Owner's Manual 

Original Instructions 

Commercial Air Conditioners 

 
 
DC Inverter Multi VRF System 

   
Applicable Models: 

GMV-60WL/A-T(U) 

GMV-48WL/A-T(U) 

GMV-36WL/A-T(U) 

Sayfa 2

 
Preface 

For correct installation and operation, please read all instructions carefully. Before reading the 
instructions, please be aware of the following items: 

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. 
Obey all safety messages that follow this symbol to avoid possible 
injury or death. 

WARNING 
This mark indicates procedures which, if improperly performed, might lead to the death or 
serious injury of the user. 

CAUTION 
This mark indicates procedures which, if improperly performed, might possibly result in 
personal harm to the user, or damage to property. 

 
 
NOTICE is used to address practices not related to personal injury. 

WARNING 

(1). 
Instructions for installation and use of this product are provided by the manufacturer. 

(2). 
Installation must be performed in accordance with the requirements of NEC and CEC by authorized personnel  only. 

(3). 
For the safe operation of this unit, please read and follow the instructions carefully. 

(4). 
During operation, total capacity of indoor units should not exceed the total capacity of outdoor units. otherwise, poor 

effect of cooling or heating may result. 

(5). 
Direct operators or maintainers should well keep this manual. 

(6). 
If this unit fails to operate normally, please contact our service center as soon as possible and provide the following 

information: 

1). Content on the name plate (model number,cooling capacity,production code,ex-factory date. 

2). Malfunction details (before and after the malfunction occurs. 

(7). 
Each unit has been strictly tested and proved to be qualified before ex-factory. In order to prevent units from being 

damaged or operating normally because of improper disassembly, please do not disassemble the unit by yourself. If you 

need to disassemble and check units, please contact our service center. We will send specialists to guide the disassembly. 

(8). 
All graphics in this manual is only for your reference. For sales or production reasons,these graphics are subject to 

change by manufacturer without prior notice. 

(9). 
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental 

capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use 

of the appliance by a person responsible for their safety.Children should be supervised to ensure that they do not play with 

the appliance. 

User Notice 

 DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste 

separately for special treatment is necessary.  

Sayfa 3

Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following 

reasons: 

(1) Damage the product due to improper use or misuse of the product; 

(2) Alter, change, maintain or use the product with other equipment without abiding by the instruction 

manual of manufacturer; 

(3) After verification, the defect of product is directly caused by corrosive gas; 

(4) After verification, defects are due to improper operation during transportation of product; 

(5) Operate, repair, maintain the unit without abiding by instruction manual or related regulations; 

(6) After verification, the problem or dispute is caused by the quality specification or performance of 

parts and components that produced by other manufacturers; 

(7) The damage is caused by natural calamities, bad using environment or force majeure. 

Exception Clauses 

Sayfa 4

1 Safety Precautions ........................................................................................................................................................ 1 

2 Product Introduction ...................................................................................................................................................... 2 

2.1 Names of Main Parts ......................................................................................................................................... 3 

2.2 Combinations of Indoor and Outdoor Units.................................................................................................... 4 

2.3 Operating Range ................................................................................................................................................ 4 

3 Preparation before Installation .................................................................................................................................... 4 

3.1 Standard Parts .................................................................................................................................................... 4 

3.2 Installation Site ................................................................................................................................................... 5 

3.3 Piping Work Requirements ............................................................................................................................... 6 

4 Installation Instruction ................................................................................................................................................... 7 

4.1 Dimension of Outdoor Unit and Mounting Hole ............................................................................................. 7 

4.2 Connection Pipe ................................................................................................................................................. 8 

4.3 Installation of Connection Pipe ...................................................................................................................... 12 

4.4 Disassembly of Compressor Feet ................................................................................................................. 17 

4.5 Vacuum Pumping, Refrigerant Adding .......................................................................................................... 18 

4.6 Electric Wiring .................................................................................................................................................. 20 

5 Check Items after Installation and Test Operation ................................................................................................. 24 

5.1 Check Items after Installation ......................................................................................................................... 25 

5.2 Test operation and debugging ........................................................................................................................ 25 

6 Common Malfunctions and Troubleshooting .......................................................................................................... 30 

7 Error Indication ............................................................................................................................................................ 32 

8 Function Setting of Outdoor Unit .............................................................................................................................. 35 

8.1 ODU Quiet Function ........................................................................................................................................ 35 

8.2 Cool & Heat Function ...................................................................................................................................... 36 

8.3 Forced Defrosting ............................................................................................................................................ 37 

8.4 Restore Factory Defaults ................................................................................................................................ 37 

8.5 Static Pressure Function ................................................................................................................................. 37 

9 Maintenance and Care ............................................................................................................................................... 38 

9.1 Outdoor Heat Exchanger ................................................................................................................................ 38 

9.2 Drain Pipe ......................................................................................................................................................... 38 

9.3 Notice before Seasonal Use .......................................................................................................................... 38 

9.4 Maintenance after Seasonal Use .................................................................................................................. 38 

9.5 Parts Replacement .......................................................................................................................................... 38 

10 After-sales Service .................................................................................................................................................... 39 

Contents 

Sayfa 5

1 Safety Precautions 

(1) This product can’t be installed at corrosive , inflammable or explosive environment or the place with special 
requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of the 
unit, or even cause fire hazard or serious injury. As for above special places, please adopt special air 
conditioner with anti-corrosive or anti-explosion function . 

(2) Follow this instruction to complete the installation work. Please carefully read this manual before unit  
startup and service. 

(3) Wire size of power cord should be large enough.The damaged power cord and connection wire should be  
replaced by exclusive cable. 

(4) After connecting the power cord, please fix the electric box cover properly in order to avoid accident. 

(5) Never fail to comply with the nitrigen charge requirements.Charge nitrogen when welding pipes. 

(6) Never short-circiut or cancel the pressure switch to prevent unit damage.  

(7) Please firstly connect the wired controller before energization, otherwise wired controller can not be used. 

(8) Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant  
leakage, electric shock, or fire etc.. 

(9) Do not insert fingers or objects into air outlet/inlet grille. 

(10) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the gas/oil 
supplied heating equipment is used. 

(11) Never start up or shut off the air conditioner by means of directly plug or unplug the power cord. 

(12) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor. 

(13) Do not allow children operate this unit. 

(14) Do not operate this unit with wet hands. 

(15) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury  
may happen. 

(16) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen. 

(17) Do not expose the unit to the moist or corrosive circumstances. 

(18) Under cooling mode, please don't set the room temperature too low and keep the temperature difference  
between indoor and outdoor unit within 5℃ (41˚F). 

(19) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please  
contact Gree appointed  service center for help.  

(20) Before installation, please check if the power supply is in accordance with the requirements specified on  
the nameplate. And also take care of the power safety. 

(21) Installation should be conducted by dealer or qualified personnel. Please do not attempt to install the unit 
by yourself. Improper handling may result in water leakage, electric shock or fire disaster etc.. 

DC Inverter Multi VRF System  

WARNING 

1 

Sayfa 6

DC Inverter Multi VRF System  

(22) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire    
accidents. 

(23) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid  
electric  
shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone line.  

(24) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off  
the power when 24 hours short-time halting (to protect the compressor).  

(25) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will emerge 
if the refrigerant gas meets fire. 

(26) Volatile liquid, such as diluent or gas will damage the unit appearance.Only use soft cloth with a little 
neutral  
detergent to clean the outer casing of unit. 

(27) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main 
power  
supply, and then immerdiately contact Gree appointed service center.If abnormality keeps going, the unit might 
be damaged and lead to electric shock or fire. 

(28)Turn off the unit after it runs at least five minutes;otherwise it will influence oil return of the compressor. 

(29) Under the standby status, the unit will consume a little power for ensuring reliability of complete unit, 
maintaining normal communication and preheating refrigerant. When the unit won’t be used for a long time, cut 
off the power of the complete unit. However, please preheat it  when operating the unit next time. 

Any personal injury or property loss caused by improper installation, improper debug, unnecessary 

repair or not following the instructions of this manual should not be the responsibility of Gree Electric 

Appliances, Inc. of Zhuhai. 

2 Product Introduction 

Gree Multi VRF System adopts inverter compressor technology. By changing the 

displacement of compressor, stepless capacity regulation within range of 15%~100% can be 

realized. Various product lineups are provided with capacity range from 36000Btu/h to 60000Btu/h, 

which can be widely used in residential, commercial and working area and especially applicable to 

places with big load change. Gree residential air conditioner is absolutely your best choice. 

