TSG_R290_Inverter_HWHP_Residential_

Bu sayfa, kılavuzun PDF dosyasındaki metnin tamamıdır (sayfa sayfa). Görseller ve çizimler için PDF'i açın. — sibastore.com

Sayfa 1

AIR SOURCE HEAT PUMP WATER
HEATER

(GC202405-I)

TECHNICAL SALES GUIDE-50Hz

CAPACITY RANGE: 2.3kW

AMBIENT OPERATION RANGE : -7~45℃

Sayfa 2

1. PRODUCT LIST························································································································· 1

2. NOMENCLATURE····················································································································· 1

3. INTRODUCTIONS TO COMPONENTS·························································································2

4. PRODUCT PARAMETERS···········································································································3

5. PRODUCE PERFORMANCE CURVES·························································································· 3

6. DIMENSION PARAMETERS······································································································· 4

7. INSTALLATION··························································································································5

7.1 Unit Installation Diagram············································································································5

7.2 Installtion Dimension··················································································································5

7.3 Installation Requirements·········································································································· 5

7.4 Wiring········································································································································· 6

7.5 Commissioning Operation··········································································································8

8. MODEL SELECTION···················································································································9

Contents

Sayfa 3

Air Source Heat Pump Water Heater

1. PRODUCT LIST

Model
Heating capacity

(W)
Power Supply
Appearance

GRS-2.3Pd/TD200ANpH-K
2300W+2000W
(electrical heater)
220V-240V ~ 50Hz

GRS-2.3Pd/TD270ANpH-K
2300W+2000W
(electrical heater)
220V-240V ~ 50Hz

2. NOMENCLATURE

GRS
-
2.3
□
Pd
□
/
T
D
200
A
□
□
Np
H
□
□
-
K

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

No.
Description
Options

1
Product code
GRS—Heat pump water heater

2
Heating capacity code
Heating capacity (Unit: kW)

3
Compressor system
Single system – Omit; Dual system – S

4
Functions characteristics 1 Fixed frequency – Omit; Inverter – P; DC Inverter – Pd; Fixed frequency modular

– M; AC Inverter modular – PM; DC Inverter modular – PdM

5
Functions characteristics 2 Normal type – Omit; Low temperature heat pump – Re

6
Water tank material
Stainless Steel – Omit; T –Enameled steel

7
Function code
No electric heating function – Omit; With electric heating function – D

8
Water tank capacity
Capacity of water tank; Unit:(L)

1

Sayfa 4

Air Source Heat Pump Water Heater

No.
Description
Options

A—LCJW: floor standing type; outer coil pipe static heating type;
B—BCJW: wall-mounted type; outer coil pipe static heating type;
C—LCJ: floor standing type; built-in coil pipe static heating type;
D—BCJ: wall-mounted type; built-in coil pipe static heating type;

9
Design code

10
Water tank shape
Round – Omit; Square – F

11
Inner tank number
Single – Omit; Double – 2

12
Refrigerant
R22 – Omit; R407c – N; R410A – Na; R134a – Nb; R32 – Nh; R290- Np

13
Design Serial number
A, B, C…or A1, A2…, B1, B2…

14
Backwater function
No – Omit; Yes – H

15
E-commerce code
Non-e-commerce models – Omit; E-commerce models – D

16
Power code
M—380-415V 3PH~50Hz; K—220V-240V 1PH~50Hz; D—220V-240V
1PH~60Hz …

3. INTRODUCTIONS TO COMPONENTS

No.
Name
Function

1
Compressor
Increases pressure for the refrigerant and provides driving force for circular flow
of the refrigerant as a main driving component.

2
Four-way valve
Reverses flow direction of the refrigerant when the system switches between the
normal heat up mode and defrosting mode.

3
Water tank
Provides heat exchange channel for refrigerant and water and stores hot water
for daily use.

4
Electronic expansion

Speeds
up high-pressure and high-temperature refrigerant
and reduces
pressure and adjusts the circulation amount of coolant.

valve

5
Finned tube exchanger
Provides heat exchange channel for refrigerant and air.

6
Fan motor
Enhances heat exchange on the air side of the finned tube exchange and
provides a low-temperature heat source continuously.

