Owner's Manual
Original Instructions
Commercial Air Conditioners

D Series Modular Air-cooled Scroll Chillers 

Applicable Models :
LSQWRF65M/NaD-M(FB01)           LSQWRF130M/NaD-M(FB01)          
LSQWRF160M/NaD-M(FB01)

Thank you for choosing commercial air conditioners. Please read
this Owner’ s Manual carefully before operation and retain it for 
future reference. 

If you have lost the Owner's Manual,please contact the local agent 
or visit www.gree.com or send an email to global@gree.com.cn for
the electronic version.   
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Sayfa 2

Thank you for selecting Gree’s product. Please read this instruction manual carefully before installing 

and using the product, so as to master and correctly use the product. In order to guide you to correctly 

install and use our product and achieve expected operating effect, we hereby instruct as below:

(1) This equipment should be installed, operated or maintained by the qualified servicemen who have had 

specific training. During operation, all safety issues covered in the labels, User’s Manual and other 

literature should be followed strictly. This equipment is not intended for use by persons (including 

children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, 

unless they have been given supervision or instruction concerning use of the appliance by a person 

responsibility for their safety. Children should be supervised to ensure that they do not play with the 

appliance.

(2) This product has gone through strict inspection and operational test before leaving the factory. In order 

to avoid damage due to improper disassembly and inspection, which may impact the normal operation 

of unit, please do not disassemble the unit by yourself. You can contact with the special maintenance 

center of our company if necessary.

(3) For personal injury or property loss and damage caused by improper operation such as improper 

installation and debugging, unnecessary maintenance, violation of related national laws and rules and 

industrial standard, and violation of this instruction manual, etc., we will bear no liability.

(4) When the product is faulted and cannot be operated, please contact with our maintenance center as 

soon as possible by providing the following information.

yy Contents of nameplate of product (model, cooling/heating capacity, product No., ex-factory date).

yy Malfunction status (specify the situations before and after the error occurs).

(5) All the illustrations and information in the instruction manual are only for reference. In order to make 

the product better, we will continuously conduct improvement and innovation. We have the right to 

make necessary revision to the product from time to time due to the reason of sales or production, and 

reserve the right to revise the contents without further notice.

(6) The final right to interpret for this instruction manual belongs to Gree Electric Appliances Inc. of Zhuhai.

To Users

Sayfa 3

This appliance is not intended for use by persons (including children) with reduced physical, sensory 

or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or 

instruction concerning use of the appliance by a person responsible for their safety.Children should be 

supervised to ensure that they do not play with the appliance.

This appliance is intended to be used by expert or trained users in shops, in light industry 

and on farms, or for commercial use by lay persons.

DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such 

waste separately for special treatment is necessary.

This appliance can be used by children aged from 8 
years and above and persons with reduced physical, 
sensory or mental capabilities or lack of experience 
and knowledge if they have been given supervision or 
instruction concerning use of the appliance in a safe way 
and understand the hazards involved.Children shall not 
play with the appliance. Cleaning and user maintenance 
shall not be made by children without supervision.

Sayfa 4

Safety Notices (Please be sure to abide )............................................................... 1

1 General Introduction.............................................................................................. 5

2 Product Data and Operating Range .................................................................... 6

3 Outline Dimension................................................................................................. 7

4 Installation Instructions......................................................................................... 8

4.1 General............................................................................................................................. 8

4.2 Acceptance Check............................................................................................................ 8

4.3 Handling and Lifting.......................................................................................................... 8

4.4 Installation Foundation...................................................................................................... 9

4.5 Vibration Reduction..........................................................................................................11

4.6 Water System...................................................................................................................11

5 Guidance to Controller Operation...................................................................... 14

5.1 Overview on Wired Controller......................................................................................... 14

5.2 Control Panel of the Wired Controller............................................................................. 14

5.3 Wired Controller Operation Instructions.......................................................................... 15

5.4 Reset (for erasing error).................................................................................................. 25

5.5 Menu Structure............................................................................................................... 26

6 Electric Control Cabinet...................................................................................... 30

6.1 Wiring for Output Control Lines....................................................................................... 30

6.2 Specification of Power Cord and Air Switch.................................................................... 30

6.3 Wiring of the Electric Control Cabinet............................................................................. 31

6.4 Filed Wiring..................................................................................................................... 31

6.5 Wiring betwween Chilled Modules.................................................................................. 32

6.6 Setup of Toggle Switches on the Motherboard............................................................... 33

6.7 Jumpers.......................................................................................................................... 33

7 Commissioning and Maintenance...................................................................... 33

7.1 Check before Startup...................................................................................................... 33

7.2 Requirements on Water System and Water Quality....................................................... 34

7.3 Trial Run.......................................................................................................................... 34

7.4 Routine Startup/Shutdown.............................................................................................. 35

7.5 Maintenance during Long-term Downtime...................................................................... 35

7.6 Startup after Long-term Shutdown.................................................................................. 35

7.7 Parts Replacement......................................................................................................... 35

Contents

Sayfa 5

7.8 Refrigerant Charging....................................................................................................... 36

7.9 Removal of the Compressor........................................................................................... 36

7.10 Freeze Protection.......................................................................................................... 36

7.11 Routine Maintenance.................................................................................................... 37

7.12 Precautions................................................................................................................... 37

8 Troubleshooting................................................................................................... 38

8.1 Error Lists and Troubleshooting Measures..................................................................... 38

8.2 After-sales Service.......................................................................................................... 39

Sayfa 6

Safety Notices (Please be sure to abide )

 WARNING: If not abide strictly, it may cause severe damage to the unit or the people.

 NOTE: If not abide strictly, it may cause slight or medium damage to the unit or the people.

 This sign indicates that the operation must be prohibited. Improper operation may cause severe 
damage or death to people.

 This sign indicates that the items must be observed. Improper operation may cause damage to 
people or property.

◆
◆Safety Notices for On-site Installation

•	 Installation should be performed by qualified servicemen who have taken specialized training and 
acquired corresponding certificates in accordance with relative laws, regulations and this manual, 
otherwise it would lead to damage to the unit, water leakage, electrocution, or fire hazards etc.

•	 The unit should be installed on the smooth foundation capable of supporting the unit and fixed with screw 
bolts. The foundation with inadequate strength would lead to leakage, turn-over or personal injury or 
death.

•	 Special lines should be used for electric installation by qualified electricians. Lines with inadequate 
capacity would lead to electrocution or fire hazards.

•	 Make sure each connector is properly tightened; otherwise it would lead to over-temperature or fire 
hazards etc.

•	 When installation is finished, please check for the drainage lines, pipelines, and electric lines to prevent 
water leakage, electrocution or fire hazards.

•	 This equipment should be installed where the drainage system can work well. Never block the drain hole. 
Improper drainage system would lead to drainage difficulty and make the unit suffer from malfunctions.

•	 When there is something unusual (like stinky smell) during installation or commissioning, please cut off 
the main power at once and then contact the after-sales service center. This ongoing unusual condition 
will damage the air conditioning unit and lead to electrocution or fire hazards.

•	 When refrigerant leaks, take corrective measures as soon as possible to prevent oxygen depletion by 
increased refrigerant concentration.

•	 Do not install the unit where there is high-intensity magnetic field or it is highly basic or acid or the voltage 
is quietly unstable.

•	 Do not install the unit where there would be leaked inflammable gas, as it would lead to fire hazards.

•	 The outer casing of the unit should be grounded. Do not connect the grounding line to the gas line, water 
line, lightning rod or communication line, otherwise it would lead to .

•	 Do not stand on the unit or place other object on it.

•	 Do not insert fingers or other objects into the outlet grill to prevent damage to the unit or personal injury 
or death.

•	 Do not start or stop the unit by inserting or drawing out the power plug.

•	 Do not let children play with this unit.

•	 The unit should be equipped with the leakage protector which should be installed in accordance with 
electric technical standards. Uninstallation or incorrect installation would lead to electrocution. Do electric 
leakage detection after electric installation is finished.

•	 Volatile liquid like thinner or gasoline would damage appearance of the unit. (Only clean the outer casing 
with of the unit with soft dry cloth or wet cloth with neutral detergent. )

D Series Modular Air-cooled Scroll Chillers 

WARNING

CAUTION

1

Sayfa 7

D Series Modular Air-cooled Scroll Chillers 

•	 Do not install the unit where conditions are severe, where it is close to the hot spring, coast or oil field, 
as it would lead to corrosion, electrocution or fire hazards. Besides, do not install the unit where there 
are corrosive, inflammable substances or smog, otherwise it would lead to normal operation failure, 
shortened service life, fire hazard, or severe injury.

•	 Do not start the compressor by manually closing the AC contactor, otherwise it would lead to electrocution 
or fire hazard.

