 Assemble units based on the 

reverse order of this 
procedure and power on the 
units for test. 

 Remove the Refrigerant 

Sensor from the Water Pump 
Assy and the Water Pump 
Assy from Left Side Plate 
Assy. Then, remove the 
Refrigerant Sensor. 

 Use a screwdriver to unscrew 

the electric box cover. 
 Remove from the master 

board the line connecting to 
the motor and remove the tie. 

return frame. 

Sayfa 96

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Motor and fan 

Precondition: The power supply has been disconnected. 

Step 
Diagram 
Operation Procedure 

3. Remove the air return 
cover plate. 
 
 Use a screwdriver to unscrew 

4. Remove the volute 
casing. 
 

5. Loosen the centrifugal fan 
and motor. 
 

6. Remove the motor. 
 

7. Install a new motor. 
 

8. Remove the Refrigerant 
Sensor. 
 

91 

the air return cover plate. 

 Loosen the fasteners that 

connect the rear volute casing 
with the front volute casing 
and remove the rear volute 
casing. 

 Use a hexagon to unscrew the 

centrifugal fan and loosen the 
fasteners of the motor. 

 Remove the motor from the 

support and remove the 
centrifugal fan from the motor 
axle. Then, remove the motor. 
 For motors that are 

accompanied with supports, 
the supports need removing 
as well. 

 Assemble units based on the 

reverse order of this 
procedure and power on the 
units for test. 

 Remove the Refrigerant 

Sensor from the Water Pump 
Assy and the Water Pump 
Assy from Left Side Plate 
Assy. Then, remove the 
Refrigerant Sensor. 

Sayfa 97

GREE                                                Multi Variable Air Conditioners Indoor Unit  

5.3 Air Handler Type Indoor Unit 

Step 
Picture 
Work Instruction 

1.Remove the upper panel. 
 

2.Remove the front panel. 
 

3.Remove the electric box. 
 

4.Remove the electric 
element. 

Disassembly and Assembly of the Electric Box 

 Loosen screws around the upper 

panel with a screwdriver. 
 Remove the upper panel away from 

the unit. 

 Loosen screws around the upper 

panel with a screwdriver. 
 Remove the front panel away from 

the unit. 

 Disconnect the power cord and 

control line from the wiring terminals, 
and then draw them out. 
 Loosen screws around the electric 

box with a screwdriver. 
 Remove the electric box from the 

unit. 

 Disconnect the electric element from 

the wiring terminal. 
 Loosen screws around the electric 

element with a screwdriver. 
 Remove the electric element from 

the electric box. 

92 

Sayfa 98

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Picture 
Work Instruction 

5.Mount the new electric 
element. 

6.Reinstall the electric box. 
 

Step 
Picture 
Work Instruction 

1.Remove the upper panel. 
 

2.Remove the fan. 
 

Disassembly and Assembly of the Electric Box 

 Place the electric element at the 

proper position. 
 Tighten the screws around the 

electric element with a screwdriver. 
 Wire the electric element to the 

wiring terminal. 

 Place the electric box at the proper 

position. 
 Tighten screws around the electric 

box with a screwdriver. 
 Connect the power cord and control 

line properly. 
 Reassemble the unit as before. 

 
Disassembly and Assembly of the Fan Motor 

 Loosen screws round the upper 

panel with a screwdriver. 
 Remove the upper panel from unit. 

 Disconnect the wires of the fan from 

the wiring terminal and draw them 
out. 
 Loosen screws located at the front of 

the fan with a screwdriver. 
 Remove the fan from the unit. 

93 

Sayfa 99

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Disassembly and Assembly of the Fan Motor 

Step 
Picture 
Work Instruction 

 Loosen screws fixing the motor and 

fan blades. 
 Loosen screw bolts fixing the 

3.Remove the motor. 
 

bracket. 
 Remove the motor rightward from 

the fan. 

 Place the motor at the proper 

position. 
 Tighten screws fixing the motor and 

fan blades. 
 Tighten screw bolts fixing the motor 

4.Reinstall the fan. 
 

bracket. 
 After the installation, reassemble the 

unit as before. 

 
Disassembly and Assembly of the Evaporator and Drain Pan 

Step 
Picture 
Work instruction 

 Loosen screws round the 

upper panel with a 
screwdriver. 
 Remove the upper panel 

1.Remove the 
upper panel. 

from unit. 

 Loosen screws round the 

2.Remove the 
lower panel (1) 
and panel (2). 

lower panel with a 
screwdriver. 
 Remove the lower panel 

from unit. 

94 

Sayfa 100

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Disassembly and Assembly of the Evaporator and Drain Pan 

Step 
Picture 
Work instruction 

3.Remove the 
enhanced frame 
if applicable. 

4.Remove the 
primary drain 
pan. 

5.Remove the 
secondary drain 
pan. 

 Remove the screws from 

enhanced frame. 
 Disassemble the enhanced 

frame from the unit. 

 
 Remove the primary drain 

pan from the unit. 

 
 Remove the secondary 

drain pan from the unit. 

95 

Sayfa 101

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Disassembly and Assembly of the Evaporator and Drain Pan 

Step 
Picture 
Work instruction 

 Remove the evaporator 

away from the primary 
drain pan. 
 Reassemble the unit as 

6.Remove the 
evaporator. 

before. 

