Owner's Manual 

 Thank you for choosing Air Conditioners, please read this owner’s manual carefully before operation and 

retain it for future reference. If you have lost the Owner’s Manual, please contact the local agent or visit 
www.gree.com or sent email to global@gree.com.cn or electronic version. 
 GREE reserves the right to interpret this manual which will be subject to any change due to product 

improvement without further notice. 
 GREE Electric Appliances, Inc. of Zhuhai reserves the final right to interpret this manual.  

 
    
 
 
Ultra Heat GMV5 

User Manual 

Air Conditioners 

Applicable Models: 

GMV-48WL/B-T(U) 

GMV-36WL/B-T(U) 

Sayfa 3

Gree DC Inverter Multi VRF System, with the most advanced technologies in the world, uses eco-friendly 

refrigerant R410A as its cooling medium. For correct installation and operation, please read this manual 

carefully. Before reading the manual, please note that: 

(1) Multi VRF system conforms to design standard: ARI 210240-2008 

(2) To ensure safety when operating this system, please strictly follow the instructions in this manual. 

(3) The total capacity of running indoor units must not exceed that of the outdoor units. Otherwise, the 

cooling (heating) effect of each IDU would be poor. 

(4) Make sure that this manual is kept by direct operators and maintainers. 

(5) In case of malfunction, please examine the following items and contact our authorized service 

centers as soon as possible. 

1) Nameplate (model, cooling capacity, product code, ex-factory date) 

2) Malfunction status (detail description of conditions before and after malfunction occurs) 

(6) All units have been strictly tested and proved to be qualified before ex-factory. To avoid damage or 

operation failure which may be caused by improper disassembly, please do not disassemble units 

by yourself. If disassembly is needed, please contact our authorized service centers. 

(7) All graphics and information in this manual are only for reference. Manufacturer reserves the right for 

changes in terms of sales or production at any time and without prior notice. 
(8) Under the standby status, the unit will consume a little power for ensuring reliability of complete unit, 
maintaining normal communication and preheating refrigerant. When the unit won’t be used for a long time, 
cut off the power of the complete unit. However, please preheat it when operating the unit next time.  

Preface 

Sayfa 4

1 Safety Precautions .......................................................................................................................................... 1 

2  Product Introduction ...................................................................................................................................... 2 

2.1 Names of Main Parts .......................................................................................................................... 3 

2.2 Combinations of Indoor and Outdoor Units ........................................................................................ 3 

2.3 Operating Range ................................................................................................................................ 3 

3 Preparation before Installation ........................................................................................................................ 3 

3.1 Standard Parts .................................................................................................................................... 4 

3.2 Installation Site ................................................................................................................................... 4 

3.3 Piping Work Requirements ................................................................................................................. 5 

4  Installation Instruction ................................................................................................................................... 5 

4.1 Dimension of Outdoor Unit and Mounting Hole ................................................................................. 6 

4.2 Connection Pipe ................................................................................................................................. 7 

4.3 Installation of Connection Pipe .......................................................................................................... 11 

4.4 Disassembly of Compressor Feet .................................................................................................... 15 

4.5 Leak Test, Vacuum Pumping, Refrigerant Adding ............................................................................ 16 

4.6 Electric Wiring ................................................................................................................................... 20 

5 Check Items after Installation and Test Operation ........................................................................................ 24 

5.1 Check Items after Installation ........................................................................................................... 24 

5.2 Trial Run ........................................................................................................................................... 25 

6 
Common Malfunctions and Troubleshooting ............................................................................................ 26 

6.1 Check before Contacting Service Center ......................................................................................... 26 

6.2 Normal Phenomenon........................................................................................................................ 27 

6.3 Error Display ..................................................................................................................................... 28 

7 Maintenance and Care .................................................................................................................................. 30 

7.1 Outdoor Heat Exchanger .................................................................................................................. 30 

7.2 Drain Pipe ......................................................................................................................................... 30 

7.3 Notice before Seasonal Use ............................................................................................................. 30 

7.4 Maintenance after Seasonal Use ..................................................................................................... 31 

7.5 Parts Replacement ........................................................................................................................... 31 

8 After-sales Service......................................................................................................................................... 31 

Contents 

Sayfa 5

1 Safety Precautions 

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. 
Obey all safety messages that follow this symbol to avoid possible injury or death. 

This mark indicates procedures which, if improperly performed, might lead to the death or 
serious injury of the user. 

This mark indicates procedures which, if improperly performed, might possibly result in 
personal harm to the user, or damage to property. 

 
NOTICE is used to address practices not related to personal injury. 

(1) 
Instructions for installation and use of this product are provided by the manufacturer. 

(2) 
Installation must be performed in accordance with the requirements of NEC and CEC by authorized personnel 
only. 

(3) 
For operating the air conditioner pleasantly, install it as outlined in this installation manual.  

(4) 
Connect the indoor unit and outdoor unit with the room air conditioner piping and cord available from our 
standard parts. This installation manual describes the correct connections using the installation set available 
from our standard parts. 
(5) 
Before installation, check the power cord if it complies with the power supply requirement on the nameplate. 
Make sure the power supply is safe. 

(6) 
This air conditioner must be properly grounded through the receptacle to avoid electric shock. The ground wire 
shouldn’t be connected with gas pipe, water pipe, lightning arrester or telephone line. 

(7) 
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a 
flame, it produces toxic gas.  

(8) 
Do not power on until all installation work is complete.  

(9) 
During installation, make sure that the refrigerant pipe is attached firmly before you run the compressor. 
Do not operate the compressor under the condition of refrigerant piping not attached properly with gas pipe 
and liquid pipe valve open. 
This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. 
(10) During the pump-down operation, make sure that the compressor is turned off before you remove the 

refrigerant piping. 
This may cause abnormal pressure in the refrigerant cycle that leads to breakage and even injury. 
(11) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant 

(R410A) to enter the refrigerant cycle. 

(12) If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value 

and cause breakage, injury, etc. 

(13) This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental 

capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction 
concerning use of the appliance by a person responsible for their safety.  

(14) Children should be supervised to ensure that they do not play with the appliance.  

(15) If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified 

persons in order to avoid a hazard.  