2 

Sayfa 7

2.1 Names of Main Parts 

 
GMV-36WL/A-T(U)、GMV-48WL/A-T(U) 
 

Fig.1 
No. 
① 
② 
③ 
④ 
⑤ 

Name 
Motor 
Fan blade 
Electric box 

DC Inverter Multi VRF System  

 
GMV-60WL/A-T(U) 

assembly 
Gas pipe valve 
Liquid pipe 

valve 

3 

Sayfa 8

DC Inverter Multi VRF System  

2.2 Combinations of Indoor and Outdoor Units 

(1)  See below the number of indoor units that can be connected to the outdoor unit. 

(2)  The total capacity of indoor units should be within 50%~135% of that of the outdoor unit. 

Model 
Min sets of connectable IDUs 
Max sets of connectable IDUS 

GMV-36WL/A-T(U) 
2 
7 

GMV-48WL/A-T(U) 
2 
8 

GMV-60WL/A-T(U) 
2 
10 

(3)  Outdoor units of DC Inverter Multi VRF System can be connected to various indoor 

units. When any one of the indoor units receives operating command, outdoor unit will 

start operation as per required capacity. When all indoor units stop, outdoor unit will be 

shut off.  

2.3 Operating Range 

Cooling 
Outdoor temperature: -5℃~48℃(23℉~118℉) 

Heating 
Outdoor temperature: -20℃~27℃(-4℉~81℉) 

3 Preparation before Installation 

NOTICE! Graphics here are only for reference. Please refer to actual products.  

3.1 Standard Parts 

Please use the supplied standard parts as required. 

No. 
Name 
Appearance 
Qty 
Remark 

1 
User Manual 

resistance) 
1 
Must be connected to the 
last IDU of communication 

2 
Wiring (match with 

3 
Corrugated pipe 
1 
GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 

4 
Liquid side 
connection pipe 
1 
This part is included in the 

5 
Gas side 
connection pipe 

Parts for Outdoor Unit 

1 
 

connection 

following models: 
GMV-60WL/A-T(U) 

1 
This part is included in the 

following models: 
GMV-60WL/A-T(U) 

4 

Sayfa 9

No. 
Name 
Appearance 
Qty 
Remark 

6 
Drainage hole cap 

7 
Drainage joint 
1 
 

3.2 Installation Site 

(1) The unit must be installed where strong enough to withstand the weight of the unit and fixed securely, 

otherwise the unit would topple or fall off.  

(2) Do not install where there is a danger of combustible gas leakage.  

(3) Do not install the unit near heat source, steam, or flammable gas.  

(4) Children under 10 years old must be supervised not to operate the unit.  

(5) Select a location which is out of children’s reach. Keep the unit away from children. 

(6) Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with 

good ventilation. 

(7) Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with 

good ventilation. 

(8) Install the unit where it will not be tilted by more than 5°. 

(9) During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed securely. 
 

(1) If possible, do not install the unit where it will be exposed to direct sunlight. (If necessary, install a blind that 

does not interfere with the air flow.)  

(2) Install ODU in a place where it will be free from getting dirty or getting wet by rain as much as possible. 

(3) Install ODU where it is convenient to connect IDU.  

(4) ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and reduce bend 

angles. 

(5) Install ODU where the condensate water can be drained out freely during heating operation. Do not place 

animals and plants in the path of the warm air. 

(6) Take the air conditioner weight into account and select a place where noise and vibration are small 

If the ODU is totally surrounded by walls, please refer to the following figures for space dimension: 

DC Inverter Multi VRF System  

Parts for Outdoor Unit 

3 
 

5 

Sayfa 10

DC Inverter Multi VRF System  

Fig.2 

3.3 Piping Work Requirements  

Refer to the table below for piping work requirements: 
 

R410A Refrigerant System 

Outer diameter (mm/inch) 
Wall thickness(mm/ inch) 

Φ6.35(Φ1/4) 
≥0.8(1/32) 

Φ9.52(Φ3/8) 
≥0.8(1/32) 

Φ12.7(Φ1/2) 
≥0.8(1/32) 

Φ15.9(Φ5/8) 
≥1.0(1/25) 

Φ19.05(Φ3/4) 
≥1.0(1/25) 

6 

Sayfa 11

4 Installation Instruction 

NOTICE! Graphics here are only for reference. Please refer to actual products.  

4.1 Dimension of Outdoor Unit and Mounting Hole 

Unit Outline and Installation Dimension: 

Unit:mm(inch) 
Model 
A 
B 
C 
D 
E 

GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 

GMV-60WL/A-T(U) 
940 
(37) 

DC Inverter Multi VRF System  

 
Fig.3 

900 
(35-3/8) 

340 
(13-3/8) 

1345 
(53) 

572 
(22-1/2) 

378 
(15) 

320 
(12 3/5) 

1430 
(56 2/7) 

632 
(24 7/8) 

350 
(14 7/8) 

7 

Sayfa 12

DC Inverter Multi VRF System  

4.2 Connection Pipe 

4.2.1 Schematic Diagram of Piping Connection 

Fig.4 

8 

Sayfa 13

DC Inverter Multi VRF System  

4.2.2 Allowable Length and Height Difference of Connection Pipe 

Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is 

shown in the figure below: 

NOTICE! Equivalent length of one Y-type branch is 0.5m(1-5/8feet). 

 
Fig.5 Allowable Length and Height Difference of Connection Pipe 

Piping parameters of GMV-36WL/A-T(U)、GMV-48WL/A-T(U) 、GMV-60WL/A-T(U) 

Allowable value 

Fitting pipe 
m 
feet 

Total length (actual length) of fitting pipe 
300 
984 
L1+L2+L3+a+b+c+d 

Actual length 
120 
394 
L1+L2+L3+d 
Equivalent length 
150 
492 

Length of farthest fitting pipe 

From the 1st branch to the farthest indoor pipe 
40 
131 
L2+L3+d 

ODU at upper 

side 
50 
164 
—— 

Height difference between ODU 

and IDU 

ODU at lower side 
40 
131 
—— 

Height difference between IDUs 
15 
49 
—— 

9 

Sayfa 14

DC Inverter Multi VRF System  

4.2.3 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch 

Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of 

outdoor connection pipe. 

Dimension of outdoor connection pipe: 

Basic module 

GMV-36WL/A-T(U) 
Φ15.9 
(Φ5/8) 

GMV-48WL/A-T(U) 
Φ15.9 
(Φ5/8) 

GMV-60WL/A-T(U) 
Φ19.05 

4.2.4 Selection of Indoor Branches 

Select indoor branches according to the total capacity of downstream indoor units. 
 

 
Fig. 6 

Pipe dimension 

Gas pipe 
(mm/inch) 

Liquid pipe 

(mm/inch) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

 
Fig.7 

10 

Sayfa 15

Refrigerant system 
Total capacity of downstream indoor units C (Btu/h) 
Model 

Y type branch 

4.2.5 Dimension of Pipe between Indoor Branches 

Select pipe between indoor branches according to the capacity of downstream indoor units; if 

the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

 
Fig.8 
Total capacity of downstream indoor units  

C (Btu/h) 

C ≤19000 
Φ12.7 
(Φ1/2) 

19000<C≤48500 
Φ15.9 

Φ9.52 
(Φ3/8) 
 

48500<C≤76400 
Φ19.05 

DC Inverter Multi VRF System  

C< 68200 
FQ01A/A 

68200≤C≤102400 
FQ01B/A 

102400<C≤238800 
FQ02/A 

238800<C≤460600 
FQ03/A 

460600<C  
FQ04/A 

Pipe 
(mm/inch) 

Liquid pipe 

(mm/inch) 

Φ6.35 
(Φ1/4) 

Φ9.52 

(5/8) 

(3/8) 

(Φ3/4) 

11 

Sayfa 16

DC Inverter Multi VRF System  

4.2.6 Dimension of Pipe between Indoor Branch and IDU 

Dimension of pipe between indoor branch and IDU should be consistent with the dimension of 

indoor pipe. 

 
Fig. 9 
Rated capacity of IDU 

C(Btu/h) 

C≤9600 
Φ9.52 
(Φ3/8) 

9600<C≤17000 
Φ12.7 
(Φ1/2) 

17000<C≤48000 
Φ15.9 
(Φ5/8) 

48000<C≤55000 
Φ19.05 

55000<C≤96000 
Φ22.2 
(Φ7/8) 

NOTICE! If the distance between IDU and its nearest branch is over 10m(33feet), then the 

liquid pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged. 

