D_SERIES_MODULAR_AIR-COOLED_SCROLL_CHILLERS_SERVICE_MANUAL

Bu sayfa, kılavuzun PDF dosyasındaki metnin tamamıdır (sayfa sayfa). Görseller ve çizimler için PDF'i açın. — sibastore.com

Sayfa 1

D SERIES MODULAR AIR-COOLED 
SCROLL CHILLERS SERVICE MANUAL

T1/R410A/50Hz

(GC201405-I)

Sayfa 2

PRODUCT .....................................................................................................2

1 LINEUP....................................................................................................................... 2

2 NOMENCLATURE...................................................................................................... 2

3 FEATURES................................................................................................................. 3

4 PRODUCT DATA........................................................................................................ 4

5 OPERATION PRINCIPLE........................................................................................... 6

CONTROL......................................................................................................8

1 OPERATION FLOWCHART....................................................................................... 8

2 CONTROL LOGIC.................................................................................................... 10

3 CONTROLLER......................................................................................................... 12

NSTALLATION.............................................................................................17

1 BEFORE INSTALLATION......................................................................................... 17

2 INSTALLATION LOCATION..................................................................................... 17

3 CAUTION FOR INSTALLATION............................................................................... 17

4 DIMENSION DATA................................................................................................... 17

5 MACHINE FOOTPRINT........................................................................................... 19

6 TYPICAL WATER PIPING DIAGRAM .................................................................................20

7 FREEZE PROTECTION........................................................................................... 21

8 ELECTRIC WIRING WORK..................................................................................... 21

MAINTENANCE............................................................................................29

1 ERROR LIST............................................................................................................ 29

2 FLOW CHART OF TROUBLESHOOTING............................................................... 30

3 REMOVALS AND REINSTALLATION...................................................................... 35

4 ROUTINE MAINTENANCE...................................................................................... 49

5 EXPLODED VIEWS AND PART LIST...................................................................... 51

CONTENTS

Sayfa 3

PRODUCT

D Series Modular Air-cooled Scroll Chillers 

Service Manual

1

PRODUCT

Sayfa 4

D Series Modular Air-cooled Scroll Chillers 
Service Manual

PRODUCT 

1 LINEUP

Series
Model Name
Product 

LSQWRF65M/NaD-M
EL01500500 
60/17.06
65/18.48

LSQWRF80M/NaD-M
EL01500520
71/20.19
79.5/22.61

D 

LSQWRF130M/NaD-M
EL01500510
120/34.12
130/36.97

LSQWRF160M/NaD-M
EL01500530
145/41.23
170/48.34

2 NOMENCLATURE

LS
QW
R
F
130
M
/
Na
D
-
M

1
2
3
4
5
6
7
8
9

NO.
Items
Options

1
Product type
LS- chillers

2
Compressor type
QW- hermetic scroll compressors

3
Function type
Default-cooling only
R-heat pump

4
Condenser type
F: air-cooled

5
Nominal cooling capacity

6
Structural design
M-modular design

7
Refrigerant
Default–R22
Na–R410A

8
Development number
—

9
Power supply
M – 380-415V,3Ph,50Hz

PRODUCT

2

Capacity
(kW/Ton)
Power
Supply
Refrigerant
Appearance

Code

Cooling
Heating

380-415V,3Ph,50Hz

R410A

Note:1Ton =12000Btu/h = 3.517kW

65:60kW= 17.06 RT
80:71kW=20.19 RT
130:120kW=34.12 RT
160:145kW=41.23 RT

Sayfa 5

D Series Modular Air-cooled Scroll Chillers 

3 FEATURES

3.1 General

D series modular air-cooled scroll chillers are well-developed products incorporated with multiple advanced 
technologies. It features the low noise level, compact structure, easy operation, reliable running, and convenient 
installation and service, widely used at newly built or retrofitted industrial and civil buildings in various sizes, such 
as, hotels, apartments, restaurants, office buildings, shopping malls, theaters, gyms, workshops, hospitals and other 
places where there are high requirements on noise level and air quality but it is troublesome to install the cooling tower.

D series modular air-cooled scroll chillers are constructed of one or up to 16 single units which may vary in 
structure and in cooling capacity. The 65, 80 units have two independent refrigeration cycle and the 130,160 units have 
four. The modular design is able to realize the modular system with the cooling capacity ranging from 60 to 1160kW.
3.2 Features

D series modular air-cooled scroll chillers work outstandingly by virtue of their major features stated below.

◆
◆High energy efficiency: It is initially certified as one of the energy-saving chiller products in China.

◆
◆Free master unit design: Any single unit can operate as the master once connected with the control 

panel. It overcomes the problem which would occur to the product of other manufacturer that the whole 
system would fail to work properly when the fixed master unit malfunctions.
◆
◆Excellent compatibility: Each chiller is constructed of up to 16 single units of 65NaD,80NaD or up to 8 

single units of 130NaD,160NaD.
◆
◆Hermetic scroll compressor: Compared with other type of compressor under the same cooling load, 

it has few movable components, smaller rotating torque, lower noise and vibration and higher reliability 
and efficiency.
◆
◆Super protection: It is equipped with the top-end microcomputer control system which is capable of 

providing well-rounded protection and self-diagnosis, such as high/low pressure protection, freeze 
protection, over-temperature protection, compressor overload protection, phase loss/reversal protection, 
water flow switch protection, etc.
◆
◆High reliability: It is constructed of well-designed refrigeration parts for multiple refrigeration cycles, 

adequately guaranteeing the reliable operation.
◆
◆Compact structure: The modular design enables the compact structure, reduced volume, light weight, 

easy handling and shipping and flexible installation.
◆
◆Low maintenance cost: The especially design structure allows easy access and service and low 

maintenance cost.
◆
◆Low noise: The unit runs with low noise and vibration, widely applicable for various projects.

◆
◆Quiet mode: The unit is allowed to run in the quiet mode based on the user’s requirement, which can 

not only save energy but also create a comfortable and pleasant living environment.
◆
◆Economy mode: The unit can run in the economy mode without lessening the air conditioning effect so 

as to cut down the electricity consumption.
◆
◆Equilibrium running: Tt indicates each compressor will run alternately so as to extend their service life.

◆
◆Powerful remote monitoring: Gree centralized air conditioning system can be perfectly integrated to 

the BMS or Gree remote monitoring system so as to realize remote control to its operation and remote 
monitoring to its running parameters and alarm data etc. 

Control 
panel

Control 
panel

Control 
panel

Wiring Drawing between Modules
◆
◆Intelligent ON/OFF control: The unit is capable of automatically turning on/off the compressor through 

controlling the entering water temperature and the temperature rise rate in accordance with the change 
in load so as to make the capacity of the unit perfectly match the required load and reduce to the most 
extent the electricity consumption and effectively avoid remarkable temperature fluctuation.

