Multi Variable Air Conditioners Indoor Units (GC202506-II) Capacity: 5800Btu/h~60000Btu/h Rated Frequency: 60Hz Refrigerant Type: R32
Thank you for choosing Gree air conditioners. In order to correctly install and use our units, and for the satisfactory operation effect, please read this manual carefully. This manual specifies safe operation requirements from perspectives of product introduction, control, troubleshooting and maintenance, as well as basic principles and implementation methods. Professional operators must abide by relevant national (local) safety requirements and technical specifications set forth in this manual during operations; otherwise, the air conditioning system may fail or be damaged, and personnel safety accident may also occur. Appliance filled with flammable gas R32. Before install the appliance, read the installation manual first. Before use the appliance, read the owner’s manual first. Before repair the appliance, read the service manual first. Foreword
PRODUCT ........................................................................................................................... 4 1 Product List ..................................................................................................................... 5 1.1 High Static Pressure Duct Type Indoor Unit ....................................................................... 5 1.2 Fresh Air Processing Duct Type Indoor Unit ...................................................................... 5 1.3 High Pressure Air Handler Indoor Unit ................................................................................ 5 1.4 360° Air Discharge Cassette Type Indoor Unit .................................................................... 6 1.5 360°Air Discharge Compact Cassette Type Indoor Unit .................................................... 6 1.6 1-way Cassette Type Indoor Unit ......................................................................................... 6 1.7 Wall Mounted Type Indoor Unit ............................................................................................ 7 2 Nomenclature .................................................................................................................. 8 3 Specifications ................................................................................................................. 9 3.1 High Static Pressure Duct Indoor Unit ................................................................................ 9 3.2 Fresh Air Processing Indoor Unit ....................................................................................... 11 3.3 Air Handler Indoor Unit ....................................................................................................... 12 3.4 360°Air Discharge Cassette Indoor Unit ............................................................................ 14 3.5 360°Air Discharge Compact Cassette Indoor Unit ........................................................... 17 3.6 1-way Cassette Indoor Unit ................................................................................................ 18 3.7 Wall Mounted Type Indoor Unit .......................................................................................... 19 CONTROL ......................................................................................................................... 22 1 Operation Flowchart ..................................................................................................... 23 2 Wired Controller ............................................................................................................ 24 2.1 Control Panel ....................................................................................................................... 24 2.2 Installation and Removal .................................................................................................... 29 3 Remote Controller ........................................................................................................ 32 3.1 Remote Controller YAP1F ................................................................................................... 32 4 Introduction to Unit Functions .................................................................................... 33 4.1 Engineering Application Functions Operated through the XE7C-23/H Wired Controller ..................................................................................................................................................... 33 4.2 Engineering Application Functions Operated through the YAP1F Remote Controller . 41 INSTALLATION ................................................................................................................. 43 1 Engineering Installation Preparation and Notice ....................................................... 44 1.1 Installation Notice ................................................................................................................ 44 1.2 Installation Key Points and Importance ............................................................................ 44 2 Installation Materials Selection ................................................................................... 45 2.1 Refrigerant Piping ............................................................................................................... 46 2.2 Condensate Water Pipe ....................................................................................................... 46 2.3 Insulation Material ............................................................................................................... 46 CONTENTS
2.4 Communication Cable and Control Cable ......................................................................... 47 2.5 Power Cable ......................................................................................................................... 47 2.6 Hanger Rod and Support .................................................................................................... 47 3 Installation of Indoor Unit ............................................................................................ 48 3.1Installation of High Static Pressure Duct Type Indoor Unit .............................................. 48 3.2 Installation of Fresh Air Processing Indoor Unit .............................................................. 50 3.3 Installation of Air Handler Type Indoor Unit ...................................................................... 51 3.4 Installation of 360°Air Discharge Cassette Type Indoor Unit .......................................... 54 3.5 Installation of 360°Air Discharge Compact Cassette Type Indoor Unit .......................... 56 3.6 Installation of 1-way Cassette Type Indoor Unit ............................................................... 57 3.7 Wall Mounted Type Indoor Unit .......................................................................................... 59 4 Installation of Connection Pipe ................................................................................... 61 4.1 Flaring Process .................................................................................................................... 61 4.2 Pipe Bending ........................................................................................................................ 62 4.3 Indoor Pipe Connection ...................................................................................................... 62 5 Installation of Drain Pipe .............................................................................................. 63 5.1 Precautions When Doing the Piping Work ........................................................................ 63 5.2 Installing the Drain Pipes .................................................................................................... 64 5.3 Precautions When Doing Riser Piping Work .................................................................... 66 5.4 Testing of Drain Piping ....................................................................................................... 66 6 Electrical Installation .................................................................................................... 66 6.1 Locking Joint Installation of 360°Air Discharge Cassette Type Indoor Unit .................. 67 6.2 Locking Joint Installation of 360°Air Discharge Compact Cassette Type Indoor Unit . 68 MAINTENANCE ................................................................................................................ 69 1 Malfunction List ............................................................................................................ 70 1.1 Malfunction List for the Wired Controller .......................................................................... 70 1.2 Display of Light Board (Only for Two-way Cassette Type Indoor Unit) .......................... 70 1.3 Exception Analyzing and Troubleshooting ....................................................................... 71 2 After-sales Emergency Masures .................................................................................. 83 3 About the Refrigerant Leakage Sensor ....................................................................... 83 4 Wiring Diagram ............................................................................................................. 85 4.1 High Static Pressure Duct Type Indoor Unit ..................................................................... 85 4.2 Fresh Air Processing Indoor Unit ...................................................................................... 86 4.3 Air Handler Type Indoor Unit .............................................................................................. 86 4.4 360°Air Discharge Casssette Type Indoor Unit ................................................................ 87 4.5 360°Air Discharge Compact Casssette Type Indoor Unit ................................................ 87 4.6 1-way Cassette Type Indoor Unit ....................................................................................... 88 4.7 Wall Mounted Type Indoor Unit .......................................................................................... 88
5 Disassembly and Assembly Procedure of Main Parts ............................................... 89 5.1 High Static Pressure Duct Type Indoor Unit ..................................................................... 89 5.2 Fresh Air Processing Indoor Unit ...................................................................................... 90 5.3 Air Handler Type Indoor Unit .............................................................................................. 92 5.4 360°Air Discharge Casssette Type Indoor Unit ................................................................ 98 5.5 360°Air Discharge Compact Casssette Type Indoor Unit .............................................. 101 5.6 1-way Cassette Type Indoor Unit ..................................................................................... 103 5.7 Wall Mounted Type Indoor Unit ........................................................................................ 106 6 Exploded Views and Part List .................................................................................... 108 6.1 High Static Pressure Duct Type Indoor Unit ................................................................... 108 6.2 Fresh Air Processing Type Indoor Unit ............................................................................ 112 6.3 Air Handler Type Indoor Unit ............................................................................................. 114 6.4 360°Air Discharge Casssette Type Indoor Unit ............................................................... 118 6.5 360°Air Discharge Compact Casssette Type Indoor Unit .............................................. 122 6.6 1-way Cassette Type Indoor Unit ..................................................................................... 124 6.7 Wall Mounted Type Indoor Unit ........................................................................................ 126
GREE Multi Variable Air Conditioners Indoor Unit PROHIBITED: (1) Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. (2) Do not pierce or burn. (3) Please note that refrigerant may be odorless. (4) The appliance shall be stored in a room without continuously operating ignition sources (For example: open flames, an operating gas appliance or an operating electric heater). (5) Indoor unit adopts special joints that can’t be detached. The installation method is the same with the common joints. However, because the joint can’t be detached, if it is badly connected and causes leakage, it needs to be cut and replaced by a new one through welding. (6) Using unsuitable parts or tools may lead to electric shock or fire hazard. (7) If refrigerant leaks during maintenance, please ventilate the room immediately. Heavy leakage may lead to breathing difficulty, severe injury or death. (8) Disconnect power before disassembling the appliance for maintenance. (9) The appliance should be maintained and cared by authorized technical personnel with necessary qualifications. WARNING: (1) If the working place is more than 2m's high, please wear a safety helmet, gloves and a safety belt. (2) Never mix any other substances except the specified refrigerant into the refrigerant circuit. (3) When re-locating the appliance, check whether the new location is strong enough to withstand the weight of the appliance. (4) If there is refrigerant leak, please fix the leak before charging in the refrigerant. After refrigerant is charged, check for refrigerant leaks. If you cannot spot the leak, stop the maintenance work. Please evacuate the system and close the service valve to prevent refrigerant leaking into the room. (5) Prepare suitable tools and protectors. (6) If you need to carry out maintenance or check the electric circuit without cutting off the power, please be careful not to touch the electrical parts. (7) The appliance should be maintained and cared by authorized technical personnel with necessary qualifications. (8) LEAK DETECTION SYSTEM installed. Unit must be powered except for service. (9) Keep any required ventilation openings clear of obstruction. (10) Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping. (11) Protection devices, piping and fittings shall be protected as far as possible against adverse environmental effects, for example, the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris. (12) Provision shall be made for expansion and contraction of long runs of piping. (13) Piping in refrigerating systems shall be so designed and installed to minimize the likelihood hydraulic shock damaging the system. Safety Notice on Maintenance 1
GREE Multi Variable Air Conditioners Indoor Unit (14) Steel pipes and components shall be protected against corrosion with a rustproof coating before applying any insulation. (15) Only auxiliary devices approved by the appliance manufacturer or declared suitable with the refrigerant shall be installed in connecting ductwork. NOTICE: (1) If the appliance is maintained at a humid place, it should be grounded to avoid electric shock. (2) Never repair the unit with wet hands. Operating the unit with wet hands may lead to electric shock. (3) If the unit is not correctly grounded, please check and fix it. (4) Before cleaning the unit, please disconnect power to prevent the inner fan from starting up and running at high speed; Otherwise personal injury may occur. (5) Measure the insulation resistance after maintenance. The resistance must be 1M or higher. Bad insulation may lead to electric shock. (6) Welding and cutting work must be done in a well-ventilated place. (7) Gas appliances, heaters and other fire sources should be kept away from the installation and maintenance site. (8) Maintenance should be done according to suggestions of the manufacturer. (9) Maintenance should be done only after the refrigerant is completely reclaimed from the unit. OBSERVED: (1) After the maintenance work is done, check the drainage of indoor unit. (2) Do not tilt the unit, otherwise, water may spill out from the unit and make the floor and furniture wet. (3) Disassembly of the unit, handling of the refrigerant, oil and accessories should all be done according to applicable local rules and regulations. 2
GREE Multi Variable Air Conditioners Indoor Unit PROHIBITED: (1) Never try to modify the unit, otherwise, it may cause electric shock, overheat or fire hazard. (2) If the power cord or conducting wires are scratched, please replace them. (3) Never use connected or extended power cord or share the power socket with other appliances. (4) Prepare a specialized power circuit for the appliance. WARNING: (1) If the power plug is dirty, please clean it before inserting it to the power socket. If the power plug is loose, please tighten it up. (2) Do not damage the power cord. A damaged or refitted power cord may lead to electric shock or fire hazard. (3) Check frequently whether the appliance is in good condition. NOTICE: (1) After changing the batteries of remote control, please discard them to avoid being swallowed by children. (2) When the unit is working, do not remove the fan cover. (3) Do not use organic solvents to wipe the controller operating panel. (4) Before cleaning the unit, cut off the power supply. Safety Notice on Operation 3
GREE Multi Variable Air Conditioners Indoor Unit PRODUCT 4
GREE Multi Variable Air Conditioners Indoor Unit 1 Product List 1.1 High Static Pressure Duct Type Indoor Unit Model Product GMV-ND07PHS/NhD-T(U) CM810N3040 7500 8500 GMV-ND09PHS/NhD-T(U) CM810N3050 9500 10500 GMV-ND12PHS/NhD-T(U) CM810N2990 12000 13500 GMV-ND15PHS/NhD-T(U) CM810N3070 15000 17000 GMV-ND18PHS/NhD-T(U) CM810N3060 18000 20000 GMV-ND24PHS/NhD-T(U) CM810N2940 24000 27000 GMV-ND30PHS/NhD-T(U) CM810N3080 30000 34000 GMV-ND36PHS/NhD-T(U) CM810N3100 36000 40000 GMV-ND42PHS/NhD-T(U) CM810N3090 42000 47000 GMV-ND48PHS/NhD-T(U) CM810N3110 48000 54000 GMV-ND54PHS/NhD-T(U) CM810N2930 54000 60000 1.2 Fresh Air Processing Duct Type Indoor Unit Model Product GMV-NDX42P/NhD-T(U) CM810N3230 42000 29000 208/230V ~60Hz R32 GMV-NDX48P/NhD-T(U) CM810N3220 48000 34000 GMV-NDX54P/NhD-T(U) CM810N3120 54000 45000 1.3 High Pressure Air Handler Indoor Unit Model Product Code GMV-ND12A/NhB-T(U) CM810N3290 12000 13500 GMV-ND18A/NhB-T(U) CM810N3020 18000 20000 GMV-ND24A/NhB-T(U) CM810N3370 24000 27000 GMV-ND30A/NhB-T(U) CM810N3010 30000 34000 GMV-ND36A/NhB-T(U) CM810N3360 36000 40000 GMV-ND42A/NhB-T(U) CM810N3000 42000 47000 GMV-ND48A/NhB-T(U) CM810N3340 48000 54000 GMV-ND54A/NhB-T(U) CM810N3350 54000 60000 GMV-ND60A/NhB-T(U) CM810N3030 60000 66000 CHAPTER 1 PRODUCT Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h Code 208/230V ~60Hz R32 Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h Code Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h 208/230V ~60Hz R32 5
GREE Multi Variable Air Conditioners Indoor Unit 1.4 360° Air Discharge Cassette Type Indoor Unit Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h Model Product Code GMV-ND07T/NhD-T(U) CM500N2470 7500 8500 GMV-ND09T/NhD-T(U) CM500N2520 9500 10500 GMV-ND12T/NhD-T(U) CM500N2440 12000 13500 GMV-ND15T/NhD-T(U) CM500N2510 15000 17000 GMV-ND18T/NhD-T(U) CM500N2430 18000 20000 208/230V ~60Hz R32 GMV-ND24T/NhD-T(U) CM500N2500 24000 27000 GMV-ND30T/NhD-T(U) CM500N2460 30000 34000 GMV-ND36T/NhD-T(U) CM500N2490 36000 40000 GMV-ND42T/NhD-T(U) CM500N2480 42000 47000 GMV-ND48T/NhD-T(U) CM500N2420 48000 54000 1.5 360°Air Discharge Compact Cassette Type Indoor Unit Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h Model Product Code GMV-ND05T/NhE-T(U) CM500N2550 5800 6200 GMV-ND07T/NhE-T(U) CM500N2570 7500 8500 GMV-ND09T/NhE-T(U) CM500N2580 9500 10500 208/230V ~60Hz R32 GMV-ND12T/NhE-T(U) CM500N2560 12000 13500 GMV-ND15T/NhE-T(U) CM500N2590 15000 17000 GMV-ND18T/NhE-T(U) CM500N2450 18000 20000 1.6 1-way Cassette Type Indoor Unit Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h Model Product Code GMV-ND07TD/NhA-T(U) CM502N0220 7500 8500 208/230V ~60Hz R32 GMV-ND09TD/NhA-T(U) CM502N0230 9500 10500 GMV-ND12TD/NhA-T(U) CM502N0210 12000 13500 6
GREE Multi Variable Air Conditioners Indoor Unit 1.7 Wall Mounted Type Indoor Unit Model Product GMV-ND06G/NhA1C-T(U) CM100N3560 6000 7500 GMV-ND07G/NhA1C-T(U) CM100N3570 7500 8500 GMV-ND09G/NhA1C-T(U) CM100N3410 9500 10500 GMV-ND12G/NhA1C-T(U) CM100N3590 12000 13500 GMV-ND14G/NhA1C-T(U) CM100N3430 15000 17000 GMV-ND18G/NhA1C-T(U) CM100N3580 18000 20000 GMV-ND24G/NhA1C-T(U) CM100N3420 24000 27000 GMV-ND06G/NhA3C-T(U) CM100N3490 6000 7500 GMV-ND07G/NhA3C-T(U) CM100N3510 7500 8500 GMV-ND09G/NhA3C-T(U) CM100N3520 9500 10500 GMV-ND12G/NhA3C-T(U) CM100N3500 12000 13500 GMV-ND14G/NhA3C-T(U) CM100N3530 15000 17000 GMV-ND18G/NhA3C-T(U) CM100N3550 18000 20000 GMV-ND24G/NhA3C-T(U) CM100N3540 24000 27000 Cooling Capacity Heating Capacity Power Supply Refrigerant Appearance Btu/h Btu/h Code 208/230V ~60Hz R32 7
