SIROCCO2

H0723600_REVC - 2022/05

Instructions for installation and use - English
Dehumidifier
Translation of the original instructions in French 
EN

More documents on:

www.zodiac.com

Sayfa 3

 WARNINGS

Carefully read the instructions in this manual before using the unit.

GENERAL WARNINGS
•	Failure to respect the warnings may cause serious damage to the pool equipment 
or cause serious injury, even death.
•	Only a person qualified in the technical fields concerned (electricity, 
hydraulics or refrigeration) is authorised to carry out maintenance or 
repair work on the appliance. The qualified technician working on the 
appliance must use/wear personal protective equipment (such as safety 
goggles and protective gloves, etc.) in order to reduce the risk of injury 
occurring when working on the appliance.
•	Before handling the appliance, check that it is switched off and isolated.
•	The appliance is intended to be used for pools and spas for a specific purpose; it 
must not be used for any purpose other than that for which it was designed.
•	This appliance is not intended for use by individuals (including children) with 
impaired physical, sensorial or mental abilities, or persons lacking in knowledge 
and experience, unless they receive supervision or prior instructions on using the 
appliance from a person responsible for their safety. Children must be supervised 
to ensure that they do not play with the appliance.
•	This appliance can be used by children under 8 and adults with impaired physical, 
sensory or mental capabilities, or who lack experience and knowledge, if they are 
correctly supervised or have been instructed in how to use the appliance safely and 
understand the hazards involved. User cleaning and maintenance operations must 
not be carried out by children without supervision.
•	The appliance must be installed according to the manufacturer’s instructions and 
in compliance with local and national standards. The installer is responsible for 
installing the appliance and for compliance with national installation regulations. 
Under no circumstances may the manufacturer be held liable in the event of failure 
to comply with applicable local installation standards.
•	For any work other than the simple user maintenance described in this manual, the 
product should be referred to a qualified professional.
•	If the appliance suffers a malfunction, do not try to repair it yourself; instead contact 
a qualified technician.
•	Deactivating, eliminating or by-passing any of the safety mechanisms integrated 
into the appliance shall automatically void the warranty, in addition to the use of 
spare parts manufactured by unauthorised third-party manufacturers.
•	Do not spray insecticide or any other chemical (inflammable or non-inflammable) 
in the direction of the appliance, as this may damage the body and cause a fire.
•	Do not touch the fan or moving parts and do not place objects or your fingers in the 
vicinity of the moving parts when the appliance is in operation. Moving parts can 
cause serious injury or even death.
WARNINGS ASSOCIATED WITH ELECTRICAL APPLIANCES
•	The power supply to the appliance must be protected by a dedicated 30 mA Residual 
Current Device (RCD), complying with the standards and regulations in force in the 
country in which it is installed.
•	Do not use any extension lead when connecting the appliance; connect the 
appliance directly to a suitable power supply.
•	A suitable disconnection method, compliant with all local and national regulations 
on category III overvoltage, and which disconnects all poles of the power supply 
circuit, must be installed on the power supply circuit to the appliance. This 
disconnection method is not provided with the appliance and must be supplied by 
the professional fitter.
•	Before carrying out any operations, check that:
	- The required input voltage indicated on the appliance information plate 

EN

1

Sayfa 4

corresponds to the mains voltage;
	- The mains supply is compatible with the appliance's electricity needs and is 

correctly grounded.
•	In the event of abnormal operation or the release of odours from the appliance, 
turn it off immediately, unplug it from its power supply and contact a professional.
•	Before servicing or performing maintenance on the appliance, check that it is 
powered off and completely disconnected from the power supply. Moreover, 
check that the heating priority (where applicable) is deactivated and that any 
other device or accessory connected to the appliance is also disconnected from 
the power supply.
•	Do not disconnect and reconnect the appliance to the power supply when in 
operation.
•	Do not pull on the power cord to disconnect it from the power supply.
•	If the power cord is damaged, it must be replaced by the manufacturer, an 
authorised representative or a repair facility only.
•	Do not perform maintenance or servicing operations on the appliance with wet 
hands or if the appliance is wet.
•	Before connecting the appliance to the power supply, check that the connection 
unit or socket to which the appliance will be connected is in good condition and 
shows no signs of damage or rust.
•	For any component or sub-assembly containing a battery: do not recharge or 
dismantle the battery, or throw it into a fire. Do not expose it to high temperatures 
or direct sunlight.
•	In stormy weather, disconnect the appliance from the power supply to prevent it 
from suffering lightning damage.
•	Do not immerse the appliance in water (with the exception of cleaners) or mud.
WARNINGS CONCERNING APPLIANCES CONTAINING R410A REFRIGERANT
•	Do not discharge R410A fluid into the atmosphere. This is a fluorinated greenhouse 
gas, covered by the Kyoto Protocol, with a Global Warming Potential (GWP) = 2088 
(European regulation EU 517/2014).
•	In order to comply with the applicable standards and regulations in terms of the 
environment and installation, in particular Decree No. 2015-1790 and/or European 
regulation EU 517/2014, a leak test must be performed on the cooling circuit when 
the appliance is first started and at least once a year. This operation must be carried 
out by a specialist certified to test cooling appliances.
 INSTALLATION AND MAINTENANCE
•	The appliance may not be installed close to combustible materials, or the air duct 
inlet of an adjacent building.
•	With some appliances, it is essential to fit a "protection grid"-type accessory if the 
unit is installed in an area with uncontrolled access.
•	During installation, troubleshooting and maintenance, pipes may not be used as 
steps: the pipe could break under the weight, spilling coolant and possibly causing 
serious burns.
•	When servicing the appliance, the composition and state of the heat transfer fluid 
must be checked, as well as the absence of any traces of coolant.
•	During the appliance's annual sealing test in accordance with applicable legislation, 
the high and low pressure switches must be checked to ensure that they are 
securely fastened to the cooling circuit and that they cut off the electrical circuit 
when tripped.
•	During maintenance work, ensure there are no traces of corrosion or oil around 
the cooling components.
•	Before beginning work on the cooling circuit, stop the appliance and wait for a few 
minutes before fitting the temperature and pressure sensors. Some elements such 
as the compressor and piping may reach temperatures in excess of 100°C and high 
pressures with the consequent risk of severe burns.
TROUBLESHOOTING
•	All brazing must be carried out by qualified brazers.
•	Replacement pipes must always be made of copper in compliance with standard 
NF EN 12735-1.

