DC INVERTER MULTI VRF SYSTEM

 TECHNICAL SALES GUIDE

BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITION

TTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONER

(GC201804)

TECHNICAL SALES GUIDE-60Hz

CAPACITY RANGE:24~60kBtu/h

SUPER HIGH AMBIENT OPERATION TO 118 ℉

GREE ELECTRIC APPLIANCES INC.OF ZHUHAI

Sayfa 2

CONTENTS

1 OUTLINE OF MULTI VRF..............................................................3

2 SUMMARY OF SYSTEM EQUIPMENTS......................................6

3 CONTROLLER..............................................................................9

4 BASIC SYSTEM CONFIGURATION...........................................10

5 EQUIPMENT SELECTION PROCEDURE..................................11

6 REFRIGERANT PIPING DESIGN................................................16

7 WIRING DESIGN........................................................................19

8 ACCESSORIES..........................................................................21

9 TECHNICAL SPECIFICATIONS..................................................22

10 FAN CHARACTERISTICS.........................................................27

11 DIMENSIONAL DRAWINGS.....................................................29

2

Sayfa 3

Dc Inverter Multi VRF System Technical Sales Guide

OUTLINE OF MULTI VRF
1

1.1 Product List

GMV-24WL/C-T(U)

GMV-28WL/C-T(U)

Model

GMV-36WL/A-T(U)

GMV-48WL/A-T(U)

GMV-60WL/A-T(U)
1.2  Product Features

1.2.1 Summary of Features
GMV5 mini DC Inverter Multi VRF System is the new generation of DC inverter multi VRF system that 
Gree developed independently. It is a single refrigeration system that made up of one air cooled 
outdoor unit connected with several direct evaporative indoor units of identical or different series or 
capacity. It provides processed air directly to an area or several areas, which is mainly applicable for 
household or light commercial facilities. This product is endowed with the features of high efficiency, 
high anti-interference ability, long connection pipe, wide operation range, good acoustic, intelligent 
capacity adjustment, all-around protection.
1.2.2  Introduction of Features
(1) High Efficiency
The system adopts all DC motor, which greatly improves efficiency. The energy efficiency for Gree all 
DC unit is increased greatly. SEER is up to 16; HSPF of GMV-24WL/C-T(U)、GMV-28WL/C-T(U)、GMV-
36WL/A-T(U) and GMV-48WL/A-T(U) is up to 9; HSPF of GMV-60WL/A-T(U) is up to 8.2.
(2) Latest CAN Bus Communication
The latest communication way-CAN bus communication is adopted, which greatly improves anti-
interference ability, precisely controls the indoor units and improves the reliability of system. Meanwhile, 
specialized shielded wire is not longer needed, while conventional communication wire can be used to 
increase the flexibility of project installation.

High anti-interference 

ability

(3) Long Connection Pipe and Big Height Difference
The max length of connection reaches 300m(984ft)(total length). The connection pipe between indoor 
unit and outdoor unit can be as long as 120m(394ft). Project installation condition is wider while the 
limitation of installation distance is smaller. Branching joint and branching manifold can also be used.
The max allowable height difference between indoor unit and outdoor unit is 50m(164ft) and that 
between indoor unit and indoor unit is 15m(49ft).
(4) Wide Operation Range
The system can operate constantly and reliably in a wide temperature range(cooling: 
-5~48

OF), heating: -20~27

OF)), which is not affected by atrocious environment.

OC(23~118

OC(-4~81

3

Sayfa 4

 GMV5 Mini DC Inverter Multi VRF

Last generation

Cooling:10~48

C

Cooling:-5~48 C

-20~27 C
50~118 F
Heatin :

-20~27 C
23~118 F
Heatin :

-4~81 F

-4~81 F

(5) Good Acoustic
A series of optimized measures are taken to solve the problem of indoor unit’s throttling sound, indoor 
unit’s oil return noise, gas bypass noise during start-up, which improves the comfort of system.

70

60

Noise classification 
refers to “Urban 
Environmental Noise 
Standard”

50

40

45db(A) The noise of

GMV Star DC 
Inverter Multi VRF is 
as low as 45db(A)

30

20

(6) PID Intelligent Capacity Adjustment
The system applies the original technology of PID intelligent capacity adjustment, which quickly and 
precisely controls indoor ambient temperature according to set temperature, with small temperature 
fluctuation and great comfort.

Temperature fluctuation the foom 

GMV System

Non VRF

33 F

(7) Intelligent Control
1) Advanced DC inverter technology
① High-efficient magnetic reluctance inverter compressor: High-efficient magnetic reluctance 

compressor is adopted to take advantage of the magnetic reluctance torque of compressor. Under 
the same output capacity, the efficiency can be improved by 5%.
② Advanced torque control technology: minimum current and maximum torque control technology 

adopts the most optimized control principle to realize maximum torque output with minimum current 
and reduce loss of motor winding and intelligent power module for higher energy efficiency.
③ Closed-loop start-up technology of compressor: Self-innovative closed-loop start-up control is applied 

to enable output torque follow with load torque, whose start-up current is small and start-up is more 
reliable.
④ High-efficient numerical PFC control: High-efficient PFC control technology is applied to improve 

efficiency by approx. 1% compared with traditional PFC; for an air condition with rated power of 

4

Sayfa 5

Dc Inverter Multi VRF System Technical Sales Guide

5KW, 50W can be saved per hour and 1.2kWh electricity can be saved per day.
⑤ 180º sine wave DC variable speed technology: 180º current output waveform is smooth sine 

wave with small harmonic wave content, small torque pulsation, wide adjustable range and stable 
operation of motor, which can satisfy the temperature requirement in various occasion, save electricity 
greatly and ensure user’s comfort in maximum.
2) Beautiful humanized controller design
① 24h timer on or timer off can be preset (countdown timer and clock timer);Detect ambient emperature 

precisely; 7 kinds of fan speed can be set;
② Auto, cool, dry, fan or heat mode can be set;
③ Master wired controller and sub-master wired controller can be set; several indoor units can be 

controlled simultaneously; 
④ Various functions can be set: sleep, ventilation, quiet (auto quiet), light, absence, energy-saving, 

clean, e-heater, x-fan, memory, etc.
3) High anti-interference ability
   The latest communication way-CAN bus communication(non-polar communication) is adopted, 

which greatly improves anti-interference ability. Specialized shielded wire is not longer needed for 
communication wire between units, while conventional communication wire can be used to increase 
the flexibility of project installation.
4) Intelligent temperature control technology and intelligent defrosting mode are adopted
   The system is with strong quick cooling/heating function, which can increase indoor temperature 

rapidly to set temperature and perform defrosting according to frosting situation.
(8) Independent remote control, wired control, zone control, centralized control, long-distance 
monitoring and weekly timer control of indoor units are available.