Service Manual

3

PRODUCT

Sayfa 6

D Series Modular Air-cooled Scroll Chillers 
Service Manual

4 PRODUCT DATA

4.1 Product Data at Rated Condition

Heat 
Pump
LSQWRF65M/NaD-M
LSQWRF80M/NaD-M
LSQWRF130M/NaD-M
LSQWRF160M/NaD-M

Models

Product 

Code
EL01500500
EL01500520
EL01500510
EL01500530

Capacity steps
%
0-50-100
0-50-100
0-25-50-75-100
0-25-50-75-100

kW
60
71
120
145

Cooling

Ton
17.06
20.19
34.12
41.23

Capacity

kW
65
79.5
130
170

Heating

Ton
18.48
22.61
36.97
48.34

Cooling
kW
21.1
25.7
42.3
53.0

Power Input

Heating
kW
21.0
27.0
44.4
56.0

EER
W/W
2.84
2.76
2.84
2.74

COP
W/W
3.09
2.94
2.93
3.04

Power Supply
—
 380-415V,3Ph,50Hz

Running Control
—
Microcomputer Auto Control; Running Status Display; Abnormal Status Alarm

Safeties
—
High-low pressure protection, discharge temp. protection, motor overload protection, anti-freeze, 
water flow protection, phase-sequence protection, compressor overload protection

Type
—
Constant Speed Scroll

Compressor 

Starting mode
—
Direct starting

Quantity
—
2
2
4
4

Refrigerant Type
—
R410A

Type
—
Dry Expansion Evaporator

3/h
10.3
12.2
20.6
24.9

m

Water flow 

volume

GPM
45.0
54.0
91.0
110.0

kPa
15
20
30
35

Water side

Pressure Drop

ft.WG
4.92
6.56
9.84
11.48

 heat 
exchanger

Max. working

Pressure
MPa
1

water in/outlet 

pipe flange 
specification

mm
DN65
DN65
DN80
DN80

Type
—
Aluminum Fin-copper Tube

Fan type/
Number of  fans
—
Axial Fan/2
Axial Fan/2
Axial Fan/4
Axial Fan/4

3/h
2.7×10
4
3.0×10
4
5.4×10
4
6.0×10
4

Air side heat 

m

exchanger

L/s
0.75×10
4
0.83×10
4
1.5×10
4
1.67×10
4

Total fan air flow

CFM
1.59×10
4
1.764×10
4
3.18×10
4
3.528×10
4

Total fan 
motor power
kW
0.65×2
0.95×2
0.65×4
0.95×4

Sound pressure level
dB(A)
70
71
72
74

Width
mm
2040
2040
2226
2226

Outline 
Dimension

Depth
mm
1000
1000
1650
1650

Height
mm
2230
2230
2230
2230

Net Weights
kg
740
792
1315
1504

Operating weight
kg
814
871
1447
1654

Auxiliary electric heater-

power (Ref.)
kW
15
15
30
30

Loading 
quantity
40'GP/40'HQ
—
10/10
10/10
6/6
6/6

Notes:

a.	The loading quality listed in the table above is just for reference.
b.	The unit is designed, manufactured, inspected and tested in accordance with GB/T18430.1-2007.
c.	Parameters on the nameplate always take precedence.

PRODUCT

4

Sayfa 7

D Series Modular Air-cooled Scroll Chillers 

d.	Consult the local sales agency concerning special requirements and we will go to the length of figuring 

out the most feasible solution.
4.2 Nominal capacities are based on the follow conditions:

Water side
Air side

Item

Water flow volume 
Leaving Water Temperature
Dry-bull temp.
Wet-bull temp.

m

3/(h·kw)
(℃)
(℃)
(℃)

Cooling

0.172
7
35
—

Heating
45
7
6

4.3 Operation Range

Water side
Air side

Leaving Water Temperature
Temperature Difference of Water
Air on Condenser

(℃)
(℃)
(℃)

Cooling
5~15
2.5~6
15~45

Heating
40~50
2.5~6
-15~24

Note: when the unit is going to operate beyond the working conditions, please contact Gree for consultation.
4.4 Electric Data

Compressor
Fan Motor
Air Switch

Model
Rated Power Supply

Qty
MRC Each

NRC Each

(A)
Qty.
NRC  Each

(A)

LSQWRF65M/NaD-M

2
29.1
17.6
2
1.71
63

LSQWRF80M/NaD-M
2
29.3
25.7
2
2.50
80

380-415V,3Ph,50Hz

LSQWRF130M/NaD-M
4
29.1
17.6
4
1.71
125

LSQWRF160M/NaD-M
4
35
25.7
4
2.50
160

Notes:
MRC: Maximum running current (A).
NRC: Nominal running current (A).

Service Manual

MRC

(A)

(A)

5

PRODUCT

Sayfa 8

D Series Modular Air-cooled Scroll Chillers 
Service Manual

5 OPERATION PRINCIPLE

5.1 Schematic Diagram

Each circuit of the modular chiller is independent and identical and herein only a circuit is taken for an example.

◆
◆Refrigeration Cycle: The low-pressure superheated refrigerant vapor from the evaporator is drawn into 

the compressor through which the low-pressure vapor is compressed to hi-temperature and hi-pressure 
refrigerant vapor. Then, the refrigerant vapor passes the condenser and turns to saturated or sub-
cooled refrigerant liquid. And then, it passes the throttling device and flows into the evaporator where it 
evaporates by absorbing heat from the second refrigerant and then is drawn into the compressor again. 
The second refrigerant is then transferred to where air cooling is required.
◆
◆Reverse Refrigeration Cycle: During the reverse refrigeration cycle, a 4-way valve is used to make the 

refrigerant flow in a reverse direction as stated below. The hi-temperature and hi-pressure refrigerant 
vapor coming out from the compressor directly releases heat to the secondary refrigerant and turns to 
the refrigeration liquid. Then, the refrigerant vapor passes the throttling device and flows into the air-
cooled exchanger where it evaporates by absorbing heat from the surrounding environment and then 
is drawn into the compressor again. The second refrigerant which has approached the temperature set 
point is then transferred to where air heating is required.

PRODUCT

6

Sayfa 9

CONTROL

D Series Modular Air-cooled Scroll Chillers 

Service Manual

7

CONTROL

Sayfa 10

D Series Modular Air-cooled Scroll Chillers 
Service Manual

CONTROL

1 OPERATION FLOWCHART

1.1 Cooling Operation 

CONTROL

8

Energize the unit

Sayfa 11

1.2 Heating Operation

D Series Modular Air-cooled Scroll Chillers 

Service Manual

Energize the unit

9

CONTROL

Sayfa 12

D Series Modular Air-cooled Scroll Chillers 
Service Manual

2 CONTROL LOGIC

2.1 Cooling Control

2.1.1 Control to the Compressor

(1). “First On, First Off” 
“First On, First Off”/“First Off, First On” control indicates the numbered compressor which is started/stopped 
firstly will then be stopped/started firstly.

(2). Temperature Drop/Rise Rate Control
The water temperature range control assisted by the temperature drop/rise rate control is capable of 
precisely adapting the load change of the terminal units and avoiding remarkable water temperature fluctuation.

2.1.2 Freeze Protection 

For each single module, when the anti-freezing temperature or the leaving water temperature is lower than 
the limit value, freeze protection will work and this module stops; when the anti-freezing temperature and the 
leaving water temperature go higher than the normal value, freeze protection will quit; when the anti-freezing 
temperature and the leaving water temperature are between the limit value and the normal value, the module is 
protected again freeze.

2.1.3 Shutdown

Shutdown manually or timely: in this case, the compressor and the auxiliary electric heater stop firstly, then the 
electronic expansion valve initializes, and then the 4-way valve is de-energized, and lastly the water pump stops.

Shutdown when reaching the set point: in this case, the compressor stops firstly, and then the fan stops and 
the electronic expansion valve initializes. However, the 4-way valve keeps its state unchanged and the water 
pump keeps running.

Shutdown due to errors: in this case, the compressor stops firstly, and then the fan stops (except that the 
fan is malfunctioning), and the electronic expansion valve initializes. However, the 4-way valve keeps its state 
unchanged and the water pump keeps running.

2.2 Heating Control

2.2.1 Control on the Compressor

It is the same as that in selection 2.1.1.

