Owner's Manual 

Original Instructions 
Commercial Air Conditioners 

 
Multi Variable Air Conditioners 
One-way Cassette Type Indoor Unit 
 

Models: 

GMV-ND07TD/A-T(U) 

GMV-ND09TD/A-T(U) 

GMV-ND12TD/A-T(U) 

Sayfa 2

For correct installation and operation, please read all instructions carefully. Before reading the 

instructions, please be aware of the following items: 

 
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. 
Obey all safety messages that follow this symbol to avoid possible injury or death. 
 
This mark indicates procedures which, if improperly performed, might lead to the death or 
serious injury of the user. 
 
This mark indicates procedures which, if improperly performed, might possibly result in 
personal harm to the user, or damage to property. 

 
NOTICE is used to address practices not related to personal injury. 

(1) 
Instructions for installation and use of this product are provided by the manufacturer.  

(2) 
Installation must be performed in accordance with the requirements of NEC and CEC by authorized personnel 
only. 

(3) 
For the safe operation of this unit, please read and follow the instructions carefully. 

(4) 
During operation, total capacity of indoor units should not exceed the total capacity of outdoor units. otherwise, 
poor effect of cooling or heating may result. 

(5) 
Direct operators or maintainers should well keep this manual. 

(6) 
If this unit fails to operate normally, please contact our service center as soon as possible and provide the 
following information:     
1) Content on the nameplate (model number, cooling capacity, production code, ex-factory date. 
2) Malfunction details(before and after the malfunction occurs. 

(7) 
Each unit has been strictly tested and proved to be qualified before ex-factory. In order to prevent units from being 
damaged or operating normally because of improper disassembly, please do not disassemble the unit by 
yourself. If you need to disassemble and check units, please contact our service center. We will send specialists 
to guide the disassembly. 

(8) 
Installation must be performed in accordance with the requirements of NEC and CEC by authorized personnel 
only. 

This appliance can be used by children aged from 8 years and above and persons with 

reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have 

been given supervision or instruction concerning use of the appliance in a safe way and 

understand the hazards involved. Children shall not play with the appliance. Cleaning and user 

maintenance shall not be made by children without supervision. 

DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of 

such waste separately for special treatment is necessary. 

Preface 

Sayfa 3

Manufacturer will bear no responsibilities when personal injury or property loss is caused by 

the following reasons: 

(1) Damage the product due to improper use or misuse of the product; 

(2) Alter, change, maintain or use the product with other equipment without abiding by the 

instruction manual of manufacturer; 

(3) After verification, the defect of product is directly caused by corrosive gas; 

(4) After verification, defects are due to improper operation during transportation of product; 

(5) Operate, repair, maintain the unit without abiding by instruction manual or related 

regulations; 

(6) After verification, the problem or dispute is caused by the quality specification or 

performance of parts and components that produced by other manufacturers; 

(7) The damage is caused by natural calamities, bad using environment or force majeure. 

Exception Clauses 

Sayfa 4

1 Safety Precautions .................................................................................................................... 1 

2 Product Introduction ................................................................................................................. 2 

2.1 Names of Key Components .................................................................................................. 2 

2.2 Rated Working Condition ...................................................................................................... 2 

3 Preparations for Installation ..................................................................................................... 2 

3.1 Standard Fittings ................................................................................................................... 2 

3.2 Installation Position Selection ............................................................................................... 3 

3.3 Requirements for Communication Line ................................................................................. 4 

3.4 Wiring Requirements ............................................................................................................. 5 

4 Installation Instructions ............................................................................................................ 6 

4.1 Installation of Indoor Unit ...................................................................................................... 6 

4.2 Refrigerant Pipe Connection ................................................................................................. 7 

4.3 Drainage Pipe Installation and Drainage System Testing ...................................................... 8 

4.4 Panel Installation ................................................................................................................. 11 

4.5 Installation of Wired Controller ............................................................................................ 12 

5 Wiring Work ............................................................................................................................. 12 

5.1 Connection of Wire and Patch Board Terminal ................................................................... 12 

5.2 Power Cord Connection ...................................................................................................... 13 

5.3 Connection of Communication Wire between Indoor Unit and Outdoor Unit (or Indoor Unit)
 .................................................................................................................................................. 14 

5.4 Connect Communication Wire of Wired Controller .............................................................. 14 

5.5 Illuminate for Connection of Wired Controller and Indoor Units Network ............................ 15 

6 Routine Maintenance .............................................................................................................. 17 

