Owner's Manual 

Original Instructions 
Commercial Air Conditioners 
 
Multi Variable Air Conditioners 
Floor and Ceiling Type Indoor Unit 
 

Models: 

GMV-ND09ZD/A-T(U)  GMV-ND12ZD/A-T(U) 

GMV-ND18ZD/A-T(U)  GMV-ND24ZD/A-T(U) 

GMV-ND30ZD/A-T(U)  GMV-ND36ZD/A-T(U) 

GMV-ND42ZD/A-T(U)  GMV-ND48ZD/A-T(U) 

Sayfa 2

Preface 

For correct installation and operation, please read all instructions carefully. Before reading the 

instructions, please be aware of the following items: 

This is the safety alert symbol. It is used to alert you to potential personal injury 
hazards. Obey all safety messages that follow this symbol to avoid possible injury 
or death. 

 
This mark indicates procedures which, if improperly performed, might lead to the 
death or serious injury of the user. 

 
This mark indicates procedures which, if improperly performed, might possibly 
result in personal harm to the user, or damage to property. 

 
NOTICE is used to address practices not related to personal injury. 

(1) 
Instructions for installation and use of this product are provided by the manufacturer. 

(2) 
Installation must be performed in accordance with the requirements of NEC and CEC by authorized 
personnel only. 

(3) 
For the safe operation of this unit, please read and follow the instructions carefully. 

(4) 
During operation, total capacity of indoor units should not exceed the total capacity of outdoor units. 
Otherwise, poor effect of cooling or heating may result. 

(5) 
Direct operators or maintainers should well keep this manual. 

(6) 
If this unit fails to operate normally, please contact our service center as soon as possible and provide the 
following information: 

1) Content on the nameplate (model number, cooling capacity, production code, ex-factory date). 

2) Malfunction details (before and after the malfunction occurs). 

(7) 
Each unit has been strictly tested and proved to be qualified before ex-factory. In order to prevent units 
from being damaged or operating normally because of improper disassembly, please do not disassemble 
the unit by yourself. If you need to disassemble and check units, please contact our service center. We will 
send specialists to guide the disassembly. 

(8) 
Under the standby status, the unit will consume a little power for ensuring reliability of complete unit, 
maintaining normal communication and preheating refrigerant. When the unit won’t be used for a long 
time, cut off the power of the complete unit. However, please preheat it when operating the unit next time. 

(9) 
All graphics in this manual is only for your reference. For sales or production reasons, these graphics are 
subject to change by manufacturer without prior notice. 

(10) These instructions shall also be available in an alternative format, e.g. on a website. 

Sayfa 3

This appliance can be used by children aged from 8 years and above and persons with 

reduced physical, sensory or mental capabilities or lack of experience and knowledge if they 

have been given supervision or instruction concerning use of the appliance in a safe way and 

understand the hazards involved. Children shall not play with the appliance. 

Cleaning and user maintenance shall not be made by children without supervision. 

DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection 

of such waste separately for special treatment is necessary.  

Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following 
reasons: 

(1) Damage the product due to improper use or misuse of the product; 
(2) Alter, change, maintain or use the product with other equipment without abiding by the instruction 

manual of manufacturer; 
(3) After verification, the defect of product is directly caused by corrosive gas; 
(4) After verification, defects are due to improper operation during transportation of product; 
(5) Operate, repair, maintain the unit without abiding by instruction manual or related regulations; 
(6) After verification, the problem or dispute is caused by the quality specification or performance of 

parts and components that produced by other manufacturers; 
(7) The damage is caused by natural calamities, bad using environment or force majeure. 
 
 
 

User Notice 

Exception Clauses 

Sayfa 4

1 Safety Precautions ............................................................................................ 1 

2 Product Introduction ......................................................................................... 2 

2.1 Names of Key Components ....................................................................................... 2 

2.2 Rated Working Condition ........................................................................................... 2 

3 Preparations for Installation ............................................................................. 2 

3.1 Standard Fittings ........................................................................................................ 2 

3.2 Installation Position Selection .................................................................................... 3 

3.3 Requirements of Communication Wire Selection ...................................................... 4 

3.4 Wiring Requirement ................................................................................................... 5 

4 Installation Instructions .................................................................................... 6 

4.1 Indoor Unit Installation ............................................................................................... 6 