2.2.2 Over-temperature Protection

For each single module, when the over-temperature is higher than the limit value, over-temperature 
protection will work; when the over-temperature goes lower than the normal value, over-temperature protection 
will quit; when the over-temperature is between the limit value and the normal value, the module is still 
protected again over-temperature.

2.2.3 Control on the Auxiliary Electric Heater

When the auxiliary electric heater is enabled through the wired controller, it will work in accordance with the 
change of the entering water temperature.

When the flow switch and the entering water temperature sensors work normally, any other error can be ignored.
When the auxiliary electric heater is disabled through the wired controller, the auxiliary electric heater will stop working.
When all entering water temperature sensors malfunction, the auxiliary electric heater will stop working.
When any flow switch malfunctions, the auxiliary electric heater will stop working.
When the unit is under over-temperature protection but the auxiliary electric heater is not allowed to stop, 
the auxiliary electric heater will keep working until the entering water temperature reaches the set point.

2.2.4 Shutdown

Shutdown manually or timely: in this case, the compressor and the auxiliary electric heater stop firstly, then the 

electronic expansion valve initializes, and then the 4-way valve is de-energized, and lastly the water pump stops.

Shutdown when reaching the set point: in this case, the compressor stops firstly, and then the fan stops and 

CONTROL

10

Sayfa 13

the electronic expansion valve initializes. However, the 4-way valve keeps its state unchanged and the water 
pump keeps running.

Shutdown due to errors: in this case, the compressor stops firstly, and then the fan stops (except that the 
fan is malfunctioning), and the electronic expansion valve initializes. However, the 4-way valve keeps its state 
unchanged and the water pump keeps running.

2.3 Freeze Protection

Under the OFF state at any mode (except the manual defrosting mode), when the freeze protection is activated 
through the wired controller, the unit will be protected again freeze. Free protection is factory defaulted to be ON.

When the module is in the freeze protection, its compressor will work as per the on/off setting and also the 
principle of “Six-minute On, Thee-minute Off”.

2.4 Control to the Compressor

All compressors run as per the principle of “First On, First Off” and “First Off, First On”. See section 2.1 and 
section 2.2.

2.5 Control to the Fan

The fan starts earlier than the compressor upon startup, and stops later than the compressor upon 
shutdown. During defrosting, the fan and the 4-way valve stops. After defrosting they start again.

2.6 Control to the 4-way Valve

The 4-way valve is stopped at the cooling mode. At the heating mode, it will start after the compressor runs. 
During defrosting it stops and then starts again after defrosting. It will stop later than the compressor upon shutdown.
2.7 Control to the Water Pump

When any module is required to run (incl. manual startup, timely startup, startup again freeze), water pumps 
of all module starts. Then, when one module reaches the set point and is shut down, water pumps of all modules 
keep running; when one module is shut down manually or timely, its water pump keeps running and will stop only 
after all modules are shut down; when one module malfunctions and is shutdown, its water pump keeps running.

2.8 Control to the Electronic Expansion Valve

The electronic expansion valve initialize when the wired controller is emerged for the first time. After the 
compressor has been started, the electronic expansion valve starts to adjust its opening angle.

2.9 Protection

2.9.1 Recoverable Protection

◆Compressor 1/2 low pressure protection
When it is detected the low-pressure switch of compressor 1 (compressor 2) is opened compressor 1 
(compressor 2) will be shut down immediately. 

Meanwhile the indicating LED will light on and the error information will be displayed among the error log 
which must be manually cleared for normal operation of next time.

◆Compressor 1/2 high discharge protection
When it is detected in three consecutive seconds that the discharge temperature of compressor 1 
(compressor 2) exceeds the set point, compressor 1 (compressor 2) will be shut down immediately but the fan 
will still run for some time. 

Meanwhile the indicating LED will light on and the error information will be displayed among the error log 
which must be manually cleared for normal operation of next time.

2.9.2 Irrecoverable Protection

◆Compressor 1/2 high pressure or over-current protection
When it is detected that the high pressure switch of compressor 1 (or compressor 2) is open, compressor 1 
(or compressor 2) will be shut down but the fan will still last for some time.

Meanwhile the indicating LED will light on and the error information will be displayed among the error log 
which must be manually cleared for normal operation of next time.

D Series Modular Air-cooled Scroll Chillers 

Service Manual

11

CONTROL

Sayfa 14

D Series Modular Air-cooled Scroll Chillers 
Service Manual

◆Fan 1/2 over-current protection
When any fan is over-current, this module unit will be shut down automatically. Meanwhile, the error information 
will be displayed among the error log which must be manually cleared for normal operation of next time.

◆Flow switch protection
When a single module unit detect that the flow switch is closed (under normal condition, it keeps open), it 
will be shut down automatically.

When all modules are shut down because of flow switch protection, the water pump will stop.
◆Communication protection
When a single module unit fails to receive any signal from the wired controller, it will be shut down 
automatically and then the water pump will stop.

◆Phase loss/reversal protection
When phase loss/reversal occurs, the power supply to the main board will be cut off.

3 CONTROLLER

3.1 Wired Controller

This wired controller, especially designed for D series modular air-cooled chillers, is capable of controlling 
and displaying each running parameter of the chiller and being integrated into the remote monitoring system.
3.1.1 Press Buttons and Icons on the Homepage 

(1). Press Buttons

NO.
Name
Function description

1
Power indicator(red)
the indicator is on when the Wired Controller is powered on, or otherwise  it is off.

2
Run indicator(green)
the indicator is on when the Wired Controller is started, or otherwise it is off.

3
Error indicator(red)
The indicator is on when the unit is at fault, or otherwise it is off.

4
On/Off button
For controlling unit conversion between start and stop, press the button (for 3 seconds) in stop 
state to start the unit and press the button (for 3 seconds) in operation state to stop the unit.

5
Reset button
Press the button to clear fault and relieve the air discharge temperature sensor locking.

6
Up selection button
in menu selection, press the button to move the cursor upward or leftward; 
and in data modification mode, press the button to increase the value.

7
Down selection button
In menu selection, press the button to move the cursor downward or rightward; 
and in data modification mode, press the button to decrease the value.

8
Exit button
Press the button to go back to the previous menu.

9
Confirm button
In menu selection, press the button to confirm the selected item; and in data modification 
mode, press the button to confirm the parameter and move the cursor.

10
LCD
Information display zone.

CONTROL

12

Sayfa 15

(2). Display Icons on the Homepage

No.
Icon
 Description

1
Time
It indicates the current time.

2
Unit name
It indicates the unit name.

3
Running mode
It indicates the running mode (cooling, heating or manual defrosting)

4
On/Off mode
It indicate the on/off mode, manual or timing)

5
Running status
It indicates the running status, on or off.

6
Module quantity
It indicates how many modules this system is consisted of. ( max. 16)

D Series Modular Air-cooled Scroll Chillers 

Service Manual

13

CONTROL

Sayfa 16

D Series Modular Air-cooled Scroll Chillers 
Service Manual

3.1.2 Menu Structure of Controller

CONTROL

14

Sayfa 17

3.2 Setup of Toggle Switches on the Motherboard

Four bit toggle switches are used for indicating hardware address (1~16) of modules, with module No. 
displayed in turn on the panel as Module 1, Module 2, ……, Module 16. Toggle switches 1, 2, 3 and 4 are binary 
code, with 1 for the lowest bit and 4 for the highest bit. Comparison drawings are as follows (Caution: The DIP 
switch is allowed to be set only when the power supply is cut off and each setting shall be unique.): 

D Series Modular Air-cooled Scroll Chillers 

Service Manual

15

CONTROL

Sayfa 18

D Series Modular Air-cooled Scroll Chillers 
Service Manual

INSTALLATION

16

Sayfa 19

NSTALLATION

1 BEFORE INSTALLATION

◆
◆Please check the attached documents for the unit and accessories in accordance with the packing list.