GREE Multi Variable Air Conditioners Indoor Unit 2 Nomenclature Nomenclature of Indoor Unit: GMV - N □ □ □ □ □ / □ □ - □ □ 1 2 3 4 5 6 7 8 9 10 11 No. Description Options 1 Product code GMV-Gree Multi VRF Units 2 indoor unit code indoor unit-N 3 Motor type D-DC motor NULL-AC motor 4 Function code X-fresh air 5 Cooling capacity/air volume code Indoor unit: nominal cooling capacity /1000(Btu/h) 6 Unit type 7 With water pump or not With water pump-S (S is not displayed for the cassette unit with water pump) 8 Refrigerant code Nh-R32 9 Design serial No. Nominate by A, B, C or expand it by 1, 2, 3… 10 Power T-208/230V~,60Hz 11 Sale Area code (U)-North America P-standard static pressure duct type indoor unit PH-high static pressure duct type indoor unit T-360°Air Discharge type indoor unit A-Air handler type indoor unit TD-one-way cassette type indoor unit 8
GREE Multi Variable Air Conditioners Indoor Unit 3 Specifications 3.1 High Static Pressure Duct Indoor Unit Model GMV-ND07PHS/NhD-T(U) GMV-ND09PHS/NhD-T(U)GMV-ND12PHS/NhD-T(U) Cooling Btu/h 7500 9500 12000 Capacity Heating Btu/h 8500 10500 13500 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 470/355/295 470/355/295 470/355/295 Airflow volume(H/M/L) m3/h 800/600/500 800/600/500 800/600/500 Pa 60/0~150 60/0~150 60/0~150 ESP In.W.G 0.24/0~0.6 0.24/0~0.6 0.24/0~0.6 Sound pressure level(H/M/L) dB(A) 33/30/27 33/30/27 35/32/29 Liquid In. 1/4 1/4 1/4 Connecting pipe Gas In. 3/8 3/8 3/8 Liquid mm Φ6.35 Φ6.35 Φ6.35 Connecting pipe Gas mm Φ9.52 Φ9.52 Φ9.52 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 Dimension (WxDxH) Package In. 47-7/16×32×14-3/16 47-7/16×32×14-3/16 47-7/16×32×14-3/16 Outline mm 1000×700×300 1000×700×300 1000×700×300 Dimension (WxDxH) Package mm 1205×813×360 1205×813×360 1205×813×360 Net weight/Gross weight LBS 94/108 94/108 94/108 Net weight/Gross weight kg 42.5/49 42.5/49 42.5/49 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 1.4 1.4 1.4 Fuse Capacity A 10 10 10 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U)GMV-ND24PHS/NhD-T(U) Cooling Btu/h 15000 18000 24000 Capacity Heating Btu/h 17000 20000 27000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 590/470/410 590/470/410 735/620/560 Airflow volume(H/M/L) m3/h 1000/800/700 1000/800/700 1250/1050/950 Pa 90/0~200 90/0~200 90/0~200 ESP In.W.G 0.36/0~0.8 0.36/0~0.8 0.36/0~0.8 Sound pressure level(H/M/L) dB(A) 39/36/33 39/36/33 40/37/34 Liquid In. 1/4 1/4 1/4 Connecting pipe Gas In. 1/2 1/2 1/2 Liquid mm Φ6.35 Φ6.35 Φ6.35 Connecting pipe Gas mm Φ12.7 Φ12.7 Φ12.7 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 39-3/8×27-9/16×11-13/16 Dimension (W×D×H) Package In. 47-7/16×32×14-3/16 47-7/16×32×14-3/16 47-7/16×32×14-3/16 Outline mm 1000×700×300 1000×700×300 1000×700×300 Dimension (W×D×H) Package mm 1205×813×360 1205×813×360 1205×813×360 9
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U)GMV-ND24PHS/NhD-T(U) Net weight/Gross weight LBS 95/109 95/109 95/109 Net weight/Gross weight kg 43/49.5 43/49.5 43/49.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 1.8 1.8 2.2 Fuse Capacity A 10 10 10 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND30PHS/NhD-T(U) GMV-ND36PHS/NhD-T(U) GMV-ND42PHS/NhD-T(U) Cooling Btu/h 30000 36000 42000 Capacity Heating Btu/h 34000 40000 47000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 1175/940/825 1175/940/825 1175/940/825 Airflow volume(H/M/L) m3/h 2000/1600/1400 2000/1600/1400 2000/1600/1400 Pa 90/0~200 90/0~200 90/0~200 ESP In.W.G 0.36/0~0.8 0.36/0~0.8 0.36/0~0.8 Sound pressure level(H/M/L) dB(A) 44/40/37 44/40/37 44/40/37 Liquid In. 3/8 3/8 3/8 Connecting pipe Gas In. 5/8 5/8 5/8 Liquid mm Φ9.52 Φ9.52 Φ9.52 Connecting pipe Gas mm Φ15.9 Φ15.9 Φ15.9 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 55-1/8×27-9/16×11-13/16 55-1/8×27-9/16×11-13/16 55-1/8×27-9/16×11-13/16 Dimension (W×D×H) Package In. 63-1/16×32×14-3/8 63-1/16×32×14-3/8 63-1/16×32×14-3/8 Outline mm 1400×700×300 1400×700×300 1400×700×300 Dimension (W×D×H) Package mm 1601×813×365 1601×813×365 1601×813×365 Net weight/Gross weight LBS 128/143 128/143 128/143 Net weight/Gross weight kg 58/65 58/65 58/65 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 2.7 2.7 2.7 Fuse Capacity A 10 10 10 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND48PHS/NhD-T(U) GMV-ND54PHS/NhD-T(U) Cooling Btu/h 48000 54000 Capacity Heating Btu/h 54000 60000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 CFM 1470/1175/1030 1470/1175/1030 Airflow volume(H/M/L) m3/h 2500/2000/1750 2500/2000/1750 Pa 90/0~200 90/0~200 ESP In.W.G 0.36/0~0.8 0.36/0~0.8 Sound pressure level(H/M/L) dB(A) 46/44/41 46/44/41 Liquid In. 3/8 3/8 Connecting pipe Gas In. 5/8 5/8 10
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND48PHS/NhD-T(U) GMV-ND54PHS/NhD-T(U) Liquid mm Φ9.52 Φ9.52 Connecting pipe Gas mm Φ15.9 Φ15.9 In. Φ1 Φ1 Drain pipe mm Φ25 Φ25 Outline In. 55-1/8×27-9/16×11-13/16 55-1/8×27-9/16×11-13/16 Dimension (W×D×H) Package In. 63-1/16×32×14-3/8 63-1/16×32×14-3/8 Outline mm 1400×700×300 1400×700×300 Dimension (W×D×H) Package mm 1601×813×365 1601×813×365 Net weight/Gross weight LBS 128/143 128/143 Net weight/Gross weight kg 58/65 58/65 MOP (Max Fuse Size) A 15 15 MCA (Min. Circuit Ampacity) A 3.7 3.7 Fuse Capacity A 10 10 Refrigeration Control Device EXV EXV Protection Device Fuse Fuse 3.2 Fresh Air Processing Indoor Unit Model GMV-NDX42P/NhD-T(U) GMV-NDX48P/NhD-T(U) GMV-NDX54P/NhD-T(U) Cooling Btu/h 42000 48000 54000 Capacity Heating*1 Btu/h 29000 34000 45000 Heating*2 Btu/h 36000 41000 52000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 705/590~1175 705/590~1175 880/705~1470 Airflow volume(H/M/L) m3/h 1200/1000~2000 1200/1000~2000 1500/1200~2500 Pa 150/50~220 150/50~220 150/50~220 ESP In.W.G 0.6/0.2~0.88 0.6/0.2~0.88 0.6/0.2~0.88 Sound pressure level(H/M/L) dB(A) 45 45 46 Liquid In. 3/8 3/8 3/8 Gas In. 5/8 5/8 5/8 Connecting pipe Liquid mm Φ9.52 Φ9.52 Φ9.52 Gas mm Φ15.9 Φ15.9 Φ15.9 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 55-1/8×27-9/16×11- 13/16 55-1/8×27-9/16×11- 13/16 55-1/8×27-9/16×11- 13/16 Package In. 63-1/16×32×14-3/8 63-1/16×32×14-3/8 63-1/16×32×14-3/8 Dimension (W×D×H) Outline mm 1400×700×300 1400×700×300 1400×700×300 Package mm 1601×813×365 1601×813×365 1601×813×365 Net weight/Gross weight LBS 126/141 126/141 126/141 Net weight/Gross weight kg 57/64 57/64 57/64 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 2.7 2.7 3.7 Fuse Capacity A 10 10 10 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse 11
GREE Multi Variable Air Conditioners Indoor Unit ① Rated cooling capacity test conditions: indoor 95.0°F DB/82.4°F WB, outdoor 95.0°F DB; connection pipe length: 24-5/8ft., without height difference between units. The default air outlet temperature of the unit is 64.4°F. ② Rated heating capacity test conditions: *1. indoor 44.6°F DB, outdoor 44.6°F DB/42.8 °F WB, *2 indoor 32°F DB, outdoor 32°F DB/26.8°F WB, connection pipe length: 24-5/8ft., without height difference between units. The default air outlet temperature of the unit is 71.6°F. ③ The Sound Pressure Level will change with the External Static Pressure. VRF fresh air series indoor unit is a kind of air processing unit that inhales the fresh air from outdoor side and then processes it to provide for the user in the room. This product series can only connect to one VRF fresh air indoor unit when linking to the outdoor unit. Optional Indoor unit model Recommended capacity of outdoor unit Connected outdoor unit series Connection condition GMV-NDX42P/NhD-T(U) 42000/48000Btu/h R32 GMV6 Mini R32 Ultra Heat GMV6 Mini GMV-NDX48P/NhD-T(U) 48000Btu/h GMV-NDX54P/NhD-T(U) 60000Btu/h Please match the outdoor unit in strict accordance with the above requirements, otherwise, the comfortableness will be affected or even the unit will be damaged. 3.3 Air Handler Indoor Unit Model GMV-ND12A/NhB-T(U) GMV-ND18A/NhB-T(U) GMV-ND24A/NhB-T(U) Cooling Btu/h 12000 18000 24000 Capacity Heating Btu/h 13500 20000 27000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 650/520/300 650/520/300 880/800/690 Airflow volume(H/M/L) m3/h 1105/884/510 1105/884/510 1495/1359/1172 Pa 50/0~250 50/0~250 50/0~250 ESP In.W.G 0.2/0~1.0 0.2/0~1.0 0.2/0~1.0 Sound pressure level(H/M/L) dB(A) 40/37/35 40/37/35 42/40/38 Liquid In. 1/4 1/4 1/4 Gas In. 3/8 1/2 1/2 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ12.7 Φ12.7 In. G1 G1 G1 Drain pipe mm Φ25.4 Φ25.4 Φ25.4 12 The capacity of outdoor unit is not less than the recommended capacity and cannot exceed 10% of the recommended capacity.
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND12A/NhB-T(U) GMV-ND18A/NhB-T(U) GMV-ND24A/NhB-T(U) Outline In. 21-1/4×18-1/8×43-1/2 21-1/4×18-1/8×43-1/2 21-1/4×18-1/8×43-1/2 Package In. 26×20-9/16×46-1/4 26×20-9/16×46-1/4 26×20-9/16×46-1/4 Dimension (W×D×H) Outline mm 540×460×1105 540×460×1105 540×460×1105 Package mm 660×523×1175 660×523×1175 660×523×1175 Net weight/Gross weight LBS 126/139 126/139 130/143 Net weight/Gross weight kg 57/63 57/63 59/65 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 2.0 2.0 3.0 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND30A/NhB-T(U) GMV-ND36A/NhB-T(U) GMV-ND42A/NhB-T(U) Cooling Btu/h 30000 36000 42000 Capacity Heating Btu/h 34000 40000 47000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 910/820/710 1230/1100/970 1260/1120/1000 Airflow volume(H/M/L) m3/h 1546/1393/1206 2090/1869/1648 2141/1903/1699 Pa 50/0~250 50/0~250 50/0~250 ESP In.W.G 0.2/0~1.0 0.2/0~1.0 0.2/0~1.0 Sound pressure level(H/M/L) dB(A) 42/40/38 48/46/44 48/46/44 Liquid In. 3/8 3/8 3/8 Gas In. 5/8 5/8 5/8 Connecting pipe Liquid mm Φ9.52 Φ9.52 Φ9.52 Gas mm Φ15.9 Φ15.9 Φ15.9 In. G1 G1 G1 Drain pipe mm Φ25.4 Φ25.4 Φ25.4 Outline In. 21-1/4×18-1/8×43-1/2 21-1/4×21×1/4×48-1/4 21-1/4×21×1/4×48-1/4 Package In. 26×20-9/16×46-1/4 26×23-3/4×51 26×23-3/4×51 Dimension (W×D×H) Outline mm 540×460×1105 540×540×1224 540×540×1224 Package mm 660×523×1175 660×603×1295 660×603×1295 Net weight/Gross weight LBS 130/143 157/172 157/172 Net weight/Gross weight kg 59/65 71/78 71/78 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 3.0 4.0 4.0 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) Cooling Btu/h 48000 54000 60000 Capacity Heating Btu/h 54000 60000 66000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 1800/1600/1500 1800/1600/1500 1820/1650/1530 Airflow volume(H/M/L) m3/h 3059/2719/2549 3059/2719/2549 3093/2804/2600 Pa 50/0~250 50/0~250 50/0~250 ESP In.W.G 0.2/0~1.0 0.2/0~1.0 0.2/0~1.0 Sound pressure level(H/M/L) dB(A) 51/50/49 51/50/49 51/50/49 13
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) Liquid In. 3/8 3/8 3/8 Gas In. 5/8 5/8 5/8 Connecting pipe Liquid mm Φ9.52 Φ9.52 Φ9.52 Gas mm Φ15.9 Φ15.9 Φ15.9 In. G1 G1 G1 Drain pipe mm Φ25.4 Φ25.4 Φ25.4 Outline In. 24-13/16×21-1/4×51- 15/16 24-13/16×21-1/4×51- 15/16 24-13/16×21-1/4×51- 15/16 Package In. 27-5/16×26×54-13/16 27-5/16×26×54-13/16 27-5/16×26×54-13/16 Dimension (W×D×H) Outline mm 630×540×1320 630×540×1320 630×540×1320 Package mm 693×660×1392 693×660×1392 693×660×1392 Net weight/Gross weight LBS 194/212 194/212 194/212 Net weight/Gross weight kg 88/96 88/96 88/96 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 7.7 7.7 7.7 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse 3.4 360°Air Discharge Cassette Indoor Unit Model GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) Cooling Btu/h 7500 9500 12000 Capacity Heating Btu/h 8500 10500 13500 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 470/412/353 470/412/353 470/412/353 Airflow volume(H/M/L) m3/h 800/700/600 800/700/600 800/700/600 Sound pressure level(H/M/L) dB(A) 37/33/28 37/33/28 37/33/28 Liquid In. 1/4 1/4 1/4 Gas In. 3/8 3/8 3/8 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ9.52 Φ9.52 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×9 7/16 Package In. 36 3/4×36 3/4×11 1/2 36 3/4×36 3/4×11 1/2 36 3/4×36 3/4×11 1/2 Dimension (W×D×H) Outline mm 840×840×240 840×840×240 840×840×240 Package mm 933×933×292 933×933×292 933×933×292 Net weight/Gross weight LBS 50/61 50/61 50/61 Net weight/Gross weight kg 22.5/27.5 22.5/27.5 22.5/27.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.9 0.9 0.9 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model TF06 TF06 TF06 Outline In. 37 3/8×37 3/8×2 9/16 37 3/8×37 3/8×2 9/16 37 3/8×37 3/8×2 9/16 Decoration Dimension paneI Package In. 40 5/8×40 1/8×4 3/8 40 5/8×40 1/8×4 3/8 40 5/8×40 1/8×4 3/8 (W×D×H) Outline mm 950×950×65 950×950×65 950×950×65 14
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) Dimension (W×D×H) Package mm 1033×1020×110 1033×1020×110 1033×1020×110 Decoration Net weight/Gross weight LBS 13.2/20.9 13.2/20.9 13.2/20.9 paneI Net weight/Gross weight kg 6/9.5 6/9.5 6/9.5 Model GMV-ND15T/NhD-T(U) GMV-ND18T/NhD-T(U) GMV-ND24T/NhD-T(U) Cooling Btu/h 15000 18000 24000 Capacity Heating Btu/h 17000 20000 27000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 560/500/440 560/500/440 736/677/588 Airflow volume(H/M/L) m3/h 950/850/750 950/850/750 1250/1150/1000 Sound pressure level(H/M/L) dB(A) 40/37/34 40/37/34 40/37/34 Liquid In. 1/4 1/4 1/4 Gas In. 1/2 1/2 1/2 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ12.7 Φ12.7 Φ12.7 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×9 7/16 33 1/16×33 1/16×11 7/16 Package In. 36 3/4×36 3/4×11 1/2 36 3/4×36 3/4×11 1/2 36 3/4×36 3/4×13 9/16 Dimension (W×D×H) Outline mm 840×840×240 840×840×240 840×840×290 Package mm 933×933×292 933×933×292 933×933×345 Net weight/Gross weight LBS 50/61 50/61 56/67 Net weight/Gross weight kg 22.5/27.5 22.5/27.5 25.5/30.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.9 0.9 1.1 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model TF06 TF06 TF06 Outline In. 37 3/8×37 3/8×2 9/16 37 3/8×37 3/8×2 9/16 37 3/8×37 3/8×2 9/16 Package In. 40 5/8×40 1/8×4 3/8 40 5/8×40 1/8×4 3/8 40 5/8×40 1/8×4 3/8 Dimension (W×D×H) Outline mm 950×950×65 950×950×65 950×950×65 Decoration paneI Package mm 1033×1020×110 1033×1020×110 1033×1020×110 Net weight/Gross weight LBS 13.2/20.9 13.2/20.9 13.2/20.9 Net weight/Gross weight kg 6/9.5 6/9.5 6/9.5 Model GMV-ND30T/NhD-T(U) GMV-ND36T/NhD-T(U) Cooling Btu/h 30000 36000 Capacity Heating Btu/h 34000 40000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 CFM 883/706/588 883/706/588 Airflow volume(H/M/L) m3/h 1500/1200/1000 1500/1200/1000 Sound pressure level(H/M/L) dB(A) 44/39/34 44/39/34 Liquid In. 3/8 3/8 Connecting pipe Gas In. 5/8 5/8 Liquid mm Φ9.52 Φ9.52 15
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND30T/NhD-T(U) GMV-ND36T/NhD-T(U) Connecting pipe Gas mm Φ15.9 Φ15.9 In. Φ1 Φ1 Drain pipe mm Φ25 Φ25 Outline In. 33 1/16×33 1/16×11 7/16 33 1/16×33 1/16×11 7/16 Package In. 36 3/4×36 3/4×13 9/16 36 3/4×36 3/4×13 9/16 Outline mm 840×840×290 840×840×290 Package mm 933×933×345 933×933×345 Net weight/Gross weight LBS 56/67 56/67 Dimension (W×D×H) Net weight/Gross weight kg 25.5/30.5 25.5/30.5 MOP (Max Fuse Size) A 15 15 MCA (Min. Circuit Ampacity) A 1.2 1.2 Fuse Capacity A 3.15 3.15 Refrigeration Control Device EXV EXV Protection Device Fuse Fuse Model TF06 TF06 Outline In. 37 3/8×37 3/8×2 9/16 37 3/8×37 3/8×2 9/16 Package In. 40 5/8×40 1/8×4 3/8 40 5/8×40 1/8×4 3/8 Dimension Decoration (W×D×H) Outline mm 950×950×65 950×950×65 paneI Package mm 1033×1020×110 1033×1020×110 Net weight/Gross weight LBS 13.2/20.9 13.2/20.9 Net weight/Gross weight kg 6/9.5 6/9.5 Model GMV-ND42T/NhD-T(U) GMV-ND48T/NhD-T(U) Cooling Btu/h 42000 48000 Capacity Heating Btu/h 47000 54000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 CFM 1060/853/677 1060/853/677 Airflow volume(H/M/L) m3/h 1800/1450/1150 1800/1450/1150 Sound pressure level(H/M/L) dB(A) 45/40/35 45/40/35 Liquid In. 3/8 3/8 Gas In. 5/8 5/8 Connecting pipe Liquid mm Φ9.52 Φ9.52 Gas mm Φ15.9 Φ15.9 In. Φ1 Φ1 Drain pipe mm Φ25 Φ25 Outline In. 33 1/16×33 1/16×11 7/16 33 1/16×33 1/16×11 7/16 Package In. 36 3/4×36 3/4×13 9/16 36 3/4×36 3/4×13 9/16 Dimension (W×D×H) Outline mm 840×840×290 840×840×290 Package mm 933×933×345 933×933×345 Net weight/Gross weight LBS 56/67 56/67 Net weight/Gross weight kg 25.5/30.5 25.5/30.5 MOP (Max Fuse Size) A 15 15 MCA (Min. Circuit Ampacity) A 1.3 1.3 Fuse Capacity A 3.15 3.15 Refrigeration Control Device EXV EXV Protection Device Fuse Fuse Model TF06 TF06 Decoration Outline In. 37 3/8×37 3/8×2 9/16 37 3/8×37 3/8×2 9/16 Dimension paneI (W×D×H) Package In. 40 5/8×40 1/8×4 3/8 40 5/8×40 1/8×4 3/8 16
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND42T/NhD-T(U) GMV-ND48T/NhD-T(U) Outline mm 950×950×65 950×950×65 Dimension (W×D×H) Package mm 1033×1020×110 1033×1020×110 Decoration paneI Net weight/Gross weight LBS 13.2/20.9 13.2/20.9 Net weight/Gross weight kg 6/9.5 6/9.5 3.5 360°Air Discharge Compact Cassette Indoor Unit Model GMV-ND05T/NhE-T(U) GMV-ND07T/NhE-T(U) GMV-ND09T/NhE-T(U) Cooling Btu/h 5800 7500 9500 Capacity Heating Btu/h 6200 8500 10500 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 290/270/220 290/270/220 360/320/280 Airflow volume(H/M/L) m3/h 500/460/370 500/460/370 620/550/480 Sound pressure level(H/M/L) dB(A) 33/30/28 33/30/28 37/35/30 Liquid In. 1/4 1/4 1/4 Gas In. 3/8 3/8 3/8 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ9.52 Φ9.52 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 Package In. 27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 Dimension (W×D×H) Outline mm 570×570×265 570×570×265 570×570×265 Package mm 698×653×295 698×653×295 698×653×295 Net weight/Gross weight LBS 37.5/47.4 37.5/47.4 37.5/47.4 Net weight/Gross weight kg 17.0/21.5 17.0/21.5 17.0/21.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.5 0.5 0.5 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model TF05 TF05 TF05 Outline In. 24 3/8×24 3/8×1 7/8 24 3/8×24 3/8×1 7/8 24 3/8×24 3/8×1 7/8 Package In. 27 1/4×27 1/4×4 1/2 27 1/4×27 1/4×4 1/2 27 1/4×27 1/4×4 1/2 Dimension (W×D×H) Outline mm 620×620×47.5 620×620×47.5 620×620×47.5 Decoration paneI Package mm 693×693×115 693×693×115 693×693×115 Net weight/Gross weight LBS 6.6/10 6.6/10 6.6/10 Net weight/Gross weight kg 3/4.5 3/4.5 3/4.5 Model GMV-ND12T/NhE-T(U) GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U) Cooling Btu/h 12000 15000 18000 Capacity Heating Btu/h 13500 17000 20000 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 360/320/280 360/320/280 430/385/330 Airflow volume(H/M/L) m3/h 620/550/480 620/550/480 730/650/560 Sound pressure level(H/M/L) dB(A) 37/35/30 37/35/30 43/40/38 17
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND12T/NhE-T(U) GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U) Liquid In. 1/4 1/4 1/4 Gas In. 3/8 1/2 1/2 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ12.7 Φ12.7 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 22 7/16×22 7/16×10 7/16 Package In. 27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 27 1/2×25 11/16×11 5/8 Dimension (W×D×H) Outline mm 570×570×265 570×570×265 570×570×265 Package mm 698×653×295 698×653×295 698×653×295 Net weight/Gross weight LBS 37.5/47.4 37.5/47.4 37.5/47.4 Net weight/Gross weight kg 17.0/21.5 17.0/21.5 17.0/21.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.5 0.5 0.5 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model TF05 TF05 TF05 Outline In. 24 3/8×24 3/8×1 7/8 24 3/8×24 3/8×1 7/8 24 3/8×24 3/8×1 7/8 Package In. 27 1/4×27 1/4×4 1/2 27 1/4×27 1/4×4 1/2 27 1/4×27 1/4×4 1/2 Dimension (W×D×H) Outline mm 620×620×47.5 620×620×47.5 620×620×47.5 Decoration paneI Package mm 693×693×115 693×693×115 693×693×115 Net weight/Gross weight LBS 6.6/10 6.6/10 6.6/10 Net weight/Gross weight kg 3/4.5 3/4.5 3/4.5 3.6 1-way Cassette Indoor Unit Model GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) Cooling Btu/h 7500 9500 12000 Capacity Heating Btu/h 8500 10500 13500 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 353/294/265 353/294/265 353/294/265 Airflow volume(H/M/L) m3/h 600/500/450 600/500/450 600/500/450 Sound pressure level(H/M/L) dB(A) 36/33/28 36/33/28 36/33/28 Liquid In. 1/4 1/4 1/4 Gas In. 3/8 3/8 3/8 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ9.52 Φ9.52 In. Φ1 Φ1 Φ1 Drain pipe mm Φ25 Φ25 Φ25 Outline In. 38 7/8×15 3/16×7 38 7/8×15 3/16×7 38 7/8×15 3/16×7 Package In. 51 1/2×19 3/4×12 3/16 51 1/2×19 3/4×12 3/16 51 1/2×19 3/4×12 3/16 Dimension (W×D×H) Outline mm 987×385×178 987×385×178 987×385×178 Package mm 1307×501×310 1307×501×310 1307×501×310 Net weight/Gross weight LBS 42/57 42/57 42/57 18