(16) When installing, specialized parts and accessories must be used. Otherwise, it may result in water leakage, 

electric shock or fire hazard. 

(17) Diameter of power cord must be large enough. Damaged power cord or connecting wire must be replaced by 

specialized electric cable. 

(18) After the power cord is connected, please install the cover of electric box to avoid danger 

(19) Nitrogen must be charged according to technical requirements. 

(20) For units with wired controllers, do not connect power supply until the wired controller is well installed. 

Otherwise, the wired controller cannot be used. 

Ultra Heat GMV5 User Manual 

1 

Sayfa 6

Ultra Heat GMV5 User Manual 

(21) When installation is finished, please check and make sure the drain pipe, pipeline and electric wire are all well 

connected so as to avoid water leakage, refrigerant leakage, electric shock and fire hazard. 

(22) Do not extend fingers or objects into air outlet or return air grille. 

(23) If you use gas heater or petroleum heater in the same room, please open the door or window to maintain good 

air circulation, otherwise the room may be lack of oxygen. 

(24) Never start or stop the air conditioner by inserting or removing the power cord. 

(25) Do not turn off the air conditioner until it runs for at least 5 minutes. Otherwise, oil return of the compressor will 

be affected. 

(26) Children are not allowed to operate the air conditioner. 

(27) Do not operate the air conditioner with wet hands. 

(28) Please turn off and unplug your air conditioner before cleaning. Otherwise, it may cause electric shock or 

personal injury. 

(29) Do not spray water on the air conditioner or it will cause malfunction or electric shock. 

(30) Do not expose the air conditioner directly under damp or corrosive surroundings. 

(31) Connect power 8 hours before operation. Do not disconnect power when you want to stop the unit in a short 

period of time, e.g. in one night. (This is for protecting the compressor.) 

(32) Volatile liquid like thinner or gasoline will damage the appearance of air conditioner. (Please use soft dry cloth 

and wet cloth with mild detergent to clean unit’s outer case.) 

(33) Under cool mode, do not set the indoor temperature too low. Keep the difference between indoor temp and 

outdoor temp within 5℃(41℉). 

(34) If abnormal condition occurs (e.g. unpleasant smell), please turn off the unit at once and disconnect power 

supply. Then contact Gree authorized service center. If the air conditioner continues to operate despite of 
abnormal condition, it may be damaged and cause electric shock or fire hazard.) 

(35) Do not repair the air conditioner by yourself. Improper repair will cause electric shock or fire hazard. Please 

contact Gree authorized service center and ask professional technicians to repair it. 
(36) Gree Electric Appliances, Inc. of Zhuhai will not assume responsibility for any personal injury or property loss 

caused by improper installation, improper debugging, unnecessary repair or not following the instructions of 
this manual. 

2  Product Introduction 

Gree Multi VRF System adopts inverter compressor technology. By changing the 
displacement of compressor, stepless capacity regulation within range of 15%~100% 
can be realized. Various product lineups are provided with capacity range from 
36000Btu/h to 48000Btu/h, which can be widely used in residential, commercial and 
working area and especially applicable to places with big load change. Gree 
residential air conditioner is absolutely your best choice. 

2 

Sayfa 7

2.1 Names of Main Parts 

No. 

Name 
Motor 
Fan blade 
Electric box 

2.2 Combinations of Indoor and Outdoor Units 

(1)  See below the number of indoor units that can be connected to the outdoor unit. 

(2)  The total capacity of indoor units should be within 50%~100% of the outdoor unit. 

Model 
Min sets of connectable IDUs 
Max sets of connectable IDUs 

GMV-36WL/B-T(U) 
2 
5 

GMV-48WL/B-T(U) 
2 
6 

(3)  Outdoor units of DC Inverter Multi VRF System can be connected to various indoor 

units. When any one of the indoor units receives operating command, outdoor unit will 

start operation as per required capacity. When all indoor units stop, outdoor unit will be 

shut off.  

2.3 Operating Range 

Cooling 
Outdoor temperature: 10℃~54℃(50℉~129℉) 

Heating 
Outdoor temperature: -35℃~27℃(-31℉~81℉) 

3 Preparation before Installation 

NOTICE! Graphics here are only for reference. Please refer to actual products.  

Ultra Heat GMV5 User Manual 

 
GMV-36WL/B-T(U) 

GMV-48WL/B-T(U) 

Fig.1 

assembly 
Gas pipe valve 
Liquid pipe 

valve 

3 

Sayfa 8

Ultra Heat GMV5 User Manual 

3.1 Standard Parts 

Please use the supplied standard parts as required. 

No. 
Name 
Appearance 
Qty 
Remark 

1 
User Manual 

2 
Wiring (match 

with resistance) 
 

3 
Corrugated pipe 

4 
Drainage 
hole 

cap 
 
3 
 

5 
Drainage jiont 

3.2 Installation Site 

(1) The unit must be installed where strong enough to withstand the weight of the unit and fixed securely, otherwise 

the unit would topple or fall off.  

(2) Do not install where there is a danger of combustible gas leakage.  

(3) Do not install the unit near heat source, steam, or flammable gas.  

(4) Children under 10 years old must be supervised not to operate the unit.  

(5) Select a location which is out of children’s reach. Keep the unit away from children. 

(6) Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with 

good ventilation. 

(7) Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with 

good ventilation. 

(8) Install the unit where it will not be tilted by more than 5°. 

(9) During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed securely. 
 

Parts for Outdoor Unit 

1 
 

Must be connected to 

the last IDU of 

1 

communication 

connection 

1 
 

1 
 

4 

Sayfa 9

Ultra Heat GMV5 User Manual 

(1) 
If possible, do not install the unit where it will be exposed to direct sunlight. (If necessary, install a blind that 
does not interfere with the air flow.)  

(2) 
Install ODU in a place where it will be free from getting dirty or getting wet by rain as much as possible. 

(3) 
Install ODU where it is convenient to connect IDU.  

(4) 
ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and reduce bend 
angles. 

(5) 
Install ODU where the condensate water can be drained out freely during heating operation. Do not place 
animals and plants in the path of the warm air. 