Disassembly and Assembly of the Filter 

Step 
Picture 
Work instruction 

 Loosen screws fixing the mounting 

1.Remove the mounting 
plate. 

plate with a screwdriver. 
 Remove the mounting plate away 

from the unit. 

 Remove the filter screen away from 

the unit. 
 After replacing the filter screen, 

2.Remove the filter screen. 
 

reassemble the unit as before. 

96 

Sayfa 102

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Picture 
Work instruction 

1.Turn the internal unit 
upside down. 

2.Install the enhanced 
frame. 

3.install the lower panel (1) 
and panel (2). 

4.install the upper panel. 
 

Installation of downward air supply mode 

 Loosen screws around the upper 

and lower panel with a screwdriver. 
 Remove the front panel away from 

the unit. 

 install the screws from enhanced 

frame. 
 install the enhanced frame from the 

unit. 

 install screws round the lower panel 

with a screwdriver. 
 install the lower panel for unit. 

 install screws round the upper 

panel with a screwdriver. 
 install the upper panel from unit. 

97 

Sayfa 103

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Picture 
Work instruction 

1.Remove the lower 
panel (1) and panel 
(2). 

2.Remove the 
refrigerant sensor. 

5.4 360°Air Discharge Casssette Type Indoor Unit 

Step 
Diagram 
Operation Procedure 

1. Remove the front panel. 

Disassembly and Assembly of refrigerant sensor 

 Loosen screws around the 

lower panel with a 
screwdriver. 
 Remove the lower panel 

away from the unit. 

 Remove the refrigerant 

sensor away from the unit. 
 After replacing the 

refrigerant sensor , 
reassemble the unit as 
before. 

Motor and fan 

 Turn off the power supply of indoor 

unit.  
 Push the 4 corner plates in the 

directions shown by the arrows.  
 Loosen the screws and remove the 

front panel.  

98 

Sayfa 104

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Diagram 
Operation Procedure 

2. Remove the cover of 
electric box and the clamp 
of power cord. 

3. Remove the water tray. 

4. Remove the fan. 
 

5. Remove the motor. 

Motor and fan 

 
 Remove the motor wire and water 

pump of the electric box.  

 Loosen the screws in the 4 corners 

and then remove the water tray. 

 Use a screwdriver to remove the 

clamping band of motor. Then 
remove the fan. 

 Use a screwdriver to unscrew the 3 

screws of motor. Then remove the 
motor. 

99 

Sayfa 105

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Diagram 
Operation Procedure 

6. Replace and install the 
motor.  
 

7. Install the fan. 
 

8. Install the water tray.  
 

9. Remove the Refrigerant 
Sensor 

Motor and fan 

 Remove the motor from motor 

support and then replace with a 
new motor.  
 Tighten the 3 screws of motor with 

a screwdriver.  

 Direct the hole of fan to the motor 

shaft and then mount on the fan.  
 Tighten the clamping band of motor 

with a wrench.  

 Direct the 4 corners of water tray to 

the 4 corners of the unit and then 
press them. Use a screwdriver to 
tighten the screws in the 4 corners.  
 Connect the power cord and water 

pump wire.  
 Place back the cover of electric box 

and the clamp of power cord. Then 
tighten the screws with a 
screwdriver.  

 Remove the 2 Refrigerant Sensor 

fixing screws, and then you can 
remove the Refrigerant Sensor. 

100 

Sayfa 106

GREE                                                Multi Variable Air Conditioners Indoor Unit  

5.5 360°Air Discharge Compact Casssette Type Indoor Unit 

Step 
Diagram 
Operation Procedure 

1. Remove the 
front panel. 

2. Remove the 
cover of electric 
box and the clamp 
of power cord. 

3. Remove the 
water tray. 

Motor and fan 

 Turn off the power supply of 

indoor unit.  
 Push the 4 corner plates in the 

directions shown by the arrows.  
 Loosen the screws and remove 

the front panel.  

 
 Remove the motor wire and water 

pump of the electric box.  

 Loosen the screws in the 4 

corners and then remove the 
water tray. 
 

101 

Sayfa 107

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Diagram 
Operation Procedure 

4. Remove the 
fan. 

5. Remove motor. 

6. Remove the 
refrigerant sensor 

7.Replacement 
and installation of 
refrigerant sensor 

Motor and fan 

 Use a screwdriver to remove the 

clamping band of motor. Then 
remove the fan. 

 Use a screwdriver to unscrew the 

4 screws of motor. Then remove 
the motor. 

 Remove the two fixing screws on 

the back of the connector plate.  
 Move upwards to remove the 

refrigerant sensor. 

 Remove the refrigerant sensor 

from the connector plate, then 
replace it with a new refrigerant 
sensor. 
 Use a screwdriver to tighten the 

two screws of the refrigerant 
sensor. 

102 

Sayfa 108

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Diagram 
Operation Procedure 

8. Replace and 
install the motor.  
 

9. Install the fan. 
 

10. Install the 
water tray.  
 

5.6 1-way Cassette Type Indoor Unit 

Step 
Diagram 
Operation Procedure 

1.Unscrew the 
water tray. 
 
 Use a screwdriver to unscrew the 

2.Remove the 
water tray. 
 
 Remove the water tray. 

Motor and fan 

 Remove the motor from motor 

support and then replace with a 
new motor.  
 Tighten the 4 screws of motor with 

a screwdriver.  

 Direct the hole of fan to the motor 

shaft and then mount on the fan.  
 Tighten the clamping band of 

motor with a wrench.  

