Owner's Manual 

Original Instructions 
Commercial Air Conditioners 

DC Inverter Multi VRF System 

Models: 

GMV-24WL/C-T(U) 

GMV-28WL/C-T(U) 

Sayfa 2

Preface 

For correct installation and operation, please read all instructions carefully. Before reading the 

instructions, please be aware of the following items: 

This is the safety alert symbol. It is used to alert you to potential personal injury 
hazards. Obey all safety messages that follow this symbol to avoid possible injury or 
death. 

 
This mark indicates procedures which, if improperly performed, might lead to the 
death or serious injury of the user. 

 
This mark indicates procedures which, if improperly performed, might possibly result 
in personal harm to the user, or damage to property. 

 
NOTICE is used to address practices not related to personal injury. 
 

(1) 
The design standard of multi VRF system conforms to related standard of sales countries.  

(2) 
To ensure safety when operating this system, please strictly follow the instructions in this manual. 

(3) 
The total capacity of running indoor units must not exceed that of the outdoor units. Otherwise, the cooling 
(heating) effect of each IDU would be poor. 
(4) 
Make sure that this manual is kept by direct operators and maintainers. 

(5) 
If the product needs to be installed, moved or maintained, please contact our designated dealer or local service 
center for professional support. Users should not disassemble or maintain the unit by themselves, otherwise it 
may cause relative damage, and our company will bear no responsibilities. 
(6) 
All the illustrations and information in the instruction manual are only for reference. In order to make the product 
better, we will continuously conduct improvement and innovation. If there is adjustment in the product, please 
subject to actual product. 
(7) 
Under the standby status, the unit will consume a little power for ensuring reliability of the complete unit, 
maintaining normal communication and preheating refrigerant. When the unit won’t be used for a long time, 
please cut off the power of the complete unit. However, please preheat it when operating the unit next time. 

User Notice 

DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of 

such waste separately for special treatment is necessary.  

Sayfa 3

Manufacturer will bear no responsibilities when personal injury or property loss is caused by the 

following reasons: 

(1) 
Damage the product due to improper use or misuse of the product. 

(2) 
Alter, change, maintain or use the product with other equipment without abiding by the 

instruction manual of manufacturer. 

(3) 
After verification, the defect of product is directly caused by corrosive gas. 

(4) 
After verification, defects are due to improper operation during transportation of product. 

(5) 
Operate, repair, maintain the unit without abiding by instruction manual or related 

regulations. 

(6) 
After verification, the problem or dispute is caused by the quality specification or 

performance of parts and components that produced by other manufacturers. 

(7) 
The damage is caused by natural calamities, bad using environment or force majeure. 

Exception Clauses 

Sayfa 4

1 Safety Precautions..................................................................................................... 1 

2 Product Introduction ................................................................................................. 2 

2.1 Names of Main Parts ........................................................................................................ 2 

2.2 Combinations of Indoor and Outdoor Units ....................................................................... 2 

2.3 Operating Range .............................................................................................................. 2 

3 Preparation before Installation ................................................................................. 2 

3.1 Standard Parts .................................................................................................................. 3 

3.2 Installation Site ................................................................................................................. 3 

3.3 Piping Work Requirements ............................................................................................... 4 

4 Installation Instruction .............................................................................................. 5 

4.1 Dimension of Outdoor Unit and Mounting Hole ................................................................. 5 

4.2 Connection Pipe ............................................................................................................... 6 

4.3 Installation of Connection Pipe.........................................................................................10 

4.4 Vacuum Pumping, Refrigerant Adding .............................................................................13 

4.5 Electric Wiring ..................................................................................................................15 

5 Check Items after Installation and Test Operation ................................................ 17 

5.1 Check Items after Installation ...........................................................................................17 

5.2 Test Operation and Debugging ........................................................................................17 

6 Common Malfunctions and Troubleshooting ........................................................ 22 

7 Error Indication ........................................................................................................ 24 

8 Maintenance and Care ............................................................................................. 26 

8.1 Outdoor Heat Exchanger .................................................................................................27 

8.2 Drain Pipe ........................................................................................................................27 

8.3 Notice before Seasonal Use ............................................................................................27 

8.4 Maintenance after Seasonal Use .....................................................................................27 

8.5 Parts Replacement ..........................................................................................................27 

9 After-sales Service ................................................................................................... 27 
 
 
 
 

Contents 

Sayfa 5

1 Safety Precautions 

(1) 
This product can’t be installed at corrosive, inflammable or explosive environment or the place with special 
requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of the unit, 
or even cause fire hazard or serious injury. As for above special places, please adopt special air conditioner with 
anti-corrosive or anti-explosion function. 

(2) 
Follow this instruction to complete the installation work. Please carefully read this manual before unit startup and 
service. 

(3) 
Wire size of power cord should be large enough. The damaged power cord and connection wire should be 
replaced by exclusive cable.  

(4) 
After connecting the power cord, please fix the electric box cover properly in order to avoid accident.  

(5) 
Never fail to comply with the nitrogen charge requirements. Charge nitrogen when welding pipes.  

(6) 
Never short-circuit or cancel the pressure switch to prevent unit damage.  

(7) 
Please firstly connect the wired controller before energization, otherwise wired controller can not be used.  

(8) 
Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant leakage, 
electric shock, or fire etc. 

(9) 
Do not insert fingers or objects into air outlet/inlet grille.  

(10) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the gas/oil supplied 

heating equipment is used.  

(11) Never start up or shut off the air conditioner by means of directly plug or unplug the power cord.  

(12) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor.  

(13) Do not allow children operate this unit.  

(14) Do not operate this unit with wet hands.  

(15) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury may happen. 

(16) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen.  

(17) Do not expose the unit to the moist or corrosive circumstances.  

(18) Under cooling mode, please don't set the room temperature too low and keep the temperature difference between 

indoor and outdoor unit within 5℃ (41℉).  

(19) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please contact our 

designated dealer or local service center for help.  

(20) Before installation, please check if the power supply is in accordance with the requirements specified on the 

nameplate. And also take care of the power safety.  

(21) Installation should be conducted by dealer or qualified personnel. Please do not attempt to install the unit by 

yourself. Improper handling may result in water leakage, electric shock or fire disaster etc. 

(22) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire accidents.  

(23) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid electric 

shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone line.  

(24) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off the power 

when 24 hours short-time halting (to protect the compressor).  

(25) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will emerge if the 

refrigerant gas meets fire.  

(26) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little neutral 

detergent to clean the outer casing of unit.  

(27) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main power supply, 

and then immediately contact our designated dealer or local service center. If abnormality keeps going, the unit 
might be damaged and lead to electric shock or fire.  

If the product needs to be installed, moved or maintained, please contact our designated dealer 

DC Inverter Multi VRF System 

1 

Sayfa 6

DC Inverter Multi VRF System 

or local service center for professional support, otherwise our company would bear no legal reliability 

for the related damages arising therefrom. 

2 Product Introduction 

Gree Multi VRF System adopts inverter compressor technology. By changing the displacement 

of compressor, stepless capacity regulation within range of 10%~100% can be realized. Various 

product lineups are provided with capacity range from 7kW to 8kW, which can be widely used in 

residential, commercial and working area and especially applicable to places with big load change. 

Gree residential air conditioner is absolutely your best choice. 