2

Sayfa 5

•	Leak detection; pressure test:
	- never use oxygen or dry air (risk of fire or explosion)
	- use dry nitrogen or the mixture of nitrogen and refrigerant indicated on the 

information plate,
	- the test pressure for both the high and low pressure circuits must not exceed 

42 bar (for R410A) in cases where the appliance is equipped with the optional 
pressure gauge.
•	The high pressure circuit pipes are made of copper and have a diameter equal to or 
greater than 1’’5/8. A certificate as indicated in §2.1 in compliance with standard 
NF EN 10204 must be requested from the supplier and filed in the installation's 
technical file.
•	Technical data relative to the safety requirements of the various applicable directives 
are indicated on the information plate. All this information must be recorded in the 
appliance's installation manual, which must be kept in its technical file: model, 
code, serial number, maximum and minimum OT, OP, year of manufacture, CE 
marking, manufacturer’s address, coolant and weight, electrical parameters, 
thermo-dynamic and acoustic performance.

Recycling
This symbol is required by the European directive DEEE 2012/19/EU (directive on waste electrical and 
electronic equipment) and means that your appliance must not be thrown into a normal bin. It will be 
selectively collected for the purpose of reuse, recycling or creating value. If it contains any substances that 
may be harmful to the environment, these will be eliminated or neutralised. Contact your retailer for recycling 
information.

EN

3

Sayfa 6

•	 Before handling the appliance, it is vital that you read this installation and user manual, as well as the 
"Warranties" booklet delivered with the appliance. Failure to do so may result in material damage or 
serious or fatal injury and will void the warranty.
•	 Keep and pass on these documents for later viewing throughout the appliance's service life.
•	 The distribution or modification of this document in any way is prohibited, without prior authorisation 
from Zodiac®.
•	 Zodiac® is constantly developing its products to improve their quality. The information contained 
herein may therefore be modified without notice. 

❶ Specifications	
5

1.1 I Description	
5

1.2 I Dimensions and marking	
6

1.3 I Technical specifications	
7

1.4 I Operating conditions	
7

❷ Installation	
8

2.1 I Installation requirements	
8

2.2 I Installation close to the pool (wall-mounted appliance)	
9

2.3 I Connection of the condensate drainage line	
10

2.4 I Access to the electrical connection terminal boards	
11

2.5 I Electricity supply connections	
12

2.6 I Option connections	
13

❸ Use	
14

3.1 I User interface presentation	
14

3.2 I Operation	
15

3.3 I Appliance configuration	
16

3.4 I User functions	
20

❹ Maintenance	
23

4.1 I Maintenance	
23

❺ Troubleshooting	
25

5.1 I Appliance behaviour	
25

5.2 I Alarm code display	
26

5.3 I Settings	
28

5.4 I Wiring diagrams	
29

Tip: to make it easier to contact your retailer

•	 Write down your retailer's contact details to help you find them more easily and fill in the "product" 
information on the back of the manual; your retailer will ask you for this information.

4

CONTENTS

Sayfa 7

❶ Specifications

1.1 I Description

Wall mounting rail + screws (x5 Ø6 mm)

Filter

Base

“Hot water coil” kit

“Electric heater” kit

“Remote control” kit

“Built in” kit

: Included
: Available as an accessory

EN

SIROCCO2

5

Sayfa 8

1.2 I Dimensions and marking

SIROCCO2
2M
3M
5M
5T

A
1,060 mm
1,410 mm

B
300 mm

C
800 mm

B

A

A

C

C

C

Front
Side
Rear

B

B

A

A

Top
Bottom

User interface

Blower grid

Integrated wall mounting rail

Condensate drainage outlets

Filter + extraction grid

Levelling screw

Cooling section

Electrical section

6

Sayfa 9

1.3 I Technical specifications

SIROCCO2 (without options)
2M
3M
5M
5T

Voltage
220 - 240V / 1 N~/ 50 Hz
380 - 400V  
/ 3 N~/ 

50 Hz
Pollution class
I
Pollution degree
2
Overvoltage category
II
Nominal electric current requirement
A
5.5
9.8
12.1
4.7
Maximum electric current requirement
A
8.7
14.3
18.5
7.3

Minimum cable section1
mm²
3 x 2.5
5 x 2.5
3G2.5
5G2.5
Dehumidifying capacity2
L/h
2.5
3.5
5.5
5.5
Power input2
W
1,210
2,150
2,660
2,720
Air flow ("Standard" mode)
m³/h
600
800
1,000
Acoustic power: "Standard" mode
db(A)
61.5
65
63.5
64.5
Acoustic power: "Silence" mode
db(A)
58.5
62
60
61
Approximate weight
kg
72
83
103
Refrigerant gas
R410A