6.1 Cleaning of Filter ................................................................................................................. 17 

6.2 Maintenance before the Seasonal Use ............................................................................... 17 

6.3 Maintenance after the Seasonal Use .................................................................................. 17 

7 Table of Error Codes for Indoor Unit ...................................................................................... 18 

8 Troubleshooting ...................................................................................................................... 18 
  

Contents

Sayfa 5

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

1 Safety Precautions  

(1) 
This product can’t be installed at corrosive, inflammable or explosive environment or the place with special 
requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of 
the unit, or even cause fire hazard or serious injury. As for above special places, please adopt special air 
conditioner with anti-corrosive or anti-explosion function . 
(2) 
Follow this instruction to complete the installation work. Please carefully read this manual before unit 
startup and service. 
(3) 
Wire size of power cord should be large enough. The damaged power cord and connection wire should be 
replaced by exclusive cable.  
(4) 
After connecting the power cord, please fix the electric box cover properly in order to avoid accident.  
(5) 
Never fail to comply with the nitrigen charge requirements. Charge nitrogen when welding pipes.  
(6) 
Never short-circiut or cancel the pressure switch to prevent unit damage.  
(7) 
Please firstly connect the wired controller before energization, otherwise wired controller can not be used.  
(8) 
Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant 
leakage, electric shock, or fire etc..  
(9) 
Do not insert fingers or objects into air outlet/inlet grille.  
(10) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the gas/oil 

supplied heating equipment is used.  
(11) Never start up or shut off the air conditioner by means of directly plug or unplug the power cord.  
(12) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor.  
(13) Do not allow children operate this unit.  
(14) Do not operate this unit with wet hands.  
(15) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury may 

happen.  
(16) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen.  
(17) Do not expose the unit to the moist or corrosive circumstances.  
(18) Under cooling mode, please don't set the room temperature too low and keep the temperature difference 

between indoor and outdoor unit within 5°C(41°F).  

(19) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please 

contact Gree appointed service center for help.  
(20) Before installation, please check if the power supply is in accordance with the requirements specified on 

the nameplate. And also take care of the power safety.  
(21) Installation should be conducted by dealer or qualified personnel. Please do not attempt to install the unit 

by yourself. Improper handling may result in water leakage, electric shock or fire disaster etc..  
(22) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire 

accidents.  
(23) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid 

electric shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone 
line.  
(24) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off the 

power when 24 hours short-time halting (to protect the compressor).  
(25) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will emerge 

if the refrigerant gas meets fire.  
(26) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little 

neutral detergent to clean the outer casing of unit.  
(27) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main power 

supply, and then immerdiately contact Gree appointed service center. If abnormality keeps going, the unit 
might be damaged and lead to electric shock or fire.  

Any personal injury or property loss caused by improper installation, improper debug, 

unnecessary repair or not following the instructions of this manual should not be the responsibility 

of Gree Electric Appliances, Inc. of Zhuhai. 

WARNING 

1 

Sayfa 6

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

2 Product Introduction 

2.1 Names of Key Components 

Fig. 2.1.1 

No. 
① 
② 
③ 
④ 
⑤ 

Name 
Connection pipe 
Panel 
Air louver 
Swing blade 
Air-in grille 

No. 
⑥ 
⑦ 
⑧ 
⑨ 
 

 Name 
Built-in filter 
Main body 
Drainage device 

(built-in) 
Drainage Pipe 
 

2.2 Rated Working Condition 

Indoor Side Condition 
Outdoor Side Condition 

Dry Bulb Temp 

Wet Bulb Temp  

Dry Bulb Temp 

Wet Bulb Temp  

 °C(°F) 

 °C(°F) 

 °C(°F) 

°C(°F) 

Rated Cooling 
26.7(80.0) 
19.4(67.0) 
35(95) 
24(75.2) 

Rated Heating 
21.1(70.0) 
15.6(60.0) 
7(44.6) 
6(42.8) 

3 Preparations for Installation 

NOTICE! Product graphics are only for reference. Please refer to actual products. Unspecified 

measure unit is mm(in.). 

3.1 Standard Fittings 

Please use the supplied standard fittings listed below as instructed. 

