Sayfa 1

Ultra Heat GMV Multi VRF for 
North America

R410A(GC201603-1 )

Sayfa 2

PRODUCT .....................................................................................................2

1 PRODUCT  LIST ..............................................................................................................................2
2 NOMENCLATURE ............................................................................................................................3
3 PRODUCT FEATURES.....................................................................................................................4
4 SPECIFICATIONS.............................................................................................................................5
5 CAPACITY CODE ...........................................................................................................................10
6 PRINCIPAL OF OPERATION.......................................................................................................... 11
CONTROL....................................................................................................13

1 Units’ Control...................................................................................................................................14
2  Wired Controller .............................................................................................................................15
3 Remote Controller ...........................................................................................................................34

INSTALLATION............................................................................................36

1 Engineering Installation Preparation and Notice.............................................................................37
2 Installation Materials Selection........................................................................................................37
3 Installation of outdoor unit ...............................................................................................................39
4 Installation of indoor Unit
..............................................................................................................40
5 Installation of Electronic Expansion Valve Assy (unit with external EXV)........................................43
6 Installation of Refrigerant Pipeline ..................................................................................................44
7  Installation of the Connection Pipe.................................................................................................47
8 Installation of Condensate Pipes.....................................................................................................52
9 Electric Wiring .................................................................................................................................54
10 Debugging of Unit .........................................................................................................................58

MAINTENANCE .............................................................................................66

1 Malfunction List ..............................................................................................................................67
2 Troubleshooting ..............................................................................................................................69
3 Power Distribution of Unit................................................................................................................73
4 Removal of Parts.............................................................................................................................76
5 Vacuum drying for the system. ........................... .............. .............................................................89
6 Exploded View of Unit and Parts’ List .......... ................................................................................. 92

CONTENTS

Sayfa 3

PRODUCT

       Ultra Heat GMV Multi VRF 

for North America

1

PRODUCT

Sayfa 4

Ultra Heat GMV Multi VRF 

for North America

PRODUCT
1 PRODUCT  LIST 
1.1 Outdoor Unit

Cooling Capacity
Heating Capacity
Power
Supply
Refrigerant
Appearance

Model
Product

 Code

Kw(Btu/h)
Kw(Btu/h)

GMV-36WL/B-T(U)
CN850W0380
10.5
 (36000)

13.2
(45000)
208/230V
~
60Hz
R410A

GMV-48WL/B-T(U)
CN850W0360
14.1
(48000)

15.8
(54000)

1.2 Indoor Unit
1.2.1 Low static pressure duct

Cooling Capacity
Heating Capacity
Power
Supply
Refrigerant
 Appearance
kW(Btu/h)
kW(Btu/h)

Model
Product

 Code

GMV-ND07PLS/

A-T(U)
CM810N0080
2.2
(7500)

2.5
(8500)

GMV-ND09PLS/

3.1
(10500)
GMV-ND12PLS/

A-T(U)
CM810N0090
2.8
(9500)

4.0
(13500)
GMV-ND14PLS/

A-T(U)
CM810N0100
3.5
(12000)

208/230V
~
60Hz
R410a

4.5
(15500)
GMV-ND18PLS/

A-T(U)
CM810N0120
4.0
(13800)

5.2
(20000)
GMV-ND22PLS/

A-T(U)
CM810N0070
5.2
(18000)

7.1
(24000)
1.2.2 Four-way Cassette

A-T(U)
CM810N0110
6.3
(22000)

Cooling Capacity
Heating Capacity
Power
Supply
Refrigerant
Appearance
kW
(Btu/h)

Model
Product

kW
(Btu/h)
GMV-ND07T/

 Code

A-T(U)
CM500N0520
2.2
(7500)

2.5
(8500)

GMV-ND09T/

3.1
(10500)
GMV-ND12T/

A-T(U)
CM500N0530
2.8
(9500)

4.0
(13500)
GMV-ND15T/

A-T(U)
CM500N0540
3.5
(12000)

5
(17000)
GMV-ND18T/

A-T(U)
CM810N0130
4.4
(15000)

5.9
(20000)
GMV-ND24T/

A-T(U)
CM500N0510
5.3
(18000)

208/230V
~
60Hz
R410a

7.9
(27000)
GMV-ND30T/

A-T(U)
CM500N0550
7.0
(24000)

10
(34000)
GMV-ND36T/

A-T(U)
CM500N0560
8.8
(30000)

11.7
(40000)
GMV-ND42T/

A-T(U)
CM500N0570
10.6
(36000)

13.8
(47000)
GMV-ND48T/

A-T(U)
CM500N0580
12.3
(42000)

A-T(U)
CM500N0590
14.1
(48000)

15.8
(54000)

2

PRODUCT

Sayfa 5

      Ultra Heat GMV Multi VRF 

for North America

1.2.3 Wall Mounted Type IDU

Cooling Capacity
Heating Capacity
Power
Supply

 Model
Product

Power
Supply
 Appearance
kW
(Btu/h)

kW
(Btu/h)
GMV-N07G/A3A-

 Code

D(U)
CM100N1480
2.2
(7500)

2.5
(8500)

GMV-N09G/A3A-

D(U)
CM100N1490
2.8
(9500)

3.2
(11000)

208/230V
~
60Hz
R410a

GMV-N12G/A3A-

D(U)
CM100N1500
3.5
(12000)

4.0
(13500)

GMV-N18G/A3A-

D(U)
CM100N1510
5.2
(18000)

5.8
(20000)

7.5
(25500)
2 NOMENCLATURE
2.1Nomenclature of outdoor units

GMV-N24G/A3A-

D(U)
CM100N1520  
7.0
(24000)

GMV
□
-
□
□
□
□
W
□
/
□
□
□

1
2
3
4
5
6
7
8
9
10

No.
Description
 Options

1
Product code
GMV-Gree Multi VRF Units

2
Suitable climate
Blank-T1 condition; T2-low temperature climate; 

T3-high temperature climate

3
Unit type
DC Inverter (omit)

4
Function code
Q—Heat Recovery; S—Water Heater; W—Water-cooled Unit; X—Fresh Air Unit

Leave blank if above functions are unavailable. 

5
Code of cooling capacity
 Nominal capacity/100(W)

6
Unit structure
M—Modular (top discharge); L—Non-modular (side discharge); blank—Non-modular (top 

discharge)

7
 Refrigerant
R410a (omit)

8
 Design No.
Named in order of A, B, C, or combined with 1, 2, 3…

9
 Power supply
7000~18000W, 1 phase—omit; 3 phase—S 

2.2Nomenclature of indoor units
GMV-
—— Power supply

Series number

With water pump or not

Units series

Cooling capacity

Function code

Motor type
Household or commercial

Code for indoor unit

Code for type

3

PRODUCT

Sayfa 6

Ultra Heat GMV Multi VRF 

for North America

Code for 
multi VRF
-
Code for 
indoor unit
Motor type
Function code
Cooling capacity

GMV
-
N

PL-Low static pressure duct type indoor unit; 

P-Standard static pressure duct type indoor; 

PH-High static pressure duct type indoor 
unit; PB-Thin duct type indoor unit; T-Four-
way cassette; TD-Single-way cassette; TS-

Two-way cassette; C-Floor mounting unit; 
ZD-Floor ceiling unit; G-Wall-mounted unit

3 PRODUCT FEATURES
3.1 General introduction

Gree Multi VRF System adopts inverter compressor technology. By changing the displacement  of compressor, stepless capacity
regulation within range of 15%~100% can be realized. Various product lineups are provided with capacity range from 36000Btu/h to 
48000Btu/h, which can be widely used in residential, commercial and working area and especially applicable to places with big load
change. It features Superior heating performance, high capacity and energy efficiency.

3.1.1 Features

(1) Superior heating performance.
         Continuous heating down to -20℃,without weakening, which is the highest level in the trade.

(2) High capacity and energy efficiency
          When heating at low temperature and cooling at high temperature, its capacity has increased by 60% and COP has increased
          by 20% compared to the traditional systems.
(3) No-brige PFC control technology
         Compared to traditional one, no-brige PFC control technology has many advantages like less energy wasting, low electromagnetism
        disturbing and so on.
(4) Intelligent temperature and humidity control energy-saving technology
         Use the intelligent temperature and humidity control energy-saving technology to make sure that the room temperature and humidity 
         are comfortable for human beings. It save more than 30% energy and makes human beings far away from diseases.
(5) Intelligent liquid-spray protection technology
         With the intelligent liquid-spray protection technology, units can calculate the current air injection dryness and control the liquid height, 
         to accurately control the air injection dryness.
(6) New generation CAN bus communication
         Due to the latest communication method—CAN Bus Communication, system’s anti-interference capability is stronger and the control 
         on indoor units is more accurate, with higher reliability. Specialized shield wire is no more needed and ordinary communication wire can 
         be applied in the construction, which has increased the installation flexibility.
(7) Reliable low-temperature running
         The controller uses the low temperature elements, which can run reliably at -35℃. The compressor can normally start up below -35℃.
(8) Small floor area and easy installation
         The floor area it occupys is the smallest one in the same capacity at the market.
(9) Complete protection
         Units are equipped with a series of protection to accurately identify errors and protect the units, which has ensured reliable and safe
         operation.
3.1.2 Features of Duct Type Indoor Unit

 ◆Flexible setting and even air supply

 ◆Convenient installation

Can be installed in the ceiling
 ◆With fresh air function to improve indoor air quality

Fresh air duct can be connected
 ◆Wide adjusting range of static pressure and air volume

Static pressure and air volume can be set according to actual requirements

3.1.3 Features of Wall Mounted Type Indoor Unit

4

PRODUCT

R-heat pump
L-cooling only

D-DC
motor
Default-AC

X-fresh air
W-dual heat sources

Nominal cooling 
capacity/100(W)

Q-heat recovery
Default-electric heating

motor

With water pump or 

not
Series number
Power supply

With water pump-
S(All cassette indoor 

A, B, C… or 1, 2, 3…
Select power supply code 
according to power supply 

units are with water 

pump, S is not 
presented in the 

model same)

Sayfa 7

గ Filter can be cleaned

గ Quiet design

గ One IDU with several wired controller and several IDUs with one wired controller

 One IDU can be connected with several wired controllers in order to control one IDU from different location; meanwhile, several IDUs 
can be connected with one wired controller in order to achieve centralized control of 16 IDUs in maximum.

గWide air supply range

 The air supply range is wide, so that the wind can be delivered to each corner of the room naturally and evenly.

గSuper cooling and heating function

 Intelligent temperature control technology is adopted with super cooling and heating function, so that the room temperature can reach 
set temperature rapidly.

గ I-feel function

When I-feel function is activated, the unit can detect the temperature around the user and adjust the temperature, so that the comfort of 
user is improved. (Remote controller shall be equipped)

గPanel is removable

 The panel of indoor unit can be removed easily for convenient maintenance.

గCAN bus communication technology and auto addressing

The response of the system is quicker with more reliable communication; auto addressing, non-polar communication and free wiring 
are available.

గ Multiple protections

Anti-freezing protection, temperature sensor malfunction protection, fan motor overload protection, auxiliary electric heating overheat 
protection (This function is not included in pure heat pump unit).
4 SPECIFICATIONS
4.1 Outdoor Unit

 Model
GMV-36WL/B-T(U)
GMV-48WL/B-T(U)

Product   Code
CN850W0380
CN850W0360

 Cooling capacity
kW(Btu/h)
10.5(36000)
14.1(48000)

Heating capacity
kW(Btu/h)
13.2(45000)
15.8(54000)

Circulating air volume
m

3/h
6000
6000

Noise
dB(A)
56
57

 Refrigerant charge volume
Kg(oz)
   6.5
   6.5

 Level
1
1

Power supply
208/230V~60Hz
208/230V~60Hz

Cooling
kW
2.6
4.2

 Rated power 

input

Heating
kW
3.1
4.2

 Unit Dimensions (mm/inch)(WxDxH)
900×340×1345mm(35.4×13.4×53.0inch)

Package Dimensions (mm/inch)(WxDxH)
993×453×1500mm(39.3×18.0×59.6 inch)

 Compressor
QXAW-F518zX440C

Water-proof level
IPX4
IPX4

Suitable climite
T1
T1

 Gas 
mm/inch
ij
ij

 Connection 

Liquid
mm/inch
ij
ij

pipe

Connection Method
Flare connection
Flare connection

 Net weight
Kg
      134.4
     134.4

2
2
5
6
50
100
50
100

Minimum NO. of connectable indoor units
Maximum NO. of connectable indoor units

Min
Max

Total capacity index of to be 
connected indoor units

Note:

ķ . The technical parameters are changed along with the products’improvement; please refer to the nameplate of the unit for actual data.

Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual operation due to environmental change.
ĸ . 

       Ultra Heat GMV Multi VRF 

for North America

5

PRODUCT

Sayfa 8

Ultra Heat GMV Multi VRF 

for North America

4.2 Indoor Unit
4.2.1 Low Static Pressure Duct Type IDU

GMV-
ND07PLS/

GMV-
ND09PLS/

GMV-
ND12PLS/

GMV-
ND14PLS/

GMV-
ND18PLS/

GMV-
ND22PLS/

Model

A-T(U)
Product   Code
CM810N0080
CM810N0090
CM810N0100
CM810N0120
CM810N0070
CM810N0110

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

Btu/h
7500
9500
12000
14000
18000
22000

Cooling Capacity

kW
2.2
2.8
3.5
4.0
5.3
6.3

Btu/h
8500
10500
13500
15000
20000
24000

Heating Capacity

kW
2.5
3.1
4.0
4.5
5.9
7.1

Galvanized Steel plate

mm
700×615×200
700×615×200
700×615×200
900×615×200 1100×615×200 1100×615×200

outline

inch
27-1/2×24-
1/4×7-7/8
27-1/2×24-
1/4×7-7/8
27-1/2×24-
1/4×7-7/8
35-3/8×24-
1/4×7-7/8
43-1/4×24-
1/4×7-7/8
43-1/4×24-
1/4×7-7/8

Dimensions

(W×D×H)

mm
893×743×305
893×743×305
893×743×305 1123×743×305 1323×743×305 1323×743×305

Packaging

inch
35-1/8×29-
1/4×12
35-1/8×29-
1/4×12
35-1/8×29-
1/4×12
44-1/2×29-
1/4×12
52×29-1/4×12
52×29-1/4×12

lbs.
51
51
51
60
69
69

Net Weight

kg
23
23
23
27
31
31

lbs.
64
64
64
73
86
86

Gross Weight

kg
29
29
29
33
39
39

mm
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ9.52
Φ9.52

Liquid Side

inch
Φ1/4
Φ1/4
Φ1/4
Φ1/4
Φ3/8
Φ3/8

mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ15.9
Φ15.9

Pipe
Connection

Gas Side

inch
Φ3/8
Φ3/8
Φ1/2
Φ1/2
Φ5/8
Φ5/8

mm
Φ25
Φ25
Φ25
Φ25
Φ25
Φ25

Drain Pipe

inch
Φ1
Φ1
Φ1
Φ1
Φ1
Φ1

Power supply
1-phase 208-230V 60Hz

Type * Quantity
Centrifugal*2
Centrifugal*2
Centrifugal*2
Centrifugal*3
Centrifugal*4
Centrifugal*4

Driving Mechanism
Direct-driven

Motor Type
BLDC

Motor Power Input
W
43
43
43
52
99
99
Motor Running 

Current
A
0.3
0.3
0.3
0.5
0.7
0.7

Fan

CFM
265/235/150
265/235/150
325/265/205
410/353/265
590/470/355
590/470/355

m

3/h
450/400/250
450/400/250
550/450/350
700/600/450
1000/800/600
1000/800/600

External
Default
in.W.G.
0.06
0.06
0.06
0.06
0.06
0.06

Pa
15
15
15
15
15
15
Range
in.W.G.
0~0.12
0~0.12
0~0.12
0~0.12
0~0.12
0~0.12

Static
Pressure

Pa
0~30
0~30
0~30
0~30
0~30
0~30

Sound Pressure Level(H/M/L)
dB(A)
31/29/25
31/29/25
32/30/27
33/31/28
35/33/30
35/33/30

Heat Exchanger

Air Filter
PP

Refrigeration Control Device
EXV

Protection Device
Fuse

6

PRODUCT

Sayfa 9

       Ultra Heat GMV Multi VRF 

for North America

4.2.2 4-way Cassette Type IDU

Model
GMV-ND07T/

GMV-ND09T/

GMV-ND12T/

GMV-ND15T/

GMV-ND18T/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

Product Code
CM500N0520
CM500N0530
CM500N0540
CM810N0130
CM500N0510

Btu/h
7500
9500
12000
15000
18000

Cooling Capacity

kW
2.2
2.8
3.5
4.4
5.3

Btu/h
8500
10500
13500
17000
20000

Heating Capacity

kW
2.5
3.1
4.0
5
5.9

Galvanized Steel plate

mm
840×840×190
840×840×240
840×840×240
840×840×240
840×840×240

Body outline

inch
33×33×7 1/2
33×33×9-1/2
33×33×9-1/2
33×33×9-1/2
33×33×9-1/2

mm
960×960×257
960×960×310
960×960×310
960×960×310
960×960×310

Body
Packaging

inch
37-3/4×37-3/4×10-
1/8
37-3/4×37-3/4×12-
1/4
37-3/4×37-3/4×12-
1/4
37-3/4×37-3/4×12-
1/4
37-3/4×37-3/4×12-
1/4

Dimensions

mm
950×950×65
950×950×65
950×950×65
950×950×65
950×950×65

(W×D×H)

Panel
 outline

inch
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2

mm
1030×1035×118
1030×1035×118
1030×1035×118
1030×1035×118
1030×1035×118

Panel
Packaging

inch
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8

lbs.
50
58
58
58
58

Main Body

kg
22.5
26.5
26.5
26.5
26.5

Net
Weigh

lbs.
15-3/8
15-3/8
15-3/8
15-3/8
15-3/8

Panel

kg
7.0
7.0
7.0
7.0
7.0

lbs.
64
75
75
75
75

Main Body

kg
29
34
34
34
34

Gross
Weigh

 lbs.
24-1/4
24-1/4
24-1/4
24-1/4
24-1/4

Panel

kg
11.0
11.0
11.0
11.0
11.0

mm
Φ6.35
Φ6.35
Φ6.35
Φ6.35
Φ9.52

Liquid Side

inch
Φ1/4
Φ1/4
Φ1/4
Φ1/4
Φ3/8

mm
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ15.9

Pipe
Connections

Gas Side

inch
Φ3/8
Φ3/8
Φ1/2
Φ1/2
Φ5/8

mm
Φ25
Φ25
Φ25
Φ25
Φ25

Drain Pipe

inch
Φ1
Φ1
Φ1
Φ1
Φ1

Power supply
1-phase 208-230V 60Hz

Type * Quantity
Centrifugal*1
Centrifugal*1
Centrifugal*1
Centrifugal*1
Centrifugal*1

