D SERIES MODULAR AIR-COOLED SCROLL CHILLERS SERVICE MANUAL T1/R410A/50Hz (GC201405-I)
PRODUCT .....................................................................................................2 1 LINEUP....................................................................................................................... 2 2 NOMENCLATURE...................................................................................................... 2 3 FEATURES................................................................................................................. 3 4 PRODUCT DATA........................................................................................................ 4 5 OPERATION PRINCIPLE........................................................................................... 6 CONTROL......................................................................................................8 1 OPERATION FLOWCHART....................................................................................... 8 2 CONTROL LOGIC.................................................................................................... 10 3 CONTROLLER......................................................................................................... 12 NSTALLATION.............................................................................................17 1 BEFORE INSTALLATION......................................................................................... 17 2 INSTALLATION LOCATION..................................................................................... 17 3 CAUTION FOR INSTALLATION............................................................................... 17 4 DIMENSION DATA................................................................................................... 17 5 MACHINE FOOTPRINT........................................................................................... 19 6 TYPICAL WATER PIPING DIAGRAM .................................................................................20 7 FREEZE PROTECTION........................................................................................... 21 8 ELECTRIC WIRING WORK..................................................................................... 21 MAINTENANCE............................................................................................29 1 ERROR LIST............................................................................................................ 29 2 FLOW CHART OF TROUBLESHOOTING............................................................... 30 3 REMOVALS AND REINSTALLATION...................................................................... 35 4 ROUTINE MAINTENANCE...................................................................................... 49 5 EXPLODED VIEWS AND PART LIST...................................................................... 51 CONTENTS
PRODUCT D Series Modular Air-cooled Scroll Chillers Service Manual 1 PRODUCT
D Series Modular Air-cooled Scroll Chillers Service Manual PRODUCT 1 LINEUP Series Model Name Product LSQWRF65M/NaD-M EL01500500 60/17.06 65/18.48 LSQWRF80M/NaD-M EL01500520 71/20.19 79.5/22.61 D LSQWRF130M/NaD-M EL01500510 120/34.12 130/36.97 LSQWRF160M/NaD-M EL01500530 145/41.23 170/48.34 2 NOMENCLATURE LS QW R F 130 M / Na D - M 1 2 3 4 5 6 7 8 9 NO. Items Options 1 Product type LS- chillers 2 Compressor type QW- hermetic scroll compressors 3 Function type Default-cooling only R-heat pump 4 Condenser type F: air-cooled 5 Nominal cooling capacity 6 Structural design M-modular design 7 Refrigerant Default–R22 Na–R410A 8 Development number — 9 Power supply M – 380-415V,3Ph,50Hz PRODUCT 2 Capacity (kW/Ton) Power Supply Refrigerant Appearance Code Cooling Heating 380-415V,3Ph,50Hz R410A Note:1Ton =12000Btu/h = 3.517kW 65:60kW= 17.06 RT 80:71kW=20.19 RT 130:120kW=34.12 RT 160:145kW=41.23 RT
D Series Modular Air-cooled Scroll Chillers 3 FEATURES 3.1 General D series modular air-cooled scroll chillers are well-developed products incorporated with multiple advanced technologies. It features the low noise level, compact structure, easy operation, reliable running, and convenient installation and service, widely used at newly built or retrofitted industrial and civil buildings in various sizes, such as, hotels, apartments, restaurants, office buildings, shopping malls, theaters, gyms, workshops, hospitals and other places where there are high requirements on noise level and air quality but it is troublesome to install the cooling tower. D series modular air-cooled scroll chillers are constructed of one or up to 16 single units which may vary in structure and in cooling capacity. The 65, 80 units have two independent refrigeration cycle and the 130,160 units have four. The modular design is able to realize the modular system with the cooling capacity ranging from 60 to 1160kW. 3.2 Features D series modular air-cooled scroll chillers work outstandingly by virtue of their major features stated below. ◆ ◆High energy efficiency: It is initially certified as one of the energy-saving chiller products in China. ◆ ◆Free master unit design: Any single unit can operate as the master once connected with the control panel. It overcomes the problem which would occur to the product of other manufacturer that the whole system would fail to work properly when the fixed master unit malfunctions. ◆ ◆Excellent compatibility: Each chiller is constructed of up to 16 single units of 65NaD,80NaD or up to 8 single units of 130NaD,160NaD. ◆ ◆Hermetic scroll compressor: Compared with other type of compressor under the same cooling load, it has few movable components, smaller rotating torque, lower noise and vibration and higher reliability and efficiency. ◆ ◆Super protection: It is equipped with the top-end microcomputer control system which is capable of providing well-rounded protection and self-diagnosis, such as high/low pressure protection, freeze protection, over-temperature protection, compressor overload protection, phase loss/reversal protection, water flow switch protection, etc. ◆ ◆High reliability: It is constructed of well-designed refrigeration parts for multiple refrigeration cycles, adequately guaranteeing the reliable operation. ◆ ◆Compact structure: The modular design enables the compact structure, reduced volume, light weight, easy handling and shipping and flexible installation. ◆ ◆Low maintenance cost: The especially design structure allows easy access and service and low maintenance cost. ◆ ◆Low noise: The unit runs with low noise and vibration, widely applicable for various projects. ◆ ◆Quiet mode: The unit is allowed to run in the quiet mode based on the user’s requirement, which can not only save energy but also create a comfortable and pleasant living environment. ◆ ◆Economy mode: The unit can run in the economy mode without lessening the air conditioning effect so as to cut down the electricity consumption. ◆ ◆Equilibrium running: Tt indicates each compressor will run alternately so as to extend their service life. ◆ ◆Powerful remote monitoring: Gree centralized air conditioning system can be perfectly integrated to the BMS or Gree remote monitoring system so as to realize remote control to its operation and remote monitoring to its running parameters and alarm data etc. Control panel Control panel Control panel Wiring Drawing between Modules ◆ ◆Intelligent ON/OFF control: The unit is capable of automatically turning on/off the compressor through controlling the entering water temperature and the temperature rise rate in accordance with the change in load so as to make the capacity of the unit perfectly match the required load and reduce to the most extent the electricity consumption and effectively avoid remarkable temperature fluctuation. Service Manual 3 PRODUCT