2.1 Names of Main Parts 

No. 
① 
② 
③ 
④ 
⑤ 

Name 
Motor 
Fan blade 
Electric box assembly 
Gas pipe valve 
Liquid pipe valve 

2.2 Combinations of Indoor and Outdoor Units 

(1) 
See below the number of indoor units that can be connected to the outdoor unit. 

(2) 
The total capacity of indoor units should be within 50%~135% of that of the outdoor unit. 

Model 
Max sets of connectable IDUS 

GMV-24WL/C-T(U) 
4 

GMV-28WL/C-T(U) 
4 

(3) 
Can be connected to various indoor units. When any one of the indoor units receives 

operating command, outdoor unit will start operation as per required capacity. When all 

indoor units stop, outdoor unit will be shut off. 

2.3 Operating Range 

Cooling 
Outdoor temperature: -5°C~48°C(23°F~118°F) 

Heating 
Outdoor temperature: -20°C~27°C(-4°F~81°F) 

3 Preparation before Installation 

Graphics here are only for reference. Please refer to actual products. Unspecified dimensions are all 

in mm/inch. 

Fig.1 

2 

Sayfa 7

3.1 Standard Parts 

Please use the supplied standard parts as required. 

No. 
Name 
Appearance 
Qty 
Remark 

1 
User Manual 
 
1 
— 

2 
Wiring (match with 
resistance) 
 
1 
Must be connected to the 
last IDU of communication 
connection 

3 
Corrugated pipe 
 
1 
— 

4 
Chassis gluey plug 
 
3 
— 

5 
Drainage joint 
 
1 
— 

6 
Tube Connector 
Sub-assy 
 
1 
GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

Some accessories are not available for some models. Please refer to the present product for details. 

3.2 Installation Site 

(1) 
The unit must be installed where strong there is a danger the weight of the unit and fixed securely, otherwise the 
unit would topple or fall off.  

(2) 
Do not install where there is a danger of combustible gas leakage.  

(3) 
Do not install the unit near heat source, steam, or flammable gas.  

(4) 
Children under 10 years old must be supervised not to operate the unit.  

(5) 
Select a location which is out of children’s reach. Keep the unit away from children. 

(6) 
Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with good 
ventilation. 

(7) 
Install the unit where it will not be tilted by more than 5°. 

(8) 
During installation, if the outdoor unit has to be exposed to strong wind, it must be fixed securely. 
 

(1) 
If possible, do not install the unit where it will be exposed to direct sunlight (If necessary, install a blind that does 
not interfere with the air flow). 

(2) 
Install ODU in a place where it will be free from getting dirty or getting wet by rain as much as possible. 

(3) 
Install ODU where it is convenient to connect IDU.  

(4) 
ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and reduce bend angles. 

(5) 
Install ODU where the condensate water can be drained out freely during heating operation. Do not place 
animals and plants in the path of the warm air. 

(6) 
Take the air conditioner weight into account and select a place where noise and vibration are small. 
 

DC Inverter Multi VRF System 

Parts for Outdoor Unit 

3 

Sayfa 8

DC Inverter Multi VRF System 

If the ODU is totally surrounded by walls, please refer to the following figures for space 

dimension: 

Fig. 2 

3.3 Piping Work Requirements  

Refer to the table below for piping work requirements: 

R410A  Refrigerant System 

Outer diameter (mm/inch) 
Wall thickness (mm/inch) 

Φ6.35 (1/4) 
≥0.8(1/32) 

Φ9.52 (3/8) 
≥0.8(1/32) 

Φ12.70 (1/2) 
≥0.8(1/32) 

Φ15.9(5/8) 
≥1.0(1/25) 

Φ19.05 (3/4) 
≥1.0(1/25) 
 

4 

Unit: mm(inch) 

Sayfa 9

4 Installation Instruction 

Graphics here are only for reference. Please refer to actual products. Unspecified dimensions are all 

in mm/inch. 

4.1 Dimension of Outdoor Unit and Mounting Hole 

Unit Outline and Installation Dimension (mm/inch). 

Model 
A 
B 
C 
D 
E 

395 
(15-5/9) 
 

GMV-24WL/C-T(U) 
GMV-28WL/C-T(U) 

DC Inverter Multi VRF System 

Fig.3 

Unit: mm/inch 

980 
(38-6/19) 

360 
(14-3/16) 

790 
(31-2/16) 

650 
(25-3/5) 

5 

Sayfa 10

DC Inverter Multi VRF System 

4.2 Connection Pipe 

4.2.1 Schematic Diagram of Piping Connection 

Fig.4 

6 

Sayfa 11

4.2.2 Allowable Length and Height Difference of Connection Pipe 

Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown 

in the figure below: 

Equivalent length of one Y-type branch is 0.5m(1-5/8feet). 

Fig.5 Allowable Length and Height Difference of Connection Pipe 

Piping parameters of GMV-24WL/C-T(U), GMV-28WL/C-T(U).  

Allowable value 

Fitting pipe 
m 
feet 

Total length (actual length) of fitting pipe 
250 
820 
L1+L2+L3+a+b+c+d 

Actual 
length 
100 
328 
L1+L2+L3+d 
Equivalent 

Length of farthest fitting pipe (m) 

length 
120 
394 

From the 1st branch to the farthest indoor pipe 
40 
131 
L2+L3+d 

ODU at 
upper side 
30 
98 
—— 

Height difference between ODU and 

IDU 

ODU at 
lower side 
30 
98 
—— 

Height difference between IDUs 
10 
33 
—— 
 

7 

DC Inverter Multi VRF System 

Sayfa 12

DC Inverter Multi VRF System 

4.2.3 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor Branch 

Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of 

outdoor connection pipe. 

Dimension of outdoor connection pipe. 

Basic module 

GMV-24WL/C-T(U) 
Φ15.9(5/8) 
Φ9.52(3/8) 

GMV-28WL/C-T(U) 
Φ15.9(5/8) 
Φ9.52(3/8) 

4.2.4 Selection of Indoor Branches 

Select indoor branches according to the total capacity of downstream indoor units. If the capacity 

exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

R410A Refrigerant system 
Total capacity of downstream indoor units X (kW) 
Model 

Y type branch 

135<X 
FQ04 
 

Fig.6 

Pipe dimension 

Gas pipe (mm/inch) 
Liquid pipe (mm/inch) 

Fig.7 

X<20 
FQ01A 

20≤X≤30 
FQ01B 

30<X≤70 
FQ02 

70<X≤135 
FQ03 

8 

Sayfa 13

4.2.5 Dimension of Pipe between Indoor Branches 

Select pipe between indoor branches according to the capacity of downstream indoor units; if the 

capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails. 

Total capacity of downstream indoor units C (kW) 
Gas pipe (mm/inch) 
Liquid pipe (mm/inch) 

C≤5.6 
Φ12.7(1/2) 
Φ6.35(1/4) 

5.6<C≤14.2 
Φ15.9(5/8) 
Φ9.52(3/8) 

14.2<C≤22.4 
Φ19.05(1/4) 
Φ9.52(3/8) 

4.2.6 Dimension of Pipe between Indoor Branch and IDU 

Dimension of pipe between indoor branch and IDU should be consistent with the dimension of 

indoor pipe. 

