T-FRESH_SERVICE_MANUAL

Bu sayfa, kılavuzun PDF dosyasındaki metnin tamamıdır (sayfa sayfa). Görseller ve çizimler için PDF'i açın. — sibastore.com

Sayfa 1

Change for life

Service Manual

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Sayfa 2

Table of Contents

Part Ⅰ: Technical Information................................... 2

1. Summary.............................................................................. 2

2. Specifications...................................................................... 3

2.1 Specification Sheet..................................................................................................3

2.2 Capacity Variation Ratio According to Temperature....................................5

2.3 Cooling and Heating Data Sheet in Rated Frequency.................................5

3. Outline Dimension Diagram............................................... 6
3.1 Indoor Unit...................................................................................................................6

3.2 Outdoor Unit...............................................................................................................7

4. Refrigerant System Diagram.............................................. 8
5. Electrical Part...................................................................... 9
5.1 Wiring Diagram..........................................................................................................9

5.2 PCB Printed Diagram.............................................................................................11

6. Function and Control........................................................ 13
6.1 Function Buttons of Air Conditioner................................................................13

6.2 Remote Controller Introduction.........................................................................15

6.3 GREE+ App Operation Manual...........................................................................19

6.4 Ewpe Smart App Operation Manual.................................................................20

6.4 Brief Description of Models and Functions...................................................21

Part Ⅱ: Installation and Maintenance ................. 23

7. Notes for Installation and Maintenance.......................... 23
8. Installation......................................................................... 30
8.1 Installation Dimension Diagram........................................................................30

8.2 Installation Parts-checking ................................................................................32

8.3 Selection of Installation Location.....................................................................32

8.4 Electric Connection Requirement.....................................................................32

Table of Contents

Sayfa 3

8.5 Installation of Indoor Unit....................................................................................33

8.6 Installation of Outdoor unit.................................................................................34

8.7 Vacuum Pumping and Leak Detection............................................................36

8.8 Check after Installation and Test operation..................................................37

9. Maintenance...................................................................... 38
9.1 Error Code List........................................................................................................38

9.2 Procedure of Troubleshooting...........................................................................43

9.3 Troubleshooting for Normal Malfunction.......................................................55

10. Exploded View and Parts List........................................ 57
10.1 Indoor Unit..............................................................................................................57

10.2 Outdoor Unit...........................................................................................................59

11. Removal Procedure......................................................... 61
11.1 Removal Procedure of Indoor Unit.................................................................61

11.2 Removal Procedure of Outdoor Unit.............................................................66

Appendix............................................................................ 72

Appendix 1: Reference Sheet of Celsius and Fahrenheit...............................72

Appendix 2: Configuration of Connection Pipe..................................................72

Appendix 3: Pipe Expanding Method.....................................................................73

Appendix 4: List of Resistance for Temperature Sensor................................74

Table of Contents

Sayfa 4

1. Summary

Indoor Unit: 

GVH32ALXH-K6DNC7A/I
GWH32QFXH-K6DNB2A/O

Remote Controller:

YAP1F11

2
Technical Information

Outdoor Unit:

Sayfa 5

2. Specifications

2.1 Specification Sheet

Model 
GVH32ALXH-K6DNC7A

Rated Voltage
V~
220-240

Power 
Supply

Rated Frequency
Hz
50

Phases
--
1

Power Supply Mode
--
Outdoor

Cooling Capacity
W
10000

Heating Capacity
W
10300

Cooling Power Input
W
2730

Heating Power Input
W
3029

Cooling Current Input
A
11.5

Heating Current Input
A
13.5

Rated Input
W
4200

Rated Cooling  Current
A
18

Rated Heating Current
A
17

Air Flow Volume
m

Dehumidifying Volume
L/h
5.00

EER 
W/W
3.66

COP 
W/W
3.40

AEER
3.73

ACOP
3.73

Application Area
m

Model
GVH32ALXH-K6DNC7A/I

Product Code
CH156N05700

Fan Type
Centrifugal

Fan Diameter Length(D×L) 
mm
Ф379×180.5

Cooling Speed
r/min
600/560/530/500

Heating Speed
r/min
600/560/530/500

Fan Motor Power Output
W
150

Fan Motor RLA
A
/

Fan Motor Capacitor 
μF
/

Evaporator Form 
--
Aluminum Fin-copper Tube

Evaporator Pipe Diameter
mm
Ф7.94

Evaporator Row-fin Gap
mm
3-1.5

Evaporator Coil Length (L×D×W)  
mm
472×62×836

Indoor Unit 

Swing Motor Model
--
MP35AB/MP24TA

Swing Motor Power Output
W
2.5/1.5

Fuse Current
A
5

Sound Pressure Level 
dB (A) 
52/50/48/47

Sound Power Level
dB (A) 
64/62/60/59

Dimension (WXHXD) 
mm
587X1882X394

Dimension of Carton Box (LXWXH)
mm
2150X735X530

Dimension of Package (LXWXH) 
mm
2153X738X545

Net Weight  
kg
57

Gross Weight
kg
79.5

3
Technical Information

3/h
1850/1600/1450/1300

2
55-85

Sayfa 6

Outdoor Unit Model
GWH32QFXH-K6DNB2A/O

Outdoor Unit Product Code
CB432W27300

Compressor Manufacturer
ZHUHAI LANDA COMPRESSOR CO.,LTD

Compressor Model
QXFS-D280zX070

Compressor Oil
/

Compressor Type
Rotary

Compressor LRA.  
A
40.00

Compressor RLA  
A
4.90

Compressor Power Input
W
2294

Compressor Overload Protector
/

Throttling Method
Electron expansion valve

Set Temperature Range 
ºC
16~30
Cooling Operation  Ambient 
Temperature Range 
ºC
-10~50

Heating Operation  Ambient 
Temperature Range 
ºC
-15~24

Condenser  Form 
Aluminum Fin-copper Tube

Condenser  Pipe Diameter 
mm
Ф7

Condenser  Rows-fin Gap
mm
3-1.4

Condenser  Coil Length (LXDXW)  
mm
955X57.15X704

Fan Motor Speed
rpm
850

Outdoor 

Fan Motor Power Output
W
90

Unit

Fan Motor RLA  
A
0.70

Fan Motor Capacitor 
μF
/

Outdoor Unit Air Flow Volume
m

Fan Type
Axial-flow

Fan Diameter
mm
570

Defrosting Method
Automatic Defrosting

Climate Type
T1

Isolation
I

Moisture Protection
IPX4

Permissible Excessive Operating 
Pressure for the Discharge Side
MPa
4.3

Permissible Excessive Operating 
Pressure for the Suction Side
MPa
2.5

Sound Pressure Level (H/M/L) 
dB (A) 
62

Sound Power Level (H/M/L) 
dB (A) 
71

Dimension(WXHXD) 
mm
1000X746X427

Dimension of Carton Box (LXWXH)
mm
1077X480X785

Dimension of Package(LXWXH)
mm
1080X483X810

Net Weight  
kg
59.5

Gross Weight
kg
64.5

Refrigerant 
R32

Refrigerant Charge
kg
1.9

Connection Pipe Length
m
5

Connection Pipe Gas Additional Charge
g/m
40

Outer Diameter Liquid Pipe
1/4"

Connection 

Outer Diameter Gas Pipe
5/8"

Pipe

Max Distance Height
m
10

Max Distance Length
m
25

Note: The connection pipe applies metric diameter.

The above data is subject to change without notice. Please refer to the nameplate of the unit.

4
Technical Information

3/h
4500

Sayfa 7

2.2 Capacity Variation Ratio According to Temperature

Heating
Cooling

120

120

100

100

Capacity ratio(%)

Capacity ratio(%)

80

80

60

60

Condition
Indoor:DB27°C WB19°C
Indoor air flow: Super High
Pipe length:5m

Conditions
Indoor:DB20°C
Indoor air flow:Super High

40

40

20

20

Pipe length:5m

0

0

-15 
-10
-7 -5 
7
6
-3
0
5 
10 
15 
20
18 
24

10
-10
-5
0
5
15
25
35
20
30
40
45
50

2.3 Cooling and Heating Data Sheet in Rated Frequency

Cooling:

Pressure of gas pipe connecting 

Inlet and outlet pipe temperature of 

Rated cooling condition(°C) (DB/WB) 

indoor and outdoor unit

heat exchanger
Fan speed of 

Fan speed of 

Model

outdoor unit
Indoor 
Outdoor 
P (MPa) 
T1 (°C) 
T2 (°C) 

indoor unit

27/19
35/24
32K
0.8~1.0
in:10~13
out:16~19

in:75~ 85
out:32~38
Super High
High

Heating:

Pressure of gas pipe connecting 

Inlet and outlet pipe temperature of 

Rated heating condition(°C) (DB/WB) 

indoor and outdoor unit

heat exchanger
Fan speed of 

Fan speed of 

Model

outdoor unit
Indoor 
Outdoor 
P (MPa) 
T1 (°C) 
T2 (°C) 

indoor unit

20/-
7/6
32K
2.5~2.7
in:60~70
out:33~39

in:-2~0
out:10~13
Super High
High

Instruction:
T1: Inlet and outlet pipe temperature of evaporator 
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.

5
Technical Information

Sayfa 8

3. Outline Dimension Diagram

3.1 Indoor Unit

6
Technical Information

+

:
'

Model
W
H
D

32K
587
1882
394

Sayfa 9

3.2 Outdoor Unit

369

746

427

395

Unit:mm

7
Technical Information

923

1000

610

Sayfa 10

4. Refrigerant System Diagram

Indoor unit 

Suction
 
Heat
exchanger
(evaporator)  
Heat 

Connection pipe specification:
Liquid pipe:1/4" 
Gas pipe:5/8"

8
Technical Information

Outdoor unit 

Gas pipe
side

Valve

4-Way valve 

Discharge

Accumlator
Compr
r

esso

r) 
exchanger

side
Liquid pipe

(condense

 Valve

Electric 
expand 
valve

Strainer
Strainer

COOLING 

HEATING 

Sayfa 11

5. Electrical Part

5.1 Wiring Diagram

●Instruction

Symbol
Symbol Color 
Symbol
Symbol Color 
Symbol
Name

WH
White
GN
Green
CAP
Jumper cap

YE
Yellow
BN 
Brown
COMP
Compressor

RD
Red
BU
Blue
Grounding wire

YEGN
Yellow/Green
BK 
Black
/
/

VT
Violet
OG
Orange
/
/

Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.

● Indoor Unit

TEMP.
ROOM

TEMP.
TUBE

DC-MOTOR
SENSOR

Note: Motor ground only 
applies to the iron shell 
motor.  

SENSOR
UP-DOWN
STEPPING

LEFT-RIGHT

M1
YEGN

STEPPING

MOTOR

MOTOR

PE

θ
θ
M3
M2

MAGNETIC
RING
L2

RT1
RT2

MAGNETIC

RING

XT

N
SWING-UD

SWING-LR

DC-MOTOR

L1

T-SENSOR

BU

BU

OUTDOOR UNIT

N(1)

L1

BK

BK

AP1

COM

2

(COM-OUT)

L1

PRINTED CIRCUIT BOARD

L
BN

AC-L
BN

BN

3

REACTOR

YEGN

YEGN

COM-DISPLAY

RD
BN

PE

L3

TERMINAL

BLOCK

X2
X1
AP4

YEGN

(OPTIONAL)
WIFI CONTACT

PE

PE

AP3
CN42

COM-MAIN

AP2

DISPLAY

600007064918

9
Technical Information

Sayfa 12

● Outdoor Unit

COMP.

OPTIONAL

Please don't touch any terminal when 
the machine is running ,stopping or has 
been powered off for less than 30 
minutes to prevent the risk of electric 
shock!

OVERLOAD
PROTECTOR

COMP

EXHAUST
TEMP.
OUTROOM
TEMP.
OUTTUBE

U

TEMP.
SENSOR SENSOR
SENSOR

V
W
BU

YE
RD

MAGNETIC

SAT

15K
20K
50K
RT1

RING

L1
L1
L1

WH WH

RT3
RT2

T-SENSOR

(T-SEN)

CN2

OVC-COMP

MAGNETIC RING

XT

BU

L2

BU

PRINTED CIRCUIT BOARD
AP1:

INDOOR UNIT

N(1)

N

L2

BK

BK
BN

(DRED)

(COM-IN)

2

COM-INNER

L2

(DRED-COMMU)
(DRED-DC)

BN

L(3)

AC-L
E

FA

DRED-COM
DRED-POWER

YEGN

OFAN

4WAY

YEGN

TERMINAL

PE

BLOCK

PE

BU
BN(BK)

VT
VT

L
N

CN1
CN3
DRED
CN4

4YV
EKV

YEGN

YEGN

M

ELECTRONIC

MAIN BOARD

PE

PE

POWER

EXPANSION 

VALVE
4-WAY

FAN

VALVE

PE

MOTOR

OPTIONAL
OPTIONAL

OPTIONAL

DRED
MODULE

600007064715 

OPTIONAL

These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.

10
Technical Information

Sayfa 13

5.2 PCB Printed Diagram

Indoor Unit

1
2
3
4
5

6

No.
Name 
No.
Name 

1
Interface of live wire
6
Interface of earthing wire

2
Fuse
7
Connection needle stand of display 
board 

3
Interface of communication wire for 
outdoor unit  
8
Left & right swing interface

4
Interface of netural wire 
9
Up & down swing interface

5
Motor interface of indoor unit 
10
Needle stand of temperature sensor

11
Technical Information

10

7
8
9

Sayfa 14

Outdoor Unit

1

2

3

4

5

6

7

8

9

10

11

12

13
14

No.
Name 
No.
Name 

1
Neutral wire
8
Terminal of high pressure protection

2
Grounding wire
9
Temperature sensor 

3
Live wire
10
Overload interface of compressor

4
Communication wire
11
Terminal of electronic expansion valve

5
4-way valve
12
Terminal of DRED

6
Electric heating belt of chassis
13
E disk(Reserved)

7
Outdoor fan
14
Terminal of compressor wire

12
Technical Information

Sayfa 15

6. Function and Control

6.1 Function Buttons of Air Conditioner

Buttons Name and Function

1
ON/OFF button

2
MODE button

3
FAN button

4
FUNCTION button

5

3

1

5

ON/OFF

FAN

6
/
button

2

4

MODE

FUNC.

6

Introduction for icons on display screen of air conditioner

Ambient temperature 
or set temperature 
display or others

Timer 
display

Operation

display

E-Heater display

Cooling display

Defrosting display

Dry display

Heating display

Fan display

Fan speed display

NOTE:

For cooling only unit, pressing MODE button under FAN mode 

will skip heating mode and enter cooling mode.)

This series unit adopts touch buttons. You only need to touch the 

buttons slightly. 

3. FAN button

1. ON/OFF button

Press this button and then fan speed can be selected and 

displayed in the sequence as below: 

● Press this button to turn on or turn off the unit. (Note: Under 

(low) 
(medium)
(high) 

X-FAN mode, press this button to turn on the unit directly.)

(turbo)

2. MODE button

(Note:Only low fan speed is available for dry mode.  Fan speed 

● Every time press this button, the mode will switchover in cycle 

can't be adjusted under dry mode. Turbo cannot be set in FAN 

among.

mode.)

COOLING
DRY

4. FUNCTION button

HEATING
FAN

Under on status, press Function button to switch between timer 

(Note: Cooling only unit won’t accept heating operation signal. 

and auxiliary heating function setting (auxiliary heating can be 

13
Technical Information

Sayfa 16

set only in heating mode). When timer or auxiliary heating icon 

is blinking, it means this function can be set. Press "▲" or "▼" 

button to set function. If there’s no operation change within 5s 

after setting is finished, the function setting will be confirmed. Or 

press Function button again to exit or confirm the function. When 

the function is selected through Function button, if the unit is not 

turned off and no remote control signal is received within 2min, 

pressing FUNCTION button again to circulate from the previous 

set function. After 2min or the unit is turned off or remote control 

signal is received, pressing FUNCTION button again to circulate 

from timer icon. (Note: Only when the unit is under heating mode 

and with auxiliary heating function, auxiliary heating function 

can be turned on or off through FUNCTION button.)

● Under off status, if the unit is in X-FAN status, press Function 

button to turn off the unit directly; if the unit is not in X-FAN 

status, press FUNCTION button to set timer ON. 

5. ▲ / ▼ button

● After each pressing of "▲" or "▼" button, set temperature will 

increase or decrease 1°C. Temperature adjustment range is 

16°C~30°C. This button is invalid under auto mode. Timer setting 

can be set in 1h increment among 0~24h. When it is adjusted to 

auxiliary heating function setting through Function button, press 

this button to turn on or turn off auxiliary heating. (Note: auxiliary 

heating is valid only for the model with this function.) 

● Hold "▲" and "▼" buttons for 3s and the air conditioner will 

display "LC", which indicates buttons are locked. Any button 

under on status or ON/OFF button and function buttons under 

off status are all invalid. Hold these two button for 3s again to 

release the lock.