D Series Modular Air-cooled Scroll Chillers Service Manual 4 PRODUCT DATA 4.1 Product Data at Rated Condition Heat Pump LSQWRF65M/NaD-M LSQWRF80M/NaD-M LSQWRF130M/NaD-M LSQWRF160M/NaD-M Models Product Code EL01500500 EL01500520 EL01500510 EL01500530 Capacity steps % 0-50-100 0-50-100 0-25-50-75-100 0-25-50-75-100 kW 60 71 120 145 Cooling Ton 17.06 20.19 34.12 41.23 Capacity kW 65 79.5 130 170 Heating Ton 18.48 22.61 36.97 48.34 Cooling kW 21.1 25.7 42.3 53.0 Power Input Heating kW 21.0 27.0 44.4 56.0 EER W/W 2.84 2.76 2.84 2.74 COP W/W 3.09 2.94 2.93 3.04 Power Supply — 380-415V,3Ph,50Hz Running Control — Microcomputer Auto Control; Running Status Display; Abnormal Status Alarm Safeties — High-low pressure protection, discharge temp. protection, motor overload protection, anti-freeze, water flow protection, phase-sequence protection, compressor overload protection Type — Constant Speed Scroll Compressor Starting mode — Direct starting Quantity — 2 2 4 4 Refrigerant Type — R410A Type — Dry Expansion Evaporator 3/h 10.3 12.2 20.6 24.9 m Water flow volume GPM 45.0 54.0 91.0 110.0 kPa 15 20 30 35 Water side Pressure Drop ft.WG 4.92 6.56 9.84 11.48 heat exchanger Max. working Pressure MPa 1 water in/outlet pipe flange specification mm DN65 DN65 DN80 DN80 Type — Aluminum Fin-copper Tube Fan type/ Number of fans — Axial Fan/2 Axial Fan/2 Axial Fan/4 Axial Fan/4 3/h 2.7×10 4 3.0×10 4 5.4×10 4 6.0×10 4 Air side heat m exchanger L/s 0.75×10 4 0.83×10 4 1.5×10 4 1.67×10 4 Total fan air flow CFM 1.59×10 4 1.764×10 4 3.18×10 4 3.528×10 4 Total fan motor power kW 0.65×2 0.95×2 0.65×4 0.95×4 Sound pressure level dB(A) 70 71 72 74 Width mm 2040 2040 2226 2226 Outline Dimension Depth mm 1000 1000 1650 1650 Height mm 2230 2230 2230 2230 Net Weights kg 740 792 1315 1504 Operating weight kg 814 871 1447 1654 Auxiliary electric heater- power (Ref.) kW 15 15 30 30 Loading quantity 40'GP/40'HQ — 10/10 10/10 6/6 6/6 Notes: a. The loading quality listed in the table above is just for reference. b. The unit is designed, manufactured, inspected and tested in accordance with GB/T18430.1-2007. c. Parameters on the nameplate always take precedence. PRODUCT 4
D Series Modular Air-cooled Scroll Chillers d. Consult the local sales agency concerning special requirements and we will go to the length of figuring out the most feasible solution. 4.2 Nominal capacities are based on the follow conditions: Water side Air side Item Water flow volume Leaving Water Temperature Dry-bull temp. Wet-bull temp. m 3/(h·kw) (℃) (℃) (℃) Cooling 0.172 7 35 — Heating 45 7 6 4.3 Operation Range Water side Air side Leaving Water Temperature Temperature Difference of Water Air on Condenser (℃) (℃) (℃) Cooling 5~15 2.5~6 15~45 Heating 40~50 2.5~6 -15~24 Note: when the unit is going to operate beyond the working conditions, please contact Gree for consultation. 4.4 Electric Data Compressor Fan Motor Air Switch Model Rated Power Supply Qty MRC Each NRC Each (A) Qty. NRC Each (A) LSQWRF65M/NaD-M 2 29.1 17.6 2 1.71 63 LSQWRF80M/NaD-M 2 29.3 25.7 2 2.50 80 380-415V,3Ph,50Hz LSQWRF130M/NaD-M 4 29.1 17.6 4 1.71 125 LSQWRF160M/NaD-M 4 35 25.7 4 2.50 160 Notes: MRC: Maximum running current (A). NRC: Nominal running current (A). Service Manual MRC (A) (A) 5 PRODUCT
D Series Modular Air-cooled Scroll Chillers Service Manual 5 OPERATION PRINCIPLE 5.1 Schematic Diagram Each circuit of the modular chiller is independent and identical and herein only a circuit is taken for an example. ◆ ◆Refrigeration Cycle: The low-pressure superheated refrigerant vapor from the evaporator is drawn into the compressor through which the low-pressure vapor is compressed to hi-temperature and hi-pressure refrigerant vapor. Then, the refrigerant vapor passes the condenser and turns to saturated or sub- cooled refrigerant liquid. And then, it passes the throttling device and flows into the evaporator where it evaporates by absorbing heat from the second refrigerant and then is drawn into the compressor again. The second refrigerant is then transferred to where air cooling is required. ◆ ◆Reverse Refrigeration Cycle: During the reverse refrigeration cycle, a 4-way valve is used to make the refrigerant flow in a reverse direction as stated below. The hi-temperature and hi-pressure refrigerant vapor coming out from the compressor directly releases heat to the secondary refrigerant and turns to the refrigeration liquid. Then, the refrigerant vapor passes the throttling device and flows into the air- cooled exchanger where it evaporates by absorbing heat from the surrounding environment and then is drawn into the compressor again. The second refrigerant which has approached the temperature set point is then transferred to where air heating is required. PRODUCT 6
CONTROL D Series Modular Air-cooled Scroll Chillers Service Manual 7 CONTROL
D Series Modular Air-cooled Scroll Chillers Service Manual CONTROL 1 OPERATION FLOWCHART 1.1 Cooling Operation CONTROL 8 Energize the unit
1.2 Heating Operation D Series Modular Air-cooled Scroll Chillers Service Manual Energize the unit 9 CONTROL
D Series Modular Air-cooled Scroll Chillers Service Manual 2 CONTROL LOGIC 2.1 Cooling Control 2.1.1 Control to the Compressor (1). “First On, First Off” “First On, First Off”/“First Off, First On” control indicates the numbered compressor which is started/stopped firstly will then be stopped/started firstly. (2). Temperature Drop/Rise Rate Control The water temperature range control assisted by the temperature drop/rise rate control is capable of precisely adapting the load change of the terminal units and avoiding remarkable water temperature fluctuation. 2.1.2 Freeze Protection For each single module, when the anti-freezing temperature or the leaving water temperature is lower than the limit value, freeze protection will work and this module stops; when the anti-freezing temperature and the leaving water temperature go higher than the normal value, freeze protection will quit; when the anti-freezing temperature and the leaving water temperature are between the limit value and the normal value, the module is protected again freeze. 2.1.3 Shutdown Shutdown manually or timely: in this case, the compressor and the auxiliary electric heater stop firstly, then the electronic expansion valve initializes, and then the 4-way valve is de-energized, and lastly the water pump stops. Shutdown when reaching the set point: in this case, the compressor stops firstly, and then the fan stops and the electronic expansion valve initializes. However, the 4-way valve keeps its state unchanged and the water pump keeps running. Shutdown due to errors: in this case, the compressor stops firstly, and then the fan stops (except that the fan is malfunctioning), and the electronic expansion valve initializes. However, the 4-way valve keeps its state unchanged and the water pump keeps running. 2.2 Heating Control 2.2.1 Control on the Compressor It is the same as that in selection 2.1.1. 2.2.2 Over-temperature Protection For each single module, when the over-temperature is higher than the limit value, over-temperature protection will work; when the over-temperature goes lower than the normal value, over-temperature protection will quit; when the over-temperature is between the limit value and the normal value, the module is still protected again over-temperature. 2.2.3 Control on the Auxiliary Electric Heater When the auxiliary electric heater is enabled through the wired controller, it will work in accordance with the change of the entering water temperature. When the flow switch and the entering water temperature sensors work normally, any other error can be ignored. When the auxiliary electric heater is disabled through the wired controller, the auxiliary electric heater will stop working. When all entering water temperature sensors malfunction, the auxiliary electric heater will stop working. When any flow switch malfunctions, the auxiliary electric heater will stop working. When the unit is under over-temperature protection but the auxiliary electric heater is not allowed to stop, the auxiliary electric heater will keep working until the entering water temperature reaches the set point. 2.2.4 Shutdown Shutdown manually or timely: in this case, the compressor and the auxiliary electric heater stop firstly, then the electronic expansion valve initializes, and then the 4-way valve is de-energized, and lastly the water pump stops. Shutdown when reaching the set point: in this case, the compressor stops firstly, and then the fan stops and CONTROL 10
