DC INVERTER MULTI VRF SYSTEM TECHNICAL SALES GUIDE BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITION TTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONER (GC201804) TECHNICAL SALES GUIDE-60Hz CAPACITY RANGE:24~60kBtu/h SUPER HIGH AMBIENT OPERATION TO 118 ℉ GREE ELECTRIC APPLIANCES INC.OF ZHUHAI
CONTENTS 1 OUTLINE OF MULTI VRF..............................................................3 2 SUMMARY OF SYSTEM EQUIPMENTS......................................6 3 CONTROLLER..............................................................................9 4 BASIC SYSTEM CONFIGURATION...........................................10 5 EQUIPMENT SELECTION PROCEDURE..................................11 6 REFRIGERANT PIPING DESIGN................................................16 7 WIRING DESIGN........................................................................19 8 ACCESSORIES..........................................................................21 9 TECHNICAL SPECIFICATIONS..................................................22 10 FAN CHARACTERISTICS.........................................................27 11 DIMENSIONAL DRAWINGS.....................................................29 2
Dc Inverter Multi VRF System Technical Sales Guide OUTLINE OF MULTI VRF 1 1.1 Product List GMV-24WL/C-T(U) GMV-28WL/C-T(U) Model GMV-36WL/A-T(U) GMV-48WL/A-T(U) GMV-60WL/A-T(U) 1.2 Product Features 1.2.1 Summary of Features GMV5 mini DC Inverter Multi VRF System is the new generation of DC inverter multi VRF system that Gree developed independently. It is a single refrigeration system that made up of one air cooled outdoor unit connected with several direct evaporative indoor units of identical or different series or capacity. It provides processed air directly to an area or several areas, which is mainly applicable for household or light commercial facilities. This product is endowed with the features of high efficiency, high anti-interference ability, long connection pipe, wide operation range, good acoustic, intelligent capacity adjustment, all-around protection. 1.2.2 Introduction of Features (1) High Efficiency The system adopts all DC motor, which greatly improves efficiency. The energy efficiency for Gree all DC unit is increased greatly. SEER is up to 16; HSPF of GMV-24WL/C-T(U)、GMV-28WL/C-T(U)、GMV- 36WL/A-T(U) and GMV-48WL/A-T(U) is up to 9; HSPF of GMV-60WL/A-T(U) is up to 8.2. (2) Latest CAN Bus Communication The latest communication way-CAN bus communication is adopted, which greatly improves anti- interference ability, precisely controls the indoor units and improves the reliability of system. Meanwhile, specialized shielded wire is not longer needed, while conventional communication wire can be used to increase the flexibility of project installation. High anti-interference ability (3) Long Connection Pipe and Big Height Difference The max length of connection reaches 300m(984ft)(total length). The connection pipe between indoor unit and outdoor unit can be as long as 120m(394ft). Project installation condition is wider while the limitation of installation distance is smaller. Branching joint and branching manifold can also be used. The max allowable height difference between indoor unit and outdoor unit is 50m(164ft) and that between indoor unit and indoor unit is 15m(49ft). (4) Wide Operation Range The system can operate constantly and reliably in a wide temperature range(cooling: -5~48 OF), heating: -20~27 OF)), which is not affected by atrocious environment. OC(23~118 OC(-4~81 3
GMV5 Mini DC Inverter Multi VRF Last generation Cooling:10~48 C Cooling:-5~48 C -20~27 C 50~118 F Heatin : -20~27 C 23~118 F Heatin : -4~81 F -4~81 F (5) Good Acoustic A series of optimized measures are taken to solve the problem of indoor unit’s throttling sound, indoor unit’s oil return noise, gas bypass noise during start-up, which improves the comfort of system. 70 60 Noise classification refers to “Urban Environmental Noise Standard” 50 40 45db(A) The noise of GMV Star DC Inverter Multi VRF is as low as 45db(A) 30 20 (6) PID Intelligent Capacity Adjustment The system applies the original technology of PID intelligent capacity adjustment, which quickly and precisely controls indoor ambient temperature according to set temperature, with small temperature fluctuation and great comfort. Temperature fluctuation the foom GMV System Non VRF 33 F (7) Intelligent Control 1) Advanced DC inverter technology ① High-efficient magnetic reluctance inverter compressor: High-efficient magnetic reluctance compressor is adopted to take advantage of the magnetic reluctance torque of compressor. Under the same output capacity, the efficiency can be improved by 5%. ② Advanced torque control technology: minimum current and maximum torque control technology adopts the most optimized control principle to realize maximum torque output with minimum current and reduce loss of motor winding and intelligent power module for higher energy efficiency. ③ Closed-loop start-up technology of compressor: Self-innovative closed-loop start-up control is applied to enable output torque follow with load torque, whose start-up current is small and start-up is more reliable. ④ High-efficient numerical PFC control: High-efficient PFC control technology is applied to improve efficiency by approx. 1% compared with traditional PFC; for an air condition with rated power of 4