6. 
 / 
 button

● Left and right swing: this button controls the left and right 

swing motor, single press it to switchover between ON and OFF.

● Up and down swing: this button controls the up and down 

swing motor, single press it to switchover between ON and OFF.

Set upper and lower limit of temperature

● Under off status, hold “▲” button for 5s to set the upper limit of 

temperature and then the set upper limit temperature will flash; 

hold “▲” or “ ▼ ”button to adjust the upper limit of temperature 

and then the set upper limit temperature will be displayed for 3s.

● Under off status, hold “▼”button for 5s to set the lower limit of 

temperature and the set lower limit temperature will flash; hold “▲” 

or “▼ ”button to adjust the lower limit of temperature, and then 

the set lower.

Note:

1.After setting upper/lower limit temperature, it's valid under 

cooling, heating, dry and fan modes.

2.The set lower limit temperature should be lower than the set 

14
Technical Information

upper limit temperature.

3.Upper temperature limit can be set only after the lower 

temperature limit has been set; lower temperature limit can be 

set only after the upper temperature limit has been set.

4.Note:If it needs to enter compulsive defrosting, freon recovery 

or adjustable memory function, resume the set upper/lower limit 

temperature to 16ºC-30ºC manually.

This function is only available for some models.

Icon function introduction

 Operation display

It indicates the air conditioner is put through the power. Under on 

status, this indicator is on; under off status, this indicator is off. 

 Timer display

When this indicator is on, it indicates the timer function is turned 

on.

 Heating display

When this indicator is on, it indicates the heating mode is turned 

on.

 Defrosting display

When this indicator is on, it indicates the defrosting function is 

turned on.

 Dry display

When this indicator is on, it indicates the dry mode is turned on. 

 E-Heater display

When this indicator is on, it indicates the E-heater function is 

turned on. (Only available for some heat pump unit)

 Cooling display

When this indicator is on, it indicates the cooling mode is turned 

on. 

 Fan display

When this indicator is on, it indicates the fan mode is turned on.

 Fan speed display

Displays the fan speed. The fan speed is displayed as below:

(low) 
(medium)
(high) 

(turbo)

Sayfa 17

6.2 Remote Controller Introduction

Buttons on remote controller

1
7

8
2
9

4
3
10
5

6
7
9

13
10

14
11

12
15

Introduction for icons on display screen

only after turning it on.)
Operation mode

Auto mode
Cool mode

Dry mode

Fan mode

Heat mode

Set time

TIMER ON/TIMER OFF

Turbo fan speed

Quiet mode

X-FAN function

Introduction for buttons on remote controller

NOTE:

● This is a general use remote controller, it could be used for 

the air conditioners with multifunction; For some function, which 

the model doesn't have, if press the corresponding button on 

the remote controller that the unit will keep the original running 

status.

● After putting through the power, the air conditioner will give 

out a sound. Operation indicator " 
 " is ON . After that, you can 

operate the air conditioner by using remote controller.

15
Technical Information

1
ON/OFF button

2
MODE button

3
FAN button

4
SAVE button

5

6

COOL button

HEAT button

     button

     button

SLEEP button

11
WiFi button

12

X-FAN button

 button 

8
13

P

14
LIGHT button

15
TIMER button

Set fan speed
(No

{

,

fan speed. It’s displayed

Send signal

battery power
 This is a general remote controller.Some 
 models have this function while some
 do not. Please refer to the actual models.

WiFi{

Child lock

Switch temperature displaying type on
the unit’s display

function
Left & right swing
Up & down swing

P

Sleep mode

● Under on status, pressing the button on the remote controller, 

the signal icon " 
 " on the display of remote controller will blink 

once and the air conditioner will give out a “di” sound, which 

means the signal has been sent to the air conditioner.

1. ON/OFF button

Press this button can turn on or turn off the air conditioner. After 

turning on the air conditioner, indoor unit will give out a sound.

2. MODE button

Press this button to select your required operation mode.

Sayfa 18

When selecting auto mode, air conditioner will operate 

automatically according to the sensed temperature. Set 

temperature can’t be adjusted and will not be displayed as well. 

Press "FAN" button can adjust fan speed. Press " 
 " / " 
 " 

button can adjust fan blowing angle.

● After selecting cool mode, air conditioner will operate under 

cool mode. Cool indicator " 
 " on indoor unit is ON (This 

indicator is not available for some models). Press "▲" or "▼" 

button to adjust set temperature. Press "FAN" button to adjust 

fan speed. Press " 
 " / " 
 " button to adjust fan blowing angle.

● When selecting dry mode, the air conditioner operates at low 

speed under dry mode. Dry indicator " 
 " on indoor unit is 

ON(This indicator is not available for some models). Under dry 

mode, fan speed can’t be adjusted. Press " 
 " / " 
 " button to 

adjust fan blowing angle.

● When selecting fan mode, the air conditioner will only blow fan, 

no cooling and no heating. Fan indicator " 
 " on indoor unit is 

ON. Press "FAN" button to adjust fan speed. Press " 
 " / " 
 " 

button to adjust fan blowing angle.

● When selecting heating mode, the air conditioner operates 

under heat mode. Heat indicator " 
 " on indoor unit is ON(This 

indicator is not available for some models). Press "▲" or "▼" 

button to adjust set temperature. Press "FAN" button to adjust 

fan speed. Press " 
 " / " 
 "  button to adjust fan blowing angle. 

(Cooling only unit won’t receive heating mode signal. If setting 

heat mode with remote controller, press ON/OFF button can’t 

start up the unit).

NOTE:

● For preventing cold air, after starting up heating mode, indoor 

unit will delay 1~5 minutes to blow air (actual delay time is 

depend on indoor ambient temperature).

● Set temperature range from remote controller: 16~30°C 

(61~86°F); Fan speed: auto, quiet speed, low speed, medium 

speed, high speed, turbo speed.

3. FAN button

Pressing this button can set fan speed circularly as: auto (AUTO), 

QUIET( 
 ), low(  ), medium( 
 ), high( 
 ), turbo( 
 ).

● Under AUTO speed, air conditioner will select proper fan 

speed automatically according to ex-factory setting.

● It’s Low fan speed under Dry mode.

● Turbo cannot be set in FAN mode.

4. SAVE button

Under cooling mode, press this button to start up or turn off 

16
Technical Information

energy-saving function. When energy-saving function is started 

up, "SE" will be shown on remote controller, and air conditioner 

will adjust the set temperature automatically according to ex-

factory setting to reach to the best energy-saving effect. Press 

this button again to exit energy-saving function.

5. ▲ / ▼ button

● Press "▲" or "▼" button once increase or decrease set 

temperature 1°C (°F). Holding "▲" or "▼" button, 2s later, 

set temperature on remote controller will change quickly. On 

releasing button after setting is finished, temperature indicator 

on indoor unit will change accordingly. (Temperature can’t be 

adjusted under auto mode)

● When setting TIMER ON, TIMER OFF, press "▲" or "▼" button 

to adjust time. (Refer to TIMER button for details)

6. COOL button

● Press this button, unit will operate in cool mode.

7. HEAT button

● Press this button, unit will operate in heat mode.

8. 
 button

● Under simple swing mode, press this button can turn on (" 
 

" icon is displayed) or turn off (" 
 " icon is not displayed) the 

left & right swing function.

● When the unit is turned off by remote controller, press "▲" 

button and " 
 " button can switch between single swing mode 

and fixed-angle swing mode. " 
 " on the remote controller will 

flash twice. Under fixed-angle swing mode, press this button and 

then left&right swing status will circulate as shown in the right 

figure:

no display

● This remote controller is the general type remote controller. 

When remote controller receives the signal of " 
 " , swing 

status is same as " 
 " ; when remote controller receives " 
 ", 

swing status is same as left & right swing OFF.

9. 
 button

● Under simple swing mode, press this button can turn on ( " 
 

" icon is displayed) or turn off (" 
 " icon is not displayed) the 

up & down swing function. 

● When the unit is turned off by remote controller, press "▲" 

button and " 
 " button can switch between single swing mode 

and fixed-angle swing mode. " 
 " on the remote controller will 

flash twice. Under fixed-angle swing mode, press this button and 

the up & down swing status will circulate as shown in the right 

figure:

no display

Sayfa 19

10. SLEEP button

Under COOL or HEAT mode, press this button to start up sleep 

function. " 
 " icon is displayed on remote controller. Press 

this button again to cancel sleep function and " 
 " icon will 

disappear. After powered on, Sleep Off is defaulted. After the 

unit is turned off, the Sleep function is canceled. In this mode, 

set temperature will be adjusted with the change of time. Under 

Fan, DRY and Auto modes, this function is not available.

11. WiFi button

Press "WiFi" button to turn on WiFi function, "WiFi" icon will be 

displayed on the remote controller; Hold "WiFi" button for 5s to 

turn off WiFi function and "WiFi" icon will disappear. Under off 

status, press "MODE" and "WiFi" buttons simultaneously for 1s, 

WiFi module will restore factory settings.

● This function is only available for some models.

12. X-FAN button

Pressing this button in COOL or DRY mode, the icon " 
 " 

is displayed and the indoor fan will continue operation for a 

few minutes in order to dry the indoor unit even though you 

have turned off the unit. After energization, X-FAN OFF is 

defaulted. X-FAN is not available in AUTO, FAN or HEAT mode.

This function indicates that moisture on evaporator of indoor unit 

will be blowed after the unit is stopped to avoid mould.

● Having set X-FAN function on: After turning off the unit by 

pressing ON/OFF button indoor fan will continue running for 

about a few minutes. at low speed. In this period, press X-FAN 

button to stop indoor fan directly.

● Having set X-FAN function off: After turning off the unit by 

pressing ON/OFF button, the complete unit will be off directly.

● Only under cooling mode and dry mode, press this button 

can turn on (characters of “X-FAN” are displayed) or turn off 

(characters of “X-FAN” are not displayed) X-FAN function.

13. 
 button

 function is for limiting power of the whole unit. Press this 

button, the controller will cercularly display as the following:

● Maximum power limited under the 
 mode is lower than that of 

 mode.

● If you want to cancel the power limiting function, press the 

button 
 till the icon in remote controller is not displayed.

● When the remote controller is turned off, power limiting 

function is cancelled. If you want to activate the function, please 

repress this button.

● If the current power is lower than the maximum power of  
 

mode, then the power will not be limited after entering into such 

mode.

● For the model with one outdoor unit and two indoor units, if 

17
Technical Information

any one of indoor units enters into power limiting function, the 

outdoor unit will enter into the set limiting power mode of indoor 

unit; when two indoor units enter into power limiting mode, then 

the power of outdoor unit will be limited according to the lower 

power of the two indoor units.

NOTE:

● This function is only available for some models.

14. LIGHT button

Press this button to turn off display light on indoor unit. Press 

this button again to turn on display light. 

15. TIMER button

● At ON status, press this button once can set TIMER OFF. The 

character of HOUR and OFF will flash. Press "▲" or "▼" button 

within 5s can adjust the time of TIMER ON. After each pressing 

of "▲" or "▼" button time will increase or decrease half an hour. 

When holding "▲" or "▼" button, 2s later, the time will change 

quickly until to reach to your required time. After that, press 

"TIMER" button to confirm it. The character of HOUR and OFF 

won't flash again. Cancel TIMER OFF: Press "TIMER" button 

again under TIMER OFF status.

● At OFF status, press this button once can set TIMER ON. 

Please refer to TIMER off for detailed operation. 

Cancel TIMER ON: Press "TIMER" button again under TIMER 

ON status.

NOTE:

● Time setting range: 0.5-24 hours.

● Time interval between two operations can’t exceed 5s. 

Otherwise, remote controller will exit the setting status 

automatically.

Function introduction for combination buttons

Child lock function

Press "▲" and "▼" simultaneously to turn on or turn off child lock 

function. When child lock function is on, " 
 "  icon is displayed 

on remote controller. If you operate the remote controller, the 

" 
 " icon will blink three times without sending signal to the unit.

blank
No Setting

Temperature display switchover function

Under OFF status, press "▼" and " MODE" but tons 

simultaneously to switch temperature display between °C and °F.

Auto clean function

Under unit off status, hold "MODE" and "FAN" buttons 

simultaneously for 5s to turn on or turn off the auto clean function. 

When the auto clean function is turned on, indoor unit displays 

"CL" . During the auto clean process of evaporator, the unit will 

perform fast cooling or fast heating. There may be some noise, 

which is the sound of flowing liquid or thermal expansion or cold 

shrinkage. The air conditioner may blow cool or warm air, which 

is a normal phenomenon. During cleaning process, please make 

sure the room is well ventilated to avoid affecting the comfort.

Sayfa 20

Note:

● The auto clean function can only work under normal ambient 

temperature. If the room is dusty, clean it once a month; if not, 

clean it once every three months. After the auto clean function 

is turned on, you can leave the room. When auto clean is 

finished,the air conditioner will enter standby status.

● This function is only available for some models.

Replacement of batteries in remote controller

1. Lift the cover along the direction of arrow (as shown in Fig 1① ).

2. Take out the original batteries (as shown in Fig 1 ② ).

3. Place two 7# (AAA 1.5V) dry batteries, and make sure the 

position of “ + ” polar and “ - ” polar is correct (as shown in Fig 2 

③ ).

4. Reinstall the cover (as shown in Fig 2 ④ ).

①

④

②

③

Fig.1
Fig.2 

NOTICE:

● During operation, point the remote control signal sender at the 

receiving window on indoor unit.

● The distance between signal sender and receiving window 

should be no more than 8m, and there should be no obstacles 

between them.

● Signal may be interfered easily in the room where there is 

fluorescent lamp or wireless telephone; remote controller should 

be close to indoor unit during operation.

● Replace new batteries of the same model when replacement is 

required.

● When you don’t use remote controller for a long time, please 

take out the batteries.

● If the display on remote controller is fuzzy or there’s no display, 

please replace batteries.

18
Technical Information

Sayfa 21

6.3 GREE+ App Operation Manual

Control Flow Chart

Home Wi-Fi
Gree

intelligent

home
appliances

Home wireless router

Operating Systems

Requirement for User's smart phone:

iOS system
Support iOS7.0 and 
above version 

Download and installation

GREE+ App Download Linkage 

Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the 
account and add the device to achieve long-distance control and LAN control of Gree smart home appliances. 
For more information, please refer to "Help" in App.

19
Technical Information

Internet

Gree Cloud

Cellular/
Other Wi-FI

Home Wi-Fi

GREE+ APP

Android system
Support Android 4.4 and 
above version

Sayfa 22

6.4 Ewpe Smart App Operation Manual

Control Flow Chart

intelligent

Home Wi-Fi

home
appliances

Home wireless router

Operating Systems

Requirement for User's smart phone:

iOS system
Support iOS7.0 and 
above version 

Download and installation

App Download Linkage 

Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed, 
register the account and add the device to achieve long-distance control and LAN control of smart home appliances. 
For more information, please refer to "Help" in App.

20
Technical Information

Internet

Cloud

Cellular/
Other Wi-FI

Home Wi-Fi

APP

Android system
Support Android 4.4 and 
above version

Sayfa 23

6.4 Brief Description of Models and Functions

●Indoor Unit

1.Basic function of system
(1)Cooling mode
(1) Under this mode, fan and swing operates at setting status. 
Temperature setting range is 16~30

OC. 
(2) During malfunction of outdoor unit or the unit is stopped 
because of protection, indoor unit keeps original operation status.
(2)Drying mode
(1) Under this mode, fan operates at low speed and swing 
operates at setting status. Temperature setting range is 16~30

OC. 
(2) During malfunction of outdoor unit or the unit is stopped 
because of protection, indoor unit keeps original operation status. 
(3) Protection status is same as that under cooling mode.
(4) Sleep function is not available for drying mode.
(3)Heating mode
(1) Under this mode, Temperature setting range is 16~30

OC. 
(2) Working condition and process for heating mode:
When turn on the unit under heating mode, indoor unit enters into 
cold air prevention status. When the unit is stopped or at OFF 
status, and indoor unit has been started up just now, the unit 
enters into residual heat-blowing status.
(4)Working method for AUTO mode:
1.Working condition and process for AUTO mode:
a.Under AUTO mode, standard heating Tpreset=20

OC and 
standard cooling Tpreset=25

OC. The unit will switch mode 
automatically according to ambient temperature.
2.Protection function
a. During cooling operation, protection function is same as that 
under cooling mode.
b. During heating operation, protection function is same as that 
under heating mode.
3. Display: Set temperature is the set value under each condition. 
Ambient temperature is (Tamb.-Tcompensation) for heat pump 
unit and Tamb. for cooling only unit. 
4. If theres I feel function, Tcompensation is 0. Others are same 
as above.
(5)Fan mode
Under this mode, indoor fan operates at set fan speed. 
Compressor, outdoor fan, 4-way valve and electric heating tube 
stop operation. Indoor fan can select to operate at high, medium, 
low or auto fan speed. Temperature setting range is 16~30

OC.
2. Other control 
(1) Buzzer
Upon energization or availably operating the unit or remote 
controller, the buzzer will give out a beep.
(2) Auto button
If press this auto button when turning off the unit, the complete 
unit will operate at auto mode. Indoor fan operates at auto fan 
speed and swing function is turned on. Press this auto button at 
ON status to turn off the unit.
(3) Auto fan
Heating mode: During auto heating mode or normal heating ode, 
auto fan speed will adjust the fan speed automatically according 
to ambient temperature and set temperature.
(4) Sleep
After setting sleep function for a period of time, system will adjust 
set temperature automatically.
(5) Timer function:
General timer and clock timer functions are compatible by 
equipping remote controller with different functions.
(6) Memory function
memorize compensation temperature, off-peak energization value.