5

Sayfa 6

SUMMARY OF SYSTEM EQUIPMENTS
2

2.1 Outdoor Unit

Model
Code
Ref.
Power
Supply
Appearance

GMV-24WL/C-T(U)
CN850W0740
R410A

GMV-28WL/C-T(U)
CN850W0750
R410A

GMV-36WL/A-T(U)
CN850W0230  
R410A

GMV-48WL/A-T(U)
CN850W0220 
R410A

GMV-60WL/A-T(U)
CN850W0270
R410A

2.1.1 Nomenclature

GMV
□
-
□
□
□
□
W
□
/
□
□
□

1
2
3
4
5
6
7
8
9
10

No.
Description
 Options

1
Product code
GMV-Gree Multi VRF Units

2
Suitable climate
Blank-T1 condition; T2-low temperature climate; 
T3-high temperature climate

3
Unit type
DC Inverter (omit)

4
Function code
Q—Heat Recovery; S—Water Heater; W—Water-cooled Unit; X—Fresh Air Unit
Leave blank if above functions are unavailable. 

5
Code of cooling 

capacity
 Nominal capacity/1000(Btu/h)

6
Unit structure
M—Modular (top discharge); L—Non-modular (side discharge); blank—Non-modular (top 
discharge)

7
 Refrigerant
R410A (omit)

8
 Design No.
Named in order of A, B, C, or combined with 1, 2, 3…

9
 Power supply
24000~61000Btu/h, 1 phase—omit; 3 phase—S 

6

208/230V
~
60Hz

208/230V
~
60Hz

208/230V
~
60Hz

208/230V
~
60Hz

208/230V
~
60Hz

Sayfa 7

Dc Inverter Multi VRF System Technical Sales Guide

2.1.2 Rated Conditions

Indoor side inlet air status
Outdoor side inlet air status

Dry bulb temperature
Wet bulb temperature
Dry bulb temperature
Wet bulb temperaturea

℃
℉
℃
℉
℃
℉
℃
℉

Cooling 
26.7
80.0
19.4
67.0
35.0
95.0
23.9
75.0

Heating
21.1
70.0
15.6
60.0
8.3
47
6.1
43

2.1.3 Branching joints

Model name
Usage
Appearance

GMV-24WL/C-T(U)

Y-shape 
branching joint

GMV-28WL/C-T(U)

 to other branching
 joint or indoor unit

Y-shape 
branching 

 Inlet

GMV-36WL/A-T(U)

FQ01A/A

 pipes used in the field 

joint

ODU

GMV-48WL/A-T(U)

GMV-60WL/A-T(U)

2.2 Indoor Unit

Cooling Capacity
Heating Capacity

Type
Appearance
Model Name

kW
Btu/h
kW
Btu/h

GMV-ND07PLS/A-T(U)
2.2
7500
2.5
8500

GMV-ND09PLS/A-T(U)
2.8
9500
3.1
10500

Duct 

GMV-ND12PLS/A-T(U)
3.5
12000
4.0
13500

type 
indoor 

GMV-ND14PLS/A-T(U)
4.0
13800
4.5
15500

unit

GMV-ND18PLS/A-T(U)
5.3
18000
5.9
20000

GMV-ND22PLS/A-T(U)
6.3
  22000
7.1
24000

7

Sayfa 8

Cooling Capacity
Heating Capacity

Type
Appearance
Model Name

kW
Btu/h
kW
Btu/h

GMV-ND07T/A-T(U)
2.2
7500
2.5
8500

GMV-ND09T/A-T(U)
2.8
9500
3.1
10500

GMV-ND12T/A-T(U)
3.5
12000
4.0
13500

GMV-ND15T/A-T(U)
4.4
15000
5
17000

GMV-ND18T/A-T(U)
5.3
18000
5.9
20000

Four-way 

Cassette

GMV-ND24T/A-T(U)
7.0
24000
7.9
27000

GMV-ND30T/A-T(U)
8.8
30000
10
34000

GMV-ND36T/A-T(U)
10.6
36000
11.7
40000

GMV-ND42T/A-T(U)
12.3
42000
13.8
47000

GMV-ND48T/A-T(U)
14.1
48000
15.8
54000

Cooling Capacity
Heating Capacity

Type
Appearance
Model Name

kW
Btu/h
kW
Btu/h

GMV-N07G/A3A-D(U)
2.2
7500
2.5
8500

GMV-N09G/A3A-D(U)
2.8
9500
3.2
11000

Wall 
Mounted 

GMV-N12G/A3A-D(U)
3.5
12000
4.0
13500

Type

GMV-N18G/A3A-D(U)
5.2
18000
5.8
20000

GMV-N24G/A3A-D(U)
7.0
24000
7.5
25500

2.2.1 Nomenclature
GMV-
——
 
Power supply

      
    
  
 
Series number

      
    
    
    
          
  
 
With water pump or not

Units series

Cooling capacity

Function code

Motor type
Household or commercial

Code for indoor unit

Code for type

Code for 
multi VRF
-
Code for 
indoor unit
Motor type
Function code
Cooling capacity

R-heat pump
L-cooling only

D-DC 
motor
Default-AC 

X-fresh air
W-dual heat sources

GMV
-
N

Q-heat recovery
Default-electric heating

motor

8

Nominal cooling 
capacity/1000(Btu/

h)

Sayfa 9

Dc Inverter Multi VRF System Technical Sales Guide

Classification
With water pump or 

not
Series number
Power supply

PL-Low static pressure duct type indoor unit; 
P-Standard static pressure duct type indoor; 
PH-High static pressure duct type indoor unit; 
PB-Thin duct type indoor unit; T-Four-way 
cassette; TD-Single-way cassette; TS-Two-way 
cassette; C-Floor mounting unit; ZD-Floor 
ceiling unit; G-Wall-mounted unit

With water pump-S(All 
cassette indoor units 
are with water pump, 
S is not presented in 
the model same)

Select power supply 
code according 
to power supply 
specification

A, B, C… or 1, 2, 3…

Power supply specification
Code
220V ~,60Hz;   208-230V ~,60Hz;  220-240V ~,60HZ;  
208/230V ~,60Hz
D

220V ~,50Hz;     230V ~,50Hz;      220-230V ~,50Hz
E

240V ~,50HZ
J

220-240V ~,50Hz;  230-240V ~,50Hz
K

208-230V ~,60Hz and 220-240V ~,50Hz General
T

CONTROLLER
3

Name
Model 

name
Appearance
Application
Function

1)Elegant appearance and adopts big LCD screen with back 
light;
2) Ten touch buttons to avoid complicated combination buttons, 
which is convenient for operation;
3) Optional modes: Auto, cool, dry, fan, heat mode or floor 
heating, 3D heat supply(heating + floor heating) mode;
4)7 kinds of fan speed;
5) Clock can be displayed and set; 24h preset ON or OFF is 
available (countdown, clock timer function);
6) Dual wired controllers can be equipped. The two wired 
controllers can control the same indoor unit simultaneously. 
Or one wired controller can control several indoor units 
simultaneously;
7)Settable functions: sleep, air, quiet(auto quiet), light, energy 
saving, E-heater, X-fan, memory, low ambient temperature 
drying, heating in absence, controllable drying and E-heater, 
filter cleaning reminding;
8)With project parameter viewing and setting functions, which 
is convenient for project installation and debugging;
9)Adopts dual wire power carrier communication technology, 
which means power supply and communication share the same 
two-core wire. Users can purchase the wire by themselves, 
flexible for project installation and wiring.