4.2 Refrigerant Pipe Connection ...................................................................................... 8 

4.3 Drainage Pipe Installation and Drainage System Testing .......................................... 9 

4.4 Wired controller installation ...................................................................................... 12 

5 Wiring Work ..................................................................................................... 12 

5.1 Connection of Wire and Patch Board Terminal ........................................................ 13 

5.2 Power Cord Connection ........................................................................................... 13 

5.3 Connection of Communication Wire between Indoor Unit and Outdoor Unit (or 
indoor unit) ..................................................................................................................... 14 

5.4 Connection of Communication Wire for Wired Controller ........................................ 15 

5.5 Wiring instructions of Wired Controller and Indoor Units Network ........................... 16 

6 Routine Maintenance....................................................................................... 16 

6.1 Cleaning of Filter ...................................................................................................... 17 

6.2 Maintenance before the Seasonal Use .................................................................... 17 

6.3 Maintenance after the Seasonal Use ....................................................................... 17 

7 Table of Error Codes for Indoor Unit .............................................................. 17 

8 Troubleshooting .............................................................................................. 18 

Contents 

Sayfa 5

1 Safety Precautions  

(1) 
This product can’t be installed at corrosive, inflammable or explosive environment or the place with 
special requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the 
service life of the unit, or even cause fire hazard or serious injury. As for above special places, please 
adopt special air conditioner with anti-corrosive or anti-explosion function. 

(2) 
Follow this instruction to complete the installation work. Please carefully read this manual before unit 
startup and service. 

(3) 
Wire size of power cord should be large enough. The damaged power cord and connection wire should 
be replaced by exclusive cable. 

(4) 
After connecting the power cord, please fix the electric box cover properly in order to avoid accident. 

(5) 
Never fail to comply with the nitrogen charge requirements. Charge nitrogen when welding pipes. 

(6) 
Never short-circuit or cancel the pressure switch to prevent unit damage.  

(7) 
Please firstly connect the wired controller before energization, otherwise wired controller can not be 
used. 

(8) 
Before using the unit, please check if the piping and wiring are correct to avoid water leakage, 
refrigerant leakage, electric shock, or fire etc. 

(9) 
Do not insert fingers or objects into air outlet/inlet grille. 

(10) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the 

gas/oil supplied heating equipment is used. 

(11) Never start up or shut off the air conditioner by means of directly plug or unplug the power cord. 

(12) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor. 

(13) Do not allow children operate this unit. 

(14) Do not operate this unit with wet hands. 

(15) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury 

may happen. 

(16) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen. 

(17) Do not expose the unit to the moist or corrosive circumstances. 

(18) Under cooling mode, please don't set the room temperature too low and keep the temperature 

difference between indoor and outdoor unit within 5°C (41°F). 

(19) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please 

contact Gree appointed service center for help.  

(20) Before installation, please check if the power supply is in accordance with the requirements specified on 

the nameplate. And also take care of the power safety. 

(21) Installation should be conducted by dealer or qualified personnel. Please do not attempt to install the 

unit by yourself. Improper handling may result in water leakage, electric shock or fire disaster etc. 

(22) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire   

accidents. 

(23) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid 

electric shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone 
line.  

(24) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off 

the power when 24 hours short-time halting (to protect the compressor).  

(25) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will 

emerge if the refrigerant gas meets fire. 

(26) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little 

neutral detergent to clean the outer casing of unit. 

(27) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main 

power supply, and then immediately contact Gree appointed service center. If abnormality keeps going, 
the unit might be damaged and lead to electric shock or fire. 

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

1 

Sayfa 6

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

2 Product Introduction 

2.1 Names of Key Components 

Fig.2.1.1 

2.2 Rated Working Condition 

Indoor Side Condition 
Outdoor Side Condition 

_ 

Dry Bulb Temp 

Wet Bulb Temp 

Dry Bulb Temp 

Wet Bulb Temp  

 °C(°F) 

°C(°F) 

 °C(°F) 

°C(°F) 

Rated Cooling 
26.7(80.0) 
19.4(67.0) 
35(95.0) 
23.9(75.0) 

Rated Heating 
21.1(70.0) 
15.6(60.0) 
8.3(47.0) 
6.1(43.0) 

3 Preparations for Installation 

This picture is for reference only, please refer to the actual product; the unit of dimension is 

mm(inch). 