◆
◆Check the model and specification in accordance with attached documents.

◆
◆Check the unit and accessories for damage

◆
◆Check the refrigerant charge for leakage

◆
◆Check the cleanliness of the water pipes. Do not remove the protective cap of the flange before 

connecting water pipes.
◆
◆Check installation and operation for compliance with the required range.
Through the check above, if there is any damage or problem, please contact the local sales office for help. 
Note that protective measures shall be taken after unpacked product has gone through all check and do not 
remove the package too early to avoid any unexpected damage to the product.
2 INSTALLATION LOCATION

In order to guarantee the unit operates normally, installation shall be performed by the skilled serviceman 
with enough knowledge of refrigeration and air conditioning. Please read this manual carefully before instillation.

◆
◆The unit shall be installed outdoor where there is good ventilation and capable of withstand the weight of the unit.

◆
◆Enough space around the unit shall be left for ventilation, operation and service.

◆
◆No obstacle is allowed above the unit.

◆
◆The drainage ditch shall be prepared.
3 CAUTION FOR INSTALLATION

◆
◆Ensure the connection pipe and power line both are routed correctly. 

◆
◆Noise and vibration levels shall be among the reliable range, rubber cushion shall be adopted.  

◆
◆The base must be constructed of cement or steel, which can bear the operation weight of the machine 

and has a level surface. 
◆
◆The installation location shall be free from fire, flammable matters, corrosive gas or waste gas. Enough 

ventilation space shall be left and measures should be taken to reduce noise and vibration as much as 
possible.
4 DIMENSION DATA

(1). Graph for the shape and size for LSQWRF65M/NaD-M, LSQWRF80M/NaD-M                             Unit:mm

D Series Modular Air-cooled Scroll Chillers 

Service Manual

17

Sayfa 20

D Series Modular Air-cooled Scroll Chillers 
Service Manual

(2). Graph for the shape and size for LSQWRF130M/NaD-M                                                               Unit:mm

(3). Graph for the shape and size for LSQWRF160M/NaD-M                                                               Unit:mm

403

339

2226
2026(Ground bolt 4-M12)
1617(Ground bolt 4-M12)

1676

18

2160

1650

Sayfa 21

5 MACHINE FOOTPRINT

A minimum spacing of 1m should be left between any two modules for unobstructed air intake and 
equipment service. Additionally, a minimum of 2m should be kept between the chiller and any barrier. If 
allowable, it would be better to set up a suncover 3m ahead of the chiller.

D Series Modular Air-cooled Scroll Chillers 

Service Manual

Unit:mm

19

Sayfa 22

D Series Modular Air-cooled Scroll Chillers 
Service Manual

6 TYPICAL WATER PIPING DIAGRAM 

20

Sayfa 23

7 FREEZE PROTECTION

When the flow passage of the shell-and-tube heat exchanger is frozen up, it would cause serious damage 
to the heat exchanger, such as cracking and leakage which are out of warranty, therefore, the user should take 
measures stated below for freeze protection.

◆
◆Under subzero conditions, it is necessary to shut down the chiller installed outdoor and then drain the 

evaporator completely.
◆
◆Failure of the chilled water flow switch and the anti-freezing temperature sensor will cause the tube 

frozen up, so the flow switch shall be interlocked with the chiller.
◆
◆When charging or recovering the refrigerant, the evaporator would crack because of frostbite provided 

the refrigerant pressure inside the evaporator is under 0.71MPa. Therefore, be sure to keep the water 
flow continually inside the evaporator or drain it completely.
8 ELECTRIC WIRING WORK

8.1 Wiring Principle

◆
◆All wiring shall comply with applicable codes and engineering requirements.

◆
◆All field wiring shall be performed by the qualified electrician.

◆
◆Never perform wiring before the power supply is cut off.

◆
◆Any damage caused by the improper external wiring shall be at the installer’s expense. 
WARNING: only copper conductor is allowed.
(1). Power Cord Routing into the Electric Box

◆
◆The power cord is wired into the internal electric box.

◆
◆The power cord must be routed inside the conduit.

◆
◆The power cord must enter the electric box through a rubber or plastic ring to avoid any damaged 

caused by the sharp edge of the metal sheet. 
◆
◆The power cord close to the electric box must be attached securely to prevent the terminal block of the 

electric box affected by the outside force. 
(2). Control Line

◆
◆The field supplied control line shall be at a minimum 1mm

2.
◆
◆What the flow switch receives is the DC low-voltage signals. The wiring of the flow switch shall not be 

parallel with the 50V or higher line. If inevitable, the hi-voltage and low-voltage signals must keep a 
distance of at least 150mm.
◆
◆The electric box will send the control signal (220 AC, 5A) to control the chilled water pump and auxiliary 

electric heater, however, never do not drive them directly through the control signal but through their AC 
contactors.
◆
◆A reasonable length of the control line should be left outside the unit and the rest should be bundled and 

fed into the electric box.  
8.2 Wiring for Output Control Lines

Note:The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump 
AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module.

D Series Modular Air-cooled Scroll Chillers 

Service Manual

21

Sayfa 24

D Series Modular Air-cooled Scroll Chillers 
Service Manual

8.3 Wiring between Chiller Modules

22

Sayfa 25

8.4 Specification of Power Cord and Air Switch

Model
Power Supply

LSQWRF65M/NaD-M

LSQWRF80M/NaD-M
25
16
16
80

380-415V,3Ph,50Hz

LSQWRF130M/NaD-M
50
25
25
125

LSQWRF160M/NaD-M
70
35
35
160

Notes:

a.	The specifications of the breaker and power cable listed in the table above are determined based on the 

maximum power (maximum amps) of the unit.
b.	The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-wire 

copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable jacket) used at 40℃ 
and resistible to 90℃(see IEC60364-5-523:1999). If the working condition changes, they should be modified 
according to the related national standard.
c.	The specifications of the breaker listed in the table above are applied to the breaker with the working temperature 

at 40℃. If the working condition changes, they should be modified according to the related national standard.
8.5 Wiring of the Electric Control Cabinet

D Series Modular Air-cooled Scroll Chillers 

Service Manual

Min. sectional area of the power cable (mm

2)
Capability of the 

Air Switch(A)
Live Line
Neutral Line
Earth Line

16
16
16
63

23

Sayfa 26

D Series Modular Air-cooled Scroll Chillers 
Service Manual

8.6 WIRING DIADRAM

(1). LSQWRF65M/NaD-M 

 The diagram is only for reference and the circuit diagram attached on the unit prevails.

24

Sayfa 27

(2). LSQWRF80M/NaD-M

The diagram is only for reference and the circuit diagram attached on the unit prevails.

D Series Modular Air-cooled Scroll Chillers 

Service Manual

25

Sayfa 28

D Series Modular Air-cooled Scroll Chillers 
Service Manual

(3). LSQWRF130M/NaD-M

 The diagram is only for reference and the circuit diagram attached on the unit prevails

26

Sayfa 29

(4). LSQWRF160M/NaD-M

D Series Modular Air-cooled Scroll Chillers 

Service Manual

27

Sayfa 30

D Series Modular Air-cooled Scroll Chillers 
Service Manual

MAINTENANCE

28

Sayfa 31

MAINTENANCE

1 ERROR LIST

Error
Rated Element
             Protection Logic

High-pressure 

High pressure 

When the pressure is too high or the current exceeds the set point, the corresponding 
compressor will stop and the indicating LED on the controll panel will light on and the error 
information will be displayed on the error log which must be manually cleared for normal 
operation of next time.
Compressor over-

protection

switch

Over-current 

current protection

protector

When it is detected the low-pressure switch of the compressor is opened frequently, the 
compressor will be shut down immediately. Meanwhile, the error information will be displayed 
among the error log which must be manually cleared for normal operation of next time.