 Direct the 4 corners of water tray 

to the 4 corners of the unit and 
then press them. Use a 
screwdriver to tighten the screws 
in the 4 corners.  
 Connect the power cord and water 

pump wire.  
 Place back the cover of electric 

box and the clamp of power cord. 
Then tighten the screws with a 
screwdriver.  

Motor and fan 

water tray. 

103 

Sayfa 109

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Diagram 
Operation Procedure 

3.Unscrew the 
volute tongue. 
 
 Use a screwdriver to unscrew the 

4.Remove the 
volute tongue. 
 
 Remove the volute tongue. 

5.Unscrew the 
outlet board. 
 

6.Remove the 
evaporator. 
 
 Remove the evaporator. 

7.Unscrew the 
motor pressing 
board. 

8.Remove the 
pressing board 
and replace the 
motor. 

Motor and fan 

volute tongue. 

 Use a screwdriver to unscrew the 

outlet board and then remove the 
board. 

 
 Use a screwdriver to unscrew the 

motor pressing board. 

 
 Remove the pressing board and 

replace the motor. 

104 

Sayfa 110

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Step 
Diagram 
Operation Procedure 

9.Screw the motor 
pressing board. 
 
 Use a screwdriver to screw the 

10.Install the 
evaporator. 
 
 Install the evaporator. 

11.Screw the 
outlet board. 
 
 Use a screwdriver to screw the 

12.Put the volute 
tongue back to 
position. 

13.Screw the 
volute tongue. 
 
 Use a screwdriver to screw the 

14.Install the 
water tray. 
 
 Install the water tray. 

15.Screw the 
water tray. 
 
 Use a screwdriver to screw the 

Motor and fan 

motor pressing board. 

outlet board. 

 
 Put the volute tongue back to 

position. 

volute tongue. 

water tray. 

105 

Sayfa 111

GREE                                                Multi Variable Air Conditioners Indoor Unit  

5.7 Wall Mounted Type Indoor Unit 

Removal of Fan Motor 

Remark: before removing, making sure power is disconnected. 

Step 
Diagram 
Operation Procedure 

1. Remove the louver 
 

2. Open the front panel 
 

3. Remove the electrical 
box cover 2 
 

4. Remove the front panel 
assembly 
 

5. Remove the electrical 
box cover 1 
 

6. Remove the main board 
 

106 

 Take off the axle bush of the 

louver. 
 Remove the louver. 

 Hold the indents on both sides 

of the panel and pull it out in the 
direction shown by the arrow. 

 Unscrew the screws fixing the 

electrical box cover with a 
screwdriver. Take off the box 
cover 2. 
 Detach the ambient 

temperature sensor from the 
conduit. 

 Unscrew the screws fixing the 

front panel assembly. 
 Remove the front panel 

assembly. 

 Press on the buckle of the box 

cover 1 and then take off the 
cover. 

 Release the wiring terminals 

connected to the main board. 
 Remove the main board. 

Sayfa 112

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Removal of Fan Motor 

Remark: before removing, making sure power is disconnected. 

Step 
Diagram 
Operation Procedure 

7. Remove the electrical 
box 
 

8. Remove the evaporator 
 

9.Remove motor’s pressing 
plate 
 

10. Remove the motor and 
fan 
 

11. Install a new motor. 
 

107 

 Unscrew the screws fixing the 

electrical box with a 
screwdriver. 
 Remove the electrical box. 

 Use a screwdriver to unscrew 

the screws fixing the press plate 
of connection pipe on the back 
of the unit and take off the press 
plate. 
 Unscrew the screws of 

evaporator with a screwdriver 
and then remove the 
evaporator. 

 Unscrew the fixing screws of 

the pressing plate with a 
screwdriver and then remove it. 

 Take off the motor and fan 

directly. 
 Use a screwdriver to unscrew 

the screws connecting the 
motor and the fan. 

 Assemble units based on the 

reverse order of this procedure 
and power on the units for test. 

Sayfa 113

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6 Exploded Views and Part List 

6.1 High Static Pressure Duct Type Indoor Unit  

Exploded View of GMV-ND07~24PHS/NhD-T(U): 

1
2
3
4
5
6
7
8
9
10

GMV-ND12PHS/NhD-T(U) 
GMV-ND15PHS/NhD-T(U) 
GMV-ND18PHS/NhD-T(U) 
GMV-ND24PHS/NhD-T(U) 
Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

Model 
GMV-ND07PHS/NhD-T(U) 
GMV-ND09PHS/NhD-T(U) 

No. 

1 
Hook             
02112466 
4 
02112466 
4 

2 
Filter Sub-Assy        
111001000045 
2 
111001000045 
2 

3 
Propeller Housing(Lower)    
26905200079 
2 
26905200079 
2 

4 
Centrifugal Fan        
10455200003 
2 
10455200003 
2 

5 
Propeller Housing(Upper)    
26905200078 
2 
26905200078 
2 

6 
Brushless DC Motor      
15010406007901 
1 
15010406007901 
1 

7 
Electric Box Assy       
100002083603 
1 
100002083603 
1 

8 
Main Board          
300002064354 
1 
300002064354 
1 

9 
Terminal Board        
42200006005404 
1 
42200006005404 
1 

10 
Terminal Board        
4201110602 
1 
4201110602 
1 

11 
Refrigerant Sensor      
340024060017 
1 
340024060017 
1 

12 
Pump Drainpipe        
200070060004 
1 
200070060004 
1 

20
21
22
23
24

19

18

17

14
15
16

13

12

11

108 

Sayfa 114

GREE                                                Multi Variable Air Conditioners Indoor Unit  

GMV-ND12PHS/NhD-T(U) 
GMV-ND15PHS/NhD-T(U) 
GMV-ND18PHS/NhD-T(U) 
GMV-ND24PHS/NhD-T(U) 
Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

Model 
GMV-ND07PHS/NhD-T(U) 
GMV-ND09PHS/NhD-T(U) 

No. 