•	 Do not misuse refrigerant, as it would lead to normal operation failure, unsatisfactory performance, fire 
hazards or even explosion etc.

•	 Installation should be done in accordance with this manual. Please read it manually prior to startup or 
troubleshooting.

•	 Installation should be done by qualified servicemen, as incorrect installation would lead to water leakage, 
electrocution or fire hazards etc.

•	 Before installation, check for all power supplies with the nameplate and check for its safety.

•	 The unit should be grounded and there should be specialized grounding line for the power socket to 
avoid of electrocution. Do not connect the groundling line to the gas tank, water line, lightning rod, or 
telephone line.

•	 Only specialized accessories and parts are allowed for installation, otherwise it would lead to water 
leakage, electrocution or fire hazards etc.

•	 Size of the power lines should be large enough. Only specialized power lines are allowed for replacing 
the damaged ones.

•	 When power lines have been connected, install the electric box as well to avoid of any safety problems.

•	 After all installation has been finished, take an overall check to the unit before powering it on.

◆
◆Safety Precautions for Usage and Maintenance

•	 When there is something unusual (like burnt smell), cut off the power supply at once and contact the 
sales agent. The ongoing unusual condition would lead to malfunctions, electrocution or fire hazards.

•	 When refrigerant leaks, take corrective measures to prevent oxygen depletion by increasing refrigerant 
concentration.

•	 Do not use or place inflammable or explosive substances near the unit.

•	 Do not do troubleshooting personally, as incorrect troubleshooting would lead to electrocution or fire 
hazards. Instead, please contact GREE after-sales service center.

•	 When the unit is charged with refrigerant, do not solder or cut any pipeline, fined heat exchanger, shell-
and-tube heat exchanger or other containers.

WARNING

2

Sayfa 8

•	 Do not let the unit out of the designed application range; otherwise it would cause the heat exchanging 
tube cracking, refrigerant leakage or even explosion.

•	 Do not let the cold/heat source directly act on the stored foods, plants, animals, precision instruments, 
and curiosities, otherwise their quality would be degraded.

•	 Only circulating water with satisfactory water qualify are allowed for the unit, as unsatisfactory water 
quality would shorten the service life of the unit or even malfunctions.

•	 When the unit has been put into use for some time, check for security of the installation foundation. 
Unstable foundation would lead to deformation or even safety accident.

•	 Once the unit is started up, stop it at least 6 minutes later, otherwise it would shorten the service life of 
the unit. Never deliberately start or stop the unit frequently.

•	 Under subzero climatic conditions, pay attention to freeze protection. When the unit is out of use in short 
time, do not cut off the power supply, as freeze protection will not act normally. When the unit is out of 
used in quite long time, add anti-freezing agent to water or drain the water system, otherwise it would 
make the shell and tube crack and then leak.

•	 Do not use the fuse out of the normal range or replace it with 

•	 Do not start or stop the unit directly by the power switch, as it would be likely to cause electrocution or 
fire hazards.

•	 Do not change settings of safety devices; otherwise it would lead to fire hazards and explosion.

•	 Do not operate the unit with wet hands.

•	 Do not clean the unit without cutting off the power supply, as it would lead to electrocution or personal 
injury.

•	 Do not let children pull power lines or climb the unit to prevent of electrocution or other dangers.

•	 Do not touch high-temperature parts of the compressor and refrigerant lines, as it would lead to burns.

•	 Do not touch sharp edges and fins of the heat exchanger; otherwise it would lead to personal injury.

•	 Do not touch any moving part; otherwise it would lead to accidental injury.

•	 Do not stand on the unit or replace objects on it.

•	 Do not bend pipeline and retrofit the unit, otherwise it would lead to refrigerant leakage, explosion, fire 
hazards or personal injury.

•	 Do operate the unit in accordance with this manual and read it carefully before startup or troubleshooting.

•	 Do turn on or off the unit with the controller.

D Series Modular Air-cooled Scroll Chillers 

CAUTION

3

Sayfa 9

D Series Modular Air-cooled Scroll Chillers 

◆
◆Safety Precaution  for Handling of the Unit

(1) Precautions for Handling of the Unit

•	 Please contact the contractor for handling and installation. Improper installation would lead to 
electrocution or fire hazard.

•	 During installation or handling, do not let foreign matters mixed with refrigerant and do not air trapped 
inside the pipe, as it would lead to increased system pressure or explosion of the compressor.

•	 Only specialized power lines are allowed. Wiring terminals should suffer no any external force and are 
fixed properly; otherwise it would lead to fire hazards. Besides, make sure insulation of power lines 
always in good condition.

•	 Connection between two ends of the power lines is not allowed. When its length is not enough, please 
contact the after-sales service center for customizing another one long enough.

•	 Treatment of water, cleaning solution, refrigerant or other waste liquid or gas should comply with local 
laws and regulations; otherwise it would lead to adverse effect to health and environment.

•	 Do not misuse refrigerant, as it is one of the causes of fire hazard and explosion.

(2) Precautions for Refrigerant Charging

•	 When charging is interrupted or finished, reinspect the unit but do not let the compressor run into 
operation.

•	 Do not use mixture of refrigerant vapor and air or oxygen for pressurizing for fear of explosion.

WARNING

CAUTION

WARNING

CAUTION

4

Sayfa 10

1 General Introduction

Main technical data of D series modular air-cooled scroll chillers are listed on the nameplate.

D series modular air-cooled scroll chillers are developed based on the B series modular air-cooled 

scroll chillers. However, it has higher reliability, efficiency and more reasonable design and can be widely 

used at newly built or retrofitted industrial and civil buildings in various sizes, such as, hotels, apartments, 

restaurants, office buildings, shopping malls, theaters, gyms, workshops, hospitals and other places 

where there are high requirements on noise level and air but the cooling tower is going to be installed 

troublesomely. 

The applicable refrigerant for D series modular air-cooled scroll chillers is R22 or R410A.

D series modular air-cooled chillers work outstandingly by virtue of their major features stated below.

◆
◆Excellent compatibility: 

Each D series modular air-cooled scroll chillers is constructed of up to 16 65kW single units or up to 8 

130/160kW single units which may vary in structure and in capacity.

◆
◆Free master module design: 

Any single unit can operate as the master once connected with the wired controller. It overcomes the 

problem which would occur to the product of other manufacturer that the whole system would fail to work 

properly when the fixed master unit malfunctions. 

◆
◆Compact structure: 

The modular design enables the compact structure, reduced volume, light weight, easy handling and 

shipping and flexible installation.  

◆
◆Powerful self-protection: 

It is equipped with the top-end microcomputer control system which is capable of providing well-rounded 

protection and self-diagnosis.

◆
◆High reliability: 

It is constructed of well-designed refrigeration parts for multiple refrigeration cycles, adequately 

guaranteeing the reliable operation.

◆
◆Hermetic scroll compressor:

 Compared with other type of compressor under the same cooling load, it has few movable components, 

smaller rotating torque, lower noise and vibration and higher reliability and efficiency.

◆
◆Equilibrium running: 

It indicates each compressor will run alternately so as to extend their service life.

◆
◆Humanized operation designing: 

When the unit runs out of the allowable temperature range, an alert will rise on the display. 

◆
◆Low maintenance cost: 

The especially design structure allows easy access and service and low maintenance cost.

◆
◆Hi-precision electronic expansion valve: 

The hi-precision electronic expansion valve is used as the throttling device, providing high reliable, 

sensitive and precise service. 

D Series Modular Air-cooled Scroll Chillers 

5

Sayfa 11

D Series Modular Air-cooled Scroll Chillers 

Fig.1-1 Schematic Diagram

2 Product Data and Operating Range 

(1) See the Data Sheet for detailed product data. Data on the product nameplate always takes 

precedence. If there is any special requirement, consult the local sales office for model selection. 

(2) Maximum and minimum water operating pressures.

6  Pa.

yy The maximum inlet water pressure is 1.0×10

6  Pa.

yy The minimum inlet water pressure is  0.2×10

(3) Operating Range

Water Side
Air Side

Item

Water Flow

Temperature (℃)
DB Temperature (℃)
WB Temperature

Leaving Water 

3/ (h·kW)

 m

(℃)

Cooling

0.172
7
35
—

Heating (Heat Pump)
45
7
6

Water Side
Air Side

Leaving Water 

Chilled Water 

Item

Ambient DB Temperature 

Temperature 

Temperature Difference 

(℃)

(℃)

(℃)

Cooling
5 ~15
2.5 ~6
15 ~48(R22)

15 ~45(R410A)

Heating (Heat Pump)
40 ~50
2.5 ~6
-15 ~24

6

Sayfa 12

D Series Modular Air-cooled Scroll Chillers 

3 Outline Dimension

(1) Graph for the shape and dimensions for LSQWRF65M/NaD-M(FB01)                                                

 (Unit:mm)

2160

238

319

1750(Ground bolt 4-M12)
967(Ground bolt)

1396

1000

2040

(2) Graph for the shape and dimensions for LSQWRF130M/NaD-M(FB01)                            

(Unit:mm)

2160

366

323

1676
2026(Ground bolt 4-M12)
1617(Ground bolt 4-M12)

1650

2226

7

Sayfa 13

D Series Modular Air-cooled Scroll Chillers 

(3) Graph for the shape and dimensions for LSQWRF160M/NaD-M(FB01)                         

403

337

2226
2026(Ground bolt 4-M12)
1617(Ground bolt 4-M12)
1650

1676

4 Installation Instructions

4.1 General

Installation should be performed by the skilled technician to guarantee the normal operation and prevent 

malfunctions and please read this manual carefully prior to installation.