Driving Mechanism
Direct-driven
Direct-driven
Direct-driven
Direct-driven
Direct-driven

Motor Type
BLDC
BLDC
BLDC
BLDC
BLDC

Motor
Power Input
W
48
48
48
48
59

Fan

Motor
Running

A
0.3
0.5
0.5
0.5
0.5

Current

CFM
440/385/325
590/530/440
590/530/440
590/530/440
590/530/440

Rate(H/M/L)

m

3/h
750/650/550
750/650/550
750/650/550
750/650/550
1000/900/750

Sound Pressure Level

(H/M/L)
dB(A)
36/34/31
36/34/31
36/34/31
36/34/31
37/35/32

Heat Exchanger

Air Filter
PP
PP
PP
PP
PP

Insulation Material
Foamed polystyrene

Refrigeration Control Device
EXV
EXV
EXV
EXV
EXV

Protection Device
Fuse
Fuse
Fuse
Fuse
Fuse

Panel name
TC01
TC01
TC01
TC01
TC01

7

PRODUCT

Sayfa 10

Ultra Heat GMV Multi VRF 

for North America

Model
GMV-ND24T/

GMV-ND30T/

GMV-ND36T/

GMV-ND42T/

GMV-ND48T/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

Product code
CM500N0550
CM500N0560
CM500N0570
CM500N0580
CM500N0590

Btu/h
24000
30000
36000
42000
48000

Cooling Capacity

kW
7
8.8
10.6
12.3
14.1

Btu/h
27000
34000
40000
47000
54000

Heating Capacity

kW
7.9
10
11.7
13.8
15.8

Galvanized Steel plate

mm
840×840×240
840×840×320
840×840×320
840×840×320
840×840×320

Body
 outline

inch
33×33×9-1/2
33×33×12-5/8
33×33×12-5/8
33×33×12-5/8
33×33×12-5/8

mm
960×960×310
960×960×394
960×960×394
960×960×394
960×960×394

Body
Packaging

inch
37-3/4×37-3/4×12-
1/4
37-3/4×37-3/4×15-
1/2
37-3/4×37-3/4×15-
1/2
37-3/4×37-3/4×15-
1/2
37-3/4×37-3/4×15-
1/2

Dimensions

mm
950×950×65
950×950×65
950×950×65
950×950×65
950×950×65

(W×D×H)

Panel
 outline

inch
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2
37-3/8×37-3/8×2-
1/2

mm
1030×1035×118
1030×1035×118
1030×1035×118
1030×1035×118
1030×1035×118

Panel
Packaging

inch
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8
40-1/2×40-1/2×4-
5/8

lbs.
58
72
72
72
72

Main
Body

kg
26.5
32.5
32.5
32.5
32.5

Net
 Weight

lbs.
15-3/8
15-3/8
15-3/8
15-3/8
15-3/8

Panel

kg
7.0
7.0
7.0
7.0
7.0

lbs.
75
88
88
88
88

Main Body

kg
34
40
40
40
40

Gross
 Weight

lbs.
24-1/4
24-1/4
24-1/4
24-1/4
24-1/4

Panel

kg
11.0
11.0
11.0
11.0
11.0

mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52

Liquid

Side

inch
Φ3/8
Φ3/8
Φ3/8
Φ3/8
Φ3/8

mm
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9

Pipe
Connections

Gas
Side

inch
Φ5/8
Φ5/8
Φ5/8
Φ5/8
Φ5/8

mm
Φ25
Φ25
Φ25
Φ25
Φ25

Drain

Pipe

inch
Φ1
Φ1
Φ1
Φ1
Φ1

Power supply
1-phase 208-230V 60Hz

Type * Quantity
Centrifugal*1
Centrifugal*1
Centrifugal*1
Centrifugal*1
Centrifugal*1

Driving
Mechanism
Direct-driven
Direct-driven
Direct-driven
Direct-driven
Direct-driven

Motor Type
BLDC
BLDC
BLDC
BLDC
BLDC

Motor
Power

W
59
98
110
110
110

Fan

Input

Motor
Running

A
0.5
0.8
0.9
0.9
0.9

Current

CFM
695/590/470
885/800/650
1000/825/650
1095/885/680
1095/885/680

Rate(H/M/

3/h
1180/1000/800
1500/1350/1100
1700/1400/1100
1860/1500/1150
1860/1500/1150

m

L)

Sound Pressure Level(H/

M/L)
dB(A)
38/36/33
40/38/35
41/38/36
43/41/38
43/41/38

Heat Exchanger

Air Filter
PP
PP
PP
PP
PP

Insulation Material
Foamed polystyrene

Refrigeration Control Device
EXV
EXV
EXV
EXV
EXV

Protection Device
Fuse
Fuse
Fuse
Fuse
Fuse

Panel name
TC01
TC01
TC01
TC01
TC01

8

PRODUCT

Sayfa 11

       Ultra Heat GMV Multi VRF 

for North America

4.2.3 Features of Wall Mounted

Model
GMV-N07G/A3A-

GMV-N09G/A3A-

GMV-N12G/A3A-

GMV-N18G/A3A-

GMV-N24G/A3A-

D(U)
Product code
CM100N1480
CM100N1490
CM100N1500
CM100N1510
CM100N1520

D(U)

D(U)

D(U)

D(U)

Btu/h
7500
9500
12000
18000
24000

Cooling Capacity

kW
2.2
2.8
3.5
5.2
7

Btu/h
8500
11000
13500
20000
25500

Heating Capacity

kW
2.5
3.2
4
5.8
7.5

Galvanized Steel plate

mm
843×180×275
843×180×275
940×200×298
940×200×298
1008×221×319

outline

inch
33 1/5×7×10 5/6
33 1/5×7×10 5/6
37×7 7/8×11 3/4
37×7 7/8×11 3/4
39 2/3×8 5/7×12 
5/9

Dimensions

(W×D×H)

mm
973×258×370
973×258×370
1068×288×395
1068×288×395
1131×398×328

Packaging

inch
38 1/3×10 1/6×14 
4/7
38 1/3×10 1/6×14 
4/7
42×11 1/3×15 5/9
42×11 1/3×15 5/9
44 1/2×15 2/3×13

lbs.
22
22
27.6
27.6
33.1

Net Weight

kg
10
10
12.5
12.5
15

lbs.
27.6
27.6
33.1
33.1
40.8

Gross Weight

kg
12.5
12.5
15
15
18.5

mm
ĭ
ĭ
ĭ
ĭ
ĭ

Liquid Side

inch
ĭ
ĭ
ĭ
ĭ
ĭ

mm
ĭ
ĭ
ĭ
ĭ
ĭ

Pipe
Connections

Gas Side

inch
ĭ
ĭ
ĭ
ĭ
ĭ

mm
ĭ
ĭ
ĭ
ĭ
ĭ

Drain Pipe

inch
ĭ
ĭ
ĭ
ĭ
ĭ

Power supply
1-phase 208-230V 60Hz

Type * Quantity

Driving Mechanism
Direct-driven

Motor Type
PG
Motor Power 

Input
W
50
50
60
60
70

Fan

Motor Running 

Current
A
0.2
0.2
0.21
0.21
0.31

CFM
295/247/206
295/247/206
370/324/283
370/324/283
440/353/294

Rate(H/M/L)

m

3/h
500/420/350
500/420/350
630/550/480
630/550/480
750/600/500

Sound Pressure Level(H/M/L) dB(A)
38/34/30
38/34/30
44/41/38
44/41/38
44/41/38

Heat Exchanger

Air Filter
PP+10%BCM+FP03

Insulation Material
Foamed polystyrene

Refrigeration Control Device
EXV

Protection Device
Fuse
4.3 Operation range

Cooling
Outdoor temperature: (50~129.2°F)

Heating
Outdoor temperature: (-31~80.6°F)

5 PRODUCT CAPACITY CORRECTION
5.1 Instruction of Product Capacity Correction

Nominal cooling capacity and nominal heating capacity are tested under given conditions:
(1) Rated cooling or heating condition.
(2) No height difference between indoor unit and outdoor unit.
(3) Short connection pipe.
If the three conditions above have changed, the cooling and heating capacity will change correspondingly and correction is needed.

9

PRODUCT

Sayfa 12

Ultra Heat GMV Multi VRF 

for North America

5.2 Capacity Code

Instruction of capacity code:
GMV-36WL/B-(U) and GMV-48WL/B-(U) are identical in components, systems and structure, etc. 

5.3 Capacity Correction Formula5.1 Correction factor of indoor and outdoor temperature 

5.3.1 Rated capacity of outdoor unit

Model
GMV-36WL/B-T(U)
GMV-48WL/B-T(U)

Rated cooling capacity
kW(Btu/h)
10.5(36000)
14.1(48000)

Rated heating capacity
kW(Btu/h)
13.2(45000)
15.8(54000)

5.3.2 Correction factor of indoor and outdoor temperature 

(1) Correction factor of cooling capacity

1.00
1.00
0.95
1.00 1.05

1.00

48

(118)

45

(113)

40 (104)

35

(95)

30

(86)

25

(77)

20

(68)

16

(61)

14
16
18
20
22
24
26
(57) (61) (64) (68)
(72)
(75) (79)

嘅嘅嘅嘅嘅嘅嘅嘅嘅

(2) Correction factor of heating capacity

1.0
1.0
1.00
1.0
0.95

-20
-25

(-4)
(-13

5.3.3 Correction factor of pipe length and height difference

(1) Symbol description:
Hp: Height difference in case indoor unit is below outdoor unit(m/feet);
Hm: Height difference in case indoor unit is above outdoor unit (m/feet);
L: Length of one-way equivalent pipe.
Below table shows the capacity variance ratio for 100% full load in standard working condition (thermostat setting is 16

10

PRODUCT

oC(61

oF) for 

Sayfa 13

       Ultra Heat GMV Multi VRF 

for North America

oC(86

oF) for heating).

cooling and 30

0. 9
9

.
0
7
9

0. 5
9

50

50

40

40

30

30

20

.
1 0

20

Hp(m)

Hp(m)

10
10
20
30

10
10
20
30

60
40
50
70
80
110
90
1001
20
150

L(m)
1301 40

60
40
50
70
80
110
90
1001
20
150
L(m)
1301 40

10

Hm(m)

10

Hm(m)

20

20

30

30

40

40

Variance ratio of heating capacity
Variance ratio of heating capacity
NOTE:

m
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150

ft
0
33
66
98
131
164
197
230
262
295
328
361
394
427
459
492

6 PRINCIPAL OF OPERATION

Name
Compressor
4-way valve
Cut-off valve
One-way valve
Capillary tube

Symbol

Name
Gas-liquid

Pressure

Pressure

sensor
exchanger
Electronic expansion valve

separator

switch

Symbol

11

PRODUCT

Sayfa 14

Ultra Heat GMV Multi VRF 

for North America

In cooling, the low-temperature and low-pressure refrigerant gas from each indoor heat exchanger will be merged and inhaled by the 
compressor and then become high-temperature and high-pressure gas, which will later be discharged into outdoor heat exchangers. By 

with indoor air, refrigerant wil become low-temperature and low-pressure gas again and repeat the circulation so as to realize the cooling 
effect. In heating, 4-way valve will be energized to make refrigerant circulate in a reverse direction of cooling. Refrigerant will release heat in 
indoor heat exchangers (electric heating elements will also work under certain circumstance and release heat) and absorb heat in outdoor 
heat exchangers circularly so as to realize the heating effect.

12

PRODUCT

Sayfa 15

CONTROL

       Ultra Heat GMV Multi VRF 

for North America

13

CONTROL

Sayfa 16

Ultra Heat GMV Multi VRF 

for North America

CONTROL
1 Units’ Control
1.1 Schematic diagram of units’ control

     Air conditioning units can be divided into indoor unit and outdoor unit. A maximum of 16 sets of indoor units
can be connected to an outdoor unit. 2-core (3-core pin header) communication cable is used for the connection
between indoor unit and outdoor unit. Indoor unit is connected to display board via 4-core communication cable. In
engineering installation, address dial-up of the display board and the mainboard of indoor unit shall be dialed. The
address dial-up of the mainboard of indoor unit must be identical with that of the display board of the same indoor
unit. Address dial-up of different indoor unit must vary. Multi VRF indoor unit is applicable to all digital or inverter
outdoor units.
     Controller of outdoor unit falls into two categories in terms of its function, i.e. main control system and
inverter drive control system

14

CONTROL

Sayfa 17

2  Wired Controller
2.1 Control panel

Fig. 1.1 Appearance of wired controller

Fig. 1.2 LCD graphics of wired controller
 LCD Display Instruction

Table 1.1 LCD display instruction

No.
Symbols
Instructions

1
Up and down swing function

2
Left and right swing function

It's valid under Save mode and displays during setting process.
Temperature lower limit for Cooling: Limit the minimum temperature value under Cooling or Dry mode.
Temperature upper limit for Heating: Limit the maximum temperature value under Heating, Space Heating or 3D 
Heating mode. 

3

4
Auto mode (Under Auto mode, the indoor units will automatically select their operating mode as per the temperature 

change so as to make the ambient comfortable.)

5
It shows the setting temperature value(In case the wired controller is controlling a Fresh Air Indoor Unit, then the 
temperature zone will display FAP)

       Ultra Heat GMV Multi VRF 

for North America

15

CONTROL

Sayfa 18

Ultra Heat GMV Multi VRF 

for North America

6
Cooling mode

7
Dry mode

8
Fan mode

9
Heating mode

10
When inquiring or setting project number of indoor unit, it displays "NO." icon

11
Floor Heating mode (When Heating and Floor Heating simultaneously shows up, it indicates 3D Heating is 
activated.)

12
Display "SET" icon under parameter setting interface

13
Space Heating mode

14
Display "CHECK" icon under parameter view interface

15
Outdoor unit operates under Save mode/upper limit of system capacitor less 100%/remote Save status

16
Sleep status

17
Current set fan speed (including auto, low speed, medium-low speed, medium speed, medium-high speed, high 
speed and turbo seven status) 

18
Air status

19

20
Quiet status (including Quiet and Auto Quiet two status)

21
Allow auxiliary electric heating On icon

22
Light On/Off  function

23
X-fan function

24
Health function

25
Fresh air status

26
Out function

27
Outdoor unit defrosting status

28
Gate-control function

29
Shielding status

30
Child Lock status

31
One wired controller controls multiple indoor units

32
Save status of indoor unit

33
It indicates the current wired controller is the slave wired controller (address of wired controller is 02)

34
Memory status (The indoor unit resumes the original setting state after power failure and then power recovery)

35
Invalid operation

36
Current wired controller connects master indoor unit

37
Timer zone:Display system clock and timer status

Note: When wired controller is connected with different indoor units, some functions will be different

16

CONTROL

Sayfa 19

Ultra Heat GMV Multi VRF 

for North America

Button Graphics

Fig. 1.3 Button graphics
2.2 Installation and removal
2.2.1 Installation dimensions

Unit:mm

8
5
.
2
0
4

1
1 2

.3
R3

6 R
-
2 7
.

5
3

22
Unit:mm
Fig.2.1.1 Dimension of wired controller

112
22

42.5

mm
112
22
2.7
3.3
5
42.5
40
82.5

inch
4.41
0.87
0.11
0.13
0.20
1.67
1.57
3.25

2.2.2 Installation method

1
2
3
4

2
H1
H

2
H1
H

2
H1
H

6
7

5

8
9

10

Fig. 2.2.2 Installation diagram for wired controller
Above is a simple installation method of wired controller. Please pay attention to the following:

1) Before installation, disconnect power of the indoor unit. Do not operate when power is connected.

2) 2-core twisted pair cable from the installation hole on the wall and lead it through the hole 
 on the back plate of wired controller.
3) Place the wired controller on wall and secure its back plate on wall with screw M4X25.
4) Connect the 2-core twisted pair cable to terminal H1 and terminal H2. Tighten up the screws.
5) Stick the cable in the slot that is left of the terminals and buckle the wired controller’s panel with its back plate.

point 5, strip some of the sheath of the communication cable to meet the installation requirement.

17

CONTROL

Sayfa 20

Ultra Heat GMV Multi VRF 

for North America

2.2.3 Removal method

H1H2

H1H2

1
2
3
4

Fig.2.1.3 Removal of Wired Controller
2.2.4 Connection of communication cord

There are 4 ways to connect wired controller with indoor units’ network:

Outdoor unit

Outdoor unit

D1
D2

D1
D2

Indoor unit

Indoor unit

D1 D2
H1 H2

D1 D2
H1 H2

Fig. 2.2.4.1 One wired controller 

Fig. 2.2.4.2 Two wired controllers 

controls one indoor unit

control one indoor unit

Outdoor unit

D1
D2

Indoor unit 1
Indoor unit 2
Indoor unit 16

D1 D2
H1 H2

D1 D2
H1
2
H

D1 D2
H1 H2

Fig. 2.2.4.3 One wired controller controls multiple indoor units simultaneously

18

CONTROL

Sayfa 21

Outdoor unit

D1
D2

Indoor unit 1
Indoor unit 2
Indoor unit 16

D1 D2
H1 H2

D1 D2
H1 H2

Fig. 3.6 Two wired controllers control multiple indoor units simultaneously

2.3 Engineering Test 

1˅Mater IDU Settings 

In power-off status, press and hold the “MODE”button for five seconds to set the IDU connected with the 

current wired controller to master IDU.If the setting is successful, MASTER icon will be on. 

2˅User Parameter Query 

Engineering Parameters can be queried in power-on of power-off status. 

(1) Press and hold the “FUNCTION”button for five seconds to enter the user parameter query interface. The 

temperature area display “C00” and “CHECK” is on.  

(2) Select a parameter code by pressing“ġ”or“Ģā
  

(3) Press“ENTER/CANCEL”botton ro return to the upper-level menu till quitting parameter query. 

The user parameter query list is as follows: 

Paremeter  

Code 
Parameter Name 
Parameter 

Range 
View Method 

C00 
Parameter setting 

ingress 
- 
- 

Operation method: 
In”C01”status,press “MODE”button to enter project 
number query of IDU.Press“ġ”or“Ģ”to switch the IDU 
SN. 

1-255˖Project 

Project number query 

Display mode: 
Temperature area:displays the fault of current IDU 

C01 

of IDU and fautly 

number of 

IDU loaciton 

online IDU 

Timer area:displays project number of current IDU 

Special operations: 
After users press the “MODE”button to enter project 

number query, the buzzer of the IDU operated by the 
wired controller will ring till users quit “C01”query or 

      Ultra Heat GMV Multi VRF 

for North America

D1 D2
H1 H2

19

CONTROL

Sayfa 22

Ultra Heat GMV Multi VRF 

for North America

switch to the next IDU 

Indoor unit  quantity 
query in the system 
network 

1-80 
Timer area: displays the number of IDUs in the system 
network. 

