DC Inverter Side Discharge VRF Ⅱ for 
North America 

 
 
 
 
Capacity: 24 kBtu/h~60 kBtu/h 
Rated Frequency: 60 Hz 
 
 
 
 

Sayfa 2

PRODUCT ........................................................................................................................... 2 

1 Product List ....................................................................................................................... 2 

2 Product Features .............................................................................................................. 2 

2.1 General introduction ................................................................................................................ 2 

3 Specifications .................................................................................................................... 3 

3.1 Outdoor Unit ............................................................................................................................ 3 

3.2 Operation range ....................................................................................................................... 5 

4 Product Capacity Correction ............................................................................................. 5 

4.1 Instruction of Product Capacity Correction .............................................................................. 5 

4.2 Capacity Code ......................................................................................................................... 5 

4.3 Capacity Correction Formula ................................................................................................... 6 

5 Principal of Operation ....................................................................................................... 7 

CONTROL ......................................................................................................................... 10 

1 Units’ Control .................................................................................................................. 10 

1.1 Schematic diagram of units’ control ....................................................................................... 10 

1.2 Operation Flow Chart ............................................................................................................. 11 

1.3 Unit Control Functions ........................................................................................................... 12 

2 Wired Controller .............................................................................................................. 13 

2.1 Control panel ......................................................................................................................... 13 

2.2 Installation and removal ......................................................................................................... 16 

3 Remote Controller ........................................................................................................... 19 

4 Monitoring Software ........................................................................................................ 21 

4.1 Function introduction ............................................................................................................. 21 

4.2 Connection of computer and units ......................................................................................... 21 

4.3 Parts introduction ................................................................................................................... 22 

4.4 Software introduction ............................................................................................................. 24 

INSTALLATION .................................................................................................................. 64 

1 Engineering Installation Preparation and Notice ............................................................. 64 

1.1 Installation notice ................................................................................................................... 64 

1.2 Installation key points and importance ................................................................................... 64 

2 Installation Materials Selection ....................................................................................... 65 

2.1 Refrigerant piping .................................................................................................................. 65 

2.2 Condensate water pipe .......................................................................................................... 66 

2.3 Insulation material ................................................................................................................. 66 

2.4 Communication cable and control cable ................................................................................ 66 

2.5 Power cable ........................................................................................................................... 67 

2.6 Hanger rod and support ......................................................................................................... 67 

3 Installation of outdoor unit ............................................................................................... 67 

CONTENTS 

Sayfa 3

3.1 Check before installation ....................................................................................................... 67 

3.2 Selection of installation site ................................................................................................... 67 

3.3 Carrying and installing outdoor unit ....................................................................................... 68 

3.4 Installation notices ................................................................................................................. 68 

3.5 Fixing and damping of unit .................................................................................................... 68 

3.6 Outline dimension and position of installation hole ................................................................ 68 

3.7 Installation space requirement ............................................................................................... 70 

4 Installation of Electronic Expansion Valve Assy (unit with external EXV) ........................ 70 

5 Installation of Refrigerant Pipeline .................................................................................. 70 

5.1 Allowable Length and Height Difference of Connection Pipe ................................................ 70 

5.2 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch ..................................... 72 

5.3 Selection of Indoor Branches ................................................................................................ 73 

5.4 Dimension of Pipe between Indoor Branches ....................................................................... 73 

5.5 Dimension of Pipe between Indoor Branch and IDU ............................................................. 74 

6 Installation of Connection Pipe ....................................................................................... 75 

6.1 Flaring Process ...................................................................................................................... 75 

6.2 Disassembly of Compressor Feet ......................................................................................... 80 

6.3 Vacuum Pumping, Refrigerant Adding ................................................................................... 80 

7 Electric Wiring ................................................................................................................. 84 

7.1 Wiring Diagram ...................................................................................................................... 84 

7.2 Power Cable Wire Gauge and Circuit Breaker Selection ...................................................... 85 

8 Debugging of Unit ........................................................................................................... 86 

8.1 Preparation for debugging ..................................................................................................... 86 

8.2 Debugging of unit .................................................................................................................. 87 

8.3 Parameters reference value for the normal operation of unit ................................................ 93 

1 Malfunction List ............................................................................................................... 96 

1.1 Malfunction list for the wired controller .................................................................................. 96 

1.2 Status display table for indicators on main board of outdoor unit .......................................... 96 

2 Troubleshooting ............................................................................................................ 100 

3 Power Distribution of Unit ............................................................................................. 110 

3.1 Power distribution of unit ...................................................................................................... 110 

3.2 Main electric parts ................................................................................................................ 110 

3.3 Circuit diagram ..................................................................................................................... 111 

4 Removal of Parts .......................................................................................................... 113 

4.1 Key parts .............................................................................................................................. 114 

4.2 Removal of key parts ............................................................................................................ 115 

5 Common Maintenance .................................................................................................. 135 

5.1 Vacuum drying for the system ............................................................................................. 135 

6 Exploded View of Unit and Parts’ List ........................................................................... 136 

Sayfa 4

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

PRODUCT 

1 

Sayfa 5

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

PRODUCT 

1 Product List 

Cooling 
Capacity 

Heating 
Capacity 
Power 
Supply 
Refrigerant 
Appearance 

Model 
Product 

Code 

kW(Btu/h) 
kW (Btu/h) 

GMV-24WL/C-T(U) 
CN850W0

740 
7 
(24000) 

8.2 
(28000) 

 
GMV-28WL/C-T(U) 
CN850W0

750 
8.2 
(28000) 

8.8 
(30000) 

GMV-36WL/A-T(U) 
CN850W0

230 
11 
(37500) 

12.3 
(42000) 

208/230V
~ 
60Hz 
R410A 

GMV-48WL/A-T(U) 
CN850W0

220 
14.1 
(48000) 

15.8 
(54000) 

GMV-60WL/A-T(U) 
CN850W0

270  
17.6 
(60000) 

18.7 
(64000) 

GMV-36WL/C-T(U) 
CN850W1

070 
11 
(37500) 

12.3 
(42000) 

GMV-48WL/C-T(U) 
CN850W1

080 
14.1 
(48000) 

15.8 
(54000) 

GMV-60WL/C-T(U) 
CN850W1

090 
17.6 
(60000) 

18.7 
(64000)) 

2 Product Features 

2.1 General introduction 

Gree DC Inverter Multi VRF System II is the latest generation of DC inverter units. One set of 

air-cooled outdoor unit can be connected with multiple direct evaporation indoor units that are of the 

same or different forms and capacity. This refrigerating system can directly provide air conditioning for 

one or more areas, and is applicable for residential and light commercial uses. It features high energy 

efficiency, strong anti-interference capability, long connectable pipe, wide operation range, good sound 

quality, intelligent capacity regulation, complete protection, etc. 

2.1.1 Features 

(1) Super high energy efficiency 

The 2nd generation of DC Inverter Multi VRF System adopts DC motor to realize complete direct 

current and upgrade the energy efficiency. SEER is up to 16; HSPF of GMV-24WL/C-T(U) 、

GMV-28WL/C-T(U) 、GMV-36WL/A-T(U) and GMV-48WL/A-T(U) is up to 9; HSPF of and 

2 

Sayfa 6

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-60WL/A-T(U) is up to 8.2. 

For the upgraded efficiency DC Inverter Multi VRF System, SEER is up to 19.5~22; HSPF of 

GMV-36WL/C-T(U) and GMV-60WL/C-T(U) is up to 10.5~11; HSPF of GMV-48WL/C-T(U) is up to 

10.6~10.8.  

(2) New generation CAN bus communication 

Due to the latest communication method—CAN Bus Communication, system’s anti-interference 

capability is stronger and the control on indoor units is more accurate, with higher reliability. Specialized 

shield wire is no more needed and ordinary communication wire can be applied in the construction, 

which has increased the installation flexibility.  

(3) Long connection pipe 

The maximum length of connection pipe is 300m(984ft) (in total) and the farthest connection pipe 

between indoor and outdoor units can be 120(394ft)m’s long, which has extended the installation 

condition and reduced the limit of installation distance. 

(4) Wide operation range 

Units can operate reliably in a wide temperature range (cooling: -5~48℃(23~118℉) ), heating: 

-20~27℃(-4~81℉) 

(5) Fine sound quality 

Through a series of optimized measures, system has reduced the throttle noise and oil return noise 

of indoor units, gas bypass noise, etc. so that units are more comfortable regarding sound quality. 

(6) Intelligent PID capacity regulation 

With the independently developed PID capacity regulation technology, units are able to control the 

indoor ambient temperature more quickly and reduce the fluctuation of room temperature. 

(7) Complete protection 

Units are equipped with a series of protection to accurately identify errors and protect the units, 

which has ensured reliable and safe operation. 

3 Specifications 

3.1 Outdoor Unit 

Model 
GMV-24WL/C

GMV-28WL/C

GMV-36WL/A-

GMV-48WL/A-

GMV-60WL/A-

-T(U) 

-T(U) 

T(U) 

T(U) 

T(U) 

kW 
7 
8.2 
11 
14.1 
17.6 

Cooling capacity 

Btu/h 
24000 
28000 
37500 
48000 
60000 

kW 
8.2 
8.8 
12.3 
15.8 
18.7 

Heating capacity 

Btu/h 
28000 
30000 
42000 
54000 
64000 

m³/h 
3900 
3900 
6000 
6300 
7800 

Circulating air 

volume 

CFM 
2295 
2295 
3531 
3708 
4590 

Noise 
dB(A) 
57 
57 
55 
56 
63 

Kg 
2.4 
2.4 
5 
5 
6.5 

Refrigerant charge 

volume 

oz 
84.7 
84.7 
176 
176 
229 

Power supply 
208/230V~60
Hz 

208/230V~60
Hz 

208/230V~60
Hz 

208/230V~60
Hz 

208/230V~60
Hz 

3 

Sayfa 7

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Model 
GMV-24WL/C

GMV-28WL/C

GMV-36WL/A-

GMV-48WL/A-

GMV-60WL/A-

T(U) 
Rated 
power 

-T(U) 

-T(U) 

T(U) 

T(U) 

Cooling 
kW 
2.00 
2.70 
3.25 
4.47 
6.45 

Heating 
kW 
2.40 
2.60 
3.72 
3.93 
5.60 

input 

mm 
980×360×790 
900×340×134
5 
940×320×1430 

Unit Dimensions 

(WxDxH) 

inch 
38 6/19×14 3/16×31 2/16 
35 7/16 
×13 3/8×53 
37×12 9/16×56 1/4 

mm 
1094×474×817 
998×458×151
5 
1033×433×1580 

Dimensions 

(WxDxH) 

inch 
43 1/16×18 11/16×32 3/16 
39 5/16 
×18×59 5/8 
40 5/8×17×62 3/16 

Compressor 
QXFS-D25Zx090H 
QXAS-F428z

X050A 
LNB53FCFMC 

Water-proof level 
IPX4 
IPX4 
IPX4 
IPX4 
IPX4 

Suitable climite 
T1 
T1 
T1 
T1 
T1 

mm 
Φ15.9 
Φ15.9 
Φ15.9 
Φ15.9 
Φ19.05 

Gas 

inch 
Φ5/8 
Φ5/8 
Φ5/8 
Φ5/8 
Φ3/4 

Connecti

mm 
Φ9.52 
Φ9.52 
Φ9.52 
Φ9.52 
Φ9.52 

on pipe 

Liquid 

inch 
Φ3/8 
Φ3/8 
Φ3/8 
Φ3/8 
Φ3/8 

Connection 

Bell mouth 
connection 

Bell mouth 
connection 

Bell mouth 
connection 

Bell mouth 
connection 

Bell mouth 
connection 

Method 

Net weight 
Kg 
80 
80 
110 
110 
124 
oz 
2822 
2822 
3880 
3880 
4375 

Model 
GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 
GMV-60WL/C-T(U) 

kW 
11 
14.1 
17.6 

Cooling capacity 

Btu/h 
37500 
48000 
60000 

kW 
12.3 
15.8 
18.7 

Heating capacity 

Btu/h 
42000 
54000 
64000 

m³/h 
6000 
6300 
7800 

Circulating air volume 

CFM 
3531 
3708 
4590 

Noise 
dB(A) 
55 
55 
63 

Kg 
3.3 
3.3 
4.6 

Refrigerant charge 

volume 

oz 
116.4 
116.4 
162.3 

Power supply 
208/230V~60Hz 
208/230V~60Hz 
208/230V~60Hz 

Rated 
power 

Cooling 
kW 
3.2 
4.2 
5.5 

Heating 
kW 
3.2 
4.6 
5.2 

input 

Unit Dimensions 

mm 
900×340×1345 
940×320×1430 

(WxDxH) 

inch 
35 3/8×13 3/8×53 
37×12 9/16×56 1/4 

mm 
998×458×1500 
1038×438×1580 

Dimensions (WxDxH) 

inch 
39 1/4×18×59 
40 5/8×17 1/4×62 1/4 

Compressor 
QXFS-F428zX450E 
LNB53FCFMC 

Water-proof level 
IPX4 
IPX4 
IPX4 

Suitable climite 
T1 
T1 
T1 

mm 
Φ15.9 
Φ15.9 
Φ19.05 

Gas 

Connection 

inch 
Φ5/8 
Φ5/8 
Φ3/4 

pipe 

Liquid 
mm 
Φ9.52 
Φ9.52 
Φ9.52 

4 

Sayfa 8

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Model 
GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 
GMV-60WL/C-T(U) 

inch 
Φ3/8 
Φ3/8 
Φ3/8 

Connection Method 
Bell mouth connection 
Bell mouth connection 
Bell mouth connection 

Net weight 
Kg 
111.5 
111.5 
124 
oz 
3933 
3933 
4375 

Note: 

① Units conform to design standard: ARI 210/240. 

② Specifications may be changed due to product improvement. Please refer to nameplates of the units. 

③ Noise data are collected from a semi-anechoic room. Decibels may be slightly higher in actual 

operation due to environmental change. 

④ Refrigerant charge volume listed in the table is based on the condition where indoor and outdoor 

units are at a same level and with no connection pipe. Supplementary refrigerant needs to be 

charged according to actual circumstance. 
3.2 Operation range 

Cooling 
Outdoor temperature: -5~48℃ (23~118℉) 

Heating 
Outdoor temperature: -20℃~27℃(-4~81℉) 

4 Product Capacity Correction 

4.1 Instruction of Product Capacity Correction 

Nominal cooling capacity and nominal heating capacity are tested under given conditions: 
(1) Rated cooling or heating condition 

(2) No height difference between indoor unit and outdoor unit 

(3) Short connection pipe 

If the three conditions above have changed, the cooling and heating capacity will change 

correspondingly and correction is needed. 
4.2 Capacity Code 

Instruction of capacity code 

GMV-24WL/C-T(U) 、GMV-28WL/C-T(U) 、GMV-36WL/A-T(U) 
、GMV-48WL/A-T(U) 
and 

GMV-60WL/A-T(U)、GMV-36WL/C-T(U) 、GMV-48WL/C-T(U) and GMV-60WL/C-T(U) are identical in 

components, systems and structure, etc. While the required capacity is set through the capacity DIP 

switch. 

Sheet of DIP Switch (5-bit DIP switch) 

Model 
Bit 1 
Bit 2 
Bit 3 
Bit 4 
Bit 5 

GMV-24WL/C-T(U) 
1 
0 
0 
0 
0 

GMV-28WL/C-T(U) 
0 
0 
0 
1 
0 

GMV-36WL/A-T(U) 
0 
0 
1 
0 
0 

GMV-48WL/A-T(U) 
0 
0 
1 
0 
1 

GMV-60WL/A-T(U) 
0 
1 
0 
0 
0 

GMV-36WL/C-T(U) 
0 
0 
1 
0 
0 

GMV-48WL/C-T(U) 
0 
0 
1 
0 
1 

GMV-60WL/C-T(U) 
0 
1 
0 
0 
0 

5 

Sayfa 9

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.3 Capacity Correction Formula 

4.3.1 Rated capacity of outdoor unit 

Model 
GMV-24WL/ 

GMV-28WL/ 

GMV-36WL/A-T(U) 
GMV-36WL/C-T(U) 

GMV-48WL/A-T(U) 
GMV-48WL/C-T(U) 

GMV-60WL/A-T(U) 
GMV-60WL/C-T(U) 

C-T(U) 

C-T(U) 

kW 
7 
8.2 
11 
14.1 
17.6 

Rated cooling 

capacity 

Btu/h 
24000 
28000 
37500 
48000 
60000 

kW 
8.2 
8.8 
12.3 
15.8 
18.7 

Rated heating 

capacity 

Btu/h 
28000 
30000 
42000 
54000 
64000 

4.3.2 Correction factor of indoor and outdoor temperature  

(1) Correction factor of cooling capacity 

(2) Correction factor of heating capacity 

4.3.3 Correction factor of pipe length and height difference 

Symbol description: 

Hp:Height difference in case indoor unit is below outdoor unit(m/feet); 

Hm: Height difference in case indoor unit is above outdoor unit (m/feet); 

L: Length of one-way equivalent pipe 

Below table shows the capacity variance ratio for 100% full load in standard working condition 

6 

Sayfa 10

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(thermostat setting is 16℃(61℉) for cooling and 30℃(86℉) for heating). 

Variance ratio of heating capacity 
NOTE: 

m 
0 
10 
20 
30 
40 
50 
60 
70 
80 
90 
100 
110 
120 
130 
140 
150 

ft 
0 
33 
66 
98 
131 
164 
197 
230 
262 
295 
328 
361 
394 
427 
459 
492 

5 Principal of Operation 

Components in flowcharts are presented according to the following table: 

Name 
Compressor 
4-way valve 
Cut-off valve 
One-way valve 
Capillary tube 

Symbol 

Name 
Gas-liquid 

Pressure 

Pressure 

Axial-flow finned heat 

exchanger 
Electronic expansion valve 

separator 

switch 

sensor 

Symbol 

7 

Sayfa 11

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

In cooling, the low-temperature and low-pressure refrigerant gas from each indoor heat exchanger 

will be merged and inhaled by the compressor and then become high-temperature and high-pressure 

gas, which will later be discharged into outdoor heat exchangers. By exchanging heat with outdoor air, 

refrigerant will turn to liquid and flow to each indoor unit via Y-type branch or manifold. Pressure and 

temperature of the refrigerant will then be lowered by throttle elements before it flows into indoor heat 

exchangers. After exchanging heat with indoor air, refrigerant wil become low-temperature and 

low-pressure gas again and repeat the circulation so as to realize the cooling effect. In heating, 4-way 

valve will be energized to make refrigerant circulate in a reverse direction of cooling. Refrigerant will 

release heat in indoor heat exchangers (electric heating elements will also work under certain 

circumstance and release heat) and absorb heat in outdoor heat exchangers circularly so as to realize 

the heating effect. 

8 

Sayfa 12

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 
 
 
 
 
CONTROL 
 
 
 
 
 
 
 

9 

Sayfa 13

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

CONTROL 

1 Units’ Control 

1.1 Schematic diagram of units’ control 

Interpretation on the schematic diagram 

(1) High pressure switch is used to identify system’s high and low pressure. When pressure is too 

high, the switch will break off and send a signal to main board. Main board will pass this signal 

to controller, where the error will be displayed, and stop unit from working. 

(2) High/low pressure sensor is used to test unit’s high/low pressure and send real-time data to 

controller, which will control each unit’s output according to the control logic. 

(3) Temperature sensors are used to test the tube temperature of the unit and send data to the 

controller, which will control each unit’s output according to the control logic. 

10 

Sayfa 14

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

1.2 Operation Flow Chart 

1.2.1 Operation Flow Chart of Indoor Unit 

(1) Cooling operation 

(2) Heating operation 

(3) Drying operation 

(4) Operation procedure is the same as that of cooling operation 

(5) Fan operation 

(6) The EXV of the indoor unit closes in fan mode, so that there is no refrigerant flow in the 

refrigerant pipe of that indoor unit. But the fan of that indoor unit operates. 

11 

Sayfa 15

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

1.2.2 Operation Flow Chart of Outdoor Unit 

(1) Cooling operation 

(2) Heating operation 

1.3 Unit Control Functions 

1.3.1 Control functions of outdoor unit 

(1) Include the following contents.  