The chiller is manufactured, inspected and tested strictly in accordance with the quality control program 

and it will work properly within the expected service life as long as its installation, operation and service 

follow the instructions covered in this manual, otherwise, it would lead to potential risks.

4.2 Acceptance Check

The user is responsible for organizing personnel to perform the acceptance check at the regulated plate 

of delivery. Checks listed below should be taken as a minimum. 

(1) If all required documents and accessories are provided as per the packing list.

(2) Check the equipment model. 

(3) If the equipment is damaged and all parts are provided.

(4) If refrigerant leaks.

(5) Do not remove the protective cover on the flagon of the shell-and-tube heat exchanger before 

connecting the water tube and check if the water pipe is clean. 

(6) Check if the installation and operation are within the allowable conditions. 

When there is damager or any other question, contact the local sales representative for applicable 

solutions. 

NOTE

•	 After the acceptance check, take necessary protection to the unpacked equipment. Note that it is not 

recommended to unpack the equipment too early to avoid any unexpected damage. 

4.3 Handling and Lifting

Each unit will undergo a series of strict factory inspections and tests to guarantee the expected 

performance and quality. However, special attention should be paid during handling and shipping to 

8

 (Unit:mm)

2160

Sayfa 14

prevent the control system and the piping system from being damaged.

It is best to unpack the chiller at the installation location and keep the chiller upward. When the chiller is 

unpacked during handing, please follow the lifting instructions stated below.

(1) Move the chiller by placing three levers 1/5 wider than the width of the chiller under the base and 

meanwhile always keep the chiller in balance.

(2) See the figure below for more details.

The expander bar
should be longer
than the width of
the unit

4.4 Installation Foundation

(1) Installation foundation shall be designed by the qualified designer in accordance with the actual 

condition. 

(2) A rubber pad shall be placed under the base of each single unit and then secured on the ground or 

the roof. Alternatively, each single unit can be placed side by side on the parallel channel steel with 

enough strength which then shall be secured with anchor bolts. Distance between each single unit 

shall be keep 1m as a minimal.

(3) Enough space shall be left for service and ventilation. Be sure there is at least 2m between the equipment 

and any barrier and it is better to set up a sun cover 3m ahead of the equipment.

(4) The unit shall be installed where it will not be affected by fire, corrosive, inflammable or waste gas, and 

proper measures shall be taken to minimize the vibration and noise.

(5) The unit shall be installed where the defrosting water can be drained out favorably. 

(6) Do not install the unit where there is heavy snow. If inevitable, build a foundation at least 300mm 

higher than the ground. 

D Series Modular Air-cooled Scroll Chillers 

protected by 
flexible materia

(Unit:mm)

9

Sayfa 15

D Series Modular Air-cooled Scroll Chillers 

10

Sayfa 16

2000

4.5 Vibration Reduction

The unit shall be securely attached to the foundation through the mounting hole by following the steps 

below.  

(1) Be sure the planeness of the concrete foundation is within ±3mm and the foundation shall be covered 

by a rubber pad.

(2) Lift the unit until to the height where it is available to install the spring shock absorber.

(3) Remove screws fixing the spring shock absorber.

(4) Place the unit on the spring shock absorber and align the bolt holes of the spring shock absorber with 

the mounting holes on the base of the unit. 

(5) Tighten screws removed in step 2.

(6) Adjust the height of the spring shock absorber and make sure the deflection is equal all round the 

spring shock absorber.

(7) Tighten the locking screws.

4.6 Water System

Considerations stated below shall be taken carfelly for the water system. 

(1) Each water inlet and outlet should be labeled properly to avoid misconnection.

(2) A flexible connector should be used at the chilled water outlet to reduce vibration transmission. 

(3) A manometer, a thermometer and a gate valve shall be installed at the chilled water inlet /outlet. 

Moreover, a drain valve shall be installed at the outlet and an air release valve shall be installed at 

the inlet. At the highest point of the water system, another release valve shall be installed, while at the 

lowest point of the water system, another drain valve shall be installed to facilitate drainage.

(4) The water inlet/outlet pipe should be tightly insulated to reduce heat loss and dewing. When pipes are 

exposed under 0℃, a electric heater shall be installed.

(5) There surely be some foreign matters in the water system which would generate scale on the surface 

of the heat exchanger, so a filter shall be installed upstream of the water pump.

(6) The unit shall be bypassed during flushing to prevent drain out from entering the system. 

D Series Modular Air-cooled Scroll Chillers 

1000

11

Sayfa 17

D Series Modular Air-cooled Scroll Chillers 

(7) Under ultra-low temperature in winter, showdown at night will cause the evaporator and pipeline frozen 

up, so it is highly recommended to add alcohol and propanol mixture in chilled water. Do not cut off the 

power supply when the unit is turned off, otherwise the freeze protection does not work. Alternatively, 

cut off the power supply and drain the water system thoroughly. 

(8) When the unit runs under the low load requirement, in order to avoid low load protection which would 

affect the service life of the unit, make sure the water capacity is more than 1/6 of total rated flow rate 

per hour of each module. If necessary, a water tank will be installed.

(9) Note: never use salt mixture to prevent the unit from being corroded.

How to drain the water system

(1) Loosen screws around the panel and then take down it.

(2) Remove anticlockwise the blind plug located at the bottom of the heat exchanger to let the chilled water 

flow out, after that, tighten the blind plug and reinstall the panel. (Note: place the drainage equipment 

beneath the drain pipe to prevent pollution caused by the drain water.)

Manual exhaust valve

Steam current Switch 

Manual exhaust valve

Steam current Switch 

Manual exhaust valve

Steam current Switch 

Steam current Switch 

12

Sayfa 18

D Series Modular Air-cooled Scroll Chillers 

Blind plug

NOTE

•	 Keep the purge valve of the water system open in order to drain the evaporator and condenser 

completely.

Diameters of Entering/Leaving Water Pipes

Diamter (mm)
Cooling load (kW)

DN15
0~3

DN20
3~7

DN25
5~13

DN32
10~25

DN40
15~38

DN50
29~75

DN65
46~126

DN80
84~230

DN100
167~461

DN125
314~586

DN150
523~1151

DN200
1068~2094

13

Sayfa 19

D Series Modular Air-cooled Scroll Chillers 

5 Guidance to Controller Operation

5.1 Overview on Wired Controller

In a 1~16 module network control system, only one Wired Controller is arranged for displaying the 

control menu, receiving and displaying parameters from the mainboard controller, setting adjustable 

parameters and transmitting set parameters to the mainboard controller.

5.2 Control Panel of the Wired Controller

1.  Power indicator(red): the indicator is on when the Wired Controller is powered on, or otherwise  it 

is off.

2.  Run indicator(green): the indicator is on when the Wired Controller is started, or otherwise it is 

off.

3.  Error indicator(red): The indicator is on when the unit is at fault, or otherwise it is off. 

4.  On/Off button: For controlling unit conversion between start and stop, press the button (for 3 

seconds) in stop state to start the unit and press the button (for 3 seconds) in operation state to 

stop the unit.

5.  Reset button: Press the button to clear fault and relieve the air discharge temperature sensor 

locking.

6.  Up selection button: in menu selection, press the button to move the cursor upward or leftward; 

and in data modification mode, press the button to increase the value.

7.  Down selection button: In menu selection, press the button to move the cursor downward or 

rightward; and in data modification mode, press the button to decrease the value.

8.  Exit button: Press the button to go back to the previous menu.

9.  Confirm button: In menu selection, press the button to confirm the selected item; and in data 

modification mode, press the button to confirm the parameter and move the cursor.

10.  LCD: Information display zone.

14

Sayfa 20

5.3 Wired Controller Operation Instructions

5.3.1 Turning on/off of the Unit

The unit under non-commissioning state can be turned on/off via the manual mode or the timing mode. 

The manual mode is given priority to the timing mode.