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) Net weight/Gross weight kg 19/26 19/26 19/26 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.3 0.3 0.3 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model TD01 TD01 TD01 Outline In. 47 1/4×18 1/8×2 3/16 47 1/4×18 1/8×2 3/16 47 1/4×18 1/8×2 3/16 Package In. 49 13/16×21 1/8×4 3/4 49 13/16×21 1/8×4 3/4 49 13/16×21 1/8×4 3/4 Dimension (W×D×H) Outline mm 1200×460×55 1200×460×55 1200×460×55 Decoration paneI Package mm 1265×536×121 1265×536×121 1265×536×121 Net weight/Gross weight LBS 9.3/13.2 9.3/13.2 9.3/13.2 Net weight/Gross weight kg 4.2/6 4.2/6 4.2/6 3.7 Wall Mounted Type Indoor Unit Model GMV-ND06G/NhA1C-T(U) GMV-ND07G/NhA1C-T(U) GMV-ND09G/NhA1C-T(U) Cooling Btu/h 6000 7500 9500 Capacity Heating Btu/h 7500 8500 10500 Power supply V/Ph/Hz 208/230V ~ 60 208/230V ~ 60 208/230V ~ 60 CFM 265 265 265 Airflow volume(H) m3/h 450 450 450 Sound pressure level(H/M/L) dB(A) 36/34/31 36/34/31 36/34/31 Liquid In. 1/4 1/4 1/4 Gas In. 3/8 3/8 3/8 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ9.52 Φ9.52 In. Φ13/16 Φ13/16 Φ13/16 Drain pipe mm Φ20 Φ20 Φ20 Outline In. 34 1/8×8 1/8×10 7/8 34 1/8×8 1/8×10 7/8 34 1/8×8 1/8×10 7/8 Package In. 39 3/16×13 1/2×10 31/32 39 3/16×13 1/2×10 31/32 39 3/16×13 1/2×10 31/32 Dimension (WxDxH) Outline mm 867×206×276 867×206×276 867×206×276 Package mm 996×343×279 996×343×279 996×343×279 Net weight/Gross weight LBS 21/26 21/26 21/26 Net weight/Gross weight kg 9.5/12 9.5/12 9.5/12 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.9 0.9 0.9 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND12G/NhA1C-T(U) GMV-ND14G/NhA1C-T(U) GMV-ND18G/NhA1C-T(U) Cooling Btu/h 12000 15000 18000 Capacity Heating Btu/h 13500 17000 20000 Power supply V/Ph/Hz 208/230V ~ 60 208/230V ~ 60 208/230V ~ 60 CFM 380 380 530 Airflow volume(H) m3/h 650 650 900 Sound pressure level(H/M/L) dB(A) 42/39/34 42/39/34 44/42/38 19
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND12G/NhA1C-T(U) GMV-ND14G/NhA1C-T(U) GMV-ND18G/NhA1C-T(U) Liquid In. 1/4 1/4 1/4 Gas In. 3/8 1/2 1/2 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ12.7 Φ12.7 In. Φ13/16 Φ13/16 Φ13/16 Drain pipe mm Φ20 Φ20 Φ20 Outline In. 38 1/2×9 3/4×13 1/8 38 1/2×9 3/4×13 1/8 43 15/16×9 3/4×13 1/8 Package In. 43 11/16×16 1/8×13 11/16 43 11/16×16 1/8×13 11/16 49 1/4×16 1/2×14 1/32 Dimension (WxDxH) Outline mm 978×248×333 978×248×333 1116×248×333 Package mm 1109×410×347 1109×410×347 1251×419×356 Net weight/Gross weight LBS 29/36 29/36 34/43 Net weight/Gross weight kg 13/16.5 13/16.5 15.5/19.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 1.1 1.1 1.1 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND24G/NhA1C-T(U) GMV-ND06G/NhA3C-T(U) GMV-ND07G/NhA3C-T(U) Cooling Btu/h 24000 6000 7500 Capacity Heating Btu/h 27000 7500 8500 Power supply V/Ph/Hz 208/230V ~60 208/230V ~60 208/230V ~60 CFM 530 265 265 Airflow volume(H) m3/h 900 450 450 Sound pressure level(H/M/L) dB(A) 44/42/38 36/34/31 36/34/31 Liquid In. 1/4 1/4 1/4 Gas In. 1/2 3/8 3/8 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ12.7 Φ9.52 Φ9.52 In. Φ13/16 Φ13/16 Φ13/16 Drain pipe mm Φ20 Φ20 Φ20 Outline In. 43 15/16×9 3/4×13 1/8 34 1/8×8 1/8×10 7/8 34 1/8×8 1/8×10 7/8 Package In. 49 1/4×16 1/2×14 1/32 39 3/16×13 1/2×10 31/32 39 3/16×13 1/2×10 31/32 Dimension (WxDxH) Outline mm 1116×248×333 867×206×276 867×206×276 Package mm 1251×419×356 996×343×279 996×343×279 Net weight/Gross weight LBS 34/43 21/26 21/26 Net weight/Gross weight kg 15.5/19.5 9.5/12 9.5/12 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 1.1 0.9 0.9 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND09G/NhA3C-T(U) GMV-ND12G/NhA3C-T(U) GMV-ND14G/NhA3C-T(U) Cooling Btu/h 9500 12000 15000 Capacity Heating Btu/h 10500 13500 17000 Power supply V/Ph/Hz 208/230V ~ 60 208/230V ~ 60 208/230V ~ 60 Airflow volume(H) CFM 265 380 380 20
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND09G/NhA3C-T(U) GMV-ND12G/NhA3C-T(U) GMV-ND14G/NhA3C-T(U) Airflow volume(H) m3/h 450 650 650 Sound pressure level(H/M/L) dB(A) 36/34/31 42/39/34 42/39/34 Liquid In. 1/4 1/4 1/4 Gas In. 3/8 3/8 1/2 Connecting pipe Liquid mm Φ6.35 Φ6.35 Φ6.35 Gas mm Φ9.52 Φ9.52 Φ12.7 In. Φ13/16 Φ13/16 Φ13/16 Drain pipe mm Φ20 Φ20 Φ20 Outline In. 34 1/8×8 1/8×10 7/8 38 1/2×9 3/4×13 1/8 38 1/2×9 3/4×13 1/8 Package In. 39 3/16×13 1/2×10 31/32 43 11/16×16 1/8×13 11/16 43 11/16×16 1/8×13 11/16 Dimension (WxDxH) Outline mm 867×206×276 978×248×333 978×248×333 Package mm 996×343×279 1109×410×347 1109×410×347 Net weight/Gross weight LBS 21/26 29/36 29/36 Net weight/Gross weight kg 9.5/12 13/16.5 13/16.5 MOP (Max Fuse Size) A 15 15 15 MCA (Min. Circuit Ampacity) A 0.9 1.1 1.1 Fuse Capacity A 3.15 3.15 3.15 Refrigeration Control Device EXV EXV EXV Protection Device Fuse Fuse Fuse Model GMV-ND18G/NhA3C-T(U) GMV-ND24G/NhA3C-T(U) Cooling Btu/h 18000 24000 Capacity Heating Btu/h 20000 27000 Power supply V/Ph/Hz 208/230V ~ 60 208/230V ~ 60 CFM 530 530 Airflow volume(H) m3/h 900 900 Sound pressure level(H/M/L) dB(A) 44/42/38 44/42/38 Liquid In. 1/4 1/4 Connecting pipe Gas In. 1/2 1/2 Liquid mm Φ6.35 Φ6.35 Connecting pipe Gas mm Φ12.7 Φ12.7 In. Φ13/16 Φ13/16 Drain pipe mm Φ20 Φ20 Outline In. 43 15/16×9 3/4×13 1/8 43 15/16×9 3/4×13 1/8 Package In. 49 1/4×16 1/2×14 1/32 49 1/4×16 1/2×14 1/32 Dimension (WxDxH) Outline mm 1116×248×333 1116×248×333 Package mm 1251×419×356 1251×419×356 Net weight/Gross weight LBS 34/43 34/43 Net weight/Gross weight kg 15.5/19.5 15.5/19.5 MOP (Max Fuse Size) A 15 15 MCA (Min. Circuit Ampacity) A 1.1 1.1 Fuse Capacity A 3.15 3.15 Refrigeration Control Device EXV EXV Protection Device Fuse Fuse 21
GREE Multi Variable Air Conditioners Indoor Unit CONTROL 22
GREE Multi Variable Air Conditioners Indoor Unit 1 Operation Flowchart CHAPTER 2 CONTROL 23
GREE Multi Variable Air Conditioners Indoor Unit 2 Wired Controller 2.1 Control Panel 2.1.1 XE7C-23/H Wired Controller Table LCD display instruction No. Name Instruction 1 Status column Display the icon of function that is turned on 2 Fan speed It is for displaying the fan speed 3 Swing It is for displaying the current swing status 4 Button prompt Display the function of MENU/OK button at the current page and the settable cursor 5 Temperature display It shows the value of temperature (If the wired controller is controlling a fresh air indoor unit, it will display FAP). 6 Mode It shows the operating mode 7 Clock display It display the date and the time. When it’s locating the indoor unit, it displays the project No. of current indoor unit. NOTE: When wired controller is connected with different indoor units, some functions will be different. Table Instruction of Status Column Icon No. Symbols Name Instructions 1 Air * Air status(indoor unit optional function) 2 Remove card The card for access control is removed 3 Clean Remind to clean the filter 4 Child lock Child lock status 5 Error There are errors for the unit 6 Health * Health function (indoor unit optional function) 7 Defrosting Defrosting status of outdoor unit 8 Main Current wired controller connects the main indoor unit. 9 Power off memory Memory status (when power recovered, indoor unit will resume previous setting status) 10 Absence Absence is displayed when this function is turned on. 11 Quiet status Quiet status (including quiet and auto quiet modes) 12 Energy-saving Energy-saving status of indoor unit Appearance of wired controller LCD graphics of wired controller 24
GREE Multi Variable Air Conditioners Indoor Unit No. Symbols Name Instructions 13 Shield Shielding status 14 Slave wired controller Slave wired controller (address of wired controller is 02). 15 Sleep Sleep status 16 Time Timer status is displayed 17 X-fan X-fan is displayed when this function is set. 18 Group control One wired controller controls multiple indoor units. 19 Valid operation It’s displayed for valid operation 20 WiFi WiFi status(If the wired controller has no WiFi function, it displays only when the unit connected to “G-Cloud”). 21 Independent swing* Independent swing status 22 Auto clean * Auto clean status 23 Setback Setback function status 24 Warning Warning status 25 Aux. Heat* 26 Aux. Heat operating NOTE: When wired controller is connected with different indoor units, some functions will be different. Table function instruction of buttons No. Name Function 1 FAN Switch fan speeds: auto, low, medium-low, medium, Medium-high and high 2 (1) Set operation temperature for the indoor unit. (3) Set and check parameters. 7 3 On/off button for turn on or turn off the unit; back button for return to previous page. 9 (1) Turn pages, and switch and select the target; (3) Set and check parameters. 4 5 MODE Switch operating modes: Auto, Cool, Dry, Fan, Heat, Floor, 3D Heat, etc. 6 MENU/OK Select mode and confirm parameters. 8 SWING Set the swing status of central air conditioners. Aux. Heat is available Button graphics (2) Move cursor. (2) Move the cursor; 25
GREE Multi Variable Air Conditioners Indoor Unit 2.1.2 LE60-24/H1 Linkage Controller The linkage controller can detect strong or weak electric access control signals as well as passive dry contact signals (window switches, fire alarms, etc.), achieving linkage control of access, windows, fire alarms, etc., to turn off the indoor units and restoring the original on/off state. 2.1.2.1 Description of Ports Diagram of Ports HBS communication port (H1, H2): It is connected to the indoor unit of air conditioner through a 2- core communication wire. It is used for the indoor unit to supply power to linkage controller and communicate with linkage controller. Dry contact interface (I1 and O1, I2 and O2): Connect the dry contact signal to the I1, O1 (or I2, O2) ports to achieve linkage controller of window switches, fire alarms, etc., for unpowered signals to turn off the indoor units and restoring the original on/off state. Attention to the following items: (1) When any dry contact detects the following signal changes, linkage controller switches unit off. 1) When the DIP switch function corresponding to the dry contact is set to “Dry contact disconnected for switching unit off”, the dry contact signal is changed from connection to disconnection and lasts for 5 seconds. Exterior Sketch of Linkage Controller 26
GREE Multi Variable Air Conditioners Indoor Unit 2) When the DIP switch function corresponding to the dry contact is set to “Dry contact connected for switching unit off”, the dry contact signal is changed from disconnection to connection and lasts for 5 seconds. (2) After the unit is switched off in above way, it can be turned on by other devices (such as a wired controller). (3) After the signal recovers, the original startup or shutdown state of the unit will restore. However, if manual operation for unit startup is done before the signal recovers, the original startup or shutdown state of the unit will not restore after the signal recovers. Gate control interface (N and L, VCC and GND): The linkage controller has gate control interface, which can be connected with gate control system to achieve access control card removal to turn off the indoor units or access control card insertion to restore the original on/off state. If you want to control indoor unit’s functions through gate control, make sure the 4th lever of the DIP switch is turned to the “1” side, then connect the gate-control terminal to the N and L port or the VCC and GND port. Attention to the following items: 1) The N and L port is the power supply interface of the 100-240V~50/60Hz gate control. 2) The VCC and GND port is the power supply interface of the DC 5-24V gate control. 3) Only one power input can be chosen between the 100-240V ~50/60Hz and the DC 5-24V. 2.1.2.2 LED Indicator The following table is a detailed description about the LED indicator: The LED indicator lights up The linkage controller works. The LED indicator blinks The communication between the indoor unit and the linkage controller has malfunction. The LED indicator lights off The power supply of linkage controller is cut off. 2.1.2.3 DIP Switch NOTE: If the setting is changed, it will take effect after the linkage controller is re-energized. (1) The 1st Lever of DIP Switch –Master/Slave HBS Device Setting The 1st lever of DIP switch is used for the setting of master/slave HBS device. The factory default setting is slave HBS device. In an HBS network, if the linkage controller is the only device that is connected to indoor units, it should be set as the master HBS device. Turn the 1st lever of DIP switch to 0. In an HBS network, if both the wired controller and linkage controller are connected to indoor units, the wired controller should be set as the master HBS device (i.e. master wired controller, please refer to the instruction manual of wired controller for the setting method). So the linkage controller should be set as the slave HBS device. Turn the 1st lever of DIP switch to 1. Diagram of DIP Switch 27
GREE Multi Variable Air Conditioners Indoor Unit Diagram of DIP Switch Setting for Master/Slave HBS Device: (2) The 2nd/3rd Lever of DIP Switch –Dry Contact 1/2 Signal Change Detection Setting The 2nd/3rd lever of DIP switch is used for the setting of dry contact 1/2 signal change detection respectively. The factory default setting is “dry contact 1/2 disconnected for switching unit off”. When dry contact 1(I1, O1) signal change detection shall be set to “Dry contact disconnected for switching unit off”, turn the 2nd lever of DIP switch to 1. When dry contact 1 signal change detection shall be set to “Dry contact connected for switching unit off”, turn the 2nd lever of DIP switch to 0. Similarly, the 3rd lever of DIP switch corresponds to dry contact 2(I2, O2) signal change detection. The setting method of dry contact 2 signal change detection is the same as that of dry contact 1 signal change detection. Diagram of DIP Switch Setting for dry contact 1/2 signal change detection: Dry contact 2 connected for switching unit off (3) The 4th Lever of DIP Switch –Gate Control System Setting The 4th lever of DIP switch is used for the setting of Gate Control System. Factory default provided with Gate-control function. If the gate-control system is involved, turn the 4th lever of DIP switch to 1. If the gate-control system is not involved, turn the 4th lever of DIP switch to 0. Diagram of DIP Switch Setting for Gate Control System: Gate-control system is not connected Slave HBS Master HBS Device Device Dry contact 1 Dry contact 1 connected for switching unit off disconnected for switching unit off Dry contact 2 disconnected for switching unit off Gate-control system is connected 28
GREE Multi Variable Air Conditioners Indoor Unit 2.2 Installation and Removal 2.2.1 Installation Dimensions Unit: mm(inch) Dimension of XE7C-23/H Unit:mm(inch) Dimension of LE60-24/H1 29
GREE Multi Variable Air Conditioners Indoor Unit 2.2.2 Installation Method (1) Wired Controller XE7C-23/H Installation Method: Installation diagram for wired controller XE7C-23/H The figure shows a simple installation course of wired controller, and the following points should be noted: ① Before installation, please cut off the power supply of indoor unit, it is not allowed to operate with power supply; ② Pull out the 2-core twisted pair inside the installation hole in the wall, and thread the wire through the hole in the back of soleplate of wired controller; ③ Stick the soleplate of wired controller on the wall, and use Self-tapping Screw ST3.9×25 MA or screw M4×25 to fix the soleplate with the installation hole of wall; ④ Connect the 2-core twisted pair to wiring terminal H1 and H2, and then tighten the screw; ⑤ Arrange the wires in the back of panel, and then buckle the panel of wired controller with the soleplate of wired controller. If caliber of the communication cord is too large, which causes difficulty in leading or sticking the cord according to above point 2 and point 4, strip some of the sheath of the communication cable to meet the installation requirement. (2) Linkage Controller LE60-24/H1 Installation Method: According to actual condition, install the linkage controller in an appropriate place indoors, and secure it with 2 screws. If necessary, push plastic expansion tubes into the wall before secure it with screws. Installation Means 30
GREE Multi Variable Air Conditioners Indoor Unit 2.2.3 Removal Method Wired Controller XE7C-23/H Disassembly diagram: Disassembly diagram of wired controller XE7C-23/H 2.2.4 Connection of Communication Cord There are 2 ways to connect wired controller with indoor units’ network. Each indoor unit has to be connected with a R32 safety system compatible wired controller. These wired controllers have implemented safety measures that will warn the user visually and audibly in case of a leak. One wired controller Two wired controllers control one indoor unit controls one indoor unit 31
GREE Multi Variable Air Conditioners Indoor Unit 3 Remote Controller 3.1 Remote Controller YAP1F Button name and function introduction No. Button name Function 1 ON/OFF Turn on or turn off the unit 2 TURBO Set turbo function 3 MODE Set operation mode 4 Set up&down swing status 5 I FEEL Set I FEEL function 6 TEMP Switch temperature displaying type on the unit’s display 7 Set health function and air function 8 LIGHT Set light function 9 X-FAN Set X-FAN function 10 SLEEP Set sleep function 11 CLOCK Set clock of the system 12 T-OFF Set timer off function 13 T-ON Set timer on function 14 Set left&right swing status 15 FAN Set fan speed 16 / Set temperature and time 1 2 3 16 15 4 14 13 12 5 6 7 11 8 10 9 32
GREE Multi Variable Air Conditioners Indoor Unit 4 Introduction to Unit Functions Function Application of IDUs Indoor unit functions cover user operation functions and engineering application functions. For user operation functions, refer to operating instructions of the IDU, wired controller, and remote controller. Engineering application functions include: SN Function Name 1 Main IDU query and settings 2 Indoor unit project number query and settings 3 Parameter View 4 User parameter settings 6 Project parameter settings Engineering application functions can be operated through the IDU wired controller XE7C-23/H. 4.1 Engineering Application Functions Operated through the XE7C-23/H Wired Controller 4.1.1 Main IDU Settings The main IDU can be set through the wired controller or remote controller. The methods for setting the main IDU through the wired controller are as follows: Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. Press “ ” or “ ” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button to go into user parameter setting page. After that, press “ ” or “ ” button to select the item “Main IDU”. When selecting the parameter, press “ ” or “ ” button to select the setting value “Yes”. Press “MENU/OK” button to save corresponding setting item. If the setting can’t be confirmed, switching the item can restore the previous setting value. If the main IDU setting is successful, " " icon will display on the homepage of wired controller . 4.1.2 Main IDU Display For IDUs connected with wired controllers, " " on the wired controller connected with the main IDU will be on. For IDUs embedded or connected with LED panels, the operation LED on the LED panel of the main IDU will blink three times. After the main IDU is successfully set, stick the “ convenience of user operation and engineering maintenance. This flag is placed in the package bag of the ODU. 4.1.3 Project Number Query and Settings (1) IDU Project Number View and Locating Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “View”, and then press “MENU/OK” button to enter into the view MASTER ” flag to the wired controller or unit panel for 33
GREE Multi Variable Air Conditioners Indoor Unit page. Press “ ” or “ ” button to select “IDU Project No. View and Locating” at the view page. Then press “MENU/OK” button to enter into “IDU Project No. View and Locating” page to see IDU project number. Synchronously, the double-eight digital LED of the IDU embedded displays its own project number. If the current wired controller works in one-to-many mode, you can press the “ ” or “ ” button to switch indoor unit number, view each indoor unit corresponding project number. It is normal if the buzzer of the IDU operated by the wired controller rings. The purpose of ringing the buzzer is to facilitate engineering commissioning personnel to locate the IDU, especially for the IDU without any LED panel because it cannot display its project number. (2) View All IDU Project Number Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “View”, and then press “MENU/OK” button to enter into the view page. Press “ ” or “ ” button to select “View All IDU Project No.” at the view page. Then press “ ” or “ ” button to select turn on or turn off this function. And press “MENU/OK” button to confirm it. When turn on the “View All IDU Project No.”, the status column on the homepage of each wired controller in the entire network displays the project number of the corresponding IDU. Synchronously, the double-eight digital LED of each IDU embedded or connected with an LED panel displays its own project number. Method for quitting query: Press the “ ” button on any wired controller in the network. (3) Project number settings of IDU Under on or off status, press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. Press “ ” or “ ” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button for 5s to go into parameter setting page. Press “ ” or “ ” button to select “Project Parameter” at the parameter setting page, and then press “MENU/OK” button to enter into the project parameter setting page. After that, press “ ” or “ ” button to select the item “IDU Project No. Setting”. If the current wired controller works in one-to-many mode, you can press the “ ” or “ ” button to switch indoor unit number. When selecting the parameter, press “MENU/OK” button to enter into the IDU project No. setting page. Then press “ ” or “ ” or “ ” or “ ” button to switch the project number. Hold it can switch it quickly. Press “MENU/OK” button to save this setting. 4.1.4 Parameter View Parameters can be queried in power-on or power-off status. Press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “View”, and then press “MENU/OK” button to enter into the view page. Press “ ” or “ ” button to select “Parameter View” at the view page. Then press “MENU/OK” button to enter into parameter view page. 34