Dc Inverter Multi VRF System Technical Sales Guide 5KW, 50W can be saved per hour and 1.2kWh electricity can be saved per day. ⑤ 180º sine wave DC variable speed technology: 180º current output waveform is smooth sine wave with small harmonic wave content, small torque pulsation, wide adjustable range and stable operation of motor, which can satisfy the temperature requirement in various occasion, save electricity greatly and ensure user’s comfort in maximum. 2) Beautiful humanized controller design ① 24h timer on or timer off can be preset (countdown timer and clock timer);Detect ambient emperature precisely; 7 kinds of fan speed can be set; ② Auto, cool, dry, fan or heat mode can be set; ③ Master wired controller and sub-master wired controller can be set; several indoor units can be controlled simultaneously; ④ Various functions can be set: sleep, ventilation, quiet (auto quiet), light, absence, energy-saving, clean, e-heater, x-fan, memory, etc. 3) High anti-interference ability The latest communication way-CAN bus communication(non-polar communication) is adopted, which greatly improves anti-interference ability. Specialized shielded wire is not longer needed for communication wire between units, while conventional communication wire can be used to increase the flexibility of project installation. 4) Intelligent temperature control technology and intelligent defrosting mode are adopted The system is with strong quick cooling/heating function, which can increase indoor temperature rapidly to set temperature and perform defrosting according to frosting situation. (8) Independent remote control, wired control, zone control, centralized control, long-distance monitoring and weekly timer control of indoor units are available. 5
SUMMARY OF SYSTEM EQUIPMENTS 2 2.1 Outdoor Unit Model Code Ref. Power Supply Appearance GMV-24WL/C-T(U) CN850W0740 R410A GMV-28WL/C-T(U) CN850W0750 R410A GMV-36WL/A-T(U) CN850W0230 R410A GMV-48WL/A-T(U) CN850W0220 R410A GMV-60WL/A-T(U) CN850W0270 R410A 2.1.1 Nomenclature GMV □ - □ □ □ □ W □ / □ □ □ 1 2 3 4 5 6 7 8 9 10 No. Description Options 1 Product code GMV-Gree Multi VRF Units 2 Suitable climate Blank-T1 condition; T2-low temperature climate; T3-high temperature climate 3 Unit type DC Inverter (omit) 4 Function code Q—Heat Recovery; S—Water Heater; W—Water-cooled Unit; X—Fresh Air Unit Leave blank if above functions are unavailable. 5 Code of cooling capacity Nominal capacity/1000(Btu/h) 6 Unit structure M—Modular (top discharge); L—Non-modular (side discharge); blank—Non-modular (top discharge) 7 Refrigerant R410A (omit) 8 Design No. Named in order of A, B, C, or combined with 1, 2, 3… 9 Power supply 24000~61000Btu/h, 1 phase—omit; 3 phase—S 6 208/230V ~ 60Hz 208/230V ~ 60Hz 208/230V ~ 60Hz 208/230V ~ 60Hz 208/230V ~ 60Hz
Dc Inverter Multi VRF System Technical Sales Guide 2.1.2 Rated Conditions Indoor side inlet air status Outdoor side inlet air status Dry bulb temperature Wet bulb temperature Dry bulb temperature Wet bulb temperaturea ℃ ℉ ℃ ℉ ℃ ℉ ℃ ℉ Cooling 26.7 80.0 19.4 67.0 35.0 95.0 23.9 75.0 Heating 21.1 70.0 15.6 60.0 8.3 47 6.1 43 2.1.3 Branching joints Model name Usage Appearance GMV-24WL/C-T(U) Y-shape branching joint GMV-28WL/C-T(U) to other branching joint or indoor unit Y-shape branching Inlet GMV-36WL/A-T(U) FQ01A/A pipes used in the field joint ODU GMV-48WL/A-T(U) GMV-60WL/A-T(U) 2.2 Indoor Unit Cooling Capacity Heating Capacity Type Appearance Model Name kW Btu/h kW Btu/h GMV-ND07PLS/A-T(U) 2.2 7500 2.5 8500 GMV-ND09PLS/A-T(U) 2.8 9500 3.1 10500 Duct GMV-ND12PLS/A-T(U) 3.5 12000 4.0 13500 type indoor GMV-ND14PLS/A-T(U) 4.0 13800 4.5 15500 unit GMV-ND18PLS/A-T(U) 5.3 18000 5.9 20000 GMV-ND22PLS/A-T(U) 6.3 22000 7.1 24000 7
Cooling Capacity
Heating Capacity
Type
Appearance
Model Name
kW
Btu/h
kW
Btu/h
GMV-ND07T/A-T(U)
2.2
7500
2.5
8500
GMV-ND09T/A-T(U)
2.8
9500
3.1
10500
GMV-ND12T/A-T(U)
3.5
12000
4.0
13500
GMV-ND15T/A-T(U)
4.4
15000
5
17000
GMV-ND18T/A-T(U)
5.3
18000
5.9
20000
Four-way
Cassette
GMV-ND24T/A-T(U)
7.0
24000
7.9
27000
GMV-ND30T/A-T(U)
8.8
30000
10
34000
GMV-ND36T/A-T(U)
10.6
36000
11.7
40000
GMV-ND42T/A-T(U)
12.3
42000
13.8
47000
GMV-ND48T/A-T(U)
14.1
48000
15.8
54000
Cooling Capacity
Heating Capacity
Type
Appearance
Model Name
kW
Btu/h
kW
Btu/h
GMV-N07G/A3A-D(U)
2.2
7500
2.5
8500
GMV-N09G/A3A-D(U)
2.8
9500
3.2
11000
Wall
Mounted
GMV-N12G/A3A-D(U)
3.5
12000
4.0
13500
Type
GMV-N18G/A3A-D(U)
5.2
18000
5.8
20000
GMV-N24G/A3A-D(U)
7.0
24000
7.5
25500
2.2.1 Nomenclature
GMV-
——
Power supply
Series number
With water pump or not
Units series
Cooling capacity
Function code
Motor type
Household or commercial
Code for indoor unit
Code for type
Code for
multi VRF
-
Code for
indoor unit
Motor type
Function code
Cooling capacity
R-heat pump
L-cooling only
D-DC
motor
Default-AC
X-fresh air
W-dual heat sources
GMV
-
N
Q-heat recovery
Default-electric heating
motor
8
Nominal cooling
capacity/1000(Btu/
h)Dc Inverter Multi VRF System Technical Sales Guide Classification With water pump or not Series number Power supply PL-Low static pressure duct type indoor unit; P-Standard static pressure duct type indoor; PH-High static pressure duct type indoor unit; PB-Thin duct type indoor unit; T-Four-way cassette; TD-Single-way cassette; TS-Two-way cassette; C-Floor mounting unit; ZD-Floor ceiling unit; G-Wall-mounted unit With water pump-S(All cassette indoor units are with water pump, S is not presented in the model same) Select power supply code according to power supply specification A, B, C… or 1, 2, 3… Power supply specification Code 220V ~,60Hz; 208-230V ~,60Hz; 220-240V ~,60HZ; 208/230V ~,60Hz D 220V ~,50Hz; 230V ~,50Hz; 220-230V ~,50Hz E 240V ~,50HZ J 220-240V ~,50Hz; 230-240V ~,50Hz K 208-230V ~,60Hz and 220-240V ~,50Hz General T CONTROLLER 3 Name Model name Appearance Application Function 1)Elegant appearance and adopts big LCD screen with back light; 2) Ten touch buttons to avoid complicated combination buttons, which is convenient for operation; 3) Optional modes: Auto, cool, dry, fan, heat mode or floor heating, 3D heat supply(heating + floor heating) mode; 4)7 kinds of fan speed; 5) Clock can be displayed and set; 24h preset ON or OFF is available (countdown, clock timer function); 6) Dual wired controllers can be equipped. The two wired controllers can control the same indoor unit simultaneously. Or one wired controller can control several indoor units simultaneously; 7)Settable functions: sleep, air, quiet(auto quiet), light, energy saving, E-heater, X-fan, memory, low ambient temperature drying, heating in absence, controllable drying and E-heater, filter cleaning reminding; 8)With project parameter viewing and setting functions, which is convenient for project installation and debugging; 9)Adopts dual wire power carrier communication technology, which means power supply and communication share the same two-core wire. Users can purchase the wire by themselves, flexible for project installation and wiring. Outdoor unit D1 D2 Wired controller XK42 Indoor unit 1 Indoor unit 2 Indoor unit 16 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 Besides the common functions, the following functions are also available: up&down swing, timer on, timer off, I-feel, sleep and 8℃ heating operation, etc. DSP1 DSP2 YAD1F Remote controller Besides the common functions, the following functions are also available: up&down swing, left&right swing, quiet, timer on, timer off, sleep, I-feel, low ambient temperature drying and 8℃ heating operation, etc. DSP1 DSP2 YV1L1 9