◆
◆Manual mode

(1) Manual start: in the unit stop state, press the on/off button for 3 seconds and start the unit, and at 

that time the operation indicator is on. When the compressor begins to run after a delay, the manual 

starting process is finished.

(2) Manual stop: in the unit operation state, press the on/off button for 3 seconds and stop the unit, and at 

that time the operation indicator is off. 

When ambient temperature is lower than -16 ℃, and Run Mode is Heat ,pressing On/Off button, the 

following prompt window comes up on the manual operator.

Press the Confirm button for acknowledgement.

If ambient temperature sensors of all linked units are at fault, and Run Mode is Heat, pressing  on/off 

button, the following prompt window comes up on the manual operator.

Press the Confirm button for acknowledgement.

In the manual defrosting mode, pressing the on/off button, the following prompt window comes up on 

the manual operator.

Press the Confirm button for acknowledgement.

◆
◆Timer mode

After the unit is energized or reset, press the Manual Mode to turn on/off the unit. 

D Series Modular Air-cooled Scroll Chillers 

Don’t ON/OFF under

manual defrost!

OK

15

Sayfa 21

D Series Modular Air-cooled Scroll Chillers 

5.3.2 Menu Operation Instructions

◆
◆Home page    

When the controller is powered on, the microcomputer will make a 3-second automatic detection and 

the LCD on the wired controller will display the following content.

The content of default home page menu is dependent on system state. XX stands for year, month, 

day, hour and minute. Only one item or none is displayed in the “【】”, representing the start/stop state of 

the system, starting method and quantity of linked modules. Presence of the “ 
 ” at the end means the 

system is at fault. 

After entering into a menu item, if no operation is made on the Wired Controller within 10 minutes, the 

system will automatically go back to the above default home page menu (Home Page). 

Press the Exit button on the wired controller at any time for enough times, you can go back the default 

home page menu as shown above.

◆
◆Main Menu   

When home page is present on the screen as shown in the above drawing, press the Confirm to enter 

into the Main Menu and the following items is displayed on the screen. 

Press the up or down selection button to choose required function and press the Confirm button to 

go to the page. 

(1)  User’s Setup     

The following is basic settings most common for users. On the Main menu, select the User’s Setup and 

press the Confirm to go to the sub-menu, as shown in the following.

User’s Setup

Module View

Parameter Setup

Version

Run Mode              【Cool/ Heat/Defrost】  

Startup
【Manual/Timer】
Auxiliary Heat 
              ON【OFF】
Auto-Antifreeze        

  Page 1

16

Sayfa 22

Press the Up or Down selection button to choose a needed function and press the Confirm to go to or 

confirm the selection. The subsequent “ON” or “OFF”, which means the function is selected or not.

yy Run Mode Set

Select the Run Mode and press the Confirm button, and the display on the screen is as follows:

Press the Confirm button to acknowledge a selected object, press the Up or Down selection button to 

change a selected object, and press the Exit button to cancel the model set. Different models have different 

display modes.If you is setting a mode in the startup state, the following prompt will appear:

Press the Confirm button for acknowledgement.

yy Startup mode set

Select the Startup  and press the Confirm button. The start/stop mode can be converted between the 

manual mode and the timing mode.

yy Auxiliary Heater Function Set

Select Auxiliary Heat and press the Confirm button, and the subsequent “ON” or “OFF”, which 

means the function is selected or not.

yy Auto-Antifreeze Protection Set 

Select Auto-Antifreeze, press Confirm, and the subsequent “ON” or “OFF”, which means the function 

is selected or not.

D Series Modular Air-cooled Scroll Chillers 

Timer Setup  
▲

Clock Setup

Sound

              ON【OFF】

Backlight

Page 2

 Page 3

Cool

Heat

Defrost

Set mode only when

unit is off!

OK

17

Sayfa 23

D Series Modular Air-cooled Scroll Chillers 

yy Timer Setup

Select Timer Setup and press Confirm to go to the page as shown in the following drawing: 

Press Confirm to change a selected object. Press Up or Down to change value or state of a selected 

object. This is timing on/off time and effective status each week. “OFF” represents the time set is invalid 

and “ON” means a valid time set. Press the Exit button to quit the page and go back to the previous menu 

and save set values.                           

yy Clock Setup

Select Clock Setup and press the Confirm button to go to the page. The following display is present on 

the screen.

Clock Setup

20XX-XX-XX

XX:XX

XXX

Press the Confirm button to change a selected object. Press the Up or Down button to change value 

or state of a selected object. Press the Exit button to quit the page and go back to the previous menu and 

save set values.

yy Sound On set

Select Sound, press the Confirm button, and the subsequent “ON” or “OFF”, which means the 

function is selected or not.                                     

yy Backlight On Set

Select Backlight, press the Confirm button, and the subsequent “ON” or “OFF”, which means the 

function is selected or not.

yy ECO.Mode Set

Select ECO.Mode, press the Confirm button, and the subsequent “ON” or “OFF”, which means the 

function is selected or not.

yy Quiet Mode Set

Select Quiet Mode, press the Confirm button, and the subsequent “ON” or “OFF”, which means the 

function is selected or not.

yy Memory Start Set

Select Memory Start, press the Confirm button, and the subsequent “ON” or “OFF”, which means the 

function is selected or not. The function is for selecting whether the unit will memorize its operation state if 

power supply is shut down.

18

Sayfa 24

(2) Module View

When the Main Menu is present on the screen, select Module View, press the Confirm to go to the 

pages as shown in the following drawing.

Page 4
Press the Exit to quit the page and go back to the previous menu. Press the Up or Down button to 

select a needed module and press the Confirm button to go to corresponding page.

A module followed with “ 
” means having a failure. The following menu will display after going to the 

module.

Press the Exit button to quit the page and go back to the previous menu. Press the Up or Down 

selection button to select a needed function and press the Confirm to go to corresponding page. “X” stands 

for one number of “1~16”, meaning number of the selected module. The “ 
” following the State View 

represents the module provides auto freeze protection operation or defrosting operation. The “ 
” following 

the Error View represents the module is at fault.

D Series Modular Air-cooled Scroll Chillers 

Module 1 
XIST【NO】

Module 2
XIST【NO】

Module 3
         
EXIST【NO】

Module 4

 Page 1

Page 2

Page 3

19

Sayfa 25

D Series Modular Air-cooled Scroll Chillers 

yy Temperature View

The function is for checking temperature at various temperature points. Select Temp. View and press 

the Confirm button to go to the pages as shown in the following drawings.

C Water Tin            
      XXX.X℃

C Water Tout           
      XXX.X℃

H Water Tin                             XXX.X℃   

H Water Tout                           XXX.X℃         
 

Page 1

Page 2

Suction T1              
     XXX.X℃

Suction T2               
     XXX.X℃

  Exhaust T1                             XXX.X℃   

Exhaust T2                             XXX.X℃         
 

Page 3
 

Throttle T1                
  XXX.X℃

Throttle T2               
     XXX.X℃

Page 4
Press the Up or Down selection button to convert among the above four pages. Press the Exit button to 

quit the menu page and go back to the previous menu. 

When page 1 is present on the screen, press the Reset button and the Exit button simultaneously for 3 

seconds, and C Water Tin and H Water Tin, as displayed previously, will be converted to C AVER.Tin and 

H AVER.Tin. And press again the Reset button and the Exit button simultaneously for 3 seconds, and C 

Water Tin and H Water Tin will be displayed again. As such, display can be converted between water inlet 

temperature and water inlet average temperature. 

NOTE

•	 Above temperature display is dependent on unit model. If the temperature sensor is not existent for a 

certain model, “NA” would be present on the display zone for corresponding temperature point.

20

▲

▲

Sayfa 26

yy State View

Used for checking the on/off status of motors. Select the State View and press the Confirm to go to the 

pages as shown in the following drawings.

Page 7
Press the Up or Down selection button to convert among the above pages. Press the Exit button to quit 

the menu page and go back to the previous menu.

D Series Modular Air-cooled Scroll Chillers 

Sys.State   【Cool/Heat/Defrost/Anti-fre.】   ▼

Page 1

 Page 2

Page 3

Page 4

Exthalpy Inc.EXV. 2

Page 5

Dis. T Sensor 1 

【Lock/Unlock】

【Lock/Unlock】
Dis. T Sensor 2

Page 6

21

Sayfa 27

D Series Modular Air-cooled Scroll Chillers 

•	 Above Items display is dependent on unit model. If this Item is not  existent for a certain model, “NA” 

would be present on the display zone for corresponding Item.

yy Error View

Used for checking the failure status of the system. Select the Error View and press the Confirm to go 
to the pages as shown in the following drawings.

