Owner's Manual 

Original Instructions 
Commercial Air Conditioners 

 
Multi Variable Air Conditioners 
Two-way Cassette Type Indoor Unit 
 

Models: 

GMV-ND09TS/A-T(U) 

GMV-ND12TS/A-T(U) 

GMV-ND15TS/A-T(U) 

GMV-ND18TS/A-T(U) 

GMV-ND24TS/A-T(U) 

Sayfa 2

Preface 
For correct installation and operation, please read all instructions carefully. Before reading 

the instructions, please be aware of the following items: 

This is the safety alert symbol. It is used to alert you to potential personal injury 
hazards. Obey all safety messages that follow this symbol to avoid possible injury or 
death. 
WARNING 

This mark indicates procedures which, if improperly performed, might lead to the death 
or serious injury of the user. 
CAUTION 

This mark indicates procedures which, if improperly performed, might possibly result in 
personal harm to the user, or damage to property. 

 
NOTICE is used to address practices not related to personal injury. 

(1) Instructions for installation and use of this product are provided by the manufacturer.  

(2) Installation must be performed in accordance with the requirements of NEC and CEC by authorized personnel 

only. 

(3) For the safe operation of this unit, please read and follow the instructions carefully. 

(4) During operation, total capacity of indoor units should not exceed the total capacity of outdoor units. Otherwise, 

poor effect of cooling or heating may result. 

(5) Direct operators or maintainers should well keep this manual. 

(6) If this unit fails to operate normally, please contact our service center as soon as possible and provide the 

following information:     

1) Content on the nameplate (model number, cooling capacity, production code, ex-factory date. 
2) Malfunction details (before and after the malfunction occurs. 

(7) Each unit has been strictly tested and proved to be qualified before ex-factory. In order to prevent units from being 

damaged or operating normally because of improper disassembly, please do not disassemble the unit by yourself. 
If you need to disassemble and check units, please contact our service center. We will send specialists to guide 
the disassembly. 

(8) Under the standby status, the unit will consume a little power for ensuring reliability of complete unit, maintaining 

normal communication and preheating refrigerant. When the unit won’t be used for a long time, cut off the power 
of the complete unit. However, please preheat it when operating the unit next time. 

(9) All graphics in this manual is only for your reference. For sales or production reasons, these graphics are subject 

to change by manufacturer without prior notice. 

(10) These instructions shall also be available in an alternative format, e.g. on a website. 

User Notice 
● This appliance can be used by children aged from 8 years and above and persons with 

reduced physical, sensory or mental capabilities or lack of experience and knowledge if they 
have been given supervision or instruction concerning use of the appliance in a safe way and 

understand the hazards involved. Children shall not play with the appliance. Cleaning and user 

maintenance shall not be made by children without supervision. 

● DISPOSAL: Do not dispose this product as unsorted municipal waste. 

Collection of such waste separately for special treatment is necessary. 

WARNING 

Sayfa 3

Manufacturer will bear no responsibilities when personal injury or property loss is caused 
by the following reasons: 

(1) Damage the product due to improper use or misuse of the product; 

(2) Alter, change, maintain or use the product with other equipment without abiding by the 

instruction manual of manufacturer; 

(3) After verification, the defect of product is directly caused by corrosive gas; 

(4) After verification, defects are due to improper operation during transportation of 

product; 

(5) Operate, repair, maintain the unit without abiding by instruction manual or related 

regulations; 

(6) After verification, the problem or dispute is caused by the quality specification or 

performance of parts and components that produced by other manufacturers; 

(7) The damage is caused by natural calamities, bad using environment or force majeure. 

Exception Clauses 

Sayfa 4

1 Safety Precautions······························································· 1 

2 Product Introduction ····························································· 2 

2.1 Names of Key Components··················································· 2 

2.2 Rated Working Condition ····················································· 2 

3 Preparations for Installation ··················································· 2 

3.1 Standard Fittings ······························································· 2 

3.2 Installation Position Selection ················································ 3 

3.3 Requirements of communication wire selection···························· 4 

3.4 Wiring Requirements ·························································· 6 

4 Installation Instructions ························································· 6 

4.1 Installation of Indoor Unit ····················································· 6 

4.2 Refrigerant Pipe Connection ················································· 8 

4.3 Drainage Pipe Installation and Drainage System Testing················· 9 

4.4 Panel installation······························································ 12 

4.5 Installation of Wired Controller ·············································· 13 

5 Wiring Work ······································································14 

5.1 Connection of Wire and Patch Board Terminal ···························· 14 

5.2 Power Cord Connection ······················································ 15 

5.3 Connection of Communication Wire between Indoor Unit and Outdoor 
Unit (or indoor unit) ···································································· 15 