Outdoor unit

D1
D2

Wired 
controller
XK42

Indoor unit 1
Indoor unit 2
Indoor unit 16

D1 D2
H1 H2

D1 D2
H1 H2

D1 D2
H1 H2

Besides the common functions, the following functions are also 
available: up&down swing, timer on, timer off, I-feel, sleep and 
8℃ heating operation, etc.

DSP1
DSP2

YAD1F
  
 

Remote 
controller

Besides the common functions, the following functions are also 
available: up&down swing, left&right swing, quiet, timer on, 
timer off, sleep, I-feel, low ambient temperature drying and 8℃ 
heating operation, etc.

DSP1
DSP2

YV1L1

9

Sayfa 10

BASIC SYSTEM CONFIGURATION
4

4.1 System legend(ex.)
Model name of outdoor unit:  GMV-48WL/A-T(U)
Allowed capacity code of indoor unit: Min:24000Btu/h Max: 64800Btu/h.
Note: The total capacity code of indoor units shall be within 50%~135% of the capacity code of selected 
outdoor unit.

ODU

GMV-160WL/A-T  Total capacity code of indoor units is 18+12+9+9=48, so the selected outdoor unit 
is. GMV-48WL/A-T(U).

10

GMV-ND18PLS/A-T(U)

GMV-ND12PLS/A-T(U)

GMV-ND09PLS/A-T(U)

GMV-ND09PLS/A-T(U)

Sayfa 11

Dc Inverter Multi VRF System Technical Sales Guide

EQUIPMENT SELECTION PROCEDURE
5

5.1 Selection flow chart

Calculate the heat load of the room

Correction of indoor unit capacity

Select indoor unit model

Select indoor unit model

Correction of outdoor unit capacity

Select outdoor unit model

5.2 Combination conditions for indoor unit and outdoor unit
1) The capacity code of indoor units = The capacity code of indoor units = total capacity code of 
outdoor unit × (50%~135%).
2)  For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units 
are decided. 

Capacity code of outdoor unit

Model name of 

Max. No. of indoor units
kW
Btu/h

outdoor unit

GMV-24WL/C-T(U)
7.0
24000
 4

GMV-28WL/C-T(U)
8.2
28000
 4

GMV-36WL/A-T(U)
11.0
37500
7

GMV-48WL/A-T(U)
14.1
48000
8

GMV-60WL/A-T(U)
17.6
60000
10

5.3 Cooling/Heating capacity characteristics
(1) Cooling capacity calculation method.
(2) Heating capacity calculation method.
Cooling or heating capacity calculation method:
R410A outdoor unit capacity = outdoor unit capacity in rated condition × correction factor of indoor 
and outdoor temperature condition × connection pipe distance, correction factor of height difference 
between indoor unit and outdoor unit.
① If the total capacity code of indoor units is smaller than the capacity code of outdoor unit, the capacity 

of outdoor unit in rated condition equals to the total capacity code of indoor units;
② If the total capacity code of indoor units is bigger than the capacity code of outdoor unit, the capacity 

11

Sayfa 12

of outdoor unit in rated condition equals to its rated cooling capacity;

③ Correction factor of indoor and outdoor temperature condition.
1)  Correction factor of cooling capacity
 

43(110)

40(104)

(℃/℉)

35(95)

30(86)

25(77)

20(68)

16(61)

14
(57)

16
(61)

18
(64)

20
(68)

22
(72)

24
(75)

26
(79)

         
(℃/℉)
2) Correction factor of heating capacity

26(79)
27(81)

(℃/℉)

24(75)

22(72)

20(68)

18(64)

16(61)

14(57)

12(54)

10(50)-15
(5)

-5
(23)

0
(32)

5
(41)

15
(59)

-10
(14)

10
(50)

         
(℃/℉)

④ Correction factor of connection pipe distance and height differenceّّ

Symbol instruction:
Hp: Height difference (m) between indoor unit and outdoor unit when indoor unit is lower than outdoor 
unit;
Hm: Height difference (m) between indoor unit and outdoor unit when indoor unit is higher than 

12

Sayfa 13

Dc Inverter Multi VRF System Technical Sales Guide

outdoor unit;
L: Single-pass equivalent connection pipe length Lّّ

The following chart is the capacity change rate in 100% load under standard condition (thermostat is set 
in 16℃(61

OF) in cooling and set in 30℃(86

OF) in heating).
 

50

40

30

20

Hp(m)

10
10
20
30

60
40
50
70
80
110
90
1001
20
150
L(m)
1301 40

10

Hm(m)

20

30

40

0.99

0.97

0.95

50

40

30

20

1.0

Hp(m)

10
10
20
30

60
40
50
70
80
110
90
1001
20
150

L(m)
1301 40

10

Hm(m)

20

30

40

Note:

(m)
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150

(ft)
0
33
66
98
131
164
197
230
262
295
328
361
394
427
459
492

(3) Capacity of each indoor unit=Capacity of outdoor unit × Total capacity of indoor units/Total capacity 
of synchronously operating indoor units.
(4) Operating temperature rang.

Temperature range

℃
℉

Cooling
-5~48
23~118

Heating
-20~27
-4~81
5.4 Example of equipment selection
(1) Overview of building model 
a.Temperature condition
b.Outdoor temperature: 35℃(95 ℉) DB; Indoor temperature: 17℃(81 ℉) WB.
c.Load in cooling

Room A
Room B
Room C
Room D

Kw
2.4
3.2
2.4
4.7

Load

Btu/h
8200
10900
8200
16000

(2) Selection Criteria for each floor
Pipe length: 55m; Height difference between indoor unit and outdoor unit: 25m (indoor unit is higher 
than outdoor unit).

13

Sayfa 14

(3) Procedure and result of equipment selection
a.Procedure of equipment selection
Introduce the equipment selection procedure step by step.
b.Equipment selection and capacity check
① Selection of indoor unit.

Select suitable indoor unit according to the corrected load of indoor unit capacity.Corrected load 
of indoor unit capacity=Load/Corrected ratio of cooling capacity related to temperature condition.
Referring to the corrected ratio chart of cooling capacity related to temperature condition, under 
outdoor temperature of 35℃(95 ℉)DB and indoor temperature of 17℃(81 ℉)WB, the 
corrected ratio of cooling capacity is 0.94.
Selection result is as below:

Room A
Room B
Room C
Room D

Corrected 

Kw
2.55
3.40
2.55
5.0

load of 
capacity

Btu/h
8720
11600
8720
17020

Unit size
09
12
09
18

② Selection of outdoor unit

The total capacity code of indoor units is 48. Please select suitable outdoor unit according to the 
total capacity of indoor units and corrected situation.Capacity of outdoor unit=Total capacity of 
indoor units/(Corrected ratio of cooling capacity related to temperature condition × Correction of 
connection pipe length and height difference) .After calculating the capacity of outdoor unit, select 
suitable outdoor unit according to 50%~135% of the capacity of outdoor unit.
In the example, capacity of outdoor unit=48/(0.94×0.95)=54.
Select the outdoor unit with capacity code of 160 and nominal cooling capacity of 14.1Kw(48000Btu/
h).
The capacity code ratio between indoor unit and outdoor unit is 48/48×100%=100%, which is 
within 50%~135% and accords with the equipment selection standard.
③ Correction of outdoor unit capacity