Press the Exit button to quit the page and go back to the previous menu. Press the Up or Down 

selectionbutton to choose a needed module. When Present Error or History Error is selected, press the 

Confirm to go to the following interface.

“XXXXXX” are possible failures as listed in the following:

      
      Comp.1 HP Pro	
      Comp.1 OverLoad Pro
      Fan1 OverLoad Pro
      Sys.1 Dis.HighTemp.
      C Water Flow Switch
      Fan3 OverLoad Pro
      Jumper Error
      Comp.2 HP Pro
      Comp.2 OverLoad Pro
      Fan2 OverLoad Pro
      Sys.2 Dis.HighTemp.
      H Water Flow Switch
      Comp.1 LP Pro
      Comp.2 LP Pro
      User Anti-Fire Pro
      Dis.T Sensor1 Mal.

If the last line on the menu is followed with a “▼”, more failures are available below. You can press the 

Down selection button for reading more failures. If the first line is followed with a “▲”, more failures are 

available above. You can press the Up selection button for reading more failures. Press the Exit button to go 

back to the previous menu. Only the lasted four failures are remained even if quantity of history failures is more 

than 4. 

NOTE

Present Error

History Error

Clear History Error

XXXXXX

XXXXXX

XXXXXX

XXXXXX

        
        Dis.T Sensor2 Mal.
        C Water-in Sensor
        C Water-out Sensor
        Anti-Frozen Sensor
        Defrost T Sensor1
        Defrost T Sensor2
        Ambient T Sensor
        Dis.T Sensor1
        Dis.T Sensor2
        Thr. Valve1 Sensor
        Thr. Valve2 Sensor
        Suction T Sensor1
        Suction T Sensor2
        LP Sensor1 Error
        LP Sensor2 Error
        H Water-in Sensor
        H Water-out Sensor

22

Sayfa 28

When the display is in Error View, select Clear History Error and press the Confirm button to go to 

the following interface.

Press the Up or Down selection button to convert between NO and YES. Press YES to confirm and 

press NO to quit the menu and go back to the previous menu.

yy Manual Defrost

Used for starting or stopping manual defrosting. Select Manal Defrost and press Confirm to go to the 

following page.

Press Confirm to start or stop manual defrost and press Exit to quit the interface and go back to the 

previous menu.When manual defrost is on and the two systems do not stop defrosting completely, the 

following prompt will come up.

Press Up or Down button to convert between YES and NO, press Confirm for acknowledgement, press 

Exit to quit the menu and go back to the previous menu.

•	 Manual defrost is not allowed for two modules simultaneously. If manual defrost is started for one module 

and such function is started for another module, the following prompt will appear: 

Press YES for acknowledgement.

If manual defrost is initiated for a certain module under non-manual defrost mode, the following prompt 

will be present: 

D Series Modular Air-cooled Scroll Chillers 

Clear History Error

NO
YES

MANUAL  DEFR.     
 

SYS. DEFR.            
 

Anti-Fre.T

Do you need to stop

Unit under defrost?

YES      
NO

NOTE

Please set the mode 

To defrost !

OK

23

Sayfa 29

D Series Modular Air-cooled Scroll Chillers 

(3) Parameter Setup

On the Main Menu on the screen, select Parameter Setup and press Confirm to go to the page as 

shown in the following drawing.

Press Exit to quit the page and go back to the previous menu. Press Up or Down selection button to 

select a needed setting interface.

yy User-level Parameter Set

Select the menu and confirm the selection for going to User Para. Setup menu. Press the Up or Down 

selection button to select the parameter to be modified and press Confirm to go to the modification page. 

Press the Up or Down selection button for entering parameters and press Confirm or Exit to go back 

to the parameter set menu. Other parameters can be modified in the same way. After entered Default 

Parameter option, System will inquire whether use Default Value, if  YES is choosed, then the parameters 

will be modified to Factory Default Value。After modification, press the Up or Down selection button to 

save parameter and quit the item. A prompt for asking whether to save the modification comes up again 

on the screen. Select Confirm to save it and go back to the Main menu. Please note that only in the above 

exit way can modifications be saved. 

•	 Above Items display is dependent on unit model. If this Item is not  existent for a certain model, “NA” 

would be present on the display zone for corresponding Item.

yy System-level Parameter Set

User shall not use the function unless under instruction of debug personnel if necessary, to prevent an 

accident. Code entry is essential for operating the function. Button points on how to operate: select the 

menu and confirm the selection, and a prompt of code entry appears on the screen; press the Up and 

Down selection buttons to enter correct password, press Confirm to confirm it, and go to Parameter Set 

Menu; press the Up and Down selection buttons to select parameters to be modified, press Confirm to go 

to modification interface, press the Up and Down selection buttons to enter parameter value, and press 

Confirm or Exit to go back to the Parameter Set menu; other parameters can be modified in the same 

way; After entered Default Parameter option, System will inquire whether use Default Value, if YES is 

chosen, then the parameters will be modified to Factory Default Value.after modification, press the Up 

and Down selection buttons to select Save and Exit item under the Parameter Set menu, and a prompt 

whether to save the modified values comes up again on the screen, and if you need to save them, you can 

select OK and then press Confirm to save modifications and go back to the Main menu. Please note that 

only in the above exit way can modifications be saved.

 Page 1

Page 2

NOTE

24

Sayfa 30

(4) Version Information

Used for checking version number of software and hardware of the wired controller. On the Main menu 

on the screen, select Version and press Confirm to go to the page as shown in the following drawing.

Press Exit to quit the page and go back to the previous menu.

5.4 Reset (for erasing error)

On any interface, press Reset, the following page appears: 

Press Exit to go back to the previous interface and press Confirm to select function as shown in the 

following: 

5.4.1 Erasing Error

Press Confirm to confirm it and go back to the previous page.

5.4.2 Relieve Discharge Temp. Sensor locking

Press Confirm to go to Code Entry page and enter correct password to go to the following page.

Press Confirm to confirm it and go back to previous page.

D Series Modular Air-cooled Scroll Chillers 

Clear Error

Remove Dis Sensor

Error is clear !

OK

Temp. Sensor Error

Is Clear !

OK

25

Sayfa 31

D Series Modular Air-cooled Scroll Chillers 

5.5 Menu Structure

26

Sayfa 32

Menu Structure
Explanation

User’s  Setup
Function setting 

Run Mode
Running modes selection

Startup
Startup and stop selection 

Auxiliary Heat
Auxiliary heat function selection

Auto-Antifreeze
Auto anti-freezing function selection

Timer setup
Timer setting 

Clock Setup
Time setting

Sound
Buttons sound setting

Backlight
Backlight turn on setting

ECO.  Mode
Energy saving mode setting

Quiet  Mode
Quiet mode setting

Memory Start
Memory function setting when power on/off 

Module View
Corresponding modular’s parameters/status checking

Temp. View
Corresponding modular’s temperatures checking

C Water Tin
Water inlet temperature checking

C Water Tout
Water outlet temperature checking

H Water Tin
Hot water inlet temperature checking

H Water Tout
Hot water outlet temperature checking

C AVER. Tout
Water inlet modular average temperature checking

H AVER. Tout
water inlet modular average temperature checking

Defrost T1
Defrosting temperature 1 checking

Defrost T2
Defrosting temperature 2 checking

Anti-Fre.T
Anti-Freeze temperature checking

Ambient T
Ambient temperature checking

Suction T1
Suction temperature 1 checking

Suction T2
Suction temperature 2 checking

Exhaust T1
Exhaust temperature 1 checking

Exhaust T2
Exhaust temperature 2 checking

Throttle T1
Throttle temperature 1 checking

Throttle T2
Throttle temperature 2 checking

State View
Corresponding modular status checking

Fan 1
Fan motor 1 status checking

Fan 2
Fan motor 2 status checking

D Series Modular Air-cooled Scroll Chillers 

Menu Structure Explanation 

27

Sayfa 33

D Series Modular Air-cooled Scroll Chillers 

Fan 3
Fan motor 3 status checking

Sys.State
Units system status checking

Compressor1
Compressor 1 status checking

Compressor2
Compressor 2 status checking

C Water Pump
Water pump status checking

H Water Pump
Hot water pump status checking

Ass. Heat 1
Auxiliary electric heating 1 status checking

Ass. Heat 2
Auxiliary electric heating 2 status checking

4-Valve 1
Four-way valve 1 status checking

4-Valve 2
Four-way valve 2 status checking

EXV.  1
Electric Expansion valve 1 number of steps checking

EXV.  2
Electric Expansion valve 2 number of steps checking

Exthalpy Inc.EXV.  1
Exthalpy electric expansion valve 1 number of steps checking

Exthalpy Inc.EXV.  2
Exthalpy electric expansion valve 2 number of steps checking