the electronic expansion valve initializes. However, the 4-way valve keeps its state unchanged and the water pump keeps running. Shutdown due to errors: in this case, the compressor stops firstly, and then the fan stops (except that the fan is malfunctioning), and the electronic expansion valve initializes. However, the 4-way valve keeps its state unchanged and the water pump keeps running. 2.3 Freeze Protection Under the OFF state at any mode (except the manual defrosting mode), when the freeze protection is activated through the wired controller, the unit will be protected again freeze. Free protection is factory defaulted to be ON. When the module is in the freeze protection, its compressor will work as per the on/off setting and also the principle of “Six-minute On, Thee-minute Off”. 2.4 Control to the Compressor All compressors run as per the principle of “First On, First Off” and “First Off, First On”. See section 2.1 and section 2.2. 2.5 Control to the Fan The fan starts earlier than the compressor upon startup, and stops later than the compressor upon shutdown. During defrosting, the fan and the 4-way valve stops. After defrosting they start again. 2.6 Control to the 4-way Valve The 4-way valve is stopped at the cooling mode. At the heating mode, it will start after the compressor runs. During defrosting it stops and then starts again after defrosting. It will stop later than the compressor upon shutdown. 2.7 Control to the Water Pump When any module is required to run (incl. manual startup, timely startup, startup again freeze), water pumps of all module starts. Then, when one module reaches the set point and is shut down, water pumps of all modules keep running; when one module is shut down manually or timely, its water pump keeps running and will stop only after all modules are shut down; when one module malfunctions and is shutdown, its water pump keeps running. 2.8 Control to the Electronic Expansion Valve The electronic expansion valve initialize when the wired controller is emerged for the first time. After the compressor has been started, the electronic expansion valve starts to adjust its opening angle. 2.9 Protection 2.9.1 Recoverable Protection ◆Compressor 1/2 low pressure protection When it is detected the low-pressure switch of compressor 1 (compressor 2) is opened compressor 1 (compressor 2) will be shut down immediately. Meanwhile the indicating LED will light on and the error information will be displayed among the error log which must be manually cleared for normal operation of next time. ◆Compressor 1/2 high discharge protection When it is detected in three consecutive seconds that the discharge temperature of compressor 1 (compressor 2) exceeds the set point, compressor 1 (compressor 2) will be shut down immediately but the fan will still run for some time. Meanwhile the indicating LED will light on and the error information will be displayed among the error log which must be manually cleared for normal operation of next time. 2.9.2 Irrecoverable Protection ◆Compressor 1/2 high pressure or over-current protection When it is detected that the high pressure switch of compressor 1 (or compressor 2) is open, compressor 1 (or compressor 2) will be shut down but the fan will still last for some time. Meanwhile the indicating LED will light on and the error information will be displayed among the error log which must be manually cleared for normal operation of next time. D Series Modular Air-cooled Scroll Chillers Service Manual 11 CONTROL
D Series Modular Air-cooled Scroll Chillers Service Manual ◆Fan 1/2 over-current protection When any fan is over-current, this module unit will be shut down automatically. Meanwhile, the error information will be displayed among the error log which must be manually cleared for normal operation of next time. ◆Flow switch protection When a single module unit detect that the flow switch is closed (under normal condition, it keeps open), it will be shut down automatically. When all modules are shut down because of flow switch protection, the water pump will stop. ◆Communication protection When a single module unit fails to receive any signal from the wired controller, it will be shut down automatically and then the water pump will stop. ◆Phase loss/reversal protection When phase loss/reversal occurs, the power supply to the main board will be cut off. 3 CONTROLLER 3.1 Wired Controller This wired controller, especially designed for D series modular air-cooled chillers, is capable of controlling and displaying each running parameter of the chiller and being integrated into the remote monitoring system. 3.1.1 Press Buttons and Icons on the Homepage (1). Press Buttons NO. Name Function description 1 Power indicator(red) the indicator is on when the Wired Controller is powered on, or otherwise it is off. 2 Run indicator(green) the indicator is on when the Wired Controller is started, or otherwise it is off. 3 Error indicator(red) The indicator is on when the unit is at fault, or otherwise it is off. 4 On/Off button For controlling unit conversion between start and stop, press the button (for 3 seconds) in stop state to start the unit and press the button (for 3 seconds) in operation state to stop the unit. 5 Reset button Press the button to clear fault and relieve the air discharge temperature sensor locking. 6 Up selection button in menu selection, press the button to move the cursor upward or leftward; and in data modification mode, press the button to increase the value. 7 Down selection button In menu selection, press the button to move the cursor downward or rightward; and in data modification mode, press the button to decrease the value. 8 Exit button Press the button to go back to the previous menu. 9 Confirm button In menu selection, press the button to confirm the selected item; and in data modification mode, press the button to confirm the parameter and move the cursor. 10 LCD Information display zone. CONTROL 12
(2). Display Icons on the Homepage No. Icon Description 1 Time It indicates the current time. 2 Unit name It indicates the unit name. 3 Running mode It indicates the running mode (cooling, heating or manual defrosting) 4 On/Off mode It indicate the on/off mode, manual or timing) 5 Running status It indicates the running status, on or off. 6 Module quantity It indicates how many modules this system is consisted of. ( max. 16) D Series Modular Air-cooled Scroll Chillers Service Manual 13 CONTROL
D Series Modular Air-cooled Scroll Chillers Service Manual 3.1.2 Menu Structure of Controller CONTROL 14
3.2 Setup of Toggle Switches on the Motherboard Four bit toggle switches are used for indicating hardware address (1~16) of modules, with module No. displayed in turn on the panel as Module 1, Module 2, ……, Module 16. Toggle switches 1, 2, 3 and 4 are binary code, with 1 for the lowest bit and 4 for the highest bit. Comparison drawings are as follows (Caution: The DIP switch is allowed to be set only when the power supply is cut off and each setting shall be unique.): D Series Modular Air-cooled Scroll Chillers Service Manual 15 CONTROL