Suppose the combination situation between indoor unit and outdoor unit is as below,GMV-48WL/
A-T(U).
Indoor unit: GMV-ND09PLS/A-T(U)×2, GMV-ND12PLS/A-T(U)×1, GMV-ND18PLS/A-T(U)×1
If the total capacity code of indoor units is bigger than the capacity code of outdoor unit, the capacity 
of outdoor unit in rated condition equals to its rated cooling capacity. So the capacity of outdoor unit 
under rated condition is 14.1Kw(48000Btu/h).
④ Referring to the corrected ratio chart of cooling capacity related to temperature condition, under 

outdoor temperature of 35
℃(95 ℉)DB and indoor temperature of 17
℃(81 ℉)WB, the 
corrected ratio of cooling capacity is 0.94.
⑤ Referring to the corrected ratio of connection pipe of 55m(180ft)long and height difference 

between indoor unit and outdoor unit of 25m(82ft)(outdoor unit is lower than indoor unit), the 
corrected ratio is 0.95.
    Capacity of outdoor unit=48×0.94×0.95=12.59Kw(42.86Btu/h)
⑥ Correction of indoor unit capacity

Capacity of each indoor unit=Capacity of outdoor unit × Total capacity of indoor units/Total capacity 
of synchronously operating indoor units.
GMV-ND09PLS/A-T(U):48×9/48=9kBtu/h
GMV-ND12PLS/A-T(U):48×12/48=12kBtu/h
GMV-ND09PLS/A-T(U):48×18/48=18kBtu/h

14

Sayfa 15

Dc Inverter Multi VRF System Technical Sales Guide

The result is as below:

Air conditioning load
Equipment selection

Indoor air 
conditioning load
Indoor unit
Outdoor unit

Capacity

Floor
RoomNo

Capacity(Btu/h)

Cooling

(Btu/h)
Model

(Btu/h)
Model

Cooling
Cooling

A
8200
GMV-ND09PLS/A-T(U)
9500

GMV-48WL/A-T(U)
48000
B
10900
GMV-ND12PLS/A-T(U)
12000

1

C
8200
GMV-ND09PLS/A-T(U)
9500

D
16000
GMV-ND18PLS/A-T(U)
18000

Piping distance
Capacity correction
Capacity check after correction

Equivalent 

Height

Pipe correction × 

Capacity

Floor
Room 

length

difference

Judgment
m
Ft
m
Ft
kW
Btu/h
kW
Btu/h

temp. correction

No.

A

2.55
8720
The selection 
should accord 
with the standard

85
280
25( ODU 
is lower than 

82m(ODU is 
lower than 

B
3.40
11600

1

12.56
42860

C
2.55
8720

IDU )

IDU)

D
5.00
17020

c.Schematic diagram
Explain the location of units in each room and connection way of indoor unit and outdoor unit with 
single-line chart.

ODU

LS/A-T(U)
IDU

GMV-ND09P

GMV-ND12P

GMV-ND09P

GMV-ND18P

LS/A-T(U)

LS/A-T(U)

LS/A-T(U)

15

Sayfa 16

REFRIGERANT PIPING DESIGN
6

6.1 Warning on refrigerant leakage 

(1) Introduction of leakage detection method
Procedures of leakage detection.Before ex-factory, the cut-off valves of gap pipe and liquid pipe of 
outdoor unit are closed. Please confirm it before installation.Before testing, apply some suitable lubricant 
on the joint of cap and pipe. Use two wrenches when fixing the cap.Connecting outdoor pipeline for 
testing is not allowed during leakage detection. The testing pressure of R410A system is 4.15MPa (for 
R22 system, it is 3.0Mpa). The medium of airproof test must be dry nitrogen. Increase the pressure 
slowly in three steps:
Step one: Slowly increase pressure to 0.5MPa and maintain pressure for 5min. Big leakage may be 
found during leakage detection;
Step two: Slowly increase pressure to 1.5MPa and maintain pressure for 5min. Small leakage may be 
found during airproof test;
Step three: For R410A system, slowly increase pressure to 4.15MPa(for R22 system, it is 3.0Mpa) and 
maintain pressure for 5min. Tiny leakage may be found during strength test. Increase pressure to testing 
pressure and maintain pressure for 24h. Check if the pressure decreases. The test is passed if pressure 
doesn’t decrease.
(2) Introduction of handling method of leakage
Firstly, discharge the refrigerant and then charge nitrogen for leakage welding. The nitrogen charging 
way is the same as that in airproof test. Blow away the impurities and clean the pipeline after finishing 
welding. Finally, rearrange airproof test for leakage detection until there is no leakage.

6.2 Free branching system

ODU

 Gas pipe

Liquid pipe

Connection pipe between outdoor unit and the first branching joint in indoor side

 Branching pipes of indoor units and connection pipes among indoor units

Indoor unit 1

Branching joints
among indoor units

Connection pipes of branching joints among indoor units

Branching pipes of indoor units and connection pipes among indoor units

Indoor unit 2

Connection pipes of branching joints among indoor units

Branching pipes of indoor units and connection pipes among indoor units

Indoor unit 3

Connection pipes of branching joints 
among indoor units

16

Sayfa 17

Dc Inverter Multi VRF System Technical Sales Guide

6.3  Allowable length/height difference of refrigerant piping

ODU
ODU

L1
L1

a

The
The1st
1st
branch
branch
section
section

IDU
IDU

Height
Height difference
differencebetween
betweenI DU
IDUand
and

Equivalent
Equivalent length
length to
to the
thef arthest
farthest
connection
connection
)
Equivalent
Equivalent length
length from
fromthe
the1st
1stb ranch
branch
to
to the
thef arthest
farthestpipe(L<4om/131ft)
pipe(L<4om/131ft)

L2
L2

L3
L3

b
c
d

IDU
IDU

IDU
IDUI
DU
IDU

Each
EachY-type
Y-typebranch
branchequals
equals to
to 0.5m
0.5m(1-5/8ft)
(1-5/8ft) and
ande ach
eachbranch
branchheader
headerequals
equals to
to 1.0m
1.0m(3-1/4ft)
(3-1/4ft).

NOTICE! The equivalent length of one Y shape branching joint is 0.5m(1-5/8ft).