Dis. T Sensor 1
Exhaust sensor 1 status checking

Dis. T Sensor 2
Exhaust sensor 2 status checking

Water_Out EXV.
Water-out electromagnetic valve status checking

Water_In EXV.
Water-in electromagnetic valve status checking

Error View
Error checking

Comp.1 HP Pro
Compressor 1 high pressure protection

Comp.1 OverLoad Pro
Compressor 1 over current protection

Fan1 OverLoad Pro
Fan motor 1 over current protection

Sys.1 Dis.HighTemp.
System 1 air exhaust high temp. protection

C Water Flow Switch
Water flow switch protection

Fan3 OverLoad Pro
Fan motor 3 over current protection

Jumper Error
Jumper error

Com.2 HP Pro
Compressor 2 high pressure protection

Comp.2 OverLoad Pro
Compressor 2 over current  protection

Fan2 OverLoad Pro
Fan motor 2 over current protection

Sys.2 Dis.HighTemp.
System 2 exhaust high temperature protection

H Water Flow Switch
Hot water flow switch

Comp.1 LP Pro
Compressor 1 low pressure protection

Comp.2 LP Pro
Compressor 2 low pressure protection

User Anti-Fire Pro
User side anti-freezing protection

Dis.T Sensor 1 Mal.
Exhaust sensor 1 fail

28

Sayfa 34

Dis.T Sensor 2 Mal.
Exhaust sensor 2 fail

C Water-in Sensor
Water in sensor malfunction

C Water-out sensor
Water out sensor malfunction

Anti-Frozen Sensor
Anti-freezing sensor malfunction

Defrost T Sensor1
Defrosting sensor 1 malfunction

Defrost T Sensor2
Defrosting sensor 2 malfunction

Ambient T Sensor
Ambient sensor malfunction

Dis.T Sensor1
Air exhaust sensor 1 malfunction

Dis.T Sensor2
Air exhaust sensor 2 malfunction

Thr. Valve1 Sensor
Throttle valve 1 sensor malfunction

Thr. Valve2 Sensor
Throttle valve 2 sensor malfunction

Suction T Sensor1
Suction sensor 1 malfunction

Suction T Sensor2
Suction sensor 2 malfunction

LP Sensor1 Error
Low voltage sensor 1 malfunction

LP Sensor2 Error
Low voltage sensor 2 malfunction

H Water-in Sensor
Hot water in sensor malfunction

H Water-out Sensor
Hot water out sensor malfunction

Parameter Setup
Parameters setting

User Para.Setup
Parameters setting for users

Cool T_in
Water inlet temperature setting

Heat T_in
Heating water inlet temperature setting

AH T_Start
Auxiliary Heat startup temperature setting

AH T_Stop
Auxiliary Heat stop temperature setting

H Water T_in
Hot water inlet temperature setting

System Para.Setup
System parameters setting

DEF.T_Start
Defrosting startup temperature

DEF.T_Stop
Defrosting stop temperature

DEF.Space
Defrosting interval 

DEF.Time
Defrosting time

Anti-Freeze
Anti-freezing temperature

Anti-Heat
Anti-overheat temperature

Temp.Rate
Water inlet temperature change rate

Com.Space
Compressor interval

D Series Modular Air-cooled Scroll Chillers 

29

Sayfa 35

D Series Modular Air-cooled Scroll Chillers 

6 Electric Control Cabinet

6.1 Wiring for Output Control Lines

Note: 

The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump 

AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module. 

6.2 Specification of Power Cord and Air Switch

Model
Power Supply

LSQWRF65M/NaD-M(FB01)

LSQWRF130M/NaD-M(FB01)
50
25
25
125

LSQWRF160M/NaD-M(FB01)
70
35
35
160

Notes:

(a) The specifications of the breaker and power cable listed in the table above are determined based on 

the maximum power (maximum amps) of the unit.

(b) The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-

wire copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable jacket) 

used at 40℃ and resistible to 90℃(see IEC60364-5-523:1999). If the working condition changes, they 

should be modified according to the related national standard.

(c) The specifications of the breaker listed in the table above are applied to the breaker with the working 

temperature at 40℃. If the working condition changes, they should be modified according to the related 

national standard.

Min. sectional area of 

2)
Capability of 

the power cable (mm

the Air Switch

(A)
Live Line
Neutral Line
Earth Line

16
16
16
63

380-400V 3N  

50Hz

30

Sayfa 36

6.3 Wiring of the Electric Control Cabinet

6.4 Filed Wiring

◆
◆Safety Code

(1) All wiring shall comply with applicable codes and engineering requirements.

(2) All field wiring shall be performed by the qualified electrician.

(3) Never perform wiring before the power supply is cut off.

(4) Any damage caused by the improper external wiring shall be at the installer’s expense. 

•	 Only copper conductor is allowed.

◆
◆The power cord is wired into the internal electric box 

(1) The power cord must be routed inside the conduit.

(2) The power cord must enter the electric box through a rubber or plastic ring to avoid any damaged 

caused by the sharp edge of the metal sheet. 

(3) The power cord close to the electric box must be attached securely to prevent the terminal block of the 

electric box affected by the outside force. 

(4) The unit shall be grounded reliably and never connect the ground wire with the gas fuel pipe, water 

pipe, lightening rod or telephone line. 

◆
◆Control Line

(1) The field supplied control line shall be at a minimum 1mm

(2) The electric box will send the control signal (220 AC, 5A) to control the chilled water pump and auxiliary 

electric heater, however, never do not drive them directly through the control signal but through their 

AC contactors.

(3) A reasonable length of the control line should be left outside the unit and the rest should be bundled 

and fed into the electric box.  

D Series Modular Air-cooled Scroll Chillers 

WARNING

2.

31

Sayfa 37

D Series Modular Air-cooled Scroll Chillers 

6.5 Wiring betwween Chilled Modules

130/160 Electric control cabinet
130/160 Electric control cabinet

32

Sayfa 38

6.6 Setup of Toggle Switches on the Motherboard

Four bit toggle switches are used for indicating hardware address (1~16) of modules, with module No. 

displayed in turn on the panel as Module 1, Module 2, ……, Module 16. Toggle switches 1, 2, 3 and 4 

are binary code, with 1 for the lowest bit and 4 for the highest bit. Comparison drawings are as follows 

(Caution: only in the condition of power supply shutoff can toggle switches be set):  

6.7 Jumpers

When it is required to replace the main board, be sure the main board can match with the applicable 

jumpers.

LSQWRF65M/NaD-M(FB01)
14
4202300114
14

LSQWRF130M/NaD-M(FB01)
14
4202300114
14

LSQWRF160M/NaD-M(FB01)
15
4202300115
15

7 Commissioning and Maintenance

The unit shall be maintained periodically by the skilled servicemen from Gree or a designed person 

under our professional guide to guarantee the unit operates reliably in a long term.

7.1 Check before Startup

Please finish the following steps before staring the system.

(1) Before energization, be sure the insulation resistance between the wiring terminal and ground complies 

with the local codes and regulations and check if the motor meets the insulation requirement with a 

resistance meter. 

(2) Check if all connenctions are in good condition and clean. 

D Series Modular Air-cooled Scroll Chillers 

33

Sayfa 39

D Series Modular Air-cooled Scroll Chillers 

(3) Close the main power switch.

(4) Check if the voltage between terminals keeps balance within deviation of 2%.

(5) Check if the power consumption of the unit complies with the rated value on the nameplate.

(6) Be sure the power cord is capable of carrying the rated current on the nameplate.

(7) Be sure all valves of water and refrigerant pipeline are placed properly.

(8) Reset all hand reset control elements.

(9) Be sure all sensor are placed installed properly.

7.2 Requirements on Water System and Water Quality

Be sure to open the water pump after the water system has been flushed times and the water quality 

has met the requirements and meanwhile be sure the water flow rate and pressure are within the allowable 

range.

The industrial water generates little scale when used as the refrigeration medium while the well or river 

water will generate much more scale and sands which would reduce the flow rate of the evaporate and 

cause freezing. Therefore, the well or river water must be firstly treated with the water softening equipment 

and analyze the PH, heat conductivity, Cl ion, and S ion before use.

Water Quality Requirement

Chilled water
Potential effect

Items

Circulating water 

(<20℃)
Supply water
Corrosion
Scale

PH
6.5~8.0
6.5~8.0
○
○

Heat Conductivity
<200uV/cm(25℃)
<200uV/cm(25℃)

Cl ion
<50ppm
<50ppm
○

SO4 ion
<50ppm
<50ppm
○

Fe
<1ppm
<0.3ppm
○
○

Basic ion
<50ppm
<50ppm

Hardness
<50ppm
<50ppm
○

S ion
/
/

Amonia ion
/
/

Si
<30ppm
<30ppm
○

Na ion
/
/

NOTE: “○” indicate possible corrosion or scale.