5.4 Connection of Communication Wire for Wired Controller ················ 16 

5.5 Wiring Instructions of Wired Controller and Indoor Units Network ····· 16 

6 Routine Maintenance ···························································18 

6.1 Cleaning of Filter······························································ 18 

6.2 Maintenance before the Seasonal Use····································· 18 

6.3 Maintenance after the Seasonal Use ······································· 18 

7 Table of Error Codes for Indoor Unit ········································19 

8 Display of Light Board··························································19 

9 Troubleshooting ·································································20 
 

Contents 

Sayfa 5

1 Safety Precautions  

(1) This product can’t be installed at corrosive, inflammable or explosive environment or the place with 

special requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service 
life of the unit, or even cause fire hazard or serious injury. As for above special places, please adopt 
special air conditioner with anti-corrosive or anti-explosion function. 

(2) Follow this instruction to complete the installation work. Please carefully read this manual before unit 

startup and service. 

(3) Wire size of power cord should be large enough. The damaged power cord and connection wire should 

be replaced by exclusive cable.  

(4) After connecting the power cord, please fix the electric box cover properly in order to avoid accident.  

(5) Never fail to comply with the nitrigen charge requirements. Charge nitrogen when welding pipes.  

(6) Never short-circiut or cancel the pressure switch to prevent unit damage.  

(7) Please firstly connect the wired controller before energization, otherwise wired controller can not be 

used.  

(8) Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant 

leakage, electric shock, or fire etc.  

(9) Do not insert fingers or objects into air outlet/inlet grille.  

(10) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the 

gas/oil supplied heating equipment is used.  

(11) Never start up or shut off the air conditioner by means of directly plug or unplug the power cord.  

(12) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor. 

(13) Do not allow children operate this unit.  

(14) Do not operate this unit with wet hands.  

(15) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury 

may happen.  

(16) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen.  

(17) Do not expose the unit to the moist or corrosive circumstances.  

(18) Under cooling mode, please don't set the room temperature too low and keep the temperature 

difference between indoor and outdoor unit within 5°C (41°F).  

(19) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please 

contact Gree appointed service center for help.  

(20) Before installation, please check if the power supply is in accordance with the requirements specified on 

the nameplate. And also take care of the power safety.  

(21) Installation should be conducted by dealer or qualified personnel. Please do not attempt to install the 

unit by yourself. Improper handling may result in water leakage, electric shock or fire disaster etc.. 

(22) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire 

accidents.  

(23) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid 

electric shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone 
line.  

(24) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off 

the power when 24 hours short-time halting (to protect the compressor).  

(25) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will 

emerge if the refrigerant gas meets fire.  

(26) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little 

neutral detergent to clean the outer casing of unit.  

(27) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main 

power supply, and then immerdiately contact Gree appointed service center. If abnormality keeps going, 
the unit might be damaged and lead to electric shock or fire.  

Any personal injury or property loss caused by improper installation, improper debug, and 

unnecessary repair or not following the instructions of this manual should not be the 

responsibility of Gree Electric Appliances, Inc. of Zhuhai. 

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

WARNING 

1 

Sayfa 6

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

2 Product Introduction 

2.1 Names of Key Components 

Fig. 2.1.1 

No. 
① 
② 
③ 
④ 
⑤ 
⑥ 
⑦ 

Air Inlet 
Grille (With 

Name 
Drainage 

Connection 

Drainage 

Main Unit 
Louver 
Panel 

Pipe 

Pipe 

Device 

Filter) 

2.2 Rated Working Condition 

Indoor Side Condition 
Outdoor Side Condition 

Dry Bulb Temp 

Wet Bulb Temp  

Dry Bulb Temp  

Wet Bulb Temp  

 °C(℉) 

°C(℉) 

°C(℉) 

°C(℉) 

Rated Cooling 
26.7(80.0) 
19.4(67.0) 
35(95.0) 
23.9(75.0) 

Rated Heating 
21.1(70.0) 
15.6(60.0) 
8.3(47.0) 
6.1(43.0) 
 
3 Preparations for Installation 

NOTICE!  

Product graphics are only for reference. Please refer to actual products. Unspecified 

measure unit is mm (in.) 