13 
Water Pump         
81200706032701 
1 
81200706032701 
1 

14 
Liquid Level Switch      
430024000005 
1 
430024000005 
1 

15 
Strainer           
07415210 
1 
07415210 
1 

16 
Strainer           
07213050 
1 
07213050 
1 

17 
Electronic Expansion Valve   
072009060064 
1 
072009060076 
1 

18 
Electric Expand Valve Fitting  
07200206000109 
1 
07200206000109 
1 

19 
Evaporator Assy        
011001063469 
1 
011001063321 
1 

20 
Temperature Sensor      
340025060014 
1 
340025060014 
1 

21 
Temperature Sensor      
340025060014 
1 
340025060014 
1 

22 
Temperature Sensor      
340025060018 
1 
340025060018 
1 

23 
Display Board         
300001061780 
1 
300001061780 
1 

24 
Drain Hose Sub-Assy     
05232050 
1 
05232050 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

109 

Sayfa 115

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Exploded View of GMV-ND30~54PHS/NhD-T(U): 

20
21
22
23
24
25

10
12
13
15
11
14
1

2
3
4
5
6
7
8
9

GMV-ND30PHS/NhD-T(U) 
GMV-ND36PHS/NhD-T(U) 
GMV-ND42PHS/NhD-T(U) 
GMV-ND48PHS/NhD-T(U) 
GMV-ND54PHS/NhD-T(U) 

Model 

No. 

Part Name 
Part Code 

1 
Filter Sub-Assy             
111001000052 
3 

2 
Propeller Housing(Upper)         
26905200078 
3 

3 
Brushless DC Motor           
1570940000805 
1 

4 
Centrifugal Fan             
10455200003 
3 

5 
Propeller Housing(Lower)         
26905200079 
3 

6 
Electric Expand Valve Fitting       
07200206000109 
1 

7 
Water Pump              
81200706032701 
1 

8 
Pump Drainpipe             
200070060004 
1 

9 
Refrigerant Sensor           
340024060017 
1 

10 
Liquid Level Switch           
430024000005 
1 

11 
Electric Box Assy            
100002083095 
1 

12 
Main Board               
300002064284 
1 

13 
Terminal Board             
42200006005404 
1 

14 
Terminal Board             
4201110602 
1 

15 
Hook                  
02112466 
4 

110 

16
17
18
19

Qty. 

Sayfa 116

GREE                                                Multi Variable Air Conditioners Indoor Unit  

GMV-ND30PHS/NhD-T(U) 
GMV-ND36PHS/NhD-T(U) 
GMV-ND42PHS/NhD-T(U) 
GMV-ND48PHS/NhD-T(U) 
GMV-ND54PHS/NhD-T(U) 

Model 

No. 

Part Name 
Part Code 

16 
Strainer                
07213050 
1 

17 
Electronic Expansion Valve        
072009060056 
1 

18 
Strainer                
07415210 
1 

19 
Evaporator Assy             
011001063320 
1 

20 
Temperature Sensor           
340025060014 
1 

21 
Temperature Sensor           
340025060014 
1 

22 
Temperature Sensor           
340025060018 
1 

23 
Display Board              
300001061780 
1 

24 
Drain Hose Sub-Assy          
05232050 
1 

25 
Corrugated Pipe             
05015408 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

111 

Qty. 

Sayfa 117

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.2 Fresh Air Processing Type Indoor Unit 

Exploded View of GMV-NDX42~54P/NhD-T(U) 

17
18

13
14
15
16

1
2
3
4
5
6
7

9
10
12
8
11

GMV-NDX42P/NhD-T(U) 
GMV-NDX48P/NhD-T(U) 
GMV-NDX54P/NhD-T(U) 
Part Name 
Part Code 
Qty. 

Model 

No. 

1 
Filter Sub-Assy             
111001000052 
3 

2 
Propeller Housing(Upper)         
26905200078 
3 

3 
Brushless DC Motor           
1570940000805 
1 

4 
Centrifugal Fan             
10455200003 
3 

5 
Propeller Housing(Lower)         
26905200079 
3 

6 
Electric Expand Valve Fitting       
07200206000109 
1 

7 
Refrigerant Sensor            
340024060017 
1 

8 
Electric Box Assy            
100002083095 
1 

9 
Main Board               
300002064284 
1 

10 
Terminal Board             
42200006005404 
1 

11 
Terminal Board             
4201110602 
1 

12 
Hook                  
02112466 
4 

13 
Strainer                 
07213050 
1 

14 
Electronic Expansion Valve        
072009060056 
1 

112 

Sayfa 118

GREE                                                Multi Variable Air Conditioners Indoor Unit  

GMV-NDX42P/NhD-T(U) 
GMV-NDX48P/NhD-T(U) 
GMV-NDX54P/NhD-T(U) 
Part Name 
Part Code 
Qty. 