C03 

Operation method: 

In”C06”status,press “MODE”button to enter Preferential 
operation query interface.Press“∧”or“∨”to switch the 

00:Common 

C06 
Preferential operation 

operation 
01:Preferential 

IDU SN. 
Display mode: 

query 

operation 

Temperature area: displays project number of current IDU 
Timer area:displays the preferential operation setting 
value of the current IDU 

Operation method: 

In”C07”status,press “MODE”button to enter the indoor 
environment temperature query interface. 
Press“∧”or“∨”to switch the IDU SN. 

C07 
Indoor environment 

temperature query 
- 

Display mode: 
Temperature area: displays project number of current IDU 

Timer area: displays the temperature value of the 
environment temperature sensor after replenishment. 

C08 
Prompt time query for  

4-416:days 
Timer area:displays the prompt time query for  air filter 

air filter cleaning 

cleaning 

C09 
Wired controller 

address query  
01,02 
Timer area: displays the adrsess of the current wired 

controller 

Indoor unit quantity 

1-16 
Timer area: displays the number of IDUs controlled by the 
wired controller 

C11 

query in one-to-many 
mode 

C12 
Outdoor environment 

temperature query 
- 
Timer area: displays the temperature value of the 

environment temperature sensor of the master ODU. 

Note: 

a. In parameter query status, FAN, TIMER, SLEEP, and SWING are invalid. By pressing the”ON/OFF”button, 

users can return to the main interface but not power on/off the unit. 

b. In parameter query status, signals of the remote controller are invalid. 

3)User Parameter Settings 

Engineering Parameters can be set in power-on of power-off status. 

(1)  Press and hold the “FUNCTION” button for five seconds to enter the user parameter query interface. The 

temperature area displays “C00”. Press and hold the “FUNCTION”button for another five seconds to entert the 

20

CONTROL

Sayfa 23

wired controller parameter setting interface.The temperature area displays “P00”. 

(2) Select a parameter code by pressing“∧”or“∨”.Press the “MODE”button to switch to parameter value 

setting.The parameter value blinks.Adjust the parameter value by pressing “∧”or“∨” and the press the 

“ENTER/CANCEL”to complete settings. 

(3) Press”ENTER/CANCEL”botton ro return to the upper-level menu till quitting parameter settings. 

The user parameter setting list is as follows: 

Parameter 

Code 
Parameter Name  
Parameter Range 
Default 

00:does not change the 

master/slave status of the 
current IDU. 
01:sets the current IDU to 

P10 
Master IDU 

settings 

master IDU 

Infrared 
connection 
settings of wired 

00:disabled 
01:enabled 
01 

P11 

controller  

01:Master wired controller  
02:Slave wired controller 
01 

P13 
Wired controller 

address settings 

Group-controlled 

00:disabled 

01-16:number of indoor 

P14 

IDU quantity 

settings 

units 

Static pressure 

Type 1: 03.04.05.06.07 

P30 

settings for 

Type 2: 
01.02.03.04.05.06.07.08.09 
05 

indoor fan 

      Ultra Heat GMV Multi VRF 

for North America

Value 
Remark 

After the IDU connected with the 

current 
wired 
controller 
is 
successfully 
set 
to 
master 

00 

IDU, 
”MASTER” 
on 
the 
wired 
controller is on. 

This setting can only be enabled 

through 
the 
master 
wired 
controller.When the infrared remote 
receiving function of wired controller 
is disabled, neither the master nor 

slave wired controller can receive 
remote signals.The wired controller 

can only be operated by pressing. 

When 
two 
wired 
controllers 
simultaneously control one or more 

IDUs, the two controllers should use 
different addresses.The slave wired 

controller (address:02) does not have 
the unit parameter setting function 

except its own address settings. 

This value is set based on the number 

of connected IDUs.If the current value 

01 

is inconsistent with the actual number 
of grou-controlled IDUs, an”L9”fault 

may occur. 

After identifying the IDU type, the 

wired controller only displays the 
available static pressure levels. 
1. The static pressure levels fall into 
five levels and nile levels for VRF 

IDUs.The 
wired 
controller 
only 

displays the static pressure levels 
matched with the identified IDU type. 

2. When the HBS network consists of 

IDUs with both five and nice static 

21

CONTROL

Sayfa 24

Ultra Heat GMV Multi VRF 

for North America

00:standard-ceiling 

P31 
Hign-ceiling 

installation height 
01:high-ceiling installation 

installation 

height 

00:common timing 
01:time-point timing 
00 
 

P33 
Timer function 

settings 

Repeating 
validity for 

00:single timing 
01:repeated everyday 
00 
This setting is valid only when the 
timer function is set to time-point 

P34 

time-point timing 

Cooling setting 

P37 

temperature in 

17℃~30℃ 
25℃ 
Cooling setting temperature – heating 

automatic mode 

Heating setting 

16℃~29℃ 
20℃ 

in remote shielding status. 
P38 

temperature in 
automatic mode 

00:common operation 
01:preferential operation 
00 

P43 
Preferential 
operation settings 

Accumulated 

00:not cleared 

P46 

time clearing for 
air filter cleaning 

01:cleared 
00 

Note: 

a. In parameter query status, FAN, TIMER, SLEEP, and SWING are invalid. By pressing the”ON/OFF”button, 

users can return to the main interface but not power on/off the unit. 

b. In parameter query status, signals of the remote controller are invalid. 

2.4 Operation Instructions 

1) On/Off 

Press ON/OFF button to turn on the unit. 

22

CONTROL

pressure levels according to the 

maximum control principle.If the 
static pressure lelvls received by the 

IDU from wired controller,remote 
controller,or 
remote 
monitoring 

system exceed the setting range,the 

limit value prevails. 

3. During power-on and synchro- 

nization the setting value of static 

pressure leverls is determined by 

setting of the IDU. 

00 
 

timing. 

setting temperature ≥1℃. 
Note: The two settings are still valid 

When power supply is insufficient, 
users are allowed to power on/off the 

IDU set with preferential operation 
and other IDUs are forcibly powered 

off.A fault code is displayed on the 
IDU that is forcibly powered off. 

Sayfa 25

Press ON/OFF button again to turn off the unit. 

The interfaces of On/Off status are shown as follow: 

 
 
2)Mode Setting 
Under On status, pressing MODE button can set mode circularly as: 

Note: 

①There will be different mode with different model of the uint.The wired controller will select the range of setting 

mode according to the model of indoor unit 

② Only in master indoor unit that AUTO mode can be set. 

③ Under the AUTO mode,when the indoor unit is cooling,“
”and“
”will be on; when the indoor unit is 

heating ,“”and“
”will be on. 

3)Temprature Setting 

Pressing“∧or∨”button in On status increases or decreases set temperature by 1°C; holding  “∧or∨”button 

increases or decreases set temperature by 1°C every 0.3s.  

In Cooling, Fan, Heating, Floor Heating, 3D Heating or Space Heating mode, temperature setting range is 

16°C~30°C.  

In Dry mode, the temperature setting range is 12°C, 16°C~30°C. In Dry mode, when temperature is 16°C, 

      Ultra Heat GMV Multi VRF 

for North America

23

CONTROL

Sayfa 26

Ultra Heat GMV Multi VRF 

for North America

continuously press  
 button twice to decrease temperature to 12°C (when Save function is activated, the 

temperature in Dry mode can’t be adjusted to 12°C and the setting range is “lowest temperature in Save mode” ~ 

30°C).  

Note:  

ķ Under Auto mode or Out function is activated, the setting temperature can not be adjusted by pressing 

“ġ”or “Ģ” 

ĸ When the wired controller is connected with a Fresh Air Indoor Unit, setting temperature won’t be 

“
displayed and can’t be adjusted via 

set in the parameter setting status.
 

4˅Fan Speed Setting
 

Under On status, pressing FAN button can set fan speed circularly as: 

Note: Under the DRY mode, the fan will be kept running at the low speed and the fan speed isn't adjustable  

5˅Timer setting 

The wired controller is equipped with two kinds of timer: general timer and clock timer. General timer is 

factory defaulted setting. Please refer to parameter setting  

a. General Timer  

Unit On/Off after a desired hour can be set through general timer.  

Set Timer: when timer is not set, press TIMER button to enter timer setting and “HOUR” icon is blinking. Press 

“ġ”or“Ģ”  button to adjust timer time. Press TIMER button to save the setting and then exit setting.  

Cancel Timer: when timer is set, press TIMER button to cancel it.  

Timer setting range: 0.5~24h. Pressing “ġ” or “Ģ”  button increases or decreases timer time by 0.5h; holding 

“ġ”or “Ģ”  button increases or decreases timer time by 0.5h every 0.3s.  

In unit On status, timer Off setting is shown as follow:
 

                                                
 
24

CONTROL

ġ” or “Ģ” button. The air outlet temperature in cooling or heating can only be 

Sayfa 27

b. Clock Setting Clock display: when the timer setting way is clock timer, timer zone displays system clock in 

unit On and Off status. 
icon is bright and the clock can be set at this time.  

Clock setting: long press TIMER button for 5s to enter clock setting and
 icon is blinking. Pressing  
“∧”or“∨” button increases or decreases clock time by 1min; holding “∧”or“∨” button for 5s increases or 

decreases clock time by 10min; Press ENTER/CANCEL button or TIMER button to save the setting and then exit 

setting.  

c. Clock Timer  

Unit On/Off at a certain time can be set through clock timer. 

Set Timer:  

(1) Press TIMER button to enter timer on setting and the “ON” icon is blinking; 
 

(2) Press “∧”or“∨” button to adjust unit On time. Press ENTER/CANCEL button to finish setting;  

(3) Before pressing ENTER/CANCEL button, pressing TIMER button can save unit On time and then switch to 

unit Off time setting with “OFF” icon blinking; 
 

(4) Press “∧”or“∨”button to adjust unit Off time. Press ENTER/CANCEL button to finish setting;  

Cancel Timer:  

Press TIMER button to enter timer setting; press TIMER button again to switch to the setting of unit ON time or 

unit Off time; press ENTER/CANCEL button to cancel timer.  

      Ultra Heat GMV Multi VRF 

for North America

25

CONTROL

Sayfa 28

Ultra Heat GMV Multi VRF 

for North America

Pressing “∧”or“∨” button increases or decreases timer time by 1min; holding  “∧”or“∨” button for 5s 

increases or decreases timer time by 10min.  

Clock Timer setting is shown as follow: 

6) Swing Setting In unit on status, up & down swing function and left & right swing function can be set.  

(1) Up & down swing function  

                 
                 
26

CONTROL

Sayfa 29

Up & down swing function has two modes: simple swing mode and fixed-angle swing mode. In unit off status, 

press “SWING” button and Ÿ button together for 5 seconds to switch between simple swing mode and fixed-angle 

swing mode. Up & down swing icon
 will blink during switching.  

a. When simple swing mode is set in unit on status, press “SWING” button to start or stop up & down swing. 
 

b. When fixed-angle swing mode is set in unit on status, press “SWING” button to adjust swing angle circularly 

as below:  

 (2) Left & right swing function  

Start left & right swing: In unit on status, press “FUNCTION” button to switch to left & right swing function 

with left & right swing icon 
blinking, and then press “ENTER/CANCLE” button to start left & right swing. 

When left & right swing is activated, left & right swing icon will be bright.  

Cancel left & right swing: When left & right swing is activated, press “FUNCTION” button to switch to left & 

right swing with left & right swing icon 
blinking, and then press “ENTER/ CANCLE” button to cancel left & 

right swing. 

7) Quiet Setting  

Quiet Function: decrease the noise of indoor unit and achieve the quiet effect. Quiet function has two modes: 

Quiet mode and Auto Quiet mode. It is available only in Auto, Cooling, Dry, Fan, Heating, 3D heating, Space 

heating mode.  

Turn on Quiet Function: press FUNCTION button to turn to Quiet function and then Quiet icon or auto 

quiet icon 
 is blinking. At this moment, press “ġ” or“Ģ” button to switch between quiet and auto quiet, 

and then press ENTER/CANCEL button to tactivate.  

Turn off Quiet Function: press FUNCTION button to turn to Quiet function and then press ENTER/CANCEL 

button to cancel Quiet function. 

The setting of Quiet function is shown as follow: 

      
Ultra Heat GMV Multi VRF 

for North America

27

CONTROL

Sayfa 30

Ultra Heat GMV Multi VRF 

for North America

8) Sleep Setting 

 Sleep Function: in this mode, the unit will operate according to the preset sleep curve to provide comfortable 

sleep environment.  

Turn on/off Sleep Function: in unit On status, press SLEEP button to tactivate or cancel Sleep function.  

When Sleep function is activated,
icon is bright and quiet or auto quiet mode is also activated.  

When Sleep function is closed, if quiet function is activated before starting Sleep function, only sleep function 

                 
                 
28

CONTROL

Sayfa 31

is closed while quiet function is still activated;  

Under Auto,Fan or Floor Heating mode, this Sleep function is not available. 

9) Air Setting  

Air Function: Adjust the amount of indoor fresh air to improve air quality and keep indoor air fresh.  

Turn on Air Function: When unit is on or off, press FUNCTION button and select Air. 
icon will blink 

and the unit enters into Air setting. Temperature zone shows the level of Air setting, which can be adjusted by 

pressing “ġ” or “Ģ” button. The adjustment range is 1~10. Press ENTER/ CANCEL button to turn on Air function. 
 

Turn off Air Function: When Air function is on, press FUNCTION button to select Air, then press 

ENTER/CANCEL button to cancel this setting.  

The setting of Air function function is shown as follow: 

10) Light On/Off Setting 

 Light On/Off Function: Light of indoor unit can be turned on or off.  

Turn on the Light: When unit is on or off, press FUNCTION button to select Light function. 
icon will 

blink. Press ENTER/CANCEL to turn on the light.  

Turn off the Light: When light of indoor unit is on, press FUNCTION button to select Light. Then press 

ENTER/CANCEL to turn off the light.  

      
Ultra Heat GMV Multi VRF 

for North America

29

CONTROL

Sayfa 32

Ultra Heat GMV Multi VRF 

for North America

Note:  

When there is no button operation on the wired controller or no remote control signal is received for 20s 

continuously:  

① If Light function is activated, the back light of LCD will turn to half bright.  

② If Light function is off, the back light of LCD will be off. 

11) Save Setting  

Save Function: Air conditioner can be operated in small temperature range by setting the minimum 

temperature under Cooling and Dry modes and setting maximum temperature under Heating, 3D Heating and 

Space Heating modes. Thus, energy saving can be realized.  

Save Setting:  

Save Setting for Cooling: When unit is on and under Cooling or Dry mode, press FUNCTION button to select 

Save function.
icon will blink and MIN icon lit up. Press“
∧”or“∨” button
 to adjust to the minimum 

temperature. Press ENTER/CANCEL button to activate this function.  

The setting of Save function is shown as follow: 

                 
                 
30

CONTROL

Sayfa 33

Save Setting for Heating: When unit is on and under Heating, 3D Heating and Space Heating modes, press 

FUNCTION button to select Save function.
 icon will blink and MAX icon lit up. Press “
∧”or“∨” button to 

adjust the MAXIMUM temperature. Press ENTER/CANCEL button to turn on this function.  

Turn off Save Function: Press FUNCTION button and select Save function. 
 icon blinks. Then press 

ENTER/CANCEL button to cancel this setting. 

12) Filter Clean Reminder Setting  

Filter Clean Reminder Function: Unit will remember its own operating time. When the setting time is up, this 

function will remind you to clean the filer. A dirty filter will result in bad heating and cooling performance, 

abnormal protection, bacteria gathering, etc.  

Turn on Filter Clean Reminder Function: When unit is on, press FUNCTION button and select Filter Clean 

Reminder.
 icon will blink. Press“
∧”or“∨” button to adjust the cleaning level, of which the range is 00, 

10-39. Press ENTER/CANCEL to turn on this function.  

Turn off Filter Clean Reminder Function: When unit is on and this function has been turned on, press 

FUNCTION button and select Clean. Then 
 icon will blink. Set the cleaning level as 00 and press 

ENTER/CANCEL function to cancel this setting.  

When Filter Clean Reminder time is up, 
 con will light up to remind you to clean the filer. Press 

FUNCTION button to turn to Filter Clean Reminder Function, then press SWING/ ENTER to cancel reminding, 

and it will retime according to the original cleaning level. The clean reminding can be cancel 
only when you didn’t reset the cleaning level under the setting of Filter Clean Reminder Function. 
 

      Ultra Heat GMV Multi VRF 

for North America

31

CONTROL

Sayfa 34

Ultra Heat GMV Multi VRF 

for North America

The setting of Filter Clean Reminder function is shown as follow: 

Note:  

Description on cleaning level: When setting the Filter Clean Reminder Function, timer zone will display 2 

digits, of which the former indicates the pollution degree of operating place and the latter indicates the operating 

time of indoor unit. There are 4 types of situations: 

Cleaning Level 
Description of Levels 

Turn off Clean 

Reminder 
Timer zone shows 00 

The former digit shows 1 while the latter one shows 0, which indicates the accumulating 

Slight 
Pollution 

operating time is 5500 hours. Each time the latter digit increases 1, the operating time increases 
500 hours. When it reaches 9, it means the operating time is 10000 hours 

The former digit shows 2 while the latter one shows 0, which indicates the accumulating 
operating time is 1400 hours. Each time the latter digit increases 1, the operating time increases 

Medium 
Pollution 

400 hours. When it reaches 9, it means the operating time is 5000 hours 

                 
                 
32

CONTROL

Sayfa 35

The former digit shows 3 while the latter one shows 0, which indicates the accumulating 
operating time is 100 hours. Each time the latter digit increases 1, the operating time increases 
100 hours. When it reaches 9, it means the operating time is 1000 hours. 

Heavy 

Pollution 

13) X-fan Setting 

X-fan Function: If unit is turned off under Cooling or Dry mode, the evaporator of indoor unit will be dried off 

automatically to prevent bacteria and mould from gathering.  

Turn on X-fan: When unit is on or under Cooling or Dry mode, press FUNCTION button to select 

X-fan.
icon will blink. Then press ENTER/CANCEL button to turn on this function.  

Turn off X-fan: When X-fan function is on, press FUNCTION button to select X-fan.
icon will blink. 

Then press ENTER/CANCEL button to turn off this function.  

14) Out Setting  

Out Function: This is used to maintain indoor temperature so that unit can realize fast heating after it is turned 

on. This function can only be used under Heating mode.  

Turn on Out Function: Under Heating mode, press FUNCTION button to select Out.
 icon will blink. 

Then press ENTER/CANCEL button to turn on this function.  