BASIC SYSTEM CONFIGURATION 4 4.1 System legend(ex.) Model name of outdoor unit: GMV-48WL/A-T(U) Allowed capacity code of indoor unit: Min:24000Btu/h Max: 64800Btu/h. Note: The total capacity code of indoor units shall be within 50%~135% of the capacity code of selected outdoor unit. ODU GMV-160WL/A-T Total capacity code of indoor units is 18+12+9+9=48, so the selected outdoor unit is. GMV-48WL/A-T(U). 10 GMV-ND18PLS/A-T(U) GMV-ND12PLS/A-T(U) GMV-ND09PLS/A-T(U) GMV-ND09PLS/A-T(U)
Dc Inverter Multi VRF System Technical Sales Guide EQUIPMENT SELECTION PROCEDURE 5 5.1 Selection flow chart Calculate the heat load of the room Correction of indoor unit capacity Select indoor unit model Select indoor unit model Correction of outdoor unit capacity Select outdoor unit model 5.2 Combination conditions for indoor unit and outdoor unit 1) The capacity code of indoor units = The capacity code of indoor units = total capacity code of outdoor unit × (50%~135%). 2) For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided. Capacity code of outdoor unit Model name of Max. No. of indoor units kW Btu/h outdoor unit GMV-24WL/C-T(U) 7.0 24000 4 GMV-28WL/C-T(U) 8.2 28000 4 GMV-36WL/A-T(U) 11.0 37500 7 GMV-48WL/A-T(U) 14.1 48000 8 GMV-60WL/A-T(U) 17.6 60000 10 5.3 Cooling/Heating capacity characteristics (1) Cooling capacity calculation method. (2) Heating capacity calculation method. Cooling or heating capacity calculation method: R410A outdoor unit capacity = outdoor unit capacity in rated condition × correction factor of indoor and outdoor temperature condition × connection pipe distance, correction factor of height difference between indoor unit and outdoor unit. ① If the total capacity code of indoor units is smaller than the capacity code of outdoor unit, the capacity of outdoor unit in rated condition equals to the total capacity code of indoor units; ② If the total capacity code of indoor units is bigger than the capacity code of outdoor unit, the capacity 11
of outdoor unit in rated condition equals to its rated cooling capacity; ③ Correction factor of indoor and outdoor temperature condition. 1) Correction factor of cooling capacity 43(110) 40(104) (℃/℉) 35(95) 30(86) 25(77) 20(68) 16(61) 14 (57) 16 (61) 18 (64) 20 (68) 22 (72) 24 (75) 26 (79) (℃/℉) 2) Correction factor of heating capacity 26(79) 27(81) (℃/℉) 24(75) 22(72) 20(68) 18(64) 16(61) 14(57) 12(54) 10(50)-15 (5) -5 (23) 0 (32) 5 (41) 15 (59) -10 (14) 10 (50) (℃/℉) ④ Correction factor of connection pipe distance and height differenceّّ Symbol instruction: Hp: Height difference (m) between indoor unit and outdoor unit when indoor unit is lower than outdoor unit; Hm: Height difference (m) between indoor unit and outdoor unit when indoor unit is higher than 12
Dc Inverter Multi VRF System Technical Sales Guide outdoor unit; L: Single-pass equivalent connection pipe length Lّّ The following chart is the capacity change rate in 100% load under standard condition (thermostat is set in 16℃(61 OF) in cooling and set in 30℃(86 OF) in heating). 50 40 30 20 Hp(m) 10 10 20 30 60 40 50 70 80 110 90 1001 20 150 L(m) 1301 40 10 Hm(m) 20 30 40 0.99 0.97 0.95 50 40 30 20 1.0 Hp(m) 10 10 20 30 60 40 50 70 80 110 90 1001 20 150 L(m) 1301 40 10 Hm(m) 20 30 40 Note: (m) 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 (ft) 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492 (3) Capacity of each indoor unit=Capacity of outdoor unit × Total capacity of indoor units/Total capacity of synchronously operating indoor units. (4) Operating temperature rang. Temperature range ℃ ℉ Cooling -5~48 23~118 Heating -20~27 -4~81 5.4 Example of equipment selection (1) Overview of building model a.Temperature condition b.Outdoor temperature: 35℃(95 ℉) DB; Indoor temperature: 17℃(81 ℉) WB. c.Load in cooling Room A Room B Room C Room D Kw 2.4 3.2 2.4 4.7 Load Btu/h 8200 10900 8200 16000 (2) Selection Criteria for each floor Pipe length: 55m; Height difference between indoor unit and outdoor unit: 25m (indoor unit is higher than outdoor unit). 13
(3) Procedure and result of equipment selection
a.Procedure of equipment selection
Introduce the equipment selection procedure step by step.
b.Equipment selection and capacity check
① Selection of indoor unit.
Select suitable indoor unit according to the corrected load of indoor unit capacity.Corrected load
of indoor unit capacity=Load/Corrected ratio of cooling capacity related to temperature condition.
Referring to the corrected ratio chart of cooling capacity related to temperature condition, under
outdoor temperature of 35℃(95 ℉)DB and indoor temperature of 17℃(81 ℉)WB, the
corrected ratio of cooling capacity is 0.94.
Selection result is as below:
Room A
Room B
Room C
Room D
Corrected
Kw
2.55
3.40
2.55
5.0
load of
capacity
Btu/h
8720
11600
8720
17020
Unit size
09
12
09
18
② Selection of outdoor unit
The total capacity code of indoor units is 48. Please select suitable outdoor unit according to the
total capacity of indoor units and corrected situation.Capacity of outdoor unit=Total capacity of
indoor units/(Corrected ratio of cooling capacity related to temperature condition × Correction of
connection pipe length and height difference) .After calculating the capacity of outdoor unit, select
suitable outdoor unit according to 50%~135% of the capacity of outdoor unit.
In the example, capacity of outdoor unit=48/(0.94×0.95)=54.
Select the outdoor unit with capacity code of 160 and nominal cooling capacity of 14.1Kw(48000Btu/
h).
The capacity code ratio between indoor unit and outdoor unit is 48/48×100%=100%, which is
within 50%~135% and accords with the equipment selection standard.
③ Correction of outdoor unit capacity
Suppose the combination situation between indoor unit and outdoor unit is as below,GMV-48WL/
A-T(U).