7
Filter
Filters impurities in refrigerant to protect components with small diameter.

Fig.3-1 Diagram of Parts

2

Sayfa 5

Air Source Heat Pump Water Heater

4. PRODUCT PARAMETERS

Model
GRS-2.3Pd/TD200ANpH-K
GRS-2.3Pd/TD270ANpH-K

Rated water storage capacity
206L
270L

Heat pump heating capacity
2300W
2300W

Rated input power
426W
426W

Electric heater power
2000W
2000W

Maximum input power
830W+2000W(Electric heater)
830W+2000W(Electric heater)

Power supply
220-240V ~ 50Hz
220-240V ~ 50Hz

Water outlet temperature
35℃~70℃
35℃~70℃

Heat pump operating range
-7~45℃
-7~45℃

Inlet/Outlet connector diameter
DN15
DN15

Water-proof grade
IPX4
IPX4

Refrigerant
R290 (330g)
R290 (330g)

Sound pressure level
44dB(A)
44dB(A)

Dimension (W×D×H)
663mm×670mm×1643mm
663mm×670mm×1924mm

Net weight
97kg
109kg
NOTES:

1 Product conforms to AS 3498:2020 and AS/NZS 2712:2007.

2 Test conditions: Outdoor ambient temperature 20/15℃(DB/WB); Water temperature from 10℃

up to 55℃.

3 Under BOOST Mode, electric heater helps to heat water.

4 Please refer to the nameplate for the exact data as this table is subject to change.

5. PRODUCE PERFORMANCE CURVES

Fig. 5-1 GRS-2.3Pd/TD270ANpH-K heating time to different hot water target temperatures for different ambient

temperatures(Only heat pump)

Fig.5-2 GRS-2.3Pd/TD200ANpH-K heating time to different hot water target temperatures for different ambient

temperatures(Only heat pump)

3

Sayfa 6

NOTES:

1 The above curve data are fitted based on the test parameters of Gree Laboratory(The test

conditions are: initial water temperature: 10℃, power supply: 230V ~ 50Hz; in a new unit with

clean heat exchangers). So there will be about 5% tolerance and the curves are for reference

only.

2 When the electrical heater and heat pump are together started to heating the heating time of

GRS-2.3Pd/TD270ANpH-K and GRS-2.3Pd/TD200ANpH-K will be decreased. On the other hand,

COP will decrease and power consumption will increase.

6. DIMENSION PARAMETERS

Model
Parameter
GRS-2.3Pd/TD200ANpH-K
GRS-2.3Pd/TD270ANpH-K

A
1643
1924

B
663
663

C
156
156

D
964
1235

E
1177
1458

Air Source Heat Pump Water Heater

Unit: mm

4

Sayfa 7

Air Source Heat Pump Water Heater

7. INSTALLATION

7.1 Unit Installation Diagram

Fig.7.1-1 Unit Installation Diagram

WARNING!


To ensure water safety, Insulation plastic pipes such as PPR pipes are recommended to be used. The PPR pipe
length at the water inlet and outlet is determined as per the formula: L≥70×R2, wherein L indicate the pipe length, and
R indicates the inner diameter of the pipe (unit: cm). The pipes should be insulated properly. No metal pipe is
allowed.

7.2 Installtion Dimension

7.3 Installation Requirements

(1)
Ensure that the sound and airflow of the unit will not affect people, animals, or plants, etc.

(2)
Ensure that the unit has good ventilation. If a canopy is installed to protect the unit, it should be

noted that heat dissipation and heat absorption shouldn’t be affected.

(3)
The unit should be installed in a place with a solid foundation and make sure that the unit is installed

upright. The impact of strong wind, typhoon and earthquake or other natural disasters should be

fully considered, and the installation should be reinforced.

Unit: mm

5

Sayfa 8

(4)
Ensure the reliable connection of the drain pipe of the unit and lead the drain pipe to a proper place

for drainage.

(5)
The unit must be installed in a place with rain and sun shading devices where it can be sheltered

from rain.

(6)
The unit and water system piping and valves should be installed as far as possible in the ambient

temperature above 0℃, and preferably installed near the main hot water point.