(2) Compressor capacity output.   

(3) Compressor start-up control. 

(4) Outdoor fan control.  

(5) Defrosting control.   

(6) Heating EXV control.   

(7) Subcooling valve control.  

(8) Refrigerant lacking control. 

12 

Sayfa 16

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

1.3.2 Control functions of indoor unit 

(1) Include the following contents 

(2) Cool 

(3) Dry  

(4) Heat 

(5) Fan   

(6) Heating temperature compensation 

(7) Anti-freezing 

(8) Air swing 

(9) Drainage pump 

(10) IDU EXV 

(11) Static pressure level 

2 Wired Controller 

2.1 Control panel 

13 

Sayfa 17

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

14 

Sayfa 18

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Button Graphics 

15 

Sayfa 19

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

2.2 Installation and removal 

2.2.1 Installation dimensions 

mm 
112 
22 
2.7 
3.3 
5 
42.5 
40 
82.5 

inch 
4.41 
0.87 
0.11 
0.13 
0.20 
1.67 
1.57 
3.25 

2.2.2 Installation method 

Above is a simple installation method of wired controller. Please pay attention to the following: 

(1) Before installation, disconnect power of the indoor unit. Do not operate when power is 

connected. 

(2) Pull out the 2-core twisted pair cable from the installation hole on the wall and lead it through 

the hole 
 on the back plate of wired controller. 

(3) Place the wired controller on wall and secure its back plate on wall with screw M4X25. 

(4) Connect the 2-core twisted pair cable to terminal H1 and terminal H2. Tighten up the screws. 

(5) Stick the cable in the slot that is left of the terminals and buckle the wired controller’s panel with 

its back plate. 

16 

Sayfa 20

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

If caliber of the communication cord is too large, which causes difficulty in leading or sticking the cord according to 
above point 2 and point 5, strip some of the sheath of the communication cable to meet the installation requirement. 

2.2.3 Removal method 

Fig.2.1.3 Removal of Wired Controller 

2.2.4 Connection of communication cord 

There are 4 ways to connect wired controller with indoor units’ network: 

Fig. 2.2.4.1 One wired controller                  Fig. 2.2.4.2 Two wired controllers 

control one indoor unit                          controls one indoor unit 

17 

Sayfa 21

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Fig. 2.2.4.3 One wired controller controls multiple indoor units simultaneously. 

Fig. 3.6Two wired controllers control multiple indoor units simultaneously. 

18 

Sayfa 22

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

3 Remote Controller 

(1) Remote controller YAP1F 

Button name and function introduction  

No. 
Button name 
Function 

1 
ON/OFF 
Turn on or turn off the unit 

2 
TURBO 
Set turbo function 

3 
MODE 
Set operation mode 

4 

 
Set up&down swing status 

5 
I FEEL 
Set I FEEL function 

6 
TEMP 
Switch temperature displaying type on the unit’s display 

7 

 
Set health function and air function 

8 
LIGHT 
Set light function 

9 
X-FAN 
Set X-FAN function 

10 
SLEEP 
Set sleep function 

11 
CLOCK 
Set clock of the system 

19 

Sayfa 23

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

No. 
Button name 
Function 

12 
TOFF 
Set timer off function 

13 
TON 
Set timer on function 

14 

 
Set left&right swing status 

15 
FAN 
Set fan speed 

16 
/
 
Set temperature and time 
(2) Remote controller YV1L1 

No. 
Button name 
Function 

1 
ON/OFF 
Turn on or turn off the unit 

2 
FAN 
Set fan speed 

3 
▲/▼ 
Set temperature and time 

4 
MODE 
Set operation mode 

5 
 
Set quiet function 

6 
 
Set health function and air function 

7 
 
Set left&right swing status 

8 
 
Set up&down swing status 

9 
X-FAN 
Set X-FAN function 

10 
TIMER ON 
Set timer on function 

11 
TIMER OFF 
Set timer off function 

12 
SAVE 
Set energy-saving function 

13 
SLEEP 
Set sleep function 

14 
LIGHT 
Set light function 

15 
CLOCK 
Set clock of the system 

16 
I FEEL 
Set I FEEL function 

17 
TEMP 
Switch temperature displaying type on the unit’s display 

20 

Sayfa 24

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4 Monitoring Software 

4.1 Function introduction 

With the rapid development of building complex, more and more central air conditioners in various 

models are used in different places, resulting in inconvenience for the management of air conditioners. 

Integrating with telecommunication technology and computing software, Gree Commissioning Tool Kits 

can realize the comprehensive monitor, control and commissioning on central air conditioners. It is an 

efficient solution for the management of central air conditioners that are separated in different parts of a 

building. Administrator doesn’t need to control every unit on site, but rather controls the units by just 

sitting in front of a computer. This will not only improve the productivity, but also reduce cost on human 

resources, property and management. 

Gree Commissioning Tool Kits can monitor and control the 2nd generation of Gree Multi VRF. User 

can monitor and control units by monitoring the computer. This software is an efficient tool for the 

intelligent air conditioning management as well as installation and after-sales service and commissioning. 

It can debug units and control units’ operation status quickly and conveniently. It will not only improve the 

productivity but also reduce the difficulty and cost of commissioning and maintenance, providing better 

and faster service to customers. 

4.2 Connection of computer and units 

It can be connected with single-system network or multi-system network. In the single-system 

network, indoor units or outdoor units are connectable, while in the multi-system network, only the 

master outdoor unit can be connected. 

Seen from the diagram, Gree commissioing network is made up of 3 parts: 

The 1st part is the monitoring computer, including Gree debugger and Gree USB converter driver 

that are installed in the computer. 

The 2nd part is Gree USB converter, which is to convert the air conditioning communication into 

computing communication. This part is made up of Gree USB data converter and USB data wire. 

The 3rd part is air conditioners, including outdoor units, indoor units and the connection wires. If 

connection wire is not long enough, it’s OK to connect via the patching board of the commissioning tool 

kits. In a single-system network, both indoor units and outdoor units can be connected, while in a 

multi-system network, only the master outdoor unit can be connected. 

21 

Sayfa 25

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.3 Parts introduction 

4.3.1 List of parts 

Name 
Model 
Material no. 
Remark 

Gree USB data converter 
MC40-00/B 
30118027 
Convert the air conditioning communication 

(CD-ROM) 
DG40-33/A(C) 
36400000003 
Include Gree debugger, monitoring 
software, USB driver and USB converter 

Gree Commissioning Tool Kits 

USB wire 
\ 
40020082 
Wire connecting computer’s USB interface 

Communicaiton board 
\ 
30118015 
This board can be used when units are far 

from the computer. 
Board connection wire (1m) 
\ 
4001023229 
4-core wire connecting units and converter 
Board connection wire (5.5m) 
\ 
4001023214 
4-core wire connecting units and converter 
Instruction manual 
\ 
64134100023 
Instruction manual 

4.3.2 Gree USB data converter 

4.3.2.1 Functions introduction 

Gree USB data converter will convert the RS485, HBS and CAN commucation within the air 

conditioners into the communication that is recognizable by computer’s USB interface. 

4.3.2.2 Appearance  

into computing communication 

configuring software. 

and converter 

22 

Sayfa 26

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.3.2.3 Operation instruction 

(1) Power LED: a red light. If the red light is on, it indicates normal power supply. If the red light is 

off, it indicates the power supply of converter is not normal. 

(2) Communication LEDs: yellow lights. When converter is working and the computer is 

transmitting data, the TX data transmitting light will be flickering. When units are uploading data 

to the computer, the RX data receiving light will be flickering. 

(3) When converter is under RS485 data transferring mode, the function LED of RS485 to USB will 

be on. 

(4) When converter is under CAN data transferring mode, the function LED of CAN to USB will be 

on. 

(5) When converter is under HBS data transferring mode, the function LED of HBS to USB will be 

on. 

(6) USB interface: connect USB data wire. 

(7) CAN interface: When converter is under CAN communication mode, connect air conditioner’s 

CAN data interface. CAN interface exhibits no polarity (A and B are equal). 

(8) HBS interface: When HBS converter is under HBS communication mode, connect air 

conditioner’s HBS data interface. HBS interface exhibits no polarity (This interface is not yet 

available for Gree debugger and the monitoring software). 

(9) RS485 interface: When RS485 converter is under RS485 communication mode, connect air 

conditioner’s RS485 data interface. RS485 interface exhibits polarity and terminal A and B are 

different. 

23 

Sayfa 27

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.3.2.4 Installation notice 

(1) Install indoors. To avoid collision, it is suggested to place it in the monitoring room together with 

the computer. 

(2) No need of power supply. Power is supplied through computer’s USB interface. 

4.3.3 Communication board 

Communication board is mainly used for transferring data. It functions similar with a patching board. 

Provided that units are far away from the monitoring computer, communication board can be used for 

connection. 

4.3.4 Communication cord 

4.3.4.1 USB wire 

Connect USB wire with computer’s USB interface at one end and with the USB interface of USB 

data converter at the other end, as indicated below: 

4.3.4.2 Board Connection Wire  

There are 2 board connection wires supplied for the commissioning tool kits. One is 1 meter’s long 

and the other is 5.5 meters’ long. They are only different in length. One end of the wire shall connect with 

air conditioner’s communication interface and the other end shall connect with CAN interface of Gree 

USB converter. As shown below, the wire can be connected to the communication interface of outdoor 

unit or the communication interface of indoor unit: 

4.4 Software introduction 

(1) One-button commissioning 

Personnel responsible for the commissioning of air conditioners can start commissioning by 

pressing one button according to the commissioning logic of software, which will give the commissioning 

USB Wire 

Board Connection Wire 

24 

Sayfa 28

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

order to units. Then commissioning will be started up automatically step by step. During the 

commissioning, the corresponding process will be ticked in green on the software interface. If any 

commissioning process is not normal, it will be displayed in red. 

(2) Comprehensive monitoring 

The software can monitor every part of the air conditioning system, including functions, equipment 

and components operating status. The monitoring results will be displayed in text or curve so that user 

can acquire the operating status of the entire system conveniently and straightforwardly. 

(3) Real-time control 

Air conditioner’s operating time and requirements may be different based on areas and functions. 

User can set units’ parameters on computer according to actual needs, such as the on/off, temperature, 

fan speed, mode, etc. Meanwhile, the software can also set or view the function parameters of outdoor 

units, gateway and other equipment. In this way, the mangement of central air conditioners is realized. 

(4) Replay history 

Software can replay and save the historical monitoring information in the data base. The replay 

speed can be selected and the information will be shown in text or curve. This function has greatly saved 

the time to track problem cause and resolved the difficulty of problem reproduction. 

(5) Applicable to multiple series, models and users 

Gree Commissioning Tool Kits is applicable to air conditioning system that comsists of multiple 

series and models. Later, it will be developed to cover all series of Gree central air conditioners, such as 

multi VRF, centrifugal chiller, screw type chiller, ground source heat pump units, modular units, fan coiled 

units, close control units, etc. It can be used by system and controller designers to develop and monitor 

units, or used for maintenance and commissioning. 

(6) Other functions 

For the convenience of users, the software has added functions like connection guide, printing 

screen, opening database folder, rebuilding database, changing database saving path, etc. 

4.4.1 Software installation 

4.4.1.1 Installation requirements 

(1) Computer Configuration 

Memory 
1 GB at least 
2 GB or above is preferred 
Hard Disc 
10 GB available 

CPU 

Operation System 

(2) CD Playing 

Make sure you have administrator access to the computer and there is a CD-ROM in the computer. 

Put the CD into the CD-ROM. If it’s automically running, then the following display will be shown. Or 

double-click the file “Launcher.exe”. 

Core 2 or higher 

1 GHz at least 
2 GHz or above is preferred 

Windows Server 2003 SP3 or higher 

Windows XP SP3 or higher 

Windows Vista 

Windows 7 

25 

Sayfa 29

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

For the first time to use Gree Commissioning Tool Kits, install these programmes: .Net Framework 

4.0, USB Data Converter, Access Driver (necessary for versions below OFFICE 2007), Gree Debugger. 

4.4.1.2 Installation flowchart 

Button Graphics 

This flowchart describes basically the software installation process. See below for details. 

26 

Sayfa 30

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.4.1.3 Installation process 

(1) Install .Net Framework 4.0 

If your computer has installed .Net Framework 4.0 or versions above, there’s no need to install 

again. Otherwise, click “Install .Net Framework 4.0”. 

Extracting files 

27 

Sayfa 31

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click and select “I have read and accept the license terms”. Then click “Install”. 

Installation is in progress. 

28 

Sayfa 32

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click “Finish” to complete the installation. 

(2) Install Access Driver 

Before operating Gree commissioning software, please first install Access Driver (necessary for 

versions below OFFICE 2007). Click “Install Access Driver”. 

29 

Sayfa 33

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 
Click ”Next”. 

Tick “I accept the terms in the License Agreement” and then click “Next” 

30 

Sayfa 34

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click “Browse” to change the default folder to the expected one, or click “Install” to continue the 

installation.  

Installation is in progress. 

31 

Sayfa 35

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click “Ok” to complete the installation. 

 
(3) Install Gree Debugger 

Before installing Gree debugger, make sure that your computer is installed with .Net Framework 4.0 

or versions above. Then click “Install Gree Debugger”. 

Click “Next”. 

32 

Sayfa 36

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click “Browse” to select installation folder. If no change is needed for the folder, click “Next” to 

continue the installation. 

Click “Next”. 

33 

Sayfa 37

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 
Installation is in progress. 

Click “Close” to complete the installation. 

34 

Sayfa 38

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(4) Install USB Converter Driver 

If USB converter driver is already installed in your computer, this part can be skipped. Otherwise, 

click “Install USB Converter Driver”. 

Then the following installation window will be shown. 

35 

Sayfa 39

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

This window will exit after installation is finished. 

(5) Install Gree USB Data Converter 

If converter baud rate is needed to be set, then converter configuring software must be installed. 

Click “Install Gree USB Data Converter”. 

Then select the setup language. You can choose Chinese ”simplified”, Chinese “traditional” or 

English. Then click “OK”. 

36 

Sayfa 40

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click “Next”. 

Tick “I accept the agreement”. Then click “Next” to continue installation. 

37 

Sayfa 41

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Click “Browse” to select your expected installation folder. Click “Next” to continue. 

Click “Browse” to change folder. Click “Next” to continue. 

38 

Sayfa 42

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

If you want to create s desktop shortcut, tick “Creat a desktop icon”. Then click “Next” to continue. 

Destiniation location, folder and additional task will be shown in the next step. If you need to change 

any of it, please click “Back”. If not, click “Install” to start installation. 

39 

Sayfa 43

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Installaiton is in progress. 

Click “Finish” to complete the installation. 

40 

Sayfa 44

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.4.2 Data monitoring 

Gree Debugger。Start up Gree Debugger. 

On the original interface, user can select language and units system. Click “OK” to confirm the 

defaulted language and units system and start up the software. 

Select language. 

41 

Sayfa 45

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Select system of units. 

If units you want to monitor are already connected, and able to communicate normally, with correct 

COM and protocal, then you may click “Connect” to enter the interface of numbers. Otherwise, connect 

in accordance with the connection diagram shown below. 

42 

Sayfa 46

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

COM selection: the serial port in your computer can be detected automatically. You just need to 

select your desired serial port. 

Protocal selection: This is to select the communication method of your units. Currently, CAN is 

applicable to the units. 

43 

Sayfa 47

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

After the selection, click “Connnect”. If units can communicate normally with computer, then the 

interface of numbers will be shown soon. Otherwise, “Connecting” will be shown. 

There are several display zones on this interface. You can hide devices information and system 

information by clicking devices information icon 
and system icon 
. Display zones of indoor unit 

information and errors can be dragged up and down at the dividing lines. As to the display zone of 

outdoor modules information, it can show information of only one module and hide information of others 

(two modules are defaulted to be shown). Menu bar can be hidden by clicking icon 
. Status bar 

shows the current time and period for data collection. 

44 

Sayfa 48

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

On the display zone of devices information, you may click to select and view units that need 

monitoring. 

45 

Sayfa 49

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.4.3 Project debugging 

Click icon of “Debug” on the menu bar and the interface will be switched to project debugging, 

where auto debugging will be started from up to down and from left to right. Note: Debugging function is 

only applicable to a single-system network. 

Click “Start” to enable the debugging function. Then debugging will be started up automatically. 
 

indicates that debugging is in progress while 
 indicates debugging is completed. 

If “OK” button is displayed, it means user needs to judge whether to continue debugging or not. 

Click icon 
 and relevant information will be shown for your reference. Click “Close” to close the 

pop-up (For No.3 Confirm ODU Basic Module NO. and No.4 Confirm IDU NO., the current number of 

units under debugging will be displayed. See the following marked with circle. For No.8 Compr. Preheat 

46 

Sayfa 50

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Confirmation, the preheat time will be displayed. See the following marked with circle). 

Icon 
 indicates that there is problem found during debugging. Debugging will not be completed 

unless problem is solved (after problem is solved, step without “OK” button will switch to the next step 

automatically, otherwise user needs to click “OK” to continue). Click icon 
 and relevant information 

detected in this step will be displayed for your reference in order to solve problems. Click “Close” to close 

the pop-up. 

During debugging, a click on “Break” can stop debugging. Click “Start” to resume debugging and 

47 

Sayfa 51

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

then debugging will be finished step by step. For No.10 ODU Valves Check Before Startup, there are 

“Back” and “Skip” buttons. If there is error in this step, you can back to step No.9 and click “OK” to restart 

debugging on step No.10. If the error in step No.10 is U6 error (valve error alarm), you can click “Skip”. 

In other cases, “Skip” button is null. 

Step 11, 13 and 14 are reserved steps. And step 13, 14, 15 and 16 are steps in parallel (only one of 

the four will be selected according to actual needs). 

4.4.4 Control units 

Click icon of “Setting” on menu bar and select parameter settings, which include “Gateway Settings”, 

“IDU Settings”, “System Settings”, “Project Number Conflict (In case there is project number conflict in 

indoor units, other functions will be shielded. Then this parameter needs to be set in order to eliminate 

the conflict)” and “System Historical Info”. Click the corresponding set and adjust the parameters. 

48 

Sayfa 52

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Take indoor unit as an example. Click “IDU Settings” and a dialog box will pop up. 

Tick the indoor units that need setting in the IDU selection zone or you may click “Select All” to 

select all of them or “Select Inverted” to select none of them. After selection, the current values of the 

corresponding parameters will be displayed in the zone of settings. Click “Set” and then click 
 in the 

pop-up dialog box to select values. Click “Set” and then the corresponding order will be sent to units. If 

setting is successful, it will be displayed at the current values. 

49 

Sayfa 53

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.4.5 Other functions 

(1) Capture screen 

Click icon of “Capture Screen” to print the interface. If you want to open the interface, click “Open”. 

50 

Sayfa 54

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) Search for database folder 

Click icon of “Open Data Folder” on the menu bar to open database folder.  

51 

Sayfa 55

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(3) Conversion of pressure value 

Click icon of “Others” on the menu bar and then click “Display Settings” to select “High Low 

Pressure Value” and “Refrigerant Type”. Select “Temperature” and the pressure parameter displayed on 

the interface will be temperature. Select “Pressure” and the pressure parameter displayed on the 

pressure interface will be pressure. Refrigerant type will affect the pressure parameter displayed on the 

interface. 

52 

Sayfa 56

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(4) Database saving of multiple systems 

Click icon of “Others” on the menu bar and click “Database Save Settings” to select which system 

that needs to save database. Because there is a large quantity of data in a network that contains multiple 

systems, data of only one system can be saved. 

53 

Sayfa 57

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(5) Change database saving path and rebuild database 

Change of database saving path and rebuilding of database should be set before the software starts 

monitoring (see below interface). Click “Change database saving path” and click “Browse” to change the 

saving path. Click “Rebuild Database” to rebuild the database folder. You can also stop monitoring and 

turn back to the connection interface to change saving path or rebuild database during monitoring. 

54 

Sayfa 58

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.4.6 Usage of USB Converter 

(1) Usage of converter 

Gree commissioning software should be connected with CAN interface when converter is used. For 

air conditioners with a single system, connect D1 and D2 interfaces of the wiring board. For air 

conditioners with multiple systems, connect G1 and G2 interfaces of the wiring board. 