GREE Multi Variable Air Conditioners Indoor Unit Press “ ” or “ ” button to switch the items. When viewing the indoor unit, if the current wired controller works in one-to-many mode, press “ ” or “ ” button to switch indoor units. Corresponding indoor unit’s parameters will be displayed on the page. When viewing the outdoor unit, if there are multiple outdoor unit, press “ ” or “ ” button to switch outdoor units. Corresponding outdoor unit’s parameters will be displayed on the page. The parameter view list is as follows: Parameter Name Range Parameter Name Range Wired Controller’s Address 1,2 No. of IDUs Wired to Main IDU’s Project No. 0,1~255 Time Left to Clean Filter 0~416 days Online IDUs of CAN1 1~100 CAN2 address 1~255 Max Distribution Ratio IDU Error History 5 historical errors Prior Operation Yes, No Indoor Temp -30°C -139°C Relative Humidity 0%~100% Inlet Temp 1 -30°C -139°C Outlet Temp 1 -30°C -139°C Inlet Temp 2* -30°C -139°C Outlet Temp 2* -30°C -139°C IDU Capacity IDU capacity and capacity Fresh Air IDU Output Temp* -30°C -139°C Indoor Unit Fan Static R32 Refrigerant Concentration 0%~100% ODU Static Pressure 0~4 ODU Error History 5 historical errors The following parameters can only be viewed from the master wired controller, they cannot be viewed from the slave wired controller Parameter Name Range Parameter Name Range Unit Code 0~9, A~Z, a~z, - Board Code 0~9, A~Z, a~z,- Outdoor Temp -30~139°C Comp1 Operation Freq. 0~200Hz Comp 2 Operation Freq. 0~200Hz ODU Fan Operation Freq. 0~100Hz High Pressure Sat. Temp -40~70°C Low Pressure Sat. Temp -69~38°C Comp1 Discharge Temp -30~150°C Comp 2 Discharge Temp. -30~150°C Comp 3 Discharge Temp -30~150°C Comp 4 Discharge Temp. -30~150°C Comp 5 Discharge Temp -30~150°C Comp 6 Discharge Temp. -30~150°C Comp 3 Operation Freq. 0~200Hz ODU Heating EXV1 0~48 ODU Heating EXV2 0~48 Subcooler EXV 0~48 Defrost Temp -30~139°C Subcooler Liquid Temp -30~139°C Separator Outlet Temp -30~139°C Oil Return Temp -30~139°C Condenser Inlet Temp -30~139°C Condenser Outlet Temp -30~139°C ① Under parameter viewing status, the signal from remote controller is invalid. ② When the parameter is invalid, it will display “--”. 4.1.5 User Parameter Settings User parameters can be set in power-on or power-off status. Press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. Press “ ” or “ ” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button to go into user parameter setting page. After that, press “ ” or “ ” button to switch the items. Hold it can switch it quickly. When selecting the parameter, press “ ” or “ ” to switch the setting value. Press “MENU/OK” button to save corresponding setting items. If the setting can’t be confirmed, switching the item can restore the Parameter View List Controller 1~16 110% 135% 150% Cool & Heat Modes Cool Only, Heat Only, Cool & Heat, Fan after adjustment IDU EXV Status 0~20 Pressure 0~999 35
GREE Multi Variable Air Conditioners Indoor Unit previous setting value. The user parameter setting list is as follows: User Parameter Setting List Item Settable range Default Remarks When it is set as no, this wired controller is slave wired controller. Status column of the homepage displays the icon of slave wired controller “ ” . The wired controller can only activate the main wired controller. It does not have the function of setting parameters for other units. Main Wired Controller Yes, No Yes Once it is activated, the current IDU is set to be the main IDU. When the setting is Yes, if the system mode priority is the master-slave mode, the status column in homepage will display the icon of main IDU “ ”; when the setting is off, master and slave status of the current IDU will not be changed. Main IDU Yes, No No Use Remote Yes, No Yes When it is set as no, the wired controller cannot receive the remote control signal. It can only be operated with buttons. Prior Operation Yes, No No When the power supply is insufficient, it is allowed to turn on the designated IDU as preferential operation; other IDUs should be forced to be off. High Ceiling Installation* Yes, No No Only applicable to cassette type IDU After setting the linkage function, the fresh air IDU will automatically turn on or turn off along with the on and off of general IDU. Meanwhile, users can manually turn on or turn off the unit. It only applicable to fresh air IDU. Link with Fresh Air Yes, No No IDU* After it is successfully set, adjust the revolving speed to ensure the air volume is close to or the same as the previous air volume. It is only applicable to the unit with PM2.5 filter. PM2.5 Filter* Yes, No No Yes: Temp and humidity Refer to Temp and indoor unit for correction RH Correction control No: Ambient temperature It can be set only when it’s supported by the indoor unit. the defaulted Control value control Yes: Humidity Dry Mode If select “yes”, set humidity is displayed under dry mode. Otherwise, set temperature is displayed. It can only be set when it’s supported by the indoor unit. control Humidity No No: Temperature Control control Clear Filter Cleaning Yes, No No — Time Indoor Fan Static Pressure 1~9 5 — 0: This function is unavailable No. of IDUs Wired to Controller 1 Set corresponding value according to the connected quantity of IDU. 1-16: quantity of IDU Angle 1 Angle 2 Angle 3 Angle of Air- return Board* Angle 2 Only applicable to the model with air-return plate. 25°C (77°F) Cooling temperature of auto mode – heating temperature of auto mode≥1°C. Heating temp of Auto Mode Cooling temp of Auto Mode 17°C~30°C (63°F~86°F) 16°C ~29°C (61°F~84°F) 20°C (68°F) Resume When it is set as No, it will keep the status after inserting the gate control card. If it is at OFF status when pulling out the card, when inserting the card, it is still at OFF status. After Inserting Yes, No Yes Card 36
GREE Multi Variable Air Conditioners Indoor Unit Item Settable range Default Remarks Cold air prevention time is the max waiting time from the time turning on the heating mode to the time blowing out the hot wind. The actual waiting time is related to the outdoor ambient temperature. If there is cold air after turning on the heating mode in the actual operation, please consult the professional person to adjust this parameter. Time for IDU 180s, 300s, 420s, 600s 180s Cold Air Prevention* Set Temp of 10°C ~30°C (50°F~86°F) 16°C (61°F) Note: It’s only applicable for the units whose dry mode is with humidity control function. RH Control Mode 01: Normal 02: Quick 03: Deep 1 Note: Only applicable to the unit with auto clean function. If “0” is displayed, this function is not available for this unit. Auto Clean Mode Cooling Temp of Fresh Air 16°C ~30°C (61°F~86°F) 18°C (64°F) Only applicable to fresh air IDU. IDU* Heating Temp of Fresh Air 16°C ~30°C (61°F~86°F) 22°C (71°F) Only applicable to fresh air IDU. IDU* Setback Yes, No No — Upper Temp 26°C (79°F) When temperature unit is °C, temperature upper limit – temperature lower limit ≥ 4°C; When temperature unit is °F, temperature upper limit – temperature lower limit ≥7°F. Lower Temp 20~30°C (68~86°F) Limit of Setback 16~26°C (61~79°F) 20°C (68°F) Limit of Setback 0: Normal Auto Wind 1: Heating Wind Sensing Auto Fan 0 — Setting Wind When Aux heating is available, the home status bar displays the “ ” icon; when Aux heating is running, the home status bar displays the “ ” icon. Note:This feature is only applicable to high static pressure air handler indoor units. Enable Aux. Heat* Yes, No Yes Setpoint- When the temperature difference between the ambient temperature and the set temperature exceeds the opening temperature difference, AUX heating is allowed to start. Note:This feature is only applicable to high static pressure air handler indoor units. Space Temperature 1~10 3 Differential for Aux. Heat* After the heat pump operation meets the start time, AUX heating is allowed to turn on. Note:This feature is only applicable to high static pressure air handler indoor units. Aux. Heat ON Timer * 0min~60mins 2mins Satisfy Room Yes, No No Note:This feature is only applicable to high static pressure air handler indoor units. Temperature with AUX* In parameter setting status, signals of the remote controller are invalid. 4.1.6 Project Parameter Settings Engineering parameters can be set in power-on or power-off status. Press “MENU/OK” button on the homepage to enter into the menu page. Press “ ” or “ ” button to select “Set”, and then press “MENU/OK” button to enter into the set page. Press “ ” or “ ” button to select “Parameter Setting” at the set page. Then press “MENU/OK” button 37
GREE Multi Variable Air Conditioners Indoor Unit for 5s to go into parameter setting page. Press “ ” or “ ” button to select “Project Parameter” at the parameter setting page, and then press “MENU/OK” button to enter into the project parameter setting page. After that, press “ ” or “ ” button to switch the items. Hold it can switch it quickly. When selecting the parameter, press “ ” or “ ” to switch the setting value. Press “MENU/OK” button to save corresponding setting items. If the setting can’t be confirmed, switching the item can restore the previous setting value. The project parameter setting list is as follows: Project Parameter Setting List Item Settable range Default Remarks No: standby after power-down recovery Yes: restoring the original status after power-down recovery Memory Yes、No Yes System Energy- Saving Yes、No No — Constant Air Volume Debugging* Yes、No No — When the number of online indoor units is greater than 1, press “ ” or “ ” to switch indoor units, press the “MENU/OK” key to enter the project number setting of the selected indoor unit: press “ ” or “ ” to increase/decrease the project number by the unit digit. Press “ ” or “ ” to increase/decrease the project number by the tenth digit. IDU Project No. Setting 1-255 — Off、10s、 20s、30s、 40s、50s、 60s Prevent Heat Accumulation Off It indicates the number of seconds for enabling the low-level fan every 15min. ODU Quiet Mode Off、1~12 — Top discharge outdoor unit defaults to Off, side discharge outdoor unit defaults to 12 Capacity Upper Limit 100%、90%、 80% 100% — -40、-30、- 20、-10、0、 10、20、30、 40 IDU Capacity 0 — Adjustment Press “ ” or “ ” to adjust the minimum opening degree. Press and hold “ ” or “ ” for 5 seconds, the minimum opening degree will increase or decrease by single digit. Press and hold for 5 to 10 seconds, the minimum opening degree will increase or decrease by ten digits. After the default minimum opening degree for heating breakdown is manually modified, the opening degree remains unchanged upon heating breakdown. Min Pulse of EXV Auto、1~500 Auto 10mins、 15mins、 20mins 15mins — Max Defrosting Time Standard、 Rapid Defrost Mode* Rapid1、 Standard — Rapid2 Force Defrost Yes、No No — 38
GREE Multi Variable Air Conditioners Indoor Unit Item Settable range Default Remarks 40mins、 50mins、 60mins 50mins — Defrosting Cycle K1 1:Return Air; 2:Wired Controller; 3:Cool:Return Air, Heat:Wired Controller; 4:Cool:Wired Controller, Heat:Return Air Amb Temp Sensor Location 1、2、3、4 3 Temperature sensor of Amb Temp Sensor unit: 0°C; temperature Cool Revise -15℃~+15℃ — sensor of wired controller: 0°C Temperature sensor of unit: -2°C; temperature Amb Temp Sensor Heat Revise -15℃~+15℃ — sensor of wired AHRI IDU Fan Speed* 100~1800 — — Heating to Temp Fan Status Stop、Breeze Breeze — Display Ambient Temp on Homepage Yes、No No — Function Setting of Lifting Panel* On、Off Off Only applicable for 360°air discharge cassette indoor unit. Cooling to Temp Fan Setting* Yes、No No This feature is only applicable to the indoor units that have this function set. IDU High and Low None、High、 Low None — Level Status* Control Method of Constant Temp Mode* Mode1、 Mode2 Mode1 — Fresh Air IDU Static Pressure* 1~13 8 Only applicable to DC Fresh Air Indoor Unit. Lowest Air Outlet Temperature Can Be 8℃~16℃ 16℃ This setting can only be done when the indoor unit is a fresh air processing indoor unit. Set* Delayed Startup of 0s、20s、 40s、60s、 80s 0s This feature is only applicable to the indoor units that have this function set. Indoor Fan Under Cooling Mode* Default 0, indoor unit reports refrigerant leak fault, automatically changes to 1 after meeting the unit requirements, automatically changes to 0 after Locked Status of Refrigerant Leakage 0、1 0 indoor unit refrigerant leak fault recovery. Manually set from 1 to 0, clear the indoor unit’s refrigerant leak fault. Item with “*” are reserved parameter. In parameter setting status, signals of the remote controller are invalid. 4.1.7 Error Display When there is error during operation, the temperature display zone on the wired controller will show the error code. If several errors happen at the same time, error codes will show on the display repeatedly. If error occurs, please turn off the unit and ask for professionals to repair it. The following figure shows the display of outdoor unit high pressure protection when unit is on. 39
GREE Multi Variable Air Conditioners Indoor Unit When the wired controller is connected with a Fresh Air Indoor Unit, fresh air indoor unit code “FAP” will be displayed as shown below. Setting temperature won’t be displayed and can’t be adjusted via “ ” or “ ” button. The air outlet temperature in cooling or heating can only be set in the parameter setting status. Display of Outdoor Unit High Pressure Protection 40
GREE Multi Variable Air Conditioners Indoor Unit 4.2 Engineering Application Functions Operated through the YAP1F Remote Controller 4.2.1 The method for setting the master IDU through the YAP1F remote controller is as follows No. Button name Function 1 ON/OFF Turn on or turn off the unit 2 TURBO Set turbo function 3 MODE Set operation mode 4 Set up&down swing status 5 I FEEL Set I FEEL function 6 TEMP Switch temperature displaying type on the unit’s display 7 Set health function and air function 8 LIGHT Set light function 9 X-FAN Set X-FAN function 10 SLEEP Set sleep function 11 CLOCK Set clock of the system 12 T-OFF Set timer off function 13 T-ON Set timer on function 14 Set left&right swing status 15 FAN Set fan speed 16 / Set temperature and time For details about the above figures, refer to the instructions 66174100016. Perform settings by pressing “▲” and “▼” in air supply mode: (1) Set the temperature to 30°C. 41
GREE Multi Variable Air Conditioners Indoor Unit (2) Press “▼” and then “▲” in five seconds. Repeat this operation for three times. After successful settings, “UC” is displayed on the receiving indicator panel of the remote controller for five seconds and “ ” is displayed on the wired controller. 4.2.2 IDU Project Number Query by Remote Controller YAP1F (1) Query method for project number of single IDU: Enter query: Under fan mode, set temperature in 16°C, press “Light” button for 5 times continuously within 5 seconds and then the IDU light board will display its project number. Exit query: 1) After entering query status, press “Light” button for 5 times continuously within 5 seconds to exit query status. 2) After 30min, it will exit query status automatically and display normal status. (2) Query method for project numbers of all IDUs in a single system: Enter query: Under fan mode, set temperature in 30°C, press “Light” button for 5 times continuously within 5 seconds and then the light boards of all indoor units will display their project numbers respectively. Exit query: 1) After entering query status, press “Light” button for 5 times continuously within 5 seconds to exit query status. 2) After 30min, it will exit query status automatically and display normal status. 4.2.3 Common Remote controller recovery refrigerant leakage fault In the startup and Fan modes, the Remote controller shall operate the light key for 5 consecutive times within 5 seconds at the interface with the set temperature of 20 ℃(68℉) to clear the refrigerant leakage fault of the internal unit. 42
GREE Multi Variable Air Conditioners Indoor Unit INSTALLATION 43
GREE Multi Variable Air Conditioners Indoor Unit 1 Engineering Installation Preparation and Notice 1.1 Installation Notice All phases of this installation must conform to NATIONAL, STATE AND LOCAL CODES. If it is required for additional information, please contact your local distributor. Personnel and property safety are highly concerned during the entire installation process. Installation implementation must abide by relevant national safety regulations to ensure personnel and property safety. All personnel involved in the installation must attend safety education courses and pass corresponding safety examinations before installation. Only qualified personnel can attend the installation. Relevant personnel must be held responsible for any violation of the regulation. 1.2 Installation Key Points and Importance VRF air conditioning systems use refrigerant, instead of other agent, to directly evaporate to carry out the system heat. High level of pipe cleanness and dryness is required in the system. Since various pipes need to be prepared and laid out onsite, carelessness or maloperation during installation may leave impurities, water, or dust inside refrigerant pipes. If the design fails to meet the requirement, various problems may occur in the system or even lead to system breakdown. Problems that usually occur during installation are as follows: No. Installation Problem Possible Consequence 1 Dust or impurities enter into the refrigeration system. Nitrogen is not filled into the refrigerant pipe or insufficient Nitrogen is filled before welding. 2 3 The vacuum degree in the refrigerant pipe is insufficient. 4 Water enters into the refrigeration system. The refrigerant pipe specifications do not meet the configuration requirements. 5 6 Refrigerant pipe is blocked. 7 Refrigerant pipe exceeds the limit. 8 Incorrect amount of refrigerant is filled. 9 The refrigerant pipe leaks. CHAPTER 3 INSTALLATION Pipes are more likely to be blocked; air conditioning performance is reduced; compressor wear is increased or even hinder the normal operation of the system and burn the compressor. Pipes are more likely to be blocked; air conditioning performance is reduced; compressor wear is increased or even hinder the normal operation of the system and burn the compressor. The refrigeration performance is reduced. The system fails to keep normal operation due to frequent protection measures. When the problem getting serious, compressor and other major components can be damaged. Copper plating may appear on the compressor and reduce the compressor efficiency with abnormal noise generated; failures may occur in the system due to ice plug. Smaller configuration specifications can increase the system pipe resistance and affect the cooling performance; larger configuration specifications are waste of materials and can also reduce the cooling performance. The cooling performance is reduced; in certain cases, it may cause long-term compressor operating under overheat conditions; the lubricating effect can be affected and the compressor may be burnt if impurities were mixed with the lubricating oil. The loss in pipe is considerable and the unit energy efficiency decreases, which are harmful for long-term running of the system. The system cannot correctly control the flow allocation; the compressor may be operating under over-heating environment or running when the refrigerant flows back to the compressor. Insufficient refrigerant circulating in the system decreases the cooling performance of the air conditioner. Long-term operation under such circumstance may cause an overheating compressor or even damage the compressor. 44