Indoor unit: GMV-ND09PLS/A-T(U)×2, GMV-ND12PLS/A-T(U)×1, GMV-ND18PLS/A-T(U)×1
If the total capacity code of indoor units is bigger than the capacity code of outdoor unit, the capacity
of outdoor unit in rated condition equals to its rated cooling capacity. So the capacity of outdoor unit
under rated condition is 14.1Kw(48000Btu/h).
④ Referring to the corrected ratio chart of cooling capacity related to temperature condition, under
outdoor temperature of 35
℃(95 ℉)DB and indoor temperature of 17
℃(81 ℉)WB, the
corrected ratio of cooling capacity is 0.94.
⑤ Referring to the corrected ratio of connection pipe of 55m(180ft)long and height difference
between indoor unit and outdoor unit of 25m(82ft)(outdoor unit is lower than indoor unit), the
corrected ratio is 0.95.
Capacity of outdoor unit=48×0.94×0.95=12.59Kw(42.86Btu/h)
⑥ Correction of indoor unit capacity
Capacity of each indoor unit=Capacity of outdoor unit × Total capacity of indoor units/Total capacity
of synchronously operating indoor units.
GMV-ND09PLS/A-T(U):48×9/48=9kBtu/h
GMV-ND12PLS/A-T(U):48×12/48=12kBtu/h
GMV-ND09PLS/A-T(U):48×18/48=18kBtu/h
14Dc Inverter Multi VRF System Technical Sales Guide The result is as below: Air conditioning load Equipment selection Indoor air conditioning load Indoor unit Outdoor unit Capacity Floor RoomNo Capacity(Btu/h) Cooling (Btu/h) Model (Btu/h) Model Cooling Cooling A 8200 GMV-ND09PLS/A-T(U) 9500 GMV-48WL/A-T(U) 48000 B 10900 GMV-ND12PLS/A-T(U) 12000 1 C 8200 GMV-ND09PLS/A-T(U) 9500 D 16000 GMV-ND18PLS/A-T(U) 18000 Piping distance Capacity correction Capacity check after correction Equivalent Height Pipe correction × Capacity Floor Room length difference Judgment m Ft m Ft kW Btu/h kW Btu/h temp. correction No. A 2.55 8720 The selection should accord with the standard 85 280 25( ODU is lower than 82m(ODU is lower than B 3.40 11600 1 12.56 42860 C 2.55 8720 IDU ) IDU) D 5.00 17020 c.Schematic diagram Explain the location of units in each room and connection way of indoor unit and outdoor unit with single-line chart. ODU LS/A-T(U) IDU GMV-ND09P GMV-ND12P GMV-ND09P GMV-ND18P LS/A-T(U) LS/A-T(U) LS/A-T(U) 15
REFRIGERANT PIPING DESIGN 6 6.1 Warning on refrigerant leakage (1) Introduction of leakage detection method Procedures of leakage detection.Before ex-factory, the cut-off valves of gap pipe and liquid pipe of outdoor unit are closed. Please confirm it before installation.Before testing, apply some suitable lubricant on the joint of cap and pipe. Use two wrenches when fixing the cap.Connecting outdoor pipeline for testing is not allowed during leakage detection. The testing pressure of R410A system is 4.15MPa (for R22 system, it is 3.0Mpa). The medium of airproof test must be dry nitrogen. Increase the pressure slowly in three steps: Step one: Slowly increase pressure to 0.5MPa and maintain pressure for 5min. Big leakage may be found during leakage detection; Step two: Slowly increase pressure to 1.5MPa and maintain pressure for 5min. Small leakage may be found during airproof test; Step three: For R410A system, slowly increase pressure to 4.15MPa(for R22 system, it is 3.0Mpa) and maintain pressure for 5min. Tiny leakage may be found during strength test. Increase pressure to testing pressure and maintain pressure for 24h. Check if the pressure decreases. The test is passed if pressure doesn’t decrease. (2) Introduction of handling method of leakage Firstly, discharge the refrigerant and then charge nitrogen for leakage welding. The nitrogen charging way is the same as that in airproof test. Blow away the impurities and clean the pipeline after finishing welding. Finally, rearrange airproof test for leakage detection until there is no leakage. 6.2 Free branching system ODU Gas pipe Liquid pipe Connection pipe between outdoor unit and the first branching joint in indoor side Branching pipes of indoor units and connection pipes among indoor units Indoor unit 1 Branching joints among indoor units Connection pipes of branching joints among indoor units Branching pipes of indoor units and connection pipes among indoor units Indoor unit 2 Connection pipes of branching joints among indoor units Branching pipes of indoor units and connection pipes among indoor units Indoor unit 3 Connection pipes of branching joints among indoor units 16