4.3 Installation of Connection Pipe 

(1) 
Conform to the following principles during pipe connection: Connection pipe should be as short as possible, 
so is the height difference between indoor and outdoor units. Keep the number of bends as little as possible. 
Radius of curvature should be as large as possible. 

(2) 
Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for 
welding process. Rosin joint or pin hole is not allowed. 

(3) 
When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm(8inch). Note 
that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or 
stretch the pipe for more than 3 times at the same position. 

Gas pipe 
(mm/inch) 
Liquid pipe (mm/inch) 

Φ6.35 
(Φ1/4) 

Φ6.35 
(Φ1/4) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

Φ9.52 
(Φ3/8) 

12 

Sayfa 17

4.3.1 Flaring Process 

(1)  Use pipe cutter to cut the connection pipe in case it is unshaped. 

(2)  Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs 

after cutting. 

(3)  Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use 

flaring tool to fix the flared nut into the pipe (as shown in Fig.10). 

(4)  Check if the flared part is flaring evenly and if there is any crack. 

4.3.2 Pipe Bending 

(1)  Reshape the pipe by hand. Be careful not to damage the pipe. 

(2)  Do not bend the pipe over 90°. 

(3)  If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch 

again. Therefore, do not bend or stretch the bend for over 3 times. 

(4)  In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the 

insulating layer, as shown in Fig. 12. Do not bend the pipe until it is exposed. When 

bending is done, wrap the pipe with insulating layer and then secure it with adhesive 

tape. 

 
                    Fig. 11                                 Fig. 12 

4.3.3 Indoor Pipe Connection 

(1)  Remove pipe cover and pipe plug. 

(2)  Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut 

tightly by hand, as in Fig. 13. (Make sure indoor pipe is correctly connected. Improper location of 

the center will prevent flared nut from being securely twisted. Thread of nut will get damaged if the 

flared nut is twisted forcibly.) 

(3)  Use torque wrench to twist on the flared nut tightly until the wrench gives out a click 

sound. (Hold the handle of wrench and make it at right angle to the pipe. as in Fig. 14) 

DC Inverter Multi VRF System  

 
            Fig. 10 

13 

Sayfa 18

DC Inverter Multi VRF System  

(1) 
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic tape. 

(2) 
Connection pipe should be supported by a bearer rather than the unit. 

(3) 
The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use a 
pipe bender to bend the pipe. 

(4) 
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case the 
capillary tube or other tubes have cracks and cause leakage. 

 
                           Fig. 13                     Fig. 14 
 

4.3.4 Outdoor Pipe Connection 

(1)Pipe connection for GMV-36WL/A-T(U)、GMV-48WL/A-T(U) 

Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as 

for indoor pipe connection. 

During engineering installation, the connection pipe inside the unit must be wrapped by 

insulation sleeve. 

 According to customer requirement or space limit, outlet pipe can be installed from the front, 

right or rear side. 

Pipe Diameter 
Tightening Torque 

6mm(1/4inch) 
15-30N·m(11-22ft.-1b.) 

9.5mm(3/8 inch) 
35-40N·m(26-29ft.-1b.) 

12.7mm(1/2 inch) 
45-50N·m(33-37ft.-1b.) 

16mm(5/8 inch) 
60-65N·m(44-48ft.-1b.) 

14 

Sayfa 19

 
Fig. 15 
    (2)Pipe connection for GMV-60WL/A-T(U) 

As shown in Fig.16 and Fig.17, open the outermost soundproof cotton and place a fire 

barrier between compressor and straight pipe. Use a soldering gun to unsolder straight pipe 1 

and straight pipe 2. Install connection pipe 1 and connection pipe 2 to the corresponding 

position and then seal the apertures with welding rod. First weld the liquid side connection 

pipe and then weld the gas side connection pipe. During welding, it’s necessary to use wet 

gauze to wrap up the two cut-off valves. Make sure the flame won’t burn the soundproof 

cotton or other components. 

DC Inverter Multi VRF System  

 
Fig. 16 

15 

Sayfa 20

DC Inverter Multi VRF System  

 
                                 Fig. 17 

4.3.5 Installation of Y-type Branch 

(1)  Y-type Branch 

 (2)  Y-type branch has several pipe sections with different dimension, which facilitates to 

match with various copper pipes. Use pipe cutter to cut in the middle of the pipe section that is of 

proper dimension and remove burrs as well. See Fig. 19. 

(3)  Y-type branch must be installed vertically or horizontally. 

 
Fig. 18 

 
Fig. 19 

16 

Sayfa 21

 
Branch shall be isolated by insulating material that can bear 120℃(248℉)or even higher temperature. The 
attached foam of branch cannot be taken as insulating material. 

4.3.6 Thermal Insulation for Pipeline 

(1)  For multi VRF system, every copper pipe should be labeled so as to avoid 

misconnection. 

(2)  At the branch inlet, leave at least 500mm(19-3/4inch) straight pipe section. 

(3)  Thermal insulation for pipeline 

 1)  To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid 

pipe must be wrapped with thermal insulating material and adhesive tape for insulation 

from the air. 

 2)  Joints of indoor and outdoor unit should be wrapped with insulating material and leave 

no gap between pipe and wall. See Fig. 20. 

 3)  When wrapping the tape, the later circle should cover half of the former one. Don’t wrap 

the rape too tight, otherwise the insulation effect will be weakened. 

 4)  After wrapping the pipe, apply sealing material to completely seal the hole on the wall. 

(1) 
Thermal insulating material shall be able bear the pipe temperature. For heat pump unit, liquid pipe should 
bear 70℃(158℉) or above and gas pipe should bear 120℃(248℉) or above. For cooling only unit, both liquid 
pipe and gas pipe should bear 70℃(158℉) or above. 

(2) 
Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of 
branches cannot be taken as insulating material. 

4.3.7 Support and Protection of Pipeline 

(1) 
Support should be made for hanging connection pipe. Distance between each support cannot be over 
1m(3-1/4feet). 
(2) 
Protection against accidental damage should be made for outdoor pipeline. When pipeline exceeds 
1m(3-1/4feet), a pinch board should be added for protection. 

4.4 Disassembly of Compressor Feet 

In order to prevent unit from damage during transportation, 2 metal pieces are fitted to 

outdoor unit’s compressor feet before unit leaves factory. See fig. 21. 

DC Inverter Multi VRF System  

 
Fig. 20 

17 

Sayfa 22

DC Inverter Multi VRF System  

When installing the unit, metal pieces for transportation must be removed. (except for 

GMV-60WL/A-T(U)).Then fasten the binding nuts again and wrap back soundproofing cotton.If 

unit runs with metal pieces fitting on, compressor will shake abnormally and unit’s operating life 

will be shortened. 

4.5 Vacuum Pumping, Refrigerant Adding 

Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra 
refrigerant in the outdoor unit for air purging!  

4.5.1 Vacuum Pumping 

(1)  Outdoor unit has been charged with refrigerant before delivery. Field-installed 

connection pipe needs to be charged with additional refrigerant. 

(2)  Confirm whether outdoor liquid and gas valves are closed. 

(3)  Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the 

outdoor valve, as shown below. 

 
Fig. 21 

 
Fig. 22 

18 

Sayfa 23

DC Inverter Multi VRF System  

4.5.2 Refrigerant Adding 

(1)  Refrigerant quantity of outdoor unit before delivery: 

Model 
GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 
GMV-60WL/A-T(U) 

6.5 
(229) 
 

Refrigerant Qty (kg/oz) 
5.0 
(176) 

5.0 
(176) 

(1) The refrigerant amount charged before delivery doesn’t include the amount that needs to be 

added to indoor units and the connection pipeline. 
(2) Length of connection pipe is decided on site. Therefore the amount of additional refrigerant 

shall be decided on site according to the dimension and length of field-installed liquid pipe. 
(3) Record the amount of additional refrigerant for convenience of after-sales service. 

(2)  Calculation of the amount of additional refrigerant 

Calculation method of the quantity of additional refrigerant (based on liquid pipe) 

Quantity of additional refrigerant = ∑length of liquid pipe X quantity of additional refrigerant per 

meter(39-3/8inch) 

Diameter of 

Φ22.2 
(Φ7/8) 

Φ19.05 

Φ15.9 
(Φ5/8) 

Φ12.7 
(Φ1/2) 

Φ9.52 
(Φ3/8) 

Φ6.35 
(Φ1/4) 

liquid pipe 
(mm/inch) 

(Φ3/4) 

kg/m 
0.35 
0.25 
0.17 
0.11 
0.054 
0.022 

oz/inch 
0.314 
0.224 
0.152 
0.099 
0.048 
0.020 

NOTICE! Liquid pipe that is within 20m(65-5/8feet) doesn’t need to be added with 

refrigerant. 