Low pressure 

Low-pressure 

protection

switch

Discharge 
temperature 

When it is detected in three consecutive seconds that the discharge temperature exceeds the 
set point, the compressor will be shut down immediately. Meanwhile, the error information will be 
displayed among the error log which must be manually cleared for normal operation of next time.

High discharge 

protection

sensor

Fan over-

When a fan is over-current, the corresponding unit will be shut down. Meanwhile, the error 
information will be displayed among the error log which must be manually cleared for normal 
operation of next time.

Fan over-current 

current 
protector

protection

When an entering water temperature sensor fails, the compressor of the corresponding module 
will be shut down immediately while the fan will still run for some time.
When a discharge temperature sensor fails, or the sensed discharge temperature is always 
below the set point, the compressor of the corresponding module will be shut down immediately. 
It can recover in three seconds but If the same case occurs more than three times, the system 
will be locked until the system is unlocked and then it should be manually cleared for normal 
operation of next time.
When the anti-freezing temperature sensor or the leaving water temperature sensor fails, it can 
be automatically cleared as the temperature sensor automatically recover. But if the same case 
occurs three times in one hour or the temperature sensor fails to recover, it should be manually 
cleared for normal operation of next time. Meanwhile, the indicating LED on the controll panel will 
light on and the error information will be displayed on the error log.

Temperature 
sensor protection

Temperature 

sensor

Water flow 
switch protection
Contactor
When a single module detects its flow switch is closed, this module will automatically be shut 
down. When all flow switches are closed, the water pump will stop.

Phase loss/
reversal protection

Phase 
protector

When phase loss/reversal occurs, the phase protector will cut off the power supply to the main 
board.

Communication 

error
Main board
When the single module fails to receive signals from the controll panel, it will automatically be 
shut off.

Error Codes

Error Name
Error Code
Jumper cap error
C5
High pressure protection
E1
Anti-freezing protection
E2
Low pressure protection
E3
High discharge temperature
E4
Compressor over-current
E5
Communication error
E6
Flow switch protection
EC
Superheating protection (unavailable for the cooling only unit)
Ed
Fan motor  over-current protection
EF
Defrosting temperature sensor
d6
Ambient temperature sensor error
F3
Discharge temperature sensor error
F4
Anti-freezing temperature sensor error
d3
Entering water temperature sensor error
F8
Leaving water temperature sensor error
F9
Discharge temperature sensor error
dp

D Series Modular Air-cooled Scroll Chillers 

Service Manual

29

Sayfa 32

D Series Modular Air-cooled Scroll Chillers 
Service Manual

2 FLOW CHART OF TROUBLESHOOTING

(1). High pressure protection

30

Sayfa 33

(2). Low pressure protection

D Series Modular Air-cooled Scroll Chillers 

Service Manual

31

Sayfa 34

D Series Modular Air-cooled Scroll Chillers 
Service Manual

(3). High discharge protection

32

Sayfa 35

(4). Compressor over-load protection

(5). Phase protection

D Series Modular Air-cooled Scroll Chillers 

Service Manual

33

Sayfa 36

D Series Modular Air-cooled Scroll Chillers 
Service Manual

(6). Water flow switch protection

(7). Temperature sensor error

34

Sayfa 37

3 REMOVALS AND REINSTALLATION

3.1  MAIN PARTS

Appearance
Name
Function

D Series Modular Air-cooled Scroll Chillers 

Service Manual

It drives the refrigerant cycle and turns the low-
temperature, low pressure refrigerant vapor into high-
temperature, high-pressure vapor. 

Compressor

Accumulator
It is used to separate oil and refrigerant liquid from the 
refrigerant vapor.

4-way Valve
It is used to shift the direction of the refrigerant flow to 
realize either cooling or heating.

In the cooling mode, it is used to absorb heat and 
evaporate the liquid refrigerant In the heating mode, it 
is used to release heat and condense the refrigerant 
vapor.

Shell-and-

tube heat 
exchanger

In the cooling mode, it is used to absorb heat and 
evaporate the liquid refrigerant In the heating mode, it 
is used to release heat and condense the refrigerant 
vapor.

Fintube heat 

exchanger

Electronic 
expansion 

It is used to regulate the flow rate of the refrigerant to 
make it perfectly match with the load in need.

valve

35

Sayfa 38

D Series Modular Air-cooled Scroll Chillers 
Service Manual

3.2 Removal and Installation of Main Parts

Compressor
(These steps listed below are applicable to the dual-system unit. For the four-system unit, please first remove the electric boxes of two 
compressors in between and then follow the steps below. )

Note: Be sure there is no refrigerant in the pipeline system and the power supply is cut off.

Steps
Graphic Reprentation
Instructions

1. Remove 
the panel

Remove the panel here

2. Remove 
the power 

cord and 
drain pipe

Remove the drain pipe 
Open the cover and 
remove the power cord

3. Separate 
the 
compressor 

from the 

pipeline 

system

Soldering spot

36

◆
◆Loosen screws around the panel with a 

screwdriver.
◆
◆Remove the panel.

◆
◆Collect the screws in case of loss.

◆
◆Place the panel in the right place to avoid 

inadvertent damage.

◆
◆Loosen screws for the power cord with a 

screwdriver.
◆
◆Draw out the power cord.

◆
◆Remove the crankcase heater, if applicable.

◆
◆Remove the drain pipe.
Note: when removing the power cord, mark 
the color of the power cord and the code of 
the wring terminal to avoid misconnection.

◆
◆Unbraze the brazing spots of the pipeline 

as quick as possible.
◆
◆Minimize damage on the compressor for 

further analysis.

Sayfa 39

4. Loose 
screws at the 

base of the 
compressor

5. Replace 
the 
compressor

6 Connect the 
pipeline and 

power cord

Note: after the compressor is replaced, most amount of oil will still remain in the system, which will not affect 
the reliability of the newly installed compressor but will increase the running resistance to the rotor and increase 
electricity consumption. Therefore, a valve should be installed at the lower part of the inlet of the suction line to 
discharge excessive oil. After installing the valve, start the compressor for ten minutes and then open this valve 
until all oil flows out completely. Do it twice to guarantee the oil keeps at the normal level.

D Series Modular Air-cooled Scroll Chillers 

Service Manual

◆
◆Remove screws with an adjustable 

wrench or a socket wrench.
◆
◆Collect screws in case of loss.

Remove four screws at the base

◆
◆Remove the compressor and do not damage 

the rubber pad.
◆
◆Package the removed compressor to 

prevent moisture entering.
◆
◆Place a new compressor at the base.

◆
◆Tighten screws.

◆
◆Connect the suction and discharge lines 

to the compressor by brazing. Note that 
nitrogen shall be charged during brazing.
◆
◆After brazing, use high-pressure nitrogen 

for leakage test.
◆
◆Energize the unit and manually close the 

AC contactor of the compressor to let the 
compressor run for 2~3 seconds.
◆
◆When the compressor runs reversely, 

sharp sound will generates.