No. 
Name 
Appearance 
Q'ty 
Usage 

1 
wireless controller 
 
1 
To control the indoor unit 

2 
paper pattern for 

installation 
 
1 
Locate the drill hole on ceiling 

3 
Tapping screw with 

washer 
 
4 
Fix paper pattern 

2 

Sayfa 7

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

No. 
Name 
Appearance 
Q'ty 
Usage 

4 
Washer fixing plate 
 
4 
Prevent the washer from falling off 

5 
Drain Hose Assembly 
 
1 
To connect with the hard PVC 

6 
Special Nut 
 
2 
To be used for connecting the 

7 
M10 Washer 
 
10 
To be used together with the 
hanger bolt for installing the unit. 

8 
Self-tapping screw 
 
10 
For mounting panels 

9 
Insulation 
 
1 
To insulate the gas pipe 

10 
Insulation  
 
1 
To insulate the liquid pipe 

11 
Sponge 
 
1 
To insulate the drain pipe 

12 
Fastener  
4 
To fasten the sponge 

13 
Remote controller holder 
 
1 
Used for holding the remote 

14 
Tapping screw 
 
2 
Used for fixing the remote 

3.2 Installation Position Selection 

(1) The appliance shall not be installed in the laundry. 

(2) The location should be able to withstand the weight of unit. 

(3) The water can be drained conveniently from drainage pipe. 

(4) There should be no obstruction near air inlet and air outlet. 

(5) Follow the installation distance required in the fig below to ensure sufficient space for 

maintenance.  

(6) The installation location should be far from heat sources, flammable or explosive gas, or 

smog spread in the air. 

(7) The indoor unit, outdoor unit, power cord and connection electricity wire should be at 

least 1m from television and radio in order to prevent interference and noise (Even 

though 1m distance is ensure, there may be noise if the electric wave is too strong.) 

(8) This indoor unit may be installed on ceilings up to 2.5m(98-3/8in.) to avoid accidental 

touching. 

drain pipe 

refrigerant pipe 

controller 

controller holder 

3 

Sayfa 8

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

>20(3/4)

≥1500
(59)

≥2500(98 3/8)

Fig. 3.2.1 

Model 
a 
b 
c 

07 
141(5 1/2) 
207(8 1/8) 
227(8 7/8) 

09 
141(5 1/2) 
207(8 1/8) 
227(8 7/8) 

12 
141(5 1/2) 
207(8 1/8) 
227(8 7/8) 
 

(1) 
The unit shall be installed in accordance with national standards or local regulations. 

(2) 
Only qualified personnel can carry out installation work, please contact with local dealer before installation. 

(3) 
Make sure all the installation work completed before energizing. 

3.3 Requirements for Communication Line 

NOTICE! If air conditioner used under strong electronic-magnetic interference circumstance, STP 

(shielded twisted pair) communication cable must be adopted.   

3.3.1 Select Communication Line for Indoor Unit and Wired Controller 

Fig. 3.3.1 

4 

Unit: mm(in.) 

c

a

≥1500
(59)

Sayfa 9

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

Total length of 
communication line 
between indoor unit and 

Material 
Standar

Wire size 
(mm2/AWG) 

Material type 

Remarks 

d 

wired controller L (m/ft.) 

1. Total length of communication 
line can't exceed 250m (820ft.). 
2. The cord shall be Circular cord 
(the cores shall be twisted 
together). 
3. If unit is installed in places with 
intense magnetic field or strong 
interference, it is necessary to 
use shielded wire. 

Light/Ordinary 

polyvinyl 

2×0.75~2×1.25 
(2×AWG18 
~2×AWG16) 

chloride 
sheathed cord. 

L≤250m 
(L≤820ft.) 

IEC 
60227-5 

(60227 IEC 52 
/60227 IEC 53) 

3.3.2 Selection of Communication Wire between Indoor Unit and Indoor Unit (or 
Outdoor Unit) 

Fig. 3.3.2 

Total Length L (m/ft.) 

of Communication 
Cable between Indoor 

Wire size 
(mm2/AWG) 

Material 
Standard 
Remarks 

Material Type 

Unit and Indoor 

(Outdoor) Unit  

1. If the wire diameter is enlarged to 
2×1 mm2 (2×AWG16), the total 
communication line length can reach 
1500 m (4920ft.).  
2. The cord shall be Circular cord (the 
cores shall be twisted together). 
3. If unit is installed in places with 
intense magnetic field or strong 
interference, it is necessary to use 
shielded wire. 