Allowable value

Piping section
M
Ft

Total extension of pipe (Liquid pipe, real length)
250
820
L1+L2+L3+a+b++c+d

Real length
100
328
L1+L2+L3+d
Equivalent length
120
394

Farthest piping length

Pipe
length

Equivalent length of farthest piping from 1st branching
40
131
L2+L3+d

Upper outdoor unit
30
98
——

Height between indoor and 

outdoor units

Lower outdoor unit
30
98
——

Height 
difference

Upper outdoor unit
10
33
——

Height between indoor units

Lower outdoor unit
10
33
——

Height
Height difference
difference

between
between

17

Sayfa 18

6.4 Selection of refrigerant piping
(1) Size of main pipe

Pipe dimension

Model

Gas pipe 
Liquid pipe

mm
inch
mm
inch

GMV-24WL/C-T(U)
Ø15.9
5/8
Ø9.52
3/8

GMV-28WL/C-T(U)
Ø15.9
5/8
Ø9.52
3/8

GMV-36WL/A-T(U)
Ø15.9
5/8
Ø9.52
3/8

GMV-48WL/A-T(U)
Ø15.9
5/8
Ø9.52
3/8

GMV-60WL/A-T(U)
Ø19.05
3/4
Ø9.52
3/8

(2) Pipe size between branching joints

Gas pipe
Liquid pipe

Total capacity of downstream indoor units C (Btu/h)

mm
inch
mm
inch

C ≤19000
Ø12.7
1/2
Ø6.35
1/4

19000 <C ≤48500
Ø15.9
5/8
Ø9.52
3/8

48500 <C ≤75000
Ø19.05
3/4
Ø9.52
3/8

(3) Piping of indoor unit

Gas pipe 
Liquid pipe 

Rated capacity of IDU C

(Btu/h)

mm
inch
mm
inch

C ≤9600
Ø9.52
3/8
Ø6.35
1/4

9600 <C ≤17000
Ø12.7
1/2
Ø6.35
1/4

17000 <C ≤48000
Ø15.9
5/8
Ø9.52
3/8

48000 <C ≤55000
Ø19.05
3/4
Ø9.52
3/8

55000 <C ≤96000
Ø22.2
7/8
9.52
3/8

(4)  Selection for branching section

R410A Refrigerant system
Total capacity of downstream indoor units C (Btu/h)
Model

C ≤68200
FQ01A/A

68200 ≤C ≤102400
FQ01B/A

Y type branch

102400 ≤C ≤238800
FQ02/A

238800 ≤C ≤460600
FQ03/A

460600 ≤C 
FQ04/A
6.5 Charging requirement with additional refrigerant

(1) Refrigerant in the system when shipped from the factory

Model
GMV-24WL/

GMV-28WL/

GMV-36WL/

GMV-48WL/

GMV-60WL/

C-T(U)

C-T(U)

A-T(U)

A-T(U)

A-T(U)

kg
2.4
2.4
5.0
5.0
6.5

Refrigerant Qty 

oz
84.7
84.7
176
176
229

(2) Additional refrigerant charge amount =∑Length of liquid pipe × refrigerant charge amount per 
meter
Note:
① The refrigerant amount inside the system before ex-factory doesn’t include the required additional 

refrigerant charge amount inside the pipeline system of indoor units and the pipeline system 
connecting indoor unit and outdoor unit.
② For the length of connection pipe in field, the required additional refrigerant charge amount shall be 

confirmed according to liquid pipe size in field and its length.

18

Sayfa 19

Dc Inverter Multi VRF System Technical Sales Guide

③ Record additional refrigerant charge amount for future reference.
Note: If the total length of liquid pipe is within 20m, no additional refrigerant is needed.
When the compressor is not working after ensuring there is no leakage, charge the required additional 
refrigerant amount to the unit from the valve of liquid pipe of outdoor unit. When the pipe pressure 
increases and the additional refrigerant can’t be charged to the required amount quickly, please set 
the unit in cooling operation status and charge refrigerant from the low pressure maintenance port of 
outdoor unit.  

WIRING DESIGN
7

7.1 General wiring principle
(1) All electrical work shall be done by professionals according to national and local laws and 
regulations.
(2) The unit must be grounded reliably according to the related requirement of GB 50169.
(3)  Connect wire according to the wiring diagram stuck on the unit.

7.2 Electrical wiring design
(1) Wiring drawing
(2) Selection of power supply cord and fuse of units

Max Fuse Size/

Max Ckt, Bkr Size/
Disjoncteur Max.(A)
Min. Circuit Ampacity

Model
Power supply

Fusible Max.

(A)

GMV-24WL/C-T(U)
208/230V~ 60Hz
25
25
21

GMV-28WL/C-T(U)
208/230V~ 60Hz
30
30
21

GMV-36WL/A-T(U)
208/230V~ 60Hz
35
35
31

GMV-48WL/A-T(U)
208/230V~ 60Hz
45
45
34

GMV-60WL/A-T(U)
208/230V~ 60Hz
60
60
39.8

7.3 Wiring diagram of units

7.4 Parameters
(1) Outdoor unit

Model
GMV-24WL/C-T

GMV-28WL/C-T

GMV-36WL/A-T

GMV-48WL/A-T

GMV-60WL/A-T

(U)

(U)

(U)

(U)

(U)

MCA
A
21
21
31
34
39.8

MOP
A
25
30
35
45
60

19

Sayfa 20

(2) Indoor unit
Low Static Pressure Duct Type Indoor Unit

GMV-
ND07PLS/

GMV-
ND09PLS/

GMV-
ND12PLS/

GMV-
ND14PLS/

GMV-
ND18PLS/

GMV-
ND22PLS/

Model

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

MCA
A
0.25
0.25
0.25
0.38
0.63
0.63

MOP
A
0.45
0.45
0.45
0.68
1.13
1.13

4-way Cassette Indoor Unit

Model
GMV-ND07T/

GMV-ND09T/

GMV-ND12T/

GMV-ND15T/

GMV-ND18T/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

MCA
A
0.25
0.25
0.25
0.25
0.31

MOP
A
0.45
0.45
0.45
0.45
0.56

Model
GMV-ND24T/

GMV-ND30T/

GMV-ND36T/

GMV-ND42T/

GMV-ND48T/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

MCA
A
0.31
0.44
0.44
0.44
0.44

MOP
A
0.56
0.79
0.79
0.79
0.79

Wall Mounted type Indoor Unit

Model
GMV-N07G/

GMV-N09G/

GMV-N12G/

GMV-N18G/

GMV-N24G/

A3A-D(U)

A3A-D(U)

A3A-D(U)

A3A-D(U)

A3A-D(U)

MCA
A
0.25
0.25
0.26
0.26
0.39

MOP
A
0.45
0.45
0.47
0.47
0.70

Legend:
MCA: Minimum Circuit Amps                    
MOCP: Maximum Overcurrent Protection(Amps)      
FLA: Full Load Amps
kW: Fan Motor Rated Output(kW)

20

Sayfa 21

Dc Inverter Multi VRF System Technical Sales Guide

ACCESSORIES
8

(1) Outdoor unit

Model name
Standard
Option
Provide for oneself 

GMV-24WL/C-T(U)
√

GMV-28WL/C-T(U)
√

GMV-36WL/A-T(U)
√

GMV-48WL/A-T(U)
√

GMV-60WL/A-T(U)
√
FQ01A/A Y shape branching 

joint
√

Condensate pipe
√

Power cord
√

Filter
√

Oil return elbow
√

Signal wires among units
√

(2) Indoor unit

Model name
Standard
Option
Provide for oneself 

XK46 Wired Controller
√

YV1L1 remote controller
√

YAD1F remote controller
√
Screw M4X25 (Cross recessed 

small pan head screw)
√

Drain Hose Assembly
√

Union Nut Assembly
√

Nut with Washer
√

Nut M10 (Type 1 Hex Nut)
√

Nut 10 ( Type 1 Hex Nut)
√

Heating Jacket of Header
√
Heating Jacket of Liquid-in 

Pipe
√

Sponge of Drain Pipe
√

Cable Tie
√

(3) Controller

Model name
Standard
Option
Provide for oneself 

Wired controller XK62
√

Central controller CE53-24/F(C)
√

21

Sayfa 22

TECHNICAL SPECIFICATIONS
9

(1) Indoor unitّّ

 Low Static Pressure Duct Type IDU

GMV-
ND07PLS/

GMV-
ND09PLS/

GMV-
ND12PLS/

GMV-
ND14PLS/

GMV-
ND18PLS/

GMV-
ND22PLS/

Model

A-T(U)
Product   Code
CM810N0080 CM810N0090 CM810N0100 CM810N0120 CM810N0070 CM810N0110