First confirm that there is no leakage from the system. When compressor is not working, 

charge additional R410a with specific amount to the unit through the filling opening of the liquid 

pipe valve of the outdoor unit. If required amount cannot be quickly filled due to pressure increase 

of the pipe, then set the unit in cooling startup and fill refrigerant from the low pressure check valve 

of the outdoor unit.  

(3)  Calculation example 

 
Fig. 23 

19 

Sayfa 24

DC Inverter Multi VRF System  

IDU 

No. 
IDU ① 
IDU ② 
IDU ③ 
IDU ④ 

Model 
Duct type 
GMV-ND18PLS/A-T(U) 

Duct type 
GMV-ND12PLS/A-T(U) 

Duct type 
GMV-ND09PLS/A-T(U) 

Duct type 
GMV-ND09PLS/A-T(U) 

Liquid pipe: 

No. 
A 
B 
C 
D 

Pipe size 
Φ9.52mm 
(Φ3/8inch) 

Φ9.52mm 
(Φ3/8inch) 

Φ9.52mm 
(Φ3/8inch) 

Φ6.35mm 
(Φ1/4inch) 

Length 
10m 
(32-3/4feet) 

5m 
(16-3/8feet) 

5m 
(16-3/8feet) 

5m 
(16-3/8feet) 

No. 
a 
b 
c 
d 

Pipe size 
Φ9.52mm 
(Φ3/8inch) 

Φ6.35mm 
(Φ1/4inch) 

Φ6.35mm 
(Φ1/4inch) 

Φ6.35mm 
(Φ1/4inch) 

Length 
3m 
(9-3/4feet) 

3m 
(9-3/4feet) 

2m 
(6-5/8feet) 

1m 
(3-1/4feet) 

Total length of each liquid pipe 

Φ9.52:A+B+C+a=10+5+5+3=23m(75-1/2 feet) 

Φ6.35: D+b+c+d=5+3+2+1=11m(36feet) 

NOTICE! Liquid pipe that is within 20m(65-5/8 feet) doesn’t need to be added with 

refrigerant. 

Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022=

0.404kg(14oz) 

4.6 Electric Wiring 

(1) 
All electrical installation must be performed by qualified technicians in accordance with local laws, regulations 
and this user manual. 

(2) 
Use air conditioner specialized power supply and make sure that it is consistent with system’s rated voltage.  

(3) 
Do not pull the power cord with force. 

(4) 
Caliber of the power cord must be large enough. A damaged power cord or connection wire must be replaced 
by specialized electrical cords. 
(5) 
Connect the unit to specialized grounding device and make sure it is securely grounded. It’s a must to install 
air switch and current circuit breaker that can cut off the power of the entire system. The air switch should 
include magnetic trip function and thermal trip function so that system can be protected from short circuit and 
overload. 

(6) 
Air conditioner belongs to class I electrical appliance, so it must be securely grounded. 

(7) 
The yellow-green wire inside the unit is a ground wire. Do not cut it off or secure it with tapping screws, 
otherwise it will lead to electric shock. 
(8) 
Power supply must include secure grounding terminal. Do not connect the ground wire to the following: 
①Water pipe; ②Gas pipe; ③Drain pipe; ④Other places that are deemed as not secure by professional 
technicians. 

4.6.1 Electrical Wiring 

(1). For solid core wiring (Fig.24) 

1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation 

about 25mm (15/16inch) . 

2) Using a screwdriver, remove the terminal screw(s) on the terminal board. 

20 

Sayfa 25

3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw. 

4) Shape the loop wire properly, place it on the terminal board and tighten securely 

with the terminal screw using a screwdriver. 

(2). For strand wiring  (Fig. 25) 

1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation 

about 10mm (3/8inch) . 

2) Using a screwdriver, remove the terminal screw (s) on the terminal board. 

3) Using a round terminal fastener or pliers, securely clamp a round terminal to each 

stripped wire end. 

4) Position the round terminal wire, and replace and tighten the terminal screw with a 

screwdriver.(Fig. 25) 

DC Inverter Multi VRF System  

Fig. 24 

Fig. 25 

Fig. 26 

21 

Sayfa 26

DC Inverter Multi VRF System  

(3). How to fix connection cord and power cord by cord clamp 

After passing the connection cord and power cord through the insulation tube, fasten it with the 

cord clamp.(Fig. 26) 

(1) 
Before starting work, check that power is not being supplied to the indoor unit and outdoor unit. 

(2) 
Match the terminal block numbers and connection cord colors with those of the indoor unit side. 
Erroneous wiring may cause burning of the electric parts. 

(3) 
Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.  

(4) 
Always fasten the outside covering of the connection cord with cord clamps. (If the insulator is not clamped, 
electric leakage may occur.) 

(5) 
Always connect the ground wire. 

4.6.2 Wiring Diagram 

(1) Connection of power cord and communication wire 

Separate power supply for IDU and ODU 

Communication wire 
between ODU and IDU

Indoor unit 
communication wire

Indoor unit 
communication wire

Wire(resistance-      

matching)

D1
D2
G1
G2

D1
D2
H1
H2

D1
D2
H1
H2

D1
D2
H1
H2

Outdoor 

Indoor 

Indoor 

Indoor 

unit

unit 2

unit N

unit 1

L N

L N

L N

L N

Remote 

Wired
controller

Wired
controller

Wired
controller

monitor

Power

Power
Power

Power

Fig.27 Connection of power cord and communication wire for IDU and ODU 

(2) The wiring diagram for power cord of outdoor unit and communication wire.  
 

22 

Sayfa 27

There are two wiring diagrams for communication wires of indoor/outdoor units and remote 

monitor:  

 
1.Real line method;  

2. Broken line method. Please select it based on the actual installation situation. 

There are two wiring diagrams for power cord:  

 
1.Real line method;  

2.Broken line method. Please select it based on the actual installation situation. 

(3) Selection of air switch and power cord: 

Model 
Power supply 

GMV-36WL/A-T(U) 
208/230V~ 60Hz 
35 
35 
31 

GMV-48WL/A- T(U) 
208/230V~ 60Hz 
45 
45 
34 

GMV-60WL/A- T(U) 
208/230V~ 60Hz 
60 
60 
39.8 
 

(1) 
Selection of circuit breaker and power cord in the above table is based upon unit’s maximum power 
(maximum current). 
(2) 
Specification of power cord is based on the working condition where ambient temperature is 40℃(104℉) and 
multi-core copper cable (working temperature is 90℃(194℉), e.g. power cable with YJV cross-linked copper, 
insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes, please adjust the 
specification according to national standard. 
(3) 
Specification of circuit breaker is based on the working condition where ambient temperature of circuit 
breaker is 40℃(104℉). If working condition changes, please adjust the specification according to national 
standard. 
 

DC Inverter Multi VRF System  

 
Fig.28 

Max Fuse 
Size/Fusible 

Max Ckt, Bkr 
Size/Disjoncteur Max. 

Min. Circuit Ampacity 

Max. 

(A) 

(A) 

(A) 

23 

Sayfa 28

DC Inverter Multi VRF System  

4.6.3 Engineering wiring of power supply and communication cable 

(1)Please refer Fig. 29 for engineering wiring. If there is the hole for cable tie in wiring route, 

please fix the wire with cable tie. Connect the power cord and communication cable to 

the corresponding terminal board and grounding screw according to the wiring diagram. 

(2)Please be noted that engineering wiring cannot touch the pipe and appliance. 

(3)This figure is only applicable for engineering wiring reference of power supply and 

communication cable. If there are differences between the figure structure and actual unit, 

please refer to the actual unit. 

(4)For engineering wiring, please refer to the wiring diagram provided with the unit. 

 
Fig. 29 Engineering Wiring View of GMV-36WL/A-T(U), GMV-48WL/A-T(U) and GMV-60WL/A- 

T(U) 

24 

Sayfa 29

5 Check Items after Installation and Test Operation 
5.1 Check Items after Installation 

Check items 
Possible conditions due to improper 

Each part of the unit is installed securely? 
Unit may drop, shake or emit noise. 
 