Refrigerant gas load
kg
0.88
1.15
1.65
1.65
TeqCO2
1.84
2.40
3.44
3.44
Refrigerant gas service pressure  
(max / min)

bar
42 / 12
MPa
4.2 / 1.2
Service temperature (max / min)
°C
65 / -16
Protecting rating
IPX4

Option “back up heating”
Power
W
2,000
3,000
4,500
4,500
Nominal electric current requirement
A
9.1
13.7
20.5
6.8
Option “hot water battery”: inlet water temperature at 70 °C minimum / 90 °C maximum
Power
W
7,070
8,110
11,090
11,090
Water flow
m³/h
0.3
0.35
0.47
0.47
Head loss
kPa
27.85
38.85
34.51
34.51
Maximum water pressure
bar
4
Option “hot water battery”: inlet water temperature at 40 °C minimum / 50 °C maximum
Power
W
2,150
3,160
3,710
3,710
Water flow
m³/h
0.18
0.27
0.31
0.31
Head loss
kPa
15.77
22.87
17.31
17.31
Maximum water pressure
bar
4

1 Values provided as a guide only for a maximum length of 20 metres, these must be verified and adjusted to suit the installation requirements and 
the installation standards of the country.
2 Model without options, under the following nominal conditions: air 30°C, humidity 70%.

1.4 I Operating conditions

Operating range1 :

•	 Dehumidification function: between 10°C and 40°C.
•	 Heating function: between 5°C and 40°C.
Optimal bathing conditions:

•	 26°C ≤ Ambient temperature in the pool room ≤ 28°C.
•	 60% ≤ Ambient relative humidity ≤ 70%.

1 Ambient temperature in the pool room.

•	 The air temperature setpoint can be adjusted to the same level as that of the water to obtain the best 
bathing conditions.

EN

7

Sayfa 10

❷ Installation

2.1 I Installation requirements

•	 When the appliance is installed and protected by a residual current device (RCD) with a maximum amperage 
of 30 mA, it should be installed at a distance of at least 2 metres from the edge of the pool.
•	 If no RCD is installed with the appliance, it should be installed at a distance of at least 3.5 metres from the 
edge of the pool.
•	 Do not lift the appliance by handling the body: use straps (not supplied, see § "1.1.1 I Positioning the 
appliance").
•	 Make sure the appliance is level, to avoid any overflow from the condensate drip tray (adjust using the two 
hexagon screws, see § “2.2 I Installation close to the pool (wall-mounted appliance)”).
•	 Only indoor installation is possible: ensure there is easy access to the appliance for maintenance and 
connections.
•	 Allow at least 10 centimetres above it for the filter. If this is not the case, the cost of handling the appliance 
will not be covered.
•	 Do not put anything in front of or on top of the blower and extraction grids.
•	 It is mandatory to install anti-vibration studs (supplied) between the appliance and wall it is mounted on.
•	 The wall should support the weight (see § “1.2 I Technical specifications”) of the appliance.
•	 For a pool room with a high ceiling or visible roof frame: destratification of the upper layers of the room = 
one or several fans with PVC blades or an air extractor with fresh air intake. Caution! 230 V AC appliances 
= must be outside volume 1 (see below),
•	 Risk of stratification:
	- height of the room < 4 to 5 metres: mechanical ventilator unit or extractor,
	- height of the room > 5 to 8 metres: ceiling fans with large blades.
•	 Building requirement: pool room = high relative humidity. Check during construction that:
	- the materials used are compatible with a swimming pool environment,
	- the walls are sufficiently waterproofed and insulated to prevent condensation from forming in the room 

when relative humidity reaches 60 to 70%,
Buildings with lightweight structures (verandas, shelters, etc.): there is no risk of deterioration of the 
structure, even in case of dew as they are designed to support this (even with a relative humidity of 70%),
•	Ventilation, renewal of air:
	- private pools: highly recommended,
	- public pools: compulsory.
The air can be renewed by:

	- a simple mechanical ventilation unit,
	- a wall or roof extractor with fresh air intake grids.
This ventilation ensures the hygienic renewal of air, the removal of any chloramines present in the air, and 
the elimination of excessively hot air, whilst contributing to the dehumidification of the room.
•	 The appliance must be installed in accordance with the IEC/HD 60364-7-702 standard and the national 
regulations in force for swimming pools.

Tips to reduce noise pollution emitted by your dehumidifier

•	 Install it in an open space (sound waves are reflected on surfaces).
•	 Activate the "Silence" mode (see § "3.3.4 Activating/deactivating "Silence" mode"), the dehumidifier 
will operate at a lower noise level with a slightly lower dehumidifying capacity.

8

Sayfa 11

2.2 I Installation close to the pool (wall-mounted appliance)

2.2.1 Positioning the appliance

•	 At least two people are required for moving the appliance.
•	 Use straps (not supplied) when lifting the appliance so as not to damage it when positioning it.
•	 Place the straps in the positions shown by the dotted lines in the following diagram:

Information: weight of appliance

•	 The left side of the appliance (as seen from the front) is heavier than the right side.

2.2.2 Selecting the location

•	 The appliance must be mounted on a wall to avoid any risk of tilting, even when it is fitted 
with a base.

1m *

EN

 : SIROCCO2

 : Condensates drain
: Air renewal system
: Fresh air intake

* minimum distance

9

Sayfa 12

•	 To mount the appliance on a (solid) wall, follow these steps:

❶

500 min
500 min

500 min
500 min

150 x4

560*

SOL

2M and 3M models
5M and 5T models

*Distance to be respected when the dehumidifier is mounted on the base. If this is not the case, this distance can be increased.
❷
❸

x5

❹

2.3 I Connection of the condensate drainage line

•	 The angle should be sufficient to ensure a correct flow.
•	 Drainage takes place through the intermediary of a syphon or funnel.
•	 Outlets underneath the appliance.
•	 Ensure the syphon is filled with water so as to avoid air entering the condensate drainage pipe.