D Series Modular Air-cooled Scroll Chillers Service Manual INSTALLATION 16
NSTALLATION 1 BEFORE INSTALLATION ◆ ◆Please check the attached documents for the unit and accessories in accordance with the packing list. ◆ ◆Check the model and specification in accordance with attached documents. ◆ ◆Check the unit and accessories for damage ◆ ◆Check the refrigerant charge for leakage ◆ ◆Check the cleanliness of the water pipes. Do not remove the protective cap of the flange before connecting water pipes. ◆ ◆Check installation and operation for compliance with the required range. Through the check above, if there is any damage or problem, please contact the local sales office for help. Note that protective measures shall be taken after unpacked product has gone through all check and do not remove the package too early to avoid any unexpected damage to the product. 2 INSTALLATION LOCATION In order to guarantee the unit operates normally, installation shall be performed by the skilled serviceman with enough knowledge of refrigeration and air conditioning. Please read this manual carefully before instillation. ◆ ◆The unit shall be installed outdoor where there is good ventilation and capable of withstand the weight of the unit. ◆ ◆Enough space around the unit shall be left for ventilation, operation and service. ◆ ◆No obstacle is allowed above the unit. ◆ ◆The drainage ditch shall be prepared. 3 CAUTION FOR INSTALLATION ◆ ◆Ensure the connection pipe and power line both are routed correctly. ◆ ◆Noise and vibration levels shall be among the reliable range, rubber cushion shall be adopted. ◆ ◆The base must be constructed of cement or steel, which can bear the operation weight of the machine and has a level surface. ◆ ◆The installation location shall be free from fire, flammable matters, corrosive gas or waste gas. Enough ventilation space shall be left and measures should be taken to reduce noise and vibration as much as possible. 4 DIMENSION DATA (1). Graph for the shape and size for LSQWRF65M/NaD-M, LSQWRF80M/NaD-M Unit:mm D Series Modular Air-cooled Scroll Chillers Service Manual 17
D Series Modular Air-cooled Scroll Chillers Service Manual (2). Graph for the shape and size for LSQWRF130M/NaD-M Unit:mm (3). Graph for the shape and size for LSQWRF160M/NaD-M Unit:mm 403 339 2226 2026(Ground bolt 4-M12) 1617(Ground bolt 4-M12) 1676 18 2160 1650
5 MACHINE FOOTPRINT A minimum spacing of 1m should be left between any two modules for unobstructed air intake and equipment service. Additionally, a minimum of 2m should be kept between the chiller and any barrier. If allowable, it would be better to set up a suncover 3m ahead of the chiller. D Series Modular Air-cooled Scroll Chillers Service Manual Unit:mm 19
D Series Modular Air-cooled Scroll Chillers Service Manual 6 TYPICAL WATER PIPING DIAGRAM 20
7 FREEZE PROTECTION When the flow passage of the shell-and-tube heat exchanger is frozen up, it would cause serious damage to the heat exchanger, such as cracking and leakage which are out of warranty, therefore, the user should take measures stated below for freeze protection. ◆ ◆Under subzero conditions, it is necessary to shut down the chiller installed outdoor and then drain the evaporator completely. ◆ ◆Failure of the chilled water flow switch and the anti-freezing temperature sensor will cause the tube frozen up, so the flow switch shall be interlocked with the chiller. ◆ ◆When charging or recovering the refrigerant, the evaporator would crack because of frostbite provided the refrigerant pressure inside the evaporator is under 0.71MPa. Therefore, be sure to keep the water flow continually inside the evaporator or drain it completely. 8 ELECTRIC WIRING WORK 8.1 Wiring Principle ◆ ◆All wiring shall comply with applicable codes and engineering requirements. ◆ ◆All field wiring shall be performed by the qualified electrician. ◆ ◆Never perform wiring before the power supply is cut off. ◆ ◆Any damage caused by the improper external wiring shall be at the installer’s expense. WARNING: only copper conductor is allowed. (1). Power Cord Routing into the Electric Box ◆ ◆The power cord is wired into the internal electric box. ◆ ◆The power cord must be routed inside the conduit. ◆ ◆The power cord must enter the electric box through a rubber or plastic ring to avoid any damaged caused by the sharp edge of the metal sheet. ◆ ◆The power cord close to the electric box must be attached securely to prevent the terminal block of the electric box affected by the outside force. (2). Control Line ◆ ◆The field supplied control line shall be at a minimum 1mm 2. ◆ ◆What the flow switch receives is the DC low-voltage signals. The wiring of the flow switch shall not be parallel with the 50V or higher line. If inevitable, the hi-voltage and low-voltage signals must keep a distance of at least 150mm. ◆ ◆The electric box will send the control signal (220 AC, 5A) to control the chilled water pump and auxiliary electric heater, however, never do not drive them directly through the control signal but through their AC contactors. ◆ ◆A reasonable length of the control line should be left outside the unit and the rest should be bundled and fed into the electric box. 8.2 Wiring for Output Control Lines Note:The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module. D Series Modular Air-cooled Scroll Chillers Service Manual 21
D Series Modular Air-cooled Scroll Chillers Service Manual 8.3 Wiring between Chiller Modules 22
8.4 Specification of Power Cord and Air Switch Model Power Supply LSQWRF65M/NaD-M LSQWRF80M/NaD-M 25 16 16 80 380-415V,3Ph,50Hz LSQWRF130M/NaD-M 50 25 25 125 LSQWRF160M/NaD-M 70 35 35 160 Notes: a. The specifications of the breaker and power cable listed in the table above are determined based on the maximum power (maximum amps) of the unit. b. The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-wire copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable jacket) used at 40℃ and resistible to 90℃(see IEC60364-5-523:1999). If the working condition changes, they should be modified according to the related national standard. c. The specifications of the breaker listed in the table above are applied to the breaker with the working temperature at 40℃. If the working condition changes, they should be modified according to the related national standard. 8.5 Wiring of the Electric Control Cabinet D Series Modular Air-cooled Scroll Chillers Service Manual Min. sectional area of the power cable (mm 2) Capability of the Air Switch(A) Live Line Neutral Line Earth Line 16 16 16 63 23
D Series Modular Air-cooled Scroll Chillers Service Manual 8.6 WIRING DIADRAM (1). LSQWRF65M/NaD-M The diagram is only for reference and the circuit diagram attached on the unit prevails. 24
(2). LSQWRF80M/NaD-M The diagram is only for reference and the circuit diagram attached on the unit prevails. D Series Modular Air-cooled Scroll Chillers Service Manual 25
D Series Modular Air-cooled Scroll Chillers Service Manual (3). LSQWRF130M/NaD-M The diagram is only for reference and the circuit diagram attached on the unit prevails 26
(4). LSQWRF160M/NaD-M D Series Modular Air-cooled Scroll Chillers Service Manual 27
D Series Modular Air-cooled Scroll Chillers Service Manual MAINTENANCE 28
MAINTENANCE
1 ERROR LIST
Error
Rated Element
Protection Logic
High-pressure
High pressure
When the pressure is too high or the current exceeds the set point, the corresponding
compressor will stop and the indicating LED on the controll panel will light on and the error
information will be displayed on the error log which must be manually cleared for normal
operation of next time.