Gree monitoring software should be connected with RS485 interface when converter is used. 

Connect outdoor or indoor units or the mainboard of wired controller according to actual needs. 

HBS, CAN and RS485 of the converter can be switched by buttons. Press the button “SET” on the 

converter to realize the conversion among HBS, CAN and RS485 interfaces. You can check the setting 

through the function LEDs. 

Notice: If it’s the first time your PC uses Gree USB data converter, in order to prevent Gree USB 

data converter from being mistaken by your computer as other devices and make sure your mouse can 

work well, it is necessary to turn off the Serail Enumerator of computer after Gree USB data converter is 

connected. Below are the steps: 

Step 1: Right-click ”My Computer” on the desktop and click ”Manage”. 

55 

Sayfa 59

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Step 2: In the pop-up window, select “Device Manager” in the left column and then find “Port (COM 

and LPT)” in the right column. Click its 
. 

56 

Sayfa 60

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Step 3: Right-click ”USB Serial Port (COM6) and then click ”Properties”. The dialog box of properties 

will then pop up. 

Step 4: Then click ”Port Settings” in the dialog box 

57 

Sayfa 61

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Step 5: Click ”Advanced” and then a new dialog box will pop up. Find the ”Serial Enumerator” in the 

miscellaneous options and cancel the tick. Click ”OK” to exit. 

58 

Sayfa 62

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) Usage of converter configuring software: 

When the converter is working, hold the button ”SET” for 5 sec. Function LED will be flickering, 

indicating that the converter has enter the baud rate setting mode. Then you can use the converter 

configuring software to set the baud rate of converter. Baud rate supported by the converter (baud rate of 

air conditioner’s communication interface matches with the baud rate of USB interface automatically): 

AC is connected with 
Baud rate of air conditioner interface 
Baud rate of USB interface 

CAN 
20000/50000 self-adaptive 
115200 

HBS 
57600 
38400 

RS485 
9600 
9600 
Baud rate look-up table for RS485 interface (unit: bps) 

RS485 interface 
4800 
9600 
19200 
38400 
57600 
115200 

USB interface 
4800 
9600 
19200 
38400 
57600 
115200 
Baud rate look-up table for HBS interface (unit: bps) 

HBS interface 
9600 
19200 
38400 
57600 

USB interface 
4800 
9600 
19200 
38400 
Baud rate look-up table of CAN interface (unit: bps) 

CAN interface 
20000 
50000 
100000 
125000 

USB interface 
115200 
115200 
256000 
256000 
Double-click the desktop shortcut. 

Select the needed communication serial port and language in the “System Settings”. 

Ex-factory defaulted baud rate: (unit: bps) 

59 

Sayfa 63

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Select the function that is to be set and the corresponding baud rate (refer to the look-up table) in 

the “Converter Setup”.Then click “Set”. 

60 

Sayfa 64

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

If you want to restore ex-factory settings, click “Default” to restore the default settings. 

Click “Get” to get the current setting details of converter. 

61 

Sayfa 65

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Switchover of Software Languages  

62 

Sayfa 66

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 
 
 
 
INSTALLATION 

63 

Sayfa 67

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

INSTALLATION 

1 Engineering Installation Preparation and Notice 

1.1 Installation notice 

Personnel and property safety are highly concerned during the entire installation process. 

Installation implementation must abide by relevant national safety regulations to ensure personnel and 

property safety.   

All personnel involved in the installation must attend safety education courses and pass 

corresponding safety examinations before installation. Only qualified personnel can attend the 

installation. Relevant personnel must be held responsible for any violation of the regulation. 

1.2 Installation key points and importance 

VRF air conditioning systems use refrigerant, instead of other agent, to directly evaporate to carry 

out the system heat. High level of pipe cleanness and dryness is required in the system. Since various 

pipes need to be prepared and laid out onsite, carelessness or maloperation during installation may 

leave impurities, water, or dust inside refrigerant pipes. If the design fails to meet the requirement, 

various problems may occur in the system or even lead to system breakdown. 

Problems that usually occur during installation are as follows: 

No. 
Installation Problem 
Possible Consequence 

1 
Dust or impurities enter into the 
refrigeration system. 

 
Nitrogen is not filled into the refrigerant 
pipe or insufficient Nitrogen is filled 
before welding. 

2 

3 
The vacuum degree in the refrigerant 
pipe is insufficient. 

4 
Water enters into the refrigeration 
system. 

5 
The refrigerant pipe specifications do not 
meet the configuration requirements. 

6 
Refrigerant pipe is blocked. 

7 
Refrigerant pipe exceeds the limit. 
The loss in pipe is considerable and the unit energy efficiency 
decreases, which are harmful for long-term running of the system. 

8 
Incorrect amount of refrigerant is filled. 

Pipes are more likely to be blocked; air conditioning performance is 
reduced; compressor wear is increased or even hinder the normal 
operation of the system and burn the compressor. 

Pipes are more likely to be blocked; air conditioning performance is 
reduced; compressor wear is increased or even hinder the normal 
operation of the system and burn the compressor. 

The refrigeration performance is reduced. The system fails to keep 
normal operation due to frequent protection measures. When the 
problem getting serious, compressor and other major components can 
be damaged. 

Copper plating may appear on the compressor and reduce the 
compressor efficiency with abnormal noise generated; failures may 
occur in the system due to ice plug. 

Smaller configuration specifications can increase the system pipe 
resistance and affect the cooling performance; larger configuration 
specifications are waste of materials and can also reduce the cooling 
performance. 
 

The cooling performance is reduced; in certain cases, it may cause 
long-term compressor operating under overheat conditions; the 
lubricating effect can be affected and the compressor may be burnt if 
impurities were mixed with the lubricating oil. 
 

The system cannot correctly control the flow allocation; the 
compressor may be operating under over-heating environment or 
running when the refrigerant flows back to the compressor. 

64 

Sayfa 68

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

No. 
Installation Problem 
Possible Consequence 

9 
The refrigerant pipe leaks. 

10 
Water drainage from the condensate 
water pipe is not smooth. 

11 
The ratio of slop for condensate water 
pipe is insufficient or the condensate 
water pipe is incorrectly connected. 

12 
The air channel is improperly fixed. 
The air channel will deform; vibration and noise occur during unit 
operating. 

13 
The guide vane of air channel is not 
reasonably manufactured. 

14 
The refrigerant pipe or condensate water 
pipe does not meet the insulation 
requirement. 

15 
The installation space for IDU is 
insufficient. 

16 
The IDU or the location of the air outlet or 
return air inlet is not designed reasonably. 

17 
The ODU is improperly installed. 

18 
Power cables are incorrectly provided. 
Unit components may be damaged and potential safety hazard may 
occur. 

19 
Control communication cables are 
incorrectly provided or improperly 
connected. 

20 
Control communication cables are not 
properly protected. 

The communication cables are short-circuited or disconnected, and 
the unit cannot be started up due to communication failure. 
Understand the special requirement (if any) for unit installation before implementation to ensure 

installation quality. Relevant installers must have corresponding engineering construction qualifications.   

Special type operators involved in the engineering implementation, such as welders, electricians, 

and refrigeration mechanics must have relevant operating licenses and are accredited with vocational 

qualification certification.   

2 Installation Materials Selection 

The materials, equipment and instruments used during air conditioning engineering construction 

must have certifications and test reports.  Products with fireproof requirements must be provided with 

fireproof inspection certificates and must meet national and relevant compulsory standards.  If 

environmentally-friendly materials are to be used as required by customers, all such materials must meet 

national environmental protection requirement and be provided with relevant certificates.   

2.1 Refrigerant piping 

(1) Material requirement: Dephosphorization drawing copper pipe for air conditioners; 

(2) Appearance requirement: The inner and outer surface of pipe should be smooth without pinhole, 

crack, peeling, blister, inclusion, copper powder, carbon deposition, rust, dirt or severe oxide 

film, and without obvious scratch, pit, spot and other defects. 

Insufficient refrigerant circulating in the system decreases the cooling 
performance of the air conditioner. Long-term operation under such 
circumstance may cause an overheating compressor or even damage 
the compressor. 

Residual water in IDUs can affect the normal operation of the system. 
The possible water leakage can damage the IDU's decoration. 

Reverse slop or inconsistent connection of condensate water pipe can 
hinder the smooth drainage and cause leakage of the IDU. 

Uneven air quantity allocation reduces the overall performance of the 
air conditioner. 

Water can easily condensate and drip to damage the indoor 
decoration, or even trigger the protection mode of system due to 
overheating operation. 

Since there is a lack of space for maintenance and checking, indoor 
decoration might need to be damaged during such operation. 

The air outlet or return air inlet may be short-circuited, thus affecting 
the air conditioning performance. 

The ODU is difficult to be maintained; unit exhaust is not smooth, 
which reduces the heat exchanging performance or even prevent the 
system from normal operation; in addition, the cold and hot air for heat 
exchange and the noise may annoy people in surrounding areas. 

The normal communication in the system fails or the control over IDUs 
and ODUs turn in a mess. 

65 

Sayfa 69

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(3) Test report: Certifications and quality test reports must be provided. 

(4) The tensile strength must be at least 240 kgf/mm². 

(5) Specifications requirement 

OD (mm/inch) 
Wall Thickness (mm/inch) 
Model 

Φ6.35(1/4) 
≥0.8(1/32) 
0 

Φ9.52(3/8) 
≥0.8(1/32) 
0 

Φ12.70(1/2) 
≥0.8(1/32) 
0 

Φ15.9(5/8) 
≥1.0(1/25) 
0 

Φ19.05(3/4) 
≥1.0(1/25) 
0 
(6) After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed 

tightly by using pipe caps, plugs or adhesive tapes. .  

2.2 Condensate water pipe 

(1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R 

pipe, PP-C pipe, and HDG steel pipe; 

(2) All relevant certificates and quality test reports are provided. 

(3) Requirements for specifications and wall thickness 

(4) Water supplying UPVC pipe: Φ32mm×2mm,Φ40mm×2mm,Φ50mm×2.5mm;  

(5) HDG steel pipe: Φ25mm×3.25mm,Φ32mm×3.25mm,Φ40mm×3.5mm,Φ50mm×3.5mm. 

2.3 Insulation material 

(1) Rubber foam insulation material; 

(2) Flame retardancy level: B1 or higher; 

(3) Refractoriness: at least 120℃(248℉); 

(4) The insulation thickness of condensate water pipe: at least 10 mm; 

(5) When the diameter of copper pipe is equal to or greater than Φ15.9 mm, the thickness of 

insulation material should be at least 20 mm; when the diameter of copper pipe is less than 

15.9 mm, the thickness of insulation material should be at least 15 mm. 

2.4 Communication cable and control cable 

Note: For air conditioning units installed in places with strong electromagnetic interference, shielded 

wire must be used as the communication cables of the IDU and wired controller, and shielded twisted 

pairs must be used as the communication cables between IDUs and between the IDU and ODU. 

Communication cable selection for ODU and IDUs 

R410A Refrigerant System 

66 

Sayfa 70

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Total Length of 
Communication Cable 
between IDU Unit and IDU 

Material Type 

(ODU ) Unit L(m/feet) 

Light/Ordinary polyvinyl 
chloride sheathed cord. 
L≤1000(3280-5/6) 
≥2×AWG18 

2.5 Power cable 

Only copper conductors can be used as power cables. The copper conductors must meet relevant 

national standard and satisfy the carrying capacity of unit. 

2.6 Hanger rod and support 

(1) Hanger rod: M8 or M10; 

(2) U-steel: 14# or above; 

(3) Angle steel: 30mm×30mm×3mm or above; 

(4) Round steel: Φ10mm or above 

3 Installation of outdoor unit 

3.1 Check before installation 

(1) Before installation, please check the power cord if it complies with the power supply 

requirement on the nameplate. Make sure the power supply is safe. 

(2) This air conditioner must be properly grounded through the receptacle to avoid electric shock. 

The ground wire shouldn’t be connected with gas pipe, water pipe, lightning arrester or 

telephone line. 

(3) Maintain good air circulation to avoid lacking oxygen. 

(4) Read this manual carefully before installation. 

3.2 Selection of installation site 

(1) Select a location which is strong enough to hold unit’s weight so that unit can stand still and 

erect. 

(2) Make sure the unit is not exposed to sun and rain. And the location can resist dust, typhoon and 

earthquake. 

(3) Please keep the unit away from inflammable, explosive and corrosive gas or waste gas. 

(4) Make sure the location has space for heat exchange and maintenance so that unit can operate 

reliably with good ventilation. 

(5) ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and 

reduce bend angles. 

(6) Select a location which is out of children’s reach. Keep the unit away from children. 

Wire size  
Remarks 

1) If the wire diameter is enlarged to 
2×AWG16, the total communication line 
length can reach 1500 m (4921-1/4feet).  
2) The cord shall be Circular cord (the cores 
shall be twisted together). 
3) If unit is installed in places with intense 
magnetic field or strong interference, it is 
necessary to use shielded wire. 

67 

Sayfa 71

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

3.3 Carrying and installing outdoor unit 

When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes. In order to 

avoid excursion from the center, the angel of ropes must be smaller than 40º during hanging and 

moving. 

3.4 Installation notices 

In order to ensure proper operation, the selection of installation site must conform to the following 

principle: 

(1) The discharged air of outdoor unit will not flow back and there is sufficient space around the unit 

for maintenance; 

(2) The installation site must be well ventilated to ensure sufficient air intake and discharge. Make 

sure there is no obstacle at the air inlet and air outlet. If there is any obstacle, please remove it; 

(3) The installation site shall be able to withstand the weight of outdoor unit and capable for 

soundproof and vibration. The air outlet and noise of unit will not affect neighbors; 

(4) The hanging of outdoor unit must use appointed hanging hole. Pay attention to protect the unit 

during hanging and installation. Prohibit hitting the sheet metal to avoid rust in the future.  

(5) Avoid direct sunlight; 

(6) The rain and condensation water can be drained out smoothly; 

(7) The outdoor unit will not be embedded by the snow and not affected by garbage and oil smog; 

(8) The installation of outdoor unit shall adopt rubber damping pad or spring damper to reduce 

noise and vibration; 

(9) The installation dimension shall accord with the installation requirement of this manual and the 

outdoor unit must be fixed at the installation site; 

(10) The installation shall be done by professional technicians. 

3.5 Fixing and damping of unit 

The outdoor unit shall be fixed with 4 M12 bolts and closely contacted with the foundation. 

Otherwise, big vibration and noise will be caused. 

The outdoor unit shall be fixed firmly. The rubber board with thickness over 20mm or corrugated 

rubber damping pad shall be applied between the unit and foundation. 

3.6 Outline dimension and position of installation hole 

When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes. In order to 

avoid excursion from the center, the angel of ropes must be smaller than 40º during hanging and 

moving. 

68 

Sayfa 72

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Model 
A 
B 
C 
D 
E 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

Fig.1 

Unit:mm(inch) 

980 
(38 6/19) 

360 
(14 3/16) 

790 
(31 2/16) 

650 
(25 3/5) 

395 
(15 5/9) 

Fig.2 

69 

Sayfa 73

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Unit:mm(inch) 

Model 
A 
B 
C 
D 
E 

GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 

900 
(35 7/16) 

340 
(13 3/8) 

1345 
(53) 

572 
(22 1/2) 

378 
(15) 

 GMV-60WL/A-T(U) 
940 
(37) 

320 
(12 9/16) 

1430 
(56 1/4) 

632 
(24 7/8) 

350 
(14 7/8) 

GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 

900 
(35 3/8) 

340  
(13 3/8)  

1345  
(53)  

572  
(22 1/2)  

378  
(15)  

GMV-60WL/C-T(U) 
940  
(37)  

320  
(12 9/16)  

1430  
(56 1/4)  

632  
(24 7/8)  

350  
(14 7/8)  

3.7 Installation space requirement 

If all sides of the ODU (including the top) are surrounded by walls, process according to the 

following requirements for installation space: 

Fig.3                                      Fig.4     

4 Installation of Electronic Expansion Valve Assy (unit with 
external EXV) 

The EXV of indoor unit is built-in. 

5 Installation of Refrigerant Pipeline 

5.1Allowable Length and Height Difference of Connection Pipe 

Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown in 

the figure below: 

NOTICE! Equivalent length of one Y-type branch is 0.5m(1-5/8feet). 

70 

Sayfa 74

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Fig.5 

Allowable Length and Height Difference of Connection Pipe 

Piping parameters of GMV-24WL/C-T(U)、GMV-28WL/C-T(U): 

- 
Allowable 
value(m/feet) 
Fitting pipe 

Total length (actual length) of fitting pipe 
250(820) 
L1+L2+L3+a+b+c+d 

Length of farthest fitting pipe (m) 
Actual length 
100(328) 
L1+L2+L3+d 
Equivalent length 
120(394) 
From the 1st branch to the farthest indoor pipe 
40(131) 
L2+L3+d 

ODU at upper side 
30(98) 
- 

Height difference between ODU and 

IDU 

ODU at lower side 
30(98) 
- 
Height difference between IDUs 
10(33) 
- 
GMV-36WL/A-T(U) 、GMV-48WL/A-T(U)、GMV-60WL/A-T(U) 

GMV-36WL/C-T(U) 、GMV-48WL/C-T(U)、GMV-60WLC-T(U): 

- 
Allowable 
value(m/feet) 
Fitting pipe 

Total length (actual length) of fitting pipe 
300(984) 
L1+L2+L3+a+b+c+d 

Length of farthest fitting pipe (m) 
Actual length 
120(394) 
L1+L2+L3+d 
Equivalent length 
150(492) 
From the 1st branch to the farthest indoor pipe 
40(131) 
L2+L3+d 

Height difference between ODU and 

ODU at upper side 
50(164) 
- 

IDU 

ODU at lower side 
40(131) 
- 
Height difference between IDUs 
15(49) 
- 
 

71 

Sayfa 75

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

5.2 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor 
Branch 

Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of 

outdoor connection pipe. 

Dimension of outdoor connection pipe: 

Basic module 

GMV-24WL/C-T(U) 
Φ15.9 
(Φ5/8) 

GMV-28WL/C-T(U) 
Φ15.9 
(Φ5/8) 

Φ9.52 
(Φ3/8) 
GMV-36WL/A-T(U) 
GMV-36WL/C-T(U) 

Φ9.52 
(Φ3/8) 
GMV-48WL/A-T(U) 
GMV-48WL/C-T(U) 

GMV-60WL/A-T(U) 
GMV-60WL/C-T(U) 

Fig.6 

Pipe dimension 

Gas pipe  
(mm/inch) 

Liquid pipe 

(mm/inch) 

Φ9.52 
(Φ3/8) 

Φ15.9 
(Φ5/8) 

Φ15.9 
(Φ5/8) 

Φ9.52 
(Φ3/8) 

Φ19.05 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

72 

Sayfa 76

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

5.3 Selection of Indoor Branches 

Select indoor branches according to the total capacity of downstream indoor units. if the capacity 

exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

Refrigerant system 
Total capacity of downstream indoor units C (Btu/h) 
Model 

Y type branch 

5.4 Dimension of Pipe between Indoor Branches 

Select pipe between indoor branches according to the capacity of downstream indoor units; if the 

capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

Fig.7 

C< 68200 
FQ01A/A 

68200≤C≤102400 
FQ01B/A 

102400<C ≤238800 
FQ02/A 

238800<C ≤460600 
FQ03/A 

460600<C 
FQ04/A 

Fig.8 

73 

Sayfa 77

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Total capacity of downstream indoor units  

C (Btu/h) 

C ≤19000 
Φ12.7 
(Φ1/2) 

19000<C≤48500 
Φ15.9 
(Φ5/8) 

48500<C≤76400 
Φ19.05 

5.5 Dimension of Pipe between Indoor Branch and IDU 

Dimension of pipe between indoor branch and IDU should be consistent with the dimension of 

indoor pipe. 