(6) 
Take the air conditioner weight into account and select a place where noise and vibration are small 

If the ODU is totally surrounded by walls, please refer to the following figures for space dimension: 

Fig.2 

3.3 Piping Work Requirements  

Refer to the table below for piping work requirements: 

R410A Refrigerant System 

Outer diameter (mm/inch) 
Wall thickness(mm/ inch) 

Φ6.35(Φ1/4) 
≥0.8(1/32) 

Φ9.52(Φ3/8) 
≥0.8(1/32) 

Φ12.7(Φ1/2) 
≥0.8(1/32) 

Φ15.9(Φ5/8) 
≥1.0(1/25) 

Φ19.05(Φ3/4) 
≥1.0(1/25) 

4  Installation Instruction 

NOTICE! Graphics here are only for reference. Please refer to actual products.  

5 

Sayfa 10

Ultra Heat GMV5 User Manual 

4.1 Dimension of Outdoor Unit and Mounting Hole 

Unit Outline and Installation Dimension: 

Unit:mm(inch) 

Model 
A 
B 
C 
D 
E 

GMV-36WL/B-T(U) 
GMV-48WL/B-T(U) 

 
Fig.3 

900 
(35-3/8) 

340 
(13-3/8) 

1345 
(53) 

572 
(22-1/2) 

378 
(15) 

6 

Sayfa 11

4.2 Connection Pipe 

4.2.1 Schematic Diagram of Piping Connection 

ODU

Outdoor connection pipe

Branchs of IDUs

4.2.2 Allowable Length and Height Difference of Connection Pipe 

Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is 

shown in the figure below: 

NOTICE! Equivalent length of one Y-type branch is 0.5m(1-5/8feet). 

Ultra Heat GMV5 User Manual 

Gas pipe

Liquid pipe

Connection pipe between ODU and the first indoor branch

Connection pipe between indoor branch and IDUs

IDU 1

Connection pipe of indoor branchs

Connection pipe between indoor branch and IDUs

IDU 2

Connection pipe of indoor branchs

Connection pipe between indoor branch and IDUs

IDU 3

Branchs of IDUs

Fig.4 

7 

Sayfa 12

Ultra Heat GMV5 User Manual 

ODU

Height difference between IDU and ODU(H≤50m/164ft)

L1

a

The 1st
branch
section

IDU

Equivalent length to the farthest
connection pipe(L≤150m/492ft)
Equivalent length from the 1st branch

L2

to the farthest pipe(L<4om/131ft)

L3

b
c
d

IDU

IDU
IDU

Each Y-type branch equals to 0.5m(1-5/8ft) and each branch header equals to 1.0m(3-1/4ft).

 
Fig.5 Allowable Length and Height Difference of Connection Pipe 

Piping parameters of GMV-36WL/B-T(U) 、GMV-48WL/B-T(U): 

Allowable value 

Fitting pipe 
m 
feet 

Total length (actual length) of fitting pipe 
300 
984 
L1+L2+L3+a+b+c+d 

Actual length 
120 
394 
L1+L2+L3+d 
Equivalent length 
150 
492 

Length of farthest fitting pipe 

From the 1st branch to the farthest indoor pipe 
40 
131 
L2+L3+d 

ODU at upper 

side 
50 
164 
—— 

Height difference between ODU 

and IDU 

ODU at lower side 
40 
131 
—— 

Height difference between IDUs 
15 
49 
—— 

4.2.3 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch 

Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of 

outdoor connection pipe. 
 

8 

between IDUs(h≤15m/49ft)

Height difference

Sayfa 13

Dimension of outdoor connection pipe: 

Basic module 

GMV-36WL/B-T(U) 
φ15.9 
(φ5/8) 

GMV-48WL/B-T(U) 
φ15.9 
(φ5/8) 

4.2.4 Selection of Indoor Branches 

Select indoor branches according to the total capacity of downstream indoor units. if the 

capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

Refrigerant system 
Total capacity of downstream indoor units C (Btu/h) 
Model 

Y type branch 

Ultra Heat GMV5 User Manual 

 
Fig. 6 

Pipe dimension 

Liquid pipe 

Gas pipe 
(mm/inch) 

(mm/inch) 

φ9.52 
(φ3/8) 

φ9.52 
(φ3/8) 

 
Fig.7 

C< 68200 
FQ01A 

68200≤C≤102400 
FQ01B 

102400<C ≤238800 
FQ02 

238800<C ≤460600 
FQ03 

9 

Sayfa 14

Ultra Heat GMV5 User Manual 

4.2.5 Dimension of Pipe between Indoor Branches 

Select pipe between indoor branches according to the capacity of downstream indoor units; if 

the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

Total capacity of downstream indoor units  

C (Btu/h) 

C ≤19000 
Φ12.7 
(Φ1/2) 

19000<C≤48500 
Φ15.9 
(Φ5/8) 

48500<C≤76400 
Φ19.05 

4.2.6 Dimension of Pipe between Indoor Branch and IDU 

Dimension of pipe between indoor branch and IDU should be consistent with the dimension of 

indoor pipe. 

460600<C  
FQ04 

 
Fig.8 

Pipe 
(mm/inch) 

Liquid pipe 

(mm/inch) 

Φ6.35 
(Φ1/4) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

10 

Sayfa 15

 
Fig. 9 
 

Rated capacity of IDU 

C(Btu/h) 

C≤9600 
Φ9.52 
(Φ3/8) 

9600<C≤17000 
Φ12.7 
(Φ1/2) 

17000<C≤48000 
Φ15.9 
(Φ5/8) 

48000<C≤55000 
Φ19.05 

55000<C≤96000 
Φ22.2 
(Φ7/8) 

NOTICE! If the distance between IDU and its nearest branch is over 10m(33feet), then the 

liquid pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged. 

4.3 Installation of Connection Pipe 

(1) 
Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so 
is the height difference between indoor and outdoor units. Keep the number of bends as little as possible. 
Radius of curvature should be as large as possible. 

(2) 
Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for welding 
process. Rosin joint or pin hole is not allowed. 

(3) 
When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm(8inch). Note 
that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch 
the pipe for more than 3 times at the same position. 

4.3.1 Flaring Process 

(1)  Use pipe cutter to cut the connection pipe in case it is unshaped. 

(2)  Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs 

after cutting. 