(7)
In order to avoid inconvenience or property damage to user due to water leakage caused by

improper connection of water pipe or normal water release of safety valve, it is forbidden to install

the unit in a place without good drainage.

(8)
The unit shall be located upright. The installation ground must be flat and spacious, and the

foundation shall be solid enough to bear four times of the weight of the unit after the unit being filled

with water. It is strictly forbidden to hang the unit or hang it on an external wall. When installing the

unit, it’s necessary to use fixing belt to protect the unit. If the unit is installed in areas with strong

winds, typhoons, or earthquakes, in addition to using fixing belt for installation, additional

reinforcement measures must be taken to prevent the unit from tipping over under external forces,

thus causing unnecessary unit damage or personal injury. The fixing belt of the unit only serves as

an auxiliary fixation and cannot bear the weight of water tank.

(9)
The water quality for the air source water heater should comply with the local sanitation standard for

the domestic drinking water and refer to the following water quality requirements.

Table 7.3-1 Water Quality Requirements
pH (25℃)
6.8~8.0
Turbidity (scattering turbidity unit)/NTU
<1

Chloride/(mg/L)
<50
Iron/(mg/L)
<0.3

Sulfate/(mg/L)
<50
Silica (SiO2)/(mg/L)
<30
Total hardness (calculated in

CaCO3)/(mg/L)
<70
Nitrate (calculated in N)/(mg/L)
<10

Conductivity (25℃)/(μs/cm)
<300
Ammonia nitrogen (calculated in N)/(mg/L)
<1.0
Total alkalinity (calculated in

CaCO3)/(mg/L)
<50
Sulfide/(mg/L)
Shall not to be

7.4 Wiring

The appliance shall be installed in accordance with national wiring regulations, and installation of the unit must be

done by qualified personnel.
The power supply must comply with the specifications on the nameplate. The carrying capacity of the power supply,

wires and sockets should be confirmed before installation.
The fixed circuit must be equipped with a residual current device (RCD) and a circuit breaker with sufficient

capacity to ensure that all poles are disconnected from the power supply when necessary. The action time of the
residual current device (RCD) should be less than 0.1s.
The unit must be grounded reliably. The grounding wire should connect with special device of buildings.
The unit circuit must be at least 1.5m away from any inflammable surface.
Separate fixed device for power supply must be used, and its structure shall match the power supply of water

heater, and comply with relevant national and local standards.
Do not use socket converters, cable extension cords or wiring boards to accommodate the power cord of water

heater, no switch to other power cords to accommodate family power. Connect wires for the water heater separately
and do not share the same circuit with other electrical appliances.
Please see the electrical schematic diagram for exact details.
If the power cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified

persons in order to avoid a hazard. It is not allowed to reconnect the damaged power cord.

Air Source Heat Pump Water Heater

detected

WARNING!

6

Sayfa 9

7.4.1 Selection of Power Cord Diameter and Circuit Breaker

Model
Power
supply

GRS-2.3Pd/TD200ANpH-K
220-240V~
50Hz
1.5
1.5
1.5
16
16
GRS-2.3Pd/TD270ANpH-K

7.4.2 Wiring Diagram

(1)
The external wiring diagram of the unit is as follows. For the internal wiring diagram, please refer to

the circuit diagram attached on the machine.

(2)
The following two installation methods can be used for the display board (wire controller).

If the wire controller needs to be installed in an indoor area other than the unit's panel, its wiring

method should be in accordance with method I in the figure.If the wire controller needs to be installed on

the unit's panel; its wiring method should be in accordance with method II in the figure.

(Note: Connect according to either method I or method II)

7.4.3 Electrical Wiring and Connection Requirement

(1)
After completing wiring connection, the power cord and

communication wires must be tightly pressed with a fixed

wire clamp. The fixed wire clamp should be pressed on

the outer sheath of the connection wire.

(2)
When arranging wiring conection for the external unit, the

communication cord of wired controller shall be separated

from the power cord. The minimum distance between the

parallel wires shall be greater than 20cm. Otherwise, the

communication of the unit might be abnormal. The strong

and weak wires shall be covered separately with wire

sleeves.