Wire the power cord

37

Sayfa 40

D Series Modular Air-cooled Scroll Chillers 
Service Manual

4-way Valve

Note: Be sure to cut off the power supply and recover the refrigerant firstly

Steps
Graphic Representation
Instructions

1. Record the 
installation 
direction of 

the 4-way 

valve

四通阀
4-way valve

2. Clean 
the system, 

replace 
the 4-way 
valve and 
reconnect 
the pipeline 

as before

Remove the 4-way valve 
and clean the system

3. Vacuum 
the system 
and charge 

refrigerant 

again

38

◆
◆Remember the installation direction of the 

4-way valve before removal.
◆
◆Remove the coil.

◆
◆Wrap the 4-way valve prior to unbrazing 

to prevent it from being damaged and use 
it for future analysis.
◆
◆Unbraze the 4-way valve.

◆
◆Replace the 4-way valve with the same 

model, or that approved by the qualified 
technician.
◆
◆Wrap the 4-way valve with wet cloth.

◆
◆Reconnect the connection pipe as before.

◆
◆Braze the pipeline.

◆
◆Charge nitroge when unbrazing.

◆
◆Vacuum the system until the pressure 

goes as low as -1.0bar.
◆
◆The refrigerant charge and quality shall 

comply with the specification on the 
nameplate.

Sayfa 41

Note: Be sure to recover the refrigerant, prepare proper devices and tools and keep a good ventilation.

Steps
Graphic Representation
Instructions

1. Remove 
the panel as 
shown in the 

right figure

2. Disconnect 
the 
connection 

pipe of the 
accumulator

3. Remove 
the 4-way 

valve 
assembly if 

necessary

D Series Modular Air-cooled Scroll Chillers 

Service Manual

Accumulator

◆
◆Remove the panel as shown in the left 

figure with a screwdriver.

panels

◆
◆Unbrazer the connection pipe of the 

accumulator.

accumulator

◆
◆Unbraze the 4-way valve assembly.

4-way valve assemly

39

Sayfa 42

D Series Modular Air-cooled Scroll Chillers 
Service Manual

4. Remove 
the bolts at 

the base

5. Remove 
the 
accumulator.

6. Purge 
the system 
by charging 

nitrogen

40

◆
◆Remove bolts at the base with a wrench.

底座螺栓
Bolts

◆
◆Remove the accumulator

◆
◆Connect the pipeline of the accumulator 

with the nitrogen tank and adhesive tape 
can is allowed to be used for the large-
sized pipeline.
◆
◆Purge the system by charging nitrogen.

Connect the accumulator 
with the nitrogen tank 

Sayfa 43

7. Check if 
oil needs to 

be added

Drill a hole close to the bottom

8. Add oil if 
necessary

Charge oil here

9. Reconnect 
the 
connection 

pipe of the 
accumulator 
and vacuum 

the system 

and then 

charge 
refrigerant 

again

D Series Modular Air-cooled Scroll Chillers 

Service Manual

◆
◆Tilt the accumulator and then drill a hole 

close to the bottom and then pour the 
oil inside the accumulator to a prepared 
container.

◆
◆Charge oil to the accumulator prior to 

brazing.

◆
◆Charge nitrogen when brazing.

◆
◆Vacuum the system until the pressure 

goes as low as -1.0bar.
◆
◆The refrigerant charge and quality shall 

comply with the specification on the 
nameplate.

41

Sayfa 44

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Shell-and-tube Heat Exchanger

Note: Check the water system and be sure the shell-and-tube heat exchanger shall be replaced. And then cut off the power and recover 
the refrigerant.

Steps
Graphic Representation
Instructions

1. Remove 
the panel as 
shown in the 

right figure

2. Loosen 
the pipeline 

connectors 
and remove 

the panel 
outside of 

the heat 
exchanger

盲塞
Blind plug

3. Unbraze 
the pipeline 

connecting 

the heat 
exchanger. 
(Different heat 

exchangers 

vary in 
structure so 
it is better to 
remember the 
piping location 

to prevent 
misconnection

42

◆
◆Remove four panels around the heat 

exchanger and the frame in front of the 
blind plug.

◆
◆Remove the pipeline

◆
◆Remove the metal sheets located 

underside with a screwdriver.
◆
◆Loosen the blind plug and drain the water 

inside the pipeline.

◆
◆Wrap the cooper pipe with wet cloth. 

◆
◆Unbraze the pipelines connecting the heat 

exchanger.

Sayfa 45

4. Loosen 
four screws 
fixing the heat 

exchanger

5. Remove 
the shell-and-

tube heat 
exchanger

6. Place a 
new heat 
exchanger 
and connect 

the pipeline 

and then 
vacuum the 
system and 
lastly charge 

refrigerant

D Series Modular Air-cooled Scroll Chillers 

Service Manual

◆
◆Loosen four screws fixing the heat 

exchanger with a screwdriver.

Screws

◆
◆Remove the shell-and-tube heat 

exchanger.

◆
◆Replac the heat exchanger with the same 

model.
◆
◆Wrap the cooper pipe with wet cloth and 

braze the pipeline. 
◆
◆Vacuum the system until the pressure 

goes as low as -1.0bar.
◆
◆The refrigerant charge and quality shall 

comply with the specification on the 
nameplate.
◆
◆Connect the water pipeline.

◆
◆Put the metal sheets back.

43

Sayfa 46

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Steps
Graphic Representation
nstructions

1. Remove 
the panel as 
shown in the 

right figure

2. Remove 
the guard 

cover

3. Remove 
the fan 
blades

44

Fan

Note: Be sure to cut off the power supply firstly

◆
◆Remove the panel as shown in the left 

figure.

◆
◆Remove the guard cover with a wrench.

◆
◆Remove the fan blades with a screwdriver.

Sayfa 47

4. Remove 
the motor
◆
◆Remove the motor with a wrench.

5. Remove 
the frame

6. Reinstall 
the fan 
assembly

D Series Modular Air-cooled Scroll Chillers 

Service Manual

◆
◆Remove the frame.

Frame

◆
◆Reinstallation sequence: 1. frame; 2. 

motor; 3. fan blades; 4. guard cover; 5. 
panel.

45

Sayfa 48

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Fintube Heat Exchanger

Note: Be sure to cut off the power supply and recover the refrigerant firstly.

Steps
Graphic Representation
Instructions

1. Remove 
the panel as 

shown the 
right figure

2. Unbraze 
the inlet/
outlet pipeline 

of the heat 
exchanger. 

Do not 
damage the 
fins and metal 
sheets during 

unbrazing
Brazing spot

3. Remove 
the frame of 

the header 
and screws 

and bolts 
on the heat 

exchanger

Frame

46

◆
◆Recover refrierant completly.

◆
◆Cut off the power supply.

◆
◆Remove the fan assembly and draw out 

the power cord of the fan motor and then 
remove the metal sheets outside the 
condenser.
Note: remember the wiring sequence of the 
fan motor.

◆
◆Unbraze the pipeline of the condenser.

◆
◆Remove the frame of the header with a 

wrench.
◆
◆Remove screws and bolts on the heat 

exchanger.

Sayfa 49

4. Place a 
new heat 
exchanger 
and vacuum 

the system 

and then 

charge 
refrigerant 

and lastly 
put the fan 

and metal 
sheets back

Note: check the refrigeration system and be sure the electronic expansion valve shall be replaced, and then cut off the power supply and 
recover the refrigerant.

Steps
Graphic Representation
Instructions

1. Recover 
the refrigerant 

and remove 

the panel

2. Remove 
the electronic 

expansion 

valve coil.

D Series Modular Air-cooled Scroll Chillers 

Service Manual

◆
◆Install a new heat exchanger.