Condensate drainage outlets (view of appliance from below)

Tip: condensate drainage
Caution, several litres of water can be drained from your appliance each day.
We strongly recommend connecting the drain to a suitable water drainage system.

10

225 x4

560*

SOL

Sayfa 13

2.4 I Access to the electrical connection terminal boards

❶
❷

❸
❹

❺
❻

EN

11

Sayfa 14

2.5 I Electricity supply connections

•	 Before any work inside the appliance, you must cut the appliance’s electricity supply as there is a risk of 
electric shock which may cause material damage, serious injury or even death.
•	 Incorrectly tightened terminals may cause the terminal box to heat up, which can invalidate the warranty.
•	 Only a qualified and experienced technician is authorised to carry out cabling work within the appliance or 
to replace the power cord.
•	 The installer must consult the electricity provider if necessary and ensure that the equipment is connected 
correctly to an electricity network with impedance under 0.095 ohm.

•	 The dehumidifier's electrical supply must be provided through a protection and circuit breaking device (not supplied) 
complying with the standards and regulations in force in the country in which it is installed.
•	 The appliance is provided for connection to a general power supply with a TT or TN-S neutral regime.
•	 Electrical protection: by circuit breaker (D curve, rating to be defined according to the table in §”1.3 I Technical 
specifications”), with a suitable dedicated residual-current device (circuit breaker or switch).
•	 Additional protection may be required during installation to guarantee the overvoltage category II.
•	 The power supply must correspond to the voltage indicated on the appliance's information plate.
•	 The power cord must be insulated against any cutting or hot elements that may damage or crush it.
•	 The appliance must be connected to an earth socket.
•	 The electrical connection lines must be fixed.
•	 Use the gland to pass the power cord into the appliance.
•	 Use the power cord (RO2V type) adapted for outdoor or buried use (or run the cable into a protection duct) with an 
external diameter of between 9 and 18 mm.
•	 We recommend burying the cable at a depth of 50 cm (85 cm under a road or path) in an electrical duct (red ribbed).
•	 If this buried cable meets another cable or pipe (gas, water, etc.), there must be more than 20 cm between them.
•	 Connect the power cord to the spring connector terminal board inside the appliance, as shown below:

❶
❷

9 - 10 mm

Pull the lever up as far as it will go, then connect the 
cable.
Return the lever back to its initial position.

12

Sayfa 15

2.5.1 Connecting the pool shutter switch

•	 Connect the pool shutter contact cables to terminals X9.5 and X9.6 as shown below.

2.6 I Option connections

Option mounting and activation :
•	 Refer to the installation and use manual supplied with the option.

2.6.1 "Hot water coil" option

•	 This option allows the dehumidifier to be used to heat the air in the room in which it is installed. A primary hot 
reservoir (exchanger, boiler, geothermal heat...) has to be mounted upstream. To do so, use the “hot water coil” kit 
available as an accessory.
•	 For the connection, consult the manual supplied with the kit.

2.6.2 "Electric heater" option

•	 This option allows the dehumidifier to be used to heat the air in the room in which it is installed. To do so, use the 
"Electric heater" kit available as an accessory.
•	 For the connection, consult the manual supplied with the kit.

2.6.3 "Remote control" option

•	 This option enables the appliance's user interface to be transferred in order to control the appliance remotely. To do 
so, use the “remote control” kit available as an accessory.
•	 For the connection, consult the manual supplied with the kit.

EN

13

Sayfa 16

❸ Use

Your dehumidifier operates based on a heat pump with extraction of the warm, humid air in the pool room and delivery 
of dryer, hotter air.
It is ideal for maintaining a humidity level that is between 60% and 70%.
When the humidity level is lower than 60%, this leads to a feeling of excessive cold when leaving the water.
When it is higher than 70%, this leads to too much moisture and condensation in the room.

3.1 I User interface presentation

3.1.1 Presentation of the display screen and function keys

Description

Multi-function display

“On/off” or “back” key

"Up" or (de)activation key for the heating function

"Down" or (de)activation key for the "Silence" mode

SET
“Adjustment” or “confirm” key

3.1.2 Description of the display screen

Symbol
Description
Steady
Flashing
Off

On/Off
Appliance switched off
/
Appliance in operation

Dehumidification
Appliance in dehumidi-
fying mode
Appliance timed
/

Heating
Appliance in heating 
mode
/
/

Defrosting
Defrosting active
/
/

Settings
Appliance in “settings” 
mode
/
/

Test mode
Test mode activated
/
/

Compressor
Compressor on
Compressor timed
Compressor idle

Fan
Fan(s) on
Fan timed
Fan(s) off

14

Sayfa 17

Electric heater
Electric heater heating
/
Electric heater off

Circulator (hot water coil 
option)
Circulator on
/
Circulator idle

Alarm
Alarm in progress
/
/

Appliance configured 
to measure in degrees 
Celsius

Celsius

/
/

“Manual” mode
Programming using 
“manual” mode.
/
/

Humidity level percentage
Appliance configured as 
a humidity sensor
/
/

3.2 I Operation

3.2.1 Switching on the appliance
•	 Power on the appliance (by switching on the general terminal board),
•	 The program version remains visible for 5 seconds then "OFF" and "KEY" is displayed before the appliance starts.
Only on Sirocco 5T models (three phased):

•	 This operation must be only be carried out by a qualified professional.
•	 The phase order controller protects the compressor. It is forbidden to invert phases:
	- On the power contactor.
	- On the compressor.
 