Ultra Heat GMV5 User Manual 

Gas pipe 
(mm/inch) 

Liquid pipe 
 (mm/inch) 

Φ6.35 
(Φ1/4) 

Φ6.35 
(Φ1/4) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

Φ9.52 
(Φ3/8) 

11 

Sayfa 16

Ultra Heat GMV5 User Manual 

(3)  Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use 

flaring tool to fix the flared nut into the pipe (as shown in Fig.10). 

(4)  Check if the flared part is flaring evenly and if there is any crack. 

4.3.2 Pipe Bending 

(1)  Reshape the pipe by hand. Be careful not to damage the pipe. 

(2)  Do not bend the pipe over 90°. 

(3)  If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch 

again. Therefore, do not bend or stretch the bend for over 3 times. 

(4)  In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the 

insulating layer, as shown in Fig. 12. Do not bend the pipe until it is exposed. When 

bending is done, wrap the pipe with insulating layer and then secure it with adhesive 

tape. 

 
                    Fig. 11                                 Fig. 12 

Correct 
Wrong 

4.3.3 Indoor Pipe Connection 

(1)  Remove pipe cover and pipe plug. 

(2)  Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut 

tightly by hand, as in Fig. 13. (Make sure indoor pipe is correctly connected. Improper location of 

the center will prevent flared nut from being securely twisted. Thread of nut will get damaged if the 

flared nut is twisted forcibly.) 

(3)  Use torque wrench to twist on the flared nut tightly until the wrench gives out a click 

sound. (Hold the handle of wrench and make it at right angle to the pipe. as in Fig. 14) 

(1) 
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic tape. 

(2) 
Connection pipe should be supported by a bearer rather than the unit. 

(3) 
The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use a 
pipe bender to bend the pipe. 

(4) 
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case the 
capillary tube or other tubes have cracks and cause leakage. 

 
Fig. 10 

12 

Sayfa 17

 
                                     Fig. 13                     Fig. 14 

4.3.4 Outdoor Pipe Connection 

Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as 

for indoor pipe connection. 

 According to customer requirement or space limit, outlet pipe can be installed from the front, 

right or rear side. 

4.3.5 Installation of Y-type Branch 

(1)  Y-type Branch 

Ultra Heat GMV5 User Manual 

Pipe Diameter 
Tightening Torque 

6mm(1/4inch) 
15-30N·m(11-22ft.-1b.) 

9.5mm(3/8 inch) 
35-40N·m(26-29ft.-1b.) 

12.7mm(1/2 inch) 
45-50N·m(33-37ft.-1b.) 

16mm(5/8 inch) 
60-65N·m(44-48ft.-1b.) 

 
Fig. 15 

13 

Sayfa 18

Ultra Heat GMV5 User Manual 

to other branches or IDUs

Outlet 1

Y-type branch

Inlet

Field supplied

Outlet 2

Field supplied
ODU

 
Fig. 16 

 (2)  Y-type branch has several pipe sections with different dimension, which facilitates to 

match with various copper pipes. Use pipe cutter to cut in the middle of the pipe section that is of 

proper dimension and remove burrs as well. See Fig. 17. 

(3)  Y-type branch must be installed vertically or horizontally. 

Within ±30°

Cut in the middle

Within ±30°

 
Fig. 17 

Branch shall be isolated by insulating material that can bear 120℃(248℉)or even higher temperature. The 
attached foam of branch cannot be taken as insulating material. 

4.3.6 Thermal Insulation for Pipeline 

(1)  For multi VRF system, every copper pipe should be labeled so as to avoid 

misconnection. 

(2)  At the branch inlet, leave at least 500mm(19-3/4inch) straight pipe section. 

(3)  Thermal insulation for pipeline 

 1)  To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid 

pipe must be wrapped with thermal insulating material and adhesive tape for insulation 

from the air. 

 3)  Joints of indoor and outdoor unit should be wrapped with insulating material and leave 

no gap between pipe and wall. See Fig. 18. 

14 

Sayfa 19

Ultra Heat GMV5 User Manual 

Thermal insulating layer is required to be wrapped a

Thermal insulatin

No gap

 
Fig. 18 

 5)  When wrapping the tape, the later circle should cover half of the former one. Don’t wrap 

the rape too tight, otherwise the insulation effect will be weakened. 

 6)  After wrapping the pipe, apply sealing material to completely seal the hole on the wall. 

(1) 
Thermal insulating material shall be able bear the pipe temperature. For heat pump unit, liquid pipe should 
bear 70℃(158℉) or above and gas pipe should bear 120℃(248℉) or above. For cooling only unit, both liquid 
pipe and gas pipe should bear 70℃(158℉) or above. 

(2) 
Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of 
branches cannot be taken as insulating material. 

4.3.7 Support and Protection of Pipeline 

(1) 
Support should be made for hanging connection pipe. Distance between each support cannot be over 
1m(3-1/4feet). 
(2) 
Protection against accidental damage should be made for outdoor pipeline. When pipeline exceeds 
1m(3-1/4feet), a pinch board should be added for protection. 

4.4 Disassembly of Compressor Feet 

In order to prevent unit from damage during transportation, 2 metal pieces are fitted to 

outdoor unit’s compressor feet before unit leaves factory. See Fig. 19. 

Compressor

Binding nut

Metal pieces

Fasten the nut after removal
Metal pieces

 
Fig. 19 

When installing the unit, metal pieces for transportation must be removed. Then fasten the 

binding nuts again and wrap back soundproofing cotton.If unit runs with metal pieces fitting on, 

15 

Sayfa 20

Ultra Heat GMV5 User Manual 

compressor will shake abnormally and unit’s operating life will be shortened. 

4.5 Leak Test, Vacuum Pumping, Refrigerant Adding

4.5.1 Leak Test 

(1) Please make sure that the stop valves of the outdoor unit are closed during the operation. 

(2) The leak test should be made by pressurizing nitrogen gas. 

(3) Turn on the Hi-knob and Lo-knob. The leak test should be done simultaneously at both the 

gas and liquid stop valves. 

(4) Open the pressure reducing valve, pressurize the connection pipes to 1.0 MPa (10 bar) slowly, 

wait fifteen minutes, and make sure that the pressure will not drop. 

(5) Rise the pressure to 4.0 MPa (40 bar) slowly, wait 24 hours, and make sure the pressure will 

not drop. 