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

Btu/h
7500
9500
12000
14000
18000
22000

Cooling Capacity

kW
2.2
2.8
3.5
4.0 
5.3
6.3

Btu/h
8500
10500
13500
15000
20000
24000

Heating Capacity

kW
2.5
3.1
4.0 
4.5 
5.9
7.1

Casing finish
Galvanized Steel plate

mm
700×615
×200

700×615
×200

700×615
×200

900×615
×200

1100×615
×200

1100×615
×200

outline

inch
27-1/2×24-
1/4×7-7/8
27-1/2×24-
1/4×7-7/8
27-1/2×24-
1/4×7-7/8
35-3/8×24-
1/4×7-7/8
43-1/4×24-
1/4×7-7/8
43-1/4×24-
1/4×7-7/8

Dimensions

mm
893×743
×305

893×743
×305

893×743
×305

1123×743
×305

1323×743
×305

1323×743
×305

(W×D×H)

Packaging

inch
35-1/8×29-
1/4×12
35-1/8×29-
1/4×12
35-1/8×29-
1/4×12
44-1/2×29-
1/4×12
52×29
-1/4×12

52×29-
1/4×12

lbs.
51 
51 
51 
60 
69 
69 

Net Weight

kg
23
23
23
27
31
31

lbs.
64 
64 
64 
73 
86 
86 

Gross Weight

kg
29
29
29
33
39
39

mm
Ø6.35
Ø6.35
Ø6.35
Ø6.35
Ø9.52
Ø9.52

Liquid Side

inch
Ø1/4
Ø1/4
Ø1/4
Ø1/4
Ø3/8
Ø3/8

mm
Ø9.52
Ø12.7
Ø12.7
Ø12.7
Ø15.9
Ø15.9

Pipe 
Connection

Gas Side

inch
Ø3/8
Ø1/2
Ø1/2
Ø1/2
Ø5/8
Ø5/8

mm
Ø25

Drain Pipe

inch
Ø1

Power supply
1-phase 208/230V~60Hz

Sound Pressure Level(H/M/L)
dB(A)
31/29/25
31/29/25
32/30/27
33/31/28
35/33/30
35/33/30

Heat Exchanger
Fenestrate plain film --hydrophilic film

Air Filter
PP

Refrigeration Control Device
EXV

Protection Device
Fuse

22

Sayfa 23

Dc Inverter Multi VRF System Technical Sales Guideّّ

4-way Cassette Type IDU

Model
GMV-ND07T/

GMV-ND09T/

GMV-ND12T/

GMV-ND15T/

GMV-ND18T/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

Product Code
CM500N0520
CM500N0530
CM500N0540
CM810N0130
CM500N0510

Btu/h
7500
9500
12000
15000
18000

Cooling Capacity

kW
2.2
2.8
3.5
4.4
5.3

Btu/h
8500
10500
13500
17000
20000

Heating Capacity

kW
2.5
3.1
4.0 
5
5.9

Casing finish 
Galvanized Steel plate

mm
840×840×190
840×840×240
840×840×240
840×840×240
840×840×240

Body outline

inch
33×33×7 1/2
33×33×9-1/2
33×33×9-1/2
33×33×9-1/2
33×33×9-1/2

mm
960×960×257
960×960×310
960×960×310
960×960×310
960×960×310

Body 
Packaging

inch
37-3/4×37-
3/4×10-1/8
37-3/4×37-
3/4×12-1/4
37-3/4×37-
3/4×12-1/4
37-3/4×37-
3/4×12-1/4
37-3/4×37-
3/4×12-1/4

Dimensions

mm
950×950×65
950×950×65
950×950×65
950×950×65
950×950×65

(W×D×H)

Panel
 outline

inch
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2

mm
1030×1035×118 1030×1035×118 1030×1035×118 1030×1035×118 1030×1035×118

Panel 
Packaging

inch
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8

lbs.
50
58
58
58
58

Main Body

kg
22.5
26.5
26.5
26.5
26.5

Net 
Weigh

lbs.
15-3/8
15-3/8
15-3/8
15-3/8
15-3/8

Panel

kg
7.0
7.0
7.0
7.0
7.0

lbs.
64
75
75
75
75

Main Body

kg
29
34
34
34
34

Gross 
Weigh

 lbs.
24-1/4
24-1/4
24-1/4
24-1/4
24-1/4

Panel

kg
11.0
11.0
11.0
11.0
11.0

mm
Ø6.35
Ø6.35
Ø6.35
Ø6.35
Ø9.52

Liquid Side

inch
Ø1/4
Ø1/4
Ø1/4
Ø1/4
Ø3/8

mm
Ø9.52
Ø12.7
Ø12.7
Ø12.7
Ø15.9

Pipe 
Connections

Gas Side

inch
Ø3/8
Ø1/2
Ø1/2
Ø1/2
Ø5/8

mm
Ø25

Drain Pipe

inch
Ø1

Power supply
1-phase 208/230V~60Hz

Sound Pressure Level

(H/M/L)
dB(A)
36/34/31
37/35/32
37/35/32
37/35/32
37/35/32

Heat Exchanger
Fenestrate plain film --hydrophilic film

Air Filter
PP
PP
PP
PP
PP

Insulation Material
Foamed polystyrene

Refrigeration Control Device
EXV
EXV
EXV
EXV
EXV

Protection Device
Fuse
Fuse
Fuse
Fuse
Fuse

Panel name
TC01
TC01
TC01
TC01
TC01

23

Sayfa 24

Model
GMV-ND24T/

GMV-ND30T/

GMV-ND36T/

GMV-ND42T/

GMV-ND48T/

A-T(U)

A-T(U)

A-T(U)

A-T(U)

A-T(U)

Product code
CM500N0550
CM500N0560
CM500N0570
CM500N0580
CM500N0590

Btu/h
24000
30000
36000
42000
48000

Cooling Capacity

kW
7
8.8
10.6
12.3
14.1

Btu/h
27000
34000
40000
47000
54000

Heating Capacity

kW
7.9
10
11.7
13.8
15.8

Casing finish
Galvanized Steel plate

mm
840×840×240
840×840×320
840×840×320
840×840×320
840×840×320

Body
 outline

inch
33×33×9-1/2
33×33×12-5/8
33×33×12-5/8
33×33×12-5/8
33×33×12-5/8

mm
960×960×310
960×960×394
960×960×394
960×960×394
960×960×394

Body 
Packaging

inch
37-3/4×37-
3/4×12-1/4
37-3/4×37-
3/4×15-1/2
37-3/4×37-
3/4×15-1/2
37-3/4×37-
3/4×15-1/2
37-3/4×37-
3/4×15-1/2

Dimensions

mm
950×950×65
950×950×65
950×950×65
950×950×65
950×950×65

(W×D×H)