Light/Ordinary 
polyvinyl chloride 

L≤1000m 
(L≤3280ft.) 

≥2×0.75 
(≥2×AWG18) IEC 60227-5 

sheathed cord. 

(60227 IEC 52 
/60227 IEC 53) 

3.4 Wiring Requirements 

Power Cord Size and Air Switch Capacity 

Model 
Power Supply 
MCA(A) 
MOP(A) 

GMV-ND07TD/A-T(U) 

1 
15 

GMV-ND09TD/A-T(U) 
1 
15 

208/230V-1ph-60Hz 

GMV-ND12TD/A-T(U) 
1 
15 
 

(1) 
An all-pole disconnection switch having a contact separation of at least 3mm(1/8 in.) in all poles should be 
connected in fixed wiring. 

5 

Sayfa 10

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

(2) 
The circuit breaker and power cord specification in above sheet is based on max power(max current) of the 
unit. 
(3) 
The power cord specification in above sheet is based on ambient temperature of 40°C(104°F). 

(4) 
The circuit breaker specification in above sheet is based on ambient temperature of 40°C(104°F). If the 
working condition is different, please adjust it according to the specification sheet of circuit breaker. 
4 Installation Instructions 

4.1 Installation of Indoor Unit 

4.1.1 Ceiling opening Dimension and suspension bolt position. 

Fig. 4.1.1 

4.1.2 Suspend the Indoor Unit 

(1) Drill bolt holes and install bolts 

1) Stick the reference cardboard on the installation position; drill 4 holes according to 

the hole site on the cardboard as shown in fig. 4.1.2; diameter of drilling hole is 

according to the diameter of expansion bolt and the depth is 60-70mm (2-3/8~2-3/4 

in.), as shown in fig. 4.1.3. 

Fig. 4.1.2                                 Fig. 4.1.3 

2) Insert the M10 expansion bolt into the hole and then knock the nail into the bolt, as 

shown in fig. 4.1.4. 

NOTICE! The length of bolt depends on the installation height of the unit; bolts are field supplied. 

6 

Sayfa 11

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

(2) Install the indoor unit temporarily 

Assemble suspension bolt on the expansion bolt, attach the hanger bracket to the suspension 

bolt. Be sure to fix it securely by using a nut and washer from upper and lower sides of the hanger 

bracket. The washer fixing plate will prevent the washer from falling. 

(3) The usage of paper pattern 

Refer to paper pattern of installation for ceiling opening dimension. The center of ceiling 

opening is indicated on the paper pattern. Fix the paper pattern to the unit with 4 screws and fix the 

corners of the waterspout at the drainage pipe by screws. 

(4) Adjust the unit to the right position. 

(5) Check the level of the unit 

The indoor unit is equipped with build-in water pump and float switch, verify the levelness of 4 

directions by level gauge or vinyl tube (filled with water) respectively. 

(6) Remove the washer locating plate and then tighten the nut on it. 

(7) Remove the paper pattern. 

4.2 Refrigerant Pipe Connection 

(1) Aim the flaring port of copper pipe at the center of screwed joint and then tighten the 

flaring nut with hand as shown in fig. 4.2.1 

Fig. 4.1.4 

Fig. 4.1.5 

7 

Sayfa 12

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

(2) Tighten the flaring nut with torque wrench. 

Pipe diameter 

Mm(in.) 
Torque(N•m) 

Φ6.35(1/4) 
15~30 

Φ9.52(3/8) 
35~40 

Φ12.7(1/2) 
45~50 

Φ15.9(5/8) 
60~65 

Fig.4.2.1 

(3) Use pipe bend when bending the pipe and the bending angle should not be too small. 

(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape. 

4.3 Drainage Pipe Installation and Drainage System Testing 

4.3.1 Notice for Installation of Drain Pipe 

(1) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines 

which are likely to produce corrosive or peculiar smell to prevent the smell from entering 

indoors or corrupt the unit. 

(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water 

from pouring in and cause property loss or personal injury. 

(3) Condensate drain pipe should be connected into special drain system for air conditioner. 

(4) The drainage pipe should be short and the gradient downwards should be at least 

1%~2% in order to drain condensation water smoothly. 

(5) The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe 

joint. 

(6) Install drainage pipe according to the following fig. and arrange insulation to the drainage 

pipe. Improper installation may lead to water leakage and damp the furniture and other 

things in the room. 

(7) You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert 

the end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire 

binder. Can’t connect the drainage hole and drainage hole with glue. 