Compressor over-
protection
switch
Over-current
current protection
protector
When it is detected the low-pressure switch of the compressor is opened frequently, the
compressor will be shut down immediately. Meanwhile, the error information will be displayed
among the error log which must be manually cleared for normal operation of next time.
Low pressure
Low-pressure
protection
switch
Discharge
temperature
When it is detected in three consecutive seconds that the discharge temperature exceeds the
set point, the compressor will be shut down immediately. Meanwhile, the error information will be
displayed among the error log which must be manually cleared for normal operation of next time.
High discharge
protection
sensor
Fan over-
When a fan is over-current, the corresponding unit will be shut down. Meanwhile, the error
information will be displayed among the error log which must be manually cleared for normal
operation of next time.
Fan over-current
current
protector
protection
When an entering water temperature sensor fails, the compressor of the corresponding module
will be shut down immediately while the fan will still run for some time.
When a discharge temperature sensor fails, or the sensed discharge temperature is always
below the set point, the compressor of the corresponding module will be shut down immediately.
It can recover in three seconds but If the same case occurs more than three times, the system
will be locked until the system is unlocked and then it should be manually cleared for normal
operation of next time.
When the anti-freezing temperature sensor or the leaving water temperature sensor fails, it can
be automatically cleared as the temperature sensor automatically recover. But if the same case
occurs three times in one hour or the temperature sensor fails to recover, it should be manually
cleared for normal operation of next time. Meanwhile, the indicating LED on the controll panel will
light on and the error information will be displayed on the error log.
Temperature
sensor protection
Temperature
sensor
Water flow
switch protection
Contactor
When a single module detects its flow switch is closed, this module will automatically be shut
down. When all flow switches are closed, the water pump will stop.
Phase loss/
reversal protection
Phase
protector
When phase loss/reversal occurs, the phase protector will cut off the power supply to the main
board.
Communication
error
Main board
When the single module fails to receive signals from the controll panel, it will automatically be
shut off.
Error Codes
Error Name
Error Code
Jumper cap error
C5
High pressure protection
E1
Anti-freezing protection
E2
Low pressure protection
E3
High discharge temperature
E4
Compressor over-current
E5
Communication error
E6
Flow switch protection
EC
Superheating protection (unavailable for the cooling only unit)
Ed
Fan motor over-current protection
EF
Defrosting temperature sensor
d6
Ambient temperature sensor error
F3
Discharge temperature sensor error
F4
Anti-freezing temperature sensor error
d3
Entering water temperature sensor error
F8
Leaving water temperature sensor error
F9
Discharge temperature sensor error
dp
D Series Modular Air-cooled Scroll Chillers
Service Manual
29D Series Modular Air-cooled Scroll Chillers Service Manual 2 FLOW CHART OF TROUBLESHOOTING (1). High pressure protection 30
(2). Low pressure protection D Series Modular Air-cooled Scroll Chillers Service Manual 31
D Series Modular Air-cooled Scroll Chillers Service Manual (3). High discharge protection 32
(4). Compressor over-load protection (5). Phase protection D Series Modular Air-cooled Scroll Chillers Service Manual 33
D Series Modular Air-cooled Scroll Chillers Service Manual (6). Water flow switch protection (7). Temperature sensor error 34
3 REMOVALS AND REINSTALLATION 3.1 MAIN PARTS Appearance Name Function D Series Modular Air-cooled Scroll Chillers Service Manual It drives the refrigerant cycle and turns the low- temperature, low pressure refrigerant vapor into high- temperature, high-pressure vapor. Compressor Accumulator It is used to separate oil and refrigerant liquid from the refrigerant vapor. 4-way Valve It is used to shift the direction of the refrigerant flow to realize either cooling or heating. In the cooling mode, it is used to absorb heat and evaporate the liquid refrigerant In the heating mode, it is used to release heat and condense the refrigerant vapor. Shell-and- tube heat exchanger In the cooling mode, it is used to absorb heat and evaporate the liquid refrigerant In the heating mode, it is used to release heat and condense the refrigerant vapor. Fintube heat exchanger Electronic expansion It is used to regulate the flow rate of the refrigerant to make it perfectly match with the load in need. valve 35
D Series Modular Air-cooled Scroll Chillers Service Manual 3.2 Removal and Installation of Main Parts Compressor (These steps listed below are applicable to the dual-system unit. For the four-system unit, please first remove the electric boxes of two compressors in between and then follow the steps below. ) Note: Be sure there is no refrigerant in the pipeline system and the power supply is cut off. Steps Graphic Reprentation Instructions 1. Remove the panel Remove the panel here 2. Remove the power cord and drain pipe Remove the drain pipe Open the cover and remove the power cord 3. Separate the compressor from the pipeline system Soldering spot 36 ◆ ◆Loosen screws around the panel with a screwdriver. ◆ ◆Remove the panel. ◆ ◆Collect the screws in case of loss. ◆ ◆Place the panel in the right place to avoid inadvertent damage. ◆ ◆Loosen screws for the power cord with a screwdriver. ◆ ◆Draw out the power cord. ◆ ◆Remove the crankcase heater, if applicable. ◆ ◆Remove the drain pipe. Note: when removing the power cord, mark the color of the power cord and the code of the wring terminal to avoid misconnection. ◆ ◆Unbraze the brazing spots of the pipeline as quick as possible. ◆ ◆Minimize damage on the compressor for further analysis.