Rated capacity of IDU C(Btu/h) 
Gas pipe (mm/inch) 
Liquid pipe (mm/inch) 

C≤9600 
Φ9.52(3/8) 
Φ6.35(1/4) 

9600<C≤17000 
Φ12.7(1/2) 
Φ6.35(1/4) 

17000<C≤48000 
Φ15.9(5/8) 
Φ9.52(3/8) 

48000<C≤55000 
Φ19.05(3/4) 
Φ9.52(3/8) 

55000<C≤96000 
Φ22.2(7/8) 
Φ9.52(3/8) 

If the distance between IDU and its nearest branch is over 10m, then the liquid pipe of IDU (rated 

capacity ≤17000 Btu/h) shall be enlarged. 

DC Inverter Multi VRF System 

Fig. 8 

Fig. 9 

9 

Sayfa 14

DC Inverter Multi VRF System 

4.3 Installation of Connection Pipe 

4.3.1 Precautions for the Installation of Connection Pipe 

(1) 
Conform to the following principles during pipe connection: Connection pipe should be as 

short as possible, so is the height difference between indoor and outdoor units. Keep the 

number of bends as little as possible. Radius of curvature should be as large as possible. 

(2) 
Weld the connection pipe between indoor and outdoor units. Please strictly follow the 

requirements for welding process. Rosin joint or pin hole is not allowed. 

(3) 
Radius of bending parts should be over 200mm(8inch). Note that pipes cannot be 

repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch 

the pipe for more than 3 times at the same position. 

4.3.2 Flaring Process 

(1) 
Use pipe cutter to cut the connection pipe in case it is unshaped. 

(2) 
Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after 

cutting. 

(3) 
Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use flaring 

tool to fix the flared nut into the pipe (as shown in Fig.10). 

(4) 
Check if the flared part is flaring evenly and if there is any crack. 

4.3.3 Pipe Bending 

(1) 
Reshape the pipe by hand. Be careful not to damage the pipe. 

                Fig. 11                                       Fig. 12 

(2) 
Do not bend the pipe over 90°. 

(3) 
If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch again. 

Therefore, do not bend or stretch the bend for over 3 times. 

(4) 
In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the 

insulating layer, as shown in Fig.12. Do not bend the pipe until it is exposed. When bending 

is done, wrap the pipe with insulating layer and then secure it with adhesive tape. 

Fig. 10 

10 

Sayfa 15

4.3.4 Indoor Pipe Connection 

(1) 
Remove pipe cover and pipe plug. 

(2) 
Direct the flared part of copper pipe to the center of screwed joint. Twist on the flared nut 

tightly by hand, as in Fig.13 (Make sure indoor pipe is correctly connected. Improper 

location of the center will prevent flared nut from being securely twisted. Thread of nut will 

get damaged if the flared nut is twisted forcibly). 

(3) 
Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound 

(Hold the handle of wrench and make it at right angle to the pipe. as in Fig.14). 

(4) 
Use sponge to wrap the un-insulated connection pipe and joint. Then tie the sponge tightly 

with plastic tape. 

(5) 
Connection pipe should be supported by a bearer rather than the unit. 

(6) 
The bending angle of piping should not be too small; otherwise the piping might have 

cracks. Please use a pipe bender to bend the pipe. 

(7) 
When connecting IDU with connection pipe, do not pull the big and small joints of IDU with 

force in case the capillary tube or other tubes have cracks and cause leakage. 

Fig. 13               Fig. 14 

4.3.5 Outdoor Pipe Connection 

Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as for 

indoor pipe connection. 

During engineering installation, the connection pipe inside the unit must be wrapped by insulation 

sleeve. 

Below is the piping diagram of GMV-24WL/C-T(U), GMV-28WL/C-T(U). According to customer 

requirement or space limit, outlet pipe can be installed from the front, right or rear side. 

DC Inverter Multi VRF System 

Pipe Diameter 
Tightening Torque 

6mm(1/4inch) 
15-30N·m(11-22ft.-1b.) 

9.5mm(3/8 inch) 
35-40N·m(26-29ft.-1b.) 

12.7mm(1/2 inch) 
45-50N·m(33-37ft.-1b.) 

16mm(5/8 inch) 
60-65N·m(44-48ft.-1b.) 

Fig.15 

11 

Sayfa 16

DC Inverter Multi VRF System 

4.3.6 Installation of Y-type Branch 

(1) 
Y-type Branch. 

(2) 
Y-type branch has several pipe sections with different dimension, which facilitates to match 

with various copper pipes. Use pipe cutter to cut in the middle of the pipe section that is of 

proper dimension and remove burrs as well. See Fig.17. 

(3) 
Y-type branch must be installed vertically or horizontally. 

(4) 
Branch shall be isolated by insulating material that can bear 120°C(248°F) or even higher 

temperature. The attached foam of branch cannot be taken as insulating material. 

4.3.7 Thermal Insulation for Pipeline 

(1) 
For multi VRF system, every copper pipe should be labeled so as to avoid misconnection. 

(2) 
At the branch inlet, leave at least 500mm(19-3/4inch) straight pipe section. 

(3) 
Thermal insulation for pipeline. 

1) 
To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid 

pipe must be wrapped with thermal insulating material and adhesive tape for insulation 

from the air. 

2) 
Thermal insulating material shall be able bear the pipe temperature. For heat pump 

unit, liquid pipe should bear 70°C(158°F) or above and gas pipe should bear 

120°C(248°F) or above. For cooling only unit, both liquid pipe and gas pipe should 

bear 70°C (158°F) or above. 

3) 
Example: Polyethylene foam (bear 120°C(248°F) or above); foaming polyethylene 

Fig. 16 

Fig. 17 

12 

Sayfa 17

(bear 100°C(212°F) or above). 

4) 
Joints of indoor and outdoor unit should be wrapped with insulating material and leave 

no gap between pipe and wall. See Fig.18. 

Fig. 18 
5) 
Thermal insulating material of branches should be the same as that of the pipeline. 

The attached foam of branches cannot be taken as insulating material. 

6) 
When wrapping the tape, the later circle should cover half of the former one. Don’t 

wrap the rape too tight, otherwise the insulation effect will be weakened. 

7) 
After wrapping the pipe, apply sealing material to completely seal the hole on the wall. 

4.3.8 Support and Protection of Pipeline 

(1) 
Support should be made for hanging connection pipe. Distance between each support 

cannot be over 1m. 

(2) 
Protection against accidental damage should be made for outdoor pipeline. When pipeline 

exceeds 1m, a pinch board should be added for protection. 

4.4 Vacuum Pumping, Refrigerant Adding 

4.4.1 Vacuum Pumping 

(1) 
Outdoor unit has been charged with refrigerant before delivery. Field-installed connection 

pipe needs to be charged with additional refrigerant. 

(2) 
Confirm whether outdoor liquid and gas valves are closed. 

(3) 
Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the 

outdoor valve, as shown below. 

DC Inverter Multi VRF System 

Fig. 19 

13 

Sayfa 18

DC Inverter Multi VRF System 

4.4.2 Refrigerant Adding 

(1) 
Refrigerant quantity of outdoor unit before delivery: 

Model 
GMV-24WL/C-T(U), GMV-28WL/C-T(U) 

Refrigerant Qty (kg) 
2.4 
 

(1) 
The refrigerant amount charged before delivery doesn’t include the amount that needs to be added to indoor 
units and the connection pipeline. 
(2) 
Length of connection pipe is decided on site. Therefore the amount of additional refrigerant shall be decided on 
site according to the dimension and length of field-installed liquid pipe. 

(3) 
Record the amount of additional refrigerant for convenience of after-sales service. 

(2) 
Calculation of the amount of additional refrigerant. 