3.1 Standard Fittings 

Please use the following provided accessories according to the requirement. 

No. 
Name 
Appearance 
Q’ty 
Usage 

1 
Remote controller 
 
 
1+2 
To control the indoor unit 

 
2 
GMV-ND09~12ZD/A-T(U) 

2 
Special hut 

 
1 
GMV-ND18~48ZD/A-T(U) 

3 
Corrugated pipe 
 
1 
GMV-ND18~48ZD/A-T(U) 

4 
M10X8 nut with 

washer 
 
8 
To be used together with the suspension 
bolt for installing the unit. 

5 
Insulation 
 
1 
To insulate the gas pipe 

6 
Insulation 
 
1 
To insulate the liquid pipe 

7 
Paper pattern for 

installation 
 
1 
Locate the drill hole on ceiling or wall 

8 
Fastener 
 
4 
To fasten the sponge 

2 

Sayfa 7

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

No. 
Name 
Appearance 
Q’ty 
Usage 

9 
Remote controller 

holder 
 
1 
Used for holding the remote controller 

10 
Tapping screw 
 
2 
Used for fixing the remote controller 
holder 

3.2 Installation Position Selection 

(1) The location should be able to withstand the weight of unit. 

(2) The water can be drained conveniently from drainage pipe. 

(3) There should be no obstruction near air inlet and air outlet. 

(4) Follow the installation distance required in the Fig.3.2.1 below to ensure sufficient 

space for maintenance. 

(5) The installation location should be far from heat sources, flammable or explosive gas, 

or smog spread in the air. 

(6) The indoor unit, outdoor unit, power cord and connection electricity wire should be at 

least 1m from television and radio in order to prevent interference and noise (Even 

though 1m distance is ensured, there may be noise if the electric wave is too strong). 

Floor type  

Ceiling type 

Fig.3.2.1 

3 

Unit: mm(inch) 

Sayfa 8

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

(1) 
The unit shall be installed in accordance with national standards or local regulations. 

(2) 
Only qualified personnel can carry out installation work, please contact with local dealer before 
installation. 

(3) 
Make sure all the installation work completed before energizing. 

3.3 Requirements of Communication Wire Selection 

If air conditioner used under strong electronic-magnetic interference circumstance, STP 

(shielded twisted pair) communication cable must be adopted. 

3.3.1 Selection of Communication Wire between Indoor Unit and Wired Controller 

Total length of 
communication wire 
between indoor unit and 

Wire type 

wired controller 

Light/Ordinary 

polyvinyl 

L≤250m 
(L≤820-1/5ft.) 

chloride 
sheathed cord 

3.3.2 Selection of Communication Wire between Indoor Unit and Indoor Unit 
(Outdoor Unit) 

Fig.3.3.1 

Wire size 
Remark 

1. Total length of communication line can't 
exceed 250m (820-1/5ft.). 
2. The cord shall be Circular cord (the cores 
shall be twisted together). 
3. If unit is installed in places with intense 
magnetic field or strong interference, it is 
necessary to use shielded wire. 

2×AWG18 
~2×AWG16 

Fig.3.3.2 

4 

Sayfa 9

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

Total length of 
communication wire 
between indoor unit and 
indoor unit(outdoor unit)  

Wire 
diameter  
Remark 

Wire type 

1. If the wire diameter is enlarged to 2×1mm2 
(2×AWG16), the total communication line 
length can reach 1500m (4921-1/4ft.).  
2. The cord shall be Circular cord (the cores 
shall be twisted together). 
3. If unit is installed in places with intense 
magnetic field or strong interference, it is 
necessary to use shielded wire. 

Light/Ordinary 

polyvinyl 

L≤1000m 
(L≤3280-5/6ft.) 
≥2×AWG18 

chloride 
sheathed cord 

3.4 Wiring Requirement 

① The circuit breaker and power cord specification in above sheet are based on max 

power (max current) of the unit. 

② The power cord specification in above sheet is based on ambient temperature of 40°C. 

③ The circuit breaker specification in above sheet is based on ambient temperature of 

40°C. If the working condition is different, please adjust it according to the specification 

sheet of circuit breaker. 