Gas leakage test is taken or not? 
Insufficient cooling (heating) capacity 
 

Unit gets proper thermal insulation or not? 
There may be condensation and dripping. 
 

Drainage is smooth or not? 
There may be condensation and dripping. 
 

Is the voltage in accordance with the rated voltage 
specified on the nameplate? 

is the electric wiring and pipe connection installed 
correctly? 

Unit is securely grounded or not? 
Electrical leakage 
 

Power cord meets the required specification? 
Unit may have malfunction or 
components may get damaged. 
 

Is the air inlet/outlet blocked? 
Insufficient cooling (heating) capacity 
 

Length of refrigerant pipe and the charging 
amount of refrigerant are recorded or not? 

Binding pieces on compressor feet are removed 
or not? 
Compressor may get damaged. 
 

5.2 Test operation and debugging 

(1) 
After finishing the first installation or replacing the main board of outdoor unit, it is necessary to perform test 
operation and debugging. Otherwise, unit won’t be able to work. 

(2) Test operation and debugging must be performed by professional technicians or under the guidance of 

professional technicians. 

5.2.1 Prepare the test operation and debugging 

(1) Do not connect power until all installation work is finished. 

(2) All control circuits and wires are correctly and securely connected. 

(3) Check whether the fixing loops for compressor fts are removed. 

(4) All small pieces, especially metal chips, thread ends and forceps holder, must be 

removed from the unit. 

(5) Check whether unit’s appearance and pipeline system has been damaged during 

transportation. 

(6) Calculate the quantity of refrigerant that needs to be added according to the pipe length. 

Pre-charge the refrigerant. In case that the required charging quantity is not reached 

while refrigerant can’t be added, record the quantity of refrigerant that still needs to add 

and complement the quantity during test operation.  For details of adding refrigerant 

during test operation, see below. 

(7) After refrigerant is added, make sure valves of outdoor unit are completely open. 

(8) For the convenience of troubleshooting during debugging, unit shall be connected to a 

PC with applicable debugging software. Make sure unit’s real-time data can be checked 

through this computer. The installation and connection of debugging software can be 

found in the Service Manual. 

DC Inverter Multi VRF System  

installation 
Check 

Unit may have malfunction or 
components may get damaged. 
 

Unit may have malfunction or 
components may get damaged. 
 

The refrigerant charging amount is not 
accurate. 
 

25 

Sayfa 30

DC Inverter Multi VRF System  

(9) Before test operation, make sure unit is power on and compressor has been preheated 

for more than 8 hours. Touch the unit to check whether it’s normally preheated. If yes, 

start test operation. Otherwise, compressor might be damaged. 

5.2.2 Test Operation and Debugging 

Description of test operation procedures and main board display of ODU 

Description of each stage of debugging progress 

—— 
Debugging 

code 
Progress code 
Status code 

LED1 
LED2 
LED3 

Code meaning and operation method 
Progress 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

db 
On  
01 
On  
AO 
On 
System is not debugged. 

Hold main board’s SW7 button for 
5s to start debugging. Main board will 
display as said in the left. 2s later, next 
step starts. 

01_ Set master 
unit 

db 
On 
01 
On 
OC 
On 

db 
On 
02 
On 
Ad 
Blink 
System is allocating addresses. 10s 
later, display as below: 

No master indoor unit. Display will be 
on for 1min, during which master IDU 
can be set manually. If not, system will 
set the unit with minimum IP address 
as the master IDU. 

02_ Allocate 
addresses 

db 
On 
02 
On 
L7 
Blink 

db 
On 
02 
On 
OC 
On 
Allocation is finished. 2s later, next 
step starts. 

db 
On 
03 
On 
01 
Blink 
System is confirming. 1s later, next 
step starts. 

03_ Confirm 
the quantity of 
ODU 

db 
On 
03 
On 
OC 
On 
System finishes confirmation. 2s later, 
next step starts. 

LED3 displays the quantity of indoor 
unit. Confirm the number manually. If 
the number is not consistent the 
display one, cut off power of IDU 
and ODU and check whether 
communication wire of IDU is 
correctly connected. After the check, 
connect power and start debugging 
from progress 01. If the number is 
then correct, press main board’s 
SW7 button to confirm. Then the 
display is as below: 

db 
On 
04 
On 
01~80 
Blink 

04_ Confirm 
the quantity of 
IDU 

db 
On 
04 
On 
OC 
On 
System has confirmed the quantity. 2s 
later, next step starts. 

Communication between master ODU 
and driver has error. Check the 
communication connection of 
ODU’s main board and drive board. 
When the error is eliminated, start next 
step. If power is off during 
troubleshooting, then restart 
debugging from progress 01 after 
power is on. 

db 
On 
05 
On 
C2 
On 

05_ Detect 
ODU’s internal 
communication 
and capacity 
ratio 

Communication of master ODU and 
driver is normal. Unit will display as in 
the left for 2s and detect the capacity 
ratio of IDU and ODU. If the ratio is 
within range, than next step will start 
2s later. If the ratio is out of range, unit 
will display as below: 

db 
On 
05 
On 
OC 
On 

26 

Sayfa 31

DC Inverter Multi VRF System  

Description of each stage of debugging progress 

—— 
Debugging 

code 
Progress code 
Status code 

LED1 
LED2 
LED3 

Code meaning and operation method 
Progress 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

Rated capacity ratio of IDU is too high. 
Change the combination way of IDU 
and ODU to make the ratio within 
range. And restart debugging from 
progress 01. 

db 
On 
05 
On 
CH 
On 

Rated capacity ratio of IDU is too low. 
Change the combination way of IDU 
and ODU to make the ratio within 
range. And restart debugging from 
progress 01. 

db 
On 
05 
On 
CL 
On 

Outdoor component’s error. LED3 will 
display the related error code. After 
errors are eliminated, system will 
start next step automatically. If power 
is off during troubleshooting, then 
restart debugging from progress 01 
after power is on. 

db 
On 
06 
On 
error 
code 
On 

06_ outdoor 
components 

db 
On 
06 
On 
OC 
On 
System detects no error on outdoor 
component. 10s later, next step starts. 

System detects error on indoor 
components. XXXX means the project 
code of IDU with error. 3s later, related 
error code will be showed. For 
instance, if no.1 IDU has d6 and d7 
errors, then the LED3 digital tube will 
show circularly 
00,01,d5,d6,07,92,d6,d7 every 2s. 
After errors are eliminated, system 
will start next step automatically. If 
power is off during troubleshooting, 
then restart debugging from progress 
01 after power is on. 

db 
On 
07 
On 
Error 
code 
On 

07_ Detect 
indoor 
components 

db 
On 
07 
On 
OC 
On 
No error on components of IDU. 2s 
later, next step starts. 

Preheat time for compressor is less 
than 8 hours. Display will be as in the 
left until the preheat time reaches 8 
hours. Press main board’s SW7 
button to confirm manually that the 
preheat time has reached 8 hours. 
Then start next step. (Note: 
Compressor may get damaged if it is 
started without 8 hours of preheat 
time) 

db 
On 
08 
On 
UO 
On 

08_ Confirm 
preheated 
compressor 

db 
On 
08 
On 
OC 
On 
Compressor has been preheated for 8 
hours. 2s later, next step starts.  

System is lack of refrigerant and 
display will be as in the left. Please cut 
off power of IDU and ODU and 
check if there is leakage on 
pipeline. Solve the leakage problem 
and complement refrigerant into the 
unit. Then connect power and restart 
debugging from progress 01. (Note: 
Before re-charging refrigerant, unit 
must be power off in case system 
starts progress 10 automatically.) 

09_ 
Refrigerant 
judgments 
before startup 

db 
On 
09 
On 
U4 
On 

db 
On 
09 
On 
OC 
On 
Refrigerant is normal and unit will 
display as in the left for 2s. Then next 

27 

Sayfa 32

DC Inverter Multi VRF System  

Description of each stage of debugging progress 

—— 
Debugging 

code 
Progress code 
Status code 

LED1 
LED2 
LED3 

Code meaning and operation method 
Progress 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

step starts. 

Valves of ODU are being inspected. 
Compressor will start operation for 
2min or so and then stop. The opening 
and closing status of outdoor valves 
are as below: 

db 
On 
10 
On 
ON 
On 

Outdoor valves are not fully turned on. 
Press main board’s SW6 button and 
display shows “db 09 OC”. Then check 
if the gas and liquid valves of ODU are 
completely open. After confirmation, 
press the SW6 button again. Then 
compressor will start running for about 
2min to inspect the status of valves. 