◆
◆Braze the pipeline.

◆
◆Vacuum the system until the pressure is as 

low as -1.0bar.
◆
◆The refrigerant charge and quality shall comply 

with the specification on the nameplate.
Take care to the wiring sequence when rewiring 
the fan motor.

Electornic Expansion Valve

◆
◆Cut off the power supply

◆
◆Recover the refrigerant.

◆
◆Remove the panel.

Electronic expansion valve

◆
◆Wrap the valve with wet close to prevent 

the slide block from being burnt down and 
never the let water flow into the pipeline. 

Coil

47

Sayfa 50

D Series Modular Air-cooled Scroll Chillers 
Service Manual

3 Remove the 
connection 

pipe of the 

electronic 
expansion 

valve

4. Remove 
the electronic 

expansion 

valve

5. Place 
a new 
electronic 
expansion 

valve

48

◆
◆Unbraze the electronic expansion valve 

◆
◆Charge nitrogen during brazing.

◆
◆Take care to prevent surrounding item from 

being burnt down owing to high temperature 
during brazing.

◆
◆Remove the electronic expansion valve.

◆
◆Braze each pipeline.

◆
◆Charge nitrogen during brazing.

◆
◆Take care to prevent surrounding item 

from being burnt down owing to high 
temperature during brazing.

Sayfa 51

6. Reinstall 
the electronic 

expansion 
valve coil and 

vacuum the 
system and 
then charge 

refrigerant 

and lastly 

put the 
panel back

4 ROUTINE MAINTENANCE

Routine maintenance shall be performed by the skilled and qualified servicemen. 
(1). Refrigerant Leakage 
Suds is usually used for the leakage test by applying it at the spot (soldering spots, valve pistols, 
connectors) where leakage is probably to occur. During the test, if soap bubbles pop up, it indicates leakage 
exists and repair is required. If suds fails to work, a electronic leakage detectors is a alternative. Refrigerant 
charge can be checked by measuring the suction and discharge pressure. Leakage test should be performed 
wherever leakage occurs or some components of the refrigeration system are replaced. 

There are two difference conditions for charging refrigeration stated as below.
◆Complete charging 
In this case, take a leakage test by charging hi-pressure nitrogen (15~20kg) or refrigerant into the system. If 
soldering is required, note that gas inside the system must be expelled firstly. The whole system must be dried 
and vacuumed prior to charging. 

a.	Connect the manifold gage.
b.	Vacuum the system with a vacuum pump.
Step 1: Expel the hi-pressure nitrogen for leakage test.
Step 2: Connect the pipeline at both the high and low pressure sides of the manifold gage as shown in the 
figure below. Note that vacuuming shall be taken at both sides. The degree of vacuum will refer to the reading 
of the manometer at the low side. 

D Series Modular Air-cooled Scroll Chillers 

Service Manual

◆
◆The coil shall be matched with the valve 

body exactly. 
◆
◆The degree of vacuum shall be kept as low 

as -1.0 bar. 
◆
◆The refrigerant charge and quality shall comply 

with the specification on the nameplate.
◆
◆After replace the electronic expansion 

valve, energize the unit again.
◆
◆Reinstall the panel.

Hi-pressure gage
Low-pressure gage

Manifold gage

Vacuum pump

Pipeline

Pipeline

Pipeline

49

Sayfa 52

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Step 3: Open the valves at both the high-pressure and low-pressure sides and then start the vacuum pump 
until the gage reading is below -1bar. After that, let the vacuum pump lasts for another 0.5~1.0 hour. 

Step 4: Close the valves and stop the vacuum pump. Note that only the valves have been closed can the 
vacuum pump be stopped, otherwise air is possible to go into the system again.

Step 5: Take the leakage test. Be sure the vacuumed system keeps a pressure no higher than 80Pa and 
keeps little pressure rise in half an hour.

c.	Refrigerant charging starts after the degree of vacuum reaches the expected range and lasts for 30 minutes. 

The amount of refrigerant charge shall comply with that specified on the nameplate or product data sheet. 
◆Adding 

Refrigerant charge is determined through stringent tests, as excess or shortage of refrigerant would cause 
the compressor to run improperly. Thus, the refrigerant charge shall be consistent with that specified on the 
nameplate. If refrigerant charge is indeed insufficient, follow the steps below for adding.

Step 1: Weigh the refrigerant tank with an electronic scale and connect the refrigerant tank with the 
pressure gage through the pipeline.

Step 2: Expel the air inside the pipeline. Firstly half open the shutoff valve of the refrigerant tank and then 
loosen the connector connecting the pressure gage to expel the air until the connector hisses for five seconds 
and then tighten the connector. 

Step 3: Return the electric scale to zero by energizing it again. 
Step 4: Open all valves between the refrigerant tank and the unit to charge refrigerant as per the amount 
specified on the nameplate. Excessive refrigerant would dilute oil while insufficient refrigerant would lower 
the refrigeration capability and result in poor lubrication and high discharge temperature etc. Note that only 
refrigerant vapor can be charged into the system at the low-pressure side when the unit is in operation. 
However, it is highly recommended to charge refrigerant at the hi-pressure side when the unit is shut down, 
otherwise it would cause slugging during startup. 

(2). Air Purge
Prior to refrigerant charging, it is imperative to expel air inside the system and the system must be 
vacuumed.

a.	Connect the manifold gage.
b.	Vacuum the system with a vacuum pump.
c.	Charge refrigerant at the low-pressure side as per the amount specified on the nameplate or product data 

sheet when the degree of vacuum appro aches the expected range.
d.	The refrigerant charge will be affected by the ambient temperature. When the charge is under the 

required amount, it is allowed to add refrigerant vapor after starting the water pump and the unit.

50

Low-pressure gage

Hi-pressure gage

Manifold gage
Refrigerant charge 

Pipeline

Pipeline

Sayfa 53

5 EXPLODED VIEWS AND PART LIST

(1). Model: LSQWRF65M/NaD-M

D Series Modular Air-cooled Scroll Chillers 

Service Manual

51

Sayfa 54

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Parts List: LSQWRF65M/NaD-M for EL01500500

No.
Name of part
Part code

1
Electric Expand Valve Fitting                            
4304413214

2
Strainer                                                                  
07210037

3
Magnet Coil                                                                 
4300040064

4
Filter                                                                   
07218603

5
Condenser Assy                                          
0112110001001

6
Rear Panel                                                                 
0154110000101P

7
Sensor Sub-assy                                          
39008000004G

8
One Way Valve                                           
0733420001

9
pipe connector                                          
06128301

10
Pressure Protect Switch                                       
4602001570

11
Pressure Protect Switch                                       
4602001579

12
Pressure Protect Switch                                       
4602001582

13
Dry Evaporator
0105887701

14
Base Frame Assy                                          
01281100012P

15
Steam current Switch                                        
45028209

16
Gas-liquid Separator                                        
07424148

17
Electrical Heater                                         
76515211

18
Pressure Protect Switch                                       
4602001569

19
Pressure Protect Switch                                       
 4602001581

20
Compressor                                                                 
00201100002

21
Pressure Protect Switch                                       
 4602001583

22
Compressor Gasket                                         
02118049

23
Electronic Expansion Valve                             
07331139

24
Electric Expand Valve Fitting                            
4304413213

25
Magnet Coil                                                                 
4300040048

26
4-way Valve                                                                 
43000339