21
Technical Information

Memory content: mode, up&down swing, light, set temperature, 
set fan speed, general timer (clock timer Can't be memorized).
After power recovery, the unit will be turned on automatically 
according to memory content.
(7) Health function
During operation of indoor fan, set health function by remote 
controller. Turn off the unit will also turn off health function.
Turn on the unit by pressing auto button, and the health is 
defaulted ON.
(8)I feel control mode
After controller received I feel control signal and ambient 
temperature sent by remote controller, controller will work 
according to the ambient temperature sent by remote controller.
(9)Entry condition for compulsory defrosting function
When turn on the unit under heating ode and set temperature is 
16
OC (or 16.5

OC by remote controller), press “ , 
, 
, 
, 
, 
” 
button successively within 5s and then indoor unit will enter into 
compulsory defrosting setting status:
(1) If theres only indoor units controller, it enters into indoor normal 
defrosting mode.
(2) If theres indoor units controller and outdoor units controller, 
indoor unit will send compulsory defrosting mode signal to outdoor 
unit and then outdoor unit will operate under normal defrosting 
mode. After indoor unit received the signal that outdoor unit has 
entered into defrosting status, indoor unit will cancel to send 
compulsory mode to outdoor unit. If outdoor unit hasnt received 
feedback signal from outdoor unit after 3min, indoor unit will also 
cancel to send compulsory defrosting signal.
(10)Refrigerant recovery function: 
Enter into Freon recovery mode actively: Within 5min after 
energization, turn on the unit at 16

OC under cooling mode, and 
press light button for 3 times within 3s to enter into Freon recovery 
mode. Fo is displayed and Freon recovery mode will be sent to 
outdoor unit.
(11)Ambient temperature display control mode
1. When user set the remote controller to display set temperature 
(corresponding remote control code: 01), current set temperature 
will be displayed. 
2. Only when remote control signal is switched to indoor ambient 
temperature display status (corresponding remote control code: 
10) from other display status (corresponding remote control code: 
00, 01,11),controller will display indoor ambient temperature for 3s 
and then turn back to display set temperature.
Under this mode, indoor fan operates at set fan speed. 
Compressor, outdoor fan, 4-way valve and electric heating tube 
stop operation. Indoor fan can select to operate at high, medium, 
low or auto fan speed. Temperature setting range is 16~30

OC.
(12)Off-peak energization function:
Adjust compressors minimum stop time. The original minimum 
stop time is 180s and then we change to: 
The time interval between two start-ups of compressor Can't be 
less than 180+Ts(0≤T≤15). T is the variable of controller. Thats to 
say the minimum stop time of compressor is 180s~195s. Read-
in T into memory chip when refurbish the memory chip each time. 
After power recovery, compressor can only be started up after 
180+T s at least.
(13) SE control mode
The unit operates at SE status. 
(14) X-fan mode
When X-fan function is turned on, after turn off the unit, indoor fan 
will still operate at low speed for 2min and then the complete unit 
will be turned off. When x-fan function is turned off, after turn off 
the unit, the complete unit will be turned off directly.

Sayfa 24

(15) 8

OC heating function
Under heating mode, you can set 8

oCheating function by remote 
controller. The system will operate at 8

oC set temperature. 
(16)Turbo function
Turbo function can be set under cooling and heating modes. 
Press Fan Speed button to cancel turbo setting. Turbo function is 
not available under auto, drying and fan modes.

●Outdoor Unit

1. Cooling mode:
Working condition and process of cooling mode:
① When Tindoor ambient temperature≥Tpreset, unit enters into 
cooling mode. Indoor fan, outdoor fan and compressor start 
operation. Indoor fan operates according to set fan speed.
② When Tindoor ambient temperature≤Tpreset-2

oC, compressor 
stops operation and outdoor fan will stop 30s later. Indoor fan 
operates according to set fan speed.
③ When Tpreset-2

oC <Tindoor ambient temperature <Tpreset, 
unit operates according to the previous status.
Under cooling mode, 4-way valve is not energized. Temperature 
setting range is 16~30

oC. If compressor stops because of 
malfunction in cooling mode, indoor fan and swing motor will work 
according to the original status.

2. Drying mode
(1) Working condition and process of drying mode
① When Tindoor ambient temperature >Tpreset, unit will be in 
drying mode. Outdoor fan and compressor start operation while 
indoor fan will operate at low fan speed.
② When Tpreset-2

oC≤Tindoor ambient temperature≤Tpreset, unit 
operates according to the previous status.
③ When Tindoor ambient temperature <Tpreset-2

oC, 
compressor stops operation and outdoor fan will stop 30s later.
(2) Under drying mode, 4-way valve is not energized. Temperature 
setting range is 16~30

oC.
(3) Protection function: same as in cooling mode.

3. Fan mode
(1) Under this mode, indoor fan can select different fan speed 
(except Turbo) or auto fan speed. Compressor, outdoor fan and 
4-way valve all stop operation.
(2) In fan mode, temperature setting range is 16~30

4. Heating mode
Working condition and process of heating mode:
① W h e n T p r e s e t - ( Ti n d o o r a m b i e n t t e m p e r a t u r e -
Tcompensation)≥1

oC, unit enters into heating mode. Compressor, 
outdoor fan and 4-way valve start operation.
② When -2

oC <Tpreset-(Tindoor ambient temperature-
Tcompensation) <1

oC, unit operates according to the previous
status.
③ When Tpreset-(Tindoor ambient temperature-Tcompensation)≤-
2
oC, compressor stops operation and outdoor fan will stop 30s 
later. Indoor fan will be in residual-heat blowing status.
④ When unit is turned off under heating mode or changed to other 
modes from heating mode, 4-way valve will be power-off 2min 
after compressor stops working (compressor is in operation status 
under heating mode).
⑤ When Toutdoor ambient temperature >30

oC, compressor 
stops operation immediately. Outdoor fan will stop 30s later.
⑥ Under the condition that compressor is turned on, when unit 
is changed to heating mode from cooling or drying mode, 4-way 
valve will be energized in 2~3mins delay.
Note: Tcompensation is determined by IDU and ODU. If IDU 
controls the compensation temperature, then Tcompensation is
determined according to the value sent by IDU to ODU; If 

22
Technical Information

IDU does not control the compensation temperature, then 
Tcompensation will default to 3

oC by the ODU.

5. Freon recovery mode
After the Freon recovery signal from IDU is received, cooling at 
rated frequency will be forcibly turned on to recover Freon.
Indoor unit will display Fo. If any signal from remote controller is 
received, unit will exit from Freon recovery mode and indoor unit 
stops displaying Fo.

6. Compulsory defrosting
If unit is turned on under heating mode and set temperature is 
16
oC (by remote controller), press “ , , , , , ” within 5s, unit 
will enter into compulsory defrosting mode and send the signal 
to ODU. When the compulsory defrosting signal from ODU is 
received, IDU will exit from the compulsory defrosting mode and 
stop sending the signal to ODU.
After ODU receives the compulsory defrosting code, it will start 
compulsory defrosting. Defrosting frequency and opening
angle will be the same as in normal defrosting mode. When 
compulsory defrosting is finished, the complete unit resumes
original status.

7. Auto mode
Auto mode is determined by controller of IDU. See IDU logic for 
details.

8. 8
oC heating
Set temperature is 8

oC. Under 
this mode, “Cold air prevention” function is shielded.
If compressor is operating under this mode, fan speed will adjust 
according to auto fan speed; if compressor stops operation
under this mode, indoor fan will be in residual-heat blowing status.

oC. Display board of IDU displays 8

When power on, communication light will be blinking in a 
normal way (after receiving a group of correct signals,
blinking stops for 0.2s~0.3s). If theres no communication, 
communication light will be always on. If other ODU has
malfunction, communication light will be on for 1s and off for 
1s in a circular way.

oC.

Sayfa 25

7. Notes for Installation and Maintenance

Safety Precautions: Important!

Please read the safety precautions carefully before 
installation and maintenance.
The following contents are very important for installation and 
maintenance.

Please follow the instructions below.

●The installation or maintenance must accord with the 
instructions.
●Comply with all national electrical codes and local electrical 
codes.
●Pay attention to the warnings and cautions in this manual.
●All installation and maintenance shall be performed by 
distributor or qualified person.
●All electric work must be performed by a licensed technician 
according to local regulations and the instructions given in 
this manual.
●Be caution during installation and maintenance. Prohibit 
incorrect operation to prevent electric shock, casualty and 
other accidents.

WARNINGS

Electrical Safety Precautions:

1. Cut off the power supply of air conditioner before checking 
and maintenance.
2. The air condition must apply specialized circuit and 
prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable location 
and ensure the power plug is touchable.
4. Make sure each wiring terminal is connected firmly during 
installation and maintenance.
5. Have the unit adequately grounded. The grounding wire 
Can't be used for other purposes.
6. Must apply protective accessories such as protective 
boards, cable-cross loop and wire clip.
7. The live wire, neutral wire and grounding wire of power 
supply must be corresponding to the live wire, neutral wire 
and grounding wire of the air conditioner.  
8. The power cord and power connection wires Can't be 
pressed by hard objects.
9. If power cord or connection wire is broken, it must be 
replaced by a qualified person.
10. If the power cord or connection wire is not long enough, 
please get the specialized power cord or connection wire 
from the manufacture or distributor. Prohibit prolong the wire 
by yourself.
11. For the air conditioner without plug, an air switch must 
be installed in the circuit. The air switch should be all-pole 
parting and the contact parting distance should be more than 
3mm.

23
Installation and Maintenance

12. Make sure all wires and pipes are connected properly and 
the valves are opened before energizing.
13. Check if there is electric leakage on the unit body. If yes, 
please eliminate the electric leakage.
14. Replace the fuse with a new one of the same specification 
if it is burnt down; dont replace it with a cooper wire or 
conducting wire.
15. If the unit is to be installed in a humid place, the circuit 
breaker must be installed.

Installation Safety Precautions:

1. Select the installation location according to the requirement 
of this manual.(See the requirements in installation part)
2. Handle unit transportation with care; the unit should not be 
carried by only one person if it is more than 20kg.
3. When installing the indoor unit and outdoor unit, a 
sufficient fixing bolt must be installed; make sure the 
installation support is firm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components 
during installation.
6. Make sure no foreign objects are left in the unit after 
finishing installation.

Refrigerant Safety Precautions:

1. When refrigerant leaks or requires discharge during 
installation, maintenance, or disassembly, it should be 
handled by certified professionals or otherwise in compliance 
with local laws and regulations.
2.Avoid contact between refrigerant and fire as it generates 
poisonous gas; Prohibit prolong the connection pipe by 
welding.
3. Apply specified refrigerant only. Never have it mixed with 
any other refrigerant. Never have air remain in the refrigerant 
line as it may lead to rupture or other hazards.
4. Make sure no refrigerant gas is leaking out when 
installation is completed.
5. If there is refrigerant leakage, please take sufficient 
measure to minimize the density of refrigerant.
6. Never touch the refrigerant piping or compressor without 
wearing glove to avoid scald or frostbite.

Improper installation may lead to fire hazard, 
explosion, electric shock or injury.

Sayfa 26

Safety Precautions for Installing and Relocating the Unit:

To ensure safety, please be mindful of the following precautions. 

WARNINGS

1. When installing or relocating the unit, be sure to 
keep the refrigerant circuit free from air or substances 
other than the specified refrigerant.

Any presence of air or other foreign substance in the refrigerant 
circuit will cause system pressure rise or compressor rupture, 
resulting in injury.

2.When installing or moving this unit, do not charge 
the refrigerant which is not comply with that on the 
nameplate or unqualified refrigerant.

Otherwise, it may cause abnormal operation, wrong action, 
mechanical malfunction or even series safety accident.

3.When refrigerant needs to be recovered during 
relocating or repairing the unit, be sure that the unit is 
running in cooling mode.Then, fully close the valve at 
high pressure side (liquid valve).About 30-40 seconds 
later, fully close the valve at low pressure side (gas 
valve), immediately stop the unit and disconnect power. 
Please note that the time for refrigerant recovery 
should  not exceed 1 minute. 

If refrigerant recovery takes too much time, air may be sucked in 
and cause pressure rise or compressor rupture, resulting in injury. 

4.During refrigerant recovery, make sure that liquid 
valve and gas valve are fully closed and power is 
disconnected before detaching the connection pipe. 

24
Installation and Maintenance

If compressor starts running when stop valve is open and 
connection pipe is not yet connected, air will be sucked in and 
cause pressure rise or compressor rupture, resulting in injury.

5.When installing the unit, make sure that connection 
pipe is securely connected before the compressor 
starts running.

If compressor starts running when stop valve is open and 
connection pipe is not yet connected, air will be sucked in and 
cause pressure rise or compressor rupture, resulting in injury.

6.Prohibit installing the unit at the place where there 
may be leaked corrosive gas or flammable gas.

If there leaked gas around the unit, it may cause explosion and 
other accidents.

7.Do not use extension cords for electrical connections. 
If the electric wire is not long enough, please contact 
a local service center authorized  and ask for a proper 
electric wire.

Poor connections may lead to electric shock or fire.

8.Use the specified types of wires for electrical 
connections between the indoor and outdoor units. 
Firmly clamp the wires so that their terminals receive 
no external stresses.

Electric wires with insufficient capacity, wrong wire connections 
and insecure wire terminals may cause electric shock or fire.

Sayfa 27

Safety Precautions for Refrigerant

●To realize the function of the air conditioner unit, a special 
refrigerant circulates in the system. The used refrigerant is 
the fluoride R32, which is specially cleaned. The refrigerant 
is flammable and inodorous. Furthermore, it can leads to 
explosion under certain conditions. But the flammability of 
the refrigerant is very low. It can be ignited only by fire.
●Compared to common refrigerants, R32 is a nonpolluting 
refrigerant with no harm to the ozonosphere. The influence 
upon the greenhouse effect is also lower. R32 has got very 
good thermodynamic features which lead to a really high 
energy efficiency. The units therefore need a less filling.

WARNINGS

●Do not use means to accelerate the defrosting process or to 
clean, other than those recommended by the manufacturer.
The appliance shall be stored in a room without continuously 
operating ignition sources (for example: open flames, an 
operating gas appliance or an operating electric heater.
●Do not pierce or burn.
●Be aware that refrigerants may not contain an odour.
● That compliance with national gas regulations shall be 
observed;
●The appliance shall be stored so as to prevent mechanical 
damage from occurring.
●Appliance shall be installed, operated and stored in a room 
with a floor area larger than Xm

2.
●Appliance filled with flammable gas R32. For repairs, 
strictly follow manufacturers instructions only. Be aware that 
refrigrants not contain odour.
●Read specialists manual.

Safety Operation of Flammable Refrigerant

Qualification of workers

●Any person who is involved with working on or breaking 
into a refrigerant circuit should hold a current valid certificate 
from an industry-accredited assessment authority, which 
authorises their competence to handle refrigerants safely 
in accordance with an industry recognised assessment 
specification.
●Servicing shall only be performed as recommended by the 
equipment manufacturer. Maintenance and repair requiring 
the assistance of other skilled personnel shall be carried out 
under the supervision of the person competent in the use of 
flammable refrigerants.

Information about the correct working procedures

● Installation and Commissioning
●The air conditioner is not allowed to use in a room that has 

25
Installation and Maintenance

running fire (such as fire source,working coal gas ware, operating 
heater).
●It is not allowed to drill hole or burn the connection pipe.
●The air conditioner must be installed in a room that is larger than 
the minimum room area.
The minimum room area is shown on the nameplate or following 
table a.

2 )

table a - Minimum room area ( m

The release 

Charge amount (kg)
<1.836 1.9 2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3 3.1 3.2 3.3
0.6
/
32 35 38 42 46 50 54 59 63 68 73 78 83 88 94

height(m)

●Connect the pipes and carry out a leak test before charging with 
refrigerant.