(8) When the drainage pipelines are used for several units, the position of pipeline should be 

about 100mm (4 in.) lower than the drainage port of each unit. In this case, thicker pipes 

should be applied. 

Fig. 4.3.1 

8 

Sayfa 13

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

4.3.2 Drainage Pipe Installation 

(1) Drainage pipe should have the same diameter or larger diameter than the connecting 

pipes (PVC pipe, outside diameter 25mm (1 in.), thickness≥1.5mm (1/16 in.)). 

(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for 

preventing forming air bubbles. 

(3) If the gradient of drainage pipe could not meet the installation requirements, rasing pipe 

should be applied. 

(4) Insert the drainage hose into drain socket, tighten the metal clamp securely. 

(5) Warp the sealing pad over drain hose and metal clamp for heat insulation. 

(6) Make sure to perform insulation work for all drainage piping in order to prevent any 

possible water drop due to dew condensation. 

(7) Apply the suitable diameter for converging drainage pipe according to the operating 

capacity of the unit. 

Fig. 4.3.2  

①- drainage pipes assembled by T-shaped joints 

(8) The installation height of raising pipe for drainage should be lower than B. The gradient 

from raising pipe towards drainage direction should be at least 1%~2%. If the raising pipe 

is vetical with the unit, the raising height should be less than C. 

Fig. 4.3.3 

Model 
A (mm/in.) 
B(mm/in.) 
C(mm/in.) 

07~12 
100(3-15/16) 
900(35-7/16) 
850(33-7/16) 
 

9 

Unit: mm(in.) 

Unit: mm(in.) 

Sayfa 14

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

(9) Drain pipes should have a downward slope of at least 1%~2%, in order to prevent pipes 

from sagging, install hanger bracket at intervals of 1000~1500mm (39-3/8~59 in.). 

Fig. 4.3.4 

4.3.3 Test of Drainage System 

(1) Please test drainage system after electric work is finished. 

Inject approximately 1L purified water to drain pan from air vent, ensure that not to splash the 

water over the electrical components (e.g. water pump. etc). 

1) Inject approximately 1L purified water to drain pan from air vent, ensure that not to 

splash the water over the electrical components (e.g. water pump. etc.). 

2) In case of commissioning finished, please energize the IDUs and switch to cooling or 

dry mode, meanwhile, the water pump operates, you can check the draining through 

the drain socket. 

3) If communication wire is not connected, communication malfunction “C0” will occur 

after 60s of energizing. In this case, the water pump operates automatically. Check if 

the water pump drains normally through drainage port. The water pump will stop 

automatically after running for 10mins. 

(2) During the test, please carefully check the drainage joint, make sure no any leakage 

occur. 

(3) It’s strongly recommend to do the drain test before ceiling decoration. 

Fig. 4.3.5 

10 

Unit: mm(in.) 

Unit:mm(in.) 

Sayfa 15

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

4.4 Panel Installation 

4.4.1 Notices for Installation 

(1) Improper decorative panel installation could cause the following problems. 

(2) Ensure that its clearance-free between decoration panel and ceiling board after 

installation, if not, please adjust the body position. 

(3) Connect the decoration panel terminals (Female) to body terminals (male) as shown in 

fig. 4.4.3. 

4.4.2 Panel Installation 

(1) Remove the grille from the panel, and then open the horizontal louver. 

(2) Aim the screw hole on panel at the corresponding screw hole on main unit.  

(3) Screw up the screws on corresponding holes and then install the corresponding screw 

cover.  

(4) Close the horizon lover, connect the butt terminal and arrange the wires. 

Fig. 4.4.1 

Fig. 4.4.2 

Fig. 4.4.3 

11 

Sayfa 16

(5) After tightening screws, reinstall the air inlet grille. 

4.5 Installation of Wired Controller 

Please refer to User Manual of Wired Controller for the installation details. 

NOTICE! When installation is finished, the unit must be tested and debugged before operation. 

Please refer to Instruction Manual of ODU for auto addressing and debugging details. 

5 Wiring Work 

Before obtaining access to terminals, all supply circuits must be disconnected. 

(1) 
Units must be earthed securely, or it may cause electric shock. 

(2) 
Please carefully read the wiring diagram before carry out the wiring work, incorrect wiring could cause 
malfunction or even damage the unit. 

(3) 
The unit should be powered by independent circuit and specific socket. 