(6) If the pressure does not decrease, the pipes have passed the test. Otherwise, look for where 

the gas leaks from. 

NO. 
1 
2 
3 
4 

Name Outdoor unit Gas side stop valve 
Liquid side stop valve 
Pressure-vacuum gauge 

NO. 
5 
6 
7 
8 

Name 
Hi-knob 
Lo-knob 
Pressure reducing valve 
Nitrogen 

Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra 
refrigerant in the outdoor unit for air purging!  

4.5.2 Vacuum Pumping 

(1) Make sure that the stop valves of the outdoor unit are closed fully during the operation. 
(2) As shown in the following figure Fig.21, expel the gas from the refrigerant pipes by the 

vacuum pump. 
(3) Open the pump and turn on the knobs to evacuate the gas in the liquid and gas pipes. 

The vacuuming should be done simultaneously at both the gas and liquid stop valves. 

 
Fig.20 

16 

Sayfa 21

(4) When the pressure of the system is less than -0.1Mpa (-1bar), keep the system for more 

than one hour under the condition. 

NO. 
1 
2 
3 
4 

Name Outdoor unit Gas side stop valve Liquid side stop valve Pressure-vacuum gauge 

NO. 
5 
6 
7 
 

Name 
Hi-knob 
Lo-knob 
Vacuum pump 
 

 
(5) Turn off the knobs firstly and then the pump. If the pressure of the pressure-vacuum 

gauge does not rise within 2 hours, the system is under a vacuum. Otherwise, the system 

has leaked, please look for where the gas leaks in. 
 

4.5.3 Refrigerant Adding 

(1)  Refrigerant quantity of outdoor unit before delivery: 

Model 
GMV-36WL/B-T(U) 
GMV-48WL/B-T(U) 

Refrigerant Qty (kg/oz) 
6.5 
(229) 

(1) The refrigerant amount charged before delivery doesn’t include the amount that needs to be 

added to indoor units and the connection pipeline. 
(2) Length of connection pipe is decided on site. Therefore the amount of additional refrigerant 

shall be decided on site according to the dimension and length of field-installed liquid pipe. 
(3) Record the amount of additional refrigerant for convenience of after-sales service. 

Ultra Heat GMV5 User Manual 

 
Fig. 21 

6.5 
(229) 

17 

Sayfa 22

Ultra Heat GMV5 User Manual 

NO. 
1 
2 
3 
4 

Name 
Outdoor unit 
Gas side stop valve Liquid side stop valve Pressure-vacuum gauge 

NO. 
5 
6 
7 
8 

Name 
Hi-knob 
Lo-knob 
R410A tank 
Scale 
Procedures for adding refrigerant 
1) 
When the liquid and gas stop valves have not been opened, the system is under the vacuum: 
① Refer to Fig. 22 (a); connect the R410A tank to the system. 
② Turn on the R410A tank and the Hi-knob; charge the R410A refrigerant into the unit from the 

liquid side stop valve. The Lo-knob should be closed completely. 
③ Turn off the R410A tank and the Hi-knob immediately, when the adding refrigerant is enough. 
④ Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and 

completely. 
2) 
If the pressure of the system is too high to charge refrigerant, you can do as follow after the 
trial run. 
① Turn off all indoor units, then turn off power after the compressor and fans stop; 
② After turn off power 5 min, refer to the right of the Fig. 22 (b) connect the R410A tank to the 

system, keep the R410A tank and the Lo-knob closing; 
③ Turn on the power of the air conditioner, and set cooling mode, running more than 20min; 
④ Turn on the R410A tank and the Lo-knob; charge the R410A refrigerant into the unit from the 

gas side stop valve. 
⑤ Turn off the R410A tank and the Lo-knob immediately when adding refrigerant is enough.  

------------------------------------------------------------------------------------------------------------------------- 

Caution! 
◆ Make sure the liquid and gas side stop valves are opened completely after the installation. 
◆ Make sure the length of liquid pipe is exactly. 
◆ Additional refrigerant charge must be measured exactly. 
◆ Make sure that the refrigerant which charge into the unit is in liquid state. 
◆ Please prevent the refrigerant leakage from your body when remove the charging hose. 
◆ Please heat the refrigerant tank with hot water or hot air when the outside temperature is too 

low. However, it must be forbidden to heat with fire directly, otherwise it may lead to 
explosion. 
------------------------------------------------------------------------------------------------------------------------- 

(2)  Calculation of the amount of additional refrigerant 

Calculation method of the quantity of additional refrigerant (based on liquid pipe) 

Quantity of additional refrigerant = ∑length of liquid pipe X quantity of additional refrigerant per 

meter(39-3/8inch) 

(a)                                  (b) 

Fig. 22 

18 

Sayfa 23

Ultra Heat GMV5 User Manual 

Diameter of 

Φ22.2 
(Φ7/8) 

Φ19.05 

Φ15.9 
(Φ5/8) 

Φ12.7 
(Φ1/2) 

Φ9.52 
(Φ3/8) 

Φ6.35 
(Φ1/4) 

liquid pipe 
(mm/inch) 

(Φ3/4) 

kg/m 
0.35 
0.25 
0.17 
0.11 
0.054 
0.022 

oz/inch 
0.314 
0.224 
0.152 
0.099 
0.048 
0.020 

NOTICE! Liquid pipe that is within 20m(65-5/8feet) doesn’t need to be added with 

refrigerant. 

First confirm that there is no leakage from the system. When compressor is not working, 

charge additional R410a with specific amount to the unit through the filling opening of the liquid 

pipe valve of the outdoor unit. If required amount cannot be quickly filled due to pressure increase 

of the pipe, then set the unit in cooling startup and fill refrigerant from the low pressure check valve 

of the outdoor unit.  