● Maintenance
●Portable equipment shall be repaired outside or in a workshop 
specially equipped for servicing units with flammable 
refrigerants.
●Ensure sufficient ventilation at the repair place.
●Be aware that malfunction of the equipment may be caused by 
refrigerant loss and a refrigerant leak is possible.
●Discharge capacitors in a way that won't cause any spark. The 
standard procedure to short circuit the capacitor terminals usually 
creates sparks.
●Reassemble sealed enclosures accurately. If seals are worn, 
replace them.
●Check safety equipment before putting into service.

● Repair
• Portable equipment shall be repaired outside or in a workshop 
specially equipped for servicing units with flammable 
refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by 
refrigerant loss and a refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark.
• When brazing is required, the following procedures shall be 
carried out in the right order:
– Remove the refrigerant. If the recovery is not required by 
national regulations, drain the refrigerant to the outside. Take care 
that the drained refrigerant will not cause any danger. In doubt, 
one person should guard the outlet. Take special care that drained 
refrigerant will not float back into the building.
– Evacuate the refrigerant circuit.
– Purge the refrigerant circuit with nitrogen for 5 min (not required 
for A2L refrigerants).
– Evacuate again (not required for A2L refrigerants).
– Remove parts to be replaced by cutting, not by flame.
– Purge the braze point with nitrogen during the brazing 
procedure.
– Carry out a leak test before charging with refrigerant.
• Reassemble sealed enclosures accurately. If seals are worn, 
replace them.
• Check safety equipment before putting into service.

● Decommissioning
• If the safety is affected when the equipment is putted out 
of service, the refrigerant charge shall be removed before 
decommissioning.
• Ensure sufficient ventilation at the equipment location.
• Be aware that malfunction of the equipment may be caused by 
refrigerant loss and a refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark.
• Remove the refrigerant. If the recovery is not required by national 
regulations, drain the refrigerant to the outside. Take care that the 

Sayfa 28

drained refrigerant will not cause any danger. In doubt, one person 
should guard the outlet. Take special care that drained refrigerant 
will not float back into the building.
• When flammable refrigerants except A2L refrigerants are used,
– Evacuate the refrigerant circuit.
– Purge the refrigerant circuit with nitrogen for 5 min.
– Evacuate again.
– Fill with nitrogen up to atmospheric pressure.
– Put a label on the equipment that the refrigerant is removed.

● Disposal
•  Ensure sufficient ventilation at the working place.
•  Remove the refrigerant. If the recovery is not required by national 
regulations, drain the refrigerant to the outside. Take care that the 
drained refrigerant will not cause any danger. In doubt, one person 
should guard the outlet. Take special care that drained refrigerant 
will not float back into the building.
•  When flammable refrigerants except A2L refrigerants are 
used,
– Evacuate the refrigerant circuit.
– Purge the refrigerant circuit with nitrogen for 5 min.
– Evacuate again.
– Cut out the compressor and drain the oil.
•  Evacuate the refrigerant circuit.
•  Purge the refrigerant circuit with nitrogen for 5 min.
•  Evacuate again.
•  Cut out the compressor and drain the oil.

Safety instructions for transportation and storage
●Please use the flammable gas detector to check before unload 
and open the container.
●No fire source and smoking.
●According to the local rules and laws.

Information on servicing

●Checks to the area

Prior to beginning work on systems containing flammable 
refrigerants, safety checks are necessary to ensure that the risk 
of ignition is minimised. For repair to the refrigerating system, the 
following precautions shall be completed prior to conducting work 
on the system.

●Work procedure
Work shall be undertaken under a controlled procedure so as to 
minimise the risk of a flammable gas or vapour being present while 
the work is being performed.

●General work area
All maintenance staff and others working in the local area shall be 
instructed on the nature of work being carried out. Work in confined 
spaces shall be avoided.

●Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector 
prior to and during work, to ensure the technician is aware of 
potentially toxic or flammable atmospheres. Ensure that the 
leak detection equipment being used is suitable for use with all 
applicable refrigerants, i.e. non-sparking, adequately sealed or 
intrinsically safe.

●Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment 
or any associated parts, appropriate fire extinguishing equipment 
shall be available to hand. Have a dry powder or CO2 fire 
extinguisher adjacent to the charging area.

26
Installation and Maintenance

●No ignition sources
No person carrying out work in relation to a refrigerating system 
which involves exposing any pipe work shall use any sources 
of ignition in such a manner that it may lead to the risk of fire 
or explosion. All possible ignition sources, including cigarette 
smoking, should be kept sufficiently far away from the site of 
installation, repairing, removing and disposal, during which 
refrigerant can possibly be released to the surrounding space. 
Prior to work taking place, the area around the equipment is to be 
surveyed to make sure that there are no flammable hazards or 
ignition risks. “No Smoking” signs shall be displayed.

●Ventilated area
Ensure that the area is in the open or that it is adequately 
ventilated before breaking into the system or conducting any hot 
work. A degree of ventilation shall continue during the period that 
the work is carried out. The ventilation should safely disperse 
any released refrigerant and preferably expel it externally into the 
atmosphere.

●Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit 
for the purpose and to the
correct specification. At all times the manufacturer’s maintenance 
and service guidelines shall
be followed. If in doubt, consult the manufacturer’s technical 
department for assistance.
The following checks shall be applied to installations using 
flammable refrigerants:
---the actual refrigerant charge is in accordance with the room 
size within which the refrigerant containing parts are installed;
---the ventilation machinery and outlets are operating adequately 
and are not obstructed;
---if an indirect refrigerating circuit is being used, the secondary 
circuit shall be checked for the presence of refrigerant;
---marking to the equipment continues to be visible and legible. 
Markings and signs that are illegible shall be corrected;
---refrigerating pipe or components are installed in a position 
where they are unlikely to be exposed to any substance which 
may corrode refrigerant containing components, unless the 
components are constructed of materials which are inherently 
resistant to being corroded or are suitably protected against being 
so corroded.

●Checks to electrical devices
Repair and maintenance to electrical components shall include 
initial safety checks and component inspection procedures. If a 
fault exists that could compromise safety, then no electrical supply 
shall be connected to the circuit until it is satisfactorily dealt with. 
If the fault cannot be corrected immediately but it is necessary to 
continue operation, an adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so all parties 
are advised.
Initial safety checks shall include:
● that capacitors are discharged: this shall be done in a safe 
manner to avoid possibility of sparking;
● that no live electrical components and wiring are exposed while 
charging, recovering or purging the system;
● that there is continuity of earth bonding.

Repairs to sealed components
1. During repairs to sealed components, all electrical supplies shall 
be disconnected from the equipment being worked upon prior to 
any removal of sealed covers, etc. If it is absolutely necessary 

Sayfa 29

to have an electrical supply to equipment during servicing, then a 
permanently operating form of leak detection shall be located at 
the most critical point to warn of a potentially hazardous situation.
2. Particular attention shall be paid to the following to ensure that 
by working on electrical components, the casing is not altered in 
such a way that the level of protection is affected. This shall include 
damage to cables, excessive number of connections, terminals not 
made to original specification, damage to seals, incorrect fitting of 
glands, etc. 
Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the 
point that they no longer serve the purpose of preventing the 
ingress of flammable atmospheres. Replacement parts shall be in 
accordance with the manufacturer’s specifications.

Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the 
circuit without ensuring that this will not exceed the permissible 
voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked 
on while live in the presence of a flammable atmosphere. The test 
apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. 
Other parts may result in the ignition of refrigerant in the 
atmosphere from a leak.
NOTE The use of silicon sealant can inhibit the effectiveness 
of some types of leak detection equipment.Intrinsically safe 
components do not have to be isolated prior to working on them.

Cabling
Check that cabling will not be subject to wear, corrosion, 
excessive pressure, vibration, sharp edges or any other adverse 
environmental effects. The check shall also take into account 
the effects of aging or continual vibration from sources such as 
compressors or fans.

Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used 
in the searching for or detection of refrigerant leaks. A halide torch 
(or any other detector using a naked flame) shall not be used.
The following leak detection methods are deemed acceptable for 
all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks 
but, in the case of flammable refrigerants, the sensitivity may not 
be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free 
area.) Ensure that the detector is not a potential source of ignition 
and is suitable for the refrigerant used. Leak detection equipment 
shall be set at a percentage of the LFL of the refrigerant and shall 
be calibrated to the refrigerant employed, and the appropriate 
percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are also suitable for use with most 
refrigerants but the use of detergents containing chlorine shall be 
avoided as the chlorine may react with the refrigerant and corrode 
the copper pipe-work.
NOTE Examples of leak detection fluids are
– bubble method,
– fluorescent method agents.
If a leak is suspected, all naked flames shall be removed/
extinguished.
If a leakage of refrigerant is found which requires brazing, all of the 
refrigerant shall be
recovered from the system, or isolated (by means of shut off 
valves) in a part of the system

27
Installation and Maintenance

remote from the leak. Removal of refrigerant shall be according to 
"Removal and evacuation".

Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or 
for any other purpose – conventional procedures shall be used. 
However, for flammable refrigerants it is important that best 
practice is followed since flammability is a consideration. The 
following procedure shall be adhered to:
• remove refrigerant;
• purge the circuit with inert gas (optional for A2L);
• evacuate (optional for A2L);
• purge with inert gas (optional for A2L);
• open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct 
recovery cylinders. For appliances containing flammable 
refrigerants other than A2L refrigerants, the system shall be 
purged with oxygen-free nitrogen to render the appliance safe for 
flammable refrigerants. This process may need to be repeated 
several times. Compressed air or oxygen shall not be used for 
purging refrigerant systems.
For appliances containing flammable refrigerants, other than A2L 
refrigerants, refrigerants purging shall be achieved by breaking 
the vacuum in the system with oxygen-free nitrogen and continuing 
to fill until the working pressure is achieved, then venting to 
atmosphere, and finally pulling down to a vacuum. This process 
shall be repeated until no refrigerant is within the system. When 
the final oxygen-free nitrogen charge is used, the system shall be 
vented down to atmospheric pressure to enable work to take place. 
This operation is absolutely vital if brazing operations on the pipe-
work are to take place.
Ensure that the outlet for the vacuum pump is not close to any 
potential ignition sources and that ventilation is available.

Charging procedures
In addition to conventional charging procedures, the following 
requirements shall be followed.
• Ensure that contamination of different refrigerants does not occur 
when using charging equipment. Hoses or lines shall be as short 
as possible to minimise the amount of refrigerant contained in 
them.
• Cylinders shall be kept in an appropriate position according to the 
instructions.
• Ensure that the refrigerating system is earthed prior to charging 
the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigerating 
system.
Prior to recharging the system, it shall be pressure-tested with the 
appropriate purging gas.
The system shall be leak-tested on completion of charging but 
prior to commissioning. A follow up leak test shall be carried out 
prior to leaving the site.

Decommissioning
Before carrying out this procedure, it is essential that the technician 
is completely familiar with the equipment and all its detail. It is 
recommended good practice that all refrigerants are recovered 
safely. Prior to the task being carried out, an oil and refrigerant 
sample shall be taken in case analysis is required prior to re-
use of recovered refrigerant. It is essential that electrical power is 
available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:

Sayfa 30

• mechanical handling equipment is available, if required, for 
handling refrigerant cylinders;
• all personal protective equipment is available and being used 
correctly;
• the recovery process is supervised at all times by a competent 
person;
• recovery equipment and cylinders conform to the appropriate 
standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant 
can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery 
takes place.
g) Start the recovery machine and operate in accordance with 
instructions.
h) Do not overfill cylinders (no more than 80 % volume liquid 
charge).
i) Do not exceed the maximum working pressure of the cylinder, 
even temporarily.
j) When the cylinders have been filled correctly and the process 
completed, make sure that the cylinders and the equipment 
are removed from site promptly and all isolation valves on the 
equipment are closed off.
k) Recovered refrigerant shall not be charged into another 
refrigerating system unless it has been cleaned and checked.

Labelling
Equipment shall be labelled stating that it has been de-
commissioned and emptied of refrigerant. The label shall be dated 
and signed. For appliances containing flammable refrigerants, 
ensure that there are labels on the equipment stating the 
equipment contains flammable refrigerant.

Recovery
When removing refrigerant from a system, either for servicing 
or decommissioning, it is recommended good practice that all 
refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only 
appropriate refrigerant recovery cylinders are employed. Ensure 
that the correct number of cylinders for holding the total system 
charge is available. All cylinders to be used are designated for 
the recovered refrigerant and labelled for that refrigerant (i.e. 
special cylinders for the recovery of refrigerant). Cylinders shall be 
complete with pressure-relief valve and associated shut-off valves 
in good working order. Empty recovery cylinders are evacuated 
and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a 
set of instructions concerning the equipment that is at hand and 
shall be suitable for the recovery of all appropriate refrigerants 
including, when applicable, flammable refrigerants. In addition, 
a set of calibrated weighing scales shall be available and in 
good working order. Hoses shall be complete with leak-free 
disconnect couplings and in good condition. Before using the 
recovery machine, check that it is in satisfactory working order, 
has been properly maintained and that any associated electrical 
components are sealed to prevent ignition in the event of a 
refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant 
supplier in the correct recovery cylinder, and the relevant waste 
transfer note arranged. Do not mix refrigerants in recovery units 
and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that 
they have been evacuated to an acceptable level to make certain 
that flammable refrigerant does not remain within the lubricant. 
The evacuation process shall be carried out prior to returning 

28
Installation and Maintenance

the compressor to the suppliers. Only electric heating to the 
compressor body shall be employed to accelerate this process. 
When oil is drained from a system, it shall be carried out safely.

Sayfa 31

Main Tools for Installation and Maintenance

Level meter
Measuring tape

Drill head
Electric drill

Torque wrench
Open-end wrench
Inner hexagon 

Vacuum pump

Pressure meter

Pipe cutter

Pipe bender
Pipe expander

Electronic scale
Refrigerant container

29
Installation and Maintenance

Screw driver

Impact drill

Electroprobe

Universal meter

Electronic 
leakage detector

spanner

Pipe pliers
Pipe pliers

Soldering appliance

Sayfa 32

8. Installation

8.1 Installation Dimension Diagram

the ceiling

Space to

>30cm

>200cm

Space to the obstuction

Space to the wall(30cm
at least for piping side)

>10cm

Space to the wall(30cm at
least for piping side)

>10cm

>5cm

Space to the back side 

obstruction
Space to the 

Space to the 

obstruction

> 50cm

>30cm

>30cm

Space to the wall

>50cm

Space to the
obstruction

Space to the obstruction

>200cm

Drainage pipe

30
Installation and Maintenance

Sayfa 33

Installation Procedures

31
Installation and Maintenance

 Start installation

Preparation before installation

Prepare tools
Read the requirements 
for electric connection

select installation 
location

Select indoor unit 
installation location

Select outdoor unit 
installation location

Install the support of outdoor unit
(select it according to the actual situation)

Install wall-mounting 
frame, drill wall holes

Connect pipes of indoor 
unit and drainage pipe

Fix outdoor unit

Install drainage joint of outdoor unit 
(only for cooling and heating unit)

Connect wires of indoor unit

Bind up pipes and 
hang the indoor unit

Make the bound pipes pass 
through the wall hole and then
 connect outdoor unit

Connect pipes of outdoor unit

Connect wires of outdoor unit

Neaten the pipes

Vacuum pumping and leakage detection

Check after installation and test operation

Finish installation

Note: this flow is only for reference; please find the more detailed installation steps in this se

Sayfa 34

8.2 Installation Parts-checking 

No.
Name

1
Indoor unit

2
Outdoor unit

3
Connection pipe

4
Drainage pipe

5
Connecting cable(power cord)

6
Wall pipe

7
Sealing gum

8
Wrapping tape

9
Support of outdoor unit

10
Fixing screw

11
Drainage plug(cooling and heating unit)

12
Owners manual, remote controller

Note:

1.Please contact the local agent for installation.
2.Dont use unqualified power cord.

8.3 Selection of Installation Location

1. Basic Requirement:
Installing the unit in the following places may cause malfunction. If 
it is unavoidable, please consult the local dealer:
(1) The place with strong heat sources, vapors, flammable or 
explosive gas, or volatile objects spread in the air.
(2) The place with high-frequency devices (such as welding 
machine, medical equipment).
(3) The place near coast area.
(4) The place with oil or fumes in the air.
(5) The place with sulfureted gas.
(6) Other places with special circumstances.
(7) The appliance shall nost be installed in the laundry.
(8) It’s not allowed to be installed on the unstable or motive base 
structure(such as truck) or in the corrosive environment (such as 
chemical factory).

2. Indoor Unit:
(1) Avoid installing the indoor unit in a place where generated or 
leaked inflammable gas will stay.
(2) Avoid installing the indoor unit in a moist place or in a place 
where oil may be splashed on the unit.
(3) Select a location where outlet air may reach each corner of the 
room.
(4) Select a location where connection pipe can be led to outdoor 
conveniently.
(5) Select a location where air inlet and outlet won't be blocked.
(6) Select a location with least affection of outdoor air.
(7) Select a location with firm and flat floor.
(8) Retain sufficient space for maintenance and installation.
(9) Ensure the installation meets the requirement of installation 
dimension diagram.
(10) Do not use the unit in the immediate surroundings of a 
laundry, a bath, a shower or a swimming pool.