(4) 
The wiring should be in accordance with related regulations in order to ensure the units reliable running. 

(5) 
Install circuit breaker for branch circuit according to related regulations and electrical standards. 

(6) 
Keep cable away from refrigerant pipings, compressor and fan motor. 

(7) 
The communication wires should be separated from power cord and connection wire between indoor unit 

(8) 
Adjust the static pressure via wired controller according to site circumstance. 

5.1 Connection of Wire and Patch Board Terminal 

(1) The connection of wire (as shown in fig. 5.1.1) 

1) Strip about 25mm (1 in.) insulation of the wire end by stripping and cutting tool. 

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

Fig. 4.4.4. 

WARNING 

12 

Sayfa 17

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

2) Remove the wiring screws on the terminal board. 

3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in 

accordance with screw. 

4) Use the screwdriver for tightening the terminal. 

(2) The connection of stranded wire (as shown in fig. 5.1.2) 

1) Strip about 10mm (3/8 in.) insulation of the end of stranded wire by stripping and 

cutting tool. 

2) Loosen the wiring screws on terminal board. 

3) Insert the wire into the ring tongue terminal and tighten by crimping tool. 

4) Use the screwdriver for tightening the terminal. 

Fig. 5.1.1                          Fig. 5.1.2 

5.2 Power Cord Connection 

(1) 
Every unit should be equipped with a circuit breaker for short-circuit and overload protection. In general, 
circuit breaker is at OFF status.  
(2) 
During operation, all indoor units and outdoor units belonging to the same system must be kept energized 
status. Otherwise, the unit can’t operate normally. 

Fig. 5.2.1 

For units with single-phase power supply. 

(1) Detach the electric box lid. 

(2) Let the power cord pass through the wiring through-holes. 

(3) Connect the power cord to terminal "L1, L2". 

(4) Fix the power card with wiring clamp. 

(5) The wire diameter of power cord can’t be less than 18AWG. 

13 

Sayfa 18

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

5.3 Connection of Communication Wire between Indoor Unit and Outdoor 
Unit (or Indoor Unit) 

(1) Detach the electric box lid. 

(2) Let the Communication cable pass through the wiring through-holes. 

(3) Connect the communication wire to terminal D1 and D2 of indoor 4-bit wiring board, as 

shown in fig. 5.3.1. 

                          Fig. 5.3.1                                 Fig. 5.3.2 

(4) Fix the communication cable with clamp of electric box. 

(5) For more reliable communication, make sure connect the terminal resistor to the most 

downstream IDU of the communication bus (terminal D1 and D2), as shown in fig. 5.3.2, 

terminal resistor is provided with each ODU. 

5.4 Connect Communication Wire of Wired Controller 

(1) Open electric box cover of indoor unit. 

(2) Let the communication wire go through the rubber ring. 

(3) Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board. 

(4) Fix the communication wire with wire clip on the electric box. 

(5) Wiring instructions of remote receiving light board and wired controller: 

1) Wired controller (standard) is shown as Fig.5.4.1, wireless controller (optional) is 

shown as Fig.5.4.2 signal receiver is provided with panel as standard accessory. 

Fig. 5.4.1                                      Fig. 5.4.2 

14 

Sayfa 19

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

2) Both IDU and wired controller are equipped with signal receiver, and available for 

wireless control respectively. 

5.5 Illuminate for Connection of Wired Controller and Indoor Units 
Network 

(1) Communication wire of indoor unit and outdoor unit (or indoor unit) is connected to D1, 

D2. 

(2) Wired controller is connected to H1, H2. 

(3) One indoor unit can connect two wired controllers that must be set as master one and 

slave one. 

(4) One wired controller can control 16 indoor unitS in maximum at the same time (as shown 

in fig.5.5.1). 

(1) 
The type of indoor units must be the same if they are controlled by the same wired controller. 

(2) 
When the indoor unit is controlled by two wired controllers, the addresses of the two wired controllers should 
be different through address setting. Address 1 is for main controller; Address 2 is for slave controller. 
Detailed setting please refer to the instruction manual of wired controller. 

Fig. 5.4.3 

15 

Sayfa 20

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

Fig. 5.5.1 

16 

Sayfa 21

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

6 Routine Maintenance 

(1) 
Do turn off the unit and cut off the main power supply when cleaning the air conditioner to avoid electric 
shock or injury. 

(2) 
Stand at solid table when cleaning the unit. 