10_ Status 
judgments of 
outdoor valves 
before startup 

db 
On 
10 
On 
U6 
On 

Valves status is normal. Unit will 
display as in the left for 2s and then 
start next step. 

db 
On 
10 
On 
OC 
On 

Ready for units to start debugging. 
Press main board’s SW7 button to 
confirm startup of debugging. 2s later, 
main board will display as below: 

db 
On 
12 
On 
AP 
Blink 

Startup is confirmed. After displaying 
for 2s, system will choose “15_Cooling 
debugging” or “16_Heating debugging” 
according to ambient temperature. If 
the project requests to add 
refrigerant but it is not 
complemented before debugging, 
then refrigerant can be added in this 
process through the L-VALVE. 

12_ Confirm 
debugging 
startup 

db 
On 
12 
On 
AE 
On 

Debugging for cooling mode. If no 
malfunction occurs for 20min when 
compressor is running, then system 
will start progress 17; If malfunction 
occurs, unit will display as below: 

db 
On 
15 
On 
AC 
On 

15_ Cooling 
debugging 

Malfunction occurs when debugging 
for cooling mode. After all 
malfunctions are eliminated, system 
will start next step.  

db 
On 
15 
On 
Error 
code 
On 

Debugging for heating mode. If no 
malfunction occurs for 20min when 
compressor is running, then system 
will start progress 17; If malfunction 
occurs, unit will display as below: 

db 
On 
16 
On 
AH 
On 

16_ Heating 
debugging 

Malfunction occurs when debugging 
for heating mode. After all 
malfunctions are eliminated, system 
will start next step. 
17_ 
Debugging 
finished 

db 
On 
16 
On 
Error 
code 
On 

00 
On 
AC/AH 
On 
OFF 
On 
The entire unit has finished debugging 
and under standby-by condition. 

28 

Sayfa 33

DC Inverter Multi VRF System  

5.2.3 Appendix: Reference of normal operation parameters 

No. 
Debug item 
Parameter name 
Unit 
Reference  

Outdoor 
temperature 
℃(℉) 
—— 

1 

●When compressor starts, discharge temp in 
cool mode is within 70~105℃(158~221℉) 
and at least 10℃(50℉) higher than the high 
pressure saturation temp; 
●As for temp in heat mode, it is within 
65~90℃(149~194℉) and at least 10℃(50℉) 
higher than the high pressure saturation 
temp. 

2 
Compressor 
discharge temp 
℃(℉) 

●In cool mode, defrosting temp is 4~10℃
(39~50℉) lower than system’s high pressure 
value; 
●In heat mode, defrosting temp is about 2℃
(36℉) different from system’s low pressure 
value. 

3 
Defrosting temp 
℃(℉) 

●In cool mode, the normal high pressure 
value is within 20℃~55℃(68~131℉). 
According to the change of ambient temp and 
system’s operating capacity, the high 
pressure value will be 10℃~30℃(50~86℉) 
higher than ambient temp. The higher 
ambient temp is, the smaller temp difference 
is. If ambient temp is 25~35℃(77~95℉) in 
cool mode, system’s high pressure value will 
be within 44~53℃(111~127℉). 
●In heat mode, if ambient temp is above -5℃
(23℉), system’s high pressure value is within 
40~52℃(104~126℉). If ambient temp is low 
and many IDUs are turned on, the high 
pressure will be lower. 

4 
System high 

pressure 
℃(℉) 

ODU 
parameters 

System 
parameters 

●When ambient temp in cool mode is 
25~35℃(77~95℉), the low pressure value is 
0~8℃(32~46℉). 
●When ambient temp in heat mode is above 
-5℃(23℉), the low pressure value is -15~8℃
(5~46℉). 

5 
System low 

pressure 
℃(℉) 

●In cool mode, the thermal electronic 
expansion valve remains 480PLS. 
●In heat mode, the adjustable opening angle 
of EXV is 60~480PLS. 

6 
Opening angle of 

thermal EXV 
PLS 

GMV-36WL/A-(U) 
GMV-48WL/A-(U) 
Changes in 10Hz~80Hz. 

7 
Compressor’s 
operating freq 
HZ 

GMV-60WL/A-(U) 
Changes in 16Hz~80Hz 

8 
Compressor’s 
operating current 
A 
When compressor works normally, the current 
is no more than 22.6A. 

When ambient temp is below 35℃(95℉), IPM 
temp is lower than 80℃(176℉) and the 
highest temp won’t be above 95℃(203℉). 

9 
Compressor’s 

IPM temp 
℃(℉) 

Changes in 0~49Hz 
according to system’s 
pressure. 

GMV-36WL/A-(U) 
GMV-48WL/A-(U) 

10 
Fan motor’s 
operating freq 
HZ 

Changes in 0~40Hz 
according to system’s 
pressure. 
11 
IDU 
IDU ambient temp 
℃(℉) 
—— 

GMV-60WL/A-(U) 

29 

Sayfa 34

DC Inverter Multi VRF System  

No. 
Debug item 
Parameter name 
Unit 
Reference  
12 
parameters 

13 

14 
Opening angle of 

15 
Communication parameters 
Communication 

16 
Drainage system 
—— 
— 

Compressor and indoor/outdoor fan motor do 
not have strange noise. Unit can operate 
normally. 
6 Common Malfunctions and Troubleshooting 

17 
Others 
—— 
— 

(1) 
If there is abnormal condition (e.g. unpleasant smell), turn unit off and disconnect power immediately. Then 
contact Gree authorized service center. If unit continues operation despite the abnormal condition, it may get 
damaged and lead to electric shock or fire hazard. 

(2) 
Do not repair the air conditioner by yourself. Improper maintenance may lead electric shock or fire hazard. 
Please contact Gree authorized service center for maintenance 
 
 
 
 
 
 
 
 
 

●According to ambient temp, for a same IDU 
in cool mode, the inlet temp will be 1℃~7℃
(34~45℉) lower than the outlet temp, and 
4~9℃(39~48℉) higher than the low pressure 
value. 
●For a same IDU in heat mode, the inlet temp 
will be 10℃~20℃(50~68℉) lower than the 
outlet temp. 

Indoor heat 
exchanger’s inlet 

℃(℉) 

temp 

●In cool mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 
●In heat mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 

GMV-36WL/A-(U) 
GMV-48WL/A-(U) 

indoor EXV 
PLS 

●In cool mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 
●In heat mode, the 
opening angle of 
indoor EXV varies 
within 40~480PLS. 

GMV-60WL/A-(U) 

Number of IDUs detected by software is the 
same with the actual number. No 
communication error. 

data 
— 

Indoor unit can drain water out completely 
and smoothly. Condensate pipe has no 
backward slope of water; Water of outdoor 
unit can be drained completely through 
drainage pipe. No water drop from unit base. 

30 

Sayfa 35

●Please check the items below before calling for maintenance. 
Problems 
Causes 
What to do 

Fuse or circuit breaker is cut off. 
Replace fuse or reset the circuit 
breaker. 

Power failure 
Restart unit when power is 
restored. 
Power is not connected. 
Connect the power. 
Remote controller’s power is not enough 
Replace new battery. 

Unit doesn’t work. 

Remote controller is out of the control range. 
Control range is within 
8m(26feet). 
Unit runs but stops 

Air inlet or air outlet of indoor and outdoor units is 
blocked. 
Clear obstructions. 

immediately. 

Air inlet or air outlet of indoor and outdoor units is 
blocked. 
Clear obstructions. 

Improper temp setting 
Adjust setting at remote 
controller or wired controller 

Fan speed is set too low. 
Adjust setting at remote 
controller or wired controller 

Abnormal cooling or 

Wind direction is not correct. 
Adjust setting at remote 
controller or wired controller 
Door or window is open. 
Close the door or window. 
Direct sunshine 
Draw curtain or louver. 
Too many people in the room. 
 
Too many heat resources in the room. 
Reduce heat resources. 
Filter is blocked and dirty. 
Clean the filter 
NOTICE! If problem cannot be solved after checking the above items, please contact Gree 
service center and describe the cases and models. 
●Following circumstances are not malfunctions. 
Malfunction 
Reason 

heating 

Overload protection switch makes it run after a 
3-min delay. 
Power is just turned on. 
Standby operation lasts for about 1min. 
Mist comes from 

Unit starts up immediately after it is 
turned off. 