Rated capacity of IDU 

C(Btu/h) 

C≤9600 
Φ9.52 
(Φ3/8) 

9600<C≤17000 
Φ12.7 
(Φ1/2) 

17000<C≤48000 
Φ15.9 
(Φ5/8) 

48000<C≤55000 
Φ19.05 

Φ9.52 
(Φ3/8) 
NOTICE! If the distance between IDU and its nearest branch is over 10m(33feet), then the liquid 

55000<C≤96000 
Φ22.2 
(Φ7/8) 

pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged. 

Pipe 
(mm/inch) 

Liquid pipe 

(mm/inch) 

Φ6.35 
(Φ1/4) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

Fig. 9 

Gas pipe 
(mm/inch) 

Liquid pipe 
 (mm/inch) 

Φ6.35 
(Φ1/4) 

Φ6.35 
(Φ1/4) 

Φ9.52 
(Φ3/8) 

Φ9.52 
(Φ3/8) 

(Φ3/4) 

74 

Sayfa 78

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

6 Installation of Connection Pipe 

(1) 
Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so is 
the height difference between indoor and outdoor units. Keep the number of bends as little as possible. Radius of 
curvature should be as large as possible. 

(2) 
Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for welding 
process. Rosin joint or pin hole is not allowed. 
(3) 
When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm(8inch). Note that 
pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch the 
pipe for more than 3 times at the same position. 
6.1Flaring Process 

(1) Use pipe cutter to cut the connection pipe in case it is unshaped. 

(2) Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after 

cutting. 

(3) Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use flaring 

tool to fix the flared nut into the pipe (as shown in Fig.10). 

(4) Check if the flared part is flaring evenly and if there is any crack. 

6.1.1 Pipe Bending 

(1) Reshape the pipe by hand. Be careful not to damage the pipe. 

(2) Do not bend the pipe over 90°. 

(3) (If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch again. 

Therefore, do not bend or stretch the bend for over 3 times. 

(4) In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the 

insulating layer, as shown in Fig. 12. Do not bend the pipe until it is exposed. When bending is 

done, wrap the pipe with insulating layer and then secure it with adhesive tape. 

                    Fig. 11                                 Fig. 12 

Fig. 10 

75 

Sayfa 79

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

6.1.2 Indoor Pipe Connection 

(1) Remove pipe cover and pipe plug. 

(2) Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut tightly 

by hand, as in Fig. 13. (Make sure indoor pipe is correctly connected. Improper location of the 

center will prevent flared nut from being securely twisted. Thread of nut will get damaged if the 

flared nut is twisted forcibly.) 

(3) Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound. 

(Hold the handle of wrench and make it at right angle to the pipe. as in Fig. 14 

(1) 
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly with plastic tape. 

(2) 
Connection pipe should be supported by a bearer rather than the unit. 

(3) 
The bending angle of piping should not be too small; otherwise the piping might have cracks. Please use a pipe 
bender to bend the pipe. 

(4) 
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with force in case the 
capillary tube or other tubes have cracks and cause leakage. 

 Fig. 13                     Fig. 14 

Pipe Diameter 
Tightening Torque 

6mm(1/4inch) 
15-30N·m(11-22ft.-1b.) 

9.5mm(3/8 inch) 
35-40N·m(26-29ft.-1b.) 

12.7mm(1/2 inch) 
45-50N·m(33-37ft.-1b.) 

16mm(5/8 inch) 
60-65N·m(44-48ft.-1b.) 

19.05mm(3/4 inch) 
70-75N·m(52-55ft.-1b.) 

6.1.3 Outdoor Pipe Connection 

(1) Pipe connection for GMV-36WL/A-T(U) 、GMV-48WL/A-T(U) 、GMV-36WL/C-T(U) 、

GMV-48WL/C-T(U) 

Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as for 

indoor pipe connection. 

 According to customer requirement or space limit, outlet pipe can be installed from the front, right 

or rear side. 

76 

Sayfa 80

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) Pipe connection for GMV-60WL/C-T(U)、GMV-60WL/C-T(U) 

As shown in Fig.16 and Fig.17, open the outermost soundproof cotton and place a fire barrier 

between compressor and straight pipe. Use a soldering gun to unsolder straight pipe 1 and straight pipe 

2. Install connection pipe 1 and connection pipe 2 to the corresponding position and then seal the 

apertures with welding rod. First weld the liquid side connection pipe and then weld the gas side 

connection pipe. During welding, it’s necessary to use wet gauze to wrap up the two cut-off valves. Make 

sure the flame won’t burn the soundproof cotton or other components. 

Gas pipe

Liquid pipe

Flared nut

Fig. 15 

  Fig. 16 

77 

Sayfa 81

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(3) Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as 

for indoor pipe connection.  

During engineering installation, the connection pipe inside the unit must be wrapped by insulation 

sleeve. 

Below is the piping diagram of GMV-24WL/C-T(U)、GMV-28WL/C-T(U). According to customer 

requirement or space limit, outlet pipe can be installed from the front, right or rear side. 

6.1.4 Installation of Y-type Branch 

(1) Y-type Branch 

Fig. 17 

 Fig. 18 

78 

Sayfa 82

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) Y-type branch has several pipe sections with different dimension, which facilitates to match with 

various copper pipes. Use pipe cutter to cut in the middle of the pipe section that is of proper 

dimension and remove burrs as well. See Fig. 20. 

(3) Y-type branch must be installed vertically or horizontally. 

 
Branch shall be isolated by insulating material that can bear 120℃(248℉)or even higher temperature. The attached 
foam of branch cannot be taken as insulating material. 

6.1.5 Thermal Insulation for Pipeline 

(1) For multi VRF system, every copper pipe should be labeled so as to avoid misconnection. 

(2) At the branch inlet, leave at least 500mm(19-3/4inch) straight pipe section. 

(3) Thermal insulation for pipeline 

1) To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid pipe 

must be wrapped with thermal insulating material and adhesive tape for insulation from the 

air. 

2) Joints of indoor and outdoor unit should be wrapped with insulating material and leave no 

gap between pipe and wall. See Fig. 21. 

3) When wrapping the tape, the later circle should cover half of the former one. Don’t wrap the 

rape too tight, otherwise the insulation effect will be weakened. 

4) After wrapping the pipe, apply sealing material to completely seal the hole on the wall. 

Fig. 19 

Fig. 20 

Fig. 21 

79 

Sayfa 83

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(1) 
Thermal insulating material shall be able bear the pipe temperature. For heat pump unit, liquid pipe should bear 
70℃(158℉) or above and gas pipe should bear 120℃(248℉) or above. For cooling only unit, both liquid pipe and 
gas pipe should bear 70℃(158℉) or above. 

(2) 
Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of 
branches cannot be taken as insulating material. 

6.1.6 Support and Protection of Pipeline 

 
(1) 
Support should be made for hanging connection pipe. Distance between each support cannot be over 
1m(3-1/4feet). 
(2) 
Protection against accidental damage should be made for outdoor pipeline. When pipeline exceeds 
1m(3-1/4feet), a pinch board should be added for protection. 

6.2 Disassembly of Compressor Feet 

In order to prevent unit from damage during transportation, 2 metal pieces are fitted to outdoor unit’s 

compressor feet before unit leaves factory. See fig.22. 

When installing the unit, metal pieces for transportation must be removed (except for 

GMV-60WL/A-T(U)). Then fasten the binding nuts again and wrap back soundproofing cotton.If unit runs 

with metal pieces fitting on, compressor will shake abnormally and unit’s operating life will be shortened. 

6.3 Vacuum Pumping, Refrigerant Adding 

Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra refrigerant in 
the outdoor unit for air purging!  

6.3.1 Vacuum Pumping 

(1) Outdoor unit has been charged with refrigerant before delivery. Field-installed connection pipe 

needs to be charged with additional refrigerant. 

(2) Confirm whether outdoor liquid and gas valves are closed. 

(3) Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the outdoor 

valve, as shown below. 

Fig. 22 

80 

Sayfa 84

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Fig. 23 

6.3.2 Refrigerant Adding 

(1) Refrigerant quantity of outdoor unit before delivery: 

Model 
GMV-24WL/C-T

GMV-28WL/C-T

GMV-36WL/A-T

GMV-48WL/A-T

GMV-60WL/A-T

(U) 

(U) 

(U) 

(U) 

(U) 

Refrigerant Qty 

2.4 
(84.7) 

2.4 
(84.7) 

5.0 
(176) 

5.0 
(176) 

6.5 
(229) 

(kg/oz) 

Model 
GMV-36WL/C-T

GMV-48WL/C-T

GMV-60WL/C-T

(U) 
- 
- 

(U) 

(U) 

Refrigerant Qty 

3.3 
(116) 

3.3 
(116) 

4.6 
(162) 
- 
- 

(kg/oz) 

 
(1) 
The refrigerant amount charged before delivery doesn’t include the amount that needs to be added to indoor units 
and the connection pipeline. 

(2) 
Length of connection pipe is decided on site. Therefore the amount of additional refrigerant shall be decided on 
site according to the dimension and length of field-installed liquid pipe. 

(3) 
Record the amount of additional refrigerant for convenience of after-sales service. 
(2) Calculation of the amount of additional refrigerant 

Calculation method of the quantity of additional refrigerant (based on liquid pipe) 

Quantity of additional refrigerant = ∑length of liquid pipe X quantity of additional refrigerant per 

meter(39-3/8inch) 

Diameter of 

Φ22.2 
(Φ7/8) 

Φ19.05 

Φ15.9 
(Φ5/8) 

Φ12.7 
(Φ1/2) 

Φ9.52 
(Φ3/8) 

Φ6.35 
(Φ1/4) 

liquid pipe 
(mm/inch) 

(Φ3/4) 

kg/m 
0.35 
0.25 
0.17 
0.11 
0.054 
0.022 

oz/inch 
0.314 
0.224 
0.152 
0.099 
0.048 
0.020 
NOTICE! Liquid pipe that is within 20m(65-5/8feet) doesn’t need to be added with refrigerant. 

First confirm that there is no leakage from the system. When compressor is not working, charge 

additional R410a with specific amount to the unit through the filling opening of the liquid pipe valve of the 

outdoor unit. If required amount cannot be quickly filled due to pressure increase of the pipe, then set the 

unit in cooling startup and fill refrigerant from the low pressure check valve of the outdoor unit.  

81 

Sayfa 85

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(3) Calculation example 

Fig. 24 

IDU: 

No. 
IDU ① 
IDU ② 
IDU ③ 
IDU ④ 

Duct type 
GMV-ND18PLS/A-T 

Duct type 
GMV-ND12PLS/A-T 

Duct type 
GMV-ND09PLS/A-T 

Duct type 
GMV-ND09PLS/A-T 

Model 

(U) 
Liquid pipe: 

(U) 

(U) 

(U) 

No. 
A 
B 
C 
D 

Pipe size 
Φ9.52mm 
(Φ3/8inch) 

Φ9.52mm 
(Φ3/8inch) 

Φ9.52mm 
(Φ3/8inch) 

Φ6.35mm 
(Φ1/4inch) 

Length 
10m 
(32-3/4feet) 

5m 
(16-3/8feet) 

5m 
(16-3/8feet) 

5m 
(16-3/8feet) 

No. 
a 
b 
c 
d 

Pipe size 
Φ9.52mm 
(Φ3/8inch) 

Φ6.35mm 
(Φ1/4inch) 

Φ6.35mm 
(Φ1/4inch) 

Φ6.35mm 
(Φ1/4inch) 

1m 
(3-1/4feet) 
Total length of each liquid pipe 

Length 
3m 
(9-3/4feet) 

3m 
(9-3/4feet) 

2m 
(6-5/8feet) 

Φ9.52:A+B+C+a=10+5+5+3=23m(75-1/2 feet) 

Φ6.35: D+b+c+d=5+3+2+1=11m(36feet) 

NOTICE! Liquid pipe that is within 20m(65-5/8feet) doesn’t need to be added with refrigerant. 

Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022 =

0.404kg(14oz) 

GMV-24WL/C-T(U)
、
GMV-28WL/C-T(U)
、
GMV-36WL/C-T(U)
、
GMV-48WL/C-T(U)
、

GMV-60WL/C-T(U): 

Quantity of additional refrigerant = ∑length of liquid pipe X quantity of additional refrigerant per 

meter+(quantity of indoor unit -2)×0.3 

Diameter of 

Φ22.2 
(Φ7/8) 

Φ19.05 

Φ15.9 
(Φ5/8) 

Φ12.7 
(Φ1/2) 

Φ9.52 
(Φ3/8) 

Φ6.35 
(Φ1/4) 

liquid pipe 
(mm/inch) 

(Φ3/4) 

kg/m 
0.35 
0.25 
0.17 
0.11 
0.054 
0.022 
oz/inch 
0.314 
0.224 
0.152 
0.099 
0.048 
0.020 
First confirm that there is no leakage from the system. When compressor is not working, charge 

additional R410A with specific amount to the unit through the filling opening of the liquid pipe valve of the 

82 

Sayfa 86

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

outdoor unit. If required amount cannot be quickly filled due to pressure increase of the pipe, then set the 

unit in cooling startup and fill refrigerant from the low pressure check valve of the outdoor unit.  

(4) Calculation example 

IDU 

No. 
IDU ① 
IDU ② 
IDU ③ 
IDU ④ 

Model 
Duct type 
GMV-ND18PLS/A-T(U) 

Duct type 
GMV-ND09PLS/A-T(U) 
Liquid pipe: 

No. 
A 
B 
C 
D 

Pipe size 
Φ9.52 
Φ9.52 
Φ9.52 
Φ6.35 

Length 
10m 
5m 
5m 
5m 

No. 
a 
b 
c 
d 

Pipe size 
Φ9.52 
Φ6.35 
Φ6.35 
Φ6.35 

Length 
3m 
3m 
2m 
1m 
Total length of each liquid pipe 

Φ9.52:A+B+C+a=10+5+5+3=23m 

Φ6.35: D+b+c+d=5+3+2+1=11m 

Quantity of indoor unit: 4 sets 

Therefore, the minimum quantity of additional refrigerant = (23×0.054+11×0.022)+(4-2)×0.3=

2.084kg(73.5oz) 

Duct type 
GMV-ND12PLS/A-T(U) 

Duct type 
GMV-ND09PLS/A-T(U) 

83 

Sayfa 87

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

7 Electric Wiring 

 
(1) 
All electrical installation must be performed by qualified technicians in accordance with local laws, regulations and 
this user manual. 

(2) 
Use air conditioner specialized power supply and make sure that it is consistent with system’s rated voltage.  

(3) 
Do not pull the power cord with force. 

(4) 
Caliber of the power cord must be large enough. A damaged power cord or connection wire must be replaced by 
specialized electrical cords. 

(5) 
Connect the unit to specialized grounding device and make sure it is securely grounded. It’s a must to install air 
switch and current circuit breaker that can cut off the power of the entire system. The air switch should include 
magnetic trip function and thermal trip function so that system can be protected from short circuit and overload. 

(6) 
Air conditioner belongs to class I electrical appliance, so it must be securely grounded. 

(7) 
The yellow-green wire inside the unit is a ground wire. Do not cut it off or secure it with tapping screws, otherwise 
it will lead to electric shock. 
(8) 
Power supply must include secure grounding terminal. Do not connect the ground wire to the following: 
(9) 
①Water pipe; ②Gas pipe; ③Drain pipe; ④Other places that are deemed as not secure by professional 
technicians. 
7.1 Wiring Diagram 

(1) Connection of power cord and communication wire 

Separate power supply for Indoor and Outdoor 

Fig.25 Connection of power cord and communication wire for IDU and ODU 

84 

Sayfa 88

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) The wiring diagram for power cord of outdoor unit and communication wire. 

There are two wiring diagrams for communication wires of indoor/outdoor units and remote monitor: 

1) Real line method; 

2) Broken line method. Please select it based on the actual installation situation. 
There are two wiring diagrams for power cord: 

1) Real line method; 

2) Broken line method. Please select it based on the actual installation situation. 
7.2 Power Cable Wire Gauge and Circuit Breaker Selection 

Model 
Power supply 

GMV-24WL/C-T(U) 
208/230V~ 
60Hz 
25 
25 
21 

GMV-28WL/C-T(U) 
208/230V~ 
60Hz 
30 
30 
21 

GMV-36WL/A-T(U) 
208/230V~ 
60Hz 
35 
35 
31 

GMV-48WL/A-T(U) 
208/230V~ 
60Hz 
45 
45 
34 

GMV-60WL/A-T(U) 
208/230V~ 
60Hz 
60 
60 
39.8 

GMV-36WL/C-T(U) 
208/230V~ 
60Hz 
35 
35 
28.5 

GMV-48WL/C-T(U) 
208/230V~ 
60Hz 
40 
40 
33 

GMV-60WL/C-T(U) 
208/230V~ 
60Hz 
40 
40 
34.5 

Max Fuse Size/Fusible 

Min. Circuit 

Max Ckt, Bkr Size/Disjoncteur 

Max. 

Ampacity 

Max. (A) 

(A) 

(A) 

85 

Sayfa 89

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

8 Debugging of Unit 

Caution:  

① After the initial installation is finished and the main board of outdoor unit is replaced, it must perform 

debugging. Otherwise, the unit can’t operate. 

② The debugging must be performed by professional person or under the the guide of professional 

person. 
8.1 Preparation for debugging  

(1) Do not disconnect the power before the installation is finished,  

(2) All wires for controller and electric wires must be connected correctly and reliably.  

(3) Check the the fixing ring of the foot of compressor for transportaion is removed.  

(4) Remove all sundries from the unit, such as metal chips, joint, forceps holder, and so on.  

(5) Check whether the appearance and pipeline system are damaged during carry or 

transportation process.  

(6) Calculate the required added refrigerant-charging volume according to the length of pipe of 

system and pre-charge the refrigerant. If refrigerant can’t be added any more when the required 

refrigerant-charging volume hasn’t been reached, record to refrigerant volume which still needs 

to be added and continue to add refrigerant during run test operation process. Please refer to 

below run test for the refrigerant-adding stage during run test process.  

(7) After adding refrigerant, please make sure the valve for outdoor is opened completely.  

(8) For the convenient of troubleshooting, the unit can’t be connected to the PC which installed with 

related debugging software and make sure that the the datas in real time of this unit can be 

inspected by this computer. Please refer to Service Manual for the installation and connection 

of the bebugging software.  

(9) Before turn test, please do make sure that the preheat time for compressor is 8h above and 

touch the compressor to see whether preheat is normal. You can perform run test only after 

normal preheat. Otherwise, it may damage the compressor.   

86 

Sayfa 90

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

8.2 Debugging of unit  

Description of test operation procedures and main board display of ODU 

GMV-24WL/C-T(U) 
、GMV-28WL/C-T(U) 、GMV-36WL/C-T(U) 、GMV-48WL/C-T(U) 、

GMV-60WL/C-T(U): 

Description of each stage of debugging progress 

- 
Debugging code 

Code meaning and operation method 
Progress 
LED 

Code 
Display status 

A0 
ON 
System is not debugged, hold main board’s SW3 button for 5s 
to start debugging. 
01 
ON 
2s later, next step starts. 

01_Set master 
unit 

02/Ad 
Display 
circularly 
System is allocating addresses. 10s later, display as below: 

No master indoor unit. Display will be on for 1min, during which 
master IDU can be set manually. If not, system will set the unit 
with minimum IP address as the master IDU. 

02_ Allocate 
addresses 

02/L7 
Display 
circularly 

02/oC 
Display 
circularly 
Allocation is finished. 2s later, next step starts. 

03_ Confirm the 
quantity of ODU 
03/01 
Display 
circularly 
System is confirming. 1s later, next step starts. 

“00~16” displays the quantity of indoor unit. Confirm the 
number manually. If the number is not consistent the display 
one, cut off power of IDU and ODU and check whether 
communication wire of IDU is correctly connected. After the 
check, connect power and start debugging from progress 01. If 
the number is then correct, press main board’s SW3 button to 
confirm. Then the display is as below: 

04/00~16 
Display 
circularly 

04_ Confirm the 
quantity of IDU 

04/oC 
Display 
circularly 
System has confirmed the quantity. 2s later, next step starts. 

“00~16” displays the quantity of indoor unit identified by the 
system. “CL” means the amount of indoor unit is very little 
(amount of indoor unit<2), at this moment, all buttons are 
invalid, the system cannot enter into the next judgment. 