Turn off Out Function: When this function is on, press FUNCTION button to select Out. 
 “ icon will 

blink. Then press ENTER/CANCEL button to turn off this function 

15) Remote Shield Function  

Remote Shield Function: Remote monitor or central controller can disable the relevant functions of wired 

controller so as to realize the function of remote control.  

Remote Shield Function includes all shield and partial shield. When All Shield function is on, all controls of 

the wired controller are disabled. When Partial Shield function is on, those controls that are shielded will be 

disabled. 

When the remote monitor or central controller activates Remote Shield on the wired controller, 
 

icon will show. If user wants to control through the wired controller, 
  icon will blink to remind that 

these controls are disabled. 

16) Child Lock Function  

When unit is turned on normally or turned off, pressing“
∧”or“∨” button together for 5 seconds will turn on 

Child Lock function.
 will show on the display. Pressing “
∧”or“∨” together again for 5 seconds to turn off 

this function.  

All the other buttons will be disabled when Child Lock function is on.  

17) Gate-control Function  

      Ultra Heat GMV Multi VRF 

for North America

33

CONTROL

Sayfa 36

Ultra Heat GMV Multi VRF 

for North America

When there is Gate-control System, user can insert a card to turn on the unit or pull off a card to turn off the 

unit. When the card is re-inserted, the unit will recover the operation as state in memory. When the card is pulled 

off (or improperly inserted), 
 icon will show. 

2.5 Error display 

When there occurs any error during operation, the temperature display zone on the wired controller will show 

error codes. If several errors happen at the same time, error codes will show on the display repeatedly.  

Note: If error occurs, please turn off the unit and send for professionals to repair.  

The display of Outdoor Unit High Pressure Protection when unit is on is shown as follow: 

3 Remote Controller

(1) Remote controller YAD1F

                 
                 
34

CONTROL

Sayfa 37

1) Button name and function introduction (outside)

No.
Button name
Function
1
ON/OFF
Turn on or turn off the unit
2
FAN
Set fan speed
3
▲/▼
Set temperature and time
4
COOL
Set cooling function
5
HEAT
Set heating function
6
SWING
Set swing status
7
TURBO
Set turbo function

2) Button name and function introduction (inside)

No.
Button name
Function

1
MODE
Set operation mode

2
TIMER ON
Set timer on function

3
TIMER OFF
Set timer off function

4
LIGHT
Set light function

5
I FEEL
Set I FEEL function

6
X-FAN
Set X-FAN function

7
TEMP
Switch temperature displaying type on the unit’s display

8
HEALTH
Set health function

9
CLOCK
Set clock of the system

10
SLEEP
Set sleep function

(2) Remote controller YV1L1

No.
Button name
Function

1
ON/OFF
Turn on or turn off the unit

2
FAN
Set fan speed

3
▲/▼
Set temperature and time

4
MODE
Set operation mode

5
Set quiet function

6
Set health function and air function

7
Set left&right swing status

8
Set up&down swing status

9
X-FAN
Set X-FAN function

10
TIMER ON
Set timer on function

11
TIMER OFF
Set timer off function

12
SAVE
Set energy-saving function

13
SLEEP
Set sleep function

14
LIGHT
Set light function

15
CLOCK
Set clock of the system

16
I FEEL
Set I FEEL function

17
TEMP
Switch temperature displaying type on the unit’s display

      Ultra Heat GMV Multi VRF 

for North America

35

CONTROL

Sayfa 38

Ultra Heat GMV Multi VRF 
 
for North America

INSTALLATION

36

Sayfa 39

INSTALLATION
1 Engineering Installation Preparation and Notice
1.1 Installation notice

Personnel and property safety are highly concerned during the entire installation process. Installation implementation must abide by 
relevant national safety regulations to ensure personnel and property safety.  

All personnel involved in the installation must attend safety education courses and pass corresponding safety examinations before 
installation. Only qualified personnel can attend the installation. Relevant personnel must be held responsible for any violation of the 
regulation.
1.2 Installation key points and importance

VRF air conditioning systems use refrigerant, instead of other agent, to directly evaporate to carry out the system heat. High level 
of pipe cleanness and dryness is required in the system. Since various pipes need to be prepared and laid out onsite, carelessness or 
maloperation during installation may leave impurities, water, or dust inside refrigerant pipes. If the design fails to meet the requirement, 
various problems may occur in the system or even lead to system breakdown.

Problems that usually occur during installation are as follows:

No.
Installation Problem
Possible Consequence

1
Dust or impurities enter into the 

refrigeration system.

2
welding.

3
The vacuum degree in the refrigerant pipe The refrigeration performance is reduced. The system fails to keep normal operation 

4
Water enters into the refrigeration system.
with abnormal noise generated; failures may occur in the system due to ice plug. 

5

6
Refrigerant pipe is blocked.

7
Refrigerant pipe exceeds the limit.
harmful for long-term running of the system.

8

9
The refrigerant pipe leaks.
of the air conditioner. Long-term operation under such circumstance may cause an 

10
Water drainage from the condensate water 

pipe is not smooth.

11
The ratio of slop for condensate water pipe 

is incorrectly connected.

12
The air channel will deform; vibration and noise occur during unit operating.

13
The guide vane of air channel is not 

reasonably manufactured.

       Ultra Heat GMV Multi VRF   

for North America

Pipes are more likely to be blocked; air conditioning performance is reduced; 
compressor wear is increased or even hinder the normal operation of the system and 

burn the compressor.  

Pipes are more likely to be blocked; air conditioning performance is reduced; 
compressor wear is increased or even hinder the normal operation of the system and 

burn the compressor.  

due to frequent protection measures. When the problem getting serious, compressor 

and other major components can be damaged.

materials and can also reduce the cooling performance.

The cooling performance is reduced; in certain cases, it may cause long-term 
compressor operating under overheat conditions; the lubricating effect can be 

affected and the compressor may be burnt if impurities were mixed with the 

lubricating oil.

to the compressor.

overheating compressor or even damage the compressor.

Residual water in IDUs can affect the normal operation of the system. The possible 

water leakage can damage the IDU's decoration.

Reverse slop or inconsistent connection of condensate water pipe can hinder the 

smooth drainage and cause leakage of the IDU.

Uneven air quantity allocation reduces the overall performance of the air conditioner.

37

Sayfa 40

 
for North America
Ultra Heat GMV Multi VRF 

14
The refrigerant pipe or condensate 
water pipe does not meet the insulation 

requirement.

15
The installation space for IDU is 
Since there is a lack of space for maintenance and checking, indoor decoration might 

16
The IDU or the location of the air outlet or 
return air inlet is not designed reasonably.

17
The ODU is improperly installed.

18
Power cables are incorrectly provided.
Unit components may be damaged and potential safety hazard may occur.

19
Control communication cables are 

incorrectly provided or improperly 

connected.

20
Control communication cables are not 

be started up due to communication failure. 
2 Installation Materials Selection

properly protected.

The materials, equipment and instruments used during air conditioning engineering construction must have certifications and test 

compulsory standards.  If environmentally-friendly materials are to be used as required by customers, all such materials must meet national 

2.1 Refrigerant piping

(1)  Material requirement: Dephosphorization drawing copper pipe for air conditioners;
(2) Appearance requirement: The inner and outer surface of pipe should be smooth without pinhole, crack, peeling, blister, inclusion, 

(3) 
(4) The tensile strength must be at least 240 kgf/mm².
(5) 

R410A Refrigerant System
OD (mm/inch)
Wall Thickness (mm)
Model
ĭ
•
0
ĭ
•
0
ĭ
•
0
ĭ
•
0
ĭ
•
0

(6)  After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed tightly by using pipe caps, plugs or 

adhesive tapes. 
2.2 Condensate water pipe

(1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R pipe, PP-C pipe, and HDG steel pipe;
(2) 
(3) 
WDWHUVXSSO\LQJ839&SLSHĭPPîPP,ĭPPîPP,ĭPPîPP
+'*VWHHOSLSHĭPPîPP,ĭPPîPP,ĭPPîPP,ĭPPîPP
(4) 
WDWHUVXSSO\LQJ839&SLSHĭPPîPPĭPPîPPĭPPîPP
+'*VWHHOSLSHĭPPîPPĭPPîPPĭPPîPPĭPPîPP
2.3 Insulation material

(1) Rubber foam insulation material;
(2)  Flame retardancy level: B1 or higher;
(3) Refractoriness: at least 120oC;
(4) The insulation thickness of condensate water pipe: at least 10 mm;
(5) When the diameter of copper pipe is equal to or greater than ĭ mm, the thickness of insulation material should be at least 20 

mm; when the diameter of copper pipe is less than 15.9 mm, the thickness of insulation material should be at least 15 mm.
2.4 Communication cable and control cable

38

Water can easily condensate and drip to damage the indoor decoration, or even 

trigger the protection mode of system due to overheating operation.  

need to be damaged during such operation.

The air outlet or return air inlet may be short-circuited, thus affecting the air 

conditioning performance.

heat exchanging performance or even prevent the system from normal operation; in 

addition, the cold and hot air for heat exchange and the noise may annoy people in 

surrounding areas.

The normal communication in the system fails or the control over IDUs and ODUs 

turn in a mess.

The communication cables are short-circuited or disconnected, and the unit cannot 

Sayfa 41

NOTICE!: For air conditioning units installed in places with strong electromagnetic interference, shielded 

wire must be used as the communication cables of the IDU and wired controller, and shielded twisted pairs must 

be used as the communication cables between IDUs and between the IDU and ODU.

 Communication cable selection for ODU and IDUs.

Communication Cables 
Between IDU and Indoor 

Number of Wire Pieces x 

Wire Type

Wire Diameter (mm2)
Wire Standard
Remark

(Outdoor) Unit L(m)

Common sheath twisted 

pair copper core (RVV)
/”
•î
GB/T

Communication cable selection for IDU and wired controller

Total Length of 
Communication Cables 

Number of Wire Pieces x 

Wire Type

Wire Diameter (mm2)
Wire Standard
Remark

of the IDU and Wired 

Controller L(m)

Common sheath twisted 

pair copper core (RVV)
/”
•î
GB/T
communication length 
FDQQRWH[FHHGP

2.5  Power cable

Only copper conductors can be used as power cables. The copper conductors must meet relevant national standard and satisfy the 
carrying capacity of unit.
2.6 Hanger rod and support

+DQJHUURG0RU0
(2) 8VWHHORUDERYH
(3)   $QJOHVWHHOPPîPPîPPRUDERYH
5RXQGVWHHOĭPPRUDERYH
3 Installation of outdoor unit
3.1 Check before installation

Before installation please check the power cord if it complies with the power supply requirement on the nameplate. Make sure the 

power supply is safe.
(2) This air conditioner must be properly grounded through the receptacle to avoid electric shock. The ground wire shouldn’t be 

FRQQHFWHGZLWKJDVSLSHZDWHUSLSHOLJKWQLQJDUUHVWHURUWHOHSKRQHOLQH
(3) Maintain good air circulation to avoid lacking oxygen.
Read this manual carefully before installation.
3.2 Selection of installation site

 Select a location which is strong enough to hold unit’s weight so that unit can stand still and erect.
(2)  Make sure the unit is not exposed to sun and rain. $QGWKHORFDWLRQFDQUHVLVWGXVWW\SKRRQDQGHDUWKTXDNH
(3) 
 Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with good ventilation.
ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and reduce bend angles.
(6) Select a location which is out of children’s reach. Keep the unit away from children.
3.3 Carrying and installing outdoor unit

DQJHORIURSHVPXVWEHVPDOOHUWKDQžGXULQJKDQJLQJDQGPRYLQJ
3.4 Installation notices
 ,QRUGHUWRHQVXUHSURSHURSHUDWLRQWKHVHOHFWLRQRILQVWDOODWLRQVLWHPXVWFRQIRUPWRWKHIROORZLQJSULQFLSOH
 
 

LQOHWDQGDLURXWOHW,IWKHUHLVDQ\REVWDFOHSOHDVHUHPRYHLW
 The installation site shall be able to withstand the weight of outdoor unit and capable for soundproof and vibration. The air outlet 

and noise of unit will not afIHFWQHLJKERUV
 The hanging of outdoor unit must use appointed hanging hole. Pay attention to protect the unit during hanging and installation. 

Prohibit hitting the sheet metal to avoid rust in the future. 
 AYRLGGLUHFWVXQOLJKW
 7KHUDLQDQGFRQGHQVDWLRQZDWHUFDQEHGUDLQHGRXWVPRRWKO\

 
for North America
       Ultra Heat GMV Multi VRF 

If the wire diameter is 
HQODUJHGWRîPPWKH

overall communication 
OHQJWKFDQUHDFKP

39

Sayfa 42

Ultra Heat GMV Multi VRF 

 
for North America

 
◆The outdoor unit will not be embedded by the snow and not affected by garbage and oil smog;

 
◆The installation of outdoor unit shall adopt rubber damping pad or spring damper to reduce noise and vibration;

 
◆

installation site;
 
◆The installation shall be done by professional technicians.
3.5 Fixing and damping of unit

caused.

between the unit and foundation.
3.6 Outline dimension and position of installation hole

angel of ropes must be smaller than 40º during hanging and moving.

Model
A
B
C
D
E

GMV-36WL/B-T(U)
GMV-48WL/B-T(U)
900(35-3/8)
340(13-3/8)
1345
(53)
572(22-1/2)
378
(15)

3.7 Installation space requirement

If all sides of the ODU (including the top) are surrounded by walls, process according to the following requirements for installation 
space:

Wall

ı350mm
˄13-3/4inch˅

ı200mm
ı200mm

˄8inch˅
ı350mm

˄8inch˅

ı2000mm

˄78-3/4inch˅

Wall

4 Installation of indoor Unit

4.1 Installation of quiet design duct type indoor unit

40

Unit:mm(inch)

Wall

ı200mm

˄8inch˅

ı2000mm

˄78-3/4inch˅
˄13-3/4inch˅

Shockproof 
material

Wall

Sayfa 43

 
for North America
       Ultra Heat GMV Multi VRF 

4.1.1 Low Static Pressure Duct Type Unit 

The following diagram is applicable for units with the cooling capacity ranging from 7 k Btu/h to 22 k Btu/h. 

Gas pipe
Liquid pipe
Electric box

Drain pipe

The following table lists the detailed dimensions.                       

 Unit: mm(inch)
                              Item 
 Model
A
B
C
D
E
F
G
H
I

GMV-ND07PLS/A-T(U)
GMV-ND09PLS/A-T(U)
GMV-ND12PLS/A-T(U)

742
(29-1/5)

491
(19-1/3)

700
(27-5/9)

615
(24-1/5)

200
(7-7/8)

121
(4-3/4)

528
(20-4/5)

161
(6-1/3)

580
(22-5/6)

GMV-ND14PLS/A-T(U)
942121
(37)

491
(19-1/3)

900
(35-3/7)

615
(24-1/5)

200
(7-7/8)

121
(4-3/4)

728
(28-2/3)

161
(6-1/3)

780
(30-5/7)

GMV-ND18PLS/A-T(U)
GMV-ND22PLS/A-T(U)

1142
(45)

491
(19-1/3)

1100
(43-1/3)

615
(24-1/5)

200
(7-7/8)

121
(4-3/4)

928
(36-1/2)

161
(6-1/3)

980
(38-4/7)

4.1.2 Installation space

150(6)

4.1.3 Installation notice

(1) 
(2)  Installation foundation

(3)  Installation site and environment
Keep the unit from insolation and rain;

Please reserve ventilation space;

Please take proper measures to reduce noise and vibration.
(4) Electrical installation of unit

41

Sayfa 44

Ultra Heat GMV Multi VRF 

 
for North America

All electrical installation must be done by professionals according to national and local laws and regulations.
The unit must be grounded reliably. Please connect wire according to the wiring diagram on the unit.
4.2 Four-way Cassette Indoor Unit
4.2.1Requirements for external dimensions and installation and maintenance spaces

D (Distance between lifting screws)

Refrigerant 
pipe

A (Decoration panel)

B (Ceiling aperture)

C (Indoor units)

Lifting screw

D (Distance between lifting screws)

C (Indoor units)

B (Ceiling aperture)

A (Decoration panel)

D (Distance between lifting screws)

Refrigerant 
pipe

A (Decoration panel)

B (Ceiling aperture)

C (Indoor units)

Lifting screw

D (Distance between lifting screws)

C (Indoor units)

B (Ceiling aperture)

A (Decoration panel)

   Unit: mm(inch)

Model
A
B
C
D
E
G
H

950
(37-2/5)

890
(35)

840
(33)

680
(26-7/9)

780
(30-5/7)

65
(2-5/9)

210
(8-1/4)

GMV-ND07T/A-T(U)

GMV-ND09T/A-T(U)
GMV-ND12T/A-T(U)

950
(37-2/5)

890
(35)

840
(33)

680
(26-7/9)

780
(30-5/7)

65
(2-5/9)

260
(10-1/4)

GMV-ND15T/A-T(U)

GMV-ND18T/A-T(U)
GMV-ND24T/A-T(U)

GMV-ND30T/A-T(U)
GMV-ND36T/A-T(U)
GMV-ND42T/A-T(U)
GMV-ND48T/A-T(U)

840
(33)

680
(26-7/9)

780
(30-5/7)

65
(2-5/9)

340
(13-2/5)

950
(37-2/5)

890
(35)

42

Sayfa 45

4.3 Installation of wall-mounted indoor unit
4.3.1 Outline and installation dimension

Model
W
H
D

GMV-N07G/A3A-D(U)
GMV-N09G/A3A-D(U)
843(33-1/5)
275(10-5/6)
180(7)

GMV-N12G/A3A-D(U)
GMV-N18G/A3A-D(U)
940(37)
298(11-3/4)
200(7-7/8)

GMV-N24G/A3A-D(U)
1008(39-2/3)
221(8-5/7)
319(12-5/9)

4.3.2 Installation space
໽㢅ᵓ
໽㢅ᵓ

ഄ䴶
ഄ䴶

4.3.3 Installation notice

(1) 
(2)  Installation foundation

(3) Installation site and environment
Keep the unit from insolation and rain;
Water can be drained from drainage pipe conveniently;

There can’t be any obstacle at air inlet and air outlet to in order to keep good ventilation;

Please take proper measures to reduce noise and vibration.
4.3.4  Electrical installation of unit

All electrical installation must be done by professionals according to national and local laws and regulations.
The unit must be grounded reliably according to related requirements in GB 50169. 
Please connect wire according to the wiring diagram on the unit.
5 Installation of Electronic Expansion Valve Assy (unit with external EXV)

The EXV of indoor unit is built-in.

 
for North America
Ultra Heat GMV Multi VRF 

 Unit: mm(inch)

๭
ຕ

43

Sayfa 46

 
for North America
Ultra Heat GMV Multi VRF 

6 Installation of Refrigerant Pipeline
6.1Allowable Length and Height Difference of Connection Pipe

NOTICE! Equivalent length of one Y-type branch is 0.5m(1-5/8feet).