32
Installation and Maintenance

3. Outdoor Unit:
(1) Select a location where the noise and outflow air emitted by 
the outdoor unit will not affect neighborhood.
(2) The location should be well ventilated and dry, in which the 
outdoor unit won't be exposed directly to sunlight or strong wind.
(3) The location should be able to withstand the weight of outdoor 
unit.
(4) Make sure that the installation follows the requirement of 
installation dimension diagram.
(5) Select a location which is out of reach for children and far 
away from animals or plants. If it is unavoidable, please add fence 
for safety purpose.
(6) The height difference between indoor unit and outdoor unit 
should be within 5m. The length of connection pipe should be 
within 10m.

8.4 Electric Connection Requirement

1. Safety Precaution
(1) Must follow the electric safety regulations when installing the 
unit.
(2) According to the local safety regulations, use qualified power 
supply circuit and air switch.
(3) Make sure the power supply matches with the requirement 
of air conditioner. Unstable power supply or incorrect wiring may 
result in electric shock, fire hazard or malfunction. Please install 
proper power supply cables before using the air conditioner.
(4) Properly connect the live wire, neutral wire and grounding wire 
of power socket.
(5) Be sure to cut off the power supply before proceeding any 
work related to electricity and safety.
(6) Do not put through the power before finishing installation.
(7) If the supply cord is damaged, it must be replaced by the 
manufacturer, its service agent or similarly qualified persons in 
order to avoid a hazard .
(8) The temperature of refrigerant circuit will be high, please keep 
the interconnection cable away from the copper tube.
(9) The appliance shall be installed in accordance with national 
wiring regulations.
(10) Appliance shall be installed, operated and stored in a room 
with a floor area larger than Xm

2(Please refer to table "a" in 
section of "Safety Operation of Inflammable Refrigerant" for Space 
X.)

Please notice that the unit is filled with 
flammable gas R32. Inappropriate treatment of 
the unit involves the risk of severe damages of 
people and material. Details to this refrigerant 
are found in chapter “refrigerant”.

2. Grounding Requirement:
(1) The air conditioner is the first class electric appliance.It must 
be properly grounding with specialized grounding device by a 
professional.
Please make sure it is always grounded effectively,otherwise it 
may cause electric shock.
(2) The yellow-green wire in air conditioner is grounding wire, 
which can't be used for other purposes.
(3) The grounding resistance should comply with national electric 
safety regulations.
(4) The appliance must be positioned so that the plug is 
accessible.

Sayfa 35

(5) An all-pole disconnection switch having a contact separation of 
at least 3mm in all poles should be connected in fixed wiring.
(6) Including an air switch with suitable capacity, please note 
the following table. Air switch should be included magnet buckle 
and heating buckle function, it can protect the circuit-short and 
overload. (Caution: please do not use the fuse only for protect the 
circuit)

Model
Air switch capacity
Power cord
32K
25A
3G2.5

8.5 Installation of Indoor Unit

1. Choosing Installation Iocation
Recommend the installation location to the client and then confirm 
it with the client.

2. Open piping hole
(1) Choose the position of piping hole according to the direction of 
outlet pipe. 
(2) Open a piping hole with the diameter of Φ70mm on the 
selected outlet pipe position. In order to drain smoothly, slant the 
piping hole on the wall slightly downward to the outdoor side with 
the gradient of 5-10°.(As show in Fig.1)

Indoor
Outdoor

5-10°
Φ70mm 

Fig.1

Note:

Pay attention to dust prevention and take relevant safety 

measures when opening the hole.

3. Connect the Pipe of Indoor Unit
(1) Remove the left and right screw covers, unscrew the screws 
that fix the air inlet panel, and remove the air inlet panel and filter.
(As show in Fig.2)
(2) According to the determined discharge method, unscrew the 
screws that fix the baffle(the rodent-proof plate), and remove the 
baffle at the corresponding position.
(3) Expand the connecting pipe and pass one end of the bellows 
through the routing hole.
(4) Bend the connecting pipe according to the required length, 
unscrew the nut on the indoor pipe, align the cone of the connecting 
pipe with the center of the corresponding indoor pipe, tighten the 
nut by hand, and then tighten it with a torque wrench.(As show in 
Fig.3)
(5) Wrap the indoor pipe and joint of connection pipe with 
insulating pipe, and then wrap it with tape. (As show in Fig.5)

33
Installation and Maintenance

screws

air-inlet panel

baffle(rodent-proof plate)

Fig.2

Open-end 
wrench

Union nut
Union nut
Pipe joint
Pipe

Pipe

Torque wrench

Indoor pipe

Fig.3
Fig.4

Refer to the following table for wrench moment of force:

Piping size
Tightening torque(N.m)

1/4"
15~20

3/8"
30~40

1/2"
45~55

5/8"
60~65

3/4"
70~75

Insulating pipe

Fig.5

4. Install Drain Hose
(1) Connect the drain hose to the outlet pipe of indoor unit.(As 
show in Fig.6)
(2) Bind the joint with tape.(As show in Fig.7)

Drain hose

Outlet pipe

drain hose
 

outlet pipe

Tape

Fig.6
Fig.7

Sayfa 36

Note:

(1) Add insulating pipe in the indoor drain hose in order to 

prevent condensation.

(2) The plastic expansion particles are not provided.

(As show in Fig.8)

Drain hose

Insulating pipe

Fig.8

5. Connect Wire of Indoor Unit
(1) Remove the cover of the electrical box and the pass wire slot 
cover.
(2) Connect the power connection wire to the wiring terminal 
according to the color, tighten the screw.
(3) Press the power connection wire with a crimping clamp, place 
the power connection wire in the wire groove, and fix it with a wire 
hook.
(4) Cover the cover of the electrical box and the cover of the cable 
groove.

N(1)
2

3

blue
black
yellow-
green

brown

Outdoor unit connection

Note: The wiring connect is for reference 
only, please refer to the actual one.

Fig.9

WARING:

(1) All wires of indoor unit and outdoor unit should be connected 
by a professional.
(2) If the length of power connection wire is insufficient, please 
contact the supplier for a new one. Avoid extending the wire by 
yourself. 

6. Wrap the connection pipe
(1) Wrap the connection pipe, the connection wire and the drain 
pipe together with an insulation sleeve, and then wrap it with a 
wrapping tape.
● Before wrapping, fix some positions for convenient 
wrapping. Fix the insulation sleeve at the position of the 
knock-off hole.
● Do not wrap too tightly.
● During wrapping, do not wrap the joint of connection pipe 
for subsequent leakage detection.
(2) Cut the sheet of the baffle(the rodent-proof plate), install the 
baffle back, adjust the position of the baffle up and down, and 
clamp the pipeline as much as possible.
(3) Tighten the baffle screws.

34
Installation and Maintenance

drain pipe
connection pipe

insulation 
sleeve

wrapping tape
connection 
pipe

drain pipe

sleeve
insulation 

wrapping tape

connection 
wire

Fig.10

indoor and outdoor power cord

indoor unit

gas pipe

liquid pipe

drain hose
band

Fig.11

9. place the Indoor Unit
(1) Put the bound pipes in the wall pipe and then make them pass 
through the wall hole.
(2) Stuff the gap between pipes and wall hole with sealing gum.
(3) Fix the wall pipe.(As show in Fig.12)

Indoor
Outdoor
Wall pipe
Sealing gum

Fig.12

Note:

Do not bend the drain hose too excessively in order to prevent 

blocking.

8.6 Installation of Outdoor unit

1. Fix the Support of Outdoor Unit(Select it according 
to the actual installation situation)
(1) Select installation location according to the house structure.
(2) Fix the support of outdoor unit on the selected location with 
expansion screws.

Note:

(1) Take sufficient protective measures when installing the 

outdoor unit.

(2) Make sure the support can withstand at least four times the 

unit weight.

(3) The outdoor unit should be installed at least 3cm above the 

floor in order to install drain joint.(As show in Fig.13)

(4) For the unit with cooling capacity of 2300W~5000W, 6 

Sayfa 37

Refer to the following table for wrench moment of force:

expansion screws are needed; for the unit with cooling capacity of 

Piping size
Tightening torque(N.m)

6000W~8000W, 8 expansion screws are needed; for the unit with 

cooling capacity of 10000W~16000W, 10 expansion screws are 

1/4"
15~20

needed.

3/8"
30~40

1/2"
45~55

5/8"
60~65

3/4"
70~75

5. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire and 

Drain vent

Chassis

power cord to the wiring terminal according to the color; fix them 

Outdoor drain joint
Drain hose

with screws.(As show in Fig.18)

At least 3cm above the floor

Fig.13
Fig.14

Note: the wiring connect is 

2. Install Drain Joint(Only for cooling and heating unit)
(1) Connect the outdoor drain joint into the hole on the chassis.
(2) Connect the drain hose into the drain vent.
(As show in Fig.14)

for reference only,please 

N(1)

2

L(3)

refer to the actual one.

yellow-
green

yellow-
green

brown

blue black brown blue

(black)

N
Indoor unit connection

L

3. Fix Outdoor Unit
(1) Place the outdoor unit on the support.
(2) Fix the foot holes of outdoor unit with bolts.
(As show in Fig.15)

POWER

Fig.18

(2) Fix the power connection wire and power cord with wire clip.

CAUTION

Foot holes

(1) After tightening the screw, pull the power cord slightly to check 

if it is firm.

(2) Never cut the power connection wire to prolong or shorten the 

Handle

distance.

Foot holes

(3)The connecting wire and connection pipe can't touch each other.

Valve cover

(4)Top cover of outdoor unit and electric box assembly should be 

Fig.15
Fig.16

fixed by the screw. Otherwise, it can cause a fire,or short circuit 

caused by water or dust.

4. Connect Indoor and Outdoor Pipes
(1) Remove the screw on the right handle and the valve cover of 
outdoor unit and then remove the handle and the valve cover.(As 
show in Fig.16)
(2) Remove the screw cap of valve and aim the pipe joint at the 
bellmouth of pipe.(As show in Fig.17)

(5) For the air conditioner without plug, an air switch must be 

installed in the line. The air switch should be all-pole parting and 

the contact parting distance should be more than 3mm.

6. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably and 
hidden possibly. Min. semidiameter of bending the pipe is 10cm.
(2) If the outdoor unit is higher than the wall hole, you must set 
a U-shaped curve in the pipe before pipe goes into the room, in 
order to prevent rain from getting into the room.(As show in Fig.19)

Liquid pipe

Pipe joint

Liquid
valve

gas pipe

Union nut

gas valve

Fig.17

(3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .

35
Installation and Maintenance

Sayfa 38

Liquid valve

Piezometer

Lo
Hi

Gas valve

the drain hose 
can't  raise 
upwards.

Valve cap

Refrigerant charging
vent

Wall

Nut of refrigerant

Charging vent

U-shaped curve

Vacuum pump

Drain hose

Fig.19
Fig.20

Inner hexagon
spanner

Note:

Open
Close

(1) The through-wall height of drain hose shouldn't be higher 
than the outlet pipe hole of indoor unit.(As show in Fig.20)
(2) Slant the drain hose slightly downwards. The drain hose 
can't be curved, raised and fluctuant, etc. (As show in Fig.21)
(3) The water outlet can't be placed in water in order to drain 
smoothly.(As show in Fig.22)

Fig.23

2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for 
leakage detection. Apply soap water at the suspected position and 
keep the soap water for more than 3min. If there are air bubbles 
coming out of this position, there's a leakage.

The drain hose 
can't be fluctuant

The water 
outlet can't 
be placed 
in water

The drain 
hose can't 
be fluctuant

The water outlet 
can't be fluctuant

Fig.21
Fig.22

8.7 Vacuum Pumping and Leak Detection

1. Use Vacuum Pump
(1) Remove the valve caps on the liquid valve and gas valve and 
the nut of refrigerant charging vent.
(2) Connect the charging hose of piezometer to the refrigerant 
charging vent of gas valve and then connect the other charging 
hose to the vacuum pump.
(3) Open the piezometer completely and operate for 10-15min to 
check if the pressure of piezometer remains in -0.1MPa.
(4) Close the vacuum pump and maintain this status for 1-2min 
to check if the pressure of piezometer remains in -0.1MPa. If the 
pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve 
and gas valve completely with inner hexagon spanner.
(6) Tighten the screw caps of valves and refrigerant charging 
vent.(As show in Fig.23)

36
Installation and Maintenance

Sayfa 39

8.8 Check after Installation and Test operation

1. Check after Installation
Check according to the following requirement after finishing 
installation.

NO.
Items to be checked
Possible malfunction

1
Has the unit been installed 
firmly?

2
Have you done the 
refrigerant leakage test?

3
Is heat insulation of pipeline 
sufficient?

4
Is water drained well?
It may cause condensation 
and water dripping.

Is the voltage of power 
supply according to the 
voltage marked on the 
nameplate?

5

6
Is electric wiring and pipeline 
installed correctly?

7
Is the unit grounded 
securely?

8
Does the power cord follow 
the specification?

9
Is there any obstruction in 
air inlet and air outlet?

10
The dust and sundries 
caused during installation 
are removed?

11
The gas valve and liquid 
valve of connection pipe are 
open completely?

12
Is the inlet and outlet of 
piping hole been covered?

2. Test Operation
(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote 
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and 
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16
oC, the air conditioner 
Can't start cooling.

37
Installation and Maintenance

The unit may drop, shake or 
emit noise.

It may cause insufficient 
cooling (heating) capacity.

It may cause condensation 
and water dripping.

It may cause malfunction or 
damage the parts.

It may cause malfunction or 
damage the parts.

It may cause electric 
leakage.

It may cause malfunction or 
damage the parts.

It may cause insufficient 
cooling (heating) capacity.

It may cause malfunction or 
damaging the parts.

It may cause insufficient 
cooling (heating) capacity.

It may cause insufficient 
cooling(heating) capacity or 
waster eletricity.

Sayfa 40

9. Maintenance

9.1 Error Code List

Error 
code 
Malfunction name 
AC status 
Possible causes 

Malfunction of jumper cap 
The complete unit stops operation 

Communication 
malfunction between 
indoor unit and outdoor 
unit 

Cool: compressor stops operation, 
while indoor fan operates;
Heat: all loads stops operation. 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates. 
Heat: all loads stops operation. 

IPM protection 

Cool/Dry: all loads stops operation 
except indoor fan. 
Heat: all loads stops operation. 

Malfunction of outdoor fan/
malfunction of DC motor 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates. 
Heat: all loads stops operation.

Overload protection of 
compressor 

Cool: compressor and outdoor fan 
stops operation, while indoor fan 
operates;
Heat: Compressor, outdoor fan 
and indoor fan stops operation. 

Refrigerant insufficient 
protection, cut-off 
protection of refrigerant 

Cool/Dry: indoor fan operates, 
while compressor and outdoor fan 
stops operation; 
Heat: all loads stops operation.

Indoor ambient 
temperature sensor is 
open/short-circuited

Cool/Dry: indoor fan operates, 
while compressor and outdoor fan 
stops operation;
Heat: all loads stops operation.

Indoor evaporator 
temperature sensor is 
open/short-circuited

No feedback from indoor 
unit’s motor 
The complete unit stops operation 

Indoor unit and outdoor 
can be matched with each 
other

Heat: compressor, outdoor unit 
and indoor fan stops operation. 
Capacity of indoor unit and outdoor unit can’t be matched. 

Heat: all loads are stopped; 
other modes: outdoor unit stops 
operation. 

Malfunction of jumper cap 
of outdoor unit 

Gas valve temperature 
sensor is ON / short-
circuited

38
Installation and Maintenance

1. Jumper cap is not installed in control panel;
2. Poor contact of jumper cap;
3. Jumper cap is damaged;
4. The tested circuit of jumper cap on control panel is abnormal.

See “Communication malfunction” 

See “IPM protection, over-phase current of compressor” 

1. Outdoor condenser, air inlet and air outlet are blocked by filth 
or dirt; 
2. Fan is blocked or loosened;
3. Motor or connection wire of motor is damaged; 
4. Main board of outdoor unit is damaged; 
(As for dual-outdoor fan, L3 indicates fan 1; LA indicates fan 2)

1. Overload wire of compressor is loose;
2. The overload protector is damaged. Under normal 
circumstances, the resistance between both ends of terminal is 
less than 1ohm. 
3.See “Overload protection of compressor , High discharge 
temperature protection of compressor” 

1. Is system cooling under high humidity environment, thus 
temperature difference of heat transfer is small;
2. Check whether the big valve and small valve of outdoor unit 
are opened completely;
3. Is the temperature sensor of evaporator of indoor unit loose?
4. Is the temperature sensor of condenser of outdoor unit loose?
5. Is the capillary or the electronic expansion valve blocked?
6. Is refrigerant leaking?