00~16/CL 
Display 
circularly 

Communication between master ODU and driver has error. 
Check the communication connection of ODU’s main board 
and drive board. When the error is eliminated, start next step. 
If power is off during troubleshooting, then restart debugging 
from progress 01 after power is on.   

05/C2 
Display 
circularly 

Communication of master ODU and driver is normal. Unit will 
display as in the left for 2s and detect the capacity ratio of IDU 
and ODU. If the ratio is within range, than next step will start 2s 
later. If the ratio is out of range, unit will display as below: 

05_ Detect ODU’s 
internal 
communication 
and capacity ratio 

05/oC 
Display 
circularly 

Rated capacity ratio of IDU is too high. Change the 
combination way of IDU and ODU to make the ratio within 
range. And restart debugging from progress 01. 

05/CH 
Display 
circularly 

Rated capacity ratio of IDU is too low. Change the combination 
way of IDU and ODU to make the ratio within range. And 
restart debugging from progress 01. 

05/CL 
Display 
circularly 

Outdoor component’s error. Besides “06”, the other blinking 
will display the related error code. After errors are eliminated, 
system will start next step automatically. If power is off during 
troubleshooting, then restart debugging from progress 01 after 
power is on. 

06/error code 
Display 
circularly 

06_ Detect 
outdoor 
components 

06/oC 
Display 
circularly 

System detects no error on outdoor component. 10s later, next 
step starts. 

87 

Sayfa 91

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Description of each stage of debugging progress 

- 
Debugging code 

Code meaning and operation method 
Progress 
LED 

Code 
Display status 

System detects error on indoor components. XX means the 
project code of IDU with error, e.g. no.1 IDU has d5 and d6 
errors, meanwhile no.3 IDU displays error d6 and d7, then the 
nixie tube will display “07”, “01”, “d5”, “d6”and “03” circularly. 
After errors are eliminated, system will start next step 
automatically. If power is off during troubleshooting, then 
restart debugging from progress 01 after power is on. 

07/XX/error 
code 

Display 
circularly 

07_ Detect indoor 
components 

If errors occur in IDU which the project code is ≥ 3-digit 
number, then it will display the 2 big digits of project code first, 
then the 2 small digits, finally the error code, e.g: L1 error 
occurs in no.101 IDU, then the nixie tube will display “01”,“01” 
and “L1” circularly. Display method is the same for several 
IDUs with multiple errors. 

07/XXXX/error 
code 

Display 
circularly 

07/oC 
Display 
circularly 
No error on components of IDU. 5s later, next step starts. 

Preheat time for compressor is less than 8 hours. Display will 
be as in the left until the preheat time reaches 8 hours. Press 
main board’s SW3 button to confirm manually that the preheat 
time has reached 8 hours. Then start next step. (Note: 
Compressor may get damaged if it is started without 8 hours of 
preheat time) 

08/U0 
Display 
circularly 

08_ Confirm 
preheated 
compressor 

08/oC 
Display 
circularly 

Compressor has been preheated for 8 hours. 2s later, next 
step starts. 

System is lack of refrigerant and display will be as in the left. 
Please cut off power of IDU and ODU and check if there is 
leakage on pipeline. Solve the leakage problem and 
complement refrigerant into the unit. Then connect power and 
restart debugging from progress 01. (Note: Before re-charging 
refrigerant, unit must be power off in case system starts 
progress 10 automatically.) 

09/U4 
Display 
circularly 

09_ Refrigerant 
judgments before 

startup 

09/oC 
Display 
circularly 

Refrigerant is normal and unit will display as in the left for 
2s.Then next step starts. 

Valves of ODU are being inspected. Compressor will start 
operation for 2min or so and then stop. The opening and 
closing status of outdoor valves are as below: 

10/on 
Display 
circularly 

Outdoor valves are not fully turned on. Press main board’s 
SW4 button and display shows “09/OC”. Then check if the gas 
and liquid valves of ODU are completely open. After 
confirmation, press the SW4 button again. Then compressor 
will start running for about 2min to inspect the status of valves. 

10_ Status 
judgments of 
outdoor valves 

10/U6 
Display 
circularly 

before startup 

10/oC 
Display 
circularly 

Valves status is normal. Unit will display as in the left for 2s and 
then start next step. 

Ready for units to start debugging. Press main board’s SW3 
button to confirm startup of debugging. 2s later, main board will 
display as below: 

12/AP 
Display 
circularly 

12_ Confirm 
debugging startup  

Startup is confirmed. After displaying for 2s, system will choose 
“15_Cooling debugging” or “16_Heating debugging” according 
to ambient temperature. If the project requests to add 
refrigerant but it is not complemented before debugging, then 
refrigerant can be added in this process through the L-VALVE. 

12/AE 
Display 
circularly 

88 

Sayfa 92

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Description of each stage of debugging progress 

- 
Debugging code 

Code meaning and operation method 
Progress 
LED 

Code 
Display status 

Debugging for cooling mode. If no malfunction occurs for 
50min when compressor is running, then the system is 
certified as normal. After shutting down the unit for 5s, the 
system will enter normal standby status. 

15/AC 
Display 
circularly 

15_ Cooling 
debugging 

15/error code 
Display 
circularly 
Malfunction occurs when debugging for cooling mode. 

Debugging for heating mode. If no malfunction occurs for 
50min when compressor is running, then the system is 
certified as normal. After shutting down the unit for 5s, the 
system will enter normal standby status. 

16/AH 
Display 
circularly 

16_ Heating 
debugging 

16/error code 
Display 
circularly 
Malfunction occurs when debugging for heating mode. 

17_ Debugging 
finished 
oF 
ON 
The entire unit has finished debugging and under standby-by 
condition. 
Debugging procedure for test run, display instruction for indicator on main board of outdoor unit and 

operation method are as below GMV-36WL/A-T(U)、GMV-48WL/A-T(U) GMV-60WL/A-T(U):  

Description of each stage of debugging progress 

- 
Debugging 

code 
Progress code 
Status code 

Code meaning and operation method 
Progress 

LED1 
LED2 
LED3 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

db 
On  
01 
On  
AO 
On 
System is not debugged. 

Hold main board’s SW7 button for 5s to 
start debugging. Main board will display 
as said in the left. 2s later, next step 
starts. 

01_ Set master 
unit 

db 
On 
01 
On 
OC 
On 

db 
On 
02 
On 
Ad 
Blink 
System is allocating addresses. 10s later, 
display as below: 

No master indoor unit. Display will be on 
for 1min, during which master IDU can be 
set manually. If not, system will set the 
unit with minimum IP address as the 
master IDU. 

02_ Allocate 
addresses 

db 
On 
02 
On 
L7 
Blink 

db 
On 
02 
On 
OC 
On 
Allocation is finished. 2s later, next step 
starts. 

db 
On 
03 
On 
01 
Blink 
System is confirming. 1s later, next step 
starts. 

03_ Confirm the 
quantity of ODU 

db 
On 
03 
On 
OC 
On 
System finishes confirmation. 2s later, 
next step starts. 

LED3 displays the quantity of indoor unit. 
Confirm the number manually. If the 
number is not consistent the display one, 
cut off power of IDU and ODU and check 
whether communication wire of IDU is 
correctly connected. After the check, 
connect power and start debugging from 
progress 01. If the number is then 
correct, press main board’s SW7 button 
to confirm. Then the display is as below: 

db 
On 
04 
On 
01~80 
Blink 

04_ Confirm the 
quantity of IDU 

db 
On 
04 
On 
OC 
On 
System has confirmed the quantity. 2s 
later, next step starts. 

89 

Sayfa 93

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Description of each stage of debugging progress 

- 
Debugging 

code 
Progress code 
Status code 

Code meaning and operation method 
Progress 

LED1 
LED2 
LED3 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

Communication between master ODU 
and driver has error. Check the 
communication connection of ODU’s 
main board and drive board. When the 
error is eliminated, start next step. If 
power is off during troubleshooting, then 
restart debugging from progress 01 after 
power is on. 

db 
On 
05 
On 
C2 
On 

Communication of master ODU and 
driver is normal. Unit will display as in the 
left for 2s and detect the capacity ratio of 
IDU and ODU. If the ratio is within range, 
than next step will start 2s later. If the 
ratio is out of range, unit will display as 
below: 

05_ Detect 
ODU’s internal 
communication 

db 
On 
05 
On 
OC 
On 

and capacity 

ratio 

Rated capacity ratio of IDU is too high. 
Change the combination way of IDU and 
ODU to make the ratio within range. And 
restart debugging from progress 01. 

db 
On 
05 
On 
CH 
On 

Rated capacity ratio of IDU is too low. 
Change the combination way of IDU and 
ODU to make the ratio within range. And 
restart debugging from progress 01. 

db 
On 
05 
On 
CL 
On 

Outdoor component’s error. LED3 will 
display the related error code. After errors 
are eliminated, system will start next step 
automatically. If power is off during 
troubleshooting, then restart debugging 
from progress 01 after power is on. 

db 
On 
06 
On 
error 
code 
On 

06_ outdoor 
components 

db 
On 
06 
On 
OC 
On 
System detects no error on outdoor 
component. 10s later, next step starts. 

90 

Sayfa 94

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Description of each stage of debugging progress 

- 
Debugging 

code 
Progress code 
Status code 

Code meaning and operation method 
Progress 

LED1 
LED2 
LED3 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

System detects error on indoor 
components. XXXX means the project 
code of IDU with error. 3s later, related 
error code will be showed. For instance, if 
no.1 IDU has d6 and d7 errors, then the 
LED3 digital tube will show circularly 
00,01,d5,d6,07,92,d6,d7 every 2s. After 
errors are eliminated, system will start 
next step automatically. If power is off 
during troubleshooting, then restart 
debugging from progress 01 after power 
is on. 

db 
On 
07 
On 
Error 
code 
On 

07_ Detect 
indoor 
components 

db 
On 
07 
On 
OC 
On 
No error on components of IDU. 2s later, 
next step starts. 

Preheat time for compressor is less than 
8 hours. Display will be as in the left until 
the preheat time reaches 8 hours. Press 
main board’s SW7 button to confirm 
manually that the preheat time has 
reached 8 hours. Then start next step. 
(Note: Compressor may get damaged if it 
is started without 8 hours of preheat time) 

db 
On 
08 
On 
UO 
On 

08_ Confirm 
preheated 
compressor 

db 
On 
08 
On 
OC 
On 
Compressor has been preheated for 8 
hours. 2s later, next step starts.  

System is lack of refrigerant and display 
will be as in the left. Please cut off power 
of IDU and ODU and check if there is 
leakage on pipeline. Solve the leakage 
problem and complement refrigerant into 
the unit. Then connect power and restart 
debugging from progress 01. (Note: 
Before re-charging refrigerant, unit must 
be power off in case system starts 
progress 10 automatically.) 

db 
On 
09 
On 
U4 
On 

09_ Refrigerant 
judgments 
before startup 

db 
On 
09 
On 
OC 
On 
Refrigerant is normal and unit will display 
as in the left for 2s. Then next step starts. 

91 

Sayfa 95

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Description of each stage of debugging progress 

- 
Debugging 

code 
Progress code 
Status code 

Code meaning and operation method 
Progress 

LED1 
LED2 
LED3 

Code 
Display 

status 
Code 
Display 

status 
Code 
Display 

status 

Valves of ODU are being inspected. 
Compressor will start operation for 2min 
or so and then stop. The opening and 
closing status of outdoor valves are as 
below: 

db 
On 
10 
On 
ON 
On 

Outdoor valves are not fully turned on. 
Press main board’s SW6 button and 
display shows “db 09 OC”. Then check if 
the gas and liquid valves of ODU are 
completely open. After confirmation, 
press the SW6 button again. Then 
compressor will start running for about 
2min to inspect the status of valves. 

10_ Status 
judgments of 
outdoor valves 

db 
On 
10 
On 
U6 
On 

before startup 

Valves status is normal. Unit will display 
as in the left for 2s and then start next 
step. 

db 
On 
10 
On 
OC 
On 

Ready for units to start debugging. Press 
main board’s SW7 button to confirm 
startup of debugging. 2s later, main board 
will display as below: 

db 
On 
12 
On 
AP 
Blink 

Startup is confirmed. After displaying for 
2s, system will choose “15_Cooling 
debugging” or “16_Heating debugging” 
according to ambient temperature. If the 
project requests to add refrigerant but it is 
not complemented before debugging, 
then refrigerant can be added in this 
process through the L-VALVE. 

12_ Confirm 
debugging 

startup 

db 
On 
12 
On 
AE 
On 

Debugging for cooling mode. If no 
malfunction occurs for 20min when 
compressor is running, then system will 
start progress 17. If malfunction occurs, 
unit will display as below: 

db 
On 
15 
On 
AC 
On 

15_ Cooling 
debugging 

Malfunction occurs when debugging for 
cooling mode. After all malfunctions are 
eliminated, system will start next step. If 
power is off during troubleshooting, 
system will start progress 17 
automatically when power is resumed. 

db 
On 
15 
On 
Error 
code 
On 

Debugging for heating mode. If no 
malfunction occurs for 20min when 
compressor is running, then system will 
start progress 17. If malfunction occurs, 
unit will display as below: 

db 
On 
16 
On 
AH 
On 

16_ Heating 
debugging 

Malfunction occurs when debugging for 
heating mode. After all malfunctions are 
eliminated, system will start next step. If 
power is off during troubleshooting, 
system will start progress 17 
automatically when power is resumed. 
17_ Debugging 
finished 
01 
On 
OFF 
On 
OFF 
On 
The entire unit has finished debugging 
and under standby-by condition. 

db 
On 
16 
On 
Error 
code 
On 

92 

Sayfa 96

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

8.3 Parameters reference value for the normal operation of unit 

No. 
Debug item 
Parameter 

name 
Unit 
Reference 

Outdoor 
temperature 

℃
(℉) 
- 

1 

When compressor starts, discharge temp in cool mode is 
within 70~105℃(158~221℉) and at least 10℃(50℉) higher 
than the high pressure saturation temp; 
As for temp in heat mode, it is within 65~90℃(149~194℉) 
and at least 10℃(50℉) higher than the high pressure 
saturation temp. 

2 
Compressor 

℃
(℉) 

discharge 

temp 

In cool mode, defrosting temp is 4~10℃(39~50℉) lower 
than system’s high pressure value; 
In heat mode, defrosting temp is about 2℃(36℉) different 
from system’s low pressure value. 

3 
Defrosting 

℃
(℉) 

temp 

In cool mode, the normal high pressure value is within 20℃
~55℃(68~131℉). According to the change of ambient temp 
and system’s operating capacity, the high pressure value will 
be 10℃~30℃(50~86℉) higher than ambient temp. The 
higher ambient temp is, the smaller temp difference is. If 
ambient temp is 25~35℃(77~95℉) in cool mode, system’s 
high pressure value will be within 44~53℃(111~127℉). 
In heat mode, if ambient temp is above -5℃(23℉), system’s 
high pressure value is within 40~52℃(104~126℉). If 
ambient temp is low and many IDUs are turned on, the high 
pressure will be lower. 

System 
paramet

ODU 
paramet

ers 

ers 

4 
System high 

℃
(℉) 

pressure 

When ambient temp in cool mode is 25~35℃(77~95℉), the 
low pressure value is 0~8℃(32~46℉). 
When ambient temp in heat mode is above -5℃(23℉), the 
low pressure value is -15~8℃(5~46℉). 

5 
System low 

℃
(℉) 

pressure 

In cool mode, the thermal electronic expansion valve 
remains 480PLS. 
In heat mode, the adjustable opening angle of EXV is 
60~480PLS. 

6 
Opening angle 
of thermal EXV 
PLS 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

Changes in 
16Hz~74Hz. 
GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 
GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 

Compressor’s 
operating freq 
HZ 

7 

GMV-60WL/A-T(U) 
GMV-60WL/C-T(U) 

8 
Compressor’s 

A 
When compressor works normally, the current is no more 
than22.6A. 

operating 

System 
paramet

ODU 
paramet

current 

When ambient temp is below 35℃(95℉), IPM temp is lower 
than 80℃(176℉) and the highest temp won’t be above 95℃
(203℉). 

9 
Compressor’s 

ers 

ers 

℃
(℉) 

IPM temp 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

10 

Fan motor’s 
operating freq 
HZ 

GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 
GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 

11 

93 

Changes in 
10Hz~80Hz. 

Changes in 
16Hz~80Hz 

Changes in 
0~37Hz according 
to system’s 

pressure. 

Changes in 
0~49Hz according 
to system’s 

pressure. 

Sayfa 97

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

No. 
Debug item 
Parameter 

name 
Unit 
Reference 

12 
GMV-60WL/A-T(U) 
GMV-60WL/C-T(U) 

IDU ambient 

℃
(℉) 
- 

13 

temp 

According to ambient temp, for a same IDU in cool mode, 
the inlet temp will be 1℃~7℃(34~45℉) lower than the outlet 
temp, and 4~9℃(39~48℉) higher than the low pressure 
value. 
For a same IDU in heat mode, the inlet temp will be 10℃
~20℃(50~68℉) lower than the outlet temp. 

14 
Indoor heat 
exchanger’s 

℃
(℉) 

inlet temp 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

15 

IDU 
paramet

ers 

GMV-36WL/A-T(U) 
GMV-48WL/A-T(U) 
GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 

Opening angle 

16 

of indoor EXV 
PLS 

17 
GMV-60WL/A-T(U) 
GMV-60WL/C-T(U) 

18 
Communication 

Communicatio

n data 
- 
Number of IDUs detected by software is the same with the 
actual number. No communication error. 

parameters 

Indoor unit can drain water out completely and smoothly. 
Condensate pipe has no backward slope of water; Water of 
outdoor unit can be drained completely through drainage 
pipe. No water drop from unit base. 

19 
Drainage system 
- 
- 

20 
Others 
- 
- 
Compressor and indoor/outdoor fan motor do not have 
strange noise. Unit can operate normally. 

94 

Changes in 
0~40Hz according 
to system’s 

pressure. 

In cool mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 
In heat mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 

In cool mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 
In heat mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 

In cool mode, the 
opening angle of 
indoor EXV varies 
within 70~480PLS. 
In heat mode, the 
opening angle of 
indoor EXV varies 
within 40~480PLS. 

Sayfa 98

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

MAINTENANCE 

95 

Sayfa 99

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

MAINTENANCE 

1 Malfunction List  

1.1  Malfunction list for the wired controller  

Display 

code 
Content 
Display 

code 
Content 
Display 

code 
Content 

Wrong number of indoor 
unit for one-to-more indoor 

L0 
Malfunction of 

d8 
Malfunction of water 

indoor unit 
L9 

temperature sensor 

unit 

L1 
Indoor fan 
protection 
LA 
Wrong series for 
one-to-more indoor unit 
d9 
Malfunction of jumper cap 

L2 
E-heater 
protection 
LH 
Alarming due to bad air 

quality 
dA 
Abnormal address for 

indoor unit 

The indoor unit model can’t 

L3 
Water overflow 

dH 
Abnormal PCB for wired 

protection 
LC 

match with outdoor unit 

controller 

model 

L4 
Overcurrent 

protection 
d1 
Poor indoor PCB 
dC 
Abnormal code-dialing 

setting of capacity 

L5 
Freeze prevention 

protection 
d3 
Malfunction of ambient 

temperature sensor 
dL 
Malfunction of air exhause 

temperature sensor 

L6 
Mode shock 
d4 
Malfunction of entry tube 

temperature sensor 
dE 
Malfunction of indoor C02 

sensor 

L7 
No main indoor 

unit 
d6 
Malfunction of exit tube 

temperature sensor 
C0 
Communication 

malfunction 

L8 
Insufficient power 

supply 
d7 
Malfunction of humidity 

sensor 
AJ 
Clean alarming for filter 

db 
Special code: engineering debugging code 
1.2 Status display table for indicators on main board of outdoor unit  

Definition:  

LED1: It displays “00” for hot water mode as for DC Inverter Side Discharge VRF 

LED2: It displays “AC” for AC mode, cooling and cooling OFF mode for indoor unit, and displays 

“AH” for heating and heating OFF mode for indoor unit  

LED3: It displays on or off status of compressor and malfunction code. It displays “ON” when the 

compressor is operating and “OFF” when the compressor stops operation. When there’s malfunction for 

the unit, it will display corresponding malfunction code; when there’re multiple malfunctions, the 

malfunction codes will be displayed in turn.   