ODU

L1

a
The 1  branch section

st 

IDU

L2

L3

Piping parameters of GMV-36WL/B-T(U) ǃGMV-48WL/B-T(U):

Allowable value(m/feet)
Fitting pipe

300(984)
L1+L2+L3+a+b+c+d

Actual length
120(394)
L1+L2+L3+d
Equivalent length
150(492)

(m)

st branch to the farthest indoor pipe
40(131)
L2+L3+d

From the 1

ODU at upper side
50(164)
—

Height difference between 

ODU and IDU

ODU at lower side
40(131)
—

Height difference between IDUs
15(49)
—

6.2 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch

Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of outdoor connection pipe.

44

Sayfa 47

Ultra Heat GMV Multi VRF 

 
for North America

ODU

The 1   indoor branch
st

st

Pipe between ODU and the 1   indoor branch

Dimension of outdoor connection pipe:

Pipe dimension

Basic module

Connection method
Gas pipe (mm/inch)
Liquid pipe(mm/inch)

GMV-36WL/B-T(U)
ĭ
ĭ

Flared joint
GMV:/%78
ĭ
ĭ

6.3 Selection of Indoor Branches

Select indoor branches according to the total capacity of downstreDPLQGRRUXQLWV

Indoor branches

ODU

IDU

R410A  Refrigerant system
Total capacity of downstream indoor units C  (Btu/h) 
Model

Y type branch
C

FQ01A

6.4 Dimension of Pipe between Indoor Branches

Select pipe between indoor branches according to the capacity of downstream indoor units; if the capacity exceeds that of the outdoor 
XQLWFDSDFLW\RIRXWGRRUXQLWSUHYDLOV

45

Sayfa 48

 
for North America
Ultra Heat GMV Multi VRF 

Pipe between 
indoor branches

ODU

IDU

Total capacity of downstream indoor units C (Btu/h) 
Gas pipe(mm/inch)
Liquid pipe(mm/inch)

C İ 19000
ĭ
ĭ

19000 ˘ C İ 
ĭ
ĭ

 ˘ C İ 
ĭ
ĭ

6.5 Dimension of Pipe between Indoor Branch and IDU

Dimension of pipe between indoor branch and IDU should be consLVWHQWZLWKWKHGLPHQVLRQRILQGRRUSLSH

Indoor branches

ODU

Pipe between indoor branch and IDU

IDU

Rated capacity of IDU C (Btu/h) 
Gas pipe(mm/inch)
Liquid pipe(mm/inch)

C İ 9600
ĭ
ĭ

9600 ˘ C İ 
ĭ
ĭ

 ˘ C İ 48000
ĭ
ĭ

48000 ˘ C İ 
ĭ
ĭ

 ˘ C İ 96000
ĭ
ĭ

NOTICE! If the distance between IDU and its nearest branch is over 10m(33feet), then the 
OLTXLGSLSHRI,'8UDWHGFDSDFLW\”%WXKVKDOOEHHQODUJHG

46

Sayfa 49

7  Installation of the Connection Pipe

1) Conform to the following principles during pipe connection: Connection pipe should be as short as 
possible, so is the height difference between indoor and outdoor units. Keep the number of bends as little 
as possible. Radius of curvature should be as large as possible.
2) Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for 
welding process. Rosin joint or pin hole is not allowed.
3) When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm(8inch). 
Note that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not 
bend or stretch the pipe for more than 3 times at the same position.

7.1 Flaring Process

1) Use pipe cutter to cut the connection pipe in case it is unshaped.
2) Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after cutting.
3) 
4) 

7.1.1 Pipe Bending

1) Reshape the pipe by hand. Be careful not to damage the pipe.

Correct
Wrong
                                                                    
2) Do not bend the pipe over 90°.
3) 
bend for over 3 times.
4) 
bend the pipe until it is exposed. When bending is done, wrap the pipe with insulating layer and then secure it with adhesive tape.
7.1.2 Indoor Pipe Connection

1) Remove pipe cover and pipe plug.
2) 

3) 
at right angle to the pipe. 

1) Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic 
tape.

 
for North America
       Ultra Heat GMV Multi VRF 

d1

d1

d2

90°±1°

d2

47

Sayfa 50

 
for North America
Ultra Heat GMV Multi VRF 

2) Connection pipe should be supported by a bearer rather than the unit.

3) The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use 
a pipe bender to bend the pipe.

4) When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case 
the capillary tube or other tubes have cracks and cause leakage.

Pipe dimension
Tightening torque

90
o

6mm(1/4inch)

1‡P1-22ft.-1b.)

9.5mm(3/8 inch)

1‡PIWE)

Torque
wrench
Common
wrench

12.7mm(1/2 inch)

1‡PIWE)

16mm(5/8 inch)

1‡PIWE)

7.1.3 Outdoor Pipe Connection

Below is the piping diagram of GMV-36WL/B-T(U),GMV-48WL/B-T(U). According to customer requirement or space limit, outlet pipe 
can be installed from the front, right or rear side.

Gas pipe

Liquid pipe

Flared nut

7.1.4 Installation of Y-type Branch

1)  Y-type Branch

to other branches or IDUs
type branch

Outlet 1

Inlet

ODU

Field supplied
Field supplied

Outlet 2

48

Sayfa 51

 
for North America
       Ultra Heat GMV Multi VRF 

2) Y-type branch has several pipe sections with different dimension, which facilitates to match with various copper pipes. Use pipe 
cutter to cut in the middle of the pipe section that is of proper dimension and remove burrs as well. 
3) Y-type branch must be installed vertically or horizontally.
4) Branch shall be isolated by insulating material that can bear 120° or even higher temperature. The attached foam of branch cannot 
be taken as insulating material.

Within ±30°

Within ±30°

o

Cut in the middle

NOTICE! Branch shall be isolated by insulating material that can bear 120

OF)or even 
higher temperature. The attached foam of branch cannot be taken as insulating material.
7.1.5 Thermal Insulation for Pipeline

OC(248

1)  For multi VRF system, every copper pipe should be labeled so as to avoid misconnection.
2)  At the branch inlet, leave at least 500mm(19-3/4inch)straight pipe section.
3)  Thermal insulation for pipeline.

ķ . To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid pipe must be wrapped with thermal insulating 

material and adhesive tape for insulation from the air.

ĸ . Thermal insulating material shall be able bear the pipe temperature. For heat pump unit, liquid pipe should bear 70

OC or above and 
gas pipe should bear120

OC or above.
      Example: Polyethylene foam (bear 120

OC or above. For cooling only unit, both liquid pipe and gas pipe should bear 70

OC or above); foaming polyethylene (bear 100

OC or above).

Ĺ . Joints of indoor and outdoor unit should be wrapped with insulating material and leave no gap between pipe and wall. 

Thermal insulating layer is required to be wrapped at this part.

Thermal insulating pipe
No gap

ĺ . Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of branches cannot be taken 

as insulating material.

Ļ . When wrapping the tape, the later circle should cover half of the former one. Don’t wrap the rape too tight, otherwise the insulation 

effect will be weakened.

ļ . After wrapping the pipe, apply sealing material to completely seal the hole on the wall.

49

Sayfa 52

 
for North America
Ultra Heat GMV Multi VRF 

1) Thermal insulating material shall be able bear the pipe temperature. For heat pump unit, liquid pipe 
should bear 70

oF) or above. For cooling only 
unit, both liquid pipe and gas pipe should bear 70

oC(158

oF) or above and gas pipe should bear 120

oC(248

oC(158

oF) or above.

2) Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of 
branches cannot be taken as insulating material.

7.1.6 Support and Protection of Pipeline

1) Support should be made for hanging connection pipe. Distance between each support cannot be over 
1m(3-1/4feet).
2) Protection against accidental damage should be made for outdoor pipeline. When pipeline exceeds 
1m(3-1/4feet), a pinch board should be added for protection.
7.2  Disassembly of Compressor Feet

factory. 

Compressor

Binding nut 

Metal pieces

Fasten the nut after removal
Metal pieces

When installing the unit, metal pieces for transportation must be removed. Then fasten the binding nuts again and wrap back 

s operating life will be shortened.
7.3 Vacuum Pumping, Refrigerant Adding

Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra refrigerant in the outdoor unit 
for air purging! 

7.3.1Vacuum Pumping

1) Outdoor unit has been charged with refrigerant before delivery. Field-installed connection pipe needs to be charged with additional 
refrigerant.
2) 
3) Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the outdoor valve, as shown below.

50

Sayfa 53

       Ultra Heat GMV Multi VRF 

 
for North America

Manometer

Manometer

HI knob

LO knob

Liquid valve

Vacuum pump

Connection hose

Gas valve

7.3.2 Refrigerant Adding 

(1) Refrigerant quantity of outdoor unit before delivery:

Mode
GMV-36WL/B-T(U)
GMV-48WL/B-T(U)

Refrigerant Qty (kg/oz)
6.5(229)
6.5(229)

1) The refrigerant amount charged before delivery doesn’t include the amount that needs to be added to indoor units and the 
connection pipeline.

2) Length of connection pipe is decided on site. Therefore the amount of additional refrigerant shall be decided on site according to 

3) Record the amount of additional refrigerant for convenience of after-sales service.

(2) Calculation of the amount of additional refrigerant
Calculation method of the quantity of additional refrigerant (based on liquid pipe)

4XDQWLW\RIDGGLWLRQDOUHIULJHUDQW ™OHQJWKRIOLTXLGSLSH;Tuantity of additional refrigerant per meterr(39-3/8inch)

Diameter of liquid 

pipe
(mm/inch)

ĭ)
ĭ)
ĭ)
ĭ)
ĭ)
ĭ

kg/m



11



oz/inch







NOTICE! Liquid pipe that is within 20m(65-5/8feet) doesn’t need to be added with refrigerant.

3) Calculation example

51

Sayfa 54

 
for North America
Ultra Heat GMV Multi VRF 

ODU

IDU

Indoor

No.
Indoorķ
Indoorĸ
Indoor Ĺ
Indoorĺ

Model
Duct type 

Duct type 

Duct type 

Duct type

GMV-ND18PLS/A-T(U)

GMV-ND12PLS/A-T(U)

GMV-ND09PLS/A-T(U)

 GMV-ND09PLS/A-T(U)

Liquid pipe:

 No.
A
B
C
D

Pipe size
ĭPPLQFK)
ĭPPLQFK)
ĭPPLQFK)
ĭPPLQFK

/HQJWK
PIHHW
PIHHW
PIHHW
PIHHW

 No.
a
b
c
d

 Pipe size
ĭPPLQFK)
ĭPPLQFK)
ĭPPLQFK)
ĭPPLQFK

/HQJWK
PIHHW
PIHHW
PIHHW
PIHHW

TRWDOOHQJWKRIHDFKOLTXLGSLSH
ĭ9.52: $%&D  P IHHW
ĭ'EFG  1PIHHW
NOTICE! Liquid pipe that is within 20m(65-5/8feet)doesn’t need to be added with refrigerant.

7KHUHIRUHWKHPLQLPXPTXDQWLW\RIDGGLWLRQDOUHIULJHUDQW î1î NJR]
8 Installation of Condensate Pipes
8.1  Ensure an inclination degree of more than 1% when connecting the drain pipe to the IDU.

(mm)

1000~1500

Inclination degree 
RIPRUHWKDQ1/100

Correct connection
Incorrect connection

IDFLOLWDWHIXUWKHUPDLQWHQDQFH

:KHQFRQQHFWLQJWKHGUDLQSLSHEUDQFKHVWRWKHPDLQSLSHOHDGWKURXJKIURPWKHDERYHSDUWRIWKHPDLQSLSH
,IWKH air YROXPH RIWKH IDUs is KLJK and outdoor air resorption PD\ be caused by QHJDWLYH suction SUHVVXUH SURYLGH a u-type drain trap 

52

Sayfa 55

Indoor unit

‹
‹ Install a drain trap connector for each unit.
‹ The drain trap connector shall be installed in a way that facilitates trap cleaning.

Indoor unit
Indoor unit

Connector

8.1.5 During condensate water pipe installation, ensure a distance above 500 mm between the pipe and the electric box of the unit for 

8.2. Requirements on Installation of Drain Pipes for Different Types of IDUs
8.2.1 Drain Pipe Installation for Hidden Air-duct-type IDU for Air Supply

a. Ensure an inclination degree of greater than 1% when connecting the drain pipe to the IDU.

maintenance.
c. There is a condensate water outlet on both sides of the IDU. After one condensate water outlet is determined, use the 
rubber stopper to block the other outlet. Tie it with threads and strap with insulation materials to prevent leakage.

Bands
PVC pipe for the unit

Drain pipe for the unit
Drain hose

e. Apply insulation materials to the condensate water pipe joints to prevent dewing. d. Insulation for connection between the 

 
for North America
Ultra Heat GMV Multi VRF 

Connector

53

Sayfa 56

 
for North America
Ultra Heat GMV Multi VRF 

8.2.2 Drain Pipe Installation for IDU

a. Use pipe clips instead of applying glue to connect the hoses provided upon delivery and plastic pipes on the device. 
Connect the other end of the joint to the elbow. The height from the suction inlet of the discharge pump is about 200 to 500 
mm. Ensure a proper inclination degree while connecting to the main drain pipe.

8.3. Requirements on Independent Drainage for Each IDU

Requirements on independent drainage design for each IDU are as follows:
a. There must be a proper inclination for the drain pipe.
b. The drain pipe must be installed to facilitate drainage to the largest extent and be as short as possible.
c. If the water is discharged to the outdoor side, it cannot drop to the outdoor ground directly. 
8.4. Requirements on Centralized Drainage for IDUs

a. When there are multiple IDUs in the same building, centralized drainage is adopted.
b. When a header pipe is used, the drain pipe of each IDU must be higher than the header pipe.
c. The diameter of the header pipe must be determined on the number and capacity of IDUs.

condensate water.
e. Connect branches to the main pipe from the upper part or side instead of lower part of the main pipe.
f. Insulate all condensate water pipes, especially for joints at elbows.
9 Electric Wiring

1) All electrical installation must be performed by qualified technicians in accordance with local laws, 
regulations and this user manual.

2) Use air conditioner specialized power supply and make sure that it is consistent with system’s rated 
voltage. 

3) Do not pull the power cord with force.

4) Caliber of the power cord must be large enough. A damaged power cord or connection wire must be 
replaced by specialized electrical cords.

54

Insulation layer for the 
condensate water pipe

Pipe cover

Roof

Hanger 
bracket
Within 300 mm

Drain hose 
(accessory)
Raising pipe for 

drainage

Less than 
1000 mm

Ceiling
Clip (accessory)

Sayfa 57

5) Connect the unit to specialized grounding device and make sure it is securely grounded. It’s a must to 
install air switch and current circuit breaker that can cut off the power of the entire system. The air switch 
should include magnetic trip function and thermal trip function so that system can be protected from short 
circuit and overload.

6) Air conditioner belongs to class I electrical appliance, so it must be securely grounded.

7) The yellow-green wire inside the unit is a ground wire. Do not cut it off or secure it with tapping screws, 
otherwise it will lead to electric shock.

8) Power supply must include secure grounding terminal. Do not connect the ground wire to the following: 
Water pipe˗Gas pipe˗Drain pipe˗Other places that are deemed as not secure by professional 
technicians.

9.1Wiring Diagram

1) Connection of power cord and communication wire

Separate power supply for Indoor and Outdoor

NOTICE! The remote monitor can be installed when it is necessary. The wire 
(match with resistance) must be connected with ODU (see a and b) only the 
remote monitor is installed.  

a Connection of power cord and communication wire for IDU and one ODU 

       Ultra Heat GMV Multi VRF 

for North America

55

Sayfa 58

 
for North America
Ultra Heat GMV Multi VRF 

b Connection of power cord and communication wire for IDU and multi ODUs 

NOTICE! : ODU n(Max)=16. The wire (match with resistance) must be 

connected with the last ODU. 

56

Sayfa 59

2) The wiring diagram for power cord of outdoor unit and communication wire. 

Wiring of the Power Cord 

(1) Open the side plate. 

(2) Connect the power cord to the terminals “L1”, “L2” and also the earthing screw, 

and then connect the communication line “D1,D2” of the indoor unit to those of the 

outdoor unit correspondingly. The communication line “G1, G2” could be used to 

connect the remote monitor. Please use the bonding screw to connect the earthing 

cord. The location is showing in the Fig.  

(3) Fix the power cord and communication line with wire clips. 

(4) Let the power cord and communication line go through the rubber ring. 

       Ultra Heat GMV Multi VRF 

for North America

57

Sayfa 60

Ultra Heat GMV Multi VRF 

 
for North America

9.2 Power Cable Wire Gauge and Circuit Breaker Selection
9.2.1 Outdoor

Max Fuse Size/

Max Ckt, Bkr Size/
Disjoncteur Max.(A)
Min. Circuit Ampacity

Model
Power supply

Fusible Max.

(A)

GMV-36WL/B-T(U)
208/230V~ 60Hz
50
50
45

GMV-48WL/B-T(U)
208/230V~ 60Hz
50
50
45

9.2.2 Indoor

(1) Low Static Pressure Duct Type Indoor Unit

Model
GMV-ND07PLS/

GMV-ND09PLS/

GMV-ND12PLS/

GMV-ND14PLS/

GMV-ND18PLS/

GMV-ND22PLS/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

MCA
A
0.25
0.25
0.25
0.38
0.63
0.63

MOP
A
0.45
0.45
0.45
0.68
1.13
1.13

(2) 4-way Cassette Indoor Unit

Model
GMV-ND07T/A-T(U)
GMV-ND09T/A-T(U)
GMV-ND12T/A-T(U)
GMV-ND15T/A-T(U)
GMV-ND18T/A-T(U)

MCA
0.25
0.31
0.31
0.31
0.31

MOP
0.45
0.56
0.56
0.56
0.56

Model
GMV-ND24T/A-T(U)
GMV-ND30T/A-T(U)
GMV-ND36T/A-T(U)
GMV-ND42T/A-T(U)
GMV-ND48T/A-T(U)

MCA
0.31
0.44
0.44
0.44
0.44

MOP
0.56
0.79
0.79
0.79
0.79

(3) Wall Mounted type Indoor Unit

Model
GMV-N07G/A3A-

GMV-N09G/A3A-

GMV-N12G/A3A-

GMV-N18G/A3A-

GMV-N24G/A3A-

D(U)

D(U)

D(U)

D(U)

D(U)

MCA
A
0.25
0.25
0.2625
0.2625
0.3875

MOP
A
0.45
0.45
0.4725
0.4725
0.6975
10 Debugging of Unit

Caution: 
ķ . 

can’t operate.

ĸ . The debugging must be performed by professional person or under the the guide of professional person.
10.1 Preparation for debugging 

(4) 
(5) All wires for controller and electric wires must be connected correctly and reliably. 