Model 

No. 

15 
Strainer                 
07415210 
1 

16 
Evaporator Assy             
011001063320 
1 

17 
Drain Hose Sub-Assy           
05232050 
1 

18 
Corrugated Pipe             
05015408 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

113 

Sayfa 119

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.3 Air Handler Type Indoor Unit 

Exploded View of GMV-ND12~30A/NhB-T(U): 

11
12
13

1
2
3
4
5

6

GMV-ND24A/NhB-T(U) 
GMV-ND30A/NhB-T(U) 
Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

Model 
GMV-ND12A/NhB-T(U) 
GMV-ND18A/NhB-T(U) 

No

. 

1 
Brushless DC Motor 
15010400001401 
1 
15010400001401 
1 

2 
Centrifugal Fan 

Housing 
1570220101 
1 
1570220101 
1 

3 
Electronic Expansion 

Valve 
072009060064 
1 
072009060076 
1 

4 
Evaporator Assy 
011001063608 
1 
011001063609 
1 

5 
Filter Sub-Assy 
111001060269 
1 
111001060269 
1 

6 
Refrigerant Sensor 
340024060017 
1 
340024060017 
1 

7 
Electric Box Assy 
100002084426 
1 
100002084426 
1 

8 
Main Board 
300002064555 
1 
300002064555 
1 

9 
Terminal Board 
42200006005404 
1 
42200006005404 
1 

10 
Transformer 
43110286 
1 
43110286 
1 

11 
Electric Expand Valve 

Fitting 
07200206000103 
1 
07200206000103 
1 

12 
Sensor Sub-Assy 
390002060766 
1 
390002060766 
1 

13 
Temperature Sensor 
390001060085 
1 
390001060085 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

114 

7
8
9
10

Sayfa 120

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Exploded View of GMV-ND36~42A/NhB-T(U): 

11
12
13

1
2
3
4
5

6

Model 
GMV-ND36A/NhB-T(U) 
GMV-ND42A/NhB-T(U) 

No. 

Part Name 
Part Code 
Qty. 

1 
Brushless DC Motor 
15010400001401 
1 

2 
Centrifugal Fan Housing 
1570220201 
1 

3 
Electronic Expansion Valve 
072009060056 
1 

4 
Evaporator Assy 
011001063610 
1 

5 
Filter Sub-Assy 
111001060160 
1 

6 
Refrigerant Sensor 
340024060017 
1 

7 
Electric Box Assy 
100002084426 
1 

8 
Main Board 
300002064555 
1 

9 
Terminal Board 
42200006005404 
1 

10 
Transformer 
43110286 
1 

11 
Electric Expand Valve Fitting 
07200206000103 
1 

12 
Sensor Sub-Assy 
390002060766 
1 

13 
Temperature Sensor 
390001060085 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

115 

7
8
9
10

Sayfa 121

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Exploded View of GMV-ND48~60A/NhB-T(U): 

8
9
10
11

12
13
14

1
2
3
4
6

5

7

GMV-ND48A/NhB-T(U) 
GMV-ND54A/NhB-T(U) 
GMV-ND60A/NhB-T(U) 

Model 

No. 

Part Name 
Part Code 
Qty. 

1 
Brushless DC Motor 
15010400001301 
1 

2 
Centrifugal Fan Housing 
1570220301 
1 

3 
Electronic Expansion Valve 
072009060056 
1 

4 
Evaporator Assy 
011001063611 
1 

5 
Strainer 
0721200102 
1 

6 
Filter Sub-Assy 
111001060188 
1 

7 
Refrigerant Sensor 
340024060017 
1 

8 
Electric Box Assy 
100002084426 
1 

9 
Main Board 
300002064555 
1 

10 
Terminal Board 
42200006005404 
1 

11 
Transformer 
43110286 
1 

12 
Electric Expand Valve Fitting 
07200206000103 
1 

116 

Sayfa 122

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 

No. 

Part Name 
Part Code 
Qty. 

13 
Sensor Sub-assy 
390002060766 
1 

14 
Temperature Sensor 
390001060085 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

GMV-ND48A/NhB-T(U) 
GMV-ND54A/NhB-T(U) 
GMV-ND60A/NhB-T(U) 

117 

Sayfa 123

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.4 360°Air Discharge Casssette Type Indoor Unit 

Exploded View of GMV-ND07~18T/NhD-T(U):  

1

2

3

4

5

6

7

8

9

10

11

12
15

GMV-ND07T/NhD-T(U) 
GMV-ND09T/NhD-T(U) 
GMV-ND12T/NhD-T(U) 

Model 

No. 

Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

1 
Terminal Board 
42200006005404 
1 
42200006005404 
1 

2 
Main Board 
300002064302 
1 
300002064302 
1 

3 
Terminal Board 
42200006001301 
1 
42200006001301 
1 

4 
Electric Box Assy 
100002083156 
1 
100002083156 
1 

5 
Diversion Circle 
200150060030 
1 
200150060030 
1 

6 
Centrifugal Fan 
103003060047 
1 
103003060047 
1 

7 
Brushless DC Motor 
150104060121 
1 
150104060121 
1 

118 

20

19

18

17

16

14

13

GMV-ND15T/NhD-T(U) 
GMV-ND18T/NhD-T(U) 

Sayfa 124

GREE                                                Multi Variable Air Conditioners Indoor Unit  

GMV-ND07T/NhD-T(U) 
GMV-ND09T/NhD-T(U) 
GMV-ND12T/NhD-T(U) 

Model 

No. 

Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

8 
Evaporator Assy 
011001063464 
1 
011001063307 
1 

9 
Electronic Expansion 

Valve 
072009060064 
1 
072009060076 
1 

10 
Strainer 
07213050 
1 
07213050 
1 

11 
Strainer A 
0721002201 
1 
0721002201 
1 

12 
Body Installing Plate 
01332701 
4 
01332701 
4 

13 
Drainage Pipe Sub-

assy 
26909400055 
1 
26909400055 
1 

14 
Water Pump 
43138000058 
1 
43138000058 
1 

15 
Refrigerant Sensor 
340024060017 
1 
340024060017 
1 

16 
Liquid Level Switch 
4502021603 
1 
4502021603 
1 

17 Electric Expand Valve 
Fitting 
4304413252 
1 
4304413252 
1 

18 
Remote Controller 
30510589 
1 
30510589 
1 

19 Drain Hose Sub-assy 
05339400001 
1 
05339400001 
1 

20 
Sensor Sub-assy 
390002060712 
1 
390002060712 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

119 

GMV-ND15T/NhD-T(U) 
GMV-ND18T/NhD-T(U) 

Sayfa 125

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Exploded View of GMV-ND24~48T/NhD-T(U): 

1

2

3

4

5

6

7

8

9

10

11
14

Model 
GMV-ND24T/NhD-T(U) 

No. 

Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

1 
Terminal Board        42200006005404 
1 
42200006005404 
1 

2 
Main Board          
300002064286 
1 
300002064286 
1 

3 
Terminal Board        42200006001301 
1 
42200006001301 
1 

4 
Electric Box Assy       
100002083157 
1 
100002083157 
1 

5 
Diversion Circle        
200150060029 
1 
200150060029 
1 

6 
Centrifugal Fan        
103003060048 
1 
103003060048 
1 

7 
Brushless DC Motor      15010406012201 
1 
15010406012201 
1 

8 
Evaporator Assy       
011001063685 
1 
011001063308 
1 

20

19

18

17

16

15

13

12

GMV-ND30T/NhD-T(U) 
GMV-ND36T/NhD-T(U) 
GMV-ND42T/NhD-T(U) 
GMV-ND48T/NhD-T(U) 

120 

Sayfa 126

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND24T/NhD-T(U) 

No. 

Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

9 
Strainer           
07213050 
1 
07213050 
1 

10 
Electronic Expansion Valve   
072009060076 
1 
072009060076 
1 

11 
Body Installing Plate      
01332701 
4 
01332701 
4 

12 
Drainage Pipe Sub-assy    
26909400055 
1 
26909400055 
1 

13 
Water Pump         
43138000058 
1 
43138000058 
1 

14 
Refrigerant Sensor      
340024060017 
1 
340024060017 
1 

15 
Liquid Level Switch      
4502021603 
1 
4502021603 
1 

16 
Electric Expand Valve Fitting  
4304413252 
1 
4304413252 
1 

17 
Remote Controller       
30510589 
1 
30510589 
1 

18 
Drain Hose Sub-assy     
05339400001 
1 
05339400001 
1 

19 
Corrugated Pipe       
035030000008 
1 
05015408 
1 

20 
Sensor Sub-assy       
390002060712 
1 
390002060712 
1 

Above data is subject to change without notice, please refer the SP in global service website. 

GMV-ND30T/NhD-T(U) 
GMV-ND36T/NhD-T(U) 
GMV-ND42T/NhD-T(U) 
GMV-ND48T/NhD-T(U) 

121 

Sayfa 127

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.5 360°Air Discharge Compact Casssette Type Indoor Unit 

Exploded View of GMV-ND05T/NhE-T(U);GMV-ND07T/NhE-T(U) ;GMV-ND09T/NhE-T(U) ;GMV-

ND12T/NhE-T(U); GMV-ND15T/NhE-T(U); GMV-ND18T/NhE-T(U). 

1

2

3

4

5

6

7

GMV-ND05T/NhE-T(U) 
GMV-ND07T/NhE-T(U) 
GMV-ND09T/NhE-T(U) 
GMV-ND12T/NhE-T(U) 

Model 

No. 

Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

1 
Diversion Circle    
20015006000301 
1 
20015006000301 
1 

2 
Centifugal Fan    
103003060008 
1 
103003060008 
1 

3 
Brushless DC Motor  
150104060012 
1 
150104060012 
1 

122 

18

17

16

15

14

13

12

11

10

9

8

GMV-ND15T/NhE-T(U) 
GMV-ND18T/NhE-T(U) 

Sayfa 128

GREE                                                Multi Variable Air Conditioners Indoor Unit  

GMV-ND05T/NhE-T(U) 
GMV-ND07T/NhE-T(U) 
GMV-ND09T/NhE-T(U) 
GMV-ND12T/NhE-T(U) 

Model 

No. 

Part Name 
Part Code 
Qty. 
Part Code 
Qty. 