3.1 Standard Fittings 

Use the following provided accessories according to the requirement. 

No. 
Name 
Appearance 
Q'ty 
Usage 

1 
Drainage hose assembly 
 
1 
To connect the drainage pipe 

 
2 
GMV-ND09~15TS/A-T(U) 

2 
Special Nut 

 
1 
GMV-ND18~24TS/A-T(U) 

3 
corrugated pipe 
 
1 
GMV-ND18~24TS/A-T(U) 

4 
Insulation 
 
1 
To insulate the gas pipe 

5 
Insulation  
 
1 
To insulate the liquid pipe 

2 

Sayfa 7

No. 
Name 
Appearance 
Q'ty 
Usage 

6 
Sponge 
 
1 
To insulate the drain pipe 

7 
Fastener  
 
4 
To fasten the sponge 

8 
paper pattern for 

installation 
 
1 
Locate the drill hole on ceiling 

9 
Tapping screw with 

washer 
 
4 
Fix paper pattern 

10 
M10 Washer 
 
10 
To be used together with the 
hanger bolt for installing the unit 

11 
Washer fixing plate 
 
4 
Prevent the washer from falling off 

12 
Remote controller 
 
1+2 
To control the indoor unit 

13 
Remote controller holder 
 
1 
Used for holding the remote 
controller 

14 
Tapping screw 
 
2 
Used for fixing the remote 
controller holder 

3.2 Installation Position Selection 

(1) The appliance shall not be installed in the laundry. 

(2) The top holder must be strong enough to support unit’s weight. 

(3) Drain pipe can drain water out easily. 

(4) There is no obstacle at inlet or outlet. Please ensure good air circulation. 

(5) In order to make sure the space for maintenance, please install the indoor unit according 

to the dimension described below. 

(6) Keep the unit away from heating source, inflammable gas or smoke. 

(7) This is a concealed ceiling type unit. 

(8) Indoor unit, outdoor unit, power cord and electric wire should stay at least 1m (39-3/8 

in.) from the TV set and radio. Otherwise, these electrical appliances may have image 

interference and noise. (Even if the distance is 1m (39-3/8 in.), when there is strong 

electric wave, noise may still occur). 

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

3 

Sayfa 8

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

(1) The unit shall be installed in accordance with national standards or local regulations. 

(2) Only qualified personnel can carry out installation work, please contact with local dealer before 

installation. 

(3) Make sure all the installation work completed before energizing. 

3.3 Requirements of communication wire selection 

NOTICE!  

If the unit is installed in the place with strong electromagnetic interference, shielded wire 

must be applied on the communication wire between indoor unit and wired controller. Twisted 

pair line with shielding function must be applied on the communication wire between indoor unit 

and indoor unit (outdoor unit).   

3.3.1 Selection of Communication Wire between Indoor Unit and Wired 
Controller 

Unit: mm (in) 

Fig. 3.2.1 

Fig. 3.3.1 

4 

Sayfa 9

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

Total length of 
communication wire 

Wire diameter (AWG) 
Wire 
standard 
Remark 

Wire type 

between indoor unit 
and wired controller 

(m/ft.) 

1. Total length of 
communication line can't 
exceed 250m (820-1/5ft.). 
2. The cord shall be Circular 
cord (the cores shall be 
twisted together). 
3. If unit is installed in 
places with intense 
magnetic field or strong 
interference, it is 
necessary to use shielded 
wire. 

Light/Ordinary 

polyvinyl 
chloride 
sheathed cord. 

L≤250m 
(L≤820-1/5ft.) 

2×0.75~2×1.25 
(2×AWG18~2×AWG16) 

IEC 
60227-5 

(60227 IEC 52 
/60227 IEC 53) 

3.3.2 Selection of communication wire between indoor unit and indoor unit (or 
outdoor unit) 

Fig. 3.3.2 

Total length of 
communication wire 

Wire diameter 

Wire type 

between indoor unit 

(AWG) 
Wire standard 
Remark 

and indoor unit 
(outdoor unit) (m/ft.) 

1. If the wire diameter is 
enlarged to 2×1 mm 2 
(2×AWG16), the total 
communication line length 
can reach 1500 m (4921-
1/4ft.).  
2. The cord shall be Circular 
cord (the cores shall be 
twisted together). 
3. If unit is installed in places 
with intense magnetic field 
or strong interference, it is 
necessary to use shielded 
wire. 