GREE Multi Variable Air Conditioners Indoor Unit No. Installation Problem Possible Consequence 10 Water drainage from the condensate water pipe is not smooth. The ratio of slop for condensate water pipe is insufficient or the condensate water pipe is incorrectly connected. 11 12 The air channel is improperly fixed. The air channel will deform; vibration and noise occur during unit operating. 13 The guide vane of air channel is not reasonably manufactured. The refrigerant pipe or condensate water pipe does not meet the insulation requirement. 14 15 The installation space for IDU is insufficient. The IDU or the location of the air outlet or return air inlet is not designed reasonably. 16 17 The ODU is improperly installed. 18 Power cables are incorrectly provided. Unit components may be damaged and potential safety hazard may occur. Control communication cables are incorrectly provided or improperly connected. 19 20 Control communication cables are not properly protected. Understand the special requirement (if any) for unit installation before implementation to ensure installation quality. Relevant installers must have corresponding engineering construction qualifications. Special type operators involved in the engineering implementation, such as welders, electricians, and refrigeration mechanics must have relevant operating licenses and are accredited with vocational qualification certification. 2 Installation Materials Selection The materials, equipment and instruments used during air conditioning engineering construction must have certifications and test reports. Products with fireproof requirements must be provided with fireproof inspection certificates and must meet national and relevant compulsory standards. If environmentally-friendly materials are to be used as required by customers, all such materials must meet national environmental protection requirement and be provided with relevant certificates. (1) Only auxiliary devices approved by the appliance manufacturer or declared suitable with the refrigerant shall be installed in connecting ductwork; (2) Do NOT install operating ignition sources (example: open flames, an operating gas appliance or Residual water in IDUs can affect the normal operation of the system. The possible water leakage can damage the IDU's decoration. Reverse slop or inconsistent connection of condensate water pipe can hinder the smooth drainage and cause leakage of the IDU. Uneven air quantity allocation reduces the overall performance of the air conditioner. Water can easily condensate and drip to damage the indoor decoration, or even trigger the protection mode of system due to overheating operation. Since there is a lack of space for maintenance and checking, indoor decoration might need to be damaged during such operation. The air outlet or return air inlet may be short-circuited, thus affecting the air conditioning performance. The ODU is difficult to be maintained; unit exhaust is not smooth, which reduces the heat exchanging performance or even prevent the system from normal operation; in addition, the cold and hot air for heat exchange and the noise may annoy people in surrounding areas. The normal communication in the system fails or the control over IDUs and ODUs turn in a mess. The communication cables are short-circuited or disconnected, and the unit cannot be started up due to communication failure. 45
GREE Multi Variable Air Conditioners Indoor Unit an operating electric heater) in the duct work. (3) Air inlet AND outlet are connected directly to the same room by ducting. Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet. (4) No auxiliary devices, which may be a potential ignition source, are installed in the duct work (example: hot surfaces with a temperature exceeding 700°C and electric switching device); 2.1 Refrigerant Piping (1) Material requirement: Dephosphorization drawing copper pipe for air conditioners. (2) Appearance requirement: The inner and outer surface of pipe should be smooth without pinhole, crack, peeling, blister, inclusion, copper powder, carbon deposition, rust, dirt or severe oxide film, and without obvious scratch, pit, spot and other defects. (3) Test report: Certifications and quality test reports must be provided. (4) The tensile strength must be at least 240 kgf/mm². (5) After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed tightly by using pipe caps, plugs or adhesive tapes. 2.2 Condensate Water Pipe (1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R pipe, PP-C pipe, and HDG steel pipe; (2) All relevant certificates and quality test reports are provided. (3) Requirements for specifications and wall thickness. Water supplying UPVC pipe: Φ32mm(1-1/4inch)×2mm(1/16inch), Φ40mm(1-3/4inch)×2mm(1/16inch), Φ50mm(1-15/16inch)×2.5mm(1/8inch). HDG steel pipe: Φ25mm(1inch)×3.25mm(1/8inch), Φ32mm(1-1/4inch)×3.25mm(1/8inch). Φ40mm(1-3/4inch)×3.5mm(1/8inch), Φ50mm(1-15/16inch)×3.5mm(1/8inch). 2.3 Insulation Material (1) Rubber foam insulation material. (2) Flame retardancy level: B1 or higher. (3) Refractoriness: at least 120°C (248°F). (4) The insulation thickness of condensate water pipe: at least 10mm (3/8inch). (5) When the diameter of copper pipe is equal to or greater than Φ15.9mm(5/8inch), the thickness of insulation material should be at least 20mm(3/4inch); when the diameter of copper pipe is less than 15.9mm(5/8inch), the thickness of insulation material should be at least 15 mm(5/8inch). 46
GREE Multi Variable Air Conditioners Indoor Unit 2.4 Communication Cable and Control Cable For air conditioning units installed in places with strong electromagnetic interference, shielded wire must be used as the communication cables of the IDU and wired controller, and shielded twisted pairs must be used as the communication cables between IDUs and between the IDU and ODU. Communication cable selection for ODU and IDUs Total Length L (m) of Communication Cable between Indoor Unit and Material Type Indoor (Outdoor) Unit Light/Ordinary polyvinyl chloride L≤1000m(L≤3280-5/6feet) ≥2×0.75 (2×AWG 18) sheathed cord. (60227 IEC 52 /60227 IEC 53) Communication cable selection for IDU and wired controller Total length of communication line between indoor unit and Material type wired controller Light/Ordinary polyvinyl chloride sheathed cord. L≤100m(L≤328feet) (60227 IEC 52 /60227 IEC 53) 2.5 Power Cable Only copper conductors can be used as power cables. The copper conductors must meet relevant national standard and satisfy the carrying capacity of unit. 2.6 Hanger Rod and Support (1) Hanger rod: M8 or M10. (2) U-steel: 14# or above. (3) Angle steel: 30mm (1-1/6inch)×30mm (1-1/6inch)×3mm (1/8inch) or above. Round steel: Φ10mm (4/10inch) or above. Wire size (mm2/AWG) Material Standard Remarks (1) If the wire diameter is enlarged to 2×1 mm2 (2×AWG16), the total communication line length can reach 1500 m (4921-1/4feet.). The average length of communication line between units is 12.5 m. (2) The cord shall be Circular cord (the IEC 60227- 5 cores shall be twisted together). (3) If unit is installed in places with intense magnetic field or strong interference, it is necessary to use shielded wire. Wire size(mm2/A Material Standard Remarks WG) (1) Total length of communication line can't exceed 100m(328feet.). The average length of the communication line between indoor unit and wired controller is 15m. (2) The cord shall be Circular cord (the 2×0.75 ~2×1.25 (2×AWG18 ~2×AWG16) IEC 60227-5 cores shall be twisted together). (3) If unit is installed in places with intense magnetic field or strong interference, it is necessary to use shielded wire. 47
GREE Multi Variable Air Conditioners Indoor Unit 3 Installation of Indoor Unit 3.1Installation of High Static Pressure Duct Type Indoor Unit 3.1.1 Outline and Installation Dimension The following table lists the detailed dimensions. Model A B C D E F G GMV-ND07PHS/NhD-T(U) GMV-ND09PHS/NhD-T(U) GMV-ND12PHS/NhD-T(U) GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U) GMV-ND24PHS/NhD-T(U) 1040 (40- 15/16) 500 (19- 11/16) 1130 (44- 1/2) 300 (11- 13/16) 754 (29- 11/16) 1000 (39-3/8) GMV-ND30PHS/NhD-T(U) GMV-ND36PHS/NhD-T(U) GMV-ND42PHS/NhD-T(U) GMV-ND48PHS/NhD-T(U) GMV-ND54PHS/NhD-T(U) 1440 (56- 11/16) 500 (19- 11/16) 1540 (62- 5/8) 300 (11- 13/16) 754 (29- 11/16) 1400 (55-1/8) 48 Unit: mm(inch) 700 (27- 9/16) 700 (27- 9/16)
GREE Multi Variable Air Conditioners Indoor Unit 3.1.2 Installation Space 3.1.3 Installation Notice The unit shall be installed by the professional personnel according to this installation instruction to ensure proper use. Please contact the local Gree appointed service center before installation. Any malfunction caused by the unit that is not installed by the Gree appointed service center would probably not be dealt with on time because of the inconvenience of the business contact. It should be guided under the professional personnel when the air conditioner unit is moved to other place. Installation of the unit must be in accordance with National Electric Codes and local regulations. Improper installation will affect unit’s performance, so do not install the unit by yourself. Please contact local dealer to arrange professional technicians for the installation. Do not connect power until all installation work is finished. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. Air duct or grille fixed with screws must be installed at the air inlet or the air outlet of duct type unit. After installation, please make sure that human's hands are unable to touch inner parts of the unit. Installation and maintenance of the unit must be carried out by professionals. Unit: mm(inch) 49
GREE Multi Variable Air Conditioners Indoor Unit 3.2 Installation of Fresh Air Processing Indoor Unit 3.2.1 Outline and Installation Dimension The following table lists the detailed dimensions. Model A B C D E F G GMV-NDX42P/NhD-T(U) GMV-NDX48P/NhD-T(U) GMV-NDX54P/NhD-T(U) 1440 (56- 11/16) 500 (19- 11/16) 1540 (62- 5/8) 300 (11- 13/16) 754 (29- 11/16) 1400 (55- 1/8) 700 (27- 9/16) 3.2.2 Installation Space 3.2.3 Installation Notice (1) Installation of the unit must be in accordance with National Electric Codes and local safety regulations. (2) Improper installation will affect unit’s performance, so do not install the unit by yourself. Please 50 Unit: mm(inch) Unit: mm(inch)
GREE Multi Variable Air Conditioners Indoor Unit contact local dealer to arrange professional technicians for the installation. (3) Do not connect power until all installation work is finished. (4) Air duct or grille fixed with screws must be installed at the air inlet or the air outlet of duct type unit. After installation, please make sure that human's hands are unable to touch inner parts of the unit. Installation and maintenance of the unit must be carried out by professionals. 3.3 Installation of Air Handler Type Indoor Unit 3.3.1 Outline and Installation Dimension The following table lists the detailed dimensions. Unit: mm(inch) Model A B C D E GMV-ND60A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND48A/NhB-T(U) 630 (24-13/16) 540 (21-1/4) 1320 (51-15/16) 295 (11-5/8) 508 (20) 508 (20) GMV-ND30A/NhB-T(U) GMV-ND24A/NhB-T(U) GMV-ND18A/NhB-T(U) GMV-ND12A/NhB-T(U) 540 (21-1/4) 540 (21-1/4) 1224 (48-1/4) 295 (11-5/8) GMV-ND42A/NhB-T(U) GMV-ND36A/NhB-T(U) 540 (21-1/4) 460 (18-1/8 ) 1105 (43-1/2) 295 (11-5/8) 508 (20) 3.3.2 Installation Notice When installing the air handler, take consideration to minimize the length of refrigerant tubing as much as possible. Do not install the air handler in a location either above or below the condenser that violates the instructions provided with the condenser. Service clearance is to take precedence. Allow a minimum of 24” in front of the unit for service clearance. When installing in an area directly over a finished ceiling (such as an attic), an emergency drain pan is required directly under the unit. See local and state codes for requirements. When installing this unit in an area that may become wet, elevate the unit with a sturdy, non-porous material. In installations that may lead to physical damage (i.e. a garage) it is advised to install a protective barrier to prevent such damage. This air handler is designed for a complete supply and return ductwork system. These duct type indoor units are used to supply conditioned air to one zone. Do not operate this product without all ductwork attached. Based upon the actual conditions, if air handler is installed as type (A), the air handler should be 51
GREE Multi Variable Air Conditioners Indoor Unit
concealed in a specific room or space and make sure the air handler is not accessible to the general
public.
Based upon the actual conditions, if air handler is installed as type (B), make sure that there is
enough space for care and maintenance and the height between the air handler and ground is above
2500mm. And the air handler is not accessible to the general public.
Type (A) Type (B)
3.3.3 Electric Heater
(1) The air handlers listed in this manual do not have factory installed electric heater. Electric heater
is available as an accessory. Please refer to installation instructions provided with heater kit for
the correct installation procedure.
(2) Refer to the “installing electric heater” section of this manual and the instructions provided with
the heater kit for the correct installation procedure.
(3) The electrical characteristics of the air handler, the electric heater kit, and the supply power
should be identical. This air handler does not have factory installed electric heater. Electric
heater is available as an accessory. If installing this option, the only heater kits that can be used
are the series as indicated below. It is forbidden to use the electric heater other than those
recommended.
(4) E-HEAT mode setting method: under off status, press “
” and “MENU/OK” button for 5s
to turn on or turn off E-heat mode. After that, the wired controller control pop-up box shows
"Enable Setting E-Heat Mode" or "Disable Setting E-Heat Mode" for 3s, and indoor unit can set
“Electric heating mode”. When E-HEAT mode has been set and indoor unit operates under
heating mode, if outdoor unit stops operation because of error, indoor unit will switch to operate
under electric heating mode.
(5) After the electric heater is shutdown, the fan of indoor unit will delay for a few minutes and then
shut down so that the indoor unit can blow the waste heat and relieve the heat accumulation in
the air duct.
(6) During installation and debugging, pay attention to verify the switch sequence of electric heater
and fan, ensure the fan must be turned on when electric heater operation and ensure the electric
heater is turned off before the fan to avoid unsafe.
52 GREE Multi Variable Air Conditioners Indoor Unit 3.3.3.1 Electric heater kits available Model Electric heater Description Manufacturer of electric GMV-ND12A/NhB-T(U) GMV-ND18A/NhB-T(U) GMV-ND24A/NhB-T(U) GMV-ND30A/NhB-T(U) LYQ-08-A,21-4227- 01 LYQ-08-C,21-4216- Circuit breaker, 5 kW、10 kW electric heater 03 LYQ-08-A,21-4227- 01 LYQ-08-C,21-4216- GMV-ND36A/NhB-T(U) GMV-ND42A/NhB-T(U) Circuit breaker, 5 kW、10 kW、15 kW 03 LYQ-08-D,21-4217- electric heater 01 LYQ-08-A,21-4227- 01 LYQ-08-C,21-4216- GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) Circuit breaker, 5 kW、10 kW、15 03 LYQ-08-D,21-4217- kW、20 kW electric heater 01 LYQ-08-E,21-4228- 01 3.3.3.2 Electric heater kits installation (1) Ensure that all power supply is disconnected prior to installing the heater kit. (2) A means of strain relief and conductor protection must be provided at the supply wire entrance into cabinet. (3) Use copper conductors only. (4) Installation must follow national electric code and other applicable codes. (5) If this appliance is installed in an enclosed area such as a garage or utility room with any carbon monoxide producing appliance, ensure the area is properly ventilated. 1) Refer to the Table for appropriate heater kit. 2) Check any physical damage, do not install damaged heater kit. 3) Remove the upper access panel from air handler. 4) Remove cover plate from air handler. 5) Slide the heater kit in to the slot and secure element plate with previously removed screws. 6) Before installing the electric heating, unplug the X1 terminal, and insert the plug-in terminals on the electric heating to the X1 and X2 terminals respectively. The power line of the unit is connected through an electrically heated circuit breaker. 7) Insert power leads into the circuit breaker lugs or stripped red and black wires (for heater kit without circuit breaker) and tighten. 8) Connect ground wire to ground lug; M6 screws are required for grounding screws when installing electric heating. 9) Knock off appropriate area of the plastic circuit breaker cover on the access panel of the air handler. Knock off the holes according to the actual installation number and positions of circuit breakers. If circuit breaker is not installed, do not knock off the holes; otherwise, electric shock may occur. 10) Replace access panel and check operation. 53 heater TUTCO Zhenjiang Dongfang
GREE Multi Variable Air Conditioners Indoor Unit 11) Connection of power cords and thermostat wires. 3.4 Installation of 360°Air Discharge Cassette Type Indoor Unit 3.4.1 Outline and Installation Dimension The following table lists the detailed dimensions. Model A B C D E GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) GMV-ND15T/NhD-T(U) GMV-ND18T/NhD-T(U) GMV-ND24T/NhD-T(U) GMV-ND30T/NhD-T(U) GMV-ND36T/NhD-T(U) GMV-ND42T/NhD-T(U) GMV-ND48T/NhD-T(U) 950(37-3/8) 890(35) 840(33-1/8) 680(26-3/4) 780(30-3/4) 54 Unit: mm(inch)
GREE Multi Variable Air Conditioners Indoor Unit 3.4.2 Installation Space Model H GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) GMV-ND15T/NhD-T(U) GMV-ND18T/NhD-T(U) GMV-ND24T/NhD-T(U) GMV-ND30T/NhD-T(U) GMV-ND36T/NhD-T(U) GMV-ND42T/NhD-T(U) GMV-ND48T/NhD-T(U) 3.4.3 Installation Notice The unit shall be installed in accordance with national standards or local regulations. Only qualified personnel can carry out installation work, please contact with local dealer before installation. Make sure all the installation work completed before energizing. The appliances are not accessible to general public. Unit: mm (inch) Unit: mm (inch) 275(10-3/4) 325(12-3/4) 55
GREE Multi Variable Air Conditioners Indoor Unit 3.5 Installation of 360°Air Discharge Compact Cassette Type Indoor Unit 3.5.1 Outline and Installation Dimension Unit: mm (inch) Model A B C D E F G GMV-ND05T/NhE-T(U) GMV-ND07T/NhE-T(U) GMV-ND09T/NhE-T(U) GMV-ND12T/NhE-T(U) GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U) 620 (24-3/8) 580 (22-13/16) 570 (22-7/16) 505 (19-7/8) 550 (22-5/8) 530 (20-7/8) 530 (20-7/8) 3.5.2 Installation Space Unit: mm (inch) 56
GREE Multi Variable Air Conditioners Indoor Unit Model H GMV-ND18T/NhE-T(U) GMV-ND15T/NhE-T(U) GMV-ND12T/NhE-T(U) GMV-ND09T/NhE-T(U) GMV-ND07T/NhE-T(U) GMV-ND05T/NhE-T(U) 3.5.3 Installation Notice The unit shall be installed by the professional personnel according to this installation instruction to ensure proper use. Please contact the local Gree appointed service center before installation. Any malfunction caused by the unit that is not installed by the Gree appointed service center would probably not be dealt with on time because of the inconvenience of the business contact. It should be guided under the professional personnel when the air conditioner unit is moved to other place. The unit shall be installed in accordance with national standards or local regulations. Only qualified personnel can carry out installation work, please contact with local dealer before installation. Make sure all the installation work completed before energizing. The appliances are not accessible to general public. 3.6 Installation of 1-way Cassette Type Indoor Unit 3.6.1 Outline and Installation Dimension Unit: mm (inch) 305(12) Unit: mm (inch) 57
GREE Multi Variable Air Conditioners Indoor Unit 3.6.2 Installation Space Model H GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) 3.6.3 Drainage Pipe Installation The installation height of raising pipe for drainage should be lower than B. The gradient from raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe is vertical with the unit, the raising height should be less than C. Model A B C GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) 100(3-15/16) 1100(43-5/16) 1050(41-5/16) 58 Unit: mm (inch) Unit: mm (inch) 207(8-1/8) Unit: mm (inch) Unit: mm (inch)
GREE Multi Variable Air Conditioners Indoor Unit
3.6.4 Installation Notice
The unit shall be installed by the professional personnel according to this installation instruction
to ensure proper use.