Dc Inverter Multi VRF System Technical Sales Guide 6.3 Allowable length/height difference of refrigerant piping ODU ODU L1 L1 a The The1st 1st branch branch section section IDU IDU Height Height difference differencebetween betweenI DU IDUand and Equivalent Equivalent length length to to the thef arthest farthest connection connection ) Equivalent Equivalent length length from fromthe the1st 1stb ranch branch to to the thef arthest farthestpipe(L<4om/131ft) pipe(L<4om/131ft) L2 L2 L3 L3 b c d IDU IDU IDU IDUI DU IDU Each EachY-type Y-typebranch branchequals equals to to 0.5m 0.5m(1-5/8ft) (1-5/8ft) and ande ach eachbranch branchheader headerequals equals to to 1.0m 1.0m(3-1/4ft) (3-1/4ft). NOTICE! The equivalent length of one Y shape branching joint is 0.5m(1-5/8ft). Allowable value Piping section M Ft Total extension of pipe (Liquid pipe, real length) 250 820 L1+L2+L3+a+b++c+d Real length 100 328 L1+L2+L3+d Equivalent length 120 394 Farthest piping length Pipe length Equivalent length of farthest piping from 1st branching 40 131 L2+L3+d Upper outdoor unit 30 98 —— Height between indoor and outdoor units Lower outdoor unit 30 98 —— Height difference Upper outdoor unit 10 33 —— Height between indoor units Lower outdoor unit 10 33 —— Height Height difference difference between between 17
6.4 Selection of refrigerant piping (1) Size of main pipe Pipe dimension Model Gas pipe Liquid pipe mm inch mm inch GMV-24WL/C-T(U) Ø15.9 5/8 Ø9.52 3/8 GMV-28WL/C-T(U) Ø15.9 5/8 Ø9.52 3/8 GMV-36WL/A-T(U) Ø15.9 5/8 Ø9.52 3/8 GMV-48WL/A-T(U) Ø15.9 5/8 Ø9.52 3/8 GMV-60WL/A-T(U) Ø19.05 3/4 Ø9.52 3/8 (2) Pipe size between branching joints Gas pipe Liquid pipe Total capacity of downstream indoor units C (Btu/h) mm inch mm inch C ≤19000 Ø12.7 1/2 Ø6.35 1/4 19000 <C ≤48500 Ø15.9 5/8 Ø9.52 3/8 48500 <C ≤75000 Ø19.05 3/4 Ø9.52 3/8 (3) Piping of indoor unit Gas pipe Liquid pipe Rated capacity of IDU C (Btu/h) mm inch mm inch C ≤9600 Ø9.52 3/8 Ø6.35 1/4 9600 <C ≤17000 Ø12.7 1/2 Ø6.35 1/4 17000 <C ≤48000 Ø15.9 5/8 Ø9.52 3/8 48000 <C ≤55000 Ø19.05 3/4 Ø9.52 3/8 55000 <C ≤96000 Ø22.2 7/8 9.52 3/8 (4) Selection for branching section R410A Refrigerant system Total capacity of downstream indoor units C (Btu/h) Model C ≤68200 FQ01A/A 68200 ≤C ≤102400 FQ01B/A Y type branch 102400 ≤C ≤238800 FQ02/A 238800 ≤C ≤460600 FQ03/A 460600 ≤C FQ04/A 6.5 Charging requirement with additional refrigerant (1) Refrigerant in the system when shipped from the factory Model GMV-24WL/ GMV-28WL/ GMV-36WL/ GMV-48WL/ GMV-60WL/ C-T(U) C-T(U) A-T(U) A-T(U) A-T(U) kg 2.4 2.4 5.0 5.0 6.5 Refrigerant Qty oz 84.7 84.7 176 176 229 (2) Additional refrigerant charge amount =∑Length of liquid pipe × refrigerant charge amount per meter Note: ① The refrigerant amount inside the system before ex-factory doesn’t include the required additional refrigerant charge amount inside the pipeline system of indoor units and the pipeline system connecting indoor unit and outdoor unit. ② For the length of connection pipe in field, the required additional refrigerant charge amount shall be confirmed according to liquid pipe size in field and its length. 18
Dc Inverter Multi VRF System Technical Sales Guide ③ Record additional refrigerant charge amount for future reference. Note: If the total length of liquid pipe is within 20m, no additional refrigerant is needed. When the compressor is not working after ensuring there is no leakage, charge the required additional refrigerant amount to the unit from the valve of liquid pipe of outdoor unit. When the pipe pressure increases and the additional refrigerant can’t be charged to the required amount quickly, please set the unit in cooling operation status and charge refrigerant from the low pressure maintenance port of outdoor unit. WIRING DESIGN 7 7.1 General wiring principle (1) All electrical work shall be done by professionals according to national and local laws and regulations. (2) The unit must be grounded reliably according to the related requirement of GB 50169. (3) Connect wire according to the wiring diagram stuck on the unit. 7.2 Electrical wiring design (1) Wiring drawing (2) Selection of power supply cord and fuse of units Max Fuse Size/ Max Ckt, Bkr Size/ Disjoncteur Max.(A) Min. Circuit Ampacity Model Power supply Fusible Max. (A) GMV-24WL/C-T(U) 208/230V~ 60Hz 25 25 21 GMV-28WL/C-T(U) 208/230V~ 60Hz 30 30 21 GMV-36WL/A-T(U) 208/230V~ 60Hz 35 35 31 GMV-48WL/A-T(U) 208/230V~ 60Hz 45 45 34 GMV-60WL/A-T(U) 208/230V~ 60Hz 60 60 39.8 7.3 Wiring diagram of units 7.4 Parameters (1) Outdoor unit Model GMV-24WL/C-T GMV-28WL/C-T GMV-36WL/A-T GMV-48WL/A-T GMV-60WL/A-T (U) (U) (U) (U) (U) MCA A 21 21 31 34 39.8 MOP A 25 30 35 45 60 19
(2) Indoor unit Low Static Pressure Duct Type Indoor Unit GMV- ND07PLS/ GMV- ND09PLS/ GMV- ND12PLS/ GMV- ND14PLS/ GMV- ND18PLS/ GMV- ND22PLS/ Model A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) MCA A 0.25 0.25 0.25 0.38 0.63 0.63 MOP A 0.45 0.45 0.45 0.68 1.13 1.13 4-way Cassette Indoor Unit Model GMV-ND07T/ GMV-ND09T/ GMV-ND12T/ GMV-ND15T/ GMV-ND18T/ A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) MCA A 0.25 0.25 0.25 0.25 0.31 MOP A 0.45 0.45 0.45 0.45 0.56 Model GMV-ND24T/ GMV-ND30T/ GMV-ND36T/ GMV-ND42T/ GMV-ND48T/ A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) MCA A 0.31 0.44 0.44 0.44 0.44 MOP A 0.56 0.79 0.79 0.79 0.79 Wall Mounted type Indoor Unit Model GMV-N07G/ GMV-N09G/ GMV-N12G/ GMV-N18G/ GMV-N24G/ A3A-D(U) A3A-D(U) A3A-D(U) A3A-D(U) A3A-D(U) MCA A 0.25 0.25 0.26 0.26 0.39 MOP A 0.45 0.45 0.47 0.47 0.70 Legend: MCA: Minimum Circuit Amps MOCP: Maximum Overcurrent Protection(Amps) FLA: Full Load Amps kW: Fan Motor Rated Output(kW) 20