Calculation method of the quantity of additional refrigerant (based on liquid pipe) 

Quantity of additional refrigerant = ∑length of liquid pipe × quantity of additional refrigerant per 

meter(39-3/8inch) +(quantity of indoor unit -2) ×0.3 

Quantity of additional refrigerant per meter for liquid pipe (kg/m)/(oz/inch) 

Φ22.2(Φ7/8) 
Φ19.05(Φ3/4) 
Φ15.9(Φ5/8) 
Φ12.7(Φ1/2) 
Φ9.52(Φ3/8) 
Φ6.35(Φ1/4) 

0.35 
0.25 
0.17 
0.11 
0.054 
0.022 

0.314 
0.224 
0.152 
0.099 
0.048 
0.020 

First confirm that there is no leakage from the system. When compressor is not working, charge 

additional R410A with specific amount to the unit through the filling opening of the liquid pipe valve of 

the outdoor unit. If required amount cannot be quickly filled due to pressure increase of the pipe, then 

set the unit in cooling startup and fill refrigerant from the low pressure check valve of the outdoor unit.  

(3) 
Calculation example. 

Fig. 20 

IDU:  

No. 
IDU ① 
IDU ② 
IDU ③ 
IDU ④ 

Model 
Duct type 
GMV-ND72PL/B-T 

Duct type 
GMV-ND50PL/B-T 

Duct type 
GMV-ND36PL/B-T 

Liquid pipe: 

No. 
A 
B 
C 
D 

Pipe size 
Φ9.52(Φ3/8) 
Φ9.52(Φ3/8) 
Φ9.52(Φ3/8) 
Φ6.35(Φ1/4) 

14 

Duct type 
GMV-ND25PL/B-T 

Sayfa 19

Length 
10m(32-3/4feet) 
5m(16-3/8feet) 
5m(16-3/8feet) 
5m(16-3/8feet) 

No. 
a 
b 
c 
d 

Pipe size 
Φ9.52(Φ3/8) 
Φ6.35(Φ1/4) 
Φ6.35(Φ1/4) 
Φ6.35(Φ1/4) 

Length 
3m(9-3/4feet) 
3m(9-3/4feet) 
2m(6-5/8feet) 
1m(3-1/4feet) 

Total length of each liquid pipe 

Φ9.52: A+B+C+a=10+5+5+3=23m (75-1/2 feet) 

Φ6.35: D+b+c+d=5+3+2+1=11m(36feet) 

Quantity of indoor unit: 4 sets 

Therefore, the minimum quantity of additional refrigerant = (23×0.054+11×0.022) +(4-2) ×0.3= 

2.084kg 

4.5 Electric Wiring 

4.5.1 Notices for Wiring 

(1) 
Install units according to national wiring codes. 

(2) 
Use air conditioner specialized power supply and make sure that it is consistent with 

system’s rated voltage. 

(3) 
Do not pull the power cord with force. 

(4) 
All electrical installation must be performed by qualified technicians in accordance with local 

laws, regulations and this user manual. 

(5) 
Caliber of the power cord must be large enough. A damaged power cord or connection wire 

must be replaced by specialized electrical cords. 

(6) 
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent 

or a similarly qualified person in order to avoid a hazard. 

(7) 
An all-pole disconnection device which has at least 3mm (3/25 inch) clearances in all poles, 

and disconnection must be incorporated in the fixed wiring in accordance with the wiring 

rules. 

(8) 
Details of type and rating for fuse:  

Model: GMV-24WL/C-T(U), GMV-28WL/C-T(U). 

Ceramic 250V5A (front main board), ceramic 250V30A (front main board). 

Connect the unit to specialized grounding device and make sure it is securely grounded. It’s a 

must to install air switch and current circuit breaker that can cut off the power of the entire system. 

The circuit breaker should include magnetic trip function and thermal trip function so that system can 

be protected from short circuit and overload.  

(9) 
Grounding Requirements. 

1) 
Air conditioner belongs to class I electrical appliance, so it must be securely grounded. 

2) 
The yellow-green wire inside the unit is a ground wire. Do not cut it off or secure it with 

tapping screws, otherwise it will lead to electric shock. 

3) 
Power supply must include secure grounding terminal. Do not connect the ground wire 

to the following: 

①Water pipe; ②Gas pipe; ③Drain pipe; 

④Other places that are deemed as not secure by professional technicians. 

DC Inverter Multi VRF System 

15 

Sayfa 20

DC Inverter Multi VRF System 

4.5.2 Wiring Diagram 

(1) 
Connection of power cord and communication wire Separate power supply for IDU and 

ODU Single-phase power supply unit. 

GMV-24WL/C-T(U), GMV-28WL/C-T(U):  

Fig.21 Connection of power cord and communication wire for IDU and ODU 

(2) 
Selection of circuit breaker and power cord. 

Model 
Power supply 

GMV-24WL/C-T(U) 
208/230V~ 60Hz 
25 
25 
21 

GMV-28WL/C-T(U) 
208/230V~ 60Hz 
30 
30 
21 
 

(1) 
Selection of circuit breaker and power cord in the above table is based upon unit’s maximum power (maximum 
current). 
(2) 
Specification of power cord is based on the working condition where ambient temperature is 40°C (104°F) and 
multi-core copper cable (working temperature is 90°C (194°F), e.g. power cable with YJV cross-linked copper, 
insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes, please adjust the 
specification according to national standard. 
(3) 
Specification of circuit breaker is based on the working condition where ambient temperature of circuit breaker is 
40°C (104°F). If working condition changes, please adjust the specification according to national standard. 

4.5.3 Engineering Wiring of Power Supply and Communication Cable 

(1) 
Please refer Fig. 22 for engineering wiring. If there is the hole for cable tie in wiring route, 

please fix the wire with cable tie. Connect the power cord and communication cable to the 

corresponding terminal board and grounding screw according to the wiring diagram. 

(2) 
Please be noted that engineering wiring cannot touch the pipe and appliance. 

(3) 
This figure is only applicable for engineering wiring reference of power supply and 

communication cable. If there are differences between the figure structure and actual unit, 

please refer to the actual unit. 

Max Fuse 
Size/Fusible Max. 

Max Ckt, Bkr 
Size/Disjoncteur Max. 

Min. Circuit Ampacity 

(A) 

(A) 

(A) 

16 

Sayfa 21

(4) 
For engineering wiring, please refer to the wiring diagram provided with the unit. 

Fig. 22 Engineering Wiring View of GMV-24WL/C-T(U), GMV-28WL/C-T(U) 

5 Check Items after Installation and Test Operation 

5.1 Check Items after Installation 

Check items 
Possible conditions due to improper installation 
Check 

Each part of the unit is installed securely? 
Unit may drop, shake or emit noise. 
 

Gas leakage test is taken or not? 
Insufficient cooling (heating) capacity. 
 

Unit gets proper thermal insulation or not? 
There may be condensation and dripping. 
 

Drainage is smooth or not? 
There may be condensation and dripping. 
 

Is the voltage in accordance with the rated voltage 
specified on the nameplate? 

Is the electric wiring and pipe connection installed 
correctly? 

Unit is securely grounded or not? 
Electrical leakage. 
 

Power cord meets the required specification? 
Unit may have malfunction or components may get 
damaged. 
 

Is the air inlet/outlet blocked? 
Insufficient cooling (heating) capacity. 
 

Length of refrigerant pipe and the charging amount 
of refrigerant are recorded or not? 
The refrigerant charging amount is not accurate. 
 