The phase error controller is located in the electrical unit, on the right hand side of the appliance.

•	 When the dehumidifier is switched on, check the status of the phase order controller as shown below:

OK~
OK~

Indicator light 

status

•	 If there is a phase inversion or missing phase:
1.	Disconnect the appliance from the power supply;
2.	Invert two phases directly on the appliance connection terminal board;
3.	Restore power to the appliance and check the status of the indicator lights.

EN

15

Sayfa 18

3.2.2 Starting the appliance

•	 Press and hold (longer than 3 seconds) 
.

•	 The screen displays all of the symbols along with an audible beep. The value displayed on the screen corresponds 
to the relative humidity (%). The ambient temperature can also be simultaneously displayed (°C). To do this, just set 
the heating mode to "Hetr" or "coiL". (see §3.3.2 "Configuring the heating mode").

3.3 I Appliance configuration

When the dehumidifier is installed, it must be configured to ensure optimal operation best adapted to the conditions of 
use. This can be done via the "EASY" menu (access reserved for qualified professionals and requiring an access code).

To access and browse the menus:

•	 Press and hold (longer than 3 seconds) SET .

•	 Browse using the 
 and 
 keys.

•	 Press SET to confirm (go to a sub-menu or confirm a selection).

•	 Press 
 to go back to the previous screen.

Information: list of menus

Menu
Description
Restriction

USER
Menu dedicated to users for managing setpoints
/

EASY
Menu intended for qualified professionals so that they can configure 
the appliance after the initial installation and/or adding an option.
Reserved 
for qualified 
professionals and 
requiring an access 

INIT PARA
Information menu dedicated to the appliance's status and basic 
settings

ADVI
Menu dedicated to the appliance's advanced settings (“Read” mode)

ADVDr
Menu dedicated to the appliance's advanced settings (“Write” mode)

3.3.1 Configuring the ventilation mode

•	 In the “EASY” menu, browse with the 
 or 
 keys until you reach the “P16” setting, then press SET to 
confirm.

•	 Using the 
 or 
 keys, choose the desired ventilation mode:
	- 0 = intermittent ventilation. The ventilation comes on every 30 seconds for 5 minutes.
	- 1 = permanent ventilation (default setting). The ventilation is always on.

•	 Press SET to confirm.

•	 Press 
 to go back to the previous screen.

	
Press 
 a number of times to return to the home screen.

16

code.

Sayfa 19

Information: the importance of the ventilation mode

•	 Ventilation helps to ensure that air circulates correctly, meaning that the temperature and humidity levels 
are more even throughout the room.
•	 Bathing comfort can be significantly and economically improved by improving ventilation.

3.3.2 Configuring the heating mode

When installing a heating kit ("electric heater" or "hot water coil"), the appropriate heating mode setting must be used.

•	 In the “EASY” menu, browse with the 
 or 
 keys until you reach the “P44” setting, then press SET  to 
validate.

•	 Using the 
 or 
 keys, choose between “dbsl”, “Hetr” or “coiL”.

	- dsbL = no heating option.

	- Hetr = electric heater (default setting).

	- coiL: hot water coil.

•	 Press SET to confirm.

•	 Press 
 to go back to the previous screen. 

Press 
 a number of times to return to the home screen.

Information: home screen update

•	 When the heating kit is confirmed ("electric heater" or "hot water coil") the home screen is updated with 
the simultaneous display:

	- The relative humidity level (%),
	- The ambient temperature (°C or F°) in the pool room.

Only the heating mode is confirmed at this stage of the configuration. The function will then have to be activated or 
deactivated from the home screen:

To enable the heating option:

•	 Press and hold (longer than 3 seconds) the 
 key, the screen shows “CHU ON”.

•	 Enabling the heating option is visible on-screen thanks to the 
 symbol.

•	 The symbol 
 indicates that the heating is activated but not necessarily active. The only indication that 

the heating function has started is when the 
 or 
 LED is lit.

To disable the heating option:

•	 Press and hold (longer than 3 seconds) the 
 key, the screen shows “CHU OFF”.

EN

17

Sayfa 20

3.3.3 Configuring pool shutter mode

The pool shutter mode is used to adapt the dehumidifier and heating functions to the pool status (covered/not 
covered).
When the shutter is detected as closed, the heating setpoint temperature switches to the (lower) point defined in 
setting P66 (see § 3.4.3 "Configuring setpoint temperatures").
This setting helps to reduce energy consumption during periods when no one is swimming.

Uncovered
Setpoint T (°C) = 28°C / P07

This example shows the temperature setpoint automatically switching from “P07” = 28°C to “P66” = 20°C when the pool is covered.

To activate this function you will have to:
1.	First connect the pool shutter switch (see §2.5.1 "Connecting the pool shutter switch");
2.	Activate the pool shutter mode:

•	In the “EASY” menu, browse with the 
 or 
 keys until you reach the “P67” setting, then press SET to 
confirm.

•	Using the 
 or 
 keys, select:

	- Yes = activate the automatic shutter mode (default setting).

	- No = deactivate the automatic shutter mode.

•	Press SET to confirm.

•	Press 
 to go back to the previous screen.

	
	 Press 
 a number of times to return to the home screen.

Information: advantages of the pool shutter function

•	 When the shutter is detected as fully closed no more pool water can evaporate. The dehumidification 
function is then automatically deactivated.
•	 If a dehumidification process is ongoing when the pool is covered, the function will only be deactivated 
once the humidity setpoint has been reached.