Please contact the local Gree appointed service center before installation. Any malfunction
caused by the unit that is not installed by the Gree appointed service center would probably not
be dealt with on time because of the inconvenience of the business contact.
It should be guided under the professional personnel when the air conditioner unit is moved to
other place.
The unit shall be installed in accordance with national standards or local regulations.
Only qualified personnel can carry out installation work, please contact with local dealer before
installation.
Make sure all the installation work completed before energizing.
3.7 Wall Mounted Type Indoor Unit
3.7.1 Outline and Installation Dimension
Below are dimensions of W, H, D for different models:
Item
Model
W
H
D
GMV-ND06G/NhA1C-T(U)
GMV-ND07G/NhA1C-T(U)
GMV-ND09G/NhA1C-T(U)
GMV-ND06G/NhA3C-T(U)
GMV-ND07G/NhA3C-T(U)
GMV-ND09G/NhA3C-T(U)
867(34-1/8)
276(10-7/8)
206(8-1/8)
GMV-ND12G/NhA1C-T(U)
GMV-ND14G/NhA1C-T(U)
GMV-ND12G/NhA3C-T(U)
GMV-ND14G/NhA3C-T(U)
978(38-1/2)
333(13-1/8)
248(9-3/4)
GMV-ND18G/NhA1C-T(U)
GMV-ND24G/NhA1C-T(U)
GMV-ND18G/NhA3C-T(U)
GMV-ND24G/NhA3C-T(U)
1116(43-15/16)
333(13-1/8)
248(9-3/4)
59
Unit: mm (inch)
Unit: mm(inch) GREE Multi Variable Air Conditioners Indoor Unit 3.7.2 Installation Space 3.7.3 Installation Notice The unit shall be installed by the professional personnel according to this installation instruction to ensure proper use. Please contact the local Gree appointed service center before installation. Any malfunction caused by the unit that is not installed by the Gree appointed service center would probably not be dealt with on time because of the inconvenience of the business contact. It should be guided under the professional personnel when the air conditioner unit is moved to other place. Maintenance/service to be done by specialized personnel, mandated by the manufacturer or authorized representative. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms or for commercial use by lay persons. This unit is a partial unit air conditioner, complying with partial unit requirements of this International standard and must only be connected to other units that have been confirmed as complying to corresponding partial unit requirements of this international standard. This unit shall only be connected to an appliance suitable for the same refrigerant. Make sure all the installation work completed before energizing. Unit: mm (inch) 60
GREE Multi Variable Air Conditioners Indoor Unit 4 Installation of Connection Pipe ① Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so is the height difference between indoor and outdoor units. Keep the number of bends as little as possible. Radius of curvature should be as large as possible. ② Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for welding process. Rosin joint or pin hole is not allowed. ③ When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm (8inch). Note that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch the pipe for more than 3 times at the same position. 4.1 Flaring Process (1) Mechanical connectors used indoors shall comply with ISO 14903. When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be refabricated. (2) Pipework shall be protected from physical damage. (3) Installation of pipework shall be kept to a minimum space required. (4) Do NOT re-use joints and copper gaskets which have been used already. (5) Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes. (6) Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrigerant, unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion. (7) After completion of field piping for split systems, the field pipework shall be pressure tested with an inert gas and then vacuum tested prior to refrigerant charging, according to the following requirements; field-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0.25 times the maximum allowable pressure. No leak shall be detected. (8) Use pipe cutter to cut the connection pipe in case it is unshaped. (9) Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after cutting. (10) Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use flaring tool to fix the flared nut into the pipe (as shown in Fig.4.1). (11) Check if the flared part is flaring evenly and if there is any crack. d2 d1 d2 90°±1° d1 Fig. 4.1 61
GREE Multi Variable Air Conditioners Indoor Unit
4.2 Pipe Bending
(1) Reshape the pipe by hand. Be careful not to damage the pipe.
(2) Do not bend the pipe over 90°.
(3) If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch againch
Therefore, do not bend or stretch the bend for over 3 times.
(4) In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the insulating
layer, as shown in Fig. 4.3. Do not bend the pipe until it is exposed. When bending is done, wrap
the pipe with insulating layer and then secure it with adhesive tape.
Fig. 4.2 Fig. 4.3
4.3 Indoor Pipe Connection
(1) Remove pipe cover and pipe plug.
(2) Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut tightly
by hand, as in Fig. 4.4 (Make sure indoor pipe is correctly connected. Improper location of the
center will prevent flared nut from being securely twisted. Thread of nut will get damaged if the
flared nut is twisted forcibly).
(3) Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound (Hold
the handle of wrench and make it at right angle to the pipe. as in Fig. 4.5).
①
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic tape.
②
Connection pipe should be supported by a bearer rather than the unit.
③
The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use a pipe
bender to bend the pipe.
④
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case the
capillary tube or other tubes have cracks and cause leakage.
Fig. 4.4 Fig. 4.5
62 GREE Multi Variable Air Conditioners Indoor Unit Pipe Diameter(mm/inch) Tightening Torque 6.35(1/4) 15-30N·m(11-22ft.-1b.) 9.52(3/8) 35-40N·m(26-29ft.-1b.) 12.7(1/2) 45-50N·m(33-37ft.-1b.) 15.9(5/8) 60-65N·m(44-48ft.-1b.) 5 Installation of Drain Pipe 5.1 Precautions When Doing the Piping Work Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that air may not remain trapped inside the pipe. For example: Keep pipe size equal to or greater than that of the connecting pipe. Install the drain piping as shown and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings. When directly connecting a hard vinyl chloride pipe joint to the drain hose connected to the indoor unit, use a commercially available hard vinyl chloride pipe joint (nominal diameter 13mm (1/2 inch)). Drain hose connected to the indoor unit Commercially available hard vinyl chloride pipe joint (nominal diameter 13mm(1/2 inch)), Commercially available hard vinyl chloride pipe(nominal diameter 13mm(1/2 inch)) Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger. 63
GREE Multi Variable Air Conditioners Indoor Unit 5.2 Installing the Drain Pipes Insert the drain hose into the drain outlet, and tighten the clamp securely with tape. Tighten the clamp until the screw head is less than 4mm (3/16 inch) from the hose. Insulate the pipe clamp and the drain hose using heat insulation sponge. Install water trap as shown below. Install one water trap for each unit. Installation of water trap shall consider easy cleaning in the future. Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main pipe The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be connected in a manner as shown below: NO.1: 3-way connection of drainage pipe joint Unit: mm (inch) 64
GREE Multi Variable Air Conditioners Indoor Unit NO.2: Connection of drain elbow NO.3: Connection of horizontal pipe When unifying multiple drain pipes, install the pipes as shown below. Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.(take the cassette type unit for example) Unit: mm (inch) 65
GREE Multi Variable Air Conditioners Indoor Unit 5.3 Precautions When Doing Riser Piping Work (1) Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leakage due to dew condensation. 1) Connect the drain hose to the drain raiser pipe, and insulate them. 2) Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp. (2) Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount supporting brackets at an interval of 1 -1.5 m (39-3/8~59in). 5.4 Testing of Drain Piping After piping work is finished, check if drainage flows smoothly. Shown in the figure, add approximately 1liter of water slowly into the drain pan and check drainage flow during COOL running. 6 Electrical Installation The wiring must be in accordance with the local rules. Rated supply voltage and special circuit for air conditioner must be used. Do not pull the power cord forcefully. All the electric installations must be carried out by specialist technicians in accordance with the local laws, rules and these instructions. The diameter of flexible wire should be wide enough. Replace the damaged power cord and connecting wire with special flexible wire. The earthing shall be reliable and connected to the special earthing device on the construction. The installation must be done by specialist technicians. The leak protection switch and air switch with enough capacity must be installed. The air switch shall have both the magnetic tripping and Unit: mm (inch) Unit: mm (inch) 66
GREE Multi Variable Air Conditioners Indoor Unit thermal tripping functions to ensure protection against the short circuit and overload. The air conditioner belongs to I type electric appliances. The reliable earthed action is a must. The yellow and green wire inside the air conditioner is the earthed wire. Do not use it for other purpose or even cut off it. Do not fix it with tapping screw, Otherwise it may cause electric shock. There should be reliable earthed terminal for the power supply. Never connect the earth lead to the following articles: ①water pipe; ②gas pipe; ③drain pipe; ④unreliable place considered by professionals. 6.1 Locking Joint Installation of 360°Air Discharge Cassette Type Indoor Unit When the power cable and communication line of the unit are connected, the power cable and communication line need to be fixed through the side panel locking connector. The fixing process is as follows. (1) Attach the locking joint to the locking joint bracket. (2) Power cable (communication line) passes through the locking joint and the side plate engineering line over the wire crossing hole. (3) Finally, reattach the locking joint bracket to the side panel. 67
GREE Multi Variable Air Conditioners Indoor Unit 6.2 Locking Joint Installation of 360°Air Discharge Compact Cassette Type Indoor Unit When the power cord and communication cable of the unit are connected, the power cable and communication cable need to be fixed through the side panel locking connector. The fixing process is as follows. (1) Remove the locking joint bracket from the side panel. (2) Attach the locking joint to the locking joint bracket. (3) Power cable (communication line) passes through the locking joint and the side plate engineering line over the wire crossing hole. (4) Finally, reattach the locking joint bracket to the side panel. 68
GREE Multi Variable Air Conditioners Indoor Unit MAINTENANCE 69
GREE Multi Variable Air Conditioners Indoor Unit CHAPTER 4 MAINTENANCE 1 Malfunction List 1.1 Malfunction List for the Wired Controller Error Code Content Error Code Content Error Code Content L0 Indoor Unit Error LA Indoor Units Incompatibility Error d9 Jumper Cap Error L1 Indoor Fan Protection LH Low Air Quality Warning dA Indoor Unit Network Address Error L2 E-heater Protection LC ODU-IDU Incompatibility Error dH Wired Controller PCB Error L3 Water Full Protection d1 Indoor Unit PCB Error dC Capacity DIP Switch Setting Error. L4 Wired Controller Power Supply Error d3 Ambient Temperature Sensor Error dL Outlet Air Temperature Sensor Error L5 Freeze protection d4 Inlet Pipe Temperature Sensor Error dE Indoor Unit CO2 Sensor Error L7 No Master Indoor Unit Error d6 Outlet Pipe Temperature Sensor Error dy Water Temperature Sensor Error L8 Power Insufficiency Protection d7 Humidity Sensor Error C0 Communication Error L9 Quantity Of Group Control Indoor Units Setting Error d8 Water Temperature Error AJ Filter Cleaning Reminder db Special Code: Field Debugging Code 1.2 Display of Light Board (Only for Two-way Cassette Type Indoor Unit) The panel of this model is without nixie tube display. The error codes will be displayed through the power light, operation light and timer light; ○, ● and ◎ stand for on, off and blink respectively. Power light ○ ◎ ◎ ◎ ◎ Operation light ◎ ● ○ ○ ◎ Timer light ● ○ ● ○ ● Error code display sheet Error code C0 A0 A3/A4 L0 L1 L3 L5 d1 d3 d4 d6 d7 E0 db Power light ◎ ○ ○ ● ● ● ○ ◎ ◎ ◎ ● ○ ● ◎ Operation light ◎ ◎ ○ ● ○ ◎ ● ○ ● ◎ ◎ ◎ ◎ ● Timer light ◎ ◎ ◎ ◎ ◎ ◎ ◎ ◎ ◎ ○ ○ ○ ● ● Communicati on error Ambient temperature sensor error Inlet pipe temperature sensor error Outlet pipe temperature sensor error Humidity sensor error Outdoor unit error Defrosting/ oil return Indoor unit error Indoor unit PCB error Field debugging code To be debugged Indoor fan protection Water full protection Freeze protection Error description 70
GREE Multi Variable Air Conditioners Indoor Unit 1.3 Exception Analyzing and Troubleshooting 1.3.1 “d1” Indoor circuit board error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Check if the reading of address chip and memory chip of IDU mainboard is normal. If the data of address chip and memory chip cannot be read, it is abnormal Possible reason: Address chip is abnormal Memory chip is abnormal. Replace main control board directly Troubleshooting: Replace main control board directly 1.3.2 “d3” Ambient temperature sensor error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD value, if the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error Possible reason: Poor contact between ambient temperature sensor and terminal in mainboard interface Ambient temperature sensor is abnormal Detecting circuit is abnormal Troubleshooting: 71
GREE Multi Variable Air Conditioners Indoor Unit 1.3.3 “d4” Inlet pipe temperature sensor error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error Possible reason: Poor contact between inlet pipe temperature sensor and terminal in mainboard interface Inlet pipe temperature sensor is abnormal Detecting circuit is abnormal Troubleshooting: 1.3.4 “d6” Outlet pipe temperature sensor error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error 72
GREE Multi Variable Air Conditioners Indoor Unit Possible reason: Poor contact between outlet pipe temperature sensor and terminal in mainboard interface Outlet pipe temperature sensor is abnormal Detecting circuit is abnormal 1.3.5 “d7” Humidity sensor error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error Possible reason: Poor contact between humidity sensor and terminal in mainboard interface Humidity sensor is abnormal Detecting circuit is abnormal 73
GREE Multi Variable Air Conditioners Indoor Unit Troubleshooting: 1.3.6 “d9” Jumper cap error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Possible reason: If jumper cap model doesn’t match with mainboard, report the error Jumper cap is not installed Jumper cap model is wrong Detecting circuit is abnormal Troubleshooting: 74
GREE Multi Variable Air Conditioners Indoor Unit 1.3.7 “dA” IDU network address error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Through testing the IDU address chip and IP address, if address chip cannot be read, IDU IP is 0 or IP is in conflict, report the error. Possible reason: ODU allocated address is wrong IDU treatment is wrong Address chip is abnormal Troubleshooting: 1.3.8 “dH” wired controller circuit board error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Wired controller IIC communication is abnormal Possible reason: Communication of wired controller touch button board and display board IIC is abnormal; Read and write of wired controller memory chip IIC is abnormal (when memory chip is existed); Troubleshooting: 75
GREE Multi Variable Air Conditioners Indoor Unit 1.3.9 “dC” Capacity DIP switch setting error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: If capacity DIP switch is set to the wrong position, report the error. Possible reason: Capacity DIP switch is set to the wrong position Detecting circuit is abnormal Troubleshooting: 1.3.10 “dL” Air outlet temperature sensor error Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error Possible reason: Poor contact between air outlet temperature sensor and terminal in mainboard interface Air outlet temperature sensor is abnormal Detecting circuit is abnormal 76
GREE Multi Variable Air Conditioners Indoor Unit Troubleshooting: 1.3.11 “db” Project debugging Error display: ODU mainboard, IDU wired controller and IDU receive light board will display Error judgment condition and method: This is a status code of project debugging, not an error code. When IDU or ODU displays this code, it means the unit is under debugging status and the IDU cannot be operated. Troubleshooting: —— Possible reason:—— 1.3.12 “L1” Indoor fan protection Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Check if the rotation speed of IDU is too slow, or it stops rotation, or protection signal of outdoor fan is transferred. If yes, it is judged that indoor fan protection occurs. Possible reason: Motor stops operation or it is blocked IDU mainboard is abnormal 77
GREE Multi Variable Air Conditioners Indoor Unit Troubleshooting: 1.3.13 “L3” Water full protection Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Check the status of IDU float switch. When water level is too high, float switch is activated, so water 78
GREE Multi Variable Air Conditioners Indoor Unit full protection happens. Possible reason: IDU is installed improperly Drainage pump is broken Float switch operates abnormally IDU mainboard is abnormal Troubleshooting: 79
GREE Multi Variable Air Conditioners Indoor Unit 1.3.14 “L4” Power supply overcurrent protection Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Check if the power supply current from IDU to wired controller is normal. If power supply current is too big, it is judged that the current is abnormal. Possible reason: Power supply conducting wire of wired controller is short circuited IDU mainboard is abnormal Mainboard of wired controller is abnormal Troubleshooting: 1.3.15 “L5” Freeze protection Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Check IDU pipe temperature. When pipe temperature is too low, freeze protection will be activated to prevent freezing damage of evaporator. Possible reason: IDU filter and evaporator are dirty IDU motor is blocked Refrigerant amount is insufficient Ambient temperature of IDU and ODU is too low 80
GREE Multi Variable Air Conditioners Indoor Unit Troubleshooting: 1.3.16 “L7” No master IDU Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: No master IDU error will happen when there is no master IDU in the system Possible reason: Master IDU is offline The mainboard of master IDU is replaced The mainboard of master IDU has error 81
GREE Multi Variable Air Conditioners Indoor Unit Troubleshooting: 1.3.17 “L9” Group-controlled IDU quantity inconsistency Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: If the IDU quantity connected with wired controller exceeds 16 sets or actually connected IDU quantity is inconsistent with the set group-controlled IDU quantity. Possible reason: IDU quantity connected with one wired controller exceeds 16 sets; Actually connected IDU quantity is inconsistent with the set group-controlled IDU quantity. Troubleshooting: 1.3.18 “LA” Group-controlled IDU series inconsistency Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: Wired controller detects that the IDUs connected with itself belong to different series. Possible reason: IDUs connected with one wired controller belong to different series 82
GREE Multi Variable Air Conditioners Indoor Unit Troubleshooting: Make sure the IDUs connected with one wired controller belong to the same series. 1.3.19 “LC” Mismatch of IDU and ODU models Error display: IDU wired controller and IDU receive light board will display Error judgment condition and method: When some IDUs or devices which cannot be identified by some ODUs are installed in the system, mismatch error of IDU and ODU models will occur. Possible reason: Mismatch of IDU and ODU Troubleshooting: When some IDUs or devices which cannot be identified by some ODUs are installed in the system (E.g. floor heating device is installed in modular DC inverter multiple VRF system), the error will occur. Please remove the relevant IDU devices or replace the ODU with suitable model. 2 After-sales Emergency Masures When some unrecoverable fault occurs to one module which is connected with several others in parallel, the following emergency measures are recommended to guarantee the heating or cooling capacity of the indoor units and the service life of modules except the faulted one are not affected. Step 1: set all indoor units under “Off” mode and cut off the power supply to the indoor and outdoor units. Step 2: shut off all cutoff valves of the faulted outdoor unit, including the cutoff valves of the liquid/gas pipe as well as the oil balancing valve. Step 3: cut off the air switch of the module. Step 4: remove the communication line between the faulted module and other modules which are still kept connected through the communication line. Step 5: readjust the address and quantity settings on the main board of the modules except the faulted one. Step 6: power and restart the unit. 3 About the Refrigerant Leakage Sensor (1) The R32 refrigerant leakage sensor must be replaced after malfunction or at the end of its lifetime. ONLY authorized persons may replace the sensor. (2) The sensor has a lifetime of 15 years. At the end of sensor lifetime or when the sensor fault, the indoor unit or wired controller displays error code "yd", and emits an alarm sound. The alarm can be canceled by operating the “On/Off” button of the wired controller or remote control. The indoor unit fan will keep running and the system can not operate until the sensor is replaced. Please contact our designated dealer or local service center to replace the sensor. (3) The R32 refrigerant leakage sensor is a semiconductor detector which may incorrectly detect substances other than R32 refrigerant. Avoid using chemical substances (e.g. organic solvents, 83
GREE Multi Variable Air Conditioners Indoor Unit hair spray, paint) in high concentrations, in the close proximity of the indoor unit because this may cause misdetection of the R32 refrigerant leakage sensor. (4) When the sensor detects refrigerant leak, the indoor unit or wired controller displays error code "yb", and emits an alarm sound. The alarm can be canceled by operating the “On/Off” button of the wired controller or remote control. The indoor unit fan will keep running and the system can not operate until the leakage is repaired. Please contact our designated dealer or local service center. (5) If the indoor unit report a refrigerant leak and returns to normal after a while, it may be a misdetection caused by other chemical substances. 84
GREE Multi Variable Air Conditioners Indoor Unit 4 Wiring Diagram This drawing is just for reference; please always refer to the electric wiring stuck to the unit for actual wiring. 4.1 High Static Pressure Duct Type Indoor Unit GMV-ND07~54PHS/NhD-T(U): 85
GREE Multi Variable Air Conditioners Indoor Unit 4.2 Fresh Air Processing Indoor Unit GMV-NDX42~54P/NhD-T(U): 4.3 Air Handler Type Indoor Unit GMV-ND12~60A/NhB-T(U): 86
GREE Multi Variable Air Conditioners Indoor Unit 4.4 360°Air Discharge Casssette Type Indoor Unit GMV-ND07~48T/NhD-T(U): 4.5 360°Air Discharge Compact Casssette Type Indoor Unit GMV-ND05~18T/NhE-T(U): 87
GREE Multi Variable Air Conditioners Indoor Unit 4.6 1-way Cassette Type Indoor Unit GMV-ND07~12TD/NhA-T(U): 4.7 Wall Mounted Type Indoor Unit GMV-ND06~24G/NhA1C-T(U)、GMV-ND06~24G/NhA3C-T(U): 88
GREE Multi Variable Air Conditioners Indoor Unit 5 Disassembly and Assembly Procedure of Main Parts 5.1 High Static Pressure Duct Type Indoor Unit The following steps are specific for GMV-ND18PHS/NhD-T(U) units. For other units, the assembly and disassembly procedure is similar except the specifications of centrifugal fans and motors. Motor and fan Precondition: The power supply has been disconnected. Step Diagram Operation Procedure 1. Remove the line connecting to the motor. 2. Remove the filter. Remove the filter from the air 3. Remove the air return cover plate. Use a screwdriver to unscrew 4. Remove the volute casing. 5. Loosen the centrifugal fan and motor. 89 Use a screwdriver to unscrew the electric box cover. Remove from the master board the line connecting to the motor and remove the tie. return frame. the air return cover plate. Loosen the fasteners that connect the rear volute casing with the front volute casing and remove the rear volute casing. Use a hexagon to unscrew the centrifugal fan and loosen the fasteners of the motor.