(6) 
(7) Remove all sundries from the unit, such as metal chips, joint, forceps holder, and so on. 
(8)  Check whether the appearance and pipeline system are damaged during carry or transportation process. 
(9)  Calculate the required added refrigerant-charging volume according to the length of pipe of system and pre-charge the refrigerant. 

If refrigerant can’t be added any more when the required refrigerant-charging volume hasn’t been reached, record to refrigerant 
volume which still needs to be added and continue to add refrigerant during run test operation process. Please refer to below run 
test for the refrigerant-adding stage during run test process. 
(10) After adding refrigerant, please make sure the valve for outdoor is opened completely. 
(11) For the convenient of troubleshooting, the unit can’t be connected to the PC which installed with related debugging software and 

make sure that the the datas in real time of this unit can be inspected by this computer. Please refer to Service Manual for the 
installation and connection of the bebugging software. 
(12) Before turn test, please do make sure that the preheat time for compressor is 8h above and touch the compressor to see whether 

preheat is normal. You can perform run test only after normal preheat. Otherwise, it may damage the compressor.  
10.2 Trial run 

10.2.1  Notice

(1) Before the trial running, make sure the unit is power on and compressor has been preheated for more than six hours. Touch the unit to 
      check whether it’s normally prehetated. Start test operation after unit is normally preheated,  otherwise compressor might be damaged.

(2) Before the test running, make sure the needed amount of refrigerant has been added to the pipe or at least 70% of the needed 

refrigerant has been added.  
(3) During the test running, system will operate according to the ambient temperature. 

1) When outdoor temperature is above 20ćdebugging shall be in cooling mode.

2) When outdoor temperature is below 20ćdebugging shall be in heating mode.

58

Sayfa 61

 
(4)  The test run should be carried out by the professionally skilled personnel on the premise that 

all items listed above are in normal conditions.

 
(5)  Let the unit energized and switch the wired controller or the remoter controller to “ON”.

 
(6)  

The fan motor and compressor of the outdoor unit will run automatically in three minutes. 

(7)

If there is some unusual so started, turn off the unit for an immediate check.
 

10.2.2  Check after Installation

Please check the following items before test operation. 

Items to be checked 
Possible malfunction 

Has it been fixed reliable? 
The unit may drop, vibrate or make noise. 

Has the gas leakage been checked? 
It may cause insufficient cooling(heating) 
capacity. 

Is the thermal insulation of the unit 
sufficient? 
It may cause condensation and dripping. 

Is the drainage well? 
It may cause condensation and dripping. 

Is the voltage in accordance with the rated 
voltage marked on the nameplate? 

Are the lines and pipelines correctly 
installed? 

Has the unit been safely grounded? 
It may cause electrical leakage. 

Are the models of lines in conformity with 
requirements? 

Are there any obstacles near the air inlet 
and outlet of the indoor and outdoor units? 

Have the length of connection pipes and 
refrigerant charge amount been recorded? 

1) 
Before test operation 
‹ The appearance of the unit and the refrigerant pipes cannot be damaged during the installation. 
‹ Do not switch on power before installation is finished completely. 
‹ Electrical wiring must be connected correctly and securely. 
‹ The stop valves of the outdoor unit should be opened fully. 
‹ All the impurities such as scraps and thrums must be cleared from the unit. 
2) 
Test operation method 
ķ The test operation should be carried out by the professionally skilled personnel on the premise that all items 

listed above are in normal conditions.  
ĸ Set the status of the power supply switch as “ON” six hours before the start of operation  
Ĺ Press mode button, to select the COOL, or HEAT. Whether the air conditioner is work normally or not. 

 
 
ĺ Make sure that every combination of indoor units can work well. 

Cautionʽ 

If the unit cannot work nor has any abnormal noise after the compressor is started, turn off the unit for an
immediate check. 

 
for North America

       Ultra Heat GMV Multi VRF 

It may cause electric malfunction or the 
components may be burned out 

It may cause electric malfunction or the 
components may be burned out 

It may cause electric malfunction or the 
components may be burned out 

It may cause insufficient cooling(heating) 
capacity. 

It is not easy to decide the charge amount of 
refrigerant. 

59

Sayfa 62

Ultra Heat GMV Multi VRF 

 
for North America

10.3 Testing Board Introduction

10.3.1 Compose of Testing Board 

The testing board is in front of electrical box and can be observed well. It has several following 
advantages: detect indoor unit numbers and indoor unit address, displays real running function and error 
code automatically. It is composed of the function section, data section, button section and DIP section.

60

Sayfa 63

Running 

state  
The display of function section 
The display of data section 

ķ The section will display the 
numbers of the indoor units which have 
established 
communication 
with 
the 
outdoor unit. For example, if there are 
twenty established indoor units, the 
section will display “20”. 

Stop 

ĸ It will display the address of the 
indoor units by turns. For example, the 
“44” is represented of the indoor unit’s IP. 

The code of running state: 

Code 
Running 

state 
Code 
Running 

UE 
Pressure 
equalization 
UH 
Heating 

Normal 

UP 
Pump down 
A4 
Oil 
returning 
UC 
Cooling 
A3 
Defrosting 

If the malfunction occurs in the 
system, the section will display the error 
code. If there are several malfunctions, it 
will display the error codes by turns at 
intervals of 2 seconds. 

Malfunction 

10.3.2

Button section
 

Key
Fuc
+
-
Enter
Back
SW1

Signification
Function
Increase
Decrease
Enter
Back
/

ķ
 
When entering the menu to set parameters, the function section will flash running codes and 

the data section will flash the current parameters. 
ĸ
 When the menu is set, the data section will flash “=”. After the “=” stops blinking, the unit will 
run the new parameters. 

 The flow chart of operation
 
10.3.3

 
for North America

       Ultra Heat GMV Multi VRF 

ķ If the function section displays the 
numbers of the indoor units, the data 
section 
will 
display 
the 
outside 
temperature. For example, the “35” is 
represented of 35ć. 

ĸ If the function section displays the 
address of the indoor unitˈthe data section 
will display the model of the indoor unit, 
for example, the “56” is represented of 56 
model. 

It displays the target gear of the 
compressor. If the gear is zero, it will 
display “0”. For example, the gear is the 
fifteenth; it will display “15”. The range of 
the gear is from 0 to 60. 

state 

ķ If the malfunction occurs in the 
outdoor unit, the section displays nothing; 
ĸ If the malfunction occurs in the indoor 
units, the section displays the address of 
the indoor unit.  

61

Sayfa 64

Ultra Heat GMV Multi VRF 

for North America

Initial state

Long press “Fuc” 
key for more than 2s

Switch with 

“+/ -”

Press “Enter”

Press “Enter”
Press “Enter”

Ft

OF/ON

CU

Press “Enter”
Press “Enter” Setting is done

Switch with 

AE

Hi/nor/Lo

“Fuc”

AC
Hi/nor/Lo
Setting is done
Press “Enter”
Press “Enter”

Switch with 

Press “Enter”
Press “Enter”

“Fuc”

A8
OF/ON
Setting is done

Press “Enter”
Press “Enter”

H1
OF/ON
Setting is done

Press “Enter”
Press “Enter”

A2
OF/ON
Setting is done

Press “Enter”

NH

Suction temperature

NP

Discharge temperature

d1

Switch with 

“Fuc”

PL

Low pressure

PH

High presuure

Note: 
ķ Long press “Fuc” key for more than 2s to enter the first-level menu. The first-level menu

includes control unit, display unit 1 and display unit 2. 
‹ Press “Enter” key to enter the second-level menu. 
‹ Press “Fuc” key to switch the menu. 
‹ Press “Back” key to the previous menu. 
ĸ Control unit (CU) operation: 

‹ When entering into the control unit: 

The function section flashes the running code and the data section display the current parameter
uninterrupted. 

‹ Set parameters: 

Press “Enter” key to enter the second-level menu, and set parameters with the “ˇ” “ˉ” keys.
Now the function section displays the running code uninterrupted and the data section flashes the set
parameters. 

‹ Finish setting: 

After press “Enter” key to the end, the function section will display the running code uninterrupted
and the data section display the set parameters uninterrupted. 

‹ Back: 

Press “Back” key to the previous menu, and long press the “Back” key to exit the operation. 

62

Setting is done

Sayfa 65

 
ķ Display unit 1 (d1) operation: 
‹ When entering into the display unit 1: 

The function section display running code uninterrupted and the data section display the current
value uninterrupted. 

‹ “ˇ” “ˉ”Keys are invalid in the operation. 
ĸ

If no operation is performed within 1min, it will automatically return to the normal display.

The code of data section
◆

For example: How to Display low pressure 
ķ Long press “Fuc” key for more than 2s to enter the first-level menu: the function section 

flashes “CU” code and the data section is blank. 
ĸ Switch with the “Fuc” key again: the function section flashes “d1” code and the data section is 

blank. 
Ĺ Press “Enter” key to enter the second-level menu: the function section flashes “NH” code and 

the data section display the current suction temperature. 
ĺ Switch with the “Fuc” key to display low pressure: the function section flashes “PL” code and 

the data section display the current low 

DIP section

The centralized control address DIP switch indicates the centralized control address required when different 
refrigerating systems are controlled in a centralized manner. The default factory setting is "0000000". 

If it is not required to use centralized control between multiple refrigerating systems, this DIP switch can 
retain the factory settings without being changed. 

If it is required to use centralized control between multiple refrigerating systems, set the DIP switch must be 
set as follows: 

DIP1
DIP2
DIP3
DIP4
DIP5
DIP6
DIP7
Address No.
0
0
0
0
x
x
x
0
1
0
0
0
x
x
x
1
0
1
0
0
x
x
x
2
1
1
0
0
x
x
x
3
0
0
1
0
x
x
x
4
1
0
1
0
x
x
x
5
0
1
1
0
x
x
x
6
1
1
1
0
x
x
x
7
0
0
0
1
x
x
x
8
1
0
0
1
x
x
x
9
0
1
0
1
x
x
x
10
1
1
0
1
x
x
x
11
0
0
1
1
x
x
x
12
1
0
1
1
x
x
x
13
0
1
1
1
x
x
x
14
1
1
1
1
x
x
x
15

       Ultra Heat GMV Multi VRF 

 
for North America

63

Sayfa 66

 
for North America

Ultra Heat GMV Multi VRF 

For example, Address No.4 of ODU setting as: 

Defines and differentiates addresses of different systems in the case of centralized control by multiple systems. 

The address DIP switch is used only when centralized control is required. Otherwise, the factory settings are 

used without being changed. 

CAUTION: Function DIP switch must be set when the ODU is powered off, and then the settings are valid after 
the ODU is powered on. 

The meaning of running code: 

Sorts 
Function 

section 
Data section 
Remarks 

Control Unit 
CU 
Blank 
 

Set evaporation 

temperature 
AE 
Default:N 

Set 
condensation 

AC 
Default:N 

temperature 

capacity, select H; else select L. 
Quickly check 
Ft 
The current parameter 
Use the “ˇ” “ˉ” keys to switch 
ON, OF. 

Vacuum 
operation 
A8 
The current parameter 

Set defrosting 

mode 
H1 
The current parameter 

Set refrigerant 
recovery mode 
A2 
The current parameter 

Display Unit 1 
d1 
Blank 

Suction temperature. 

Display suction 

temperature 
NH 

For example, 15 

represents 15ć 
Display 
discharge 
temperature 

Discharge temperature. 

NP 

For example, 70 

represents 70ć 

Low pressure. For 
example, 95 represents 

Display low 

pressure 
PL 

0.95Mpa 

High pressure. For 

Display high 

pressure 
PH 

example, 280 
represents 2.80Mpa 

64

Use the “ˇ” “ˉ” keys to switch L, N 
and H. 

If you want to get a higher cooling 

capacity, select L; else select H. 

Use the “ˇ” “ˉ” keys to switch L, N 
and H. 

If you want to get a higher heating 

ON represents that the unit is 
running the current state. 

OF represents that the unit isnot 
running the current state. 

“ˇ” “ˉ”Keys are invalid in the 

operation. 

Sayfa 67

10.4 Parameters reference value for the normal operation of unit 

No. 
Parameters name 
Unit 
Reference value 

1 
Outdoor 
temperature 
ć ̣
 

‹ After compressor is started up, normal discharge 

temperature for cooling is 60~105ć , which is 
10ć above more than the high pressure 
saturation temperature.  

2 
Discharge 

ć 

temperature 

‹ The normal temperature for heating is 50ć 

~100ć, which is 10ć above more than the high 
pressure saturation temperature. 

‹ Under the cooling mode at the ambient temperature 

of 25~40ć , the high pressure value of the system 
is 2.2~3.5MPa; 

3 
High pressure 
MPa 

‹ Under the heating mode when the ambient 

temperature is above -5ć . The high pressure 
value of the system is 2.0~3.5MPa. 

‹ Under the cooling mode at the ambient temperature 

of 25~40ć , the low pressure value of the system 
is 0.6~1.5MPa; 

4 
Low pressure 
MPa 

‹ Under the heating mode when the ambient 

temperature is above -5ć . The low pressure value 
of the system is 0.4~1.5MPa. 

5 
Current 
A 
Current should be no more than 20A during 
normal operation for compressor 

       Ultra Heat GMV Multi VRF 

 
for North America

65

Sayfa 68

 
for North America

Ultra Heat GMV Multi VRF 

66

MAINTENANCE

Sayfa 69

DEBUGGING & MAINTENANCE 
1 Malfunction List 

1.1 Error Code of Protection
 

Error Item 
Code 
Indoor Unit 

Indoor fan protection 
L1 
L1 
L1 

Water overflow protection 
L3 
L3 
L3 

Anti-freeze protection 
L5 
L5 
L5 

Mode conflict 
L6 
- 
L6 

Indoor ambient temperature sensor error 
d3 
d3 
d3 

Indoor coil inlet temperature sensor error 
d4 
d4 
d4 

Indoor mid-coil temperature sensor error 
d5 
d5 
d5 

Indoor coil outlet temperature sensor error 
d6 
d6 
d6 

Indoor humidity sensor error 
d7 
d7 
d7 

Jumper error 
d9 
d9 
d9 

Outdoor ambient temperature sensor error 
b1 
b1 
b1 

Outdoor heat-exchanger coil outlet 
temperature sensor error 
b3 
b3 
b3 

Vapor-liquid separator inlet temperature 
sensor error 
b6 
b6 
b6 

High pressure protection 
E1 
E1 
E1 

Low pressure protection 
E3 
E3 
E3 

Discharge protection 
E4 
E4 
E4 

Refrigerant-lacking protection 
Ed 
E0 
Ed 

Compressor power protection 
EN 
E0 
EN 

Intermediate vapor injection temperature 
sensor error 
Fb 
E0 
Fb 

EEPROM read-write error 
F0 
F0 
F0 

High pressure sensor error 
F1 
F1 
F1 

Middle pressure sensor error 
F2 
E0 
F2 

Low pressure sensor error 
F3 
F3 
F3 

Discharge temperature sensor error 
F6 
F6 
F6 

High pressure switch 
Fd 
E0 
Fd 

AC over current 
P5 
P0 
P5 

IPM over current protection 
P6 
E0 
P6 

       Ultra Heat GMV Multi VRF 

 
for North America

Outdoor Unit 

Display 

Display 

67

Sayfa 70

Ultra Heat GMV Multi VRF 

 
for North America

IPM module overheat 
P8 
P0 
P8 

Desynchronizing protection 
P9 
P0 
P9 

Busbar over voltage protection 
PH 
P0 
PH 

Phase current detection fault 
PC 
P0 
PC 

Busbar under voltage protection 
PL 
P0 
PL 

Capacitor charge error 
PF 
P0 
PF 

Demagnetization protection 
PU 
P0 
PU 

Communication error between indoor and 
outdoor units, indoor unit’s wired controller 
C0 
C0 
C0 

485 communication error between main 
controller and drive controller 
C2 
C2 
C2 

Fan motor error 
H0 
H0 
H0 

PFC over current protection 
P4 
E0 
P4 

PFC module overheat 
Pn 
P0 
Pn 

Phase loss protection of compressor 
PE 
P0 
PE 

Malfunction of lack of IDU 
C4 
C4 
C4 

485 communication error between main 
controller and debugging controller 
C1 
- 
C1 

1.2 Error Code of Limiting Frequency Reduction Protection 

Error Item 
Code 
Display 

Limited frequency reduction for high pressure protection 
FA 

Limited frequency reduction for low pressure protection 
FH 

Limited frequency reduction for discharge temperature 

protection 

Limited frequency reduction for AC current protection 
F8 

Limited frequency reduction for power protection 
FC 

Limited frequency reduction for IPM temperature protection 
FL 

Limited frequency reduction for PFC temperature protection 
FE 

68

F9 

Only the outdoor 

unit displays the 

code 

Sayfa 71

1.3 Operation Code 

Operation 
Code 
Indoor Unit Display 
Outdoor Unit Display 

Trail run 
A0 
A0 
A0 

Fluorine recycle 
A2 
A2 
A2 

Defrosting 
A3 
A3 
A3 

Oil return 
A4 
- 
A4 

Testing online 
A5 
A3 
A4 

Vacuumization 
A8 
A8 
- 

Test module 
SS 
- 
SS 

Note: Last ten records of protection shutdown or limited frequency reduction for protection can 

be searched through the debugging controller. 

2 Troubleshooting 

Troubleshooting principle 
(1)  Communication malfunction 

communication  

malfunction

check whether indoor 
unit and outdoor unit is 

power supplied 

measure whether the 

communication wire 

is in normal

       Ultra Heat GMV Multi VRF 

 
for North America

Energize indoor unit

 and outdoor unit 

repiace 
communication

 wire 

69

Sayfa 72

 
for North America
Ultra Heat GMV Multi VRF 

(2) Low-pressure protection 

Low pressure 

protection

Me asure wh ethe r the low 

Me asure wh ether the 

no

yes

Re place ma in board of 

pressure is too low with 

pressure switch is 

outdoor unit

ma no me ter

norm al

Re place pressure 

yes

no

sw itch

yes

Ch eck wh ethe r the 
refrigerant-charging volum e 

Ch arge refrige rant according to the volum e on nam eplate; check 

wh ethe r there‹s leakage for the system 

is insufficient

no

no

Ch eck wh ethe r ga s valve 
and liquid valve are ope n 

Op en the valve 

comp letely

comp letely

yes

no

Check wh ether the 
panel of outdoor unit is 
covered and sealed well

Co ver the pa ne l of 

outdoor unit we ll

yes

no

Check wh ether the air can blow 
sm oothly at the heat exchanger 

Eliminate obstacles and 

sund ries

of indoor unit and outdoor unit

yes

no

Ch eck wh ethe r the indoor fan 

Me asure the circum stances 
of fan motor and signal inpu t

and outdoor fan can operate 

yes

no

Me asure the 
circum stances of swing 

Ch eck wh ethe r the indoor 

sw ing blade is ope n 

mo tor and sign al inp ut

comp letely 

yes

no

Ch eck wh ethe r the electronic 

expa nsion valve for indoor 

Enga ge valve and coil

unit and outdoor unit can 

operate no rm ally

yes

no

Ma inly che ck the air inlet and air outlet conne cting indoor 
unit and main pipe , and the expa nsion valve for indoor unit 

Blockage for system 

pipe line

and outdoor unit. Replace electronic expa nsion valve , dry 

strainer, ect. 