4. Loose screws at the base of the compressor 5. Replace the compressor 6 Connect the pipeline and power cord Note: after the compressor is replaced, most amount of oil will still remain in the system, which will not affect the reliability of the newly installed compressor but will increase the running resistance to the rotor and increase electricity consumption. Therefore, a valve should be installed at the lower part of the inlet of the suction line to discharge excessive oil. After installing the valve, start the compressor for ten minutes and then open this valve until all oil flows out completely. Do it twice to guarantee the oil keeps at the normal level. D Series Modular Air-cooled Scroll Chillers Service Manual ◆ ◆Remove screws with an adjustable wrench or a socket wrench. ◆ ◆Collect screws in case of loss. Remove four screws at the base ◆ ◆Remove the compressor and do not damage the rubber pad. ◆ ◆Package the removed compressor to prevent moisture entering. ◆ ◆Place a new compressor at the base. ◆ ◆Tighten screws. ◆ ◆Connect the suction and discharge lines to the compressor by brazing. Note that nitrogen shall be charged during brazing. ◆ ◆After brazing, use high-pressure nitrogen for leakage test. ◆ ◆Energize the unit and manually close the AC contactor of the compressor to let the compressor run for 2~3 seconds. ◆ ◆When the compressor runs reversely, sharp sound will generates. Wire the power cord 37
D Series Modular Air-cooled Scroll Chillers Service Manual 4-way Valve Note: Be sure to cut off the power supply and recover the refrigerant firstly Steps Graphic Representation Instructions 1. Record the installation direction of the 4-way valve 四通阀 4-way valve 2. Clean the system, replace the 4-way valve and reconnect the pipeline as before Remove the 4-way valve and clean the system 3. Vacuum the system and charge refrigerant again 38 ◆ ◆Remember the installation direction of the 4-way valve before removal. ◆ ◆Remove the coil. ◆ ◆Wrap the 4-way valve prior to unbrazing to prevent it from being damaged and use it for future analysis. ◆ ◆Unbraze the 4-way valve. ◆ ◆Replace the 4-way valve with the same model, or that approved by the qualified technician. ◆ ◆Wrap the 4-way valve with wet cloth. ◆ ◆Reconnect the connection pipe as before. ◆ ◆Braze the pipeline. ◆ ◆Charge nitroge when unbrazing. ◆ ◆Vacuum the system until the pressure goes as low as -1.0bar. ◆ ◆The refrigerant charge and quality shall comply with the specification on the nameplate.
Note: Be sure to recover the refrigerant, prepare proper devices and tools and keep a good ventilation. Steps Graphic Representation Instructions 1. Remove the panel as shown in the right figure 2. Disconnect the connection pipe of the accumulator 3. Remove the 4-way valve assembly if necessary D Series Modular Air-cooled Scroll Chillers Service Manual Accumulator ◆ ◆Remove the panel as shown in the left figure with a screwdriver. panels ◆ ◆Unbrazer the connection pipe of the accumulator. accumulator ◆ ◆Unbraze the 4-way valve assembly. 4-way valve assemly 39
D Series Modular Air-cooled Scroll Chillers Service Manual 4. Remove the bolts at the base 5. Remove the accumulator. 6. Purge the system by charging nitrogen 40 ◆ ◆Remove bolts at the base with a wrench. 底座螺栓 Bolts ◆ ◆Remove the accumulator ◆ ◆Connect the pipeline of the accumulator with the nitrogen tank and adhesive tape can is allowed to be used for the large- sized pipeline. ◆ ◆Purge the system by charging nitrogen. Connect the accumulator with the nitrogen tank
7. Check if oil needs to be added Drill a hole close to the bottom 8. Add oil if necessary Charge oil here 9. Reconnect the connection pipe of the accumulator and vacuum the system and then charge refrigerant again D Series Modular Air-cooled Scroll Chillers Service Manual ◆ ◆Tilt the accumulator and then drill a hole close to the bottom and then pour the oil inside the accumulator to a prepared container. ◆ ◆Charge oil to the accumulator prior to brazing. ◆ ◆Charge nitrogen when brazing. ◆ ◆Vacuum the system until the pressure goes as low as -1.0bar. ◆ ◆The refrigerant charge and quality shall comply with the specification on the nameplate. 41
D Series Modular Air-cooled Scroll Chillers Service Manual Shell-and-tube Heat Exchanger Note: Check the water system and be sure the shell-and-tube heat exchanger shall be replaced. And then cut off the power and recover the refrigerant. Steps Graphic Representation Instructions 1. Remove the panel as shown in the right figure 2. Loosen the pipeline connectors and remove the panel outside of the heat exchanger 盲塞 Blind plug 3. Unbraze the pipeline connecting the heat exchanger. (Different heat exchangers vary in structure so it is better to remember the piping location to prevent misconnection 42 ◆ ◆Remove four panels around the heat exchanger and the frame in front of the blind plug. ◆ ◆Remove the pipeline ◆ ◆Remove the metal sheets located underside with a screwdriver. ◆ ◆Loosen the blind plug and drain the water inside the pipeline. ◆ ◆Wrap the cooper pipe with wet cloth. ◆ ◆Unbraze the pipelines connecting the heat exchanger.
4. Loosen four screws fixing the heat exchanger 5. Remove the shell-and- tube heat exchanger 6. Place a new heat exchanger and connect the pipeline and then vacuum the system and lastly charge refrigerant D Series Modular Air-cooled Scroll Chillers Service Manual ◆ ◆Loosen four screws fixing the heat exchanger with a screwdriver. Screws ◆ ◆Remove the shell-and-tube heat exchanger. ◆ ◆Replac the heat exchanger with the same model. ◆ ◆Wrap the cooper pipe with wet cloth and braze the pipeline. ◆ ◆Vacuum the system until the pressure goes as low as -1.0bar. ◆ ◆The refrigerant charge and quality shall comply with the specification on the nameplate. ◆ ◆Connect the water pipeline. ◆ ◆Put the metal sheets back. 43
D Series Modular Air-cooled Scroll Chillers Service Manual Steps Graphic Representation nstructions 1. Remove the panel as shown in the right figure 2. Remove the guard cover 3. Remove the fan blades 44 Fan Note: Be sure to cut off the power supply firstly ◆ ◆Remove the panel as shown in the left figure. ◆ ◆Remove the guard cover with a wrench. ◆ ◆Remove the fan blades with a screwdriver.
4. Remove the motor ◆ ◆Remove the motor with a wrench. 5. Remove the frame 6. Reinstall the fan assembly D Series Modular Air-cooled Scroll Chillers Service Manual ◆ ◆Remove the frame. Frame ◆ ◆Reinstallation sequence: 1. frame; 2. motor; 3. fan blades; 4. guard cover; 5. panel. 45
D Series Modular Air-cooled Scroll Chillers Service Manual Fintube Heat Exchanger Note: Be sure to cut off the power supply and recover the refrigerant firstly. Steps Graphic Representation Instructions 1. Remove the panel as shown the right figure 2. Unbraze the inlet/ outlet pipeline of the heat exchanger. Do not damage the fins and metal sheets during unbrazing Brazing spot 3. Remove the frame of the header and screws and bolts on the heat exchanger Frame 46 ◆ ◆Recover refrierant completly. ◆ ◆Cut off the power supply. ◆ ◆Remove the fan assembly and draw out the power cord of the fan motor and then remove the metal sheets outside the condenser. Note: remember the wiring sequence of the fan motor. ◆ ◆Unbraze the pipeline of the condenser. ◆ ◆Remove the frame of the header with a wrench. ◆ ◆Remove screws and bolts on the heat exchanger.