(3) 
Do not clean the unit with hot water whose temperature is higher than 45°C to prevent fade or deformation. 

(4) 
Do not dry the filters by fire, or it may catch fire or become deformed. 

(5) 
Clean the filter with a wet cloth dipped in neutral detergent. 

(6) 
Please contact after-sales service staff if there is abnormal situation. 

6.1 Cleaning of Filter 

(1) Remove the filters from inlet of IDU. Use a vacuum cleaner to remove dust. If the filters 

are dirty, wash them with warm water and mild detergent, and dry the filters in the shade. 

(2) If the unit used in the environment with much dust, please clean it regularly (Usually once 

every two weeks). 

6.2 Maintenance before the Seasonal Use 

(1) Check if the air inlet and air outlet of indoor and outdoor unit are blocked. 

(2) Check if securely grounded. 

(3) Check if all the power cord and communication cable are securely connected. 

(4) Check if any error code displayed after energized. 

6.3 Maintenance after the Seasonal Use 

(1) Set the unit in fan mode for half a day in a sunny day to dry the inner part of unit; 

(2) When the unit won’t be used for a long time, please cut off power supply for energy 

saving; the characters on the wired controller screen will disappear after cutting off the 

power supply. 

17 

Sayfa 22

Multi Variable Air Conditioners One-way Cassette Type Indoor Unit 

7 Table of Error Codes for Indoor Unit 

Error 
Code 
Content 
Error 
Code 
Content 
Error 
Code 
Content 

L0 
Indoor Unit Error 
LA 
Indoor Units 
Incompatibility Error 
d9 
Jumper Cap Error 

L1 
Indoor Fan Protection 
LH 
Low Air Quality Warning 
dA 
Indoor Unit Network 
Address Error 

L2 
E-heater Protection 
LC 
ODU-IDU Incompatibility 
Error 
dH 
Wired Controller PCB 
Error 

L3 
Water Full Protection 
d1 
Indoor Unit PCB Error 
dC 
Capacity DIP Switch 
Setting Error. 

L4 
Wired Controller Power 
Supply Error 
d3 
Ambient Temperature 
Sensor Error 
dL 
Outlet Air Temperature 
Sensor Error 

L5 
Freeze protection 
d4 
Inlet Pipe Temperature 
Sensor Error 
dE 
Indoor Unit CO2 Sensor 
Error 

L7 
No Master Indoor Unit 
Error 
d6 
Outlet Pipe Temperature 
Sensor Error 
dy 
Water Temperature 
Sensor Error 

L8 
Power Insufficiency 
Protection 
d7 
Humidity Sensor Error 
C0 
Communication Error 

Quantity Of Group 
Control Indoor Units 
Setting Error 

L9 

d8 
Water Temperature Error 
AJ 
Filter Cleaning Reminder 

db 
Special Code: Field Debugging Code 

8 Troubleshooting 

The air conditioner is not expected to be serviced by users. Incorrect repair may cause 

electric shock or fire, so please contact an authorized service center for professional service. The 

following checks prior to contact may save your time and money. 

Phenomenon 
Troubleshooting 

① Power supply is not connected. 
② Circuit breaker tripping caused by leakage of electricity. 
③ Input voltage is too low. 
④ Defect of main PC-board. 
The unit stops after running 
for a while. 
① The inlet or outlet of ODU or IDU are blocked by obstacle. 

The unit can’t start 

① The filter is dirty. 
② Too heavy heat load of room (e.g. too many people). 
③ Door or windows is open. 
④ Inlet and outlet of IDU are blocked. 
⑤ Setting temperature is too high. 
⑥ Refrigerant is insufficient (e.g. refrigerant leakage). 

Poor cooling effect 

① The filter is dirty. 
② Door or window is open. 
③ Setting temperature is too low. 
④ Refrigerant is insufficient (e.g. refrigerant leakage). 

Poor heating effect 

① At starting, the IDU fan could not operate till the heat exchange become hot, for 

Indoor fan doesn’t start  
up during heating  

preventing delivering the cool air. 
② At defrosting, the IDU fan stopped due to system switch to cooling mode. For 

preventing delivering the cool air, and resume operating after defrosting. 

NOTICE! 

If air conditioner still fails to work normally after checking and handling as described above, 

please stop using it immediately and contact local service center for assistance. 

18 

Sayfa 23

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070
Tel: (+86-756) 8522218