70

Sayfa 73

 
for North America
       Ultra Heat GMV Multi VRF 

(3)  Discharge temperature protection 

71

Sayfa 74

 
for North America
Ultra Heat GMV Multi VRF 

(4) Mafunction of temperature sensor 

(5) Malfunction of sensor 

(6) Unit and main board can’t be energized 

72

Sayfa 75

       Ultra Heat GMV Multi VRF 

 
for North America

(7) Failure start-up 

3 Power Distribution of Unit
3.1 Power distribution of unit

The main loop is showed by bold line (line width: 1mm); the control loop is showed by slim line (line width: 0.2mm). 

Power wiring board

Filter plate 
Drive board
Compressor 

Fan

Temperatuer sensor,electric 

4-way valve,by-pass 
valve,electric heating belt 

expansion valve,high 
pressure and low pressure 

and control signal 

switch and so on

(Bold line is the power line and the slim line is the control line)

3.2 Main electric parts

Name 
Photo 
Function introduction 

There are three complemental IGBT tube inside the IPM 
module. They are controlled by PWM wave and then bring 

the pressure of DC bus bar to different stator windings of 
compressor at different stage, and then generate current on 

IPM Module 

stator winding, and push the operation of rotor and then drive 

compressor to operate. 

Four diodes and two MOS pipe are intergrated inside the 
PFC module. It will transform AC input power into DC power. 
Meanwhile, MOS pipe is controlled by PWM wave. Pressure 

PFC module 

will be increased by induction.  

73

Sayfa 76

 
for North America

Ultra Heat GMV Multi VRF 

3.3Circuit diagram

Note: 
This drawing is just for reference; please always refer to the electric wiring stuck to the 
unit for actual wiring. 

3.3.1Circuit diagram of outdoor unit 

W5

YEGN

PE

XT1
G

POWER

L2

W1

BN

L

L

AC-L

L2

W2

BU

L8

W12 RD

W

N

N

N

AP1

W

E

L8

W14

G
W8 YEGN

W11 YE

V
COMP

DRIVE BOARD 

V

U
LA
YEGN

L8

W10 BU

L5
L4

U

YE

LX2-1

G
G

COMPRESSOR

LX1-1

L6
L7
L6
L7

WH
BN

L3

W3

BN

LX1-2

CN485

L3

LX2-2

BU

W4

L5
L4

BU

LA

LOW PRESSURE 

MDEIUM PRESSURE 

HIGH PRESSURE 

DISPLAY

SRNSOR

SRNSOR

SRNSOR

SOLENOID 
 VALVE 4
W7
BN

SOLENOID 
 VALVE 1

SOLENOID
 VALVE 2

INDOOR MAIN BOARD

BOARD

PC

 4-WAY VALVE

D1
D2
CAN
SP
SP

SP

CAN

G

XT2

4YV

YV1

YV2

YV4

INDOOR UNIT 1

D2
D1

YEGN

4

W17
W18

W6

3

BK
RD

INDOOR MAIN

CAN

AC-L
N

PE

BOARD

CAN

CN485-XS
CN485-QD1

CN485-QD

CN-CAN1

L-PRESS
M-PRESS
H-PRESS

WAY
4

VA-1

VA-2

VA-4

INDOOR UNIT 2

(YE)
(RD)
(WH)
(BU)

AP2

INDOOR MAIN

MASTER BOARD

CAN

CAN

BOARD

INDOOR UNIT 3

T-SENSOR1(WH)
T-SENSOR2(RD)

+($77,(˄2*˅
HPP2

OFAN2(GN)
OFAN1(WH)

+($77,(˄*1˅

FA(WH)

)%˄5'˅

RT4
RT5
RT2
RT3

INDOOR MAIN

CAN

5

5

©
©
©
©
©

BOARD

P

HP

TEMPERATURE SENSOR
LOW PRESSURE SUCTION 

OUTDOOR AMBIENT 

INDOOR UNIT n

MEDIUM PRESSURE SUCTION 

TEMPERATURE SENSOR

TEMPERATURE SENSOR

TEMPERATURE SENSOR

TEMPERATURE SENSOR

DISCHARGE 

M1
M2

DEFROSTING

EKV

EKV

COMPRESSOR BAND HEATER

HIGH PRESSURE SWITCH

BOTTOM BAND HEATER

EXPANSION VALVE A

EXPANSION VALVE B

ELECTRONIC

ELECTRONIC

 FAN UPPER  

 FAN LOWER 

74

Sayfa 77

 
for North America
       Ultra Heat GMV Multi VRF 

 3.3.2 Circuit Diagram

(1) Low Static Pressure Duct Type IDU
GMV-ND07PLS/A-T(U) ~ GMV-ND22PLS/A-T(U):

Environment 

IND OOR UNI T

XT1

Ou t 
temp. 
sensor

I n 
temp. 
sensor

Temp. 
Sensor

1RD

Water 
pump

L1
L2

L1
L2

Water 
Swi tch

2WH

~M

RT1

RT2

RT4

12BU
13BK

G

θ

θ
20K

θ

POWER 

15K

20K

G

X2
X1

CN35

CN8
CN25
CN26

CN2
CN3

CN28

G

CN41
8

AP 3
CN1

Di spl ay 

Communi cati on 
cord interface

XT2

9

board
CN42

8RD
9BK
10BN
11OG

CN2

D1
D2
H1
H2

AP 1

Op tional accessory
CN12

22K
R
CN31

6BU

CN19 
CN20

Op tional
 accessoryThe uni t wi th 

CN21
CN22
CN23

CN6

Wi red 
control l er 

Hu mi di ty Sensor 
shoul d connect  
i t to CN31,
Ot herwi se 
conne ct CN31 
wi th a 22K 
resistance.

 
Hu mi di ty 

i nterface

sensor

5
5
5

Ou tdoor 

Wi red 
control l er 

4

or 
i ndoor

EKV

M2
M3
M4

M1

AP 2

Up - Down
swi ng motor

electroni c 
expansi on 
val ve

Ho rizontal 
auto swi ng 

Up - Down
swi ng motor

DC motor

motor

Op tional accessory

No teX5 -core Electroni c expansion valve conne ct to CN20. 

6-core El ectronic expansi on val ve conne ct to CN19;

(2) 4-way Cassette Type IDU
GMV-ND07T/A-T(U) ~ GMV-ND48T/A-T(U):

75

Sayfa 78

 
for North America
Ultra Heat GMV Multi VRF 

(3) Wall Mounted Type IDU
GMV-N07G/A3A-D(U)~GMV-N24G/A3A-D(U):

RECEI VER AND 
DI SPLAY BOAR D

Electroni c expansion valve

IND OOR UNI T

Di spl ay

YEGN

POWER

EKV

G
G

BK

L1
L2

RD
GN

Electri cal box
Evaporator

13

G

AC - L

N

G
YEGN

RT1
15K

( ROOM )
( PI PE-I N)
( PI PE-ON )

CN3
CN25

CN41
CN42

CN20( FB)

Environment 
temp.sensor

Evaporator

I n/outdoor 
 unit

XT1

RD

D1
D2

( COM - OUT )
( Humi d)

RT2
20K

BN
BK

CN12

AP1

H1

I n temp. sensor

Wi red 
control ler

OG

H2

RT4
20K

22K

CN2

WH
WH

CN31

Ou t temp. sensor

CN6

CN7

CN22

X1

HE AT - N1

HE AT - L1

5

RD

WH BN

BK WH BN

M1

Steppi ng

 
M
 
 M2

Motor

Motor

4 Removal of Parts
4.1 Key parts 

Photo
Name
Function

Core part of air conditioning system. It sucks low 
temperature and low pressure gas, compress it to 
high temperature and high pressure gas, and then 

compressor

discharge it. 

Electronic expansion 

Throttling device. It transforms high pressure 

valve 

refrigerant liquid into low pressure steam.  

4-way valve 
between cooling and heating. 

76

Sayfa 79

4.2 Removal of key parts
4.2.1GMV-36WL/B-T(U)\GMV-48WL/B-T(U) series unit

Remark: Before removing the panel, please make sure that the unit is disconected with the power

Process
Photo
Operation Instruction 

1. Remove 
top cover 

Ultra Heat GMV Multi VRF 

 
for North America

It stays between discharge outlet of compressor and 
inlet of condenser. It used for separating the lubricant 

Oil separator 

oil of compressor when the high temperature and 
high pressure refrigerant gas is discharged from the 

compressor. 

It stays between outlet of evaporator and suction ouitlet 

Vapour liquid separator 

of compressor. It used for separating low temperature 

and low pressure refrigerant. 

It used for separating middle pressure gas from the 
refrigerant, which will be sucked in the compressure.  

Accumulator  

Control to the high-voltage current: open upon power 

Solenoid valve 

on; close upon power off

It used for connecting indoor unit and outdoor unit, and 

Cut-off valve

used for maintenance and installation. 

Removal operation for panel

screwdriver
Ɣ+ROGWKHWRSFRYHUXSZDUGVDQGWKHQSXWLWRQ

77

Sayfa 80

 
for North America
Ultra Heat GMV Multi VRF 

2. Remove 
front side 
plate sub-

assy 

3. Remove 
front panel 

and grille  

4. Remove 
left side 
plate and 

rear side 

plate 

5HPDUN%HIRUHUHPRYLQJWKHPRWRrSOHDVHPDNHVXUHWKDWWKHXQLWLVGLVFRQQHFWHGZLWKWKHSRZHr. 

Process 
3KRWR
 Operation Instruction 

1. Remove grille 

78

screwdriver
Ɣ+ROGWKHIURQWVLGHSODWHXSZDUGVDQGWKHQSXWLW

ZLWKVFUHZGULYHU

SODWHZLWKVFUHZGULYHU
ƔUHPRYHWKHUHDUVLGHSODWH

Removal operation for blade 

Ɣ 7KHQUHPRYHWKHJULOOH

Sayfa 81

2. Remove 
blade 

3. Remove 
motor  
ƔWKHQUHPRYHWKHSRZHUFRUGRIPRWRU
Ɣ TDNHRXWWKHGDPDJHGPRWRU

,QVWDOOPRWRU

5. $VVHPEOH
XQLW

5HPRYDORSHUDWLRQRIFRPSUHVVRU
5HPDUN%HIRUHUHPRYLQJWKHFRPSUHVVRrSOHDVHPDNHVXUHWKDWWKHUH’VQRUHIULJHUDQWLQVLGHWKHSLSHOLQHDQGWKHSRZHULV
GLVFRQQHFWHG
3URFHVV
3KRWR
2SHUDWLRQ,QVWUXFWLRQ

 
for North America
Ultra Heat GMV Multi VRF 

Ɣ5HSODFHWKHPRWRrWLJKWHQVFUHZVZLWK
VFUHZGULYHUDQGWKHQFRQQHFWWHKSRZHUFRUGRI
motor 

Ɣ $VVHPEOHWKHXQLWLQWKHWKHFRQYHUVHVHTXHQFH

79

Sayfa 82

Ultra Heat GMV Multi VRF 

 
for North America

1. Remove 
wiring cover of 

compressor 

2. Disconnect 
compressor and 
connected pipeline 

3. Loose nuts 

compressor 

4. Remove the 
chassis from 

compressor 

5. Fix the new 
compressor at the 

chassis 

6. Connect suction 
pipe and discharge 

pipe of copressor 

and pipeline of 

system again 

80

screwdriver 
Ɣ Then pull out the power cord
Note: When removing the power cord, make marks 
for different color power cords and corresponding 
wiring terminals for wrong terminal. 

ƔWeld suction pipe and discharge pipe of 
compressor 
ƔWKHQSXOORXWWKHFRQQHFWLRQSLSHIURPWKH
compressor

burn out other parts. 

Twist off four nuts 
for compressor with 
wrench

 Twist off the nuts for compressor with wrench 

Ɣ Take out the compressor and replace it
Note: When replacing the compressor, do not 
damage nearby pipelines and other parts

bottom of compressor 

ƔWeld the connection pipe of compressor, 
connect the pipeline and compressor 

burn out other parts 

Sayfa 83

7. Connect the 
power cord of 
compressor well 

8. ChecN DQd open 
the upper cover 

SODWH

5HPRYDORSHUDWLRQIRUZD\YDOYH
5HPDUN%HIRUHUHPRYLQJWKHZD\YDOYHSOHDVHPDNHVXUHWKDWWKere’VQRUHIULJHUDQWLQVLGHWKHSLSHOLQHRIV\VWHPDQGWKHQSRZHULV
disconnected. 
 Process 
 Photo
2SHUDWLRQ,QVWUXFWLRQ

1. Disconnect 
the coil of wD\

YDOYHIURPWKH

ZD\YDOYH

2. Disconnect 
WKHZD\YDOYH

DQGFRQQHFWLRQ

pipeline 

 
for North America
Ultra Heat GMV Multi VRF 

screwdriver
ƔFRQHQFWWKHSRZHUFRUGZHOODJDLQ
1RWH:KHQFRQQHFWLQJWKHSRZHUFRUGPDNH
PDUNVIRUGLfIHUHQWFRORUSRZHUFRUGVDQG
FRUUHVSRQGLQJZLULQJWHUPLQDOV

Ɣ&KHFNZKHWKHUWKHSLSHOLQHLVFRQQHFWHGZHOO
Ɣ&KHFNZKHWHKUDOOSDUWVDQGFRQQHFWLRQZLUHV
DUHFRQQHFWHGZHOO
Ɣ,IWKHUH’VQRSUREOHPDIWHUFKHFNLQJLQVWDOOIURQW
DQGUHDUFRYHUSODWHV

Ɣ5HPRYHWKHFRLORIZD\YDOYHDW

ƔWHOGWKRVHFRQQHFWLRQVSRWVRQ
ZD\YDOYHDQGWKHQSXOORXWWKH
connection pipe 
1RWH'XULQJZHOGLQJSURFHVVGRQRW

81

Sayfa 84

 
for North America
Ultra Heat GMV Multi VRF 

3. Replace 
4-way valve 

4. Replace 
4-way valve 

Remival operation for eletronic expansion valve 

Remark: Before removing the electronic expansion valve, please make sure that there’s no refrigerant in th pipeline of system and the 

power is disconnected
 Process 
 Photo 
Operation Instruction 

1. Disconnec 
the electronic 

expansion 
valve from the 

pipeline 

2. Take out 
the electronic 
expansion valve 

and replace it 

82

Ɣ5HSODFHZD\YDOYH
Note: During welding process, do not 

ƔWeld the connection position 
between 4-way valve and pipeline 
Note: During welding process, do not 

Ɣ5HPRYHWKHFRLORIHOHFWURF

ƔWeld the connection pipe for 
expansion valve, and then pull out the 
connection pipe
Note: During welding process, do 

Take out the electronic expansion 
valve and replace it

Sayfa 85

3. Replace 
electronic 
expansion valve

 Removal operation of gas liquid separator 

Remark: Before removing the gas liquid separator, please make sure that there’s no refrigerant inside the pipeline of system and 

disconnect the power  
Process 
 Photo 
2SHUDWLRQ,QVWUXFWLRQ

1. Disconnect  
inlet pipe and 
exit pipe of gas 
liquid separator 

 
2. Replace gas 
liquid separator 

3.  Replace gas 
liquid separator

 
for North America
Ultra Heat GMV Multi VRF 

ƔWeld the connection pipe of 
electronic expansion valve
Ɣ,QLVWDOOWKHFRLORIHOHFWURQLF
expansion valve

Note: During welding process, do 

Ɣ Weld those two connection spots on 
the gas liquid separator and then pull 
out the connection pipe
Note: During welding process, do not 

Ɣ/RRVHVFUHZVZLWKVFUHZGULYHU
Ɣ5HSODFHJDVOOLTXLGVHSDUDWRU

ƔWeld the pipe connected with gas 
liquid separator
Ɣ)L[WKHVFUHZVRIJDVOLTXLG
separator well again
Note: During welding process, do not 

83

Sayfa 86

Ultra Heat GMV Multi VRF 

 
for North America

4.3 Assembling and Disassembling Key Parts of IDUs6 Common Maintenance 
 
◆Low static pressure duct

similar except the numbers of louvers and motors. 

Motor and fan

Precondition: The power supply has been disconnected.

Step
Diagram
Operation Procedure

1. Remove the 
line connecting 
to the motor. 

2. Remove the 
return frame. 

3. Remove the 
air return cover 
plate. 

4. Remove the 
rear propeller 
housing. 

5. Remove the 
front propeller 
housing. 

6. Loosen the 
louver and 
motor. 

 
Ɣ5HPRYHWKHPRWRUIURPWKH
support and remove the louver 
from the motor axle. Then, 
remove the motor. 
Ɣ)RUPRWRUVWKDWDUH
accompanied with supports, the 
supports need removing as well. 

7. Remove the 
motor. 

8. Install a new 

motor. 

84

Ɣ8VHDVFUHZGULYHUWRXQVFUHZ
the electric box cover. 
Ɣ5HPRYHIURPWKHPDVWHUERDUG
the line connecting to the motor 
and remove the tie. 

Ɣ8VHDVFUHZGULYHUWRXQVFUHZ
the air return cover plate. 

Ɣ/RRVHQWKHIDVWHQHUVWKDW
connect the rear propeller 
housing with the front propeller 
housing and remove the rear 
propeller housing. 

Ɣ8VHDVFUHZGULYHUWRXQVFUHZ
the front propeller housing 
and then remove the propeller 
housing. 

Ɣ8VHDKH[DJRQWRXQVFUHZWKH
louver and loosen the fasteners 
of the motor. 

Ɣ$VVHPEOHXQLWVEDVHGRQWKH
reverse order of this procedure 
and power on the units for test. 

Sayfa 87

 
◆Four-way Cassette

Step
Diagram
Operation Procedure

1. Unscrew the 
water tray. 

5HPRYHWKH
water tray. 
Ɣ5HPRYHWKHZDWHUWUDy. 

3. Unscrew the 
ORXYHr. 
Ɣ8se a wrench to unscrew the louYer. 

5HPRYHWKH
ORXYHr. 
Ɣ5HPRYHWKHORXYHr. 