18

Covered
Setpoint T (°C) = 20°C / P66

Sayfa 21

3.3.4 Configuring the test mode

Once the installation of the dehumidifier is finished, the installer can check the appliance in test mode. This mode is 
used to force the dehumidification functions (and the heating kit, if installed).
To activate/deactivate the test mode:

•	 In the “EASY” menu, browse with the 
 or 
 keys until you reach the “P25” setting, then press SET to 
confirm.

•	 Using the 
 or 
 keys, select:

	- 0 = stop test mode (default settings)

	- 1 = start test mode.

•	 Press SET to confirm.

•	 Press 
 to go back to the previous screen. 

Press 
 a number of times to return to the home screen.

•	 When the test mode is activated, the 
 symbol is displayed.

To set the test mode duration:

•	 In the “EASY” menu, browse with the 
 or 
 keys until you reach the  “P26” setting, then press SET to 
confirm.

•	 Using the 
 or 
 keys, choose the desired duration (in minutes). The default duration is 30 minutes. Note that 
the duration must be set before running the test mode. Changes to this setting during the test will only be taken 
into account later.

•	 Press SET to confirm.

•	 Press 
 to go back to the previous screen. 

Press 
 a number of times to return to the home screen.

•	 If the test mode is manually stopped prematurely ("P25" = 0), the 
 symbol remains on the screen 
until “P26” has counted down.

Several checks can be performed in test mode:

•	 Check that hot air is coming out of the appliance's blower grids.
•	 Check that the following symbols are displayed:
Dehumidification
Heating

Depending on the test conditions, checking the condensate drainage is not mandatory.

EN

 or 

19

Sayfa 22

3.4 I User functions

3.4.1 Switching the appliance on and off

To switch the appliance on:

•	 Press and hold (longer than 3 seconds) 
.

•	 The screen displays all of the symbols along with an audible beep. The value displayed on the screen corresponds 

to the relative humidity (%). The ambient temperature can also be simultaneously displayed (°C). To do this, just set 

the heating mode to "Hetr" or "coiL". (see §3.3.2 "Configuring the heating mode").

•	 The displayed values can change significantly when the ventilation is started with the intermittent 
ventilation setting.

To switch the appliance off:

•	 Press and hold (longer than 3 seconds) 
.

20

Sayfa 23

3.4.2 Unlocking the keyboard

If the “Lock keyboard” option is activated, when no key has been pressed for 10 seconds, the keyboard automatically 
locks.
When a key is pressed, “LOC” is displayed.
To unlock the keyboard:

•	 Press and hold down (longer than 3 seconds) one of the following keys: 
, 
 or SET .
•	 “ULOC” is displayed after the screen is unlocked.

3.4.3 Configuring setpoint temperatures

•	 Press and hold (longer than 3 seconds) SET .

•	 Browse with the 
 or 
 keys until you reach the “USER” menu, then press SET to validate.

•	 Browse with the 
 or 
 keys until you reach the setting to change (refer to the “Information: list of setpoint 

settings” heading below) then press SET to validate.

•	 Set the setpoint to the chosen temperature using the 
 or 
 keys, then press SET to confirm.

•	 Press 
 to go back to the previous screen. 

Press 
 a number of times to return to the home screen.

Information: list of setpoint settings

Setting
Description

P4
Dehumidification setpoint

P7
Heating setpoint

P66
Heating setpoint (handling the automatic shutter mode)

EN

21

Sayfa 24

3.4.4 Activation/deactivation of "Silence" mode

The "Silence" mode is used to reduce the appliance’s noise level by lowering the ventilation speed when the dehumidifying 
and/or heating functions are activated.
When the "Silence" mode is activated, the appliance’s dehumidifying capacity deteriorates slightly.

Information: "Silence" mode = ZEn

•	 On the appliances' display, the “Silence” mode is named “ZEn”.

To activate the "Silence" mode:

•	 Press and hold (longer than 3 seconds) 
.

•	 The display shows the status of the "Silence" mode ("ZEn" + "On") by flashing 3 times and then returns to the initial 
screen.

•	 The duration of the "Silence" mode is set at 2 hours. The “Standard” mode is automatically reactivated 
after this 2 hour period to restore a suitable dehumidification regime; a new “Silence” mode cycle can be 
reactivated if the measured humidity level is satisfactory.

To deactivate the "Silence" mode:

•	 Press and hold (longer than 3 seconds) 
.

•	 The display shows the status of the "Silence" mode ("ZEn" + "OFF") by flashing 3 times and then returns to the initial 
screen.

Tip: using the "Silence"' mode

•	 If the relative humidity that is measured, at any moment, is higher than the level recommended for user 
comfort or the building's viability, the "Silence" mode will stop automatically to ensure an adequate level 
of dehumidification.

22

Sayfa 25

❹ Maintenance

4.1 I Maintenance

•	 Before any maintenance work on the appliance, you must cut the electricity supply as there is 
a risk of electric shock which may cause material damage, serious injury or even death.
•	 It is recommended that the appliance undergo general servicing at least on a yearly basis to 
ensure its proper operation, maintain performance levels and prevent any possible failures. 
These operations are carried out at the user's expense, by a qualified technician.

4.1.1 Monthly user maintenance

•	 Visually check the condensate drainage and check that the drainage tube is correctly positioned.
•	 Check for clogging in the filters:
	- Manually remove any accumulated fibres and dust. Vacuum if necessary.
	- Wash the filter with warm soapy water and leave to dry.
	- If necessary, replace the filter by removing it as shown below (the filter is fixed by a bracket that must be unscrewed):

❶
❷

•	 The correct maintenance of the appliance is helped by the display of a filter maintenance message which 
is programmed in relation to the ventilation time.