GREE Multi Variable Air Conditioners Indoor Unit Motor and fan Precondition: The power supply has been disconnected. Step Diagram Operation Procedure 6. Remove the motor. 7. Install a new motor. 8. Remove the Refrigerant Sensor. 5.2 Fresh Air Processing Indoor Unit Motor and fan Precondition: The power supply has been disconnected. Step Diagram Operation Procedure 1. Remove the line connecting to the motor. 2. Remove the filter. Remove the filter from the air 90 Remove the motor from the support and remove the centrifugal fan from the motor axle. Then, remove the motor. For motors that are accompanied with supports, the supports need removing as well. Assemble units based on the reverse order of this procedure and power on the units for test. Remove the Refrigerant Sensor from the Water Pump Assy and the Water Pump Assy from Left Side Plate Assy. Then, remove the Refrigerant Sensor. Use a screwdriver to unscrew the electric box cover. Remove from the master board the line connecting to the motor and remove the tie. return frame.
GREE Multi Variable Air Conditioners Indoor Unit Motor and fan Precondition: The power supply has been disconnected. Step Diagram Operation Procedure 3. Remove the air return cover plate. Use a screwdriver to unscrew 4. Remove the volute casing. 5. Loosen the centrifugal fan and motor. 6. Remove the motor. 7. Install a new motor. 8. Remove the Refrigerant Sensor. 91 the air return cover plate. Loosen the fasteners that connect the rear volute casing with the front volute casing and remove the rear volute casing. Use a hexagon to unscrew the centrifugal fan and loosen the fasteners of the motor. Remove the motor from the support and remove the centrifugal fan from the motor axle. Then, remove the motor. For motors that are accompanied with supports, the supports need removing as well. Assemble units based on the reverse order of this procedure and power on the units for test. Remove the Refrigerant Sensor from the Water Pump Assy and the Water Pump Assy from Left Side Plate Assy. Then, remove the Refrigerant Sensor.
GREE Multi Variable Air Conditioners Indoor Unit 5.3 Air Handler Type Indoor Unit Step Picture Work Instruction 1.Remove the upper panel. 2.Remove the front panel. 3.Remove the electric box. 4.Remove the electric element. Disassembly and Assembly of the Electric Box Loosen screws around the upper panel with a screwdriver. Remove the upper panel away from the unit. Loosen screws around the upper panel with a screwdriver. Remove the front panel away from the unit. Disconnect the power cord and control line from the wiring terminals, and then draw them out. Loosen screws around the electric box with a screwdriver. Remove the electric box from the unit. Disconnect the electric element from the wiring terminal. Loosen screws around the electric element with a screwdriver. Remove the electric element from the electric box. 92
GREE Multi Variable Air Conditioners Indoor Unit Step Picture Work Instruction 5.Mount the new electric element. 6.Reinstall the electric box. Step Picture Work Instruction 1.Remove the upper panel. 2.Remove the fan. Disassembly and Assembly of the Electric Box Place the electric element at the proper position. Tighten the screws around the electric element with a screwdriver. Wire the electric element to the wiring terminal. Place the electric box at the proper position. Tighten screws around the electric box with a screwdriver. Connect the power cord and control line properly. Reassemble the unit as before. Disassembly and Assembly of the Fan Motor Loosen screws round the upper panel with a screwdriver. Remove the upper panel from unit. Disconnect the wires of the fan from the wiring terminal and draw them out. Loosen screws located at the front of the fan with a screwdriver. Remove the fan from the unit. 93
GREE Multi Variable Air Conditioners Indoor Unit Disassembly and Assembly of the Fan Motor Step Picture Work Instruction Loosen screws fixing the motor and fan blades. Loosen screw bolts fixing the 3.Remove the motor. bracket. Remove the motor rightward from the fan. Place the motor at the proper position. Tighten screws fixing the motor and fan blades. Tighten screw bolts fixing the motor 4.Reinstall the fan. bracket. After the installation, reassemble the unit as before. Disassembly and Assembly of the Evaporator and Drain Pan Step Picture Work instruction Loosen screws round the upper panel with a screwdriver. Remove the upper panel 1.Remove the upper panel. from unit. Loosen screws round the 2.Remove the lower panel (1) and panel (2). lower panel with a screwdriver. Remove the lower panel from unit. 94
GREE Multi Variable Air Conditioners Indoor Unit Disassembly and Assembly of the Evaporator and Drain Pan Step Picture Work instruction 3.Remove the enhanced frame if applicable. 4.Remove the primary drain pan. 5.Remove the secondary drain pan. Remove the screws from enhanced frame. Disassemble the enhanced frame from the unit. Remove the primary drain pan from the unit. Remove the secondary drain pan from the unit. 95
GREE Multi Variable Air Conditioners Indoor Unit Disassembly and Assembly of the Evaporator and Drain Pan Step Picture Work instruction Remove the evaporator away from the primary drain pan. Reassemble the unit as 6.Remove the evaporator. before. Disassembly and Assembly of the Filter Step Picture Work instruction Loosen screws fixing the mounting 1.Remove the mounting plate. plate with a screwdriver. Remove the mounting plate away from the unit. Remove the filter screen away from the unit. After replacing the filter screen, 2.Remove the filter screen. reassemble the unit as before. 96
GREE Multi Variable Air Conditioners Indoor Unit Step Picture Work instruction 1.Turn the internal unit upside down. 2.Install the enhanced frame. 3.install the lower panel (1) and panel (2). 4.install the upper panel. Installation of downward air supply mode Loosen screws around the upper and lower panel with a screwdriver. Remove the front panel away from the unit. install the screws from enhanced frame. install the enhanced frame from the unit. install screws round the lower panel with a screwdriver. install the lower panel for unit. install screws round the upper panel with a screwdriver. install the upper panel from unit. 97
GREE Multi Variable Air Conditioners Indoor Unit Step Picture Work instruction 1.Remove the lower panel (1) and panel (2). 2.Remove the refrigerant sensor. 5.4 360°Air Discharge Casssette Type Indoor Unit Step Diagram Operation Procedure 1. Remove the front panel. Disassembly and Assembly of refrigerant sensor Loosen screws around the lower panel with a screwdriver. Remove the lower panel away from the unit. Remove the refrigerant sensor away from the unit. After replacing the refrigerant sensor , reassemble the unit as before. Motor and fan Turn off the power supply of indoor unit. Push the 4 corner plates in the directions shown by the arrows. Loosen the screws and remove the front panel. 98
GREE Multi Variable Air Conditioners Indoor Unit Step Diagram Operation Procedure 2. Remove the cover of electric box and the clamp of power cord. 3. Remove the water tray. 4. Remove the fan. 5. Remove the motor. Motor and fan Remove the motor wire and water pump of the electric box. Loosen the screws in the 4 corners and then remove the water tray. Use a screwdriver to remove the clamping band of motor. Then remove the fan. Use a screwdriver to unscrew the 3 screws of motor. Then remove the motor. 99
GREE Multi Variable Air Conditioners Indoor Unit Step Diagram Operation Procedure 6. Replace and install the motor. 7. Install the fan. 8. Install the water tray. 9. Remove the Refrigerant Sensor Motor and fan Remove the motor from motor support and then replace with a new motor. Tighten the 3 screws of motor with a screwdriver. Direct the hole of fan to the motor shaft and then mount on the fan. Tighten the clamping band of motor with a wrench. Direct the 4 corners of water tray to the 4 corners of the unit and then press them. Use a screwdriver to tighten the screws in the 4 corners. Connect the power cord and water pump wire. Place back the cover of electric box and the clamp of power cord. Then tighten the screws with a screwdriver. Remove the 2 Refrigerant Sensor fixing screws, and then you can remove the Refrigerant Sensor. 100
GREE Multi Variable Air Conditioners Indoor Unit 5.5 360°Air Discharge Compact Casssette Type Indoor Unit Step Diagram Operation Procedure 1. Remove the front panel. 2. Remove the cover of electric box and the clamp of power cord. 3. Remove the water tray. Motor and fan Turn off the power supply of indoor unit. Push the 4 corner plates in the directions shown by the arrows. Loosen the screws and remove the front panel. Remove the motor wire and water pump of the electric box. Loosen the screws in the 4 corners and then remove the water tray. 101
GREE Multi Variable Air Conditioners Indoor Unit Step Diagram Operation Procedure 4. Remove the fan. 5. Remove motor. 6. Remove the refrigerant sensor 7.Replacement and installation of refrigerant sensor Motor and fan Use a screwdriver to remove the clamping band of motor. Then remove the fan. Use a screwdriver to unscrew the 4 screws of motor. Then remove the motor. Remove the two fixing screws on the back of the connector plate. Move upwards to remove the refrigerant sensor. Remove the refrigerant sensor from the connector plate, then replace it with a new refrigerant sensor. Use a screwdriver to tighten the two screws of the refrigerant sensor. 102
GREE Multi Variable Air Conditioners Indoor Unit Step Diagram Operation Procedure 8. Replace and install the motor. 9. Install the fan. 10. Install the water tray. 5.6 1-way Cassette Type Indoor Unit Step Diagram Operation Procedure 1.Unscrew the water tray. Use a screwdriver to unscrew the 2.Remove the water tray. Remove the water tray. Motor and fan Remove the motor from motor support and then replace with a new motor. Tighten the 4 screws of motor with a screwdriver. Direct the hole of fan to the motor shaft and then mount on the fan. Tighten the clamping band of motor with a wrench. Direct the 4 corners of water tray to the 4 corners of the unit and then press them. Use a screwdriver to tighten the screws in the 4 corners. Connect the power cord and water pump wire. Place back the cover of electric box and the clamp of power cord. Then tighten the screws with a screwdriver. Motor and fan water tray. 103
GREE Multi Variable Air Conditioners Indoor Unit Step Diagram Operation Procedure 3.Unscrew the volute tongue. Use a screwdriver to unscrew the 4.Remove the volute tongue. Remove the volute tongue. 5.Unscrew the outlet board. 6.Remove the evaporator. Remove the evaporator. 7.Unscrew the motor pressing board. 8.Remove the pressing board and replace the motor. Motor and fan volute tongue. Use a screwdriver to unscrew the outlet board and then remove the board. Use a screwdriver to unscrew the motor pressing board. Remove the pressing board and replace the motor. 104
GREE Multi Variable Air Conditioners Indoor Unit Step Diagram Operation Procedure 9.Screw the motor pressing board. Use a screwdriver to screw the 10.Install the evaporator. Install the evaporator. 11.Screw the outlet board. Use a screwdriver to screw the 12.Put the volute tongue back to position. 13.Screw the volute tongue. Use a screwdriver to screw the 14.Install the water tray. Install the water tray. 15.Screw the water tray. Use a screwdriver to screw the Motor and fan motor pressing board. outlet board. Put the volute tongue back to position. volute tongue. water tray. 105
GREE Multi Variable Air Conditioners Indoor Unit 5.7 Wall Mounted Type Indoor Unit Removal of Fan Motor Remark: before removing, making sure power is disconnected. Step Diagram Operation Procedure 1. Remove the louver 2. Open the front panel 3. Remove the electrical box cover 2 4. Remove the front panel assembly 5. Remove the electrical box cover 1 6. Remove the main board 106 Take off the axle bush of the louver. Remove the louver. Hold the indents on both sides of the panel and pull it out in the direction shown by the arrow. Unscrew the screws fixing the electrical box cover with a screwdriver. Take off the box cover 2. Detach the ambient temperature sensor from the conduit. Unscrew the screws fixing the front panel assembly. Remove the front panel assembly. Press on the buckle of the box cover 1 and then take off the cover. Release the wiring terminals connected to the main board. Remove the main board.
GREE Multi Variable Air Conditioners Indoor Unit Removal of Fan Motor Remark: before removing, making sure power is disconnected. Step Diagram Operation Procedure 7. Remove the electrical box 8. Remove the evaporator 9.Remove motor’s pressing plate 10. Remove the motor and fan 11. Install a new motor. 107 Unscrew the screws fixing the electrical box with a screwdriver. Remove the electrical box. Use a screwdriver to unscrew the screws fixing the press plate of connection pipe on the back of the unit and take off the press plate. Unscrew the screws of evaporator with a screwdriver and then remove the evaporator. Unscrew the fixing screws of the pressing plate with a screwdriver and then remove it. Take off the motor and fan directly. Use a screwdriver to unscrew the screws connecting the motor and the fan. Assemble units based on the reverse order of this procedure and power on the units for test.
GREE Multi Variable Air Conditioners Indoor Unit 6 Exploded Views and Part List 6.1 High Static Pressure Duct Type Indoor Unit Exploded View of GMV-ND07~24PHS/NhD-T(U): 1 2 3 4 5 6 7 8 9 10 GMV-ND12PHS/NhD-T(U) GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U) GMV-ND24PHS/NhD-T(U) Part Name Part Code Qty. Part Code Qty. Model GMV-ND07PHS/NhD-T(U) GMV-ND09PHS/NhD-T(U) No. 1 Hook 02112466 4 02112466 4 2 Filter Sub-Assy 111001000045 2 111001000045 2 3 Propeller Housing(Lower) 26905200079 2 26905200079 2 4 Centrifugal Fan 10455200003 2 10455200003 2 5 Propeller Housing(Upper) 26905200078 2 26905200078 2 6 Brushless DC Motor 15010406007901 1 15010406007901 1 7 Electric Box Assy 100002083603 1 100002083603 1 8 Main Board 300002064354 1 300002064354 1 9 Terminal Board 42200006005404 1 42200006005404 1 10 Terminal Board 4201110602 1 4201110602 1 11 Refrigerant Sensor 340024060017 1 340024060017 1 12 Pump Drainpipe 200070060004 1 200070060004 1 20 21 22 23 24 19 18 17 14 15 16 13 12 11 108
GREE Multi Variable Air Conditioners Indoor Unit GMV-ND12PHS/NhD-T(U) GMV-ND15PHS/NhD-T(U) GMV-ND18PHS/NhD-T(U) GMV-ND24PHS/NhD-T(U) Part Name Part Code Qty. Part Code Qty. Model GMV-ND07PHS/NhD-T(U) GMV-ND09PHS/NhD-T(U) No. 13 Water Pump 81200706032701 1 81200706032701 1 14 Liquid Level Switch 430024000005 1 430024000005 1 15 Strainer 07415210 1 07415210 1 16 Strainer 07213050 1 07213050 1 17 Electronic Expansion Valve 072009060064 1 072009060076 1 18 Electric Expand Valve Fitting 07200206000109 1 07200206000109 1 19 Evaporator Assy 011001063469 1 011001063321 1 20 Temperature Sensor 340025060014 1 340025060014 1 21 Temperature Sensor 340025060014 1 340025060014 1 22 Temperature Sensor 340025060018 1 340025060018 1 23 Display Board 300001061780 1 300001061780 1 24 Drain Hose Sub-Assy 05232050 1 05232050 1 Above data is subject to change without notice, please refer the SP in global service website. 109
GREE Multi Variable Air Conditioners Indoor Unit Exploded View of GMV-ND30~54PHS/NhD-T(U): 20 21 22 23 24 25 10 12 13 15 11 14 1 2 3 4 5 6 7 8 9 GMV-ND30PHS/NhD-T(U) GMV-ND36PHS/NhD-T(U) GMV-ND42PHS/NhD-T(U) GMV-ND48PHS/NhD-T(U) GMV-ND54PHS/NhD-T(U) Model No. Part Name Part Code 1 Filter Sub-Assy 111001000052 3 2 Propeller Housing(Upper) 26905200078 3 3 Brushless DC Motor 1570940000805 1 4 Centrifugal Fan 10455200003 3 5 Propeller Housing(Lower) 26905200079 3 6 Electric Expand Valve Fitting 07200206000109 1 7 Water Pump 81200706032701 1 8 Pump Drainpipe 200070060004 1 9 Refrigerant Sensor 340024060017 1 10 Liquid Level Switch 430024000005 1 11 Electric Box Assy 100002083095 1 12 Main Board 300002064284 1 13 Terminal Board 42200006005404 1 14 Terminal Board 4201110602 1 15 Hook 02112466 4 110 16 17 18 19 Qty.