1. Temperature sensor is not well connected;
2. Temperature sensor is damaged 
3. Main board of indoor unit is damaged. 

1. Temperature sensor is not well connected;
2. Temperature sensor is damaged 
3. Main board of indoor unit is damaged. 

1. Is the fan blocked?
2. Is the motor terminal loose?
3. Is the connection wire of motor damaged?
4. Is the motor damaged?
5. Is the main board of indoor unit damaged? 

Jumper cap of outdoor unit hasn’t been installed. 

1. Temperature sensor is not well connected or damaged; 
2. The wire of temperature sensor is damaged, causing short 
circuit to copper pipe or outer casing;
3. Main board of outdoor unit is damaged.

Sayfa 41

Error 

code 
Malfunction name 
AC status 
Possible causes 

Liquid valve temperature 
sensor is ON / short-
circuited

Cool/Dry:  all loads stops operation 
except indoor fan; 
Heat: all loads stops operation. 

High pressure protection of 
system 

Cool: compressor, outdoor fan 
and indoor fan stop operation; 
Heat: compressor and outdoor fan 
stop operation at first. About 1min 
later, indoor fan stops operation; 
2mins later, the 4-way valve stop 
operation. 

Low pressure/low system 
pressure protection/
compressor low pressure 
protection   

Cool/Dry: compressor and outdoor 
fan stops operation, while indoor 
fan operates;
Heat: all loads stops operation. 

High discharge 
temperature protection of 
compressor 

Cool/Dry: compressor and outdoor 
fan stops operation, while indoor 
fan operates;
Heat: all loads stops operation. 

AC overcurrent protection

Mode shock/sysmte mode 
shock 

Load of indoor unit stops operation 
(indoor fan, E-heater, swing)

Cool: compressor stops operation 
while indoor fan operates; 
Heat: all loads stops operation. 

High temperature 
prevention protection 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; 
Heat: all loads stops operation.

 Malfunction of EEPROM

Cool/Dry: compressor and outdoor 
fan stops operation, while indoor 
fan operates. 

Refrigerant-recovery mode 

Cool/Dry: compressor and outdoor 
fan stop operation, while indoor fan 
operates; 
Heat: all loads stops operation. 

Outdoor ambient 
temperature is open/short-
circuited 

39
Installation and Maintenance

1. Temperature sensor is not well connected or damaged;
2. The wire of temperature sensor is damaged, causing short 
circuit to copper pipe or outer casing;
3. Main board of outdoor unit is damaged.

1. Heat exchange of outdoor unit is too dirty, or it blocked the air 
inlet/outlet;
2. Is power voltage normal; (three-phase unit)
3. Ambient temperature is too high;
4. Wiring of high pressure switch is loose or high pressure 
switch is damaged;
5. The internal system is blocked; (dirt blockage, ice blockage, 
oil blockage, angle valve is not completely opened)
6. Main board of outdoor unit is damaged;
7. Refrigerant is too much.

1. Low pressure switch is damaged;
2. Refrigerant inside the system is insufficient. 

See “Overload protection of compressor , High discharge 
temperature protection of compressor” 

1. Power voltage is unstable;
2. Power voltage is too low;
3. System load is too high, which leads to high current;
4. Heat exchange of indoor unit is too dirty, or it blocked the air 
inlet/outlet;
5. Fan motor operation is abnormal; the fan speed is too low or 
not functioning;
6. Compressor is blocked;
7. The internal system is blocked; (dirt blockage, ice blockage, 
oil blockage, angle valve is not completely opened)
8. Main board of outdoor unit is damaged.
See  “AC overcurrent protection”

Malfunction of one-to-more system; there may be two indoor 
units which has set the shock mode, such as one is cooling and 
the other is heating. 

See “High temperature prevention protection; high power; 
system isabnormal” 

Main board of outdoor unit is damaged. 

Refrigerant recovery. 
The maintenance personnel operate it when he is maintaining 
the unit. 

1. Temperature sensor is not connected well or damaged; 
2.Temperature sensor wire of outdoor unit is damaged; short 
circuit between the temperature sensor and copper pipe or outer 
case 
3.Main board of outdoor unit is damaged; 

Sayfa 42

Error 

code 
Malfunction name 
AC status 
Possible causes 

Cool/Dry: compressor and outdoor 
fan stop operation, while indoor fan 
operates; 
Heat: after operating for 3mins, all 
loads stops operation. 

Outdoor condenser 
temperature sensor is 
open/short-circuited

Outdoor air discharge 
temperature is open/short-
circuited

Complete unit stops operation; 
motor of sliding door is cut off 
power. 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; 
Heat: all loads stops operation.

Malfunction of micro switch

Cool/Dry:  all loads stops operation 
except indoor fan; 
Heat: all loads stops operation. 

System is abnormal 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation. 

Desynchronizing of 
compressor 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation.

PFC  protection 

Cool: compressor and outdoor fan 
stop operation; Heat: compressor 
and outdoor fan stop operation at 
first; about 1min later, indoor fan 
stops operation. 

Demagnetization 
protection of compressor

Communication 
malfunction between 
indoor unit and inspection 
board 

Normal operation 

Malfunction of humidity 
sensor 

Compressor, outdoor fan and 
indoor fan stop operation; 
The inspection board is damaged. 

Cool: compressor and outdoor fan 
stops operation, while indoor fan 
operates. 

High power protection 

Cool/Dry: compressor stops, while 
indoor fan operates; Heat: all loads 
stops operation. 

Start-up failed 

Cool: compressor and outdoor fan 
stop operation; Heat: compressor 
and outdoor fan stop operation at 
first; about 1min later, indoor fan 
stops operation. 

Lost phase 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation. 

Over-phase current 
protection of compressor 

40
Installation and Maintenance

1. Temperature sensor is not connected well or damaged; 
2. Temperature sensor wire of outdoor unit is damaged; short 
circuit between the temperature sensor and copper pipe or outer 
case;
3. Main board of outdoor unit is damaged. 

1. The exhaust temperature sensor is not connected well or 
damaged.
2.Temperature sensor wire of outdoor unit is damaged; short 
circuit between the temperature sensor and copper pipe or outer 
case 
3.Main board of outdoor unit is damaged; 

1. The sliding door is blocked; 
2. Malfunction of the photoelectric inspection panel of sliding 
door; 

See “High temperature prevention protection; high power; 
system isabnormal” 

See “Desynchronization diagnosis for compressor” 

1. The power grid quality is bad; AC input voltage fluctuates 
sharply;
2. Power plug of air conditioner or wiring board or reactor is not 
connected reliably;
3. Indoor and outdoor heat exchanger is too dirty, or air inlet/
outlet is blocked; 
4. Main board of outdoor unit is damaged.

1. The main board of outdoor unit is damaged;
2. Compressor is damaged; 

1. Poor connection between the indoor unit and the inspection 
board. 
2.The main board of indoor unit is damaged;
3. The inspection board is damaged;

See “High temperature prevention protection; high power; 
system is abnormal” 

See “Malfunction diagnosis for failure startup” 

1. The main board of outdoor unit is damaged; 
2. The compressor is damaged; 
3. The connection wire of compressor is not connected well.

See “Overload protection of compressor , High discharge 
temperature protection of compressor” 

Sayfa 43

Error 

code 
Malfunction name 
AC status 
Possible causes 

Cool: compressor and outdoor 
fan stops operation, while indoor 
fan operates; Heat: compressor, 
outdoor fan and indoor fan stop 
operation. 

Undefined outdoor unit 
error

Cool: compressor and outdoor fan 
stops operation; Heat: compressor 
and outdoor fan stop at first; 
about 1min later, indoor fan stops 
operation;  

Communication 
malfunction between the 
drive board and the main 
board 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation.

Circuit malfunction of 
module temperature 
sensor 

Cool: compressor stops operation, 
while indoor fan operates; Heat: all 
loads stops operation. 

Module overheating 
protection

Cool: compressor, outdoor fan and 
indoor fan stop operation; Heat: 
compressor and outdoor fan stop 
operation at first; about 1min later, 
indoor fan stops operation. 

Malfunction of ambient 
temperature sensor of 
drive board 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation.

DC bus voltage is too high

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation.

DC bus voltage is too low

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation. 

Charging malfunction of 
capacitor 

Cool: compressor and outdoor fan 
stop operation; Heat: compressor 
and outdoor fan stop operation at 
first; about 1min later, indoor fan 
stops operation. 

Malfunction of RF module 

Cool: compressor and outdoor 
fan stops operation, while indoor 
fan operates; Heat: compressor, 
outdoor fan and indoor fan stops 
operation. 

Phase current detection 
circuit malfunction of 

Cool: compressor and outdoor fan 
stop operation; Heat: compressor 
and outdoor fan stop operation at 
first; about 1min later, indoor fan 
stops operation. 

Lost phase protection of 
compressor 

41
Installation and Maintenance

1. Outdoor ambient temperature exceeds the operation range 
of unit (eg: less than-20

oC for cooling; more 
than 30

oC or more than 60

oC for heating); 
2. Are wires of compressor not connected tightly?
3. Failure startup of compressor?
4. Is compressor damaged?
5. Is main board damaged? 

1. The drive board is damaged;
2. The main board of outdoor unit is damaged;
3. The drive board and the main board is not connected well.

Replace outdoor control board 

1. Air inlet / air outlet of outdoor unit are blocked by filth or dirt;
2. Condenser of outdoor unit is blocked by filth or dirt; 
3. IPM screw of main board is not tightened;
4. Main board of outdoor unit is damaged; 

1. The ambient temperature sensor of the drive board is not 
connected well;
2. Malfunction of the ambient temperature sensor of drive board. 

1. Measure the voltage between position L and position N on the 
wiring board (XT). If it’s higher than 265 VAC, please turn on the 
unit until the power voltage is decreased to the normal range; 
2. If the AC input is normal, please replace the outdoor control 
board. 

1. Measure the voltage between position L and position N on the 
wiring board (XT). If it’s lower than 150 VAC, please turn on the 
unit until the power voltage is increased to the normal range; 
2. If the AC input is normal, please replace the outdoor control 
board.

See “Charging malfunction of capacitor” 

1. The connection wire of RF module is not connected well. 
2. Malfunction of RF module;

The control board is damaged

1. The main board of outdoor unit is damaged; 
2. The compressor is damaged; 
3. The connection wire of compressor is not connected well. 

Sayfa 44

Error 

code 
Malfunction name 
AC status 
Possible causes 

Cool/Dry: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation. 

DC bus voltage drop 
malfunction 

Cool: compressor and outdoor 
fan stops operation, while indoor 
fan operates; Heat: compressor, 
outdoor fan and indoor fan 
stops operation. 

Current detection 
malfunction of unit 

4-way valve is abnormal 
This malfunction occurs when 
the unit is heating. All loads 
stops operation. 

Malfunction of zero-
crossing signal of indoor 
unit 

Compressor, outdoor fan and 
indoor fan stop operation. 

Cool: compressor stops 
operation, while indoor fan 
operates; Heat: all loads stops 
operation. 

Zero-crossing malfunction 
of outdoor unit

Evaporator anti-freezing 
protection
Not error code, it is the status code in cooling process

Anti cold air protection
Not error code, it is the status code in cooling process

Defrosting
Heat indicator Flash once/10s
Not error code, it is the status code in cooling process

Analysis or processing of some of the malfunction display:
1. Compressor discharge protection
Possible causes: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short pass for condenser; the sys­
tem has noncondensing gas (such as air, water etc.); blockage of capillary assy (including filter); leakage inside four-way 
valve causes incorrect operation; malfunction of compressor; malfunction of protection relay; malfunction of discharge sen­
sor; outdoor temperature too high.
Processing method: refer to the malfunction analysis in the above section.
2. Low voltage overcurrent protection
Possible cause: Sudden drop of supply voltage.
3.Communication malfunction
Processing method: Check if communication signal cable is connected reliably.
4. Sensor open or short circuit
Processing method: Check whether sensor is normal, connected with the corre sponding position on the controller and if 
damage of lead wire is found.
5. Compressor over load protection
Possible causes: insufficient or too much refrigrant; blockage of capillary and increase of suction temp.; improper running of 
compressor, burning in or stuck of bearing, damage of discharge valve; malfunction of protector.
Processing method: adjust refrigerant amount; replace the capillary; replace the compressor; use universal meter to check if 
the contactor of compress or is fine when it is not overheated, if not replace the protector.
6. System malfunction
i.e.overload protection. When tube temperature(Check the temperature of outdoor heat exchanger when cooling and check 
the temperatur e of indoor heat exchanger when heating) is too high, protection will be activated.
Possible causes: Outdoor temperature is too high when cooling; insufficient outdoor air circulation; refrigerant flow malfunc­
tion.
please refer to the malfunction analysis in the previous section for handling method .
7. IPM module protection
Processing method:Once the module malfunction happens,if it persists for a long time and can not be selfcanceled, cut off 
the power and turn off the unit,and then re-energize the unit again after about 10 min. After repeating the procedure for sever 
times, if the malfunction still exists,replace the module.

42
Installation and Maintenance

The power voltage is unstable. 

1. Is the complete unit lacking of refrigerant?
2. There’s malfunction for the circuit of control board of outdoor 
unit. Replace the control board of outdoor unit. 

1. Power voltage is lower than AC175V;
2. Wiring terminal of 4-way valve is loose or broken;3. 4-way 
valve is damaged. Replace the 4-way valve. 

1. The power is abnormal;
2. Main board of indoor unit is damaged. 

Replace the control board of outdoor unit. 

Sayfa 45

9.2 Procedure of Troubleshooting

1. Troubleshooting for jumper cap  

Main check points: 
    (1) jumper cap   (2) control board of indoor unit 

43
Installation and Maintenance

Display shows “C5”

Check whether the main 
board of controller is inserted with 

Insert the equipped 
jumper cap 

N

jumper cap. 

Eliminate 
malfunction 

Y

N

Insert the jump cap 
tightly again 
Check whether the
jumper cap is not inserted 

Y

well. 

N

N
Y

Eliminate 
malfunction 

Replace the jumper 
cap with a new one 

Eliminate 
malfunction 

Y

Y

N

It's the malfunction of 
main board. Replace 
the main board with 
the a new one. 

End

Sayfa 46

2. Communication malfunction 
 

Main check points: 
    (1) Connection wire between indoor unit and outdoor unit   
    (2) Wiring inside the unit  
    (3) Communication circuit of control board of indoor unit 
    (4) Communication circuit of control board of outdoor unit 

Start

Check whether the 
unit has operated normally before 

N

the malfunction occurs. 

Y

Check the connection wire of 
indoor unit and outdoor unit 
according to the wiring diagram. 

Check whether the connection 
wire of controller inside the 
electric box of indoor/outdoor 
unit is loose. 

Is the 
connection correct? 

Y

N

N

Connect the connection 
wire of indoor/outdoor unit 
correctly according to the 
wiring diagram. 

Connect the connection wire of 
indoor/outdoor unit correctly 
according to the wiring diagram. 

Is the connection 
wire of electric box is 

Y

normal? 

N

Eliminate 
malfunction 

Check the communication 
circuit of outdoor unit 

N

Eliminate 
malfunction 

Is there's problem 
for the communication 

Replace the control 
board of outdoor unit.

Y

circuit? 

N

Eliminate 
malfunction 

N

Replace the control board 
of indoor unit.

Y

Y

Y

End

Note: method for checking the communication circuit of inverter split type and floor standing unit: cut off the 
communication wires of indoor/outdoor unit, and then measure the voltage between COM and N of the control board of 
outdoor unit (DC notch, about 56V)

44
Installation and Maintenance

Sayfa 47

3. IPM protection 
, over-phase current of compressor 

  
Main check points:
  (1) compressor COMP terminal   (2) power supply voltage  (3) compressor   
  (4) charging amount of refrigerant   (5) air inlet and air outlet of indoor/outdoor unit

   NOTE:The control board as below means the control board of outdoor unit.

Put through the 
power and turn 
on the unit 

Check the connection between 
the control board and the 
compressor according to the 
electric wiring diagram. 

IPM occurs when 
the unit has operated for a 

N

period of time. 

Y

Connect the compressor wires 
correctly according to the electric 
wiring diagram, and then put 
through the power and then turn 
on the unit 

Check whether the 
compressor wire (UVW) is connected 

Y

and the connection sequence 

is correct. 
Measure the voltage of terminal 
L and terminal N of wiring board 
with AC voltmeter. 

N

Measure the resistance among
 three terminals (UVW) with the 
resistance measuring meter. 
Check the power supply 
voltage and make it resume 
to the range of ±10% of 
rated voltage. 

Is the voltage between 
terminal L and terminal N of XT in the 

N

range of  ±10% of rated 

voltage?

Is the resistance value 
for the three terminals of compressor 

are almost the same? 