7.4.4 Wired Controller Installation

The wire controller is installed on the front panel of the unit by default. When it needs to be adjusted

to other places outside the unit, it is recommended that the length of the communication cable between

the wired controller and the unit can't be more than 8m.

Air Source Heat Pump Water Heater

Table 7.4-1 Unit Power Cord Configuration Table

Minimum sectional area (mm2) of power

cord
Circuit breaker

Fuse capacity

(A)
L
N
PE

(A)

GRS-2.3Pd/TD200ANpH-K
GRS-2.3Pd/TD270ANpH-K

Power cord: 3×1.5mm²
Display board cord:2×0.75mm²

Fig.7.4-1 External wiring

Fig.7.4-2 External wiring and fixing figure

7

Sayfa 10

Air Source Heat Pump Water Heater

7.5 Commissioning Operation

WARNING!

Safety measures must be taken for operation. All personnel involved in commissioning and maintenance must

master the safety regulations of construction and implement them in strict accordance with the regulations.
The electrician, welder and other special types of operators must get the permission for the corresponding post.

When performing related operations on the equipment, the power supply of the whole unit must be cut off.
Meanwhile, operate the unit in strict accordance with related safety requirements.
All installation and maintenance operations must comply with the product design requirements and national and

local safety operation requirements. Illegal operations are strictly prohibited.

7.5.1 Check before Commissioning

After the air source water heater is installed, be sure to check the unit according to the following

table.

Table 7.5-1 Unit Installation Checklist
Items to be checked
What may happen if the installation is improper

Whether the unit is installed reliably
The operation of the unit produces noise or vibration, and
even causes danger such as falling
Whether there are obstacles at the air outlet and air inlet of
the unit
The unit operates abnormally

Whether the cold water inlet pipe and hot water outlet pipe
use PPR pipes
Safety hazard may happen

Whether the safety valve of water tank is installed
The operation pressure of water tank is high and there
may be safety hazard.

The operation pressure of water tank is high. The safety
valve
continuously
discharges
water
and
produces
abnormal noise
Whether all parts of the water pipeline have been properly
insulated

Whether a stabilizing valve is installed when the inlet
pressure of water tank is too high

The performance of the unit may be affected and the
pipeline may be damaged by freezing
Whether the power supply voltage is consistent with the
product nameplate, and whether the wire type meets the
regulations

The unit has malfunction or the parts are burned out

7.5.2 Trial Operation

NOTE!

The water tank of the unit must be filled with water before the unit can be powered on.

The whole unit can be debugged only after the unit has passed the installation inspection. The

debugging steps are as follows:

(1)
Water recharge of the unit: refer to the installation tips label on the water tank of the unit to perform

water recharge. Ensure that there is no water leakage in the pipelines, joints, etc.

(2)
Energization of the whole unit: After the unit is energized, observe whether the display of wired

controller is normal. If there is no fault, it is normal.

(3)
System time calibration of wired controller: set the time according to the manual of the wired

controller.

(4)
Operation of the whole unit: turn on the unit with the wired controller. When the wired controller

displays heating icon, check whether the unit is operating normally. Normal judgement criterion: the

fan is running normally, the whole unit is running stably without obvious vibration and abnormal

noise. The unit can be delivered to the user after running for at least 20 minutes without abnormality.

8

Sayfa 11

Air Source Heat Pump Water Heater

8. MODEL SELECTION

The capacity of water tank for residential water heater system is 150L~300L in general. It can be
calculated as following floor standing type water tank: Water tank capacity = (50~80) L×n (number of
person).

Table 8-1 Model Selection Suggestion

Applicable Range
Model

A family of three or four persons
GRS-2.3Pd/TD200ANpH-K

A family of four or five persons
GRS-2.3Pd/TD270ANpH-K
NOTE:

Above suggested range is just for reference, please select the appropriate model according to
user's need.

9

Sayfa 12

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI 519070

Add: West Jinji Rd, Qianshan Zhuhai, Guangdong, China
Tel: (+86-756)8522218
Fax: (+86-756)8669426
E-mail: gree@cn.gree.com www.gree.com