Display code table of outdoor unit is as below:  

 Content 

symbol 
Division  

0 
1 
2 
3 
4 
5 

symbol 

Auxiliary 

Freeze 
prevention 

L 
Malfunction of 

Protection of 

Water-full 
protection 

Over-current 

heating 
protection 

IDU (uniform) 

indoor fan 

protection 

protection 

Indoor  

Malfunction 

Malfunction 
of entry-tube 

Malfunction 

d 
- 
Indoor PCB is 

of ambient 
temperature 

of middle 
temperature 

poor 
- 

temperature 

sensor 

sensor 

sensor 

96 

Sayfa 100

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 Content 

symbol 
Division  

0 
1 
2 
3 
4 
5 

symbol 

High 
discharge 
temperature 
protection of 

Discharge 
low-temperature 

E 
Malfunction of 
ODU (uniform) 

High-pressure 

Low-pressure 

- 

protection 

protection 

protection 

compressor 

Malfunction 
of discharge 
temperature 

Malfunction 

Malfunction of 

F 
Main board of 

of 
low-pressure 

high-pressure 

- 

- 

ODU is poor 

sensor of 
compressor 

sensor 

sensor 

1 

Over-current 
protection of 
compressor 1 

J 
- 

- 
- 
- 
- 

Outdoor  

Malfunction of 

Malfunction 

Malfunction 

Malfunction of 

outdoor 
ambient 
temperature 

of liquid 
temperature 

of gas 
temperature 

defrosting 
temperature 

b 
- 

- 

sensor of 
sub-cooler 

sensor of 
sub-cooler 

sensor 1 

sensor 

Voltage 
protection of 
driving board 

Driving board 
of compressor 

Reset 
protection of 

malfunction of 
driving board of 

Over-current 
protection of 

Drive PFC 
protection of 

P 

operates 
abnormally 

driving 
module of 
compressor 

compressor 

power of 
compressor 

inverter 
compressor 

compressor 

(uniform) 

(uniform) 

(uniform) 

Wrong 
address for 

Wrong setting of 

Preheat time of 

ODU’s capacity 

U 

compressor is 

- 

- 
- 

driving 
board of 
compressor 

code/jumper 

insufficient 

cap 

Communication 

Debugging  

Communication 

malfunction 
between main 

Alarm 
because 
project code 

malfunction 
between IDU,  
ODU and IDU’s 
wired controller 

Malfunction 

C 

- 

control and 

- 

of lack of 

inverter 
compressor 

IDU 

of IDU is 
inconsistent 

driver 

Inquiry of 
compressor 

A 
Unit waiting for 

- 
Defrosting  
Oil-return 
Online test 

debugging 

operation 
parameters 

Status  

Setting of upper 

SE operation 

Setting of 
defrosting 

limit of 
IDU/ODU 

n 

setting of 

- 
- 
- 

system 

cycle K1 

capacity 
distribution ratio 

97 

Sayfa 101

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 Content 

symbol 
Division  

0 
1 
2 
3 
4 
5 

symbol 

Setting for 
general unit 

and high 

Anti-ice 
temperature 
setting under 

Upper limit of 

Upper limit 
of correction 

sensible 
heat unit (0 

correction 

Shield setting 
for compressor 

value for 
target low 
pressure is 

value for 
target low 
pressure is 

q 
- 

represents 

low 
temperature 

frequency 

general,1 
represents 

condition  

Z0 

Z2 

high 
sensible 

heat) 
 

 Content 

symbol 
Division  

6 
7 
8 
9 
A 
H 

symbol 

Alarm due to 

1-to-more: 
IDU series 

1-to-more: 
number of IDU 

bad air 

L 
Mode shock 
No main IDU 
Power supply 

quality 
(Fresh air 

is insufficient 

is 
inconsistent 

is inconsistent 

unit) 

Malfunction of 

Web 
address of 

Malfunction 

PCB of wired 

exit-tube 
temperature 

- 
Malfunction of 

d 

of humidity 

controller is 

jumper cap 

IDU is 
abnormal 

sensor 

abnormal 

sensor 

Protection 

Gas-mixing 
protection of 

High pressure 
ratio protection 

due to 
abnormal 

J 
- 

- 

- 

Indoor 

4-way valve 

of system 

pressure 

Malfunction of 

Malfunction 

Malfunction of 
heat exchanger 

inlet temp 

of outlet 
temp sensor 
of gas-liquid 

Clock of 
system is 
abnormal 

b 

sensor of 
gas-liquid 
separator 

- 

- 

temperature 

sensor 

separator 

Malfunction 

High-voltage 
protection of 
compressor’s 

Drive IPM 

Drive IPM high 

Desynchronizing 

of drive 
temperature 

module 
protection of 

temperature 
protection of 

protection of 

P 

- 

inverter 
compressor 

sensor of 
compressor 

drive DC bus 

compressor 

compressor  

bar 

Alarm because 

Short-circuit 
malfunction of 

Malfunction of 

valve is 
abnormal 

U 

- 

pipe-line for 

- 
- 

IDU 

ODU 

Debugging  

Rated 
capacity is 

C 
- 
- 
- 
- 
- 

too high 

EU AA level 

A 
Heat pump 
function setting 

Quiet mode 

Vacuum pump 

mode 
IPLV test 

EER test 

Heating  

setting 

mode 

Status  

Engineering 

Parameter 

n 
Malfunction 
inquiry of unit 

No. inquiry 

- 
Heat pump 

Heating only 

inquiry of 

of indoor 

unit 

unit 

unit  

unit 

98 

Sayfa 102

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

 Content 

symbol 
Division  

6 
7 
8 
9 
A 
H 

symbol 

Low 
temperature 

Setting for 
engineering 

Select 
Centigrade 

Heat 
recover 

main body 

protection 
correction 

Defrost mode 

q 

ability 
correction 

conducts 

or 
Fahrenheit 

setting 

status 

heating 

value for 
discharge 

factor θ 

Content  

symbol 
Division 
 symbol 

C 
L 
E 
F 
J 
P 

Models for 

IDU and 
ODU are not 

L 

- 
- 
- 
- 
- 

matched 

Malfunction of 

Abnormal 
setting for 

Malfunction of 

air-outlet 
temperature 
sensor(Fresh 

indoor CO2 
sensor (fresh 

d 

- 
- 
- 

capacity 

button 

air unit) 

air unit) 

Drop 
protection of 

discharge 
temperature 

E 

- 
- 
- 
- 
- 

sensor of 
compressor 

1 

Indoor  

F 
- 
- 
- 
- 
- 
Malfunction 
of DC motor 

J 
- 
High-pressure 

protection 
- 
- 
- 
- 

Drive current 

Drive 
charging 

Low-voltage 
protection of 
compressor’s 

detection 

Failure 
startup of 

AC current 
protection of 

Phase-lacking 

circuit 
malfunction 

circuit 
malfunction 

P 

of inverter 
compressor 

inverter 
compressor 

inverter 
compressor 

drive DC bus 

of 
compressor 

of 
compressor 

bar 

Drive current 

Drive 
charging 

detection 

Low-voltage 
protection of 
fan’s drive DC 

Failure 
startup of 
inverter fan 

AC current 
protection of 

circuit 
malfunction 

Phase-lacking 

H 

circuit 
malfunction 

of inverter fan 

inverter fan 

of fan 

bus bar 

of fan 

Setting of 
main IDU is 

Charging of 
refrigerant is 

Wrong 
button-dial 

U 

- 
- 
- 

successful 

invalid 

Debugging  

Malfunction 

Malfunction 

Malfunction 

Malfunction 

of lack of 
main control 

Rated capacity 

of multiple 
main control 

of multiple 
main wired 

of multiple 
main wired 

C 

is too low 
- 

unit 

units 

controllers 

controllers 

Debugging 
confirmation 
for startup of 

Charging 
refrigerant 
automatically 

Charging 
refrigerant 

Fan 
Alarm for 
cleaning filter 

A 
Cooling 

Status  

manually 

unit 

n 
Cooling only 

unit 
- 
Negative sign 

code 
Fan model 
- 
- 

99 

Sayfa 103

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Content  

symbol 
Division 
 symbol 

C 
L 
E 
F 
J 
P 

The main 

Dual heat 
source water 

body 
conducts 

Static pressure 

EVI operation 

Compulsory 
cooling mode 

q 

- 

setting 

status setting 

emptying 

cooling 

Content 
 symbol 
Division  
symbol 

U 
b 
d 
n 
y 

Communication 

malfunction 
between IDU and 
the receiving lamp 

Overflow 
distribution of IP 

Debugging  
C 

- 
- 
- 

address 

plate 

Emergency 

A 
Long-distance 
emergency stop 

stop of 
operation 

Limit operation 
- 
- 

Status  

Working mode 
of compressor 

q 
- 
- 
- 
- 

heating zone 
2 Troubleshooting  

Troubleshooting principle  

(1) Communication malfunction  

Communication 

malfunction 

NO

Check whether indoor unit and 

Energize indoor unit and 

outdoor unit is power supplied

outdoor unit

YES

NO

Check whether the 
communication wire between 
indoor unit and outdoor unit is 

Connect the  communication 

wire for indoor unit and 

outdoor unit  correctly

correct

YES

NO

Measure whether the 
communication wire is in 

Replace communication 

wire

normal 

100 

Sayfa 104

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) High pressure protection  

High pressure 

protection

NO

YES

Measure whether 

Replace main 
board of outdoor 

Measure whether the high pressure 

the pressure 
switch is normal

is too high with manometer

unit

YES

NO

Replace 
pressure switch

YES

Charge refrigerant according to the volume on 
nameplate; check whether there is leakage for the 

Check whether the refrigerant-
charging volume is superfluous

system

YES

NO

Open the valve 

Check whether gas valve and liquid 

valve are open completely

completely

YES

NO

Cover the panel of 

Check whether the panel of 
outdoor unit is covered and sealed 

outdoor unit well

well

YES

NO

E liminate obstacles 

Check whether the air can blow 
smoothly at the heat exchanger of 

and sundries

indoor unit and outdoor unit

YES

NO

Measure the 
circumstances of fan 
motor and signal input

Check whether the indoor fan and 

outdoor fan can operate

YES

NO

Measure the 
circumstances of swing 

Check whether the indoor swing 

blade is open completely

motor and signal input

YES

NO

Check whether the electronic expansive value for 
indoor unit and outdoor unit can operate normally
Engage valve and 

coil

YES

NO

Mainly check the air inlet and air outlet connecting 
indoor unit and main pipe, and the expansive valve 
for indoor unit and outdoor unit. Replace electronic 

Blockage for 
system pipeline

expansion valve, dry strainer,ect.

101 

Sayfa 105

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(3) Low-pressure protection  

Low pressure 

protection

NO

Measure 
whether the 
pressure switch 

YES

Replace main 
board of outdoor 

Measure whether the low pressure 

is too low with manometer

unit

is normal

NO

Replace 
pressure switch

yes

YES

Charge refrigerant according to the volume 

Check whether the refrigerant-
charging volume is insufficient

on nameplate; check whether there is 

leakage for the system

NO

NO

Open the valve 

Check whether gas valve and liquid 

valve are open completely

completely

YES

NO

Cover the panel 

Check whether the panel of 
outdoor unit is covered and sealed 

of outdoor unit 

well

well

YES

NO

Eliminate obstacles and 

Check whether the air can blow 
smoothly at the heat exchanger of 

sundries

indoor unit and outdoor unit

YES

NO

Measure the 
circumstances of fan 
motor and signal input

Check whether the indoor fan 

and outdoor fan can operate

YES

NO

Measure the 
circumstances of swing 

Check whether the indoor swing 

blade is open completely

motor and signal input

YES

NO

Engage valve and 

Check whether the electronic 
expansive value for indoor unit and 

coil

outdoor unit can operate normally

YES

NO

Mainly check the air inlet and air outlet 
connecting indoor unit and main pipe, and the 
expansive valve for indoor unit and outdoor unit. 

Blockage for 
system pipeline

Replace electronic expansion valve, dry 

strainer,ect.

102 

Sayfa 106

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(4) Discharge temperature protection  

Discharge temperature 

protection

YES

Measure whether the 

NO

Replace main board of 

resistance valve for 
temperature sensor is 

Check whether the discharge 
temperature for compressor is 

outdoor unit 

reached to 113℃

normal

NO

YES

Replace discharge 
temperature sensor

YES

Charge refrigerant according to the volume on nameplate; check 

Check whether the refrigerant-
charging volume is insufficient

whether there is leakage for the system  

NO

NO

Check whether the gas valve 

Open the valve 

and liquid valve are open 

completely

completely

YES

NO

Check whether the panel of 
outdoor unit is covered and 

Cover the panel for 

outdoor unit well

sealed well

YES 

NO

Check whether the air can blow 
smoothly at the heat exchanger 

Eliminate obstacles and 

sundries

of indoor unit and outdoor unit

YES

NO

Measure the circumstances 
of fan motor and signal input

Check whether the indoor fan 

and outdoor fan can operate

YES

NO

Measure the circumstances 

Check whether the indoor swing 

of swing motor and signal 

blade is open completely

input

YES

NO

Check whether the electronic 
expansion valve for indoor unit 

Engage valve and coil

and outdoor unit can operate 

normally

YES

NO

Mainly check the air inlet and air outlet connecting indoor 
unit and main pipe, and the expansive valve for indoor unit 

Blockage for system 

pipeline

and outdoor unit. Replace electronic expansion valve, dry 

strainer,ect.

103 

Sayfa 107

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(5) Mafunction of temperature sensor  

(6) Malfunction of sensor  

(7) Unit and main board can’t be energized  

Malfunction of 

temperature 

sensor

NO

 Conform whether the 

 Whether the plug of temperature is 
connected with the plug of main board 

plug is connected 

correctly

correctly

YES

NO

Replace temperature 

Measure whether resistance value of 
temperature sensor is in the normal range 

sensor

YES

Replace main 

board

Malfunction of 

sensor

NO

Confirm whether the 

Check whether plug of sensor is 

plug is connected 

connected with socket correctly

correctly

YES

YES

Replace 
pressure 

Measure whether the output value (DC 
voltage) for socket of main board of outdoor 

unit is normal 

sensor

NO

Replace main board 

of outdoor unit

Unit and main board can’t 

be energized 

Check whether it’s 

NO

the malfunction of 

Measure whether voltage between pole L 

and pole N  of wiring board is 220V 

power supply for 

wiring board

YES

NO

Replace filter 

Check whether there’s power 

supply for  filter board

board 

YES

Replace main board 

of outdoor unit

104 

Sayfa 108

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(8) Failure start-up  

Failure start-up for 

consecutive 6 

times

YES
NO

Work normally after 
replacing main board?

Replace compressor and 

Work normally

liquid gas separator

(9) Reset protection for drive module of compressor, drive PFC protection for compressor, 

malfunction of drive temperature sensor for compressor, circuit malfunction of drive current 

detection for compressor 

Wired 
controller 
displays P0

 LED3 dual-8 nixie 
tube displays P3, P4,
P7  or PC

Replace main 

board

Work normally

(10)  Drive IPM overtemperature protection for compressor  

Wired 
controller 
displays P0

LED3 dual-8 

nixie tube 
displays P8

yes

no

Whether two IPM 
module is tightened?

Replace main 

Tighten 
module

board

Work normally

105 

Sayfa 109

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(11)  Desynchronizing protection for inverter compressor  

(12)  Failure startup for inverter compressor 

Wired 
controller 
displays P0

LED3 dual-8 

nixie tube 
displays P9

Whether the 
sequence of wire 
for compressor is 

no

Adjust the 
sequence of wire 

for compressor

correct?

yes

yes

Connect the wires 

Whether 
the wiring terminal 

of compressor 

for compressor is 

tightly

loose?

no

yes

Replace the main 

board. Work 

normally?

no

Replace 
compressor
Work normally

Wired 
controller 
displays P0

LED3 dual-8 

nixie tube 
displays PJ

yes

Replace main 

board. Work 

normally?

no

Replace 
compressor

Work normally

106 

Sayfa 110

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(13)  Loop malfunction of driven charging for compressor 

(14)  Malfunction of memory chip for inverter compressor 

Wired 
controller 
displays  P0

LED3 dual-8 

nixie tube 
displays PF

yes
no

Check whether the 

wires for PFC 
induction is correct/

Reinsert the 
wires for PFC
Replace main 

board

Work normally

Wire controller 

displays P0

LED3 dual-8 nixie 

tube displays PA

Whether the 
memory chip is 
inserted inversely

yes

Adjust the memory 

chip

no

Whether the 
memory chip is 

yes

Insert the memory 

chip tightly

loose?

no

Replace main 

board

Work normally

107 

Sayfa 111

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(15) Overcurrent protection for inverter compressor, IPM module protection, phase-lacking of 

inverter compressor  

(16) High pressure protection for driven DC bus bar of compressor, low pressure protection for  

driven DC bus bar of compressor  

Wired controller 

displays P1

LED3 dual-8 nixie tube 
displays P5、P6 or PE

no

Whether the 
sequence of wire 
for compressor is 

Adjust the sequence of 

wire for compressor

correct?

yes

yes

Whether the 
wiring terminal of 

Connect the wires of 

compressor is 

compressor tightly

loose?

no

yes

Replace main 

board. Work 

normally?

no

Replace 
compressor
Work normally

Wired controller 

displays P2

LED3 nixie tube 
displays PH or PL

no
 

yes

Whether the power 

voltage is 
185V~264V?

yes

Replace main 

board. Work 

normally?

no

Close Upon power off 

Replace compressor
Work normally

and ask authorized 

personnel

108 

Sayfa 112

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(17)  AC current protection for inverter compressor 

Wired 
controller 
displays E0

LED3 dual-8 

nixie tube 
displays PP

Replace main 

board

Work normally

(18)  Communication malfunction between main contoller and driver of inverter compressor  

Wired controlled 

displays C2

LED3 dual-8 nixie 

tube displays C2

yes

no

Check whether the 

main control CPU 

board is inserted 

well?

Replace main 

Insert the CPU 

board

board well 

Work normally

109 

Sayfa 113

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

3 Power Distribution of Unit 

3.1 Power distribution of unit 

The control logical relationship among parts inside the electric box of unit is showed by the mongline 

diagram (CAD source file).  

The main loop is showed by bold line (line width: 1mm); the control loop is showed by slim line (line 

width: 0.2mm).  

Power wiring 

board

Filter plate
Drive board
Compressor

Main control board

4-way valve, by-pass valve, 
electric heating belt and control 

signal 

(Bold line is the power line and the slim line is the control line) 

3.2 Main electric parts 

Name  
Photo  
Function introduction  

Filter plate 

IPM Module  

Fan

Temperature sensor, electric 
expansion valve, high pressure and 

low pressure switch and so on

It main effect is to eliminate the interference 
of power for protecting unit’s anti-interference 
capability and prevent the interference to 
other electric appliances.  

There are three complemental IGBT tube 
inside the IPM module. They are controlled 
by PWM wave and then bring the pressure of 
DC bus bar to different stator windings of 
compressor at different stage, and then 
generate current on the stator. Meanwhile, 
magnetic field will be generated on the stator 
winding, and push the operation of rotor and 
then drive compressor to operate.  

110 

Sayfa 114

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Name  
Photo  
Function introduction  

PFC module  

3.3 Circuit diagram 

GMV-24WL/C-T(U)、GMV-28WL/C-T(U) 

Four diodes and two MOS pipe are 
intergrated inside the PFC module. It will 
transform AC input power into DC power. 
Meanwhile, MOS pipe is controlled by PWM 
wave. Pressure will be increased by 
induction.   

111 

Sayfa 115

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-36WL/A-T(U)、GMV-48WL/A-T(U) 

GMV-36WL/C-T(U)、GMV-48WL/C-T(U) 

112 

Sayfa 116

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-60WL/A-T(U) 

4 Removal of Parts 

GMV-60WL/C-T(U) 

113 

Sayfa 117

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.1 Key parts  

Photo 
Name 
Function 

Core part of air conditioning 
system. It sucks low temperature 
and low pressure gas, compress it 
to high temperature and high 
pressure gas, and then discharge 
it. 

compressor 

Throttling device. It transforms high 
pressure refrigerant liquid into low 
pressure steam. 