4 
Evaporator Assy   
011001063859 
1 
011001063623 
1 

5 
Filter         
07216221 
1 
07216221 
1 

6 
Strainer       
07213032 
1 
07213032 
1 

7 
Electric expand valve 

fitting        
43040001 
1 
43040001 
1 

8 
Drain Pipe      
200070060005 
1 
200070060005 
1 

9 
Water Pump 
4313800005802 
1 
4313800005802 
1 

10 
Liquid Level Switch  
430024000005 
4 
430024000005 
4 

11 
Refrigerant Sensor  
340024060017 
1 
340024060017 
1 

12 
Remote Controller   
30510589 
1 
30510589 
1 

13 
Sensor Sub-assy   
390002060768 
1 
390002060768 
1 

14 
Drain Hose Sub-Assy 
007008000001 
1 
007008000001 
1 

15 
Electric Box Assy   
100002084482 
1 
100002084482 
1 

16 
Main Board      
300002064558 
1 
300002064558 
1 

17 
Terminal Board    
42200006005404 
1 
42200006005404 
1 

18 
Terminal Board    
4201110602 
1 
4201110602 
1 

Above data is subject to change without notice, please reference the SP in global service website.  

123 

GMV-ND15T/NhE-T(U) 
GMV-ND18T/NhE-T(U) 

Sayfa 129

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.6 1-way Cassette Type Indoor Unit 

Exploded View of GMV-ND07TD/NhA-T(U); GMV-ND09TD/NhA-T(U); GMV-ND12TD/NhA-T(U) 

1

2

3

4

5

6

7
8
9

GMV-ND07TD/NhA-T(U) 
GMV-ND09TD/NhA-T(U) 
GMV-ND12TD/NhA-T(U) 

Model 

No. 

Part Name 
Part Code 
Qty. 

1 
Water Tray 
26904100035 
1 

2 
Evaporator Assy 
011001063631 
1 

3 
Cross Flow Fan 
10454100001 
1 

4 
Brushless DC Motor 
1501214301 
1 

5 
Refrigerant Sensor 
340024060017 
1 

6 
Hook 
02112466 
1 

124 

19

18

17

16

15

14

13

12

11

10

Sayfa 130

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 

No. 

Part Name 
Part Code 
Qty. 

7 
Remote Controller 
30510589 
1 

8 
Sensor Sub-assy 
390002060770 
1 

9 
Drain Hose 
05232046 
1 

10 
Liquid Level Switch 
430024000005 
1 

11 
Water Pump 
81200706001601 
1 

12 
Pump Drainpipe 
26905288 
1 

13 
Strainer 
07213050 
1 

14 
Electric expand valve fitting 
43040001 
1 

15 
Strainer 
0721200102 
4 

16 
Electric Box Assy 
100002084624 
1 

17 
Main Board 
300002064551 
1 

18 
Terminal Board 
42200006005404 
1 

19 
Terminal Board 
42000100000102 
1 
Above data is subject to change without notice, please reference the SP in global service website. 

GMV-ND07TD/NhA-T(U) 
GMV-ND09TD/NhA-T(U) 
GMV-ND12TD/NhA-T(U) 

125 

Sayfa 131

GREE                                                Multi Variable Air Conditioners Indoor Unit  

6.7 Wall Mounted Type Indoor Unit 

Exploded View of GMV-ND06G/NhA1C-T(U),GMV-ND07G/NhA1C-T(U),GMV-ND09G/NhA1C-T(U), 

GMV-ND06G/NhA3C-T(U),GMV-ND07G/NhA3C-T(U),GMV-ND09G/NhA3C-T(U). 

Model 

No. 

Part Name 
Part Code 
Qty. 

1 
Front Panel 
200003060356T 
1 

2 
Filter Sub-Assy 
1112246803 
2 

3 
Front Case 
200002060102 
1 

4 
Evaporator Assy 
011001063588 
1 

5 
Electronic Expansion Valve 
072009060064 
1 

6 
Filter Sub-Assy 
11120011 
1 

7 
Electric Expand Valve Fitting 
07200206001901 
1 

8 
Guide Louver 
200004060236 
1 

9 
Stepping Motor 
1521210712 
1 

10 
Axile Bush 
10542036 
1 

11 
Electric Box Assy 
100002084357 
1 

GMV-ND06G/NhA1C-T(U)、GMV-ND06G/NhA3C-T(U) 
GMV-ND07G/NhA1C-T(U)、GMV-ND07G/NhA3C-T(U) 
GMV-ND09G/NhA1C-T(U)、GMV-ND09G/NhA3C-T(U) 

126 

Sayfa 132

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 

No. 

Part Name 
Part Code 
Qty. 

12 
Terminal Board 
4201026807 
1 

13 
Main Board 
300002064511 
1 

14 
Display Board 
300001061358 
1 

15 
Right Side Plate 
200086060076 
1 

16 
Wall Mounting Frame 
012043000008 
1 

17 
Stepping Motor 
1521210704 
1 

18 
Brushless DC Motor 
15010406011702 
1 

19 
Gas Sensor 
340024060017 
1 

20 
Air Louver (Auto) 
200007060117 
1 

21 
Rear Grill Sub-Assy 
209168000017 
1 

22 
Air Louver(Right) 
200007060110 
1 

23 
Swing Lever 
200035060044 
1 

24 
Air Louver (Left)(Auto) 
200007060111 
1 

25 
Axile Bush Sub-Assy 
10542047 
1 

26 
Rear Grill Sub-Assy 
209168000016 
1 

27 
Left Side Plate 
200085060070 
1 

28 
Remote Controller 
305001060060 
1 

29 
Drainage Hose 
05230014 
1 
 

GMV-ND06G/NhA1C-T(U)、GMV-ND06G/NhA3C-T(U) 
GMV-ND07G/NhA1C-T(U)、GMV-ND07G/NhA3C-T(U) 
GMV-ND09G/NhA1C-T(U)、GMV-ND09G/NhA3C-T(U) 

127 

Sayfa 133

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Exploded View of GMV-ND12G/NhA1C-T(U),GMV-ND14G/NhA1C-T(U), 

GMV-ND12G/NhA3C-T(U),GMV-ND14G/NhA3C-T(U). 