Even if the water qualify is under the strict control, calcium dioxide or other minerals will still form on the 

surface of the heat exchanger which will affect the heat exchange efficiency and be eliminated by formic 

acid, lemon acid, acetic acid or other organic acid.

7.3 Trial Run

See the operation manual of the applicable controller for more details.

(1) When the unit has not been used for a long period or the ambient temperature is quiet low, keep the 

unit energized 8 hours before startup to preheat the crankcase of the compressor so as evaporate 

the liquid refrigerant inside the compressor which otherwise would cause adverse effect on the 

compressor.

(2) Be sure valves are opened properly to prevent the compressor from being damaged by the abnormal 

high pressure.

(3) Carefully adjust the flow control valve and the shutoff valve of the chilled water system to make the 

flow rate meet the rated value on the nameplate.

34

Sayfa 40

(4) Turn on the wired controller to check the error record. If any error exists, eliminated it before restarting 

the unit.

(5) When the trial run takes 30 minutes and the entering/leaving water temperature approaches the 

regulated range, It is able to set the entering/leaving water temperature based on the actual load. The 

unit should be restarted at least 10 later after the shutdown. Then, check the set points of the controls 

in accordance with the instructions of the control system. 

•	 During flushing, be sure the control panel on the main unit is disabled to start/stop the water pump. 

•	 Do not start up the unit before the water system has not yet been drained up.

•	 Do not restart the unit when the unit has been stopped less than for 6 minutes. 

7.4 Routine Startup/Shutdown

It is recommended to start the system through the wired controller in the sequence of the water pump first 

and then the main unit, and stop the system in a reverse sequence. Remember to keep the unit energized 8 

hours before startup to preheat the crankcase of the compressor so as evaporate the liquid refrigerant inside 

the compressor which otherwise would cause adverse effect on the compressor.

•	 When the water temperature is lower than 15~20℃, do not start the terminal equipment until the water 

temperature reaches higher than 35℃ for guaranteeing a sound and reliable operation.

7.5 Maintenance during Long-term Downtime

When the chiller is going to be stopped for a long period, maintenance listed below shall be performed:

(1) Take the leakage test for the refrigerant tube. If leakage occurs, eliminate it. 

(2) Maintain the water pump and air conditioning divides in accordance with the suggestions provided by 

the manufacturer.

(3) Drain the water system by opening the discharge valve (especially in winter) to avoid frostbite on the 

shell and tube. 

(4) Switch off the power supply of the chiller and the water pump.

(5) Clean and dry the inside and outside surface of the chiller. Then, cover it against dust.

7.6 Startup after Long-term Shutdown

Preparations shall be taken when starting up the chiller which has not been used for a long period.

(1) Completely check and clean up the chiller.

(2) Clean the water piping system.

(3) Check the water pump.

(4) Tighten all connectors.

(5) Take the leakage test for all piping. If leakage occurs, eliminate it. 

(6) Regulate the water flow through the balance valve and check the water pressure. 

(7) Check if the oil circulation goes properly through the sight glass located on the compressor. 

(8) Check if the fan rotates properly.

(9) Check if the system vibration and noise are acceptable.

7.7 Parts Replacement

Only parts supplied by Gree can be replaced instead of similar parts supplied by others.

D Series Modular Air-cooled Scroll Chillers 

WARNING

NOTE

35

Sayfa 41

D Series Modular Air-cooled Scroll Chillers 

7.8 Refrigerant Charging

Refrigerant charging should be done based on the discharge and suction pressure. An air tight test must 

be taken on the condition refrigerant leaks or some part is required to be replaced. Refrigerant charging 

comes into two cases stated below.

◆
◆Complete charging

In this case, take a leakage test by charging hi-pressure nitrogen (15~20kg) or refrigerant into the 

system. If soldering is required, note that gas inside the system must be expelled firstly. The whole system 

must be dried and vacuumed prior to charging. 

(1) Connect the manifold gauge.

(2) Vacuum the system with the vacuum pump.

(3) After the system pressure reaches the required value (<80Pa) for more than 30 minutes and keeps 

below 100Pa, charge refrigerant at the low pressure side as per the rated specification on the 

nameplate. 

(4) Refrigerant charge will be affected by the ambient temperature. When charged refrigerant is under 

the required amount, add in accordance with the other charging case stated below.

◆
◆Adding 

Connect the refrigerant charging port at the lower pressure side to the refrigerant tank and install a 

manifold gage.

(1) Circuit the chilled water and start up the unit.

(2) Charge refrigerant vapor into the system slowly and check the suction and discharge pressure. 

•	 When performing the leakage and air tight test, never charge oxygen, acetylene and other flammable and 

toxic gases but only hi-pressure air, nitrogen or refrigerant.

•	 Mineral scale on the surface of the heat exchanger will affect the heat exchanging efficiency and increase 

the water resistance and lower the refrigeration capacity. Therefore, it should be cleared away through 

dilute acid. Note that contents of different water quality vary and should be treated with different type of 

acid by the qualified chemical company.

7.9 Removal of the Compressor

Please take the steps below when the compressor is required to be removed.

(1) Cut off the power supply.

(2) Recover the refrigerant in a reasonable speed to prevent oil from being drawn out. 

(3) Remove the power cord and the temperature sensor.

(4) Unsolder the soldering spots of the suction and discharge lines.

(5) Remove the screw bolts of the compressor and check the oil quality and accumulator.

(6) Remove the compressor.

(7) Clean up the pipeline.

7.10 Freeze Protection

When the flow passage of the shell-and-tube heat exchanger is frozen up, it would cause serious 

damage to the heat exchanger, such as cracking and leakage which are out of warranty, therefore, the 

user should take measures stated below for freeze protection.

(1) Under subzero conditions, it is necessary to shut down the chiller installed outdoor and then drain the 

evaporator completely.

WARNING

36

Sayfa 42

(2) Failure of the chilled water flow switch and the anti-freezing temperature sensor will cause the tube 

frozen up, so the flow switch shall be interlocked with the chiller.

(3) When charging or recovering the refrigerant, the evaporator would crack because of frostbite provided 

the refrigerant pressure inside the evaporator is under 0.4MPa. Therefore, be sure to keep the water 

flow continually inside the evaporator or drain it completely.

7.11 Routine Maintenance

Routine maintenance shall be performed periodically by the qualified technician so as to extend the 

service life of the unit and lower the possibility of occurrence of faults.

Record and keep the running status of the unit to facilitate troubleshooting for the servicemen.

◆
◆Daily Maintenance

(1) Check the circulating water pump and the flow rate.

(2) Check the voltage and power supply.

◆
◆Weekly Maintenance

(1) Check if the oil level keeps more than half of the sight glass, however the oil shall not be overcharged.

(2) Check the main unit, like if the compressor runs with abnormal noise, if the distribution box is attached 

securely and if the pipeline generates abnormal vibration or leakage. 

(3) Record key parameters, like pressure, pressure etc.

◆
◆Quarterly Maintenance

(1) Check the electric wiring and electric insulation.

(2) Check and adjust the set point of the temperature.

◆
◆Yearly Maintenance

(1) Check valves and pipeline of the water system. If necessary, clean the filter and analyze the water 

quality. If the water circuit needs to be cleaned, please consult the assistance of the qualified 

personnel. 

(2) Clean the corrosive surface and paint it again, and check if the door of the electric control cabinet is 

tightly closed. 

(3) Check if the pipeline is secured and so the water pump and fittings. Additionally, check if the refrigerant 

charge is sufficient, if not, add some.

(4) Perform the items for weekly maintenance.

(5) Check if the control device is set and acts properly.

(6) Check if the refrigerant pipe is attached securely.

(7) Check if the motor coil is insulated.

7.12 Precautions

(1) Take periodic maintenance to the unit to guarantee normal operation. 

(2) Once refrigerant leaks, shut down the unit immediately and contact the serviceman. No open fire is 

allowed in that refrigerant will decompose into toxic gas. 

(3) Switch off the main power supply in case of a fire hazard and extinguish it with effective measures.

(4) The working environment shall be far away from the inflammable substance, such as petroleum and 

alcoholic etc. to avoid explosion.

(5) The unit is allowed restarted only after any malfunction is eliminated, otherwise refrigerant or chilled 

water would leak, in which case, it is imperative to turn off all switches or the main power supply. 

(6) Do not short-circuit the protection device, otherwise it would cause some malfunction. 