Dc Inverter Multi VRF System Technical Sales Guide ACCESSORIES 8 (1) Outdoor unit Model name Standard Option Provide for oneself GMV-24WL/C-T(U) √ GMV-28WL/C-T(U) √ GMV-36WL/A-T(U) √ GMV-48WL/A-T(U) √ GMV-60WL/A-T(U) √ FQ01A/A Y shape branching joint √ Condensate pipe √ Power cord √ Filter √ Oil return elbow √ Signal wires among units √ (2) Indoor unit Model name Standard Option Provide for oneself XK46 Wired Controller √ YV1L1 remote controller √ YAD1F remote controller √ Screw M4X25 (Cross recessed small pan head screw) √ Drain Hose Assembly √ Union Nut Assembly √ Nut with Washer √ Nut M10 (Type 1 Hex Nut) √ Nut 10 ( Type 1 Hex Nut) √ Heating Jacket of Header √ Heating Jacket of Liquid-in Pipe √ Sponge of Drain Pipe √ Cable Tie √ (3) Controller Model name Standard Option Provide for oneself Wired controller XK62 √ Central controller CE53-24/F(C) √ 21
TECHNICAL SPECIFICATIONS 9 (1) Indoor unitّّ Low Static Pressure Duct Type IDU GMV- ND07PLS/ GMV- ND09PLS/ GMV- ND12PLS/ GMV- ND14PLS/ GMV- ND18PLS/ GMV- ND22PLS/ Model A-T(U) Product Code CM810N0080 CM810N0090 CM810N0100 CM810N0120 CM810N0070 CM810N0110 A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) Btu/h 7500 9500 12000 14000 18000 22000 Cooling Capacity kW 2.2 2.8 3.5 4.0 5.3 6.3 Btu/h 8500 10500 13500 15000 20000 24000 Heating Capacity kW 2.5 3.1 4.0 4.5 5.9 7.1 Casing finish Galvanized Steel plate mm 700×615 ×200 700×615 ×200 700×615 ×200 900×615 ×200 1100×615 ×200 1100×615 ×200 outline inch 27-1/2×24- 1/4×7-7/8 27-1/2×24- 1/4×7-7/8 27-1/2×24- 1/4×7-7/8 35-3/8×24- 1/4×7-7/8 43-1/4×24- 1/4×7-7/8 43-1/4×24- 1/4×7-7/8 Dimensions mm 893×743 ×305 893×743 ×305 893×743 ×305 1123×743 ×305 1323×743 ×305 1323×743 ×305 (W×D×H) Packaging inch 35-1/8×29- 1/4×12 35-1/8×29- 1/4×12 35-1/8×29- 1/4×12 44-1/2×29- 1/4×12 52×29 -1/4×12 52×29- 1/4×12 lbs. 51 51 51 60 69 69 Net Weight kg 23 23 23 27 31 31 lbs. 64 64 64 73 86 86 Gross Weight kg 29 29 29 33 39 39 mm Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø9.52 Ø9.52 Liquid Side inch Ø1/4 Ø1/4 Ø1/4 Ø1/4 Ø3/8 Ø3/8 mm Ø9.52 Ø12.7 Ø12.7 Ø12.7 Ø15.9 Ø15.9 Pipe Connection Gas Side inch Ø3/8 Ø1/2 Ø1/2 Ø1/2 Ø5/8 Ø5/8 mm Ø25 Drain Pipe inch Ø1 Power supply 1-phase 208/230V~60Hz Sound Pressure Level(H/M/L) dB(A) 31/29/25 31/29/25 32/30/27 33/31/28 35/33/30 35/33/30 Heat Exchanger Fenestrate plain film --hydrophilic film Air Filter PP Refrigeration Control Device EXV Protection Device Fuse 22
Dc Inverter Multi VRF System Technical Sales Guideّّ 4-way Cassette Type IDU Model GMV-ND07T/ GMV-ND09T/ GMV-ND12T/ GMV-ND15T/ GMV-ND18T/ A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) Product Code CM500N0520 CM500N0530 CM500N0540 CM810N0130 CM500N0510 Btu/h 7500 9500 12000 15000 18000 Cooling Capacity kW 2.2 2.8 3.5 4.4 5.3 Btu/h 8500 10500 13500 17000 20000 Heating Capacity kW 2.5 3.1 4.0 5 5.9 Casing finish Galvanized Steel plate mm 840×840×190 840×840×240 840×840×240 840×840×240 840×840×240 Body outline inch 33×33×7 1/2 33×33×9-1/2 33×33×9-1/2 33×33×9-1/2 33×33×9-1/2 mm 960×960×257 960×960×310 960×960×310 960×960×310 960×960×310 Body Packaging inch 37-3/4×37- 3/4×10-1/8 37-3/4×37- 3/4×12-1/4 37-3/4×37- 3/4×12-1/4 37-3/4×37- 3/4×12-1/4 37-3/4×37- 3/4×12-1/4 Dimensions mm 950×950×65 950×950×65 950×950×65 950×950×65 950×950×65 (W×D×H) Panel outline inch 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 mm 1030×1035×118 1030×1035×118 1030×1035×118 1030×1035×118 1030×1035×118 Panel Packaging inch 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 lbs. 50 58 58 58 58 Main Body kg 22.5 26.5 26.5 26.5 26.5 Net Weigh lbs. 15-3/8 15-3/8 15-3/8 15-3/8 15-3/8 Panel kg 7.0 7.0 7.0 7.0 7.0 lbs. 64 75 75 75 75 Main Body kg 29 34 34 34 34 Gross Weigh lbs. 24-1/4 24-1/4 24-1/4 24-1/4 24-1/4 Panel kg 11.0 11.0 11.0 11.0 11.0 mm Ø6.35 Ø6.35 Ø6.35 Ø6.35 Ø9.52 Liquid Side inch Ø1/4 Ø1/4 Ø1/4 Ø1/4 Ø3/8 mm Ø9.52 Ø12.7 Ø12.7 Ø12.7 Ø15.9 Pipe Connections Gas Side inch Ø3/8 Ø1/2 Ø1/2 Ø1/2 Ø5/8 mm Ø25 Drain Pipe inch Ø1 Power supply 1-phase 208/230V~60Hz Sound Pressure Level (H/M/L) dB(A) 36/34/31 37/35/32 37/35/32 37/35/32 37/35/32 Heat Exchanger Fenestrate plain film --hydrophilic film Air Filter PP PP PP PP PP Insulation Material Foamed polystyrene Refrigeration Control Device EXV EXV EXV EXV EXV Protection Device Fuse Fuse Fuse Fuse Fuse Panel name TC01 TC01 TC01 TC01 TC01 23