Model 
GMV-ND12G/NhA1C-T(U)、GMV-ND12G/NhA3C-T(U) 
GMV-ND14G/NhA1C-T(U)、GMV-ND14G/NhA3C-T(U) 

No. 

Part Name 
Part Code 
Qty. 

1 
Front Panel 
200003060382T 
1 

2 
Filter Sub-Assy 
111001060404 
2 

3 
Front Case 
200002060099 
1 

4 
Evaporator Assy 
011001063589 
1 

5 
Electronic Expansion Valve 
072009060076 
1 

6 
Filter Sub-Assy 
11120011 
1 

7 
Electric Expand Valve Fitting 
07200206001901 
1 

8 
Guide Louver 
200004060235 
1 

9 
Stepping Motor 
1521240212 
1 

10 
Axile Bush 
10542036 
1 

11 
Electric Box Assy 
100002084358 
1 

12 
Terminal Board 
4201026807 
1 

13 
Main Board 
300002064511 
1 

14 
Display Board 
300001061358 
1 

128 

Sayfa 134

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND12G/NhA1C-T(U)、GMV-ND12G/NhA3C-T(U) 
GMV-ND14G/NhA1C-T(U)、GMV-ND14G/NhA3C-T(U) 

No. 

Part Name 
Part Code 
Qty. 

15 
Right Side Plate 
200086060074 
1 

16 
Wall Mounting Frame 
012043060024 
1 

17 
Gas Sensor 
340024060017 
1 

18 
Brushless DC Motor 
15010406008802 
1 

19 
Stepping Motor 
1521210704 
1 

20 
Air Louver (Auto) 
200007060116 
1 

21 
Rear Grill Sub-Assy 
209168000010 
1 

22 
Air Louver(Right) 
200007060115 
1 

23 
Swing Lever 
200035060043 
1 

24 
Rear Grill Sub-Assy 
209168000011 
1 

25 
Air Louver (Left) 
200007060114 
1 

26 
Axile Bush Sub-Assy 
1054204701 
1 

27 
Left Side Plate 
200085060068 
1 

28 
Remote Controller 
305001060060 
1 

29 
Drainage Hose 
05230014 
1 
 

129 

Sayfa 135

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Exploded View of GMV-ND18G/NhA1C-T(U),GMV-ND24G/NhA1C-T(U), 

GMV-ND18G/NhA3C-T(U),GMV-ND24G/NhA3C-T(U). 

Model 
GMV-ND18G/NhA1C-T(U)、GMV-ND18G/NhA3C-T(U) 
GMV-ND24G/NhA1C-T(U)、GMV-ND24G/NhA3C-T(U) 

No. 

Part Name 
Part Code 
Qty. 

1 
Front Panel 
200003060359T 
1 

2 
Filter Sub-Assy 
1101200703 
2 

3 
Front Case 
20000206010301 
1 

4 
Evaporator Assy 
011001063590 
1 

5 
Electronic Expansion Valve 
072009060076 
1 

6 
Filter Sub-Assy 
11120011 
1 

7 
Electric Expand Valve Fitting 
07200206001901 
1 

8 
Stepping Motor 
1521240210 
1 

9 
Axile Bush 
10542036 
2 

10 
Electric Box Assy 
100002084359 
1 

11 
Terminal Board 
4201026807 
1 

130 

Sayfa 136

GREE                                                Multi Variable Air Conditioners Indoor Unit  

Model 
GMV-ND18G/NhA1C-T(U)、GMV-ND18G/NhA3C-T(U) 
GMV-ND24G/NhA1C-T(U)、GMV-ND24G/NhA3C-T(U) 

No. 

Part Name 
Part Code 
Qty. 

12 
Main Board 
300002064511 
1 

13 
Display Board 
300001061358 
1 

14 
Right Side Plate 
20008606007401 
1 

15 
Wall Mounting Frame 
012043060024 
1 

16 
Stepping Motor 
1521210704 
1 

17 
Gas Sensor 
340024060017 
1 

18 
Brushless DC Motor 
15010406011601 
1 

19 
Air Louver 
200007060103 
1 

20 
Air Louver 1 
200007060104 
1 

21 
Air Louver 1 
200007060101 
2 

22 
Swing Lever 
200035060042 
1 

23 
Rear Grill Sub-Assy 
209168000018 
3 

24 
Axile Bush Sub-Assy 
1054204701 
1 

25 
Left Side Plate 
20008506006801 
1 

26 
Remote Controller 
305001060060 
1 

27 
Drainage Hose 
0523001405 
1 

131 

Sayfa 137

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI 519070

Add: West Jinji Rd, Qianshan Zhuhai, Guangdong, China
Tel: (+86-756)8522218
Fax: (+86-756)8669426
E-mail: global@cn.gree.com www.gree.com

JF00305743