Light/Ordinary 
polyvinyl chloride 

L≤1000m 
(L≤3280-5/6ft.) 

≥2×0.75 
(≥2×AWG18) 
IEC 60227-5 

sheathed cord. 

(60227 IEC 52 
/60227 IEC 53) 

5 

Sayfa 10

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

3.4 Wiring Requirements 

Power Cord Size and Air Switch Capacity 

Model 
Power Supply 
MCA(A) 
MOP(A) 

GMV-ND09TS/A-T(U) 

1 
15 

GMV-ND12TS/A-T(U) 
1 
15 

GMV-ND15TS/A-T(U) 
1 
15 

208/230V-1ph-60Hz 

GMV-ND18TS/A-T(U) 
1 
15 

GMV-ND24TS/A-T(U) 
1 
15 
 

(1) An all-pole disconnection switch having a contact separation of at least 3mm (1/8 in.) in all poles should 

be connected in fixed wiring. 

(2) The circuit breaker and power cord specification in above sheet is based on max power (max current) 

of the unit. 

(3) The power cord specification in above sheet is based on ambient temperature of 40(104°F). 

(4) The circuit breaker specification in above sheet is based on ambient temperature of 40(104°F). If the 

working condition is different, please adjust it according to the specification sheet of circuit breaker. 

4 Installation Instructions  

4.1 Installation of Indoor Unit 

4.1.1Ceiling opening Dimension and suspension bolt position. 

Fig. 4.1.1 

Unit: mm(in.) 

Outer diameter of 

connection 
pipe(mm(in.)) 

Model 
Indoor 
unit(A) 

Suspension 
bolt pitch(B) 

Ceiling 
opening(C) 

Decoration 

panel(D) 

Liquid pipe 
Gas pipe 

GMV-ND09TS/A-T(U) 
1200 
(47-1/4) 

1252 
(49-5/16) 

1386 
(54-9/16) 

1416 
(55-3/4) 

6.35 
(1/4) 

9.52 
(3/8) 

6 

Sayfa 11

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

Outer diameter of 

connection 
pipe(mm(in.)) 

Model 
Indoor 
unit(A) 

Suspension 
bolt pitch(B) 

Ceiling 
opening(C) 

Decoration 

panel(D) 

Liquid pipe 
Gas pipe 

GMV-ND12TS/A-T(U) 
GMV-ND15TS/A-T(U) 

1200 
(47-1/4) 

1252 
(49-5/16) 

1386 
(54-9/16) 

1416 
(55-3/4) 

6.35 
(1/4) 

12.7 
(1/2) 

GMV-ND18TS/A-T(U) 
GMV-ND24TS/A-T(U) 

1200 
(47-1/4) 

1252 
(49-5/16) 

1386 
(54-9/16) 

1416 
(55-3/4) 

9.52 
(3/8) 

15.9 
(5/8) 

4.1.2 Suspend the indoor unit 

(1) Drill bolt holes and install bolts. 

1) Stick the paper pattern on the installation position; drill 4 holes according to the hole 

site on the cardboard as shown in fig. 4.1.2; diameter of drilling hole is according to 

the diameter of expansion bolt and the depth is 60~70 (2-1/3~2-3/4) mm, as shown 

in fig. 4.1.3. 

Unit: mm (in.) 

Fig. 4.1.2                                 Fig. 4.1.3 

2) Insert the M10 expansion bolt into the hole and then knock the nail into the bolt, as 

shown in fig. 4.1.4. 

NOTICE!  

 The length of bolt depends on the installation height of the unit, bolts are field 

supplied. 

Fig. 4.1.4 

(2) Install the indoor unit temporarily. 

Assemble suspension bolt on the expansion bolt, attach the hanger bracket to the 

suspension bolt. Be sure to fix it securely by using a nut and washer from upper and lower sides 

of the hanger bracket. The washer fixing plate will prevent the washer from falling. 

(3) The usage of paper pattern. 

Refer to paper pattern of installation for ceiling opening dimension. The center of ceiling 

7 

Sayfa 12

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

opening is indicated on the paper pattern. Fix the paper pattern to the unit with 4 screws and fix 

the corners of the waterspout at the drainage pipe by screws. 

(4) Adjust the unit to the right position. 

(5) Check the level of the unit. 

The indoor unit is equipped with build-in water pump and float switch, verify the levelness 

of 4 directions by level gauge or vinyl tube (filled with water) respectively. 

(6) Remove the washer locating plate and then tighten the nut on it. 

(7) Remove the paper pattern. 