Panel
 outline

inch
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2
37-3/8×37-
3/8×2-1/2

mm
1030×1035×118
1030×1035×118
1030×1035×118
1030×1035×118
1030×1035×118

Panel 
Packaging

inch
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8
40-1/2×40-
1/2×4-5/8

lbs.
58
72
72
72
72

Main 
Body

kg
26.5
32.5
32.5
32.5
32.5

Net
 Weight

lbs.
15-3/8
15-3/8
15-3/8
15-3/8
15-3/8

Panel

kg
7.0
7.0
7.0
7.0
7.0

lbs.
75
88
88
88
88

Main Body

kg
34
40
40
40
40

Gross
 Weight

lbs.
24-1/4
24-1/4
24-1/4
24-1/4
24-1/4

Panel

kg
11.0
11.0
11.0
11.0
11.0

mm
Ø9.52
Ø9.52
Ø9.52
Ø9.52
Ø9.52

Liquid 

Side

inch
Ø3/8
Ø3/8
Ø3/8
Ø3/8
Ø3/8

mm
Ø15.9
Ø15.9
Ø15.9
Ø15.9
Ø15.9

Pipe 
Connections

Gas 
Side

inch
Ø5/8
Ø5/8
Ø5/8
Ø5/8
Ø5/8

mm
Ø25

Drain 

Pipe

inch
Ø1

Power supply
1-phase 208/230V~60Hz

Sound Pressure Level(H/

M/L)
dB(A)
38/36/33
40/38/35
41/38/36
43/41/38
43/41/38

Heat Exchanger
Fenestrate plain film --hydrophilic film

Air Filter
PP
PP
PP
PP
PP

Insulation Material
Foamed polystyrene

Refrigeration Control Device
EXV
EXV
EXV
EXV
EXV

Protection Device
Fuse
Fuse
Fuse
Fuse
Fuse

Panel name
TC01
TC01
TC01
TC01
TC01

24

Sayfa 25

Dc Inverter Multi VRF System Technical Sales Guideّّ

Features of Wall Mounted

Model
GMV-N07G/A3A-

GMV-N09G/A3A-

GMV-N12G/A3A-

GMV-N18G/A3A-

GMV-N24G/A3A-

D(U)
Product code
CM100N1480 
CM100N1490 
CM100N1500  
CM100N1510 
CM100N1520  

D(U)

D(U)

D(U)

D(U)

Btu/h
7500
9500
12000
18000
24000

Cooling Capacity

kW
2.2
2.8
3.5
5.2
7

Btu/h
8500
11000
13500
20000
25500

Heating Capacity

kW
2.5
3.2
4
5.8
7.5

Casing finish
Galvanized Steel plate

mm
843×180×275
843×180×275
940×200×298
940×200×298
1008×221×319

outline

inch
33 1/5×7×10 5/6 33 1/5×7×10 5/6 37×7 7/8×11 3/4 37×7 7/8×11 3/4 39 2/3×8 5/7×12 
5/9

Dimensions

(W×D×H)

mm
973×258×370
973×258×370
1068×288×395
1068×288×395
1131×398×328

Packaging

inch
38 1/3×10 
1/6×14 4/7
38 1/3×10 
1/6×14 4/7
42×11 1/3×15 
5/9
42×11 1/3×15 
5/9
44 1/2×15 
2/3×13

lbs.
22
22
27.6
27.6
33.1

Net Weight

kg
10
10
12.5
12.5
15

lbs.
27.6
27.6
33.1
33.1
40.8

Gross Weight

kg
12.5
12.5
15
15
18.5

mm
Ø6.35
Ø6.35
Ø6.35
Ø9.52
Ø9.52

Liquid Side

inch
Ø1/4
Ø1/4
Ø1/4
Ø3/8
Ø3/8

mm
Ø9.52
Ø9.52
Ø12.7
Ø15.9
Ø15.9

Pipe 
Connections

Gas Side

inch
Ø3/8
Ø3/8
Ø1/2
Ø5/8
Ø5/8

mm
Ø17
Ø17
Ø17
Ø17
Ø17

Drain Pipe

inch
Ø2/3
Ø2/3
Ø2/3
Ø2/3
Ø2/3

Power supply
1-phase 208/230V~60Hz

Sound Pressure Level(H/M/L)
dB(A)
38/34/30
38/34/30
44/41/38
44/41/38
44/41/38

Heat Exchanger
Fenestrate plain film -- hydrophilic film

Air Filter
PP+10%BCM+FP03

Insulation Material
Foamed polystyrene

Refrigeration Control Device
EXV

Protection Device
Fuse

25

Sayfa 26

(2) Outdoor unit

 Model
GMV-24WL/

GMV-28WL/

GMV-36WL

GMV-48WL

GMV-60WL

C-T(U)

C-T(U)

/A-T(U)

/A-T(U)

/A-T(U)

kW
7
8.2
11
14.1
17.6

Cooling capacity

Btu/h
24000
28000
37500
48000
60000

kW
8.2
8.8
12.3
15.8
19.3

Heating capacity

Btu/h
28000
30000
42000
54000
66000

3/h
3900
3900
6000
6300
7800

m

Circulating air volume

CFM
2295
2295
3532
3708
4601

Noise
dB(A)
57
57
55
56
63

Kg
2.4
2.4
5
5
6.5

Refrigerant charge volume

oz
84.7
84.7
176
176
229

Power supply
208/230V ~60Hz

Cooling
kW
2.0
2.7
3.3
4.5
6.1

Rated power 

input

Heating
kW
2.4
2.6
3.7
4.4
5.5

mm
980×360×790
900×340×1345
940×320
×1430

Unit Dimensions (WxDxH)

inch
38_6/19×14_3/16×31_2/16
35_3/7×13
_2/5×53

37×12_3
/5×56_2/7

mm
1097×477×937
998×458×1500
1033×433×1580

Dimensions (WxDxH)

inch
43_3/16×18_12/16×36_14/16
39_2/7×18
×59 

40_2/3×17
×62_1/5

Compressor
QXFS-D25Zx090H
QXAS-F428zX050A
LNB53FCFMC

Water-proof level
IPX4
IPX4
IPX4
IPX4
IPX4

Suitable climite
T1
T1
T1
T1
T1

mm
Ø15.9
Ø15.9
Ø15.9
Ø15.9
Ø19.05

Gas 

inch
5/8
5/8
5/8
5/8
3/4

mm
Ø9.52
Ø9.52
Ø9.52
Ø9.52
Ø9.52

Connection 

Liquid 

pipe

inch
3/8
3/8
3/8
3/8
3/8

Connection Method
Bell mouth 
connection

Bell mouth 
connection

Bell mouth 
connection

Bell mouth 
connection

Bell mouth
 connection

Kg
80
80
110
110
124

Net weight

oz
2822
2822
3880
3880
4375

26

Sayfa 27

Dc Inverter Multi VRF System Technical Sales Guide

FAN CHARACTERISTICS
10

GMV-ND07PLS/A-T(U)

Air flow volume(H

Air flow volume(M

Air flow volume(L

GMV-ND09PLS/A-T(U)

25

Extermal static pressur(Pa)

20

Air flow volume(H)

15

Air flow volume(M

10

Air flow volume

5

0

Air volume (Pa)

27

Sayfa 28

28

GMV-ND12PLS/A-T(U)\GMV-ND14PLS/A-T(U)

25
25

Extermal
Extermal static
static pressur(Pa)
pressur(Pa)

20
20

Air
Air flow
flow volume(H)
volume(H)

15
15

Air
Air flow
flow volume(M)
volume(M)

10
10

Air
Air flow
flow

5

0

Air
Air volume
volume (Pa)
(Pa)

GMV-ND18PLS/A-T(U)、GMV-ND22PLS/A-T(U)

25

Extermal static pressur(Pa)

20

Air flow volume(H)

15

Air flow volume(M

Air flow volume

10

5

0

Sayfa 29

Dc Inverter Multi VRF System Technical Sales Guide

DIMENSIONAL DRAWINGS
11

(1) Indoor unitّّ

Duct Type (include the dimension of main unit, air return case and suspension hole)

The following table lists the detailed dimensions.                       