Model GMV-ND24T/ GMV-ND30T/ GMV-ND36T/ GMV-ND42T/ GMV-ND48T/ A-T(U) A-T(U) A-T(U) A-T(U) A-T(U) Product code CM500N0550 CM500N0560 CM500N0570 CM500N0580 CM500N0590 Btu/h 24000 30000 36000 42000 48000 Cooling Capacity kW 7 8.8 10.6 12.3 14.1 Btu/h 27000 34000 40000 47000 54000 Heating Capacity kW 7.9 10 11.7 13.8 15.8 Casing finish Galvanized Steel plate mm 840×840×240 840×840×320 840×840×320 840×840×320 840×840×320 Body outline inch 33×33×9-1/2 33×33×12-5/8 33×33×12-5/8 33×33×12-5/8 33×33×12-5/8 mm 960×960×310 960×960×394 960×960×394 960×960×394 960×960×394 Body Packaging inch 37-3/4×37- 3/4×12-1/4 37-3/4×37- 3/4×15-1/2 37-3/4×37- 3/4×15-1/2 37-3/4×37- 3/4×15-1/2 37-3/4×37- 3/4×15-1/2 Dimensions mm 950×950×65 950×950×65 950×950×65 950×950×65 950×950×65 (W×D×H) Panel outline inch 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 37-3/8×37- 3/8×2-1/2 mm 1030×1035×118 1030×1035×118 1030×1035×118 1030×1035×118 1030×1035×118 Panel Packaging inch 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 40-1/2×40- 1/2×4-5/8 lbs. 58 72 72 72 72 Main Body kg 26.5 32.5 32.5 32.5 32.5 Net Weight lbs. 15-3/8 15-3/8 15-3/8 15-3/8 15-3/8 Panel kg 7.0 7.0 7.0 7.0 7.0 lbs. 75 88 88 88 88 Main Body kg 34 40 40 40 40 Gross Weight lbs. 24-1/4 24-1/4 24-1/4 24-1/4 24-1/4 Panel kg 11.0 11.0 11.0 11.0 11.0 mm Ø9.52 Ø9.52 Ø9.52 Ø9.52 Ø9.52 Liquid Side inch Ø3/8 Ø3/8 Ø3/8 Ø3/8 Ø3/8 mm Ø15.9 Ø15.9 Ø15.9 Ø15.9 Ø15.9 Pipe Connections Gas Side inch Ø5/8 Ø5/8 Ø5/8 Ø5/8 Ø5/8 mm Ø25 Drain Pipe inch Ø1 Power supply 1-phase 208/230V~60Hz Sound Pressure Level(H/ M/L) dB(A) 38/36/33 40/38/35 41/38/36 43/41/38 43/41/38 Heat Exchanger Fenestrate plain film --hydrophilic film Air Filter PP PP PP PP PP Insulation Material Foamed polystyrene Refrigeration Control Device EXV EXV EXV EXV EXV Protection Device Fuse Fuse Fuse Fuse Fuse Panel name TC01 TC01 TC01 TC01 TC01 24
Dc Inverter Multi VRF System Technical Sales Guideّّ Features of Wall Mounted Model GMV-N07G/A3A- GMV-N09G/A3A- GMV-N12G/A3A- GMV-N18G/A3A- GMV-N24G/A3A- D(U) Product code CM100N1480 CM100N1490 CM100N1500 CM100N1510 CM100N1520 D(U) D(U) D(U) D(U) Btu/h 7500 9500 12000 18000 24000 Cooling Capacity kW 2.2 2.8 3.5 5.2 7 Btu/h 8500 11000 13500 20000 25500 Heating Capacity kW 2.5 3.2 4 5.8 7.5 Casing finish Galvanized Steel plate mm 843×180×275 843×180×275 940×200×298 940×200×298 1008×221×319 outline inch 33 1/5×7×10 5/6 33 1/5×7×10 5/6 37×7 7/8×11 3/4 37×7 7/8×11 3/4 39 2/3×8 5/7×12 5/9 Dimensions (W×D×H) mm 973×258×370 973×258×370 1068×288×395 1068×288×395 1131×398×328 Packaging inch 38 1/3×10 1/6×14 4/7 38 1/3×10 1/6×14 4/7 42×11 1/3×15 5/9 42×11 1/3×15 5/9 44 1/2×15 2/3×13 lbs. 22 22 27.6 27.6 33.1 Net Weight kg 10 10 12.5 12.5 15 lbs. 27.6 27.6 33.1 33.1 40.8 Gross Weight kg 12.5 12.5 15 15 18.5 mm Ø6.35 Ø6.35 Ø6.35 Ø9.52 Ø9.52 Liquid Side inch Ø1/4 Ø1/4 Ø1/4 Ø3/8 Ø3/8 mm Ø9.52 Ø9.52 Ø12.7 Ø15.9 Ø15.9 Pipe Connections Gas Side inch Ø3/8 Ø3/8 Ø1/2 Ø5/8 Ø5/8 mm Ø17 Ø17 Ø17 Ø17 Ø17 Drain Pipe inch Ø2/3 Ø2/3 Ø2/3 Ø2/3 Ø2/3 Power supply 1-phase 208/230V~60Hz Sound Pressure Level(H/M/L) dB(A) 38/34/30 38/34/30 44/41/38 44/41/38 44/41/38 Heat Exchanger Fenestrate plain film -- hydrophilic film Air Filter PP+10%BCM+FP03 Insulation Material Foamed polystyrene Refrigeration Control Device EXV Protection Device Fuse 25
(2) Outdoor unit Model GMV-24WL/ GMV-28WL/ GMV-36WL GMV-48WL GMV-60WL C-T(U) C-T(U) /A-T(U) /A-T(U) /A-T(U) kW 7 8.2 11 14.1 17.6 Cooling capacity Btu/h 24000 28000 37500 48000 60000 kW 8.2 8.8 12.3 15.8 19.3 Heating capacity Btu/h 28000 30000 42000 54000 66000 3/h 3900 3900 6000 6300 7800 m Circulating air volume CFM 2295 2295 3532 3708 4601 Noise dB(A) 57 57 55 56 63 Kg 2.4 2.4 5 5 6.5 Refrigerant charge volume oz 84.7 84.7 176 176 229 Power supply 208/230V ~60Hz Cooling kW 2.0 2.7 3.3 4.5 6.1 Rated power input Heating kW 2.4 2.6 3.7 4.4 5.5 mm 980×360×790 900×340×1345 940×320 ×1430 Unit Dimensions (WxDxH) inch 38_6/19×14_3/16×31_2/16 35_3/7×13 _2/5×53 37×12_3 /5×56_2/7 mm 1097×477×937 998×458×1500 1033×433×1580 Dimensions (WxDxH) inch 43_3/16×18_12/16×36_14/16 39_2/7×18 ×59 40_2/3×17 ×62_1/5 Compressor QXFS-D25Zx090H QXAS-F428zX050A LNB53FCFMC Water-proof level IPX4 IPX4 IPX4 IPX4 IPX4 Suitable climite T1 T1 T1 T1 T1 mm Ø15.9 Ø15.9 Ø15.9 Ø15.9 Ø19.05 Gas inch 5/8 5/8 5/8 5/8 3/4 mm Ø9.52 Ø9.52 Ø9.52 Ø9.52 Ø9.52 Connection Liquid pipe inch 3/8 3/8 3/8 3/8 3/8 Connection Method Bell mouth connection Bell mouth connection Bell mouth connection Bell mouth connection Bell mouth connection Kg 80 80 110 110 124 Net weight oz 2822 2822 3880 3880 4375 26
Dc Inverter Multi VRF System Technical Sales Guide FAN CHARACTERISTICS 10 GMV-ND07PLS/A-T(U) Air flow volume(H Air flow volume(M Air flow volume(L GMV-ND09PLS/A-T(U) 25 Extermal static pressur(Pa) 20 Air flow volume(H) 15 Air flow volume(M 10 Air flow volume 5 0 Air volume (Pa) 27
28 GMV-ND12PLS/A-T(U)\GMV-ND14PLS/A-T(U) 25 25 Extermal Extermal static static pressur(Pa) pressur(Pa) 20 20 Air Air flow flow volume(H) volume(H) 15 15 Air Air flow flow volume(M) volume(M) 10 10 Air Air flow flow 5 0 Air Air volume volume (Pa) (Pa) GMV-ND18PLS/A-T(U)、GMV-ND22PLS/A-T(U) 25 Extermal static pressur(Pa) 20 Air flow volume(H) 15 Air flow volume(M Air flow volume 10 5 0
Dc Inverter Multi VRF System Technical Sales Guide
DIMENSIONAL DRAWINGS
11
(1) Indoor unitّّ
Duct Type (include the dimension of main unit, air return case and suspension hole)
The following table lists the detailed dimensions.