Binding pieces on compressor feet are removed or 
not? 
Compressor may get damaged. 
 

5.2 Test Operation and Debugging 

(1) 
After finishing the first installation or replacing the main board of outdoor unit, it is necessary to perform test 
operation and debugging. Otherwise, unit won’t be able to work. 
(2) 
Test operation and debugging must be performed by professional technicians or under the guidance of 
professional technicians. 

5.2.1 Prepare the Test Operation and Debugging 

(1) 
Do not connect power until all installation work is finished. 

(2) 
All control circuits and wires are correctly and securely connected. 

(3) 
Check whether the fixing loops for compressor foots are removed. 

(4) 
All small pieces, especially metal chips, thread ends and forceps holder, must be removed 

from the unit. 

DC Inverter Multi VRF System 

Unit may have malfunction or components may get 
damaged. 
 

Unit may have malfunction or components may get 
damaged. 
 

17 

Sayfa 22

DC Inverter Multi VRF System 

(5) 
Check whether unit’s appearance and pipeline system has been damaged during 

transportation. 

(6) 
Calculate the quantity of refrigerant that needs to be added according to the pipe length. 

Pre-charge the refrigerant. In case that the required charging quantity is not reached while 

refrigerant can’t be added, record the quantity of refrigerant that still needs to add and 

complement the quantity during test operation. For details of adding refrigerant during test 

operation, see below. 

(7) 
After refrigerant is added, make sure valves of outdoor unit are completely open. 

(8) 
For the convenience of troubleshooting during debugging, unit shall be connected to a PC 

with applicable debugging software. Make sure unit’s real-time data can be checked 

through this computer. The installation and connection of debugging software can be found 

in the Service Manual. 

(9) 
Before test operation, make sure unit is power on and compressor has been preheated for 

more than 8 hours. Touch the unit to check whether it’s normally preheated. If yes, start test 

operation. Otherwise, compressor might be damaged. 

5.2.2 Test Operation and Debugging 

Description of test operation procedures and main board display of ODU. 

Description of each stage of debugging progress 

—— 
Debugging code 

Code meaning and operation method 
Progress 

LED 

Code 
Display status 

A0 
ON 
System is not debugged, hold main board’s SW3 button for 5s 
to start debugging. 

01_Set master 
unit 

01 
ON 
2s later, next step starts. 

02/Ad 
Display 
circularly 
System is allocating addresses. 10s later, display as below: 

No master indoor unit. Display will be on for 1min, during 
which master IDU can be set manually. If not, system will set 
the unit with minimum IP address as the master IDU. 

02_ Allocate 
addresses 

02/L7 
Display 
circularly 

02/oC 
Display 
circularly 
Allocation is finished. 2s later, next step starts. 

03_ Confirm the 
quantity of ODU 
03/01 
Display 
circularly 
System is confirming. 1s later, next step starts. 

“00~16” displays the quantity of indoor unit. Confirm the 
number manually. If the number is not consistent the display 
one, cut off power of IDU and ODU and check whether 
communication wire of IDU is correctly connected. After the 
check, connect power and start debugging from progress 01. 
If the number is then correct, press main board’s SW3 button 
to confirm. Then the display is as below: 

04/00~16 
Display 
circularly 

04_ Confirm the 
quantity of IDU 

04/oC 
Display 
circularly 
System has confirmed the quantity. 2s later, next step starts. 

18 

Sayfa 23

Description of each stage of debugging progress 

—— 
Debugging code 

Code meaning and operation method 
Progress 

LED 

Code 
Display status 

Communication between master ODU and driver has error. 
Check the communication connection of ODU’s main board 
and drive board. When the error is eliminated, start next step. 
If power is off during troubleshooting, then restart debugging 
from progress 01 after power is on.   

05/C2 
Display 
circularly 

Communication of master ODU and driver is normal. Unit will 
display as in the left for 2s and detect the capacity ratio of IDU 
and ODU. If the ratio is within range, then next step will start 
2s later. If the ratio is out of range, unit will display as below: 

05_ Detect ODU’s 
internal 
communication 
and capacity ratio 

05/oC 
Display 
circularly 

Rated capacity ratio of IDU is too high. Change the 
combination way of IDU and ODU to make the ratio within 
range. And restart debugging from progress 01. 

05/CH 
Display 
circularly 

Rated capacity ratio of IDU is too low. Change the 
combination way of IDU and ODU to make the ratio within 
range. And restart debugging from progress 01. 

05/CL 
Display 
circularly 

Outdoor component’s error. Besides “06”, the other blinking 
will display the related error code. After errors are eliminated, 
system will start next step automatically. If power is off during 
troubleshooting, then restart debugging from progress 01 after 
power is on. 

06/error code 
Display 
circularly 

06_ Detect 
outdoor 
components 

06/oC 
Display 
circularly 

System detects no error on outdoor component. 10s later, 
next step starts. 

System detects error on indoor components. XX means the 
project code of IDU with error, e.g. no.1 IDU has d5 and d6 
errors, meanwhile no.3 IDU displays error d6 and d7, then the 
nixie tube will display “07”, “01”, “d5”, “d6” and “03” circularly. 
After errors are eliminated, system will start next step 
automatically. If power is off during troubleshooting, then 
restart debugging from progress 01 after power is on. 

07/XX/error 
code 

Display 
circularly 

07_ Detect indoor 
components 

If errors occur in IDU which the project code is ≥ 3-digit 
number, then it will display the 2 big digits of project code first, 
then the 2 small digits, finally the error code, e.g: L1 error 
occurs in no.101 IDU, and then the nixie tube will display 
“01”,“01” and “L1” circularly. Display method is the same for 
several IDUs with multiple errors. 

07/XXXX/error 
code 

Display 
circularly 

07/oC 
Display 
circularly 
No error on components of IDU. 5s later, next step starts. 

Preheat time for compressor is less than 8 hours. Display will 
be as in the left until the preheat time reaches 8 hours. Press 
main board’s SW3 button to confirm manually that the preheat 
time has reached 8 hours. Then start next step (Note: 
Compressor may get damaged if it is started without 8 hours 
of preheat time). 

08/U0 
Display 
circularly 

08_ Confirm 
preheated 
compressor 

08/oC 
Display 
circularly 

Compressor has been preheated for 8 hours. 2s later, next 
step starts. 

System is lack of refrigerant and display will be as in the left. 
Please cut off power of IDU and ODU and check if there is 
leakage on pipeline. Solve the leakage problem and 
complement refrigerant into the unit. Then connect power and 
restart debugging from progress 01 (Note: Before re-charging 
refrigerant, unit must be power off in case system starts 
progress 10 automatically). 

09/U4 
Display 
circularly 

09_ Refrigerant 
judgments before 

startup 

09/oC 
Display 
circularly 

Refrigerant is normal and unit will display as in the left for 2s. 
Then next step starts. 

19 

DC Inverter Multi VRF System 

Sayfa 24

DC Inverter Multi VRF System 

Description of each stage of debugging progress 

—— 
Debugging code 

Code meaning and operation method 
Progress 

LED 

Code 
Display status 

Valves of ODU are being inspected. Compressor will start 
operation for 2min or so and then stop. The opening and 
closing status of outdoor valves are as below: 

10/on 
Display 
circularly 

Outdoor valves are not fully turned on. Press main board’s 
SW4 button and display shows “09/OC”. Then check if the gas 
and liquid valves of ODU are completely open. After 
confirmation, press the SW4 button again. Then compressor 
will start running for about 2min to inspect the status of valves. 