Fig. 4.1.5 
4.2 Refrigerant Pipe Connection 

(1) Aim the flaring port of copper pipe at the center of screwed joint and then tighten the 

flaring nut with hand as shown in fig. 4.2.1. 

(2) Tighten the flaring nut with torque wrench.  

Fig.4.2.1 

Pipe diameter 

mm(in.) 
Torque(N•m) 

6.35(1/4) 
15~30 

9.52(3/8) 
35~40 

12.7(1/2) 
45~50 

15.9(5/8) 
60~65 

8 

Sayfa 13

(3) Use pipe bend when bending the pipe and the bending angle should not be too small. 

(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape. 

4.3 Drainage Pipe Installation and Drainage System Testing 

4.3.1 Notice for Installation of Drainage Pipe 

(1) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines 

which are likely to produce corrosive or peculiar smell to prevent the smell from entering 

indoors or corrupt the unit. 

(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water 

from pouring in and cause property loss or personal injury. 

(3) Condensate drain pipe should be connected into special drain system for air conditioner. 

(4) The drainage pipe should be short and the gradient downwards should be at least 1%~2% 

in order to drain condensation water smoothly. 

(5) The diameter of drainage hose should be bigger or equal to the diameter of drainage 

pipe joint. 

(6) Install drainage pipe according to the following fig. and arrange insulation to the drainage 

pipe. Improper installation may lead to water leakage and damp the furniture and other 

things in the room. 

(7) You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert 

the end of PVC pipe into the drainage hole and then tighten it with drainage hole and 

wire binder. Can’t connect the drainage hole and drainage hole with glue. 

(8) When the drainage pipelines are used for several units, the position of pipeline should 

be about 100mm (4 in.) lower than the drainage port of each unit. In this case, thicker 

pipes should be applied. 

4.3.2 Installation of Drainage pipe 

(1) Drainage pipe should have the same diameter or larger diameter than the connection 

pipes (PVC pipe, outside diameter 25mm (1 in.), thickness≥1.5mm (1/16 in.)). 

(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for 

preventing forming air bubbles. 

(3) If the gradient of drainage pipe could not meet the installation requirements, raising pipe 

should be applied. 

(4) Insert the drainage hose into drain socket and then tighten the metal clamp securely.                

(5) Warp the sealing pad over drainage hose and metal clamp for heat insulation.  

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

Fig. 4.3.1 

9 

Sayfa 14

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

(6) Make sure to perform insulation work for all drainage hoses in the room in order to 

prevent any possible water dropping due to dew condensation. 

(7) Apply the suitable diameter for converging drainage pipe according to the operating 

capacity of the unit, as show in Fig. 4.3.2. 

① - drainage pipes assembled by T-shaped joints 

Fig. 4.3.2 

(8) The installation height of raising pipe for drainage should be lower than B. The gradient 

from raising pipe towards drainage direction should be at least 1%~2%. If the raising 

pipe is vertical with the unit, the raising height should be less than C. 

Fig. 4.3.3 

Model 
A(mm(in.)) 
B(mm(in.)) 
C(mm(in.)) 

GMV-ND09TS/A-T(U) 
GMV-ND12TS/A-T(U) 
GMV-ND15TS/A-T(U) 
GMV-ND18TS/A-T(U) 
GMV-ND24TS/A-T(U) 

260(11-3/4) 
740(30-7/8) 
690(27-3/16) 

(9) Drainage pipes should have a downward slope of at least 1%~2%, in order to prevent 

pipes from sagging; install hanger bracket at intervals of 1000~1500mm (39-3/8~59 in.). 

Fig. 4.3.4 

10 

Unit: mm (in.) 

Unit: mm (in.) 

Unit: mm (in.) 

Sayfa 15

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

(10) During the installation, distance from soft drain pipe to the gasket is C mm when the 

bolt is tightened. It is not allowed to apply PVC or other related glue in the joints of two 

ends of drain pipe. 

Fig. 4.3.5 

Model 
C (mm/in.) 

GMV-ND09TS/A-T(U) 
GMV-ND12TS/A-T(U) 
GMV-ND15TS/A-T(U) 
GMV-ND18TS/A-T(U) 
GMV-ND24TS/A-T(U) 

4.3.3 Test of Drainage System 

(1) Please test drainage system after electric work is finished. 

1) Inject approximately 1L purified water to drain pan from air vent, ensure that not to 

splash the water over the electrical components (e.g. water pump. etc). 