Dimension of power cord and capacity of air switch 

Model 
Power specification 
MCA(A) 
MOP(A) 

GMV-ND09ZD/A-T(U) 

1 
15 

GMV-ND12ZD/A-T(U) 
1 
15 

GMV-ND18ZD/A-T(U) 
1 
15 

GMV-ND24ZD/A-T(U) 
1 
15 

208/230V-1ph-60Hz 

GMV-ND30ZD/A-T(U) 
1 
15 

GMV-ND36ZD/A-T(U) 
1 
15 

GMV-ND42ZD/A-T(U) 
1 
15 

GMV-ND48ZD/A-T(U) 
1 
15 

5 

Sayfa 10

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

4 Installation Instructions 

4.1 Indoor Unit Installation 

4.1.1 Indoor unit dimension and suspension bolt position 

Below are dimensions of A, B, C, etc. for different models:  

Models: 
A 
B 
C 
D 
H 

GMV-ND09ZD/A-T(U) 
1220 
(48) 

700 
(27-1/2) 
GMV-ND12ZD/A-T(U) 
GMV-ND18ZD/A-T(U) 
GMV-ND24ZD/A-T(U) 
GMV-ND30ZD/A-T(U) 

700 
(27-1/2) 
GMV-ND36ZD/A-T(U) 
GMV-ND42ZD/A-T(U) 
GMV-ND48ZD/A-T(U) 

Models: 

GMV-ND09ZD/A-T(U) 

GMV-ND12ZD/A-T(U) 
6.35(1/4) 
12.7(1/2) 

GMV-ND18ZD/A-T(U) 
9.52(3/8) 
15.9(5/8) 

GMV-ND24ZD/A-T(U) 
GMV-ND30ZD/A-T(U) 
9.52(3/8) 
15.9(5/8) 

GMV-ND36ZD/A-T(U) 
GMV-ND42ZD/A-T(U) 
GMV-ND48ZD/A-T(U) 

 The drilling work must be carried out by qualified personnel. 

4.1.2 Suspend the indoor unit 

(1) Determine the location of the hanger through the paper template, and then remove the 

Fig.4.1.1 

Unit: mm(inch) 

225 
(8-7/8) 

1158 
(45-5/8) 

280 
(11) 

1420 
(55-15/16) 

245 
(9-5/8) 

1354 
(53-5/16) 

280 
(11) 

1700 
(66-15/16) 

245 
(9-5/8) 

1634 
(64-21/64) 

280 
(11) 

700 
(27-1/2) 

Outer diameter of connection pipe 

Drainage pipe 
(Outer Diameter × wall 

(mm/inch) 

thickness) (mm/inch) 

Liquid pipe 
Gas pipe 

6.35(1/4) 
9.52(3/8) 

Φ17×1.75 
(Φ11/16×1/16) 

9.52(3/8) 
15.9(5/8) 

6 

Sayfa 11

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

paper template, as shown in Fig.4.1.2.1(a). 

  Fig.4.1.2.1(a)                           Fig.4.1.2.1(b)              

(2) Insert the anchor bolts into the drilled holes, and drive the pins completely into the 

anchor bolts with a hammer, as shown in Fig.4.1.2.1(b). 

(3) Remove the right and left side panels, as shown in Fig.4.1.2.2. 

(4) Put the hanger bolt into the clasp of the indoor unit and tighten screws on the hanger 

to prevent the indoor unit from moving, as shown in Fig.4.1.2.2. 

(5) Reinstall and tighten the right and left side panels, as shown in Fig.4.1.2.3. 

(6) Adjust the height of the unit to make the drain pipe slant slightly downward so that the 

drainage will become much smoother, as shown in Fig.4.1.2.3. 

Floor type 

Fig.4.1.2.2 

7 

Sayfa 12

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

Ceiling type 

4.1.3 Leveling 

The water level test must be done after installing the indoor unit to make the unit is 

horizontal, as shown Fig.4.1.3. 

Adjust the height of the unit to make the drain pipe slant slightly downward so that the drainage 

will become much smoother. 

4.2 Refrigerant Pipe Connection 

(1) Aim the flaring port of copper pipe at the center of screwed joint and then tighten the 

flaring nut with hand as shown in Fig.4.2.1. 

Unit: mm(inch) 

Fig.4.1.2.3 

Fig.4.1.3 

8 

Sayfa 13

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

(2) Tighten the flaring nut with torque wrench.  