10_ Status 
judgments of 
outdoor valves 

10/U6 
Display 
circularly 

before startup 

10/oC 
Display 
circularly 

Valves status is normal. Unit will display as in the left for 2s 
and then start next step. 

Ready for units to start debugging. Press main board’s SW3 
button to confirm startup of debugging. 2s later, main board 
will display as below: 

12/AP 
Display 
circularly 

Startup is confirmed. After displaying for 2s, system will 
choose “15_ Cooling debugging” or “16_ Heating debugging” 
according to ambient temperature. If the project requests to 
add refrigerant but it is not complemented before debugging, 
then refrigerant can be added in this process through the 
L-VALVE. 

12_ Confirm 
debugging startup 

12/AE 
Display 
circularly 

Debugging for cooling mode. If no malfunction occurs for 
50min when compressor is running, then the system is 
certified as normal. After shutting down the unit for 5s, the 
system will enter normal standby status. 

15/AC 
Display 
circularly 

15_ Cooling 
debugging 

15/error code 
Display 
circularly 
Malfunction occurs when debugging for cooling mode. 

Debugging for heating mode. If no malfunction occurs for 
50min when compressor is running, then the system is 
certified as normal. After shutting down the unit for 5s, the 
system will enter normal standby status. 

16/AH 
Display 
circularly 

16_ Heating 
debugging 

16/error code 
Display 
circularly 
Malfunction occurs when debugging for heating mode. 

17_ Debugging 
finished 
oF 
ON 
The entire unit has finished debugging and under standby-by 
condition. 
 

20 

Sayfa 25

DC Inverter Multi VRF System 

5.2.3 Appendix: Reference of normal operation parameters 

No 
Debug item 
Parameter name 
Unit 
Reference 

Outdoor 
temperature 
°C(°F) 
—— 

1 

 When compressor starts, discharge temp in cool mode 

is within 70~105°C(158~221°F) and at least 
10°C(50°F) higher than the high pressure saturation 
temp. 
 As for temp in heat mode, it is within 

2 
Compressor 
discharge temp 
°C(°F) 

65~90°C(149~194°F) and at least 10°C(50°F) higher 
than the high pressure saturation temp. 

 In cool mode, defrosting temp is 4~10°C(39~50°F) 

lower than system’s high pressure value. 
 In heat mode, defrosting temp is about 2°C(36°F) 

3 
Defrosting temp 
°C(°F) 

different from system’s low pressure value. 

 In cool mode, the normal high pressure value is within 

20°C~55°C(68~131°F). According to the change of 
ambient temp and system’s operating capacity, the high 
pressure value will be 10°C~30°C(50~86°F) higher 
than ambient temp. The higher ambient temp is, the 
smaller temp difference is. If ambient temp is 25~35°C 
(77~95°F) in cool mode, system’s high pressure value 
will be within 44~53°C(111~127°F). 
 In heat mode, if ambient temp is above -5°C(23°F), 

4 
System high 

pressure 
°C(°F) 

ODU 
parameters 

system’s high pressure value is within 
40~52°C(104~126°F). If ambient temp is low and many 
IDUs are turned on, the high pressure will be lower. 

System parameters 

 When ambient temp in cool mode is 

25~35°C(77~95°F), the low pressure value is 
0~8°C(32~46°F). 
 When ambient temp in heat mode is above -5°C(23°F), 

5 
System low 

pressure 
°C(°F) 

the low pressure value is -15~8°C(5~46°F). 

 In cool mode, the thermal electronic expansion valve 

6 
Opening angle 
of thermal EXV 
PLS 

remains 480PLS. 
 In heat mode, the adjustable opening angle of EXV is 

40~480PLS. 

7 
Compressor’s 
operating freq 
Hz 
Changes in 10Hz~80Hz. 

8 
Compressor’s 

A 
When compressor works normally, the current is no more 
than 18.4A. 

operating 

current 

When ambient temp is below 35°C(95°F), IPM temp is 
lower than 80°C(176°F) and the highest temp won’t be 
above 95°C(203°F). 

9 
Compressor’s 

IPM temp 
°C 

10 
Fan motor’s 
operating freq 
Hz 
Changes in 0~49Hz according to system’s pressure. 

IDU ambient 

11 

temp 
°C(°F) 
—— 

12 
Indoor heat 
exchanger’s 

 According to ambient temp, for a same IDU in cool 

°C(°F) 

mode, the inlet temp will be 1°C~7°C (34~45°F) lower 
than the outlet temp, and 4~9°C(39~48°F) higher than 
the low pressure value. 
 For a same IDU in heat mode, the inlet temp will be 

inlet temp 

10°C~20°C(50~68°F) lower than the outlet temp. 
13 
Indoor heat 
exchanger’s 

IDU 
parameters 

°C(°F) 

inlet temp 

 In cool mode, the opening angle of indoor EXV varies 

14 
Opening angle 

within 70~480PLS. 
 In heat mode, the opening angle of indoor EXV varies 

of indoor EXV 
PLS 

within 70~480PLS. 

21 

Sayfa 26

DC Inverter Multi VRF System 

No 
Debug item 
Parameter name 
Unit 
Reference 

15 
Communication 

Communication 

data 
— 
Number of IDUs detected by software is the same with 
the actual number. No communication error. 

parameters 

Indoor unit can drain water out completely and smoothly. 
Condensate pipe has no backward slope of water; Water 
of outdoor unit can be drained completely through 
drainage pipe. No water drop from unit base. 

16 
Drainage system 
—— 
— 

17 
Others 
—— 
— 
Compressor and indoor/outdoor fan motor do not have 
strange noise. Unit can operate normally. 
6 Common Malfunctions and Troubleshooting 

(1) 
If an abnormal situation (such as peculiar smell) occurs, please stop the operation immediately and turn off the 
main power supply, and then contact Gree authorized maintenance center. If the unit continues to operate under 
abnormal situation, the air conditioner will be damaged and an electric shock or fire accident may result. 
(2) 
Do not maintain the air conditioner by yourself, misoperation may cause electric shock or fire hazard. Please 
contact professional personnel of Gree authorized maintenance center to maintain. 
● Before asking for maintenance, please check the following issues first.  

(1) 
Please check the items below before calling for maintenance. 

Problems 
Causes 
What to do 

Fuse or circuit breaker is cut off. 
Replace fuse or reset the circuit breaker. 

Power failure. 
Restart unit when power is restored. 

Unit doesn’t work. 

Power supply is not connected 
Connect the power. 

Remote controller’s power is not enough. 
Replace new battery. 

Remote controller is out of the control range. 
Control range is within 8m. 

Unit runs but stops 
immediately. 

Air inlet or air outlet of indoor and outdoor 
units is blocked. 
Clear obstructions. 

Air inlet or air outlet of indoor and outdoor 
units is blocked. 
Clear obstructions. 

Improper temp setting. 
Adjust setting at remote controller or wired 
controller. 

Fan speed is set too low. 
Adjust setting at remote controller or wired 
controller. 

Abnormal cooling or 
heating. 

Wind direction is not correct. 
Adjust setting at remote controller or wired 
controller. 

Door or window is open. 
Close the door or window. 

Direct sunshine. 
Draw curtain or louver. 

Too many people in the room. 
— 

Too many heat resources in the room. 
Reduce heat resources. 