2) In case of commissioning finished, please energize the IDUs and switch to cooling 

or dry mode, meanwhile, the water pump operates, you can check the draining 

through the drain socket. 

3) If communication wire is not connected, communication malfunction “C0” will occur 

after 60s of energizing. In this case, the water pump operates automatically. Check 

if the water pump drains normally through drainage port. The water pump will stop 

automatically after running for 10mins. 

(2) During the test, please carefully check the drainage joint, make sure no any leakage 

occur. 

(3) It is strongly recommend to do the drain test before ceiling decoration. 

Fig. 4.3.6 

11 

8~12(5/16~1/2) 

Sayfa 16

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

4.4 Panel installation 

4.4.1 Notices for installation 

(1) Improper decorative panel installation could cause the following problems. 

(2) Ensure that its clearance-free between decoration panel and ceiling board after 

installation, if not, please adjust the body position. 

(3) Connect the decoration panel terminals (Female) to body terminals (male) as shown in 

fig.4.4.3. 

Fig. 4.4.1 

Fig. 4.4.2 

Fig. 4.4.3 

12 

Sayfa 17

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

4.4.2 Panel installation 

(1) Adjust the panel direction. Let the swing motor on the panel keep the same 

side with connection pipe. 

Fig. 4.4.4 
(2) Adjust the position of panel to make the panel holes fix at the holes on the unit. 

(3) Fix the 4 screws at the two side of panel and then fix the 2 screws in the middle of panel. 

(4) Install the air inlet grille and then lock the clasp. 

(5) Tighten the screw until the thickness of sealing material between panel and indoor unit 

is about 5~8mm(3/16~5/16in). 

Fig. 4.4.5 

4.5 Installation of Wired Controller 

Please refer to User Manual of Wired Controller for the installation details. 

NOTICE!  

When installation is finished, the unit must be tested and debugged before operation. 

Please refer to Instruction Manual of ODU for auto addressing and debugging details. 

13 

Unit: mm (in.) 

Sayfa 18

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

5 Wiring Work 

WARNING 

Before obtaining access to terminals, all supply circuits must be disconnected. 

(1) Units must be earthed securely, or it may cause electric shock. 

(2) Please carefully read the wiring diagram before carry out the wiring work, incorrect wiring could cause 

malfunction or even damage the unit. 

(3) The unit should be powered by independent circuit and specific socket. 

(4) The wiring should be in accordance with related regulations in order to ensure the units reliable running. 

(5) Install circuit breaker for branch circuit according to related regulations and electrical standards. 

(6) Keep cable away from refrigerant pipings, compressor and fan motor. 

(7) The communication wires should be separated from power cord and connection wire between indoor unit 

(8) Adjust the static pressure via wired controller according to site circumstance. 

5.1 Connection of Wire and Patch Board Terminal 

(1) The connection of wire (as shown in fig. 5.1.1) 

1) Strip about 25mm (1 in.) insulation of the wire end by stripping and cutting tool. 

2) Remove the wiring screws on the terminal board. 

3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in 

accordance with screw. 

4) Use the screwdriver for tightening the terminal. 

(2) The connection of stranded wire (as shown in fig. 5.1.2) 

1) Strip about 10mm (3/8 in.) insulation of the end of stranded wire by stripping and 

cutting tool. 

2) Loosen the wiring screws on terminal board. 

3) Insert the wire into the ring tongue terminal and tighten by crimping tool. 

4) Use the screwdriver for tightening the terminal. 

Fig. 5.1.1                         Fig. 5.1.2 

14 

Unit: mm (in.) 

Sayfa 19

5.2 Power Cord Connection 

NOTICE! 

Every unit should be equipped with a circuit breaker for short-circuit and overload protection. 

During operation, all indoor units connected to the same outdoor unit system must be kept 

energized status. Otherwise, the unit can’t operate normally. 

For units with single-phase power supply. 

(1) Detach the electric box lid. 

(2) Let the power cord pass through the wiring through-holes. 

(3) Connect the power cord to terminal "L1, L2, 
“. 

(4) Fix the power card with wiring clamp. 

(5) The wire diameter of power cord can’t be less than 18AWG. 

5.3 Connection of Communication Wire between Indoor Unit and 
Outdoor Unit (or indoor unit) 

(1) Detach the electric box cover. 

(2) Let the Communication cable pass through the wiring through-holes. 

(3) Connect the communication wire to terminal D1 and D2 of indoor 4-bit wiring board, as 

shown in Fig.5.3.1. 