4. Place a new heat exchanger and vacuum the system and then charge refrigerant and lastly put the fan and metal sheets back Note: check the refrigeration system and be sure the electronic expansion valve shall be replaced, and then cut off the power supply and recover the refrigerant. Steps Graphic Representation Instructions 1. Recover the refrigerant and remove the panel 2. Remove the electronic expansion valve coil. D Series Modular Air-cooled Scroll Chillers Service Manual ◆ ◆Install a new heat exchanger. ◆ ◆Braze the pipeline. ◆ ◆Vacuum the system until the pressure is as low as -1.0bar. ◆ ◆The refrigerant charge and quality shall comply with the specification on the nameplate. Take care to the wiring sequence when rewiring the fan motor. Electornic Expansion Valve ◆ ◆Cut off the power supply ◆ ◆Recover the refrigerant. ◆ ◆Remove the panel. Electronic expansion valve ◆ ◆Wrap the valve with wet close to prevent the slide block from being burnt down and never the let water flow into the pipeline. Coil 47
D Series Modular Air-cooled Scroll Chillers Service Manual 3 Remove the connection pipe of the electronic expansion valve 4. Remove the electronic expansion valve 5. Place a new electronic expansion valve 48 ◆ ◆Unbraze the electronic expansion valve ◆ ◆Charge nitrogen during brazing. ◆ ◆Take care to prevent surrounding item from being burnt down owing to high temperature during brazing. ◆ ◆Remove the electronic expansion valve. ◆ ◆Braze each pipeline. ◆ ◆Charge nitrogen during brazing. ◆ ◆Take care to prevent surrounding item from being burnt down owing to high temperature during brazing.
6. Reinstall the electronic expansion valve coil and vacuum the system and then charge refrigerant and lastly put the panel back 4 ROUTINE MAINTENANCE Routine maintenance shall be performed by the skilled and qualified servicemen. (1). Refrigerant Leakage Suds is usually used for the leakage test by applying it at the spot (soldering spots, valve pistols, connectors) where leakage is probably to occur. During the test, if soap bubbles pop up, it indicates leakage exists and repair is required. If suds fails to work, a electronic leakage detectors is a alternative. Refrigerant charge can be checked by measuring the suction and discharge pressure. Leakage test should be performed wherever leakage occurs or some components of the refrigeration system are replaced. There are two difference conditions for charging refrigeration stated as below. ◆Complete charging In this case, take a leakage test by charging hi-pressure nitrogen (15~20kg) or refrigerant into the system. If soldering is required, note that gas inside the system must be expelled firstly. The whole system must be dried and vacuumed prior to charging. a. Connect the manifold gage. b. Vacuum the system with a vacuum pump. Step 1: Expel the hi-pressure nitrogen for leakage test. Step 2: Connect the pipeline at both the high and low pressure sides of the manifold gage as shown in the figure below. Note that vacuuming shall be taken at both sides. The degree of vacuum will refer to the reading of the manometer at the low side. D Series Modular Air-cooled Scroll Chillers Service Manual ◆ ◆The coil shall be matched with the valve body exactly. ◆ ◆The degree of vacuum shall be kept as low as -1.0 bar. ◆ ◆The refrigerant charge and quality shall comply with the specification on the nameplate. ◆ ◆After replace the electronic expansion valve, energize the unit again. ◆ ◆Reinstall the panel. Hi-pressure gage Low-pressure gage Manifold gage Vacuum pump Pipeline Pipeline Pipeline 49
D Series Modular Air-cooled Scroll Chillers Service Manual Step 3: Open the valves at both the high-pressure and low-pressure sides and then start the vacuum pump until the gage reading is below -1bar. After that, let the vacuum pump lasts for another 0.5~1.0 hour. Step 4: Close the valves and stop the vacuum pump. Note that only the valves have been closed can the vacuum pump be stopped, otherwise air is possible to go into the system again. Step 5: Take the leakage test. Be sure the vacuumed system keeps a pressure no higher than 80Pa and keeps little pressure rise in half an hour. c. Refrigerant charging starts after the degree of vacuum reaches the expected range and lasts for 30 minutes. The amount of refrigerant charge shall comply with that specified on the nameplate or product data sheet. ◆Adding Refrigerant charge is determined through stringent tests, as excess or shortage of refrigerant would cause the compressor to run improperly. Thus, the refrigerant charge shall be consistent with that specified on the nameplate. If refrigerant charge is indeed insufficient, follow the steps below for adding. Step 1: Weigh the refrigerant tank with an electronic scale and connect the refrigerant tank with the pressure gage through the pipeline. Step 2: Expel the air inside the pipeline. Firstly half open the shutoff valve of the refrigerant tank and then loosen the connector connecting the pressure gage to expel the air until the connector hisses for five seconds and then tighten the connector. Step 3: Return the electric scale to zero by energizing it again. Step 4: Open all valves between the refrigerant tank and the unit to charge refrigerant as per the amount specified on the nameplate. Excessive refrigerant would dilute oil while insufficient refrigerant would lower the refrigeration capability and result in poor lubrication and high discharge temperature etc. Note that only refrigerant vapor can be charged into the system at the low-pressure side when the unit is in operation. However, it is highly recommended to charge refrigerant at the hi-pressure side when the unit is shut down, otherwise it would cause slugging during startup. (2). Air Purge Prior to refrigerant charging, it is imperative to expel air inside the system and the system must be vacuumed. a. Connect the manifold gage. b. Vacuum the system with a vacuum pump. c. Charge refrigerant at the low-pressure side as per the amount specified on the nameplate or product data sheet when the degree of vacuum appro aches the expected range. d. The refrigerant charge will be affected by the ambient temperature. When the charge is under the required amount, it is allowed to add refrigerant vapor after starting the water pump and the unit. 50 Low-pressure gage Hi-pressure gage Manifold gage Refrigerant charge Pipeline Pipeline
5 EXPLODED VIEWS AND PART LIST (1). Model: LSQWRF65M/NaD-M D Series Modular Air-cooled Scroll Chillers Service Manual 51