5. Unscrew the 
motor. 

6. Replace the 
motor with a new 
one. 

Ultra Heat GMV Multi VRF 

for North America

Motor and fan

Loosen the 

screws

Ɣ8VHDVFUHZGULYHUWRXQVFUHZWKH

water tray. 

Ɣ8VHDVFUHZGULYHUWRXQVFUHZWKH

motor. 

Ɣ5HSODFHWKHPRWRUZLWKDQHZRQH

85

Sayfa 88

Ultra Heat GMV Multi VRF 

 
for North America

7. Screw the 
motor. 

,QVWDOODQG
VFUHZWKHORXYHr. 

,QVWDOODQG
VFUHZWKHZDWHU
WUDy. 

6WHS
'LDJUDP
2SHUDWLRQ3URFHGXUH

8QVFUHZWKHZDWHUWUDy. 

5HPRYHWKHZDWHUWUDy. 
Ɣ5HSODFHWKHZDWHUWUDy. 

5HPRYHWKHGUDLQDJHGXFW
DQGXQVFUHZWKHSXPS

86

Ɣ8VHDVFUHZGULYHUWRVFUHZWKH

motor. 

Ɣ,QVWDOOWKHORXYHUDQGXVHDZUHQFK

WRVFUHZWKHORXYHr. 

/RRVHQWKH

VFUHwV

Ɣ8VHDVFUHZGULYHUWRVFUHZWKH

ZDWHUWUD\

3XPS

/RRVHQWKH

VFUHwV

Ɣ8VHDVFUHZGULYHUWRXQVFUHZWKHZDWHUWUDy. 

8QVFUHZWKHRXWOHWSLSe

8QVFUHZWKHSXmS

5HPRYHWKHGUDLQDJHGXFWDQGXVHD

VFUHZGULYHUWRXQVFUHZWKHSXPS

Sayfa 89

Ultra Heat GMV Multi VRF 

 
for North America

4. Replace the pump. 
Ɣ5HSODFHWKHSXPS

1. Screw the outlet pipe

2. Screw the pump

5. Connect the drainage duct 
and screw the new pump. 

Ɣ&RQQHFWWKHGUDLQDJHGXFWDQGXVHD

screwdriver to screw the new pump. 

Tighten the screws

6. Install and screw the water 
tray. 

Ɣ8VHDVFUHZGULYHUWRVFUHZWKHZDWHUWUDy. 

 
◆Wall Mounted T\SH,'8

Removal of Fan Motor

Remark: before removing, making sure power is disconnected.

Step
Diagram
Operation Procedure

ƔTake off the axle bush of the louver.
Ɣ5HPRYHWKHORXYHr.

1.Remove the louver

2.Open the front panel
Ɣ+ROGWKHLQGHQWVRQERWKVLGHVRIWKH
panel and pull it out in the direction 
shown by the arrow.

box cover with a screwdriver. Take off 
the box cover 2.
ƔDetach the ambient temperature sensor 
from the conduit.

3. Remove the electrical box 
cover 2

 87

Sayfa 90

Ultra Heat GMV Multi VRF 

for North America

4. Remove the front panel 
assembly
panel assembly.
Ɣ5HPRYHWKHIURQWSDQHODVVHPEOy.

5. Remove the electrical box 
cover 1

6. Remove the main board
Ɣ5HOHDVHWKHZLULQJWHUPLQDOVFRQQHFWHG
to the main board.
Ɣ5HPRYHWKHPDLQERDUG

7. Remove the electrical box
ER[ZLWKDVFUHZGULYHr.
Ɣ5HPRYHWKHHOHFWULFDOER[

8. Remove the evaporator

9.Remove motor’VSUHVVLQJSODWH
SUHVVLQJSODWHZLWKDVFUHZGULYHUDQG
then remove it.

10. Remove the motor and 
fan

11. ,QVWDOODQHZPRWRr.
Ɣ$VVHPEOHXQLWVEDVHGRQWKHUHYHUVHRUGHU

88

Ɣ3UHVVRQWKHEXFNOHRIWKHER[FRYHU
DQGWKHQWDNHRff the cover.

Ɣ8VHDVFUHZGULYHUWRXQVFUHZ

FRQQHFWLRQSLSHRQWKHEDFNRIWKHXQLW
DQGWDNHRff the press plate.
Ɣ8QVFUHZWKHVFUHZVRIHYDSRUDWRU
ZLWKDVFUHZGULYHUDQGWKHQUHPRYHWKH
evaporator.

ƔTDNHRff the motor and fan directly.

Ɣ8VHDVFUHZGULYHUWRXQVFUHZWKH
VFUHZVFRQQHFWLQJWKHPRWRUDQGWKH

fan.

RIWKLVSURFHGXUHDQGSRZHURQWKHXQLWVIRU

test.

Sayfa 91

5 Vacuum drying for the system
5.1 Selection requirement for the vaccum pump
Do not use different vacuum pump for vaccum-pumping for different refrigerant system
;

The final vacuum for the vacuum pump should reach -0.1MPa.

The air discharge volume for the vacuum pump should reach 4L/S above;
The precision of vacuum pup should reach 0.02mmHg above;
The system vacuum pump for R410A must be with check valve. 

5.2 Operation procedure and notices for Vacuum drying
1) Operation procedure 
 a 

.Before vacuum-pumping, please confirm that the cut-off valve for gas pipe and liquid 
pipe is at off status; 

 b .Use charging conduct pipe to connect the governing value and vacuum heat pump 

to the detection joint of gas valve and liquid valve;

 c .After vacuum-pumping for 4h, check whether the vacuum degree is reached to 

-0.1MPa or above; If not, there may be gas leakage. Please perform the leakage 

inspection again. If there’s no gas leakage, please vacuum pump for another 2h. 

 d 

.If the required vacuum degree cannot be satisfied after vacuum-pumping for two
times, there are water inside the pipeline. please drain out the water by the method of
vaccum damage. The detailed method: charge 0.05MPa nitrogen into the pipeline,  

vacuum pump for 2h and then keep the vacuum for 1h. If -0.1 MPa vaccum degree
still can’t be reached, repeat this operation unitl the water is drained out completely.

 e . After evacuation, close the regulating valve, and 1 hour later check if its pressure 

goes up or not.
2) 

After the vacuum pump is finished, turn off the valve of governing valve and stop 
vacuum pump and keep it for 1h. Please confirm that  the pressure of governing valve
hasn’t been increased. 

 a .Vacuum pump for the gas pipe and liquid valve at the same time; 

Pressure gauge connector valve

Gas 

liquid

Refrigerant cylinder

Spring balance

 b 

.When turn off the vacuum pump to stop vacuum-pumping, please turn off the valve at first and then 
de-energize the vacuum pump; 

 c 

.Keep the vacuum pump for 2h and confrm that the pressure of vacuum meter hasnot been increased; 

5.3 Fill and charge refrigerant 
5.3.1 Filling procedure of regrigerant 
Refrigerant quantity of outdoor unit before delivery:

Model
GMV-36WL/B-T(U)
GMV-48WL/B-T(U)

 Refrigerant Qty (kg/oz)
6.5(229)
6.5(229)

Ultra Heat GMV Multi VRF 

 
for North America

Connector on gas side

Connector on liquid side

89

Sayfa 92

Ultra Heat GMV Multi VRF 

 
for North America

NOTICE

(1) The refrigerant amount charged before delivery doesn’t include the amount that needs to be added

to indoor units and the connection pipeline. 
(2) Length of connection pipe is decided on site. Therefore the amount of additional refrigerant shall be 

decided on site according to the dimension and length of field-installed liquid pipe. 

(3) Record the amount of additional refrigerant for convenience of after-sales service.

 Calculation of the amount of additional refrigerant

Calculation method of the quantity of additional refrigerant (based on liquid pipe)
4XDQWLW\RIDGGLWLRQDOUHIULJHUDQW ™OHQJWKof liquid pipe X quantity of additional refrigerant 
 per meter(39-3/8inch)

Diameter of 

liquid pipe
(mm/inch)

ĭ
ĭ)
ĭ)
ĭ)
ĭ)
ĭ

kg/m


0.1
0.11

0.022
oz/inch
0.31
0.22
2
0.099

0.020
NOTICE! Liquid pipe that is within 20m(65-5/8feet) doesn’t need to be added with 
refrigerant.
      First confirm that there is no leakage from the system.When compressor is not working, 
FKDUJHDGGLWLRQDO5$ZLWKVSHFLILFDPRXnt to the unit through the filling opening of the 
liquid pipe valve of the outdoor unit. If required amount cannot be quickly filled due to 
pressure increase of the pipe, then set the unit in cooling startup and fill refrigerant from the
low pressure check valve of the outdoor unit.

Calculation example

ODU

IDU

Indoor unit 
:
No.
IDU ①
IDU ②
IDU ③
IDU ④

Model
Duct type GMV-ND18PLS/

Duct type GMV-ND12PLS/

Duct type GMV-ND09PLS/

$78
Duct type GMV1'3/6$78

$78

$78

Liquid pipe:

 No.
$
B
C
D

Pipe size
ijPPLQFK)
ijPPLQFK)
ijPPLQFK
ijPPLQFK

 Length
PIHHW
PIHHW
PIHHW
PIHHW

 No.
a
b
c
d

Pipe size
ijPPLQFK)
ijPPLQFK)
ijPPLQFK
ijPPLQFK

 Length
PIHHW
PIHHW
PIHHW
PIHHW
Total length of each liquid pipe

ij$%&D  PIeet)

ij'EFG  1PIHHW

 90

Sayfa 93

NOTICE! Liquid pipe that is within 20m(65-5/8 feet) doesn’t need to be added refrigerant.
     Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022=
0.404kg(14oz).

5.3.2 Operation procedure for adding refrigerant 
(1) Put the charging tank on the weightometer, record the reading and then calculate the 

data after charging refrigerant; 
(2) Use charging conduct pipe to connect the double-ended manometer with governing valve

 and liquid-charging tank to the detection head of gas valve and liquid valve. Before
 connection, please release some refrigerant and then drain out the air inside the charging

conduct pipe.

Confirm that the gas valve and liquid for outdoor unit is at of status. 
(3) 

(4) When the unit hasn’t been turned on, open the governing valve for the liquid-charging 

tank and then charge refrigerant from gas pipe and liquid pipe at the same time. 
(5) Obeserve the data weightometer, close the valve after it is reached to requirement and 

then close the valve for liquid-charging tank; 
(6) If the refrigerant can’t be added completely, add it when turning on the unit. Charge 

refrigerant from the detection joint of cooling gas pipe or detection joint of gas vavle. 

5.3.3 Notice for filling refrigerant 

(1) Calculate the section and length of cooling liquid pipe preciously for the precision 

refrigerant-charing volume. 
(2) Measure the additional refrigerant volume preciously; 
(3) Invert to charge the R410A for ensuting the liquid-charging; 
(4) When the temperature is low, heat the liquid-storage tank with hot water or hot 

wind for helping refrigerant-charging. However, prohibit use flame to heat the 
liquid-storage tank directly. Otherwise, it may cuase personal injury or property 
damage due to explosion. 

5.4  Airtightness test 
5.4.1 Importance of airtightness test 
     The airtightness of VRF system is the leak tightness of the pipeline for refrigerant, 
which the guarantee for safe and reliable operation. The leakage of refrigerant may 
affect  the operation of air conditioner seriously, or even damage compressor and then
 lead to breakdown of system. Therefore, it needs to perform the airtightness test.
 If the there’s gas leakage after the system is installed completely, because the indoor
celling decoration are all finished, it is will be very difficult to find out the leakage point. 
Thus, the airtightness test of the system must be finished before finishing indoor 
decoration. 
5.4.2 Operation procedure for the airtightness test 

(1) Before ex-factory,cut-off valve for gas pipe and liquid pipe of outdoor unit is
turned off, Please confirm that before operation; 

(2) Before test please smear a little corresponding lubricant oil at Blanking plug and
 pipe terminal, and use two wrenches for fixing blanking plug.
(3) Do not allow to connect the pipeline of outdoor unit for test during airtightness test. 

(4) The system test pressure for R410A is 4.15MPa (3.0MPa for R22 refrigerant 
system). Nitrogen must be used as the medium for the airtightness test and the nitrogen
should be dry. Increase pressure slowly for three steps: 

Ultra Heat GMV Multi VRF 

 
for North America

91

Sayfa 94

Ultra Heat GMV Multi VRF 

 
for North America

Step 1: Increase pressure slowly to 0.5MPa, stop for 5min and then check the gas leakage. 
Big leakage may be found out;

Step 2: Increase pressure slowly to 1.5MPa, stop for 5min to check the airtightness. Small 

leakage may be found out; 
Step 3: Increase pressure slowly to 4.15MPa for R410A slowly  (3.0MPa for R22 

refrigerant system), stop for 5min and perform the strength test. Minor leakage or 
sand hole may be found. Increase pressure to test pressurem, keep it for 24h and
observe whether the pressure is decreasing. If not, the pressure is qualified.

5.4.3 Cautions 
 a .The test manometer range for R410A should be 4.5MPa above (3.5MPa above for R22

 refrigerant system); 
 b .Record the data on manometerk, ambient temperature and test time at the same time; 
 c 

.Pressure modification: when temperature changes 1℃, the temperature will change 
0.01MPa correspondingly. 

 d .Pressure should be kept the same. 
 e .If it needs to keep pressure for a long time, decrease the pressire lower than 0.55MPa

 pr below. Long-time high pressure can lead to leakage at the welding position, which 
may cause risk.  
 f 

.Before the airtightness for the pipeline of refrigerant is finished, do not allow to insulate
and bundle the welding positions and connection position of bellmouth of indoor unit.

Note: Before airtightness test, all welding lines can’t be insulated and bundled. 

6 Exploded View of Unit and Parts’ List

6.1  Exploed view for outdoor unit and parts’ list 

(1)  Model: GMV-36WL/B-T(U)\GMV-48WL/B-T(U)

  Exploded view:

92

Sayfa 95

Parts list:

NO.
Name of Part

1
Coping                                                                  
01264100008P
1

2
Electric Box Cover                                          
012020000071
1

3
Motor Support Sub-Assy                                                               017012000032
1

4
Brushless DC Motor                                       
15704100013
1

5
Brushless DC Motor 
1570410001301
1

6
PFC Inductance
340032000005 
1

7
Cable Cross Loop
76512008 
1

8
Inductance Box Sub-assy
01394100625 
1

9
Left Side Plate
01314100013P
1

10
Sensor Sub-assy
39008000141G 
1

11
Diversion Circle                                                             
10474100001
1

12
Cabinet                                                          
01514100002P 
1

13
Front Grill                                                                
01574100009
1

14
Front Side Plate                                        
01314100012P 
1

15
Axial Flow Fan                                                               
10434100004 
2

16
Clapboard Sub-Assy                                                             
1244100043 
1

17
Cut off Valve Sub-Assy                                                               07334100077 
1

18
Joint Plank groupware                                         
01344100113
1

Ultra Heat GMV Multi VRF 

 
for North America

GMV-36WL/B-T(U)\GMV-48WL/B-T(U)

Product Code
CN850W0380\CN850W0360 

Part Code
Quantity

93

Sayfa 96

 
for North America

Ultra Heat GMV Multi VRF 

19
Liquid side stop Valve                                                                   07330000002
1

20
Underlay groupware                                       
01894100090
1

21
Electrical Heater(compressure)                                         7651521215 
1

22
Magnet Coil                                        
4304000425 
1

23
Electromagnetic Valve                                                          
43000054 
1

24
Electromagnetic Valve groupware                                    
43044100234  
1

25
43044100232
1

Electromagnetic Valve groupware                                    

26
Electromagnetic Valve                             
43003091 
1

27
Magnet Coil                                                                 
4304000439 
1

28
Chassis Sub-assy                                                           
01194100051P 
1

29
Drainage Connecter                            
06123401 
1

30
Nage hole Cap                 
06813401
3

31
Fixity groupware(Compressor)
 
P
2
8
0
0
0
1
4
4
8
1
0                                                        
1

32
3
1
0
0
0
0
2
1
0
9
0
0
       
                                                           t
e
k
s
a
G
 r
o
s
s
e
r
p
m
o
C
4

33
Compressor                                    
00204100030
1

34
Underlay
 01894100088  
1

35
Underlay                                       
01854100009  
1

36
 
7
8
5
1
0
0
2
0
6
4
       
                                                        
h
cti
w
S
 tc
e
t
o
r
P
 
e
r
u
s
s
e
r
P
1

37
Oil Separator                                    
07424105
1

38
Discharge Tube Sub-assy                                                              
04514100561 
1

39
Suction Tube Sub-assy                                   
04574100170 
1

40
Gas side stop Valve                           
07334100079 
1

41
4-Way Valve Assy                                         
030152000095  
1

42
Sensor (Low Pressure)                                       
322101002
1

43
Magnet Coil                                        
4304000431
1

44
4-way Valve                                                           
43000338 
1

45
Sensor (High Pressure)              
322101032 
1

46
Electronic Expansion Valve                                    
43044100172 

47
Electric Expansion Valve Sub-Assy                       
43044100233 
1

48
Electric Expand Valve Fitting                    
4304413205 
1

49
Front Connection Board                             
01344100002P 
1

50
Gland Bush                          
26904100134 
1

51
     
e
ri
w
 r
o
f 
e
pi
P
 26904100132  
1

52
Right Connection Board                                                             
01344100003P 
1

53
 
P
4
1
0
0
0
1
4
1
3
1
0
       
                                                          
e
t
al
P
 
e
di
S
 r
a
e
R
1

54
Handle                                                                
26904100016
2

55
Pipeline groupware                             
 030205000005  
1

 
3
7
1
0
0
1
4
4
0
3
       
                                                          
e
vla
V
 
n
ois
n
a
p
x
E
 cin
o
rtc
el
E
6
5
1

57
Electric Expand Valve Fitting                                      
4304413220
1

58
Sensor(High Pressure)                                                               
322101036 
1

59
Oil Returning Pipe Sub-assy                                                                04224100556  
1

60
Electromagnetic Valve                                                            
43003091
1

61
Magnet Coil                                   
4304000415 
1

62
Accumulator                                     
07424100031
1

63
Gas-liquid Separator                                                                
07424140 
1

64
Condenser Assy                                                              
000100000022  
1
65
Rear Grill                                                            
01574100004 
1

66
Electric Box Assy                                                               
100002000222  
1
67
Testing Board                                                              
30118000096  
  1
68
Radiator                                                              
49018000136  
1

69
Cable Cross Loop                                                              
43138000047 
2
70
Reactor                                                              
07424140 
1

71
Electric Box Sub-Assy                                                              
01394100626  
1

72
Electric Box                                                            
26904100086 
1

73
Main Board                                                               
300027000025 
1
74
Gas-liquid Separator                                                                
30224100009  
1

Above data is subject to change without notice,pls reference the SP in global service website

94