Service Manual 102 Installation and Maintenance
Service Manual 13 103 Installation and Maintenance
28K
Note:Take Capillary Sub-assy for example.
Step
Procedure
1. Before disassembly
2. Remove top cover
Remove the screws fixing top panel and then remove
the top panel.
3. Remove big handle and valve cover
Remove the screws fixing big handle, valve cover and
then remove them.
104
Installation and Maintenance
Service Manual
top cover
big handle
valve coverService Manual
Step
Procedure
4. Remove front panel assy
Remove connection screws connecting the front panel
assy with the chassis and the motor support, and then
remove the front panel assy.
5. Remove rear grill
Remove the screws connecing the left side plate and
right side plate and then remove rear grill.
6. Remove right side plate assy
Rescrew the ground screws, remove the ground wires,
loosen the screws fixing terminal board, remove the
terminal board, rescrew the screws fixing the right
plate, and remove the right side plate assy.
105
Installation and Maintenance
Front Panel Assy
Rear Grill
Right Side
Plate AssyStep
Procedure
7. Remove valve suppprt
Remove the valve support bolck, remove the screws
fixing valve support, remove the screws fixing the liquid
valve and gas valve then remove the valve support.
8. Remove gas valve and liquid valve
Unsolder the welding joint connecting the gas valve
and the liquid valve, remove them.
Note:
Discharge the refrigerant completely befor unsoldering;
when unsoldering, wrap the gas valve with a wet cloth
completely to avoid damage to the valve caused by
high temperature.
9. Remove electric box assy
Remove the terminals, lift up and rotate the electrical
box assy to the right so that the snaps on the clapboard
are removed and the electrical box assy are removed.
106
Installation and Maintenance
Service Manual
valve supprt
Electronic expansion valve
welding joint
liquid valve
gas valve
Electric Box AssyService Manual
Step
Procedure
10. Remove 4-way valve assy
Unsolder the welding joints connecting the 4-way valve
assy, remove the 4-way valve.
Note:
Before unsoldering the welding joint, wrap the 4-way
valve with a wet cloth completely to avoid damage to
the valve caused by high temperature.
11. Remove Capillary Sub-assy
Unsolder the welding joint connecting the capillary
subassy and then remove the capillary sub-assy.
12. Remove axial flow fan
Remove the nut on the fan and then remove the axial
flow fan.
107
Installation and Maintenance
4-way valve
assy
welding joint
Capillary Sub-assy
welding joint
axial flow fanStep
Procedure
13. Remove motor
Remove the screws fixing the motor and then remove
the motor.
14. Remove motor support
Remove the screws fixing the motor support and lift the
motor support to remove it.
15. Remove clapboard assy
Remove the screws fixing the clapboard assy and then
remove the clapboard assy.
108
Installation and Maintenance
Service Manual
motor
motor support
clapboard assyService Manual
Step
Procedure
16. Remove compressor
Remove the 3 foot nuts on the compressor and then
remove the compressor.
109
Installation and Maintenance
compressor
foot nutService Manual Appendix Appendix 1: Reference Sheet of Celsius and Fahrenheit Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Set temperature Fahrenheit display temperature(℉) Fahrenheit Celsius Fahrenheit display temperature(℉) Fahrenheit Celsius Fahrenheit display temperature(℉) Fahrenheit Celsius (℉) (℃) (℉) (℃) (℉) (℃) 61 60.8 16 69/70 69.8 21 78/79 78.8 26 62/63 62.6 17 71/72 71.6 22 80/81 80.6 27 64/65 64.4 18 73/74 73.4 23 82/83 82.4 28 66/67 66.2 19 75/76 75.2 24 84/85 84.2 29 68 68 20 77 77 25 86 86 30 Ambient temperature Fahrenheit display temperature(℉) Fahrenheit Celsius Fahrenheit display temperature(℉) Fahrenheit Celsius Fahrenheit display temperature(℉) Fahrenheit Celsius ( ℉) (℃) (℉) (℃) (℉) (℃) 32/33 32 0 55/56 55.4 13 79/80 78.8 26 34/35 33.8 1 57/58 57.2 14 81 80.6 27 36 35.6 2 59/60 59 15 82/83 82.4 28 37/38 37.4 3 61/62 60.8 16 84/85 84.2 29 39/40 39.2 4 63 62.6 17 86/87 86 30 41/42 41 5 64/65 64.4 18 88/89 87.8 31 43/44 42.8 6 66/67 66.2 19 90 89.6 32 45 44.6 7 68/69 68 20 91/92 91.4 33 46/47 46.4 8 70/71 69.8 21 93/94 93.2 34 48/49 48.2 9 72 71.6 22 95/96 95 35 50/51 50 10 73/74 73.4 23 97/98 96.8 36 52/53 51.8 11 75/76 75.2 24 99 98.6 37 54 53.6 12 77/78 77 25 Appendix 2: Configuration of Connection Pipe 1.Standard length of connection pipe(More details please refer to the specifications.) 