D Series Modular Air-cooled Scroll Chillers 

37

Sayfa 43

D Series Modular Air-cooled Scroll Chillers 

8 Troubleshooting

8.1 Error Lists and Troubleshooting Measures

Error
Possible Causes
Troubleshooting Measures

•	 There is air or other incondensable gas 
inside the system
•	 Fins of the condenser are dirty or 
clogged
•	 The air flow for condensing is insufficient 
or the fan of the condenser runs 
improperly
•	 The suction pressure is too high
•	 Refrigerant is charged too much
•	 Ambient temperature is too high

Too high 

discharge 

pressure

Too low 

•	 The suction pressure is too low
•	 Refrigerant leaks or is charged 
insufficiently

discharge 

pressure

•	 The discharge pressure is too high
•	 Refrigerant is charged exceedingly
•	 Liquid refrigerant flows from the 
evaporator to the compressosr
•	 The entering chilled water temperature is 
higher than the allowable value

Too high 

suction 

pressure

•	 The ambient temperature is too low
•	 The check valve or the drier-filter is 
clogged
•	 The expansion valve works improperly
•	 Refrigerant is insufficient
•	 The entering chilled water is lower than 
the setpoint
•	 The chilled water flow is insufficient

Too low 

suction 

pressure

•	 The ambient temperature is too high
•	 The air flow for condensing is insufficient 
or the fan of the condenser malfunctions
•	 The high-pressure swtichs malfunctions
•	 Refrigerant is charged exceedingly

High 

pressure 

protection

•	 The voltage is too high or too low
•	 The discharge pressrue is too high or too 
low
•	 The backwater temperature is too high
•	 The overloaded elment malfunctions
•	 The ambient temperateure is too high
•	 The motor and wiring terminal is short-
circuited

Overload 

protection

•	 Expel incondensable air and vacuum the 
system if necessary
•	 Clean fins
•	 Repair the fan of the condenser
•	 See “Too high suction pressure”
•	 Let part of refrigerant out

•	 See “Too low suction pressure”
•	 Take leakage test and add refrigerant

•	 See “Too high discharge pressure”
•	 Let the exceedance of refrigerant out
•	 Check and regulate the expansion valve 
and be sure the temperature sensor of the 
expansion valve is attached with the suction 
line closely and tightly insulated

•	 Replace the check valve or the drier-filter
•	 Regulate the expansion valve properly or 
take a leakage test to the expansion valve
•	 Take a leakage test and add refrigerant
•	 Check the intallaiton
•	 Check the entering/leaving water pressure 
and regulate the water flowrate

•	 Repair the fan of the condenser
•	 Check the high pressure switch
•	 Check the refrigeration charge and let the 
exceedance out

•	 Check the voltage which is required to 
be within the rated value ±20V and the 
exceedance of the  phase difference to be 
within ±30%
•	 Check the discharge pressure and figure out 
why
•	 Check the backwater temperature and figure 
out why
•	 Check the electric current of the compressor
•	 Improve the ventilation
•	 Check the corresponding resistance of the 
motor and the terminal

38

Sayfa 44

•	 The voltage is too high or too low
•	 The discharge pressure is too high
•	 The entering chilled water temperature is 
too high
•	 The internal overtemperature protection 
device malfunctions
•	 Refrigerant is charged insufficiently

Internal over-

temperature 

protection

•	 The check valve or the drier-filter is 
clogged
•	 The expanson valve malfunctions
•	 The low pressure switch malfunctions
•	 Refrigerant is charged insufficiently

Low pressure 

protection

•	 The circuit breaker trips or the fuse is 
blown out
•	 The control circuit fails to get through
•	 There is no electric currrent
•	 High or low pressure protection acts
•	 The contact coil is blown out.
•	 Power phase is wired improperly
•	 The water system malfunctions and the 
flow switch is opened
•	 An alarm is raised on the wired controller
•	 The ON/OFF Timer is improperly set 
•	 The temperature sensor is set out of the 
set point

Failure to 

startup

Without commissioning, warranty will turned invalid under the following conditions:

•	 Refrigerant leaks in that the user personally opens some valve or pipe connector. 

•	 The user personally dismantles the unit without Gree’s approval.

•	 The user personally powers the control cabinet or the compressor motor.

•	 The user personally charges oil or refrigerant to the unit.

•	 The user personally starts up the system.

•	 The user personally passes directly hot water or steam to the evaporator.  

•	 The user fails to operate the unit following the instructions covered in this manual.

8.2 After-sales Service

When the unit in warranty has a quality issue or fails to operate properly under the allowable operation 

condition, please contact the local sales representative for free service.

The user is required to designate personnel to take charge of the unit following the instructions covered 

in this manual, otherwise any maintenance cost caused by the improper operation will be at the user’s 

expense.

D Series Modular Air-cooled Scroll Chillers 

•	 Check the voltage which is required to be 
within the allowable range
•	 Check the discharge pressure and figure out 
why
•	 Check the entering chilled water and figure 
out why
•	 Take the leakage test

•	 Replace the check valve or the drier-filter
•	 Adjust or replace the expansion valve
•	 Check the low presure switch
•	 Add refrigerant

•	 Replace the damaged element
•	 Check the wiring of the control system
•	 Check the power supply
•	 See “Too high discharge pressure”, “Too low 
discharge pressure”, “Too high discharge 
pressure”, and “Too low discharge pressure”
•	 Replace the damaged element
•	 Rewire the power phase
•	 Check the water system
•	 Check the alarm type and take 
countermeasures
•	 Check and adjust the set point

WARNING

39

Sayfa 45

D Series Modular Air-cooled Scroll Chillers 

Appendix A: Inspection Records Prior to Commissioning

value
0.0080MPa
Duration (min)>
30min

RabR
bc
Rac
Min. allowable valu eR
ag
RbgR
cg
Min. allowable valu e

R12R
23
R13
Min. allowable valu eR
1g
R2gR
3g
Min. allowable valu e

R12R
23
R13
Min. allowable valu eR
1g
R2gR
3g
Min. allowable valu e

state
Shutoff valve state
Flushing times
Water quality

Location
Min. distance from barriers
>2m (Ref.)

Arrangement 
Highest point and lowest point
>2m (Ref.)

(V)
Allowable range 380~400 V
%A
llowable value <5%

Water 
Shutoff valve (On/Off)
Drain valve (On/O ff)F
ilter (On/Off)
Air release valve (On/O ff)

1
1

1
1

1
1

Interphase insulation resistance 
 P
hase-ground insulation resistance 
 

Interphase insulation resistance 
 P
hase-ground insulation resistance 
 

Interphase insulation resistance 
Phase-ground insulation resistance 
 

pressure (MPa)
Ambient temp 

(℃)

insulation state
Refrigeration load 

state

(3Ph)
Leaving water temp ( ℃)V
acuuming stop tim e

SetpointS
etpointD
eviation
Setpoint

Foundation(Concrete/Steel frame )
Shock absorber

state
Insulation

Air conditioning space 

pressure(Mpa)
System Ⅱbalance 

allowable 

Max. 

Pressure gaugeT
hermometer
Flow switch 

discharge 

InletO
utlet

InletO
utletI
nlet
Outlet

state

Air 

brazing
Vacuuming

(MPa)

Load
FCU
Air supply 

outlet

Power supply monitor 

System I balance 

380~400V

Supply voltage 

Repair 

whole unit (main air 

protection devices

Insulation of the 

the compressor 

(terminal block)

Chilled water 

Refrigeration 

Power supply

Insulation of 

Control and 

pipeline

switch)

system

Installation

Routine Check

Appendix B: Trial Run and Commissioning Records

40

Sayfa 46

D Series Modular Air-cooled Scroll Chillers 

temp at shutdown (℃)
Runtime (s)
Vacuuming time (s)
5s

temp at shutdown (℃)
Runtime (s)
Vacuuming time (s)
5s

Flow control
Final flow rate (T/h)
Entering water temp (℃)
Nominal value: 12/7℃

startup (℃)
2nd downtime (s)

startup (℃)
2nd downtime (s)

Direction
Water temp
Sufficient air discharge (Y/N)

Chilled water (℃)
Entering 

Chilled water (℃)
Entering 

System I
Leaving

System I
Leaving

90% flow rate
Ambient temp (℃)

 (T/h)
Full load (Y/N)

Delivery
Operation training
Precautions
Emergency stop
Special service

Startup
Start current (A)
Startup state (Normal/Abnormal)

System Ⅱ
Entering air temp.

temp at shutdown (℃)
1st downtime (min)
Leaving water temp at 2nd 

temp at shutdown (℃)
1st downtime (min)
Leaving water temp at 2nd 

Hi-pressure
Low-pressure

Hi-pressure
Low-pressure

System Ⅱ leaving water 

System Ⅱ leaving water 

System I leaving water 

System I leaving water 

Flow rate

System Ⅱ

Pre-start
Water 

system

Troubleshooting

Unloading state

Unloading state

Running state

10min after 
startup

30min after 
startup

Conclusion

Trial Run

Commissioning

41

Sayfa 47