Fig.4.2.1 

Pipe diameter mm(inch) 
Torque (N•m) 

6.35(1/4) 
15~30 

9.52(3/8) 
35~40 

12.7(1/2) 
45~50 

15.9(5/8) 
60~65 

(3) Use pipe bender when bending the pipe and the bending angle should not be too small. 

(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape. 

4.3 Drainage Pipe Installation and Drainage System Testing 

4.3.1 Notices for Installation of Drainage Pipe 

(1) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines 

which are likely to produce corrosive or peculiar smell to prevent the smell from 

entering indoors or corrupt the unit. 

(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain 

water from pouring in and cause property loss or personal injury. 

(3) Condensate drain pipe should be connected into special drain system for air 

conditioner. 

(4) The drainage pipe should be short and the gradient downwards should be at least 

1%~2% in order to drain condensation water smoothly. 

(5) The diameter of drainage hose should be bigger or equal to the diameter of drainage 

pipe joint. 

(6) Install drainage pipe according to the following Fig.4.3.1.1 and arrange insulation to 

the drainage pipe. Improper installation may lead to water leakage and damp the 

furniture and other things in the room. 

(7) You can buy normal hard PVC pipe used as the drainage pipe. During connection, 

insert the end of PVC pipe into the drainage hole and then tighten it with drainage hose 

and wire binder. Never connect the drainage hole and drainage hose with glue. 

(8) When the drainage pipelines are used for several units, the position of pipeline should 

be about 100mm (3-15/16inch) lower than the drainage port of each unit. In this case, 

thicker pipes should be applied. 

9 

Sayfa 14

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

(9) Connect the drainage pipe properly, as shown in Fig.4.3.1.2. 

4.3.2 Drainage pipe installation 

(1) Drainage pipe should have the same diameter or larger diameter than the connection 

pipes (PVC pipe, outside diameter 17mm (11/16inch), thickness≥1.75mm (1/16inch)). 

(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for 

preventing forming air bubbles. 

(3) Insert the drainage hose into drain socket, tighten the metal clamp securely. 

(4) Warp the sealing pad over drain hose and metal clamp for heat insulation. 

(5) Make sure to perform insulation work for all drainage piping in order to prevent any 

possible water drop due to dew condensation. 

(6) Apply the suitable diameter for converging drainage pipe according to the operating 

capacity of the unit, as show in Fig.4.3.2.1. 

Fig.4.3.1.1 

Fig.4.3.1.2 

10 

Sayfa 15

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

Fig.4.3.2.1 

(7) The horizontal pipe can’t be connected to vertical pipe in the same level; please select 

the connection way as shown in following figure. 

No.1: Three-way connection of drainage pipe joints (Fig.4.3.2.2) 

No.2: Connection of downspout elbow (Fig.4.3.2.3) 

No.3: Inserting horizontal pipe connection (Fig.4.3.2.4) 

    Fig.4.3.2.2                      Fig.4.3.2.3                Fig.4.3.2.4 

(8) Drain pipes should have a downward slope of at least 1~2%, in order to prevent 

pipes from sagging, install hanger bracket at intervals of 1000~1500mm (39-

3/8~59inch). 

Fig.4.3.2.5 

(9) Prepare the local piping at the connection point for the drain pipe, as shown in the 

installation drawings. 

11 

Unit: mm(inch) 

Sayfa 16

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

4.3.3 Test of Drainage System 

(1) Please test drainage system after electric work is finished. Inject approximately 1L 

purified water to drain pan from air vent, ensure that not to splash the water over the 

electrical components (e.g. water pump etc.). 

(2) During the test, please carefully check the drainage joint and make sure no any leakage 

occur. 

(3) It is strongly recommended to do the drain test before ceiling decoration. 

4.4 Wired controller installation 

Wired controller is optional accessory. If wired controller is needed, please contact your 

local dealer and install the wired controller according to the instruction manual. 

Do perform the commissioning operation before first use, automatic addressing or other settings, 

please refer to the manual of ODU. 

5 Wiring Work 

① Units must be grounded securely, or it may cause electric shock. 

② Please carefully read the wiring diagram before carry out the wiring work, incorrect 

wiring could cause malfunction or even damage the unit. 

③ The capacity of power supply must be sufficient and the sectional area of wires in the 

room should be above 2.5mm2. 

Fig.4.3.2.6 

Fig.4.3.3.1 

12 

Sayfa 17

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

④ The unit should be powered by independent circuit and specific socket. 