(3)  Calculation example 

ODU

D
C
B
A

d
c
b
a

IDU

④
③
②
①

 
Fig. 23 

IDU 

No. 
IDU ① 
IDU ② 
IDU ③ 
IDU ④ 

Model 
Duct type 
GMV-ND18PLS/A-T(U) 

Duct type 
GMV-ND12PLS/A-T(U) 

Duct type 
GMV-ND09PLS/A-T(U) 

Duct type 
GMV-ND09PLS/A-T(U) 

Liquid pipe: 

No. 
A 
B 
C 
D 

Pipe size 
φ9.52mm 
(φ3/8inch) 

φ9.52mm 
(φ3/8inch) 

φ9.52mm 
(φ3/8inch) 

φ6.35mm 
(φ1/4inch) 

Length 
10m 
(32-3/4feet) 

5m 
(16-3/8feet) 

5m 
(16-3/8feet) 

5m 
(16-3/8feet) 

No. 
a 
b 
c 
d 

Pipe size 
φ9.52mm 
(φ3/8inch) 

φ6.35mm 
(φ1/4inch) 

φ6.35mm 
(φ1/4inch) 

φ6.35mm 
(φ1/4inch) 

Length 
3m 
(9-3/4feet) 

3m 
(9-3/4feet) 

2m 
(6-5/8feet) 

1m 
(3-1/4feet) 

Total length of each liquid pipe 

φ9.52:A+B+C+a=10+5+5+3=23m(75-1/2 feet) 

19 

Sayfa 24

Ultra Heat GMV5 User Manual 

φ6.35: D+b+c+d=5+3+2+1=11m(36feet) 

NOTICE! Liquid pipe that is within 20m(65-5/8 feet) doesn’t need to be added with 

refrigerant. 

Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022=

0.404kg(14oz) 

4.6 Electric Wiring 

(1) 
All electrical installation must be performed by qualified technicians in accordance with local laws, regulations 
and this user manual. 

(2) 
Use air conditioner specialized power supply and make sure that it is consistent with system’s rated voltage.  

(3) 
Do not pull the power cord with force. 

(4) 
Caliber of the power cord must be large enough. A damaged power cord or connection wire must be replaced 
by specialized electrical cords. 

(5) 
Connect the unit to specialized grounding device and make sure it is securely grounded. It’s a must to install air 
switch and current circuit breaker that can cut off the power of the entire system. The air switch should include 
magnetic trip function and thermal trip function so that system can be protected from short circuit and overload. 

(6) 
Air conditioner belongs to class I electrical appliance, so it must be securely grounded. 

(7) 
The yellow-green wire inside the unit is a ground wire. Do not cut it off or secure it with tapping screws, 
otherwise it will lead to electric shock. 
(8) 
Power supply must include secure grounding terminal. Do not connect the ground wire to the following: 
①Water pipe; ②Gas pipe; ③Drain pipe; ④Other places that are deemed as not secure by professional 
technicians. 

4.6.1 Electrical Wiring 

(1). For solid core wiring (Fig.24) 

1). Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation about 

25mm (15/16inch) . 

2). Using a screwdriver, remove the terminal screw(s) on the terminal board. 

3). Using pliers, bend the solid wire to form a loop suitable for the terminal screw. 

4). Shape the loop wire properly, place it on the terminal board and tighten securely with 

the terminal screw using a screwdriver. 

(2). For strand wiring  (Fig. 24) 

1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation 

about 10mm (3/8inch) . 

2) Using a screwdriver, remove the terminal screw (s) on the terminal board. 

3) Using a round terminal fastener or pliers, securely clamp a round terminal to each 

stripped wire end. 

4) Position the round terminal wire, and replace and tighten the terminal screw with a 

screwdriver.(Fig. 25) 

20 

Sayfa 25

(3). How to fix connection cord and power cord by cord clamp 

After passing the connection cord and power cord through the insulation tube, fasten it with the 

cord clamp.(Fig. 26) 

(1) 
Before starting work, check that power is not being supplied to the indoor unit and outdoor unit. 

(2) 
Match the terminal block numbers and connection cord colors with those of the indoor unit side. 
Erroneous wiring may cause burning of the electric parts. 

(3) 
Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.  

(4) 
Always fasten the outside covering of the connection cord with cord clamps. (If the insulator is not clamped, 
electric leakage may occur.) 

(5) 
Always connect the ground wire. 

4.6.2 Wiring Diagram 

(1) Connection of power cord and communication wire 

Separate power supply for IDU and ODU  

NOTICE! The remote monitor can be installed when it is necessary. The wire (match 
with resistance) must be connected with ODU (see Fig. 27a and b) only the remote 
monitor is installed.  

Ultra Heat GMV5 User Manual 

Fig. 24 

Fig. 25                                    Fig. 26 

21 

Sayfa 26

Ultra Heat GMV5 User Manual 

 
  Fig.27 a Connection of power cord and communication wire for IDU and one ODU 

 
  Fig.27 b Connection of power cord and communication wire for IDU and multi ODUs 

NOTICE! : ODU n(Max)=16.The wire (match with resistance) must be connected with 

the last ODU. 

(2) The wiring diagram for power cord of outdoor unit and communication wire.  

22 

Sayfa 27

 
Fig.28 
Wiring of the Power Cord 

(1) Open the side plate. 

(2) Connect the power cord to the terminals “L1”, “L2” and also the earthing screw, and then 

connect the communication line “D1,D2” of the indoor unit to those of the outdoor unit 

correspondingly. The communication line “G1, G2” could be used to connect the remote 

monitor. Please use the bonding screw to connect the earthing cord. The location is showing 

in the Fig.28. 

(3) Fix the power cord and communication line with wire clips. 

(4) Let the power cord and communication line go through the rubber ring. 

(3) Selection of air switch and power cord: 

Model 
Power supply 

GMV-36WL/B-T(U) 
208/230V~ 60Hz 
50 
50 
45 

GMV-48WL/B- T(U) 
208/230V~ 60Hz 
50 
50 
45 

(1) 
Selection of circuit breaker and power cord in the above table is based upon unit’s maximum power 

(maximum current). 

(2) 
Specification of power cord is based on the working condition where ambient temperature is 40℃(104℉) and 

multi-core copper cable (working temperature is 90℃(194℉), e.g. power cable with YJV cross-linked copper, 

insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes, please adjust the 

specification according to national standard. 

(3) 
Specification of circuit breaker is based on the working condition where ambient temperature of circuit 

Ultra Heat GMV5 User Manual 

Max Fuse 
Size/Fusible Max. 

Max Ckt, Bkr 
Size/Disjoncteur 

Min. Circuit Ampacity 

(A) 

(A) 

Max. (A) 

23 

Sayfa 28

Ultra Heat GMV5 User Manual 

breaker is 40℃(104℉). If working condition changes, please adjust the specification according to national 

standard. 