2.Min length of connection pipeFor the unit with standard connection pipe of 5m, there is no limitation for themin length of connection pipe. For the unit with standard connection pipe of 7.5m and 8m, the min length of connection pipe is 3m. 3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications.) 4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe ● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each additional 5m of connection pipe. ● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe): ● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet. ● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter Additional refrigerant charging amount for R32 Piping size Indoor unit throttle Outdoor unit throttle Cooling only, cooling and heating Liquid pipe Gas pipe Cooling only(g/m) Cooling and heating(g/m) (g / m) 1/4” 3/8” or 1/2” 16 12 16 1/4” or 3/8” 5/8” or 3/4” 40 12 40 1/2” 3/4” or 7/8” 80 24 96 5/8” 1" or 1 1/4” 136 48 96 3/4'' / 200 200 200 7/8'' / 280 280 280 110 Installation and Maintenance
Appendix Service Manual Appendix 3: Pipe Expanding Method Note: Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps: A:Cut the pip ● Confirm the pipe length according to the distance of indoor unit and outdoor unit. ● Cut the required pipe with pipe cutter. B:Remove the burrs ● Remove the burrs with shaper and prevent the burrs from getting into the pipe. C:Put on suitable insulating pipe. D:Put on the union nut ● Remove the union nut on the indoor connection pipe and outdoor valve; install the union nut on the pipe. E:Expand the port ● Expand the port with expander. Note: ● "A" is different according to the diameter, please refer to the sheet below: Outer diameter(mm) A(mm) Max Min Ф6 - 6.35 (1/4") 1.3 0.7 Ф9 - Ф9.52 (3/8”) 1.6 1.0 Ф12 - 12.70 (1/2”) 1.8 1.0 Ф16 - 15.88 (5/8”) 2.4 2.2 F:Inspection ● Check the quality of expanding port. If there is any blemish, expand the port again according to the steps above. 111 Installation and Maintenance Pipe Pipe cutter Leaning Uneven Burr Pipe Shaper Downwards Union pipe Pipe Hard mold Expander Pipe Smooth surface Improper expanding leaning damaged crack uneven thickness surface The length is equal
Appendix Appendix 4: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units(15K) oC) Resistance(kΩ) Temp( Temp( -19 138.10 0 49.02 20 18.75 40 7.97 -18 128.60 2 44.31 22 17.14 42 7.35 -16 115.00 4 40.09 24 15.68 44 6.79 -14 102.90 6 36.32 26 14.36 46 6.28 -12 92.22 8 32.94 28 13.16 48 5.81 -10 82.75 10 29.90 30 12.07 50 5.38 -8 74.35 12 27.18 32 11.09 52 4.99 -6 66.88 14 24.73 34 10.20 54 4.63 -4 60.23 16 22.53 36 9.38 56 4.29 -2 54.31 18 20.54 38 8.64 58 3.99 Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K) oC) Resistance(kΩ) Temp( Temp( -19 181.40 20 25.01 60 4.95 100 1.35 -15 145.00 25 20.00 65 4.14 105 1.16 -10 110.30 30 16.10 70 3.48 110 1.01 -5 84.61 35 13.04 75 2.94 115 0.88 0 65.37 40 10.62 80 2.50 120 0.77 5 50.87 45 8.71 85 2.13 125 0.67 10 39.87 50 7.17 90 1.82 130 0.59 15 31.47 55 5.94 95 1.56 135 0.52 Resistance Table of Discharge Temperature Sensor for Outdoor(50K) Temp( oC) Resistance(kΩ) Temp( -30 911.400 10 98 50 17.65 90 4.469 -25 660.8 15 77.35 55 14.62 95 3.841 -20 486.5 20 61.48 60 12.17 100 3.315 -15 362.9 25 49.19 65 10.18 105 2.872 -10 274 30 39.61 70 8.555 110 2.498 -5 209 35 32.09 75 7.224 115 2.182 0 161 40 26.15 80 6.129 120 1.912 5 125.1 45 21.43 85 5.222 125 1.682 112 Installation and Maintenance Service Manual oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) oC) Resistance(kΩ) Temp( oC) Resistance(kΩ) Temp( oC) Resistance(kΩ)