D Series Modular Air-cooled Scroll Chillers Service Manual Parts List: LSQWRF65M/NaD-M for EL01500500 No. Name of part Part code 1 Electric Expand Valve Fitting 4304413214 2 Strainer 07210037 3 Magnet Coil 4300040064 4 Filter 07218603 5 Condenser Assy 0112110001001 6 Rear Panel 0154110000101P 7 Sensor Sub-assy 39008000004G 8 One Way Valve 0733420001 9 pipe connector 06128301 10 Pressure Protect Switch 4602001570 11 Pressure Protect Switch 4602001579 12 Pressure Protect Switch 4602001582 13 Dry Evaporator 0105887701 14 Base Frame Assy 01281100012P 15 Steam current Switch 45028209 16 Gas-liquid Separator 07424148 17 Electrical Heater 76515211 18 Pressure Protect Switch 4602001569 19 Pressure Protect Switch 4602001581 20 Compressor 00201100002 21 Pressure Protect Switch 4602001583 22 Compressor Gasket 02118049 23 Electronic Expansion Valve 07331139 24 Electric Expand Valve Fitting 4304413213 25 Magnet Coil 4300040048 26 4-way Valve 43000339 27 Front Panel 01541100003P 28 Front Panel 01541100002P 29 Streamlined Dome 22265801 30 Centrifugal Fan 10355801 31 Fan Motor 1570110000101 32 Electric Box Assy 01391100045 33 Terminal Board 42018452 34 Terminal Board 42011135 35 Over Current Protector 46028000011 36 Terminal Board 420102471 37 Phase Reverse Protector 32214101 38 Single-phase Air Switch 45020203 39 AC Contactor 44010235 40 AC Contactor 44010229 41 Main Board 30222000002 52
(2). Model: LSQWRF80M/NaD-M D Series Modular Air-cooled Scroll Chillers Service Manual 53
D Series Modular Air-cooled Scroll Chillers Service Manual Parts List: LSQWRF80M/NaD-M for EL01500520 No. Name of part Part code 1 Electric Expand Valve Fitting 4304413213 2 Electronic Expansion Valve 07331139 3 Magnet Coil 4300040064 4 4-way Valve 43000412 5 Filter 07414118 6 Pressure Protect Switch 4602001570 7 Pressure Protect Switch 4602001582 8 Pressure Protect Switch 4602001579 9 Rear Panel 01541100001P 10 One Way Valve 0733420001 11 Sensor Sub-assy 39008000004G 12 pipe connector 06128301 13 Compressor 00201100004 14 Dry Evaporator 01058800057 15 Steam current Switch 45028209 16 Gas-liquid Separator 07421111 17 Compressor Gasket 02118049 18 Electrical Heater 76515211 19 Pressure Protect Switch 4602001583 20 Pressure Protect Switch 4602001581 21 Pressure Protect Switch 4602001569 22 Strainer 07210037 23 Electric Expand Valve Fitting 4304413214 24 Magnet Coil 4300040048 25 Condenser Assy 01121100020 26 Front Panel 01541100003P 27 Front Panel 01541100002P 28 Streamlined Dome 22265801 29 Centrifugal Fan 10355801 30 Fan Motor 15701100003 31 Electric Box Assy 01391100061 32 Terminal Board 42018452 33 AC Contactor 44010229 34 Terminal Board 42011135 35 Single-phase Air Switch 45020203 36 Terminal Board 420102471 37 AC Contactor 44010240 38 Phase Reverse Protector 32214101 39 Over Current Protector 46028000010 40 Main Board 30222000002 54
(3). Model: LSQWRF130M/NaD-M D Series Modular Air-cooled Scroll Chillers Service Manual 55
D Series Modular Air-cooled Scroll Chillers Service Manual Parts List: LSQWRF130M/NaD-M for EL01500510 No. Name of part Part code 1 Rear Grill 01571100001 2 Condenser Assy 1 0112110001101 3 Lower panel 01541100005P 4 4-way Valve 43000339 5 Electric Expand Valve Fitting 4304413214 6 Filter 07218603 7 Electronic Expansion Valve 07331139 8 Condenser Assy 2 0112110001201 9 Lower panel 01541100006P 10 Lower panel 01541100007P 11 Sensor Sub-assy 39008000003G 12 One Way Valve 07332224 13 Chassis Sub-assy 01191100004P 14 Dry Evaporator 01058800013 15 Pressure Protect Switch 4602001570 16 Pressure Protect Switch 4602001584 17 Pressure Protect Switch 4602001585 18 Steam current Switch 45028209 19 Compressor 00201100002 20 Gas-liquid Separator 07424148 21 Compressor Gasket 02118049 22 Pressure Protect Switch 4602001582 23 Pressure Protect Switch 4602001579 24 Electrical Heater 76515211 25 pipe connector 06128301 26 Pressure Protect Switch 4602001547 27 Strainer 07210037 28 Electric Expand Valve Fitting 4304413213 29 Magnet Coil 4300040048 30 Magnet Coil 4300040049 31 Lower panel 01541100004P 32 Side Plate 01311100006P 33 Streamlined Dome 22265801 34 Centrifugal Fan 10355801 35 Fan Motor 15701100001 36 Terminal Board 420111251 37 AC Contactor 44010235 38 Terminal Board 42010247 39 Terminal Board 42010254 40 Terminal Board 42011135 41 Over Current Protector 46028000011 42 Terminal Board 42018452 43 Main Board 30222000002 44 Electric Box Assy 01391100047 45 AC Contactor 44010229 46 Single-phase Air Switch 45020203 47 Phase Reverse Protector 32214101 56
(4). Model: LSQWRF160M/NaD-M D Series Modular Air-cooled Scroll Chillers Service Manual 57
D Series Modular Air-cooled Scroll Chillers Service Manual Parts List: LSQWRF160M/NaD-M for EL01500530 No. Name of part Part code 1 Condenser assy 2 0112110002501 2 Rear Grill 01571100001 3 Electric Expand Valve Fitting 4304413213 4 Magnet Coil 4300040049 5 4-Way Valve 43000412 6 Electronic Expansion Valve 07331139 7 Filter 07414118 8 Pressure Protect Switch 4602001570 9 Condenser assy 1 0112110002601 10 Lower Panel 3 01541100082P 11 Lower Panel 4 01541100047P 12 Sensor Sub-assy 39008000046G 13 One Way Valve 0733420001 14 Pressure Protect Switch 4602001579 15 Pressure Protect Switch 4602001582 16 Dry Evaporator 01058800064 17 Gas-liquid Separator 07421111 18 Pressure Protect Switch 4602001591 19 Pressure Protect Switch 4602001590 20 Steam current Switch 45028209 21 Pressure Protect Switch 4602001583 22 Electrical Heater 76515211 23 Pressure Protect Switch 4602001581 24 Compressor 00201100004 25 Compressor Gasket 02118049 26 Chassis Sub-assy 01191100011P 27 pipe connector 06128301 28 Pressure Protect Switch 4602001569 29 Strainer 07210037 30 Lower Panel 01541100067P 31 Pressure Protect Switch 4602001589 32 Electric Expand Valve Fitting 4304413214 33 Magnet Coil 4300040048 34 Handle 26235253 35 Lower Panel 1 01541100053P 36 Side Plate 01311100006P 37 Scram switch 45010024 38 Streamlined Dome 22265801 39 Fan Motor 15701100003 40 Centrifugal Fan 10355801 41 Fan Motor 1570110000301 42 Terminal Board 420111251 43 Electric Cabinet Assy 01391100069 44 Terminal Board 42010254 45 Terminal Board 42010247 46 Terminal Board 42011135 47 AC Contactor 44010229 48 Terminal Board 42018452 49 Main Board 30222000002 50 AC Contactor 44010240 51 Phase Reverse Protector 32214101 52 Single-phase Air Switch 45020203 53 Over Current Protector 46028000008 58
For continuous improvement in the products, Gree reserves the right to modify the product specification and appearance in this manual without notice and without incurring any obligations.