Y

Y

1.Check whether the heat exchanger of indoor/outdoor unit is dirty and whether the 
   heat exchanger is covered by foreign object
2.Check whether the indoor fan and the outdoor fan operate normally;
3.Check whether the system pressure is too high;
4.Check whether the pressure is too high because there are too much refrigerant;

Measure the resistance among 
three terminals (UVW) and the 
copper pipe with the resistance 
measuring meter.

Is the resistance
 more than 500M

Correct them basing on
the Service Manual and 
then put through the 
power and then turn on 
the unit. 
Replace the compressor 

Are there abnormal 
circumstances described 

N

Y

as above? 

N

N

Y

Does the unit operate normally? 

N

Y

Replace the control 
board 

Y

End 

45
Installation and Maintenance

Sayfa 48

4. Overload protection of compressor 
, high discharge temperature, protection of compressor 
  

Main check points:
     (1) electronic expansion valve   (2) expansion valve terminal   
     (3) charging amount of refrigerant   (4) overload protector    
  
NOTE:The control board as below means the control board of outdoor unit.

After the unit has been 
cut off the power for more 
than 20mins 

Check whether the 
overload protector SAT is connected.

Y

Under the ambient temperature,
 use the ohmmeter to measure the resistance of 

overload protector. Is the resistance 

less than 1000ohm? 

Y

Check whether the wiring 
terminal FA of electronic expansion valve is 

N

connected well. 

Y

The resistance between the first four leading 
feet closing to the terminal hole and the fifth
leading feet are almost the same respectively 
and they are all less than 100ohm. 

Replace overload protector SAT.

Replace the coil of electronic 
expansion valve EKV. 

Eliminate malfunction 

N

Check whether the refrigerant is
leaking; if yes, please charge the 
refrigerant according to the 
technical specification. 

Eliminate malfunction 

N

Replace control board 

End

46
Installation and Maintenance

N

Connect the wires well 
according to the wiring 
diagram. 

N

Y

Y

Sayfa 49

5.Troubleshooting for temperature sensor 
,
,
,
,
            

Main check points:
   (1) connection terminal  (2) temperature sensor  (3) main board 

47
Installation and Maintenance

Start

Check whether the 
connection terminal between the 
temperature sensor and the control board is 

loose or not connected 

well. 

Insert the temperature 
sensor well 

Eliminate 
the malfunction 

Check whether there 
is short circuit  caused by 
the tripped-over elements on the 

control board.

Pull the elements uprightly 

Eliminate 
the malfunction 

Check whether the 
resistance of temperature sensor is 

normal by referring to the 

resistance table. 

Replace the temperature 

sensor with another one 

with the same model 

Eliminate 
the malfunction 

Replace the controller with 
a new one with the same 
model 

End

Sayfa 50

6.High temperature prevention protection 
; high power 
; system is abnormal 

Main check points:
    (1) outdoor temperature  (2) fan  (3)air inlet and air outlet of indoor/outdoor unit
   NOTE:The control board as below means the control board of outdoor unit.

48
Installation and Maintenance

Overload protection, 
high temperature 
prevention protection 

Normal protection. Please operate 
it when the outdoor ambient 
temperature is improved. 

Is the outdoor ambient temperature
 higher than 53℃?

Y

N

After the complete unit is disconnected
from the power for 20mins 

Improve the unit's 
radiation environment. 

Is the radiation of indoor unit 
and outdoor unit is not good? 

Y

N

Check whether the fan terminal 
OFAN is connected well

Check whether the outdoor 
fan operates normally? 

N

Replace the outdoor fan

Y

Replace the fan capacitor C1

Replace the control board

Measure any two 
terminal with the ohmmeter and resistance 

is less than 1,000ohm. 

End

Sayfa 51

7.Desynchronization diagnosis for compressor 
  Main check point:
  (1) system pressure  (2) power supply voltage 

   NOTE:The control board as below means the control board of outdoor unit.

Desynchronization occurs 
after turning on the unit 

N

normally? 
Check whether the compressor 
has stopped operation for more 

than 3mins. 

Y

Check whether 
the compressor wire (UVW) is 
connected well and the connection 

sequence is the clockwise 

direction. 

N

Y

unit normal? 
Connect the wires

Replace the control board 

Eliminate 
malfunction 

Y

N

Replace the compressor 

End 

49
Installation and Maintenance

Desynchronization occurs 
during operation 

Check whether the fan
terminal OFAN is 
connected well. 

Replace the fan 
capacity C1.
Does the outdoor fan operate 

N

Y 

Improve the radiation of the 
unit (such as clean the heat 
exchanger, strengthen the 
ventilation, etc.) .

Replace the outdoor fan 
Is the radiation for the unit 

Y

not good? 

N

Turn on the unit when the 
power has resumed to the 
normal range. 

Is the input voltage of the 

N

Y

Charge the refrigerant 
according the Service 
Manual. 
Is the refrigerant too much? 

Y

N

Replace the control board

Eliminate 
malfunction 

Y

N

Replace the compressor 

End 

Sayfa 52

8.Malfunction diagnosis for failure startup 
  Main check points:
  (1) compressor wire  (2) compressor   (3) charging amount of refrigerant 

   NOTE:The control board as below means the control board of outdoor unit.

Put through the 
power and turn on 
the unit 

Check whether the compressor 
has stopped operation for more than 

3mins.

Y

Check whether the compressor wire 
(UVW) is connected and the connection sequence

 is correct. 

Y

Check whether the charging 
amount of refrigerant is too much.

Y

N

Charge the refrigerant according to 
the Service Manual. 

Does the unit started 

up normally? 

N

Replace the control board 

Eliminate malfunction 

N

Replace the compressor 

End

50
Installation and Maintenance

The time for stop operation is not enough and 
the system's high pressure and low pressure is 
unbalanced. Please wait for 3mins and then
 turn on the unit again. 

N

Please improve the connection between 
the control board and the compressor 
and then connect it well according to 
the wiring diagram. 

N

Does the unit started 

Y

up normally? 

N

Y

Sayfa 53

9. Charging malfunction of capacitor  

   Main check points:
   (1) wiring board XT  (2) reactor 
   NOTE:The control board as below means the control board of outdoor unit.

Put through the power 
to turn on the unit and 
then wait for 1min

Measure the voltage at both 
ends of electrolytic capacitor 
with DC voltmeter. 

Is the 
voltage higher than 85% of 

Replace the control
board 

Y

rated voltage?  

N

Measure the AC voltage between 
terminal L and terminal N of wiring 
board XT. 

Turn off the power 
and maintain the 
power supply to 
make the voltage 
resume to ±10% 
of rated voltage. 

Is the voltage is 
within ±10% of rated 

N

voltage?  

Y

Wait for 20min after turning off the 
power or use DC voltmeter to measure 
the voltage at both ends of capacity 
until it's lower than 20V.

Check the connection status 
of reactor (L in the electric 
wiring diagram).

Connect the wires 
of reactor L according 
to the electric wiring 
diagram. 

Is the wire connection 
of reactor L normal? 

N

Y

Replace the control 
board 

End 

51
Installation and Maintenance

There's malfunction 
for the voltage 
detection circuit of 
control board.

Put through the 
power and turn 
on the unit again

Eliminate 
malfunction 

Y

N

Put through the 
power and turn 
on the unit again. 

Eliminate 
malfunction 

Y

N

Sayfa 54

10. Troubleshooting-motor(indoor fan) doesn't operate  

     Main check points:
     (1) connection terminal  (2) motor  (3) control board AP1 of indoor unit  (4) blade

     10.1 DC motor 

52
Installation and Maintenance

Display shows "H6" 

Pull the blade with hand 
under de-energization 
status 

Check whether the 
blade operates smoothly 

Adjust the motor and the blade 
to make the motor operate 
smoothly. 

1

Put through the 
power to check whether the 

<
1

malfunction is 

eliminated 

Under power-off status, 
check whether the wiring terminal 

Insert the wiring terminal 
of indoor fan again 

<

between the indoor fan and the 

main board is loose

Put through the 
power and turn on the unit to 
check whether the malfunction is 

1
<

1

eliminated 

Put through the power and 
turn on the unit to check whether the 
voltage between terminal 1 and terminal 2 

It's the malfunction of main board. 
Replace the main board with a 
new one with the same model.

1

of motor is 280~310VD

<

<

Check whether the 
voltage between terminal 2 and 

It's the malfunction of main board. 
Replace the main board with a 
new one with the same model.

1

terminal 3 of motor is 15VDC 

1

Check whether there's 
voltage signal between terminal 2 

It's the malfunction of main board. 
Replace the main board with a 
new one with the same model.

1

and terminal 4 of motor 

<

End
It's the malfunction of motor. 
Replace the motor with a new 
one with the same mode

Sayfa 55

10.2 PG motor 

Display shows "H6" 

Pull the blade with 
hand under de-
energization status 

Adjust the motor and 
the blade to make the 
blade operate 
smoothly. 

Check whether 
the blade operates 

N

smoothly 

Y

Eliminate 
malfunction 

N

Check whether 
the feedback terminal of 

Insert the feedback 
terminal again

Y

indoor fan's motor

 is loose. 

Eliminate 
malfunction 

N

Y

N

Check whether the 
control terminal of indoor 

Replace the jumper 
cap with a new one 

Y

fan's motor is loose 

Y

Measure the voltage between this 
foot and the neutral wire of main 
board. 

N

Eliminate 
malfunction 

N

Y

PG

Put through the power 
and turn on the unit again. Measure 
whether the output voltage of control terminal of indoor 

Replace the fan with 
a new one 

Y

fan's motor is more than 50V within 1min 

after the horizontal louver 

is opened. 

N

Eliminate 
malfunction 

N

It's the malfunction of 
main board. Replace 
the main board with 
another one. 

Y

End

53
Installation and Maintenance

Sayfa 56

11. AC overcurrent protection 

Start

The power voltage is unstable.
The normal fluctuation is about 10% of rated 
voltage on the nameplate. 

Y

N

N

The power voltage is too low and the 

load is too high.
Adjust the power voltage to make it normal. 

Y

N

N

Check whether 
indoor or outdoor heat exchanger is 

Clean the outdoor and indoor heat exchangers to 
eliminate the blockage of air inlet and air outlet. 

Y

too dirty or the air inlet and the air 

outlet is blocked. 

N

N

Check whether
 the fan motor can operate. The fan operates 

Check the motor and install the motor again to 
let the fan operate normally 

Y

abnormally; fan speed is too lower the the 

fan can't operate. 

N

N

Check whether the 
compressor operates normal; whether there's 

Y

Solve the operation problem of compressor 

abnormal sound, oil leakage and high 

temperature for the case, etc.

N

N

System is blocked 
(check the capillary and filter, 

Y

Replace the blockage component

or if the cut off valve is 

frosted).  

N

N

Use the ampere meter 
to measure the current of live wire of main board. 

Y

Check the system 

Check whether the current is more than 

the overcurrent protection 

value. 

N

N

Replace the control board

End

54
Installation and Maintenance

Eliminate malfunction 

Y

Eliminate malfunction 

Y

Y

Eliminate malfunction 

Eliminate malfunction 

Y

Eliminate malfunction 

Y

Eliminate malfunction 

Y

Y

Eliminate malfunction 

Sayfa 57

9.3 Troubleshooting for Normal Malfunction

1. Air Conditioner can't be Started Up

Possible Causes 
Discriminating Method (Air conditioner Status)
Troubleshooting 

Confirm whether its due to power failure. If yes, 
wait for power recovery. If not, check power 
supply circuit and make sure the power plug is 
connected well. 
Wrong wire connection between 
indoor unit and outdoor unit, or poor 
connection for wiring terminals 

No power supply, or poor connection 
for power plug

After energization, operation indicator isn't bright 
and the buzzer can't give out sound 

Under normal power supply circumstances, 
operation indicator isn't bright after energization

Make sure the air conditioner is grounded reliably
Make sure wires of air conditioner is connected 
correctly
Check the wiring inside air conditioner. Check 
whether the insulation layer of power cord is 
damaged; if yes, place the power cord.
Model selection for air switch is 
improper
After energization, air switch trips off
Select proper air switch

Electric leakage for air conditioner
After energization, room circuit breaker trips off at 
once

After energization, operation indicator is bright, 
while no display on remote controller or buttons 
have no action. 

Malfunction of remote controller 

2. Poor Cooling (Heating) for Air Conditioner 

Possible Causes 
Discriminating Method (Air conditioner Status)
Troubleshooting 

Set temperature is improper
Observe the set temperature on remote controller  Adjust the set temperature

Rotation speed of the IDU fan 
motor is set too low
Small wind blow 
Set the fan speed at high or medium 

Filter of indoor unit is blocked 
Check the filter to see its blocked 
Clean the filter 

Check whether the installation postion is proper 
according to installation requirement for air 
conditioner 

Installation position for indoor unit 
and outdoor unit is improper 

Discharged air temperature during cooling is 
higher than normal discharged wind temperature; 
Discharged air temperature during heating is lower 
than normal discharged wind temperature; Units 
pressure is much lower than regulated range 

Refrigerant is leaking 

Malfunction of 4-way valve 
Blow cold wind during heating 
Replace the 4-way valve 

Discharged air temperature during cooling is 
higher than normal discharged wind temperature; 
Discharged air temperature during heating is lower 
than normal discharged wind temperature; Unitt 
pressure is much lower than regulated range. If 
refrigerant isn't leaking, part of capillary is blocked 

Malfunction of capillary

Flow volume of valve is insufficient The pressure of valves is much lower than that 

stated in the specification
Open the valve completely 

Malfunction of horizontal louver 
Horizontal louver can't swing 
Refer to point 3 of maintenance method for details 

Malfunction of the IDU fan motor 
The IDU fan motor can't operate 
Refer to troubleshooting for H6 for maintenance 
method in details 

Malfunction of the ODU fan motor The ODU fan motor can't operate 
Refer to point 4 of maintenance method for details 

Malfunction of compressor 
Compressor can't operate 
Refer to point 5 of maintenance method for details 

3. Horizontal Louver can't Swing

Possible Causes 
Discriminating Method (Air conditioner Status)
Troubleshooting 

Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Stepping motor is damaged 
Stepping motor can't operate 
Repair or replace stepping motor 

Main board is damaged 
Others are all normal, while horizontal louver 
can't operate 
Replace the main board with the same model

55
Installation and Maintenance

Check the circuit according to circuit diagram 
and connect wires correctly. Make sure all wiring 
terminals are connected firmly

Replace batteries for remote controller
Repair or replace remote controller

Adjust the installation position, and install the 
rainproof and sunproof for outdoor unit

Find out the leakage causes and deal with it. Add 
refrigerant. 

Replace the capillary

Connect wires according to wiring diagram to make 
sure all wiring terminals are connected firmly

Sayfa 58

4. ODU Fan Motor can't Operate

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 

Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Measure the capacity of fan capacitor with an 
universal meter and find that the capacity is out of 
the deviation range indicated on the nameplate of 
fan capacitor.

Capacity of the ODU fan motor is 
damaged 

Power voltage is a little low or high Use universal meter to measure the power supply 

voltage. The voltage is a little high or low 
Suggest to equip with voltage regulator 

When unit is on, cooling/heating performance is 
bad and ODU compressor generates a lot of noise 
and heat. 

Motor of outdoor unit is damaged

5. Compressor can't Operate

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 
Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Measure the capacity of fan capacitor with an 
universal meter and find that the capacity is out of 
the deviation range indicated on the nameplate of 
fan capacitor.

Capacity of compressor is 
damaged 

Power voltage is a little low or high Use universal meter to measure the power supply 

voltage. The voltage is a little high or low 
Suggest to equip with voltage regulator 

Coil of compressor is burnt out
Use universal meter to measure the resistance 
between compressor terminals and its 0
Repair or replace compressor

Cylinder of compressor is blocked Compressor can't operate 
Repair or replace compressor 

6. Air Conditioner is Leaking 

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 

Drain pipe is blocked 
Water leaking from indoor unit
Eliminate the foreign objects inside the drain pipe

Drain pipe is broken 
Water leaking from drain pipe
Replace drain pipe 

Wrapping is not tight
Water leaking from the pipe connection place of 
indoor unit
Wrap it again and bundle it tightly 

7. Abnormal Sound and Vibration

Possible causes 
Discriminating method (air conditioner status)
Troubleshooting 

When turn on or turn off the unit, 
the panel and other parts will 
expand and theres abnormal sound 

Theres the sound of "PAPA"
Normal phenomenon. Abnormal sound will 
disappear after a few minutes. 

When turn on or turn off the unit, 
theres abnormal sound due to flow 
of refrigerant inside air conditioner

Water-running sound can be heard 
Normal phenomenon. Abnormal sound will 
disappear after a few minutes. 