Electronic expansion 

valve 

4-way valve 
It changes the flow direction of 
refrigerant for switching between 
cooling and heating. 

It stays between discharge outlet of 
compressor and inlet of condenser. 
It used for separating the lubricant 
oil of compressor when the high 
temperature and high pressure 
refrigerant gas is discharged from 
the compressor. 

Oil separator 

It stays between outlet of 
evaporator and suction ouitlet of 
compressor. It used for separating 
low temperature and low pressure 
refrigerant. 

Vapour liquid separator 

114 

Sayfa 118

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Photo 
Name 
Function 

It used for storing the superfluous 
high pressure refrigerant liquid 
during cooling process. 

High pressure liquid 

storage tank 

Solenoid valve 
-- 

It used for connecting indoor unit 
and outdoor unit, and used for 
maintenance and installation. 

Cut-off valve 

4.2 Removal of key parts 

4.2.1 GMV-24WL/C-T(U), GMV-28WL/C-T(U) , series unit 

Removal operation for panel  

Remark: Before removing the panel, please make sure that the unit is disconected with the power 

Process 
Photo 
Operation Instruction 

● Loose the screws fixing the top 
cover with screwdriver 
●  Hold the top cover upwards 
and then put it on the floor flatly 

1.Remove top 
cover  

115 

Sayfa 119

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Remark: Before removing the panel, please make sure that the unit is disconected with the power 

Process 
Photo 
Operation Instruction 

2. Remove front 
side plate 
sub-assy  

3. Remove front 
panel and grille   

4. Remove left 
side plate and 
rear side plate  

Removal operation for panel  

● Loose the screw fixing the front 
side plate with screwdriver 
● Hold the front side plate 
upwards and then put it on the 
floor flatly  

● Loose the screws fixing the 
front 
panel 
and 
grille 
with 
screwdriver 
● Put the front panel and grille on 
the floor flatly  

● Loose screws fixing left side 
plate and rear side plate with 
screwdriver 
● remove the rear side plate  

116 

Sayfa 120

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for blade 
Remark: Before removing the motor, please make sure that the unit is disconnected with the power. 
Process 
Photo 
Operation Instruction 

1. Remove grille 
● Loose screws fixing the panel 
with screwdriver 
● Then remove the grille 

2. Remove 
blade 

3. Remove 
motor 

4. Install motor 
● Replace the motor, tighten 
screws with screwdriver and then 
connect the power cord of motor 

● Loosen nuts fixing the blade 
with wrench 
● Then remove the blade and put 
it on the floor flatly 

● Loose screws fixing the motor 
with screwdriver 
● then remove the power cord of 
motor 
● Take out the damaged motor 

117 

Sayfa 121

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for blade 
Remark: Before removing the motor, please make sure that the unit is disconnected with the power. 
Process 
Photo 
Operation Instruction 

5. Assemble 
unit 

Removal operation of compressor 
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the 

power is disconnected. 
Process 
Photo 
Operation Instruction 

1. Remove wiring 
cover of 
compressor 

2. Disconnect 
compressor and 
connected 
pipeline 

● Assemble the unit in the the 
converse sequence 

● Loose screws fiixng 
the compressor with 
screwdriver 
● Then pull out the 
power cord 
 
Note: When 
removing the power 
cord, make marks for 
different color power 
cords and 
corresponding wiring 
terminals for wrong 
terminal. 

● Weld suction pipe 
and discharge pipe of 
compressor 
● then pull out the 
connection pipe from 
the compressor 
Note: During welding 
process, do not let 
the flame burn out 
other parts. 

118 

Sayfa 122

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of compressor 
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the 

power is disconnected. 
Process 
Photo 
Operation Instruction 

3. Loose nuts 
fixing the foot of 
compressor 

4. Remove the 
compressor 
from the chassis 

5. Fix the new 
compressor at the 
chassis 

6. Connect suction 
pipe and 
discharge pipe of 
copressor and 
pipeline of system 
again 

Twist off the nuts for 
compressor with 
wrench 

● Take out the 
compressor and 
replace it 
Note: When replacing 
the compressor, do 
not damage nearby 
pipelines and other 
parts 

After replacing the 
compresor, fix the 
nuts at the bottom of 
compressor 

Weld the connection 
pipe of compressor, 
connect the pipeline 
and compressor 
Note: During welding 
process, do not let 
flame burn out other 
parts 

119 

Sayfa 123

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of compressor 
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the 

power is disconnected. 
Process 
Photo 
Operation Instruction 

7. Connect the 
power cord of 
compressor well 

8. Check and 
open the upper 
cover plate 

Removal operation for 4-way valve 
Remark: Before removing the 4-way valve, please make sure that there’s no refrigerant inside the pipeline of system 

and then power is disconnected. 
Process 
Photo 
Operation Instruction 

1.Disconnect 
the coil of 4-way 
valve from the 
4-way valve 

● Loose screws fixing 
the power cord with 
screwdriver 
● conenct the power 
cord well again 
Note: When 
connecting the power 
cord, make marks for 
different color power 
cords and 
corresponding wiring 
terminals. 

●Check whether the 
pipeline is connected 
well 
●Check whetehr all 
parts and connection 
wires are connected 
well 
●If there’s no 
problem after 
checking, install front 
and rear cover 
plates. 
 

●Remove the coil of 
4-way valve at first 

120 

Sayfa 124

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for 4-way valve 
Remark: Before removing the 4-way valve, please make sure that there’s no refrigerant inside the pipeline of system 

and then power is disconnected. 
Process 
Photo 
Operation Instruction 

2.Disconnect 
the 4-way valve 
and connection 
pipeline 

3. Replace 
4-way valve 

4. Replace 
4-way valve 

● Weld those 4 
connection spots on 
4-way valve, and 
then pull out the 
connection pipe 
Note: During welding 
process, do not let 
the flae burn out 
other parts 

● Replace 4-way 
valve 
Note: During welding 
process, do not let 
the flame burn out 
other parts 

● Weld the 
connection position 
between 4-way valve 
and pipeline 
Note: During welding 
process, do not let 
flame burn out other 
parts 

121 

Sayfa 125

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Remival operation for eletronic expansion valve 
Remark: Before removing the electronic expansion valve, please make sure that there’s no refrigerant in th pipeline of 

system and the power is disconnected 
Process 
Photo 
Operation Instruction 

1. Disconnec 
the electronic 
expansion valve 
from the 
pipeline 

2. Take out the 
electronic 
expansion valve 
and replace it 

3. Replace 
electronic 
expansion valve 

● Remove the coil of 
electroc expansion 

valve at first 

● Weld the 
connection pipe for 
expansion valve, and 

then pull out the 

connection pipe 

Note: During 
welding process, do 
not let flame burn out 

other parts 

●Take out the 
electronic expansion 

valve and replace it 

● Weld the 
connection pipe of 
electronic expansion 

valve 
● Inistall the coil of 
electronic expansion 

valve 

 
Note; During 
welding process, do 
not let the flame burn 

out other parts 

122 

Sayfa 126

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of gas liquid separator 
Remark: Before removing the gas liquid separator, please make sure that there’s no refrigerant inside the pipeline of 

system and disconnect the power 
Process 
Photo 
Operation Instruction 

1.Disconnect  
inlet pipe and 
exit pipe of gas 
liquid separator 
 

2. Replace gas 
liquid separator 

3.  Replace 
gas liquid 
separator 

● Weld those two 
connection spots on 
the gas liquid 
separator and then 
pull out the 
connection pipe 
Note: During welding 
process, do not let 
flame burn out other 
parts 

● Loose 4 screws 
with screwdriver 
● Replace gas lliquid 
separator 

● Weld the pipe 
connected with gas 
liquid separator 
● Fix the screws at 
the base of gas liquid 
separator well again 
Note: During welding 
process, do not let 
flame burn out other 
parts 

123 

Sayfa 127

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for plate heat exchanger 
Remark: Before removing the plate heat exchanger, please make sure that there’s no refrigerant inside the pipeline of 

system and disconnect the power 
Process 
Photo 
Operation Instruction 

1. Remove top 
cover, back 
plate and right 
plate 

2.Remove the 
bracket of plate 
heat exchanger 

3. Weld those 4 
connection 
spots on the 
plate heat 
exchanger, and 
then pull out 
plate heat 
exchanger 

4. Replace new 
plate heat 
exchanger 

●Twist off the nuts 
fixing the plate, 
remove front plate 
firstly, then remove 
right plate, and  
remove back plate 
finally 

● Twist off the nuts 
fixing the bracket of 
plate heat exchanger 

●Weld those 4 
connection spots on 
the plate heat 
exchanger, and then 
pull out the 
connection pipe. 
Note: During welding 
process, do not let 
flame burn out other 
parts 
 

● Weld the pipe 
connected with plate 
heat exchanger 
Note: During welding 
process, do not let 
flame burn out other 
parts 
 

124 

Sayfa 128

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

4.2.2 GMV-36WL/A-T(U), GMV-48WL/A-T(U), GMV-60WL/A-T(U) 

GMV-36WL/C-T(U), GMV-48WL/C-T(U), GMV-60WL/C-T(U) , series unit 

Removal operation for panel 
Remark: Before removing the panel, please make sure that the unit is disconected with the power 
Process 
Photo 
Operation Instruction  

1.Remove top 
cover 

2. Remove front 
side plate 
sub-assy 

3. Remove front 
panel and grille 

 Loose the screws 
fixing the top cover 
with screwdriver 
  Hold the top cover 
upwards and then put 
it on the floor flatly 

 Loose the screw 
fixing the front side 
plate with screwdriver 
 Hold the front side 
plate upwards and 
then put it on the floor 
flatly 

 Loose the screws 
fixing the front panel 
and grille with 
screwdriver 
 Put the front panel 
and grille on the floor 
flatly 
 

125 

Sayfa 129

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for panel 
Remark: Before removing the panel, please make sure that the unit is disconected with the power 
Process 
Photo 
Operation Instruction  

4. Remove left 
side plate and 
rear side plate 

Removal operation for blade 
Remark: Before removing the motor, please make sure that the unit is disconnected with the power. 
Process 
Photo 
Operation Instruction 

1. Remove grille 

2. Remove 
blade 

 Loose screws fixing 
left side plate and rear 
side plate with 
screwdriver 
 remove the rear side 
plate 

 Loose screws fixing 
the 
panel 
with 
screwdriver 
 Then remove the 
grille 

 Loosen nuts fixing 
the 
blade 
with 
wrench 
 Then remove the 
blade and put it on 
the floor flatly 
 

126 

Sayfa 130

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for blade 
Remark: Before removing the motor, please make sure that the unit is disconnected with the power. 
Process 
Photo 
Operation Instruction 

3. Remove 
motor 

4. Install motor 

5. Assemble 
unit 

 Loose screws fixing 
the 
motor 
with 
screwdriver 
 then 
remove 
the 
power cord of motor 
 Take 
out 
the 
damaged motor 

 Replace the motor, 
tighten screws with 
screwdriver and then 
connect teh power 
cord of motor 

 Assemble the unit in 
the 
the 
converse 
sequence 

127 

Sayfa 131

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of compressor 
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the 

power is disconnected. 
Process 
Photo 
Operation Instruction 

1. Remove wiring 
cover of 
compressor 

2. Disconnect 
compressor and 
connected 
pipeline 

3. Loose nuts 
fixing the foot of 
compressor 

 Loose screws fiixng 
the compressor with 
screwdriver 
 Then pull out the 
power cord 
 
Note: When 
removing the power 
cord, make marks for 
different color power 
cords and 
corresponding wiring 
terminals for wrong 
terminal. 

 Weld suction pipe 
and discharge pipe of 
compressor 
 then pull out the 
connection pipe from 
the compressor 
Note: During welding 
process, do not let 
the flame burn out 
other parts. 

Twist off the nuts for 
compressor with 
wrench 

128 

Sayfa 132

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of compressor 
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the 

power is disconnected. 
Process 
Photo 
Operation Instruction 

4. Remove the 
compressor from 
chassis 

5. Fix the new 
compressor at the 
chassis 

6. Connect suction 
pipe and 
discharge pipe of 
copressor and 
pipeline of system 
again 

 Take out the 
compressor and 
replace it 
Note: When replacing 
the compressor, do 
not damage nearby 
pipelines and other 
parts 

After replacing the 
compresor, fix the 
nuts at the bottom of 
compressor 

Weld the connection 
pipe of compressor, 
connect the pipeline 
and compressor 
Note: During welding 
process, do not let 
flame burn out other 
parts 

129 

Sayfa 133

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of compressor 
Remark: Before removing the compressor, please make sure that there’s no refrigerant inside the pipeline and the 

power is disconnected. 
Process 
Photo 
Operation Instruction 

7. Connect the 
power cord of 
compressor well 

8. Check and 
open the upper 
cover plate 

Removal operation for 4-way valve 
Remark: Before removing the 4-way valve, please make sure that there’s no refrigerant inside the pipeline of system 

and then power is disconnected. 
Process 
Photo 
Operation Instruction 

1.Disconnect 
the coil of 4-way 
valve from the 
4-way valve 

 Loose screws fixing 
the power cord with 
screwdriver 
 conenct the power 
cord well again 
Note: When 
connecting the power 
cord, make marks for 
different color power 
cords and 
corresponding wiring 
terminals. 

Check whether the 
pipeline is connected 
well 
Check whetehr all 
parts and connection 
wires are connected 
well 
If there’s no problem 
after checking, install 
front and rear cover 
plates. 
 

Remove the coil of 
4-way valve at first 

130 

Sayfa 134

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for 4-way valve 
Remark: Before removing the 4-way valve, please make sure that there’s no refrigerant inside the pipeline of system 

and then power is disconnected. 
Process 
Photo 
Operation Instruction 

2.Disconnect 
the 4-way valve 
and connection 
pipeline 

3. Replace 
4-way valve 

4. Replace 
4-way valve 

 Weld those 4 
connection spots on 
4-way valve, and 
then pull out the 
connection pipe 
Note: During welding 
process, do not let 
the flae burn out 
other parts 

 Replace 4-way 
valve 
Note: During welding 
process, do not let 
the flame burn out 
other parts 

 Weld the connection 
position between 
4-way valve and 
pipeline 
Note: During welding 
process, do not let 
flame burn out other 
parts 

131 

Sayfa 135

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Remival operation for eletronic expansion valve 
Remark: Before removing the electronic expansion valve, please make sure that there’s no refrigerant in th pipeline of 

system and the power is disconnected 
Process 
Photo 
Operation Instruction 

1. Disconnec 
the electronic 
expansion valve 
from the 
pipeline 

2. Take out the 
electronic 
expansion valve 
and replace it 

3. Replace 
electronic 
expansion valve 

 Remove the coil of 
electroc expansion 
valve at first 
 Weld the connection 
pipe for expansion 
valve, and then pull 
out the connection 
pipe 
Note: During 
welding process, do 
not let flame burn out 
other parts 

Take out the 
electronic expansion 
valve and replace it 

 Weld the connection 
pipe of electronic 
expansion valve 
 Inistall the coil of 
electronic expansion 
valve 
Note; During 
welding process, do 
not let the flame burn 
out other parts 

132 

Sayfa 136

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation of gas liquid separator 
Remark: Before removing the gas liquid separator, please make sure that there’s no refrigerant inside the pipeline of 

system and disconnect the power 
Process 
Photo 
Operation Instruction 

1.Disconnect  
inlet pipe and 
exit pipe of gas 
liquid separator 
 

2. Replace gas 
liquid separator 

3.  Replace 
gas liquid 
separator 

 Weld those two 
connection spots on 
the gas liquid 
separator and then 
pull out the 
connection pipe 
Note: During welding 
process, do not let 
flame burn out other 
parts 

 Loose 4 screws with 
screwdriver 
 Replace gas lliquid 
separator 

 Weld the pipe 
connected with gas 
liquid separator 
 Fix the screws at the 
base of gas liquid 
separator well again 
Note: During welding 
process, do not let 
flame burn out other 
parts 

133 

Sayfa 137

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for plate heat exchanger 
Remark: Before removing the plate heat exchanger, please make sure that there’s no refrigerant inside the pipeline of 

system and disconnect the power 
Process 
Photo 
Operation Instruction 

1. Twist off two 
nuts fixing the 
plate heat 
exchanger with 
wrench 

2.Disconnect 
inlet pipe and 
outlet pipe of 
plate heat 
exchanger 

3. Replace plate 
heat exchanger 

Twist off two nuts 
fixing the plate heat 
exchanger with 
wrench 
 

 Weld those 4 
connection spots on 
the plate heat 
exchanger, and then 
pull out the 
connection pipe. 
Note: During welding 
process, do not let 
flame burn out other 
parts 
 

Replace plate heat 
exchanger 

134 

Sayfa 138

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Removal operation for plate heat exchanger 
Remark: Before removing the plate heat exchanger, please make sure that there’s no refrigerant inside the pipeline of 

system and disconnect the power 
Process 
Photo 
Operation Instruction 

4. Replace gas 
liquid separator 

5 Common Maintenance  

5.1 Vacuum drying for the system 

5.1.1 Selection requirement for the vaccum pump 

Do not use different vacuum pump for vaccum-pumping for different refrigerant system; 

The final vacuum for the vacuum pump should reach -0.1Mpa; 

The air discharge volume for the vacuum pump should reach 4L/S above; 

The precision of vacuum pup should reach 0.02mmHg above; 

The system vacuum pump for R410A must be with check valve.  

5.1.2 Operation procedure and notices for Vacuum drying 

(1) 1Operation procedure  

a) Before vacuum-pumping, please confirm that the cut-off valve for gas pipe and liquid pipe is 

at off status;  

b) Use charging conduct pipe to connect the governing value and vacuum heat pump to the 

detection joint of gas valve and liquid valve;  

c) After vacuum-pumping for 4h, check whether the vacuum degree is reached to -0.1MPa or 

above; If not, there may be gas leakage. Please perform the leakage inspection again. If 

there’s no gas leakage, please vacuum pump for another 2h.  

d) If the required vaccum degree can’t be satisfied after vacuum-pumping for two times, there 

are water inside the pipeline. Please drain out the water by the method of vaccum damage. 

The detailed method: charge 0.05MPa nitrogen into the pipeline, vacuum pump for 2h and 

then keep the cacuum for 1h. If -0.1 MPa vaccum degree still can’t be reached, repeat this 

operation unitl the water is drained out completely.  
(2) After the vacuum pump is finished, turn off the valve of governing valve and stop vacuum pump 

and keep it for 1h. Please confirm that the pressure of governing valve hasn’t been increased.  