                        Fig. 5.3.1                               Fig. 5.3.2 

(4) Fix the communication cable with clamp of electric box. 

(5) For more reliable communication, make sure connect the terminal resistor to the most 

downstream IDU of the communication bus (terminal D1 and D2), as shown in fig 5.3.2, 

terminal resistor is provided with each ODU. 

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

Fig. 5.2.1 

15 

Sayfa 20

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

5.4 Connection of Communication Wire for Wired Controller 

(1) Detach the electric box cover. 

(2) Let the communication wire pass through the wiring through-holes. 

(3) Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board. 

(4) Fix the communication wire with clamp. 

(5) Wiring instructions of signal receiver and wired controller. 

1) Wired controller (optional) is shown as Fig.5.4.1, wireless controller (standard) is 

shown as Fig.5.4.2, signal receiver is provided with panel as standard accessory. 

Fig. 5.4.1                            Fig. 5.4.2 

2) Both IDU and wired controller are equipped with signal receiver, and available for 

wireless control respectively. 

5.5 Wiring Instructions of Wired Controller and Indoor Units Network 

(1) Communication wire of indoor unit and outdoor unit (or indoor unit) is connected to D1, 

D2. 

(2) Wired controller is connected to H1, H2. 

(3) One indoor unit can connect two wired controllers that must be set as master one and 

slave one. 

(4) One wired controller can control 16 indoor unitS in maximum at the same time. (As 

shown in Fig.5.5.1). 

(1) The type of indoor units must be the same if they are controlled by the same wired controller. 

(2) When the indoor unit is controlled by two wired controllers, the addresses of the two wired controllers 

should be different through address setting. Address 1 is for main controller; Address 2 is for slave 
controller. Detailed setting please refer to the instruction manual of wired controller. 

16 

Sayfa 21

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

Fig. 5.5.1 

17 

Sayfa 22

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

6 Routine Maintenance 

(1) Do turn off the unit and cut off the main power supply when cleaning the air conditioner to avoid electric shock 

or injury. 

(2) Stand at solid table when cleaning the unit. 

(3) Do not clean the unit with hot water whose temperature is higher than 45°C to prevent fade or deformation. 

(4) Do not dry the filters by fire, or it may catch fire or become deformed. 

(5) Clean the filter with a wet cloth dipped in neutral detergent. 

(6) Please contact after-sales service staff if there is abnormal situation. 

6.1 Cleaning of Filter 

(1) Remove the air filter on the air inlet for cleaning. Use a dust catcher or water to clean it. 

If the filter is very dirty (e.g. greasy), you can clean it using warm water (below 45°C) 

that is mixed with mild detergent. Then let it dry naturally in cool places. 

(2) If the air conditioner is used in dusty place, please clean the air filter regularly (generally 

once every 2 weeks). 

6.2 Maintenance before the Seasonal Use 

(1) Check if the air inlet and air outlet of indoor and outdoor unit are blocked. 

(2) Check if the grounding wire is in good condition. 

(3) Check if all the power cord and communication cable are securely connected. 

(4) Check if any error code displayed after energized. 

6.3 Maintenance after the Seasonal Use 

(1) Set the unit in fan mode for half a day in a sunny day to dry the inner part of unit. 

(2) When the unit won’t be used for a long time, please cut off power supply for energy 

saving; the characters on the wired controller screen will disappear after cutting off the 

power supply. 
 
 
 
 
 
 
 
 
 
 
 
 
 

18 

Sayfa 23

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

7 Table of Error Codes for Indoor Unit 

Error 
Code 
Content 
Error 
Code 
Content 
Error 
Code 
Content 

L0 
Indoor Unit Error 
LA 
Indoor Units 
Incompatibility Error 
d9 
Jumper Cap Error 

L1 
Indoor Fan Protection 
LH 
Low Air Quality 

Warning 
dA 
Indoor Unit Network 

Address Error 

L2 
E-heater Protection 
LC 
ODU-IDU 
Incompatibility Error 
dH 
Wired Controller PCB 

Error 

L3 
Water Full Protection 
d1 
Indoor Unit PCB Error 
dC 
Capacity DIP Switch 

Setting Error. 