⑤ The wiring should be in accordance with related regulations in order to ensure the units 

reliable running. 

⑥ Install circuit breaker for branch circuit according to related regulations and electrical 

standards. 

⑦ Crimp terminal or single wire must be applied for all wires. 

⑧ Keep cable away from refrigerant piping, compressor and fan motor. 

⑨ Do not change the wiring inside the unit. 

⑩ If there is strong electromagnetic interference around the unit, shielded twisted pair line 

should be applied; The metal shielded layer of twisted pair wire must be grounded to 

avoid electromagnetic interference. 

⑪ 
The communication wires should be separated from power cord and connection wire 

between indoor unit and outdoor unit.   

⑫ 
Adjust the static pressure via wired controller according to site circumstance. 

5.1 Connection of Wire and Patch Board Terminal 

(1) The connection of wire (as shown in Fig.5.1.1) 

1) Strip about 25mm insulation of the wire end by stripping and cutting tool. 

2) Remove the wiring screws on the patch board. 

3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in 

accordance with screw. 

4) Use the screwdriver for tightening the terminal. 

(2) The connection of stranded wire (as shown in Fig.5.1.2) 

1) Strip about 10mm insulation of the end of stranded wire by stripping and cutting tool. 

2) Loosen the wiring screws on patch board. 

3) Insert the wire into the ring tongue terminal and tighten by crimping tool. 

4) Use the screwdriver for tightening the terminal. 

Fig.5.1.1                   Fig.5.1.2 

5.2 Power Cord Connection 

① Every unit should be equipped with an circuit breaker for short-circuit and overload 

protection. 

13 

Unit: mm(inch) 

Sayfa 18

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

② During operation, all indoor units connected to the same outdoor unit system must be 

kept energized status. Otherwise, the unit can’t operate normally. 

(1) Detach the electric box lid. 

(2) Let the power cord pass through the wiring through-holes. 

(3) Connect wires according to Fig. 5.2.1. 

(4) Fix the power cord with wiring clamp. 

(5) The wire diameter of power cord can’t be less than 18AWG. 

5.3 Connection of Communication Wire between Indoor Unit and 
Outdoor Unit (or indoor unit) 

For units with single-phase power supply. 

(1) Detach the electric box lid. 

(2) Let the Communication cable pass through the wiring through-holes. 

(3) Connect the communication wire to terminal D1 and D2 of indoor 4-bit wiring board, as 

shown in Fig.5.3.1. 

Fig.5.2.1 

  Fig.5.3.1          

14 

Sayfa 19

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

              Fig.5.3.1                              Fig.5.3.2 

(4) Fix the communication cable with clamp of electric box. 

(5) For more reliable communication, make sure connect the downstream IDU of the 

communication bus (terminal D1 and D2), as shown in Fig.5.3.2, terminal resistor to 

the most terminal resistor is provided with each ODU. 

5.4 Connection of Communication Wire for Wired Controller 

(1) Detach the electric box lid. 

(2) Let the communication wire pass through the wiring through-holes. 

(3) Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board. 

(4) Fix the communication wire with clamp. 

(5) Wiring instructions of signal receiver and wired controller. 

Fig.5.4.1 

(6) Both IDU and wired controller are equipped with signal receiver, and available for 

remote control respectively (Fig.5.4.2). 

Fig.5.4.2 

15 

Sayfa 20

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

5.5 Wiring instructions of Wired Controller and Indoor Units Network 

(1) Communication wire of indoor unit and outdoor unit (or indoor unit) is connected to D1, 

D2. 

(2) Wired controller is connected to H1, H2. 

(3) One indoor unit can connect two wired controllers that must be set as master one and 

slave one. 

(4) One wired controller can control 16 indoor units in maximum at the same time (As 

shown in Fig.5.5.1). 

(1) 
The type of indoor units must be the same if they are controlled by the same wired controller. 

(2) 
When the indoor unit is controlled by two wired controllers, the addresses of the two wired controllers 
should be different through address setting. Address 1 is for main controller; Address 2 is for slave 
controller. Detailed setting please refer to the instruction manual of wired controller. 
6 Routine Maintenance 

(1) 
Do turn off the unit and cut off the main power supply when cleaning the air conditioner to avoid electric 
shock or injury. 
(2) 
Stand at solid table when cleaning the unit. 