Filter is blocked and dirty. 
Clean the filter. 

If problem cannot be solved after checking the above items, please contact Gree service center and 

describe the cases and models. 

22 

Sayfa 27

(2) 
Following circumstances are not malfunctions. 

Malfunction 
Reason 

Unit doesn’t starts up after it is just being 
turned off. 

Unit doesn’t operate 

When power is turned on. 
Standby operating for about 1 minute. 

Mist comes from the 
unit 
Under cooling. 
Indoor high humidity air is cooled rapidly. 

When the power supply is connected, there is 
small “dada” sound. 

It is the sound of startup action of electronic 
expansion valve. 
When the system is conducting cooling or 
defrosting, there is continuous “sa——” sound. 

This is the sound of refrigerant flowing inside 
the unit. 
When the system is switching cooling and 
heating modes; during heating operation, the 
unit enters or quits defrosting operation or oil 
return operation, there is “chi——” sound. 

When the system is started or stopped for a 
short time, you can hear the sound of “sa——”; 
you can also hear this sound for a short time 
after the start or stop of the defrosting 
operation. 

When the system is in cooling operation or 
after it stops running, a continuous “sa——” 
sound can be heard 

When the system is running or after it stops 
running, a “creaking” sound can be heard. 

Noise is emitted 

When the system is in heating operation, after 
the indoor unit stops running, the sound like 
running water can be heard. 

This sound can be heard when other indoor 
units are running. This is to prevent oil and 
refrigerant from staying in the indoor unit, and 
to keep a small amount of refrigerant flowing. 
When the unit is running, the operating sound 
of the compressor changes. 

When the indoor unit stops running, a faint “sa
——” sound or “gurgling” sound can be heard. 

This is caused by changes in compressor 
operating frequency. 
During the operation of the unit or after the 
operation is started or stopped, a continuous 
“sa——” sound can be heard. 

When the operating mode of the unit changes, 
the indoor unit and outdoor unit will produce 
“sa——” and "gurgling" sounds. 

The sound from the outdoor unit can be heard 
indoors 

There is dust 
blowing out from the 
unit 

Start operation after it is not used for a long 
time 

The unit emits odor Operating. 
The odor of the air conditioner is sucked into 
the room and then blown out 

The indoor unit is 
still running after 
shutting down 

The indoor unit is still running after shutting 
down 

DC Inverter Multi VRF System 

Overload protection switch makes it run after 
3 minutes delay. 

This is the sound for direction reversal of 
4-way valve. 

This is the sound produced when the 
refrigerant stops or changes the flow. 

This is the operation sound of drain system. 

This is the sound produced when plastic parts 
such as panels expansion and contraction 
due to temperature changes. 

The unit is melting the frost on the outdoor 
unit, please wait about 10 minutes (due to 
different unit models, the waiting time will 
vary). 

This is the sound produced when the 
refrigerant bypass valve operates. 

This is the sound produced when the 
refrigerant stops or changes flow. 

This is because the outdoor unit is installed 
close to the window or wall, and the sound 
insulation is poor, and the external noise is 
transmitted in. 

Dust in indoor unit is blew out. 

The fan of indoor unit will continue to work for 
20 to 70 seconds to fully use the residual 
cooling or heat of the heat exchanger, and to 
prepare for the next use. 

23 

Sayfa 28

DC Inverter Multi VRF System 

Malfunction 
Reason 

When the selected operation mode of the 
indoor unit conflicts with the operation mode 
of the outdoor unit, after five seconds, the 
indoor unit error indicator flashes or the 
remote controller displays the operation 
conflict, and the indoor unit shuts down. At 
this time, the indoor unit can be converted to 
run with the outdoor unit. The mode can be 
restored to normal without conflict. The 
cooling mode and dry mode do not conflict, 
and the air supply does not conflict with any 
mode. 
7 Error Indication 

Mode conflict 
Cooling or heating mode cannot start up 

Inquiry method of error indication: combine division symbol and content symbol to check the 

corresponding error. 

Indoor: 

Error Code 
Content 
Error Code 
Content 

L0 
Malfunction of IDU (uniform) 
d1 
Indoor PCB is poor 

L1 
Protection of indoor fan 
d3 
Malfunction of ambient temperature 
sensor 

L2 
Auxiliary heating protection 
d4 
Malfunction of entry-tube temperature 
sensor 
L3 
Water-full protection 
d5 
Malfunction of middle temperature sensor 

L4 
Abnormal power supply for wired 
controller 
d6 
Malfunction of exit-tube temperature 
sensor 
L5 
Freeze prevention protection 
d7 
Malfunction of humidity sensor 

L6 
Mode shock 
d9 
Malfunction of jumper cap 

L7 
No main IDU 
dA 
Web address of IDU is abnormal 

L8 
Power supply is insufficient 
dH 
PCB of wired controller is abnormal 

L9 
1-to-more: number of IDU is inconsistent  
dC 
Setting capacity of DIP switch code is 
abnormal 

LA 
t1-to-more: IDU series is inconsistent 
dL 
Malfunction of air outlet temperature 
sensor 

LH 
Alarm due to bad air quality (Fresh air 
unit) 
dE 
Malfunction of indoor CO2 sensor 

LC 
IDU is not matching with outdoor unit 
db 
Debugging status 

Outdoor: 

Error Code 
Content 
Error Code 
Content 

E0 
Malfunction of ODU (uniform) 
F0 
Main board of ODU is poor 

E1 
High-pressure protection 
F1 
Malfunction of high-pressure sensor 

E2 
Discharge low-temperature protection 
F3 
Malfunction of low-pressure sensor 

E3 
Low-pressure protection 
F5 
Malfunction of discharge temperature 
sensor of compressor 1 

E4 
High discharge temperature protection of 
compressor 
FP 
Malfunction of DC motor  

E5 
High discharge temperature protection of 
compressor 1 
b1 
Malfunction of outdoor ambient 
temperature sensor 

EC 
Drop protection of discharge temperature 
sensor of compressor 1 
b2 
Malfunction of defrosting temperature 
sensor 1 

J1 
Over-current protection of compressor 1 
b4 
Malfunction of liquid temperature sensor 
of sub-cooler 

24 

Sayfa 29

Error Code 
Content 
Error Code 
Content 

J7 
Gas-mixing protection of 4-way valve 
b5 
Malfunction of gas temperature sensor of 
sub-cooler 

J8 
High pressure ratio protection of system 
b6 
Malfunction of inlet tube temperature 
sensor of vapor liquid separator 

J9 
Low pressure ratio protection of system 
b7 
Malfunction of exit tube temperature 
sensor of vapor liquid separator  

JA 
Protection because of abnormal pressure 
b9 
Malfunction of gas temperature sensor of 
heat exchanger 

JL 
Protection because high pressure is too 
low  
bH 
Clock of system is abnormal 

P0 
malfunction of driving board of 
compressor (uniform) 
H0 
Malfunction of driving board of fan 
(uniform) 

P1 
Driving board of compressor operates 
abnormally (uniform) 
H1 
Driving board of fan operates abnormally 
(uniform) 

P2 
Voltage protection of driving board power 
of compressor (uniform) 
H2 
Voltage protection of driving board power 
of fan (uniform) 

P3 
Reset protection of driving module of 
compressor 
H3 
Reset protection of driving module of fan 

P4 
Drive PFC protection of compressor 
H4 
Drive PFC protection of fan 

P5 
Over-current protection of inverter 
compressor 
H5 
Over-current protection of inverter fan 