5 Check Items after Installation and Test Operation 

5.1 Check Items after Installation 

Check Items 
Conditions Might Happen 
Check 

Has the unit been fixed firmly? 
The unit may drop, shake or emit noise. 
 

Has the gas leakage be checked? 

Does the unit get proper thermal 

insulation? 

Does the unit drain well? 
It may cause condensation and dripping. 
 

Is the voltage in accordance with the 

related voltage specified on the 

nameplate? 

Is the electric wiring and piping 

connection installed correctly and 

securely?  

Has the unit been earthed securely? 
It may cause electrical leakage. 
 

Is the power cord specified? 
It may cause malfunction or damage the part. 
 

Has the inlet and outlet been 

clogged? 

Has the pipe length and refrigerant 

charging amount been recorded? 

Is the communication line 

connection installed correctly? 

Is the piping connection and valves 

states installed correctly?  

It may cause insufficient cooling/heating 

capacity.  

It may cause condensation and dripping. 
 

It may cause malfunction or damage the part. 
 

It may cause malfunction or damage the part. 

It may cause insufficient cooling/heating 

capacity. 

The refrigerant charging amount is not 

accurate. 

It causes communication malfunction the part. 
 

It may cause malfunction or damage the part. 
 

24 

Sayfa 29

5.2 Trial Run 

5.2.1 Check before Trial Running, Must Preheat Compressor 

5.2.2 Trial Run 

 
5.2.2.1 Notices 

(1) Before the trial running, make sure the unit is power on and compressor has been preheated 

Ultra Heat GMV5 User Manual 

 
Fig.29 

25 

Sayfa 30

Ultra Heat GMV5 User Manual 

for more than six hours. Touch the unit to check whether it’s normally preheated. Start test 

operation after unit is normally preheated, otherwise compressor might be damaged. 

(2) Before the trial running, make sure the needed amount of refrigerant has been added to the 

pipe or at least 70% of the needed refrigerant has been added. 

(3) During the trial running, system will operate according to the ambient temperature. 

1) When outdoor temperature is above 20℃(68℉), debugging shall be in cooling mode. 

2) When outdoor temperature is below 20℃(68℉), debugging shall be in heating mode. 

5.2.2.2 Trial Run 

(1)  The trial run should be carried out by the professionally skilled personnel on the premise that 

all items listed above are in normal conditions. 

(2)  Let the unit energized and switch the wired controller or the remoter controller to “ON”. 

(3)  The fan motor and compressor of the outdoor unit will run automatically in three minutes. 

(4)  If there is some unusual so started, turn off the unit for an immediate check. 

Before restarting the unit, make sure the compressor has been preheated for more than 6 

hours. 

6 Common Malfunctions and Troubleshooting 

(1) In the event of abnormal conditions (like, stinky smell), please shut off the main power supply immediately and 

then contact the GREE appointed service center; otherwise the continuous abnormal running would damage 

the air conditioning unit and also would cause electric shock or fire hazard etc. 

(2) Do not repair the air conditioning personally but instead contact the professionally skilled personnel at the 

Gree appointed service center, as the incorrect repair would cause electric shock or fire hazard etc. 

6.1 Check before Contacting Service Center 

Conditions 
Causes 
Corrective Actions 

Broken fuse or opened breaker. 
Change the fuse or close the breaker. 

Power off. 
Restart the unit when power on. 

Power supply plug is loose. 
Plug the power supply properly. 

The unit does not 

Insufficient 
energy 
of 
remote 

run 

controller. 

Remote controller out of the control 

scope. 

The unit stops soon Clogged 
air 
intake/outlet 
of Clear the obstacle. 

Change new battery. 

Keep the control distance within 8 

meters  

26 

Sayfa 31

after it starts 
indoor/outdoor unit. 

Clogged 
air 
intake/outlet 
of 

indoor/outdoor unit. 

Improper temperature setting. 

Too low set of fan speed. 

Abnormal cooling or 

Incorrect airflow direction 

heating 

Opened door or window. 
Close the door or window. 

Direct sunlight. 

Too much people in the room. 
 

Too much heat sources in the room. Reduce heat sources. 

Dirty filter screen. 
Clean the filter screen. 

Note:  

If problem cannot be solved after the above check, please contact Gree appointed service 

center and also give a description of the error occurred as well as the model of the unit.  

6.2 Normal Phenomenon 

Conditions 
Causes 

When restarting the unit soon after it is 

stopped. 
The overload protection switch makes 

the startup delay for 2 minutes. 
As soon as press the “Temperature 

The unit does not run 

Set” button. 

The moment the unit is powered on. 

The unit blows out 

When the cooling operation starts. 

mist 

The unit “buzzes” as soon as it starts 

The unit generates 

running. 

noise 

The unit “swishes” during the cooling 

operation. 

Ultra Heat GMV5 User Manual 

Clear the obstacle. 

Adjust the setting of wireless remote 

controller or wired controller. 

Adjust the setting of wireless remote 

controller or wired controller. 

Adjust setting at wireless remote 

controller or wired controller 

Hang a curtain or blinds over the 

window.  

The unit will stand by for approximate 

one minute. 

The hi-humidity air indoor is cooled 

quickly. 

It is the sound generated during the 

initialization of the electronic expansion 

valve. 

It is the sound when the refrigerant gas 

runs inside the unit. 

27 

Sayfa 32

Ultra Heat GMV5 User Manual 

The unit “swishes” when it is started or 

stopped. 

The unit “swishes” when it is in and 

after the running. 

The unit “squeaks” when it is in and 

after the running. 

The unit blows out 

When the unit restarts after it is not 

dust. 

used for a long time. 

The unit emits odors. 
When the unit is running. 