27
Front Panel                                                                 
01541100003P

28
Front Panel                                                                 
01541100002P

29
Streamlined Dome                                          
22265801

30
Centrifugal Fan                                          
10355801

31
Fan Motor                                                                  
1570110000101

32
Electric Box Assy                                         
01391100045 

33
Terminal Board                                          
42018452

34
Terminal Board                                          
42011135

35
Over Current Protector                                        
46028000011

36
Terminal Board                                          
420102471

37
Phase Reverse Protector                                       
32214101

38
Single-phase Air Switch                                       
45020203

39
AC Contactor                                                                
44010235

40
AC Contactor                                                                
44010229

41
Main Board                                                                 
30222000002

52

Sayfa 55

(2). Model: LSQWRF80M/NaD-M

D Series Modular Air-cooled Scroll Chillers 

Service Manual

53

Sayfa 56

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Parts List: LSQWRF80M/NaD-M for EL01500520

No.
Name of part
Part code

1
Electric Expand Valve Fitting                            
4304413213

2
Electronic Expansion Valve                             
07331139

3
Magnet Coil                                                                 
4300040064

4
4-way Valve                                                                 
43000412

5
Filter                                                                   
07414118

6
Pressure Protect Switch                                       
4602001570

7
Pressure Protect Switch                                       
4602001582

8
Pressure Protect Switch                                       
4602001579

9
Rear Panel                                                                 
01541100001P

10
One Way Valve                                           
0733420001

11
Sensor Sub-assy                                          
39008000004G

12
pipe connector                                          
06128301

13
Compressor                                                                 
00201100004

14
Dry Evaporator                                          
01058800057

15
Steam current Switch                                        
45028209

16
Gas-liquid Separator                                        
07421111

17
Compressor Gasket                                         
02118049

18
Electrical Heater                                         
76515211

19
Pressure Protect Switch                                       
4602001583

20
Pressure Protect Switch                                       
4602001581

21
Pressure Protect Switch                                       
4602001569

22
Strainer                                                                  
07210037

23
Electric Expand Valve Fitting                            
4304413214

24
Magnet Coil                                                                 
4300040048

25
Condenser Assy                                          
01121100020

26
Front Panel                                                                 
01541100003P

27
Front Panel                                                                 
01541100002P

28
Streamlined Dome                                          
22265801

29
Centrifugal Fan                                          
10355801

30
Fan Motor                                                                  
15701100003

31
Electric Box Assy                                         
01391100061

32
Terminal Board                                          
42018452

33
AC Contactor                                                                
44010229

34
Terminal Board                                          
42011135

35
Single-phase Air Switch                                       
45020203

36
Terminal Board                                          
 420102471

37
AC Contactor                                                                
44010240

38
Phase Reverse Protector                                       
32214101

39
Over Current Protector                                        
46028000010

40
Main Board                                                                 
30222000002

54

Sayfa 57

(3). Model: LSQWRF130M/NaD-M

D Series Modular Air-cooled Scroll Chillers 

Service Manual

55

Sayfa 58

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Parts List: LSQWRF130M/NaD-M for EL01500510  

No.
Name of part
Part code

1
Rear Grill                                                                 
01571100001

2
Condenser Assy 1                                          
0112110001101

3
Lower panel                                                                 
01541100005P

4
4-way Valve                                                                 
43000339

5
Electric Expand Valve Fitting                            
4304413214

6
Filter                                                                   
07218603

7
Electronic Expansion Valve                             
07331139

8
Condenser Assy 2                                         
0112110001201

9
Lower panel                                                                 
01541100006P

10
Lower panel                                                                 
01541100007P

11
Sensor Sub-assy                                          
39008000003G

12
One Way Valve                                           
07332224

13
Chassis Sub-assy                                          
01191100004P

14
Dry Evaporator
01058800013

15
Pressure Protect Switch                                       
4602001570

16
Pressure Protect Switch                                       
4602001584 

17
Pressure Protect Switch                                       
4602001585

18
Steam current Switch                                        
45028209

19
Compressor                                                                 
00201100002 

20
Gas-liquid Separator                                        
07424148

21
Compressor Gasket                                         
02118049

22
Pressure Protect Switch                                       
4602001582 

23
Pressure Protect Switch                                       
4602001579 

24
Electrical Heater                                         
76515211

25
pipe connector                                          
06128301

26
Pressure Protect Switch                                       
4602001547

27
Strainer                                                                  
07210037

28
Electric Expand Valve Fitting                            
4304413213

29
Magnet Coil                                                                 
4300040048

30
Magnet Coil                                                                 
4300040049

31
Lower panel                                                                 
01541100004P

32
Side Plate                                                                 
01311100006P

33
Streamlined Dome
22265801

34
Centrifugal Fan                                          
10355801

35
Fan Motor                                                                  
15701100001

36
Terminal Board                                          
420111251

37
AC Contactor                                                                
44010235

38
Terminal Board                                          
42010247

39
Terminal Board                                          
42010254

40
Terminal Board                                          
42011135

41
Over Current Protector                                        
46028000011

42
Terminal Board                                          
42018452

43
Main Board                                                                 
30222000002

44
Electric Box Assy                                         
01391100047 

45
AC Contactor                                                                
44010229

46
Single-phase Air Switch                                       
45020203

47
Phase Reverse Protector                                       
32214101

56

Sayfa 59

(4). Model: LSQWRF160M/NaD-M

D Series Modular Air-cooled Scroll Chillers 

Service Manual

57

Sayfa 60

D Series Modular Air-cooled Scroll Chillers 
Service Manual

Parts List: LSQWRF160M/NaD-M for EL01500530  

No.
Name of part
Part code

1
Condenser assy 2
0112110002501

2
Rear Grill
01571100001

3
Electric Expand Valve Fitting
4304413213

4
Magnet Coil
4300040049

5
4-Way Valve
43000412

6
Electronic Expansion Valve
07331139

7
Filter
07414118

8
Pressure Protect Switch
4602001570

9
Condenser assy 1
0112110002601

10
Lower Panel 3
01541100082P

11
Lower Panel 4
01541100047P

12
Sensor Sub-assy
39008000046G

13
One Way Valve
0733420001

14
Pressure Protect Switch
4602001579

15
Pressure Protect Switch
4602001582

16
Dry Evaporator
01058800064

17
Gas-liquid Separator
07421111

18
Pressure Protect Switch
4602001591

19
Pressure Protect Switch
4602001590

20
Steam current Switch
45028209

21
Pressure Protect Switch
4602001583

22
Electrical Heater
76515211

23
Pressure Protect Switch
4602001581

24
Compressor
00201100004

25
Compressor Gasket
02118049

26
Chassis Sub-assy
01191100011P

27
pipe connector
06128301

28
Pressure Protect Switch
4602001569

29
Strainer
07210037

30
Lower Panel
01541100067P

31
Pressure Protect Switch
4602001589

32
Electric Expand Valve Fitting
4304413214

33
Magnet Coil
4300040048

34
Handle
26235253

35
Lower Panel 1
01541100053P

36
Side Plate
01311100006P

37
Scram switch
45010024

38
Streamlined Dome
22265801

39
Fan Motor
15701100003

40
Centrifugal Fan
10355801

41
Fan Motor
1570110000301

42
Terminal Board
420111251

43
Electric Cabinet Assy
01391100069 

44
Terminal Board
42010254

45
Terminal Board
42010247

46
Terminal Board
42011135

47
AC Contactor
44010229

48
Terminal Board
42018452

49
Main Board
30222000002

50
AC Contactor
44010240

51
Phase Reverse Protector
32214101

52
Single-phase Air Switch
45020203

53
Over Current Protector
46028000008

58

Sayfa 61

For continuous improvement in the products, Gree reserves the right to modify the product specification and appearance in this manual without notice and without incurring any obligations.