 Weld the pipe 
connected with plate 
heat exchanger 
Note: During welding 
process, do not let 
flame burn out other 
parts 
 

135 

Sayfa 139

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

a) Vacuum pump for the gas pipe and liquid valve at the same time;  

b) When turn off the vacuum pump to stop vacuum-pumping, please turn off the valve at first 

and then de-energize the vacuum pump;  

c) Keep the vacuum pump for 2h and confirm that the pressure of vacuum meter hasn’t been 

increased.   
6 Exploded View of Unit and Parts’ List 

Exploed view for outdoor unit and parts’ list  

(1) Model: GMV-24WL/C-T(U)、GMV-28WL/C-T(U) 

  Exploded view 

1

2

3

61
60
59
58
57
56
63
66
64 65

62

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24
25 26 27 28 29 30 31 32 33 34 35 36
43 44
41
42
46
45

39 40
37 38

136 

55

54

53

52

51

50

49

48

47

22

Sayfa 140

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

Parts list  

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

NO. 
Name of Part 

Product Code 
CN850W0740

 
Product Code 
CN850W0750 

1 
Compressor and 

Fittings 
'00900100019501 
1 
'00900100019501 
1 

2 
Compressor Overload 

Protector(External) 
'00180030 
1 
'00180030 
1 

3 
Compressor Overload 

Protector(External) 
'00183032 
1 
'00183032 
1 

4 
Compressor Overload 

Protector(External) 
'00183031 
1 
'00183031 
1 

5 
Compressor Gasket 
'009012000004 
3 
'009012000004 
3 

6 
Chassis Sub-assy 
'017000000148P 
1 
'017000000148P 
1 

7 
Chassis 
'01284100101 
1 
'01284100101 
1 

8 
Electrical Heater 
'765100047 
1 
'765100047 
1 

9 
Electric 
Heater(Compressor) 
'7651873215 
1 
'7651873215 
1 

10 
Condenser Assy 
'011002060314 
1 
'011002060314 
1 

11 
Sensor Insert 
'42020063 
1 
'42020063 
1 

12 
Cable Cross Loop 
'76510021 
1 
'76510021 
1 

13 
Silencer 
'07444105 
1 
'07444105 
1 

14 
Pressure Protect 

Switch 
'46020006 
1 
'46020006 
1 

15 
Strainer 
'07415200002 
1 
'07415200002 
1 

16 
Sensor Insert 
'42020063 
1 
'42020063 
1 

17 
Gas-liquid Separator 
'07422809 
1 
'07422809 
1 

18 
Nozzle for Adding 

Freon 
'06120012 
1 
'06120012 
1 

19 
Temp Sensor Sleeving 
'05212423 
1 
'05212423 
1 

20 
Joint 
'06652200001 
1 
'06652200001 
1 

21 
fusible plug 
'06332200001 
1 
'06332200001 
1 

22 
Sensor Insert 
'42020063 
1 
'42020063 
1 

23 
Pressure Sensor 
'322101002 
1 
'322101002 
1 

24 
Plate-type Heat 
Exchanger Assy 
'00904100017 
1 
'00904100017 
1 

25 
Nut with Washer 
'70310012 
2 
'70310012 
2 

26 
Plate-type Heat 
Exchanger Assy 
'007023000006 
1 
'007023000006 
1 

27 
Electronic Expansion 

Valve 
'07334390 
1 
'07334390 
1 

28 
Discharge Charge 

Valve 
'07133771 
1 
'07133771 
1 

29 
Plate-type Heat 

Exchanger 
'00904100003 
1 
'00904100003 
1 

30 
Temp Sensor Sleeving 
'05212423 
1 
'05212423 
1 

31 
Current Divider 
'07223431 
1 
'07223431 
1 

32 
Electronic Expansion 

Valve 
'07334447 
1 
'07334447 
1 

33 
Sensor Insert 
'42020063 
1 
'42020063 
1 

34 
Electric Expand Valve 

Fitting 
'4304413205 
1 
'4304413205 
1 

35 
Electric Expand Valve 

Fitting 
'4304413220 
1 
'4304413220 
1 

137 

Sayfa 141

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

NO. 
Name of Part 

Product Code 
CN850W0740

 
Product Code 
CN850W0750 

36 
Connection pipe 

sub-assy 
'05024100604 
1 
'05024100604 
1 

37 
Nozzle for Adding 

Freon 
'06120014 
1 
'06120014 
1 

38 
Pressure Sensor 
'322101032 
1 
'322101032 
1 

39 
Valve Support Assy 
'01804100306 
1 
'01804100306 
1 

40 
Cut-off valve 
sub-assy(small valve) 
'07334100042 
1 
'07334100042 
1 

41 
Cut off Valve 
'07130209 
1 
'07130209 
1 

42 
Strainer 
'07212001 
1 
'07212001 
1 

43 
Cut-off valve 
sub-assy(big valve) 
'07334100044 
1 
'07334100044 
1 

44 
Cut off Valve 
'07334100016 
1 
'07334100016 
1 

45 
Bidirection Strainer 
'07210044 
1 
'07210044 
1 

46 
4-Way Valve Assy 
'030152000272 
1 
'030152000272 
1 

47 
4-way Valve 
'4300008201 
1 
'4300008201 
1 

48 
Temp Sensor Sleeving 
'05212423 
3 
'05212423 
3 

49 
Sensor Insert 
'42020063 
3 
'42020063 
3 

50 
Magnet Coil 
(electromagnetic valve) 
'4304410018903 
1 
'4304410018903 
1 

51 
Capillary sub-assy 
'030006000255 
1 
'030006000255 
1 

52 
Electromagnetic Valve 
'43000054 
1 
'43000054 
1 

53 
Magnet Coil 
(electromagnetic valve) 
'4304410018901 
1 
'4304410018901 
1 

54 
Motor Support 

Sub-Assy 
'01804100309 
1 
'01804100309 
1 

55 
Brushless DC Motor 
'1570280000401 
1 
'1570280000401 
1 

56 
Axial Flow Fan 
'10434100005 
1 
'10434100005 
1 

57 
Left Side Plate 
'01314100043P 
1 
'01314100043P 
1 

58 
Left Side Plate 
'01314100043 
1 
'01314100043 
1 

59 
Right Side Plate 

Sub-Assy 
'01314100109 
1 
'01314100109 
1 

60 
Right Side Plate 
'01314100046P 
1 
'01314100046P 
1 

61 
Gland Bush 
'26904100134 
2 
'26904100134 
2 

62 
Wire conduit 
'26904100132 
2 
'26904100132 
2 

63 
Electric Box Assy 
'100002062449 
1 
'100002062449 
1 

64 
Bolt 
'70210051 
1 
'70210051 
1 

65 
Radiator 
'430034000014 
1 
'430034000014 
1 

66 
Main Board 
'300027000235 
1 
'300027000235 
1 

67 
Relay 
'44020444 
1 
'44020444 
1 

68 
Main Board 
'300027000570 
1 
'300027000570 
1 

69 
XY capacitor 
'33020201 
2 
'33020201 
2 

70 
Fuse 
'46010055 
1 
'46010055 
1 

71 
Terminal Board 
'422000000015 
1 
'422000000015 
1 

72 
Terminal Board 
'422000060004 
1 
'422000060004 
1 

73 
Insulation GasketC 
'70410523 
1 
'70410523 
1 

74 
Wire Clamp 
'71010102 
1 
'71010102 
1 

75 
Wire Clamp 
'71010103 
1 
'71010103 
1 

76 
Magnetic Ring 
'49010118 
3 
'49010118 
3 

138 

Sayfa 142

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

NO. 
Name of Part 

Product Code 
CN850W0740

 
Product Code 
CN850W0750 

77 
Cable Cross Loop 
'26900000008 
1 
'26900000008 
1 

78 
Pass Wire Ring 

Sub-assy 
'76614102 
1 
'76614102 
1 

79 
Cable Cross Loop 
'76512008 
1 
'76512008 
1 

80 
Filter Sub-Assy 
'111001000086 
1 
'111001000086 
1 

81 
Jumper 
'4202021905 
1 
'4202021905 
1 

82 
Electric Box Cover 
'012077060106 
1 
'012077060106 
1 

83 
Cabinet 
'01514100007P 
1 
'01514100007P 
1 

84 
Cabinet 
'01514100007 
1 
'01514100007 
1 

85 
Diversion Circle 
'10474100003 
1 
'10474100003 
1 

86 
Front Grill 
'01572800003 
1 
'01572800003 
1 

87 
Rear Side Plate 
'01314100045P 
1 
'01314100045P 
1 

88 
Handle 
'26235253 
1 
'26235253 
1 

89 
Front Side Plate 
'01314100044P 
1 
'01314100044P 
1 

90 
Front Side Plate 
'01314100044 
1 
'01314100044 
1 

91 
Handle 
'26235253 
1 
'26235253 
1 

92 
Coping 
'01264100027P 
1 
'01264100027P 
1 

93 
Rear Grill 
'01574100010 
1 
'01574100010 
1 

94 
Sensor Sub-assy 
'39008000060G 
1 
'39008000060G 
1 

95 
Temperature Sensor 

Support 
'26905202 
1 
'26905202 
1 

96 
Heat Insulator 
'12128748 
13 
'12128748 
13 

97 
"Pipe Connection Nut 

(""D"" shape) " 
'06320004 
2 
'06320004 
2 

98 
Corrugated Pipe 
'05015408 
1 
'05015408 
1 

99 
Drainage hole Cap 
'06813401 
3 
'06813401 
3 

100 
Drainage Joint 
'06123401 
1 
'06123401 
1 
 

139 

Sayfa 143

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(2) Model: GMV-36WL/A-T(U)、GMV-48WL/A-T(U) 、GMV-60WL/A-T(U) 

  Exploded view 

Parts list  

NO. 
Name of Part 

1 
Coping 
01264100008P 
1 
01264100047P 
1 

2 
Inductance Assy 
01394100050 
1 
/ 
/ 

3 
Inductance 
43120122 
1 
43128000015 
1 

4 
Electric Box Assy 
01394100427 
1 
100002000013 
1 

5 
Main Board 
30228000005 
1 
30221000029 
1 

6 
Radiator 
49018000013 
1 
49018000097 
1 

7 
Filter Board 
30228000006 
1 
30228000006 
1 

8 
Main Board 
30226000045 
1 
30226000045_KZ0
016 
1 

9 
Terminal Board 
42018000026 
1 
42018000026 
1 

10 
Terminal Board 
420111453 
1 
420111453 
1 

GMV-36WL/A-T(U)/ 

GMV-48WL/A-T(U) 
GMV-60WL/A-T(U) 

Product Code 
CN850W0230/ 

CN850W0220 
Product Code 
CN850W0270 

49018000098 
1 

140 

Sayfa 144

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-36WL/A-T(U)/ 

GMV-48WL/A-T(U) 
GMV-60WL/A-T(U) 

NO. 
Name of Part 

Product Code 
CN850W0230/ 

CN850W0220 
Product Code 
CN850W0270 

11 
Left Side Plate 
01314100013P 
1 
01314100084 
1 

12 
Clapboard 
01244100005 
1 
01244100029 
1 

13 
Fan Motor 
15704115 
1 
1570280206 
1 

14 
Sensor Sub-Assy 
39008000061G 
1 
39008000061G 
1 

15 
Fan Motor 
1570411501 
1 
1570280201 
1 

16 
Front Grill 
01574100009 
2 
01572800003 
2 

17 
Cabinet 
01514100002P 
1 
01514100013P 
1 

18 
Front Side Plate 
01314100012P 
1 
01314100082P 
1 

19 
Handle 
26235253 
1 
26904100016 
1 

20 
Front Connection Board 
01344100002P 
1 
01314100082P 
1 

21 
Diversion Circle 
10474100001 
2 
10474100003 
2 

22 
Axial Flow Fan 
 1043410000301 
2 
10434100006 
2 

23 
Chassis Assy 
01194100061 
1 
209058000001 
1 

24 
Motor Support 

Sub-Assy 
01805200260 
1 
017012000006 
1 

25 
Pressure Protect 

Switch 
4602000902 
1 
4602000902 
1 

26 
Discharge Tube 

Sub-Assy 
04534100057 
1 
030013000052 
1 

27 
Silencer 
07444105 
1 
/ 
 

28 
Oil Separator 
07424105 
1 
07424105 
1 

29 
Compressor and 

Fittings 
0020410000102 
1 
00209400005 
1 

30 
Electrical 
Heater(Compressor) 
765152128 
1 
765152128 
1 

31 
Cut off Valve 
07330000002 
1 
07334100011 
1 

32 
Strainer 
07212001 
1 
0721200102 
1 

33 
Gas-liquid Separator 
07424100014 
1 
07424140 
1 

34 
Electrical Heater 
765100047 
1 
765100047 
1 

35 
Capillary Sub-Assy 
 04004100023 
1 
030006000087 
1 

36 
Strainer 
07415200002 
2 
07415200002 
3 

37 
Electromagnetic Valve 
43000054 
1 
43000054 
1 

38 
Magnet Coil 
4304000417 
1 
4304000416 
1 

39 
Right Connection Board 
01344100003P 
1 
01344100059P 
1 

40 
Rear Side Plate 

Sub-Assy 
01314100011P 
1 
01314100083P 
1 

41 
Sensing Device 
322101002 
1 
322101002 
1 

42 
Sensor (High Pressure) 
322101032 
1 
322101034 
1 

43 
Gas By-pass Sub- Assy 
04534100056 
1 
030082000003 
1 

44 
Cut off Valve 
07330000002 
1 
07334100054 
1 

45 
Plate-type Heat 
Exchanger Assy 
00904100013 
1 
007023000001 
1 

46 
Discharge Charge 
07133771 
1 
07133771 
1 

141 

Sayfa 145

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

GMV-36WL/A-T(U)/ 

GMV-48WL/A-T(U) 
GMV-60WL/A-T(U) 

NO. 
Name of Part 

Product Code 
CN850W0230/ 

CN850W0220 
Product Code 
CN850W0270 

Valve 

47 
Electronic Expansion 

Valve 
07334447 
1 
43044100172 
1 

48 
Electric Expand Valve 

Fitting 
4304413205 
1 
4304413220 
1 

49 
Electronic Expansion 

Valve 
07334390 
1 
43044100173 
1 

50 
Electric Expand Valve 

Fitting 
4304413220 
1 
4304413205 
1 

51 
Low Pressure Survey 

Valve Sub-Assy 
07334100067 
1 
07334100063 
1 

52 
Cut off Valve 
07130239 
1 
07130239 
1 

53 
Strainer 
07212121 
1 
07415200002 
1 

54 
Silencer 
07245012 
1 
/ 
/ 

55 
Connection Pipe 

Sub-Assy 
04064100002 
1 
030072000008 
1 

56 
Strainer 
07210037 
1 
07212403 
1 

57 
One way Valve 
07130118 
1 
/ 
/ 

58 
4-way Valve 
43000338 
1 
43000338 
1 

59 
Magnet Coil 
4300040029 
1 
4300040094 
1 

60 
Magnet Coil 
4304000406 
1 
/ 
/ 

61 
Nozzle for Adding 

Freon 
06120012 
1 
0612001202 
2 

62 
Condenser Assy 
01124100143 
1 
000100000001 
1 

63 
Rear Grill 
01574100004 
1 
01574100011 
1 
 

142 

Sayfa 146

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(3) Model: GMV-36WL/C-T(U)、GMV-48WL/C-T(U)  

  Exploded view 

Parts list  

NO. 
Name of Part 

1 
Front Grill 
01314100013 
1 

2 
Diversion Circle 
06123401 
1 

3 
Cabinet 
390002060018 
1 

4 
Handle 
765152128 
1 

5 
Front Side Plate 
765100047 
1 

6 
7 
Axial Flow Fan 
Brushless DC Motor 

8 
Brushless DC Motor 
01264100008 
1 

9 
Chassis 
100002068219 
1 

10 
Oil Separator 
300027060121 
1 

11 
Strainer 
300027060346 
1 

12 
Compressor and Fittings 
42200000001501 
1 

13 
Compressor Gasket 
422000060004 
1 

14 
Pressure Sensor 
300020000003 
1 

GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 

Product Code 
CN850W1070 
CN850W1080 

43120122 
1 

01394100545 
1 

143 

Sayfa 147

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

NO. 
Name of Part 

15 
Drainage hole Cap 
4304000492 
1 

16 
Pressure Protect Switch 
4300040094 
1 

17 
Electromagnetic Valve 
4304413205 
1 

18 
Pressure Sensor 
4304413220 
1 

19 
Electronic Expansion Valve 
05015408 
1 

20 
Discharge Charge Valve 
01574100004 
1 

21 
Plate-type Heat Exchanger Assy 
01100206067601 
1 

22 
Electronic Expansion Valve 
0721212101 
1 

23 
Strainer 
07225016 
1 

24 
Cut off Valve 3/8 
43000338 
1 

25 
Rear Side Plate 
07224803 
1 

26 
Cut off Valve 
07334100016 
1 

27 
Filter 
01314100014 
1 

28 
4-way Valve 
07130209 
1 

29 
Gas-liquid Separator 
07212001 
1 

30 
Strainer 
07334447 
1 

31 
Condenser Assy 
007023000004 
1 

32 
Rear Grill 
071015000002 
1 

33 
Corrugated Pipe 
43044100173 
1 

34 
Electric Expand Valve Fitting 
430044000016 
1 

35 
Electric Expand Valve Fitting 
43000054 
1 

36 
4 Way Valve Coil 
4602000902 
1 

37 
Magnet Coil 
06813401 
3 

38 
Filter Board 
43004400001501 
1 

39 
Terminal Board 
009012000013 
3 

40 
Terminal Board 
009001060077 
1 

41 
Main Board 
07225088 
2 

42 
Main Board 
07424105 
1 

43 
Electric Box Assy 
01284100149 
1 

44 
Coping 
1570410001306 
1 

45 
Inductance Box Assy 
1570410001305 
1 

46 
Inductance 
1043410000301 
2 

47 
Electrical Heater 
01314100012 
1 

48 
Electrical Heater 
2690410001603 
2 

49 
Sensor Sub-assy 
01514100002 
1 

50 
Drainage Joint 
10474100001 
2 

51 
Left Side Plate 
016004060002 
2 
 

GMV-36WL/C-T(U) 
GMV-48WL/C-T(U) 

Product Code 
CN850W1070 
CN850W1080 

144 

Sayfa 148

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

(4) Model: GMV-60WL/C-T(U)  

  Exploded view 

Parts list  

NO. 
Name of Part 

1 
Coping               
4304413220 
1 

2 
Electric Box Assy           
4304000453 
1 

3 
PFC Inductance           
4300040094 
1 

4 
Filter Board             
4304413205 
1 

5 
Drive Board             
26113009 
1 

6 
Main Board              
39008000061G 
1 

7 
Terminal Board            
765152128 
1 

8 
Terminal Board            
765100047 
1 

9 
Left Side Plate            
01574100011 
1 

10 
Brushless DC Motor          
07212403 
1 

11 
Pressure Sensor           
4602000902 
1 

12 
Gas-liquid Separator         
07424105 
1 

13 
Nozzle for Adding Freon        
010002000003 
1 

14 
Strainer               
322101034 
1 

15 
Axial Flow Fan            
43044100173 
1 

GMV-60WL/C-T(U) 

Product Code 
CN850W1090 

145 

Sayfa 149

GREE                                     DC Inverter Side Discharge VRF Ⅱ for North America 

NO. 
Name of Part 

16 
Front Grill              
07133771 
1 

17 
Diversion Circle            
01314100083 
1 

18 
Handle               
00904100005 
1 

19 
Front Side Plate           
0721200102 
1 

20 
Cabinet               
43044100172 
1 

21 
Brushless DC Motor          
035222000004 
1 

22 
Chassis Sub-assy           
030072060154 
1 

23 
Electromagnetic Valve         
07212402 
1 

24 
Cut off Valve             
07334100054 
1 

25 
Cut-off valve             
76715005 
3 

26 
Strainer               
00209400005 
1 

27 
Compressor and Fittings        
07415200002 
1 

28 
Drainage hole Cap          
07130239 
1 

29 
Cut off valve             
07334100011 
1 

30 
Strainer               
43003091 
1 

31 
4-Way Valve Sub-Assy         
017000000005 
1 

32 
fusible plug              
15010406001302 
1 

33 
Electronic Expansion Valve       
01514100013 
1 

34 
Strainer               
01314100082 
1 

35 
Plate-type Heat Exchanger       
2690410001603 
1 

36 
Rear Side Plate            
10474100003 
2 

37 
Discharge Charge Valve        
01572800003 
2 

38 
Electronic Expansion Valve       
10434100006 
2 

39 
Pressure Sensor           
0721650101 
1 

40 
Condenser Sub-Assy         
0612001202 
1 

41 
Oil Separator             
07424140 
1 

42 
Pressure Protect Switch        
322101002 
1 

43 
Strainer               
150104060013 
1 

44 
Rear Grill              
01314100084P 
1 

45 
Electrical Heater           
422000060004 
1 

46 
Electrical Heater           
42200006000304 
1 

47 
Sensor Sub-assy           
300027060346 
1 

48 
Drainage Joint            
300078060095 
1 

49 
Electric Expand Valve Fitting      
300020000003 
1 

50 
4 Way Valve Coil           
43128000015 
1 

51 
Magnet Coil             
100002068220 
1 

52 
Electric Expand Valve Fitting      
01264100047P 
1 

GMV-60WL/C-T(U) 

Product Code 
CN850W1090 

146 

Sayfa 150