Unit: mm(inch)
Item
Model
A
B
C
D
E
F
G
H
I
GMV-ND07PLS/A-T(U)
GMV-ND09PLS/A-T(U)
GMV-ND12PLS/A-T(U)
GMV-ND14PLS/A-T(U)
GMV-ND18PLS/A-T(U)
GMV-ND22PLS/A-T(U)
Installation space:
Unit outline and installation dimension
Gas pipe
Liquid pipe
Electric box
Drain pipe
742
(29-
3/16)
491
(19-
5/16)
700
(27-1/2)
528
(20-
13/16)
161
(6-5/16)
580
(22
13/16)
615
(24-1/4)
200
(7-7/8)
121
(4-3/4)
942
(37-
1/16)
491
(19-
5/16)
900
(35-3/8)
728
(28-
11/16)
161
(6-5/16)
780
(30-
11/16)
615
(24-1/4)
200
(7-7/8)
121
(4-3/4)
1142
(44-
5/16)
491
(19-
5/16)
1100
(43-1/4)
928
(36-
9/16)
161
(6-5/16)
980
(38-
9/16)
615
(24-1/4)
200
(7-7/8)
121
(4-3/4)
150(6)
29Wall Mounted Type 1) Unit outline and installation dimension Model W H D GMV-N07G/A3A-D(U) GMV-N09G/A3A-D(U) 843 (33-1/5) 275 (10-5/6) GMV-N12G/A3A-D(U) GMV-N18G/A3A-D(U) 940 (37) 298 (11-3/4) GMV-N24G/A3A-D(U) 1008 (39-2/3) 221 (8-5/7) 2) Unit installation space Celling Celling Floor Floorّّ Four-way Cassette Indoor Unit D (Distance between lifting screws) Refrigerant pipe A (Decoration panel) B (Ceiling aperture) C (Indoor units) Lifting screw D (Distance between lifting screws) C (Indoor units) B (Ceiling aperture) A (Decoration panel) 30ّّ Unit:mm(inch) 180 (7) 200 (7-7/8) 319 (12-5/9) Wall
Dc Inverter Multi VRF System Technical Sales Guide D (Distance between lifting screws) Refrigerant pipe A (Decoration panel) B (Ceiling aperture) C (Indoor units) Lifting screw D (Distance between lifting screws) C (Indoor units) B (Ceiling aperture) A (Decoration panel) Unit: mm(inch) Model A B C D E G H GMV-ND07T/A-T(U) 950 (37-2/5) 890 (35) 840 (33) 680 (26-7/9) 780 (30-5/7) 65 (2-5/9) 210 (8-1/4) GMV-ND09T/A-T(U) GMV-ND12T/A-T(U) GMV-ND18T/A-T(U) GMV-ND24T/A-T(U) 950 (37-2/5) 890 (35) 840 (33) 680 (26-7/9) 780 (30-5/7) 65 (2-5/9) 260 (10-1/4) GMV-ND30T/A-T(U) GMV-ND36T/A-T(U) GMV-ND42T/A-T(U) GMV-ND48T/A-T(U) 950 (37-2/5) 890 (35) 840 (33) 680 (26-7/9) 780 (30-5/7) 65 (2-5/9) 340 (13-2/5) (2) Outdoor unitّّ Include the required dimension of installation space of main unit and single unit. Model A B C D E GMV-24WL/C-T(U) GMV-28WL/C-T(U) 980(38_6/19) 360(14_3/16) 790(31_2/16) 650(25_3/5) 395(15_5/9) 31
A B D E Unit:mm(inch) Model A B C D E GMV-36WL/A-T(U) GMV-48WL/A-T(U) 900 (35-3/8) 340 (13-3/8) 1345 (53) 572 (22-1/2) 378 (15) 350 (14 7/8)ّّ Installation dimension: GMV-60WL/A-T(U) 940 (37) 320 (12 3/5) 1430 (56 2/7) 632 (24 7/8) Wall Wall ≥200mm (8inch) ≥350mm (13-3/4inch) ≥200mm ≥200mm (8inch) ≥350mm (8inch) ≥2000mm (78-3/4inch) (13-3/4inch) ≥2000mm Shockproof material (78-3/4inch) Wall Wall (3) ranching join Length of each kind of Y-shape branching joint and the dimension of connection pipe port. Y-shape branching joint:FQ01A/A 32
Dc Inverter Multi VRF System Technical Sales Guide Gas pipe Liquid pipe 33
Gree Electric Appliances, Inc. of Zhuhai, founded in 1991, is the world's largest air conditioner enterprise integrating R&D, manufacturing, marketing and services. Technology Innovation and quality are always our priority. With efforts of thousands of Gree's engineers, we own more than 3500 patents for our products. Nowadays, we have 7 production bases in Zhuhai, Chongqing, Hefei and Zhengzhou(China), as well as Brazil, Pakistan and Vietnam, with annual production capacity of 30 million sets of residential air conditioners and 4 million sets of commercial air conditioners. With the installation of Gree commercial air conditioners in important projects at home and abroad like Media Village for 2008 Beijing Olympic Games, Stadiums for 2010 World Cup in South Africa, as well as India Telecom base station, Gree commercial air conditioners are ready to develop steadily to every corner in the world, to present a more comfortable and harmonious working environment and family atmosphere. GREE MAKING BETTER AIR CONDITIONERS GREE MAKING BETTER AIR CONDITIONERS GREE MAKING BETTER AIR CONDITIONER GREE MAKIN BETTER Add: West Jinji Rd,Qianshan Zhuhai,Guangdong,China519070 Tel: (+86-756)8614883 Fax: (+86-756)8614998 Http://www.gree.com Email: gree@gree.com.cn For continous improvement in the products, Gree reserves the right to modify the product specification and appearence in this manual without notice and without incurring and obligations. SJ00422346