Foreign objects inside the indoor 
unit or therere parts touching 
together inside the indoor unit 

Remove foreign objects. Adjust all parts position 
of indoor unit, tighten  screws and stick damping 
plaster between connected parts 
Foreign objects inside the outdoor 
unit or therere parts touching 
together inside the outdoor unit 

Theres abnormal sound fro indoor unit

Remove foreign objects. Adjust all parts position 
of outdoor unit, tighten  screws and stick damping 
plaster between connected parts 
Short circuit inside the magnetic 
coil 

Theres abnormal sound fro outdoor unit

During heating, the way valve has abnormal 
electromagnetic sound 
Replace magnetic coil 

Abnormal shake of compressor 
Outdoor unit gives out abnormal sound 
Adjust the support foot mat of compressor, tighten 
the bolts 

Abnormal sound inside the 
compressor 
Abnormal sound inside the compressor 

56
Installation and Maintenance

Connect wires according to wiring diagram to make 
sure all wiring terminals are connected firmly

Replace the capacity of fan

Change compressor oil and refrigerant. If no better, 
replace the compressor with a new one

Connect wires according to wiring diagram to make 
sure all wiring terminals are connected firmly

Replace the compressor capacitor

If add too much refrigerant during maintenance, 
please reduce refrigerant properly. Replace 
compressor for other circumstances. 

Sayfa 59

10. Exploded View and Parts List

10.1 Indoor Unit

34

7
8

1
2
4
6
3
5

30
31
33

32

27
29
26

24
25
28

37

21

36
35

22
23

39

38

41
40

16
17
18
19
20

9
10
11
12
13
15

14

42
43

The component picture is only for reference; please refer to the actual product.

57
Installation and Maintenance

Sayfa 60

NO.
Description

1
Right Side Plate Sub-Assy

2
Rear Plate Sub-Assy

3
Right Air Guard

4
Top Cover Sub-Assy

5
Left Air Guard

6
Left Side Plate Sub-Assy

7
Evaporator Assy

8
Air Guard Assy

9
Chassis

10
Wire Clamp

11
Fan Motor

12
Water Tray Sub-Assy

13
Breakwater Sub-Assy

14
Protection Cover

15
Remote Control Panel Sub-assy

16
Propeller Housing Sub-assy

17
Centrifugal Fan

18
Diversion Circle

19
Gasket

20
Electric Box Cover Sub-Assy

21
Electric Box Assy

22
Main Board

Some models may not contain some parts,  please refer to the actual product.

58
Installation and Maintenance

NO.
Description

23
Terminal Board

24
Motor Cover

25
Stepping Motor

26
Air Guide Bushing

27
Guide Blade Lever

28
Stepping Motor

29
Crank 1

30
Air Louver 1

31
Air Louver 2

32
Guide Louver

33
Crankshaft of Guide Louver

34
Air Outlet Panel Assy

35
Display Sub-Assy

36
Display Board

37
Remote Controller

38
Screw Cover

39
Air Intake Panel Assy

40
Filter (lower)

41
Filter Sub-assy(Upper)

42
Connecting Cable

43
Connecting Cable

Sayfa 61

10.2 Outdoor Unit

27
28
30
31
32
34
33
35
25

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

The component is only for rererence;please refer to the actual product

59
Installation and Maintenance

26
24
29

36

23

22

21

20

19

18

17

16

Sayfa 62

NO.
Description

1
Front Grill

2
Cabinet

3
Axial Flow Fan

4
Brushless DC Motor

5
Chassis Sub-assy

6
Drainage Plug

7
Drainage Connecter

8
Cushioned Nut

9
Clap Board Assy

10
Compressor and fittings

11
4-way Valve Assy

12
Right Side Plate Assy

13
Valve Support Sub

14
Cut-off Valve(gas)

15
Back Cover Nut

16
Cut-off Valve(liquid)

17
Back Cover Nut

18
Valve Cover

19
Union Nut

20
Union Nut

21
Handle

22
Support

23
Valve Support Baffle

24
Rear Grill

25
Electronic Expansion Valve assy

26
Temperature Sensor

27
Condenser Assy

28
Electric Box Cover

29
Pipe Clamp

30
Main Board

31
Electric box

32
Top Cover-assy

33
Motherboard radiator

34
Motor Support Sub-Assy

35
Left Side Plate

36
Terminal Board

37
Electric Expand Valve Fitting

Some models may not contain some parts,  please refer to the actual product.

60
Installation and Maintenance

Sayfa 63

11. Removal Procedure

11.1 Removal Procedure of Indoor Unit
Caution: discharge the refrigerant 
completely before removal.

Step
Procedure

1. Before disassemble

2. Remove Air Intake Panel Assy

(1) Open the screw cover, use the screwdriver to 

remove 2 screws at both sides of air intake panel and 

then pull the air intake panel to remove it;

(2) Draw out the filter sub-assy.

61
Installation and Maintenance

Screw cover

Air Intake Panel

Screw

Filter Sub-Assy

Sayfa 64

Step
Procedure

3. Remove Electric Box Cover and Pass Wire Slot 
Cover

Remove 3 screws used for fixing the electric box cover, 

remove the electric box cover.

Remove 3 screws used for fixing the pass wire slot 

cover, remove the pass wire slot cover.

4. Remove Electric Box Assy and Electric Raceway

Loosen the bundle used for fixing the motor wire in the 

electric raceway.

Remove 5 screws used for fixing the electric raceway, 

and then remove the electric raceway.

Pull out the wiring terminals for each component, then 

remove screws used for fixing the electric box, pull the 

electric box outwards to remove it.

62
Installation and Maintenance

Electric Box Cover

Screws

Screws

Pass Wire Slot Cover

Screws

Electric Raceway

Screws

Sayfa 65

Step
Procedure

5. Remove Air Outlet Panel Assy

Remove 3 screws at the top part of the air outlet panel, 

2 screw at the lower part and screws under the screw 

cover, push the air outlet panel upwards slightly and 

then remove the air outlet panel.

6. Remove Air Guard

Remove 10 screws used for fixing the air guard, and 

then the air guard can be removed.

7. Remove top cover

Remove 7 screws on the top cover, and then pull the 

top cover upwards to remove it.

63
Installation and Maintenance

Air Outlet 
Panel Assy

Screws

Air Guard

Top cover

Sayfa 66

Step
Procedure

8. Remove evaporator

Remove 3 screws on the evaporator, 2 screw at the 

middle part and 2 screws at the lower part. Pull left and 

right side plates outwards slightly and then take out the 

evaporator, baffle board and water tray. 

When the evaporator is removed, the left and the right 

air damper and the baffle board of the evaporator can 

be removed.

9. Remove retaining plate of water tray and 
evaporator

Remove 3 screws used for fixing the press plate of 

propeller housing and then remove the press plate of 

propeller housing;

Rotate the guide loop to a certain position along the 

clockwise direction, and then remove the guide loop;

Remove 9 screws used for fixing the propeller housing, 

and then remove the propeller housing;

Use wrench to twist off the nuts used for fixing the 

centrifugal chiller and then pull the centrifugal blade 

outwards;

Remove the centrifugal blade;

Remove 4 nuts used for fixing the motor and 2 screws 

used for fixing the wire-pressing plate, and the remove 

the motor.

10. Remove breakwater sub-assy and water tray sub-
assy

Remove 2 screws used for fixing the left and right side 

plate and then remove the breakwater sub-assy and 

water tray sub-assy.

64
Installation and Maintenance

Evaporator

Centrifugal blade

Motor
Propeller housing

Guide loop

Press plate 
of propeller 
housing

Breakwater sub-assy

Water tray sub-assy

Sayfa 67

Step
Procedure

11. Remove chassis

After 9 screws are removed, pull the chassis 

downwards to remove it.

12. Remove left and right side plate sub-assys

Remove screws at both sides, pull them to both sides 

respectively and then left and right plate sub-assys can 

be removed.

65
Installation and Maintenance

Right side plate 
sub-assy

Left side plate 
sub-assy

Sayfa 68

11.2 Removal Procedure of Outdoor Unit
Caution: discharge the refrigerant 
completely before removal.

Step
Procedure

    1. Before disassembly

   2. Remove top cover

Remove the screws fixing top cover and then remove 
the top cover.

    3. Remove big handle and valve cover

Remove the screws fixing big handle, valve cover and 
then remove them.

66
Installation and Maintenance

top cover

big handle

valve cover

Sayfa 69

Step
Procedure

    4. Remove front panel assy

Remove connection screws connecting the front panel 
assy with the chassis and the motor support, and then 
remove the front panel assy.

   5. Remove rear grill

Remove the screws connecing the left side plate and 
right side plate and then remove rear grill.

   6. Remove right side plate assy

Rescrew the ground screws, remove the ground wires, 
loosen the screws fixing terminal board, remove the 
terminal board, rescrew the screws fixing the right 
plate, and remove the right side plate assy.

67
Installation and Maintenance

Front Panel Assy

Rear Grill

Right Side 
Plate Assy

Sayfa 70

Step
Procedure

    7. Remove valve suppprt

Remove the valve support bolck, remove the screws 
fixing valve support, remove the screws fixing the liquid 
valve and gas valve  then remove the valve support.

    8. Remove gas valve and liquid valve

Unsolder the welding joint connecting the gas valve 
and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering; 
when unsoldering, wrap the gas valve with a wet cloth 
completely to avoid damage to the valve caused by 
high temperature.

  9. Remove electronic expansion valve

Remove the terminals of the electric expand valve 

fitting and rotate to remove the electric expand valve 

fitting.

Unsolder the welding joint connecting the electronic 

expansion Valve and then remove the electronic 

expansion valve.

68
Installation and Maintenance

valve supprt

Valve Support Block

welding joint

liquid valve

gas valve

electric expand 

valve fitting

electric expansion 

valve sub-Assy

welding joint

Sayfa 71

Step
Procedure

   10. Remove electric box assy

Unplug the terminals, unscrew 1 screw that secures 

the electrical box assy, release the two snaps on the 

electrical box assy (in the clapboard and condenser 

angle), pull outwards, and remove the electrical box 

assy.

    11. Remove 4-way valve assy

Unsolder the welding joints connecting the 4-way valve 

assy, remove the 4-way valve.

Note:

Before unsoldering the welding joint, wrap the 4-way 

valve with a wet cloth completely to avoid damage to 

the valve caused by high temperature.

    12. Remove axial flow fan

Remove the nut on the fan and then remove the axial 

flow fan.

69
Installation and Maintenance

Electric Box Assy

4-way valve 

assy

axial flow fan

Sayfa 72

Step
Procedure

   13. Remove motor

Remove the screws fixing the motor and then remove 

the motor.

    14. Remove motor support

Remove the screws fixing the motor support and lift the 

motor support to remove it.

    15. Remove clapboard assy

Remove the screws fixing the clapboard assy and then 

remove the clapboard assy.

70
Installation and Maintenance

motor

motor support

clapboard assy

Sayfa 73

Step
Procedure 

     16. Remove compressor

Remove the 3 foot nuts on the compressor and then 

remove the compressor.

71
Installation and Maintenance

compressor

Sayfa 74

Appendix

Appendix 1: Reference Sheet of Celsius and Fahrenheit

Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32

Set temperature

 Fahrenheit display 

Fahrenheit

Celsius

 Fahrenheit display 

Fahrenheit

Celsius

 Fahrenheit display 

Fahrenheit

Celsius

temperature(

temperature(

temperature(

oF)

oF)

oC)

oF)

oF)

oC)

oF)

oF)

oC)

(

(

(

(

(

(

61
60.8
16
69/70
69.8
21
78/79
78.8
26

62/63
62.6
17
71/72
71.6
22
80/81
80.6
27

64/65
64.4
18
73/74
73.4
23
82/83
82.4
28

66/67
66.2
19
75/76
75.2
24
84/85
84.2
29

68
68
20
77
77
25
86
86
30

Ambient temperature

 Fahrenheit display 

Fahrenheit

Celsius

 Fahrenheit display 

Fahrenheit

Celsius

 Fahrenheit display 

Fahrenheit

Celsius

temperature(

temperature(

temperature(

oF)

oF)

oC)

oF)

oF)

oC)

oF)

oF)

oC)

(

(

(

(

(

(

32/33
32
0
55/56
55.4
13
79/80
78.8
26

34/35
33.8
1
57/58
57.2
14
81
80.6
27

36
35.6
2
59/60
59
15
82/83
82.4
28

37/38
37.4
3
61/62
60.8
16
84/85
84.2
29

39/40
39.2
4
63
62.6
17
86/87
86
30

41/42
41
5
64/65
64.4
18
88/89
87.8
31

43/44
42.8
6
66/67
66.2
19
90
89.6
32

45
44.6
7
68/69
68
20
91/92
91.4
33

46/47
46.4
8
70/71
69.8
21
93/94
93.2
34

48/49
48.2
9
72
71.6
22
95/96
95
35

50/51
50
10
73/74
73.4
23
97/98
96.8
36

52/53
51.8
11
75/76
75.2
24
99
98.6
37

54
53.6
12
77/78
77
25

Appendix 2: Configuration of Connection Pipe

1.Standard length of connection pipe(More details please refer to the specifications.)
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications.)
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each 
additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant 
charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter 

Additional refrigerant charging amount for R32

Piping size
Outdoor unit throttle

Liquid pipe
Gas pipe
Cooling only(g/m)
Cooling and heating(g/m)

1/4”
3/8” or 1/2”
12
16

1/4” or 3/8”
5/8” or 3/4”
12
40

1/2”
3/4” or 7/8”
24
96

5/8”
1" or 1 1/4”
48
96

3/4''
/
200
200
7/8''
/
280
280

72
Installation and Maintenance

Sayfa 75

Appendix 3: Pipe Expanding Method

Note:

Improper pipe expanding is the main cause of refrigerant leakage.Please expand 

the pipe according to the following steps:

A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.

B:Remove the burrs
● Remove the burrs with shaper and prevent the burrs from getting into the pipe.

C:Put on suitable insulating pipe.

D:Put on the union nut
● Remove the union nut on the indoor connection pipe and outdoor valve; install
the union nut on the pipe.

E:Expand the port
● Expand the port with expander.

Note:

● "A" is different according to the diameter, please refer to the sheet below:

Outer diameter(mm)
A(mm)
Max
Min
Ф6 - 6.35 (1/4")
1.3
0.7
Ф9 - Ф9.52 (3/8”)
1.6
1.0
Ф12 - 12.70 (1/2”)
1.8
1.0
Ф16 - 15.88 (5/8”)
2.4
2.2

F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the port 
again according to the steps above.

73
Installation and Maintenance

Pipe

Pipe cutter

Leaning
Uneven
Burr

Pipe

Shaper

Downwards

Union pipe

Pipe

Hard
mold

Expander

Pipe

Smooth surface

Improper expanding

leaning
damaged

crack
uneven
thickness

surface

The length is equal

Sayfa 76

Appendix 4: List of Resistance for Temperature Sensor

Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K)

oC)
Resistance(kΩ)
Temp(

Temp(

-19
138.10 
0
49.02 
20
18.75 
40
7.97 

-18
128.60 
2
44.31 
22
17.14 
42
7.35 

-16
115.00 
4
40.09 
24
15.68 
44
6.79 

-14
102.90 
6
36.32 
26
14.36 
46
6.28 

-12
92.22 
8
32.94 
28
13.16 
48
5.81 

-10
82.75 
10
29.90 
30
12.07 
50
5.38 

-8
74.35 
12
27.18 
32
11.09 
52
4.99 

-6
66.88 
14
24.73 
34
10.20 
54
4.63 

-4
60.23 
16
22.53 
36
9.38 
56
4.29 

-2
54.31 
18
20.54 
38
8.64 
58
3.99 

Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)

oC)
Resistance(kΩ)
Temp(

Temp(

-19
181.40 
20
25.01 
60
4.95 
100
1.35 

-15
145.00 
25
20.00 
65
4.14 
105
1.16 

-10
110.30 
30
16.10 
70
3.48 
110
1.01 

-5
84.61 
35
13.04 
75
2.94 
115
0.88 

0
65.37 
40
10.62 
80
2.50 
120
0.77 

5
50.87 
45
8.71 
85
2.13 
125
0.67 

10
39.87 
50
7.17 
90
1.82 
130
0.59 

15
31.47 
55
5.94 
95
1.56 
135
0.52 

Resistance Table of Discharge Temperature Sensor for Outdoor(50K)

Temp(

oC)
Resistance(kΩ)
Temp(

-30
911.400 
10
98
50
17.65
90
4.469

-25
660.8
15
77.35
55
14.62
95
3.841

-20
486.5
20
61.48
60
12.17
100
3.315

-15
362.9
25
49.19
65
10.18
105
2.872

-10
274
30
39.61
70
8.555
110
2.498

-5
209
35
32.09
75
7.224
115
2.182

0
161
40
26.15
80
6.129
120
1.912

5
125.1
45
21.43
85
5.222
125
1.682

74
Installation and Maintenance

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)
Temp(

oC)
Resistance(kΩ)

Sayfa 77

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070
Tel: (+86-756) 8522219         
Fax: (+86-756) 8669426
E-mail: global@cn.gree.com

For product improvement, specifications and appearance in this manual are subject to change without prior notice.

JF00305529