6.3 Error Display 

6.3.1 Error Code of Protection 

Error Item 
Code 
Indoor Unit 

Indoor fan protection 
L1 
L1 
L1 

Water overflow protection 
L3 
L3 
L3 

Anti-freeze protection 
L5 
L5 
L5 

Mode conflict 
L6 
- 
L6 

Indoor ambient temperature sensor error 
d3 
d3 
d3 

Indoor coil inlet temperature sensor error 
d4 
d4 
d4 

Indoor mid-coil temperature sensor error 
d5 
d5 
d5 

Indoor coil outlet temperature sensor error 
d6 
d6 
d6 

Indoor humidity sensor error 
d7 
d7 
d7 

Jumper error 
d9 
d9 
d9 

Outdoor ambient temperature sensor error 
b1 
b1 
b1 

Outdoor heat-exchanger coil outlet 
temperature sensor error 
b3 
b3 
b3 

Vapor-liquid separator inlet temperature 
sensor error 
b6 
b6 
b6 

High pressure protection 
E1 
E1 
E1 

Low pressure protection 
E3 
E3 
E3 

Discharge protection 
E4 
E4 
E4 

Refrigerant-lacking protection 
Ed 
E0 
Ed 

Compressor power protection 
EN 
E0 
EN 

Intermediate vapor injection temperature 
sensor error 
Fb 
E0 
Fb 

It is the sound when the refrigerant gas 

stops running. 

It is the sound when the draining 

system is operating. 

It is the sound of frication generated by 

the skin plate etc which swells due to 

the temperature change. 

The dust inside the unit is blown out 

again  

The odors absorbed in are blown out 

again.  

Outdoor Unit 

Display 

Display 

28 

Sayfa 33

EEPROM read-write error 
F0 
F0 
F0 

High pressure sensor error 
F1 
F1 
F1 

Middle pressure sensor error 
F2 
E0 
F2 

Low pressure sensor error 
F3 
F3 
F3 

Discharge temperature sensor error 
F6 
F6 
F6 

High pressure switch 
Fd 
E0 
Fd 

AC over current 
P5 
P0 
P5 

IPM over current protection 
P6 
E0 
P6 

IPM module overheat 
P8 
P0 
P8 

Desynchronizing protection 
P9 
P0 
P9 

Busbar over voltage protection 
PH 
P0 
PH 

Phase current detection fault 
PC 
P0 
PC 

Busbar under voltage protection 
PL 
P0 
PL 

Capacitor charge error 
PF 
P0 
PF 

Demagnetization protection 
PU 
P0 
PU 

Communication error between indoor and 
outdoor units, indoor unit’s wired controller 
C0 
C0 
C0 

485 communication error between main 
controller and drive controller 
C2 
C2 
C2 

Fan motor error 
H0 
H0 
H0 

PFC over current protection 
P4 
E0 
P4 

PFC module overheat 
Pn 
P0 
Pn 

Phase loss protection of compressor 
PE 
P0 
PE 

Malfunction of lack of IDU 
C4 
C4 
C4 

485 communication error between main 
controller and debugging controller 
C1 
- 
C1 

6.3.2 Error Code of Limiting Frequency Reduction Protection  

Limited frequency reduction for high pressure protection 
FA 

Limited frequency reduction for low pressure protection 
FH 

Limited frequency reduction for discharge temperature 

protection 

Limited frequency reduction for AC current protection 
F8 

Limited frequency reduction for power protection 
FC 

Limited frequency reduction for IPM temperature protection 
FL 

Limited frequency reduction for PFC temperature protection 
FE 

Ultra Heat GMV5 User Manual 

Error Item 
Code 
Display 

F9 

Only the outdoor 

unit displays the 

code 

29 

Sayfa 34

Ultra Heat GMV5 User Manual 

6.3.3 Operation Code 

Operation 
Code 
Indoor Unit Display 
Outdoor Unit Display 

Trail run 
A0 
A0 
A0 

Fluorine recycle 
A2 
A2 
A2 

Defrosting 
A3 
A3 
A3 

Oil return 
A4 
- 
A4 

Testing online 
A5 
A3 
A4 

Vacuumization 
A8 
A8 
- 

Test module 
SS 
- 
SS 

Note: Last ten records of protection shutdown or limited frequency reduction for protection 

can be searched through the debugging controller. 

7 Maintenance and Care 

Regular check, maintenance and care can extend unit’s service life. Please have specialized 

person in charge of the management of air conditioners. 

7.1 Outdoor Heat Exchanger 

 Outdoor heat exchanger shall be cleaned regularly, which is at least once every two months. 

You can use a dust catcher with nylon brush to clean away the dust on the heat exchanger. If 

compressed air source is available, it also can be used to clean the heat exchanger. Do not clean 

it with water. 

7.2 Drain Pipe 

Please check regularly whether drain pipe is blocked or not. Make sure condensate can be 

drained out smoothly. 

7.3 Notice before Seasonal Use 

(1)  Check whether air inlets and air outlets of indoor and outdoor units are blocked; 

(2)  Check whether ground connection is reliable or not; 

(3)  Check whether batteries in the remote controller are replaced or not; 

(4)  Check whether air filter is properly installed; 

(5)  If unit starts up after not operating for a long time, it should be power on 8 hours before 

operation starts so as to preheat the outdoor compressor; 

(6)  Check whether outdoor unit is securely installed. If there is any problem, please contact 

Gree authorized service center. 

30 

Sayfa 35

7.4 Maintenance after Seasonal Use 

(1)  Disconnect power of the entire system; 

(2)  Clean the air filter and outer case of indoor and outdoor units; 

(3)  Clean away the dust and obstacles on indoor and outdoor units; 

(4)  If outdoor unit has rust, please apply some paint to it so as to prevent the rust from 

growing. 

7.5 Parts Replacement  

Parts and components can be obtained from nearby Gree office or Gree distributor. 

 
When you are conducting air tightness test and leakage test, do not mix oxygen, C2H2 or other dangerous gas into 
the refrigerant circuit. Otherwise, it may lead to danger. Use nitrogen or refrigerant to conduct the tests. 

8 After-sales Service 

     If there’s quality defect or other problems in the product, please contact Gree local 

after-sales service department for help. 

Warranty must be based on the following conditions: 

(1)Product’s initial startup must be performed by professional technicians from Gree service center 

or persons assigned by Gree. 

(2)Only Gree spare parts are used, 

(3)All instructions of unit operation and maintenance in this manual must be strictly followed 

according to set period and set frequency. 

(4)Any breach of the above conditions will disable the warranty. 

Ultra Heat GMV5 User Manual 

31 

Sayfa 36

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI 

Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070 
Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 
E-mail: gree@gree.com.cn www.gree.com