P6 
Drive IPM module protection of 
compressor 
H6 
Drive IPM module protection of fan 

P7 
Malfunction of drive temperature sensor 
of compressor 
H7 
Malfunction of drive temperature sensor 
of fan 

P8 
Drive IPM high temperature protection of 
compressor 
H8 
Drive IPM high temperature protection of 
fan 

P9 
Desynchronizing protection of inverter 
compressor 
H9 
Desynchronizing protection of inverter 
fan 

PH 
High-voltage protection of compressor’s 
drive DC bus bar 
HH 
High-voltage protection of fan’s drive DC 
bus bar 

PC 
Malfunction of current detection circuit 
drive of compressor  
HC 
Malfunction of current detection circuit of 
fan drive 

PL 
Low voltage protection for DC bus bar of 
drive of compressor  
HL 
Low voltage protection of bus bar of fan 
drive  
PE 
Phase-lacking of inverter compressor  
HE 
Phase-lacking of inverter fan 

PF 
Malfunction of charging loop of driven of 
compressor  
HF 
Malfunction of charging loop of fan drive 

PJ 
Failure startup of inverter compressor  
HJ 
Failure startup of inverter fan 

PP 
AC current protection of inverter 
compressor  
HP 
AC current protection of inverter fan  

Ed 
Low temperature protection for drive 
module 
 
 

Debugging: 

Error Code 
Content 
Error Code 
Content 

U0 
Preheat time of compressor is insufficient 
C4 
Malfunction of lack of IDU 

U2 
Wrong setting of ODU’s capacity 
code/jumper cap 
C5 
Alarm because project code of IDU is 
inconsistent 

U4 
Refrigerant-lacking protection 
C8 
Emergency status of compressor 

U5 
Wrong address for driving board of 
compressor 
C9 
Emergency status of fan 

U6 
Alarm because valve is abnormal 
CH 
Rated capacity is too high 

U8 
Malfunction of pipeline for IDU 
CC 
Malfunction of lack of main control unit 

U9 
Malfunction of pipeline for ODU 
CL 
Rated capacity is too low  

UC 
Setting of main IDU is successful 
CF 
Malfunction of multiple main control units  

DC Inverter Multi VRF System 

25 

Sayfa 30

DC Inverter Multi VRF System 

Error Code 
Content 
Error Code 
Content 

UL 
Wrong button-dial 
CJ 
Address DIP switch code of system is 
shocking  

UE 
Charging of refrigerant is invalid  
CP 
Malfunction of multiple wired controller  

C0 
Communication malfunction between 
IDU, ODU and IDU’s wired controller 
CU 
Communication malfunction between 
IDU and the receiving lamp plate  

Communication malfunction between 
main control and inverter compressor 
driver 

C2 

C3 
Communication malfunction between 
main control and inverter fan driver 
— 
— 

Status: 

Error Code 
Content 
Error Code 
Content 

A0 
Unit waiting for debugging 
AP 
Debugging confirmation when starting up 
the unit 

A1 
Inquiry of compressor operation 
parameters 
AU 
Long-distance emergency stop 

A2 
Refrigerant recovery operation of 
after-sales 
Ab 
Emergency stop of operation 

A3 
Defrosting  
Ad 
Limit operation 

A4 
Oil-return 
n0 
SE operation setting of system 

A6 
Heat pump function setting 
n1 
Setting of defrosting cycle K1 

A7 
Quiet mode setting 
n2 
Setting of upper limit of IDU/ODU 
capacity distribution ratio 

A8 
Vacuum pump mode 
n4 
Limit setting for max. capacity/output 
capacity 

A9 
IPLV test 
n6 
Inquiry of malfunction 

AA 
EU AA level EER test mode 
n7 
Inquiry of parameters 

AH 
Heating 
n8 
Inquiry of project code of IDU 

AC 
Cooling  
nA 
Heat pump unit 

AL 
Charge refrigerant automatically 
nH 
Heating only unit 

AE 
Charge refrigerant manually  
nC 
Cooling only unit  

AF 
Fan 
nE 
Negative code  

AJ 
Cleaning reminding of filter  
nF 
Fan model  

q1 
Anti-ice temperature setting under low 
temperature condition 
qA 
Heat recover status 

q2 
Shield setting for compressor frequency 
qH 
main body conducts heating 

q3 
Upper limit of correction value for target 
low pressure is Z0 
qC 
The main body conducts cooling 

q4 
Upper limit of correction value for target 
low pressure is Z2 
qL 
Static pressure setting 

Setting for general unit and high sensible 
heat unit (0 represents general, 1 
represents high sensible heat) 

q5 

q6 
Setting for engineering ability correction 
factor θ 
qF 
Compulsory cooling mode 

q7 
Select Centigrade or Fahrenheit 
qJ 
Dual heat source water emptying 

q8 
Low temperature protection correction 
value for discharge 
qy 
Working mode of compressor heating 
zone 

q9 
Defrost mode setting 
 
 

8 Maintenance and Care 

Regular check, maintenance and care can extend unit’s service life. Please have specialized 

person in charge of the management of air conditioners. 

Cb 
Overflow distribution of IP address 

qE 
EVI operation status setting 

26 

Sayfa 31

8.1 Outdoor Heat Exchanger 

Outdoor heat exchanger shall be cleaned regularly, which is at least once every two months. You 

can use a dust catcher with nylon brush to clean away the dust on the heat exchanger. If compressed 

air source is available, it also can be used to clean the heat exchanger. Do not clean it with water. 

8.2 Drain Pipe 

Please check regularly whether drain pipe is blocked or not. Make sure condensate can be 

drained out smoothly. 

8.3 Notice before Seasonal Use 

(1) 
Check whether air inlets and air outlets of indoor and outdoor units are blocked. 

(2) 
Check whether ground connection is reliable or not. 

(3) 
Check whether batteries in the remote controller are replaced or not. 

(4) 
Check whether air filter is properly installed. 

(5) 
If unit starts up after not operating for a long time, it should be power on 8 hours before 

operation starts so as to preheat the outdoor compressor. 

(6) 
Check whether outdoor unit is securely installed. If there is any problem, please contact 

Gree authorized service center. 

8.4 Maintenance after Seasonal Use 

(1) 
Disconnect power of the entire system. 

(2) 
Clean the air filter and outer case of indoor and outdoor units. 

(3) 
Clean away the dust and obstacles on indoor and outdoor units. 

(4) 
If outdoor unit has rust, please apply some paint to it so as to prevent the rust from growing. 

8.5 Parts Replacement  

Parts and components can be obtained from nearby Gree office or Gree distributor. 

When you are conducting air tightness test and leakage test, do not mix oxygen, C2H2 or other 

dangerous gas into the refrigerant circuit. Otherwise, it may lead to danger. Use nitrogen or 

refrigerant to conduct the tests.  

9 After-sales Service 

If there’s quality defect or other problems in the product, please contact Gree local after-sales 

service department for help. 

Warranty must be based on the following conditions: 

(1) 
Product’s initial startup must be performed by professional technicians from Gree service 

center or persons assigned by Gree. 

(2) 
Only Gree spare parts are used. 

(3) 
All instructions of unit operation and maintenance in this manual must be strictly followed 

according to set period and set frequency. 

(4) 
Any breach of the above conditions will disable the warranty. 

DC Inverter Multi VRF System 

27 