EN

23

Sayfa 26

4.1.2 Annual maintenance to be performed by a qualified technician

•	 Check that the electric cable connections are correctly tightened to their terminals on the terminal board, in addition 
to the contactor screws,
•	 Check that each command relay and power contactor is operational.

•	 On the Sirocco 5T, thanks to the phase order controller, any modification of the sequence of phases on 
the distribution network or on the existing electrical installation is detected. The appliance then goes into 
fault mode (see 5.2 "Alarm display").

•	 Clean the outside of the whole unit with a slightly damp cloth.
•	 Check the cleanliness of the condensation tray and drainage tube,
•	 A visual inspection of coil clogging (evaporator/condenser and hot water) can improve the appliance's performance, 
and is performed by following the disassembly procedure below (when powered off) :

❶
❷

❸

•	 Depending on the condition, clean with a bristle brush and vacuum cleaner.

24

Sayfa 27

❺ Troubleshooting

•	 Before you contact your retailer, please carry out these few simple checks using the following 
tables if a problem occurs.
•	 If the problem persists, contact your retailer.

•	
: Actions to be performed by a qualified technician only

5.1 I Appliance behaviour

The appliance is discharging 
water

•	 Your appliance is discharging water, known as condensates. This water is the 
humidity your dehumidifier condenses to dry the air.

•	 This is the dew point, which is the point at which the water vapour contained in 
the air changes states when in contact with a cold surface. This is known as the 
phenomenon of condensation. This does not mean your appliance is not working. 
This phenomenon is normal, because of the presence of humidity in the air (65% 
humidity in comfortable conditions), and a cold outside temperature.

The appliance is working but 
the windows are covered in 
water

The dehumidifier blows hot 
air even though the heating is 
absent or deactivated

•	 The dehumidification function is based on the thermodynamic principle which 
transforms part of the absorbed energy into heat, which is then transferred to the 
ventilated air flow.

•	 The dehumidifier's cooling circuit is affected by the local operating conditions. 
Lower temperatures and the moisture content of the ambient air are more likely 
to create frost.
•	 To ensure its correct operation, the appliance eliminates all traces of frost by 
initiating a short defrosting cycle lasting a few minutes.

The appliance begins defrost-
ing

•	 The noise level drops at the same time as the ventilation speed. In fact, the same 
amount of heat is transmitted with a lower air flow. The blown air is therefore 
warmer.

The blown air is warmer in 
"Silence" mode

The ventilation stays on even 
when the setpoint tempera-
ture(s) have been reached

•	 Ventilation continues for a few minutes after the temperature and humidity 
setpoints have been reached. This optimises the appliance's efficiency by 
evacuating the residual calories in the batteries that are still hot.

•	 The voltage supplied to the appliance falls below the nominal operating power, 
the fan stops operating for protection purposes until the nominal voltage is re-
established.

The fan is not running

EN

25

Sayfa 28

5.2 I Alarm code display

5.2.1 Displaying the alarm code on the screen

When an alarm is activated, the 
  icon appears on the screen:

To find out the alarm code which activated the alarm:

•	 Press and hold  SET .

•	 Press SET to enter the Selection menu.

•	 Press 
 twice.

•	 Press SET to enter the ALARM menu:

•	 Press SET , to find out the number of alarms in progress:

	- If the screen remains identical, there is only one alarm in progress.

	- If the figure increases, press SET until you return to the figure 1: the highest figure corresponds to the number of 

alarms in progress.

•	 Press 
 to display the alarm code, then 
 to return to the number of alarm .  

•	 Press 
 to exit the menu.

26

Sayfa 29

5.2.2 Alarm code meaning

Code
Description
Possible cause
Resetting

•	 Sensor has short circuited.
•	 Sensor disconnected.
•	 Faulty sensor (replace sensor).
Automatic

A01
Faulty
Humidity sensor

•	 Sensor has short circuited.
•	 Sensor disconnected.
•	 Faulty sensor (replace sensor).
Automatic

A02
Faulty
Ambient temperature sensor

•	 Sensor has short circuited.
•	 Sensor disconnected.
•	 Faulty sensor (replace sensor).
Automatic

A03
Faulty
Temperature sensor - evaporator

•	 Sensor has short circuited.
•	 Sensor disconnected.
•	 Faulty sensor (replace sensor).
Automatic

A04
Faulty
Temperature sensor - blower

A05
Ambient temperature too high
•	 Temperature outside range of 
operation.
•	 Faulty sensor.

A06
Ambient temperature too low
Automatic

A07
Maintenance alarm
•	 Reminder for global maintenance.
Manual 
 

•	 Clogged filter.
•	 Faulty sensor.
•	 Faulty fan.
Automatic

A13
Blowing temperature too high

•	 Clogged filter.
•	 Obstructed air inlet.
•	 Cooling circuit problem.
Automatic*

A14
High pressure

A15
Low pressure
•	 Cooling circuit problem.
Automatic*

A16
Fan speed
•	 Faulty fan.
•	 Electric power unstable.
Automatic*

*Automatic reactivation except if the alarm is activated more than three times in one hour.

5.2.3 Maintenance alarm

After using your appliance for some time, the alarm symbol 
 may appear on your screen, but the appliance will 
continue to operate as usual.

Checking the alarm code meaning ( see “5.2.1 Displaying the alarm code on the screen”, page 26), you may get the 
alarm code “A07”. This alarm code signals that your appliance is due for a maintenance check on the 6 subsystems :

•	 Fan.