L4 
Wired Controller Power 

Supply Error 
d3 
Ambient Temperature 

Sensor Error 
dL 
Outlet Air Temperature 

Sensor Error 

L5 
Freeze protection 
d4 
Inlet Pipe Temperature 

Sensor Error 
dE 
Indoor Unit CO2 

Sensor Error 

Outlet Pipe 
Temperature Sensor 

L7 
No Master Indoor Unit 

dy 
Water Temperature 

Error 
d6 

Sensor Error 

Error 

L8 
Power Insufficiency 

Protection 
d7 
Humidity Sensor Error 
C0 
Communication Error 

Quantity Of Group 
Control Indoor Units 

d8 
Water Temperature 

Error 
AJ 
Filter Cleaning 

L9 

Reminder 

Setting Error 

o1 
Low busbar volage of 

indoor unit 
o2 
High busbar volage of 

indoor unit 
o3 
IPM Module Protection 

of Indoor Unit 

Current Detection 
Circuit Malfunction of 

o4 
Failure Startup of 

Indoor Unit 
o5 
Overcurrent Protection 

of Indoor Unit 
o6 

Indoor Unit 

Desynchronizing 
Protection of Indoor 

Communication 
Malfunction of Indoor 

Communication 
Malfunction of Main 
Mater of Indoor Unit 

o7 

o8 

o9 

Unit 

Unit’s Drive 

Malfunction of 
Temperature Sensor of 

Charging Circuit 
Malfunction of Indoor 

oA 
Overtemprature of 
Indoor Unit’s Module 
ob 

oC 

Indoor Unit’s Module 

Unit 

o0 
Other Drive 
Malfunction 
db 
Special Code: Field Debugging Code 

8 Display of Light Board 

The panel of this model is without nixie tube display. The error codes will be displayed 

through the power light, operation light and timer light; ○, ● and ◎ stand for on, off and blink 

respectively. 

Power light 
○ 
◎ 
◎ 
◎ 
◎ 

Operation light 
◎ 
● 
○ 
○ 
◎ 

Timer light 
● 
○ 
● 
○ 
● 

19 

Sayfa 24

Multi Variable Air Conditioners Two-way Cassette Indoor Unit 

Error code display sheet 

A3  

Error code 
C0 
A0 

L0 
L1 
L3 
L5 
d1 
d3 
d4 
d6 
d7 
E0 
db 
A4 

Power 

light 
◎ 
○ 
○ 
● 
● 
● 
○ 
◎ 
◎ 
◎ 
● 
○ 
● 
◎ 

Operation 

light 
◎ 
◎ 
○ 
● 
○ 
◎ 
● 
○ 
● 
◎ 
◎ 
◎ 
◎ 
● 

Timer light 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
◎ 
○ 
○ 
○ 
● 
● 

Defrosting 

Outlet pipe temperature 
sensor error 

Communication error 

Inlet pipe temperature 
sensor error 

Field debugging code 

Humidity sensor error 

Indoor fan protection 

Indoor unit PCB error 

Ambient temperature 
sensor error 

Water full protection 

Outdoor unit error 

Freeze protection 

Error description 

To be debugged 

Indoor unit error 

oil return 

9 Troubleshooting 

The air conditioner is not expected to be serviced by users. Incorrect repair may cause 

electric shock or fire, so please contact an authorized service center for professional service. 

The following checks prior to contact may save your time and money. 

Phenomenon 
Troubleshooting 

① Power supply is not connected. 
② Circuit breaker tripping caused by leakage of electricity. 
③ Input voltage is too low. 
④ Defect of main PC-board. 

The unit can’t start 

The unit stops after running 
for a while 
① The inlet or outlet of ODU or IDU are blocked by obstacle. 

① The filter is dirty or blocked. 
② Too heavy heat load of room(e.g. too many people). 
③ Door or windows is open. 
④ Inlet and outlet of IDU are blocked. 
⑤ Setting temperature is too high or refrigerant leaks. 
⑥ Refrigerant is insufficient (e.g. refrigerant leakage). 

Poor cooling effect 

① The filter is dirty or blocked. 
② Door or window is open. 
③ Setting temperature is too low. 
④ Refrigerant is insufficient (e.g. refrigerant leakage). 

Poor heating effect 

① At starting, the IDU fan could not operate till the heat exchange become hot, 
for preventing delivering the cool air. 
② At defrosting, the IDU fan stopped due to system switch to cooling mode. For 
preventing delivering the cool air, and resume operating after defrosting. 

Indoor fan doesn’t start  
up during heating  

NOTICE! 

If air conditioner still fails to work normally after checking and handling as described above, 

please stop using it immediately and contact local service center for assistance. 