(3) 
Do not clean the unit with hot water whose temperature is higher than 45°C to prevent fade or deformation. 

(4) 
Do not dry the filters by fire, or it may catch fire or become deformed. 

(5) 
Clean the filter with a wet cloth dipped in neutral detergent. 

(6) 
Please contact after-sales service staff if there is abnormal situation. 

Fig.5.5.1 

16 

Sayfa 21

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

6.1 Cleaning of Filter 

(1) Remove the filters from inlet of IDU. Use a vacuum cleaner to remove dust. If the filters 

are dirty, wash them with warm water and mild detergent, and then dry the filters in the 

shade. 

(2) If the unit used in the environment with much dust, please clean it regularly (usually 

once every two weeks). 

6.2 Maintenance before the Seasonal Use 

(1) Check if the air inlet and air outlet of indoor and outdoor unit are blocked. 

(2) Check if securely grounded. 

(3) Check if all the power cord and communication cable are securely connected. 

(4) Check if any error code displayed after energized. 

6.3 Maintenance after the Seasonal Use 

(1) Set the unit in fan mode for half a day in a sunny day to dry the inner part of unit; 

(2) When the unit won’t be used for a long time, please cut off power supply for energy 

saving; the characters on the wired controller screen will disappear after cutting off the 

power supply. 

7 Table of Error Codes for Indoor Unit 

Error 
Code 
Content 
Error 
Code 
Content 
Error 
Code 
Content 

L0 
Indoor Unit Error 
LA 
Indoor Units 
Incompatibility Error 
d9 
Jumper Cap Error 

L1 
Indoor Fan Protection 
LH 
Low Air Quality Warning 
dA 
Indoor Unit Network 

Address Error 

L2 
E-heater Protection 
LC 
ODU-IDU 
Incompatibility Error 
dH 
Wired Controller PCB 

Error 

L3 
Water Full Protection 
d1 
Indoor Unit PCB Error 
dC 
Capacity DIP Switch 

Setting Error 

L4 
Wired Controller Power 

Supply Error 
d3 
Ambient Temperature 

Sensor Error 
dL 
Outlet Air Temperature 

Sensor Error 

L5 
Freeze protection 
d4 
Inlet Pipe Temperature 

Sensor Error 
dE 
Indoor Unit CO2 Sensor 

Error 

Outlet Pipe 
Temperature Sensor 

L7 
No Master Indoor Unit 

dy 
Water Temperature 

Error 
d6 

Sensor Error 

Error 

L8 
Power Insufficiency 

Protection 
d7 
Humidity Sensor Error 
C0 
Communication Error 

Quantity Of Group 
Control Indoor Units 

d8 
Water Temperature 

Error 
AJ 
Filter Cleaning 

L9 

Reminder 

Setting Error 

db 
Special Code: Field Debugging Code 
 

17 

Sayfa 22

Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit 

8 Troubleshooting 

The air conditioner is not expected to be serviced by users. Incorrect repair may cause electric 

shock or fire, so please contact an authorized service center for professional service. The 

following checks prior to contact may save your time and money. 

Phenomenon 
Troubleshooting 

The unit can’t start up 

The unit stops after running for a 
while 

Poor cooling effect 

Poor heating effect 

Indoor fan doesn’t start up during 
heating 

If air conditioner still fails to work normally after checking and handling as described above, 

please stop using it immediately and contact local service center for assistance. 

① Power supply is not connected 
② Circuit breaker tripping caused by leakage of electricity 
③ Input voltage is too low 
④ Operation button is closed 
⑤ Control loop is abnormal 

① There is obstacle in front of the condenser 
② Control loop is abnormal 
③ Set the unit in cooling mode when outdoor ambient temperature is 

higher than 43°C 

① The filter is dirty 
② Too heavy heat load of room (e.g. too many people) 
③ Door or window is open 
④ Inlet and outlet of IDU are blocked 
⑤ Setting temperature is too high 
⑥ The performance of room temperature sensor is getting worse 

① The filter is dirty 
② Door or window is open 
③ Setting temperature is too low 
④ Refrigerant leakage 
⑤ Outdoor ambient temperature is lower than -5°C 
⑥ Abnormality of control circuit 

① Placing position of tube temperature sensor head is not suitable 
② Tube temperature sensor head isn't inserted well 
③ Wiring of tube temperature sensor head is broken 
④ Capacitor is leaking electricity 

18 