Unit doesn’t run. 

the unit. 
Under cooling 
Indoor air with high humidity is cooled rapidly. 

Slight cracking sound is heard when unit 
is just turned on. 

It is the noise when electronic expansion valve is 
initialized. 
There is consecutive sound when 
cooling. 

There is sound when unit starts or stops. 
It is the sound when gas refrigerant stops 
flowing. 
There is slight and consecutive sound 
when unit is running or after running. 
This is the sound of drainage operation. 

Noise is emitted. 

This is the sound caused by the expansion of 
panel and other parts of the unit due to 
temperature change.  
Unit blows out 

Cracking sound is heard when unit is 
running or after running. 

Unit starts up after not operating for a 
long time. 
Dust in indoor unit is blown out. 

dust. 

Unit emits odor. 
Under operation 
Unit absorbs the room odor and then blows it 
out. 
 

DC Inverter Multi VRF System  

It is the sound for gas refrigerant flowing in the 
unit. 

31 

Sayfa 36

DC Inverter Multi VRF System  

7 Error Indication 

Inquiry method of error indication: combine division symbol and content symbol to check the 

corresponding error. 

For example, division symbol L and content symbol 4 together means over-current protection. 

Content 

symbol 
Division 
symbol 

0 
1 
2 
3 
4 
5 

Auxiliary 

Freeze 
prevention 

L 
Malfunction of 

Protection of 

Water-full 
protection 

Over-curren

heating 
protection 

IDU (uniform) 

indoor fan 

t protection 

protection 

Indoor  

Malfunction 

Malfunction 

Malfunction 

of 
entry-tube 
temperature 

d 
 
Indoor PCB 

of ambient 
temperature 

of middle 
temperature 

is poor 
 

sensor 

sensor 

sensor 

High 
discharge 
temperature 

Discharge 
low-temperatur

E 
Malfunction of 
ODU (uniform) 

High-pressur

Low-pressur

e protection 

e protection 

protection 

e protection 

of 
compressor 

Malfunction 
of discharge 
temperature 

Malfunction 

Malfunction 

F 
Main board of 

of 
high-pressur

of 
low-pressure 

ODU is poor 

sensor of 
compressor 

e sensor 

sensor 

1 

Over-current 
protection of 
compressor 1 

Outdoor  

J 
 

Malfunction 

Malfunction 

Malfunction 

Malfunction of 

of outdoor 

of liquid 
temperature 

of gas 
temperature 

defrosting 
temperature 

b 
 

ambient 
temperature 

sensor of 
sub-cooler 

sensor of 
sub-cooler 

sensor 1 

sensor 

Driving board 

Voltage 
protection of 
driving board 

Reset 
protection of 

malfunction of 

of 
compressor 

Drive PFC 

Over-curren

driving board 
of compressor 

protection 

t protection 

P 

driving 
module of 
compressor 

operates 
abnormally 

power of 
compressor 

of 
compressor 

of inverter 
compressor 

(uniform) 

(uniform) 

(uniform) 

Wrong setting 

Wrong 
address for 

Preheat time of 

of ODU’s 

U 

compressor is 

capacity 
code/jumper 

driving 
board of 
compressor 

insufficient 

cap 

Debuggin

Communication 

Communicatio

g  

malfunction 
between main 

Alarm 
because 
project code 

n malfunction 
between IDU,  

Malfunction 

C 

control and 

of lack of 

ODU and 
IDU’s wired 

inverter 
compressor 

IDU 

of IDU is 
inconsistent 

controller 

driver 

32 

Sayfa 37

DC Inverter Multi VRF System  

Content 

symbol 
Division 
symbol 

0 
1 
2 
3 
4 
5 

Inquiry of 
compressor 

A 
Unit waiting for 

 
Defrosting  
Oil-return 
Online test 

debugging 

operation 
parameters 

Setting of upper 

Status  

limit of 
IDU/ODU 

SE operation 

Setting of 
defrosting 

n 

setting of 

capacity 
distribution 

system 

cycle K1 

ratio 

Content 

symbol 
Division 
symbol 

6 
7 
8 
9 
A 
H 

1-to-more: 
IDU series 
is 
inconsisten
t 

Alarm due to 
bad air 
quality 
(Fresh air 
unit) 

1-to-more: 
number of IDU 
is inconsistent 

L 
Mode shock 
No main IDU 
Power supply 
is insufficient 

Malfunction 
of exit-tube 
temperature 
sensor 

Web 
address of 
IDU is 
abnormal 

Malfunction 
of humidity 
sensor 

PCB of wired 
controller is 
abnormal 

 
Malfunction of 
jumper cap 

d 

High pressure 
ratio 
protection of 
system 

Protection 
due to 
abnormal 
pressure 

Gas-mixing 
protection of 
4-way valve 

J 
 

Indoor  

Malfunction 
of inlet temp 
sensor of 
gas-liquid 
separator 

Malfunction 
of outlet 
temp sensor 
of gas-liquid 
separator 

Malfunction of 
heat exchanger 
temperature 
sensor 

Clock of 
system is 
abnormal 

b 

Malfunction 
of drive 
temperature 
sensor of 
compressor 

Drive IPM 
high 
temperature 
protection of 
compressor  

High-voltage 
protection of 
compressor’
s drive DC 
bus bar 

Drive IPM 
module 
protection of 
compressor 

Desynchronizin
g protection of 
inverter 
compressor 

P 

Alarm 
because 
valve is 
abnormal 

Short-circuit 
malfunction of 
IDU 

Malfunction of 
pipe-line for 
ODU 

U 

Debuggin
g  

Rated 
capacity is 
too high 

C 
 
 
 
 
 

Heat pump 
function 
setting 

EU AA 
level EER 
test mode 

Quiet mode 
setting 

Vacuum pump 
mode 
IPLV test 

A 

Heating  

Status  

Engineerin
g No. 
inquiry of 
indoor unit 

Malfunctio
n inquiry of 
unit 

Paramete
r inquiry 
of unit  

 
Heat pump 
unit 

Heating only 
unit 

n 

33 

Sayfa 38

DC Inverter Multi VRF System  

Content 

symbol 
Division 
symbol 

C 
L 
E 
F 
J 
P 

Models for 
IDU and 
ODU are not 
matched 

L 

Malfunction of 
air-outlet 
temperature 
sensor(Fresh 
air unit) 

Abnormal 
setting for 
capacity 
button 

Malfunction of 
indoor CO2 
sensor (fresh 
air unit) 

d 

Drop 
protection of 
discharge 
temperature 
sensor of 
compressor 
1 

E 

Indoor  

F 
 
 
 
 
 
Malfunction 
of DC motor 

J 
 
High-pressure 
protection 
 
 
 
 

Drive current 
detection 
circuit 
malfunction 
of 
compressor 

Drive 
charging 
circuit 
malfunction 
of 
compressor 

Low-voltage 
protection of 
compressor’s 
drive DC bus 
bar 

Failure 
startup of 
inverter 
compressor 

AC current 
protection of 
inverter 
compressor 

Phase-lacking 
of inverter 
compressor 

P 

Drive current 
detection 
circuit 
malfunction 
of fan 

Drive 
charging 
circuit 
malfunction 
of fan 

Low-voltage 
protection of 
fan’s drive DC 
bus bar 

Failure 
startup of 
inverter fan 

AC current 
protection of 
inverter fan 

Phase-lacking 
of inverter fan 

H 

Setting of 
main IDU is 
successful 

Charging of 
refrigerant is 
invalid 

Wrong 
button-dial 

U 

Debugging  

Malfunction 
of lack of 
main control 
unit 

Malfunction 
of multiple 
main control 
units 

Malfunction 
of multiple 
main wired 
controllers 

Malfunction 
of multiple 
main wired 
controllers 

Rated capacity 
is too low 
 

C 

Debugging 
confirmation 
for startup of 
unit 

Charging 
refrigerant 
automatically 

Charging 
refrigerant 
manually 

Alarm for 
cleaning 
filter 

A 
Cooling 

Fan 

Status  

n 
Cooling only 
unit 
 
Negative sign 
code 
Fan model 
 
 

34 

Sayfa 39

DC Inverter Multi VRF System  

Content 
 symbol 
Division  
symbol 

U 
b 
d 
n 
y 

Communication 

malfunction 
between IDU and 
the receiving lamp 

Overflow 
distribution of 

Debugging  
C 

IP address 

plate 

Emergency 

Status  
A 
Long-distance 
emergency stop 

stop of 
operation 

Limit operation 
 
 

8 Function Setting of Outdoor Unit 

When debugging is finished, press SW3 on the master unit and unit will be ready for function 
setting. Default display of outdoor unit’s main board is as below: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress 
Display 
Current status 
Display 

A7 
Blink 
00 
Blink 
00 
Blink 

Then press SW1 button(▲) and SW2 button(▼) on the master unit to switch function codes of 

LED1 to select relevant functions. 