GREE Multi Variable Air Conditioners Indoor Unit GMV-ND30PHS/NhD-T(U) GMV-ND36PHS/NhD-T(U) GMV-ND42PHS/NhD-T(U) GMV-ND48PHS/NhD-T(U) GMV-ND54PHS/NhD-T(U) Model No. Part Name Part Code 16 Strainer 07213050 1 17 Electronic Expansion Valve 072009060056 1 18 Strainer 07415210 1 19 Evaporator Assy 011001063320 1 20 Temperature Sensor 340025060014 1 21 Temperature Sensor 340025060014 1 22 Temperature Sensor 340025060018 1 23 Display Board 300001061780 1 24 Drain Hose Sub-Assy 05232050 1 25 Corrugated Pipe 05015408 1 Above data is subject to change without notice, please refer the SP in global service website. 111 Qty.
GREE Multi Variable Air Conditioners Indoor Unit 6.2 Fresh Air Processing Type Indoor Unit Exploded View of GMV-NDX42~54P/NhD-T(U) 17 18 13 14 15 16 1 2 3 4 5 6 7 9 10 12 8 11 GMV-NDX42P/NhD-T(U) GMV-NDX48P/NhD-T(U) GMV-NDX54P/NhD-T(U) Part Name Part Code Qty. Model No. 1 Filter Sub-Assy 111001000052 3 2 Propeller Housing(Upper) 26905200078 3 3 Brushless DC Motor 1570940000805 1 4 Centrifugal Fan 10455200003 3 5 Propeller Housing(Lower) 26905200079 3 6 Electric Expand Valve Fitting 07200206000109 1 7 Refrigerant Sensor 340024060017 1 8 Electric Box Assy 100002083095 1 9 Main Board 300002064284 1 10 Terminal Board 42200006005404 1 11 Terminal Board 4201110602 1 12 Hook 02112466 4 13 Strainer 07213050 1 14 Electronic Expansion Valve 072009060056 1 112
GREE Multi Variable Air Conditioners Indoor Unit GMV-NDX42P/NhD-T(U) GMV-NDX48P/NhD-T(U) GMV-NDX54P/NhD-T(U) Part Name Part Code Qty. Model No. 15 Strainer 07415210 1 16 Evaporator Assy 011001063320 1 17 Drain Hose Sub-Assy 05232050 1 18 Corrugated Pipe 05015408 1 Above data is subject to change without notice, please refer the SP in global service website. 113
GREE Multi Variable Air Conditioners Indoor Unit 6.3 Air Handler Type Indoor Unit Exploded View of GMV-ND12~30A/NhB-T(U): 11 12 13 1 2 3 4 5 6 GMV-ND24A/NhB-T(U) GMV-ND30A/NhB-T(U) Part Name Part Code Qty. Part Code Qty. Model GMV-ND12A/NhB-T(U) GMV-ND18A/NhB-T(U) No . 1 Brushless DC Motor 15010400001401 1 15010400001401 1 2 Centrifugal Fan Housing 1570220101 1 1570220101 1 3 Electronic Expansion Valve 072009060064 1 072009060076 1 4 Evaporator Assy 011001063608 1 011001063609 1 5 Filter Sub-Assy 111001060269 1 111001060269 1 6 Refrigerant Sensor 340024060017 1 340024060017 1 7 Electric Box Assy 100002084426 1 100002084426 1 8 Main Board 300002064555 1 300002064555 1 9 Terminal Board 42200006005404 1 42200006005404 1 10 Transformer 43110286 1 43110286 1 11 Electric Expand Valve Fitting 07200206000103 1 07200206000103 1 12 Sensor Sub-Assy 390002060766 1 390002060766 1 13 Temperature Sensor 390001060085 1 390001060085 1 Above data is subject to change without notice, please refer the SP in global service website. 114 7 8 9 10
GREE Multi Variable Air Conditioners Indoor Unit Exploded View of GMV-ND36~42A/NhB-T(U): 11 12 13 1 2 3 4 5 6 Model GMV-ND36A/NhB-T(U) GMV-ND42A/NhB-T(U) No. Part Name Part Code Qty. 1 Brushless DC Motor 15010400001401 1 2 Centrifugal Fan Housing 1570220201 1 3 Electronic Expansion Valve 072009060056 1 4 Evaporator Assy 011001063610 1 5 Filter Sub-Assy 111001060160 1 6 Refrigerant Sensor 340024060017 1 7 Electric Box Assy 100002084426 1 8 Main Board 300002064555 1 9 Terminal Board 42200006005404 1 10 Transformer 43110286 1 11 Electric Expand Valve Fitting 07200206000103 1 12 Sensor Sub-Assy 390002060766 1 13 Temperature Sensor 390001060085 1 Above data is subject to change without notice, please refer the SP in global service website. 115 7 8 9 10
GREE Multi Variable Air Conditioners Indoor Unit Exploded View of GMV-ND48~60A/NhB-T(U): 8 9 10 11 12 13 14 1 2 3 4 6 5 7 GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) Model No. Part Name Part Code Qty. 1 Brushless DC Motor 15010400001301 1 2 Centrifugal Fan Housing 1570220301 1 3 Electronic Expansion Valve 072009060056 1 4 Evaporator Assy 011001063611 1 5 Strainer 0721200102 1 6 Filter Sub-Assy 111001060188 1 7 Refrigerant Sensor 340024060017 1 8 Electric Box Assy 100002084426 1 9 Main Board 300002064555 1 10 Terminal Board 42200006005404 1 11 Transformer 43110286 1 12 Electric Expand Valve Fitting 07200206000103 1 116
GREE Multi Variable Air Conditioners Indoor Unit Model No. Part Name Part Code Qty. 13 Sensor Sub-assy 390002060766 1 14 Temperature Sensor 390001060085 1 Above data is subject to change without notice, please refer the SP in global service website. GMV-ND48A/NhB-T(U) GMV-ND54A/NhB-T(U) GMV-ND60A/NhB-T(U) 117
GREE Multi Variable Air Conditioners Indoor Unit 6.4 360°Air Discharge Casssette Type Indoor Unit Exploded View of GMV-ND07~18T/NhD-T(U): 1 2 3 4 5 6 7 8 9 10 11 12 15 GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) Model No. Part Name Part Code Qty. Part Code Qty. 1 Terminal Board 42200006005404 1 42200006005404 1 2 Main Board 300002064302 1 300002064302 1 3 Terminal Board 42200006001301 1 42200006001301 1 4 Electric Box Assy 100002083156 1 100002083156 1 5 Diversion Circle 200150060030 1 200150060030 1 6 Centrifugal Fan 103003060047 1 103003060047 1 7 Brushless DC Motor 150104060121 1 150104060121 1 118 20 19 18 17 16 14 13 GMV-ND15T/NhD-T(U) GMV-ND18T/NhD-T(U)
GREE Multi Variable Air Conditioners Indoor Unit GMV-ND07T/NhD-T(U) GMV-ND09T/NhD-T(U) GMV-ND12T/NhD-T(U) Model No. Part Name Part Code Qty. Part Code Qty. 8 Evaporator Assy 011001063464 1 011001063307 1 9 Electronic Expansion Valve 072009060064 1 072009060076 1 10 Strainer 07213050 1 07213050 1 11 Strainer A 0721002201 1 0721002201 1 12 Body Installing Plate 01332701 4 01332701 4 13 Drainage Pipe Sub- assy 26909400055 1 26909400055 1 14 Water Pump 43138000058 1 43138000058 1 15 Refrigerant Sensor 340024060017 1 340024060017 1 16 Liquid Level Switch 4502021603 1 4502021603 1 17 Electric Expand Valve Fitting 4304413252 1 4304413252 1 18 Remote Controller 30510589 1 30510589 1 19 Drain Hose Sub-assy 05339400001 1 05339400001 1 20 Sensor Sub-assy 390002060712 1 390002060712 1 Above data is subject to change without notice, please refer the SP in global service website. 119 GMV-ND15T/NhD-T(U) GMV-ND18T/NhD-T(U)
GREE Multi Variable Air Conditioners Indoor Unit Exploded View of GMV-ND24~48T/NhD-T(U): 1 2 3 4 5 6 7 8 9 10 11 14 Model GMV-ND24T/NhD-T(U) No. Part Name Part Code Qty. Part Code Qty. 1 Terminal Board 42200006005404 1 42200006005404 1 2 Main Board 300002064286 1 300002064286 1 3 Terminal Board 42200006001301 1 42200006001301 1 4 Electric Box Assy 100002083157 1 100002083157 1 5 Diversion Circle 200150060029 1 200150060029 1 6 Centrifugal Fan 103003060048 1 103003060048 1 7 Brushless DC Motor 15010406012201 1 15010406012201 1 8 Evaporator Assy 011001063685 1 011001063308 1 20 19 18 17 16 15 13 12 GMV-ND30T/NhD-T(U) GMV-ND36T/NhD-T(U) GMV-ND42T/NhD-T(U) GMV-ND48T/NhD-T(U) 120
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND24T/NhD-T(U) No. Part Name Part Code Qty. Part Code Qty. 9 Strainer 07213050 1 07213050 1 10 Electronic Expansion Valve 072009060076 1 072009060076 1 11 Body Installing Plate 01332701 4 01332701 4 12 Drainage Pipe Sub-assy 26909400055 1 26909400055 1 13 Water Pump 43138000058 1 43138000058 1 14 Refrigerant Sensor 340024060017 1 340024060017 1 15 Liquid Level Switch 4502021603 1 4502021603 1 16 Electric Expand Valve Fitting 4304413252 1 4304413252 1 17 Remote Controller 30510589 1 30510589 1 18 Drain Hose Sub-assy 05339400001 1 05339400001 1 19 Corrugated Pipe 035030000008 1 05015408 1 20 Sensor Sub-assy 390002060712 1 390002060712 1 Above data is subject to change without notice, please refer the SP in global service website. GMV-ND30T/NhD-T(U) GMV-ND36T/NhD-T(U) GMV-ND42T/NhD-T(U) GMV-ND48T/NhD-T(U) 121
GREE Multi Variable Air Conditioners Indoor Unit 6.5 360°Air Discharge Compact Casssette Type Indoor Unit Exploded View of GMV-ND05T/NhE-T(U);GMV-ND07T/NhE-T(U) ;GMV-ND09T/NhE-T(U) ;GMV- ND12T/NhE-T(U); GMV-ND15T/NhE-T(U); GMV-ND18T/NhE-T(U). 1 2 3 4 5 6 7 GMV-ND05T/NhE-T(U) GMV-ND07T/NhE-T(U) GMV-ND09T/NhE-T(U) GMV-ND12T/NhE-T(U) Model No. Part Name Part Code Qty. Part Code Qty. 1 Diversion Circle 20015006000301 1 20015006000301 1 2 Centifugal Fan 103003060008 1 103003060008 1 3 Brushless DC Motor 150104060012 1 150104060012 1 122 18 17 16 15 14 13 12 11 10 9 8 GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U)
GREE Multi Variable Air Conditioners Indoor Unit GMV-ND05T/NhE-T(U) GMV-ND07T/NhE-T(U) GMV-ND09T/NhE-T(U) GMV-ND12T/NhE-T(U) Model No. Part Name Part Code Qty. Part Code Qty. 4 Evaporator Assy 011001063859 1 011001063623 1 5 Filter 07216221 1 07216221 1 6 Strainer 07213032 1 07213032 1 7 Electric expand valve fitting 43040001 1 43040001 1 8 Drain Pipe 200070060005 1 200070060005 1 9 Water Pump 4313800005802 1 4313800005802 1 10 Liquid Level Switch 430024000005 4 430024000005 4 11 Refrigerant Sensor 340024060017 1 340024060017 1 12 Remote Controller 30510589 1 30510589 1 13 Sensor Sub-assy 390002060768 1 390002060768 1 14 Drain Hose Sub-Assy 007008000001 1 007008000001 1 15 Electric Box Assy 100002084482 1 100002084482 1 16 Main Board 300002064558 1 300002064558 1 17 Terminal Board 42200006005404 1 42200006005404 1 18 Terminal Board 4201110602 1 4201110602 1 Above data is subject to change without notice, please reference the SP in global service website. 123 GMV-ND15T/NhE-T(U) GMV-ND18T/NhE-T(U)
GREE Multi Variable Air Conditioners Indoor Unit 6.6 1-way Cassette Type Indoor Unit Exploded View of GMV-ND07TD/NhA-T(U); GMV-ND09TD/NhA-T(U); GMV-ND12TD/NhA-T(U) 1 2 3 4 5 6 7 8 9 GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) Model No. Part Name Part Code Qty. 1 Water Tray 26904100035 1 2 Evaporator Assy 011001063631 1 3 Cross Flow Fan 10454100001 1 4 Brushless DC Motor 1501214301 1 5 Refrigerant Sensor 340024060017 1 6 Hook 02112466 1 124 19 18 17 16 15 14 13 12 11 10
GREE Multi Variable Air Conditioners Indoor Unit Model No. Part Name Part Code Qty. 7 Remote Controller 30510589 1 8 Sensor Sub-assy 390002060770 1 9 Drain Hose 05232046 1 10 Liquid Level Switch 430024000005 1 11 Water Pump 81200706001601 1 12 Pump Drainpipe 26905288 1 13 Strainer 07213050 1 14 Electric expand valve fitting 43040001 1 15 Strainer 0721200102 4 16 Electric Box Assy 100002084624 1 17 Main Board 300002064551 1 18 Terminal Board 42200006005404 1 19 Terminal Board 42000100000102 1 Above data is subject to change without notice, please reference the SP in global service website. GMV-ND07TD/NhA-T(U) GMV-ND09TD/NhA-T(U) GMV-ND12TD/NhA-T(U) 125
GREE Multi Variable Air Conditioners Indoor Unit 6.7 Wall Mounted Type Indoor Unit Exploded View of GMV-ND06G/NhA1C-T(U),GMV-ND07G/NhA1C-T(U),GMV-ND09G/NhA1C-T(U), GMV-ND06G/NhA3C-T(U),GMV-ND07G/NhA3C-T(U),GMV-ND09G/NhA3C-T(U). Model No. Part Name Part Code Qty. 1 Front Panel 200003060356T 1 2 Filter Sub-Assy 1112246803 2 3 Front Case 200002060102 1 4 Evaporator Assy 011001063588 1 5 Electronic Expansion Valve 072009060064 1 6 Filter Sub-Assy 11120011 1 7 Electric Expand Valve Fitting 07200206001901 1 8 Guide Louver 200004060236 1 9 Stepping Motor 1521210712 1 10 Axile Bush 10542036 1 11 Electric Box Assy 100002084357 1 GMV-ND06G/NhA1C-T(U)、GMV-ND06G/NhA3C-T(U) GMV-ND07G/NhA1C-T(U)、GMV-ND07G/NhA3C-T(U) GMV-ND09G/NhA1C-T(U)、GMV-ND09G/NhA3C-T(U) 126
GREE Multi Variable Air Conditioners Indoor Unit Model No. Part Name Part Code Qty. 12 Terminal Board 4201026807 1 13 Main Board 300002064511 1 14 Display Board 300001061358 1 15 Right Side Plate 200086060076 1 16 Wall Mounting Frame 012043000008 1 17 Stepping Motor 1521210704 1 18 Brushless DC Motor 15010406011702 1 19 Gas Sensor 340024060017 1 20 Air Louver (Auto) 200007060117 1 21 Rear Grill Sub-Assy 209168000017 1 22 Air Louver(Right) 200007060110 1 23 Swing Lever 200035060044 1 24 Air Louver (Left)(Auto) 200007060111 1 25 Axile Bush Sub-Assy 10542047 1 26 Rear Grill Sub-Assy 209168000016 1 27 Left Side Plate 200085060070 1 28 Remote Controller 305001060060 1 29 Drainage Hose 05230014 1 GMV-ND06G/NhA1C-T(U)、GMV-ND06G/NhA3C-T(U) GMV-ND07G/NhA1C-T(U)、GMV-ND07G/NhA3C-T(U) GMV-ND09G/NhA1C-T(U)、GMV-ND09G/NhA3C-T(U) 127
GREE Multi Variable Air Conditioners Indoor Unit Exploded View of GMV-ND12G/NhA1C-T(U),GMV-ND14G/NhA1C-T(U), GMV-ND12G/NhA3C-T(U),GMV-ND14G/NhA3C-T(U). Model GMV-ND12G/NhA1C-T(U)、GMV-ND12G/NhA3C-T(U) GMV-ND14G/NhA1C-T(U)、GMV-ND14G/NhA3C-T(U) No. Part Name Part Code Qty. 1 Front Panel 200003060382T 1 2 Filter Sub-Assy 111001060404 2 3 Front Case 200002060099 1 4 Evaporator Assy 011001063589 1 5 Electronic Expansion Valve 072009060076 1 6 Filter Sub-Assy 11120011 1 7 Electric Expand Valve Fitting 07200206001901 1 8 Guide Louver 200004060235 1 9 Stepping Motor 1521240212 1 10 Axile Bush 10542036 1 11 Electric Box Assy 100002084358 1 12 Terminal Board 4201026807 1 13 Main Board 300002064511 1 14 Display Board 300001061358 1 128
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND12G/NhA1C-T(U)、GMV-ND12G/NhA3C-T(U) GMV-ND14G/NhA1C-T(U)、GMV-ND14G/NhA3C-T(U) No. Part Name Part Code Qty. 15 Right Side Plate 200086060074 1 16 Wall Mounting Frame 012043060024 1 17 Gas Sensor 340024060017 1 18 Brushless DC Motor 15010406008802 1 19 Stepping Motor 1521210704 1 20 Air Louver (Auto) 200007060116 1 21 Rear Grill Sub-Assy 209168000010 1 22 Air Louver(Right) 200007060115 1 23 Swing Lever 200035060043 1 24 Rear Grill Sub-Assy 209168000011 1 25 Air Louver (Left) 200007060114 1 26 Axile Bush Sub-Assy 1054204701 1 27 Left Side Plate 200085060068 1 28 Remote Controller 305001060060 1 29 Drainage Hose 05230014 1 129
GREE Multi Variable Air Conditioners Indoor Unit Exploded View of GMV-ND18G/NhA1C-T(U),GMV-ND24G/NhA1C-T(U), GMV-ND18G/NhA3C-T(U),GMV-ND24G/NhA3C-T(U). Model GMV-ND18G/NhA1C-T(U)、GMV-ND18G/NhA3C-T(U) GMV-ND24G/NhA1C-T(U)、GMV-ND24G/NhA3C-T(U) No. Part Name Part Code Qty. 1 Front Panel 200003060359T 1 2 Filter Sub-Assy 1101200703 2 3 Front Case 20000206010301 1 4 Evaporator Assy 011001063590 1 5 Electronic Expansion Valve 072009060076 1 6 Filter Sub-Assy 11120011 1 7 Electric Expand Valve Fitting 07200206001901 1 8 Stepping Motor 1521240210 1 9 Axile Bush 10542036 2 10 Electric Box Assy 100002084359 1 11 Terminal Board 4201026807 1 130
GREE Multi Variable Air Conditioners Indoor Unit Model GMV-ND18G/NhA1C-T(U)、GMV-ND18G/NhA3C-T(U) GMV-ND24G/NhA1C-T(U)、GMV-ND24G/NhA3C-T(U) No. Part Name Part Code Qty. 12 Main Board 300002064511 1 13 Display Board 300001061358 1 14 Right Side Plate 20008606007401 1 15 Wall Mounting Frame 012043060024 1 16 Stepping Motor 1521210704 1 17 Gas Sensor 340024060017 1 18 Brushless DC Motor 15010406011601 1 19 Air Louver 200007060103 1 20 Air Louver 1 200007060104 1 21 Air Louver 1 200007060101 2 22 Swing Lever 200035060042 1 23 Rear Grill Sub-Assy 209168000018 3 24 Axile Bush Sub-Assy 1054204701 1 25 Left Side Plate 20008506006801 1 26 Remote Controller 305001060060 1 27 Drainage Hose 0523001405 1 131
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI 519070 Add: West Jinji Rd, Qianshan Zhuhai, Guangdong, China Tel: (+86-756)8522218 Fax: (+86-756)8669426 E-mail: global@cn.gree.com www.gree.com JF00305743