 Unit: mm(inch)
                           Item
Model
A
B
C
D
E
F
G
H
I

GMV-ND07PLS/A-T(U)
GMV-ND09PLS/A-T(U)
GMV-ND12PLS/A-T(U)

GMV-ND14PLS/A-T(U)

GMV-ND18PLS/A-T(U)
GMV-ND22PLS/A-T(U)

Installation space:

Unit outline and installation dimension

Gas pipe
Liquid pipe
Electric box

Drain pipe

742
(29-
3/16)

491
(19-
5/16)
700
(27-1/2) 

528
(20- 
13/16) 
161
(6-5/16)

580
(22 
13/16)

615
(24-1/4) 

200
(7-7/8)

121
(4-3/4)

942
(37-
1/16)

491
(19-
5/16)
900
(35-3/8)

728
(28-
11/16)
161
(6-5/16)

780
(30-
11/16)

615
(24-1/4)

200
(7-7/8)

121
(4-3/4)

1142
(44-
5/16) 

491
(19-
5/16)
1100
(43-1/4)

928
(36-
9/16)
161
(6-5/16)

980
(38-
9/16)

615
(24-1/4)

200
(7-7/8)

121
(4-3/4)

150(6)

29

Sayfa 30

Wall Mounted Type
1)  Unit outline and installation dimension
 

Model
W
H
D

GMV-N07G/A3A-D(U)
GMV-N09G/A3A-D(U)

843
(33-1/5)

275
(10-5/6)

GMV-N12G/A3A-D(U)
GMV-N18G/A3A-D(U)

940
(37)

298
(11-3/4)

GMV-N24G/A3A-D(U)
1008
(39-2/3)

221
(8-5/7)

2)  Unit installation space
Celling
Celling

Floor
Floorّّ
Four-way Cassette Indoor Unit

D (Distance between lifting screws)

Refrigerant 
pipe

A (Decoration panel)

B (Ceiling aperture)

C (Indoor units)

Lifting screw

D (Distance between lifting screws)

C (Indoor units)

B (Ceiling aperture)

A (Decoration panel)

30ّّ

Unit:mm(inch)

180
(7)

200
(7-7/8)

319
(12-5/9)

Wall

Sayfa 31

Dc Inverter Multi VRF System Technical Sales Guide

D (Distance between lifting screws)

Refrigerant 
pipe

A (Decoration panel)

B (Ceiling aperture)

C (Indoor units)

Lifting screw

D (Distance between lifting screws)

C (Indoor units)

B (Ceiling aperture)

A (Decoration panel)

   Unit: mm(inch)

Model
A
B
C
D
E
G
H

GMV-ND07T/A-T(U)
950
(37-2/5)

890
(35)

840
(33)

680
(26-7/9)

780
(30-5/7)

65
(2-5/9)

210
(8-1/4)

GMV-ND09T/A-T(U)
GMV-ND12T/A-T(U)
GMV-ND18T/A-T(U)
GMV-ND24T/A-T(U)

950
(37-2/5)

890
(35)

840
(33)

680
(26-7/9)

780
(30-5/7)

65
(2-5/9)

260
(10-1/4)

GMV-ND30T/A-T(U)
GMV-ND36T/A-T(U)
GMV-ND42T/A-T(U)
GMV-ND48T/A-T(U)

950
(37-2/5)

890
(35)

840
(33)

680
(26-7/9)

780
(30-5/7)

65
(2-5/9)

340
(13-2/5)

(2) Outdoor unitّّ

Include the required dimension of installation space of main unit and single unit.

Model
A
B
C
D
E

GMV-24WL/C-T(U)
GMV-28WL/C-T(U)
980(38_6/19)
360(14_3/16)
790(31_2/16)
650(25_3/5)
395(15_5/9)

31

Sayfa 32

A
B

D
E

Unit:mm(inch)

Model
A
B
C
D
E

GMV-36WL/A-T(U)
GMV-48WL/A-T(U)

900
(35-3/8)

340
(13-3/8)

1345
(53)

572
(22-1/2)

378
(15)

350
(14 7/8)ّّ
Installation dimension:

GMV-60WL/A-T(U)
940
(37)

320
(12 3/5)

1430
(56 2/7)

632
(24 7/8)

Wall

Wall

≥200mm

(8inch)

≥350mm
(13-3/4inch)

≥200mm
≥200mm

(8inch)
≥350mm

(8inch)

≥2000mm

(78-3/4inch)
(13-3/4inch)

≥2000mm

Shockproof 
material

(78-3/4inch)

Wall

Wall

(3) ranching join
Length of each kind of Y-shape branching joint and the dimension of connection pipe port.
Y-shape branching joint:FQ01A/A

32

Sayfa 33

Dc Inverter Multi VRF System Technical Sales Guide

Gas pipe
Liquid pipe

33

Sayfa 34

Gree Electric Appliances, Inc. of Zhuhai, founded in 1991, is the world's largest air 

conditioner enterprise integrating R&D, manufacturing, marketing and services.

Technology Innovation and quality are always our priority. With efforts of thousands of 

Gree's engineers, we own more than 3500 patents for our products.

Nowadays, we have 7 production bases in Zhuhai, Chongqing, Hefei and Zhengzhou(China), 

as well as Brazil, Pakistan and Vietnam, with annual production capacity of 30 million sets of 

residential air conditioners and 4 million sets of commercial air conditioners.

With the installation of Gree commercial air conditioners in important projects at home and 

abroad like Media Village for 2008 Beijing Olympic Games, Stadiums for 2010 World Cup 

in South Africa, as well as India Telecom base station, Gree commercial air conditioners are 

ready to develop steadily to every corner in the world, to present a more comfortable and 

harmonious working environment and family atmosphere.

GREE MAKING BETTER AIR CONDITIONERS GREE MAKING BETTER AIR CONDITIONERS GREE MAKING BETTER AIR 

CONDITIONER GREE MAKIN BETTER

Add: West Jinji Rd,Qianshan Zhuhai,Guangdong,China519070
Tel: (+86-756)8614883    Fax: (+86-756)8614998
Http://www.gree.com       Email: gree@gree.com.cn
For continous improvement in the products, Gree reserves the right to modify 
the product specification and appearence in this manual without notice and 
without incurring and obligations.

SJ00422346