•	 Compressor.

•	 Air heating (optional).

•	 Humidity sensor.

•	 Air blowing sensor.

•	 Defrost sensor.

We recommend that you contact an authorized technician within a month to do the necessary maintenance checks to 
maintain the long lasting operation of your appliance. 

 Only a qualified technician may check on the appliance to reset the maintenance alarm. 

Automatic

EN

27

Sayfa 30

5.3 I Settings

Menu
Setting
Description
Unit/Values

User
P4
Humidity setpoint
%

User
P7
Heating setpoint
°C

Easy Inst
P16
Type of ventilation
•	 Intermittent
•	 Permanent

Easy Inst
P25
Test mode: "Stop/Start"
•	 0 = Stop
•	 1 = Start

Easy Inst
P26
Test mode: duration
Minutes

Easy Inst
P44
Type of heating

User
P66
Heating setpoint
°C

Easy Inst
P67
Shutter mode
•	 0 = No
•	 1 = Yes

28

•	 dsbL = No heating option
•	 Hetr = Electric heater
•	 coiL = Hot water coil

Sayfa 31

5.4 I Wiring diagrams

5.4.1 SIROCCO2 2M

230 VAC

L
X2.2
X2.5

N

PE

EN

Option Apport Electrique

R1
S
R

KM2

1
1
2
2
3
3
4
4
5
5
6
6

1
2
3
4
5
6

PS
PS
HV2
HV2
HV1
HV1
NC6
C6
NO6
NO5
C5
NO4
C4
NO3
C3
NO2
C2
NO1
C1

C-
C+
B
A
GND
ITB
5V
12V
GND
M1
M2
M3
M4
M5
M6
M7
M8
M9
A01
A02
A03
A04

HP
BP

1
2
3
4
1

4

4

3

3

2

2

1

C1 : 35µF (2.5M) 

C

M

C1

1

c-pro 3

S1

S2
S3
S4

KM2

A1

THSA

THSM

A2

X9.5

X9.6

X2.4
X2.1

X9.3

X9.4

X9.1

X9.2

10 V/MLI

+10 V

Vitesse

GND

L

N

PE

29

Sayfa 32

5.4.2 SIROCCO2 3M - 5M

230 VAC

N

L
X2.2
X2.5

PE

R1

KM2

R2
R3

KM2

R1

C

C1 : 60µF (3.5M & 5M)

S
R

M

1

C1

KM1

1
1
2
2
3
3
4
4
5
5
6
6

1
2
3
4
5
6

PS
PS
HV2
HV2
HV1
HV1
NC6
C6
NO6
NO5
C5
NO4
C4
NO3
C3
NO2
C2
NO1
C1

C-
C+
B
A
GND
ITB
5V
12V
GND
M1
M2
M3
M4
M5
M6
M7
M8
M9
A01
A02
A03
A04

HP
BP

1
2
3
4
1

4

4

3

3

2

2

1

KM1

c-pro 3

S1

S2
S3
S4

KM2

THSA

THSM

A1

A2

X9.5

X9.6

X2.4
X2.1

X9.3

X9.4

X9.1

X9.2

10 V/MLI

+10 V

Vitesse

GND

L

N

PE

30

Sayfa 33

5.4.3 SIROCCO2 5T

N

L3

L2

L1
X2.2
X2.5

EN

KM1
R1 R2 R3

KM2

M

3

KM1

COP

6
6

1
1

5
5

3
3
4
4

2
2

6

5

4

3

2

1

PS
PS
HV2
HV2
HV1
HV1
NC6
C6
NO6
NO5
C5
NO4
C4
NO3
C3
NO2
C2
NO1
C1

C-
C+
B
A
GND
ITB
5V
12V
GND
M1
M2
M3
M4
M5
M6
M7
M8
M9
A01
A02
A03
A04

HP
BP

1
2
3
4

4

4

3

3

2

2

1

1

COP1

14

11

c-pro 3

S1

S2
S3
S4

KM2

THSA

A1

A2

THSM

X9.5

X9.6

X2.4
X2.1

X9.3

X9.4

X9.1

X9.2

10 V/MLI

+10 V

Vitesse

GND

L

N

PE

31

Sayfa 34

Symbol
Description
HV1
HP switch
HV2
LP switch
M7
Heating priority
M9
Remote ON/OFF
M5
Pool shutter status
M6
Fan thermal switch
M8
Fan speed reading
C1
Fan
C2
Circulator
C3
Alarm
C4
/
C5
Electrical resistor
C6
Compressor
COP
Check the order of the phases
KM1
Compressor contactor
KM2
Contactor for electric option
M1
Humidity sensor
M2
Room sensor
M3
Evaporator sensor
M4
Air outlet sensor
A01
Fan
A02
/
A02
/
A04
/

Remote display EVJ LCD

Local display EV3K

CON11 fan

CON10 fan

Electric heater option

Kit 5M : Electric heater option

Kit 3M : Electric heater option

32

Sayfa 36

Votre revendeur 
Your retailer 

Modèle appareil 
Appliance model

Numéro de série 
Serial number

Pour plus d’informations, enregistrement produit et support client :  

For more information, product registration and customer support:  

www.zodiac.com

©2022 Zodiac Pool Systems LLC. All rights reserved. ZODIAC® is a registered trademark of Zodiac International, 
S.A.S.U., used under license. All other trademarks are the property of their respective owners.

ZPCE - ZA La Balme - 31450 Belberaud - S.A.S.U. au capital de 1 267 140 € / SIRET 395 068 679 00046 / RCS TOULOUSE