Function setting includes: outdoor silent mode setting (A7), heating and cooling function 

setting (A6), compulsory defrosting (n3) 

After selecting relevant functions, press SW7 to confirm and start setting this function. Main 

board of outdoor unit will display as below: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress 
Display 
Current status 
Display 

A7 
On 
00 
Blink 
oC 
Blink 

A6 
On 
CH 
Blink 
CH 
Blink 

n3 
On 
35 
Blink 
oC 
Blink 

8.1 ODU Quiet Function 

This function is suitable for projects that have strict requirements for noise. It includes two 

modes: smart night silent mode, compulsory silent mode. 

When unit enters function setting, main board of outdoor unit will display as below: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress 
Display 
Current status 
Display 

A7 
On 
00 
Blink 
oC 
Blink 
Press SW1 button (▲) and SW2 button (▼) to select the following silent modes. 

LED1 
LED2 
LED3 

Function code 
Silent mode 
Display 
Current status 
Display 

A7 
00~12 
Blink 
oC 
Blink 
When applicable mode is selected, press SW7 to confirm. Main board of outdoor unit will 

display as below: 

35 

Sayfa 40

DC Inverter Multi VRF System  

LED1 
LED2 
LED3 

Function code 
Silent mode 
Display 
Current status 
Display 

A7 
00~12 
On 
oC 
On 

Notice: code 00 of LED2 refers to normal mode. Codes 01~09 refer to smart night silent mode. 

Codes 10~12 refer to compulsory silent mode. When setting is finished, master unit will memorize 

it so that it can’t be cancelled even when power is on or off. 

Then press SW6 on the master unit to return to the previous step. (If this button is pressed 

when function is being set, system will return to the previous step. If SW6 is pressed when setting 

is finished, system will resume displaying the current operation status.) 

If then no motion is taken to the master unit for 5min, unit will exit and resume displaying the 

current status. 

8.2 Cool & Heat Function 

This function can set operation modes and prevent mode collision that is caused by setting 

different modes for different indoor units. It is especially suitable for hotels and other small 

business areas. There are 3 levels for this setting: 

Level A—Mode Lock Control 

Upon entering this function setting, main board of outdoor unit will display as below: 

LED1 
LED2 
LED3 

Function code 
Current progress 
Display 
Current status 
Display 

A6 
nC 
Blink 
nC 
Blink 
Press SW1 button (▲) and SW2 button (▼) to select the following functions: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress/mode 
Display 
Current status 
Display 

A6 
On 
nC 
Blink 
nC 
Blink 

A6 
On 
nH 
Blink 
nH 
Blink 

A6 
On 
nA 
Blink 
nA 
Blink 

A6 
On 
nF 
Blink 
nF 
Blink 

When applicable mode is selected, press SW7 to confirm. The related display is as below: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress/mode 
Display 
Current status 
Display 

A6 
On 
nC 
On 
nC 
On 

A6 
On 
nH 
On 
nH 
On 

A6 
On 
nA 
On 
nA 
On 

A6 
On 
nF 
On 
nF 
On 

This setting will be memorized by master unit and can’t be cancelled even when power is on 

or off. 
 

Then press SW6 on the master unit to return to the previous step.  

If then no motion is taken to the master unit for 5min, unit will exit and resume displaying the 

current status. 

(If this button is pressed when function is being set, system will return to the previous step. If 

SW6 is pressed when setting is finished, system will resume displaying the current operation 

status.) 

36 

Sayfa 41

Default setting is “nA” cooling and heating type. 

Level B—IDU Mode Auto Control 

When Level A is disabled or outdoor unit is set to be cooling and heating type, the operation 

mode within one system depends on the master-salve setting of indoor units. 

8.3 Forced Defrosting 

This function can only be set when outdoor compressor is running. 

Upon entering this function, main board of outdoor unit will display as below: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress/mode 
Display 
Current status 
Display 

n3 
On 
00 
Blink 
00 
Blink 

Press SW7 to confirm. When system enters this function, main board of outdoor unit will 

display as below: 

LED1 
LED2 
LED3 

Function code 
Display 
Current progress/mode 
Display 
Current status 
Display 

n3 
On 
00 
On 
00 
On 

Then unit will be in compulsory defrosting mode. Once unit is under compulsory defrosting, 

this mode can only be stopped when requirements for exit are met. 

8.4 Restore Factory Defaults 

(1) If you want to restore factory defaults, hold SW8 button on the main board of ODU for more 

than 10s, then all LEDs will blink for 3s. Main board will cancel all setting, including the IP 

addresses and project codes of IDU and ODU. The mark for finished debugging is “0”. 

(2) If you want to restore factory defaults and don’t need project debugging, then hold SW3 and 

SW8 on the main board of ODU for more than 10s, then all LEDs will blink for 5s. All settings 

are cleared out, including the IP addresses and project codes of IDU and ODU. The mark for 

finished debugging remains the same. 

(3) When you only want to restore the default functions, hold SW5 and SW8 button for more than 

10s, then all LED will blink for 7s. All function settings are cleared out, but IDU and ODU’s 

project codes and the mark for finished debugging remain the same. 

8.5 Static Pressure Function 

If ODU’s installation area is not convenient for releasing air and users do not have strict 

requirements for ODU noise, this function can be set to satisfy the heat exchange of ODU. 

Before power on, set codes of SA6 of main board. The relevant static pressure is: 

Code setting SA6 
Static pressure 

(Pa) 
DIP1 
DIP2 

0 
0 
0 

1 
0 
20 

Note: code of number side is “1”; default code of SA6 is “00”. 

DC Inverter Multi VRF System  

37 

Sayfa 42

DC Inverter Multi VRF System  

9 Maintenance and Care 

Regular check, maintenance and care can extend unit’s service life. Please have specialized 

person in charge of the management of air conditioners. 

9.1 Outdoor Heat Exchanger 

 Outdoor heat exchanger shall be cleaned regularly, which is at least once every two months. 

You can use a dust catcher with nylon brush to clean away the dust on the heat exchanger. If 

compressed air source is available, it also can be used to clean the heat exchanger. Do not clean 

it with water. 

9.2 Drain Pipe 

Please check regularly whether drain pipe is blocked or not. Make sure condensate can be 

drained out smoothly. 

9.3 Notice before Seasonal Use 

(1)  Check whether air inlets and air outlets of indoor and outdoor units are blocked; 

(2)  Check whether ground connection is reliable or not; 

(3)  Check whether batteries in the remote controller are replaced or not; 

(4)  Check whether air filter is properly installed; 

(5)  If unit starts up after not operating for a long time, it should be power on 8 hours before 

operation starts so as to preheat the outdoor compressor; 

(6)  Check whether outdoor unit is securely installed. If there is any problem, please contact 

Gree authorized service center. 

9.4 Maintenance after Seasonal Use 

(1)  Disconnect power of the entire system; 

(2)  Clean the air filter and outer case of indoor and outdoor units; 

(3)  Clean away the dust and obstacles on indoor and outdoor units; 

(4)  If outdoor unit has rust, please apply some paint to it so as to prevent the rust from 

growing. 

9.5 Parts Replacement  

Parts and components can be obtained from nearby Gree office or Gree distributor. 

When you are conducting air tightness test and leakage test, do not mix oxygen, C2H2 or other dangerous gas into 
the refrigerant circuit. Otherwise, it may lead to danger. Use nitrogen or refrigerant to conduct the tests. 

38 

Sayfa 43

10 After-sales Service 

     If there’s quality defect or other problems in the product, please contact Gree local 

after-sales service department for help. 

Warranty must be based on the following conditions: 

(1) Product’s initial startup must be performed by professional technicians from Gree service 

center or persons assigned by Gree. 

(2) Only Gree spare parts are used, 

(3) All instructions of unit operation and maintenance in this manual must be strictly followed 

according to set period and set frequency. 

(4) Any breach of the above conditions will disable the warranty. 

DC Inverter Multi VRF System  

39 

Sayfa 44

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070
Tel: (+86-756) 8522218