Z400iQ

H0638700_REVM - 2022/06

Instructions for installation and use - English
Heat pump
Translation of the original instructions in French
EN

More documents on:
www.zodiac.com

Sayfa 3

Read the instructions in this 
manual carefully before using the 
device.
The appliance contains R32.

•	Before handling the appliance, it is vital that you read this installation and user 
manual, as well as the “Warranty” booklet delivered with the appliance. Failure 
to do so may result in material damage or serious or fatal injury and will void the 
warranty.
•	Keep and pass on these documents for later viewing throughout the appliance’s 
service life.
•	The distribution or modification of this document in any way is prohibited, without 
prior authorisation from Zodiac®.
•	Zodiac® is constantly developing its products to improve their quality; therefore, 
the information contained in this document may be modified without notice. 

GENERAL WARNINGS
•	Failure to respect the warnings may cause serious damage to the pool equipment 
or cause serious injury, even death.
•	Only a person qualified in the technical fields concerned (electricity, 
hydraulics or refrigeration) is authorised to perform any servicing 
or repairs to the appliance. The qualified technician working on the 
appliance must use/wear personal protective equipment (such as safety 
goggles and protective gloves, etc.) in order to reduce the risk of injury 
occurring when working on the appliance.  
•	Before handling the machine, ensure that the power is switched off and isolated 
from the power supply.
•	The appliance is intended to be used for pools and spas for a specific purpose; it 
must not be used for any purpose other than that for which it was designed.
•	This appliance is not intended for use by persons (including children) with reduced 
physical, sensory or mental capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction concerning use of the appliance by 
a person responsible for their safety. Children should be supervised to ensure that 
they do not play with the appliance.
•	This appliance can be used by children aged from 8 years and above and persons 
with reduced physical, sensory or mental capabilities or lack of experience and 
knowledge if they have been given supervision or instruction concerning use of 
the appliance in a safe way and understand the hazards involved. Children shall 
not play with the appliance. Cleaning and user maintenance shall not be made by 
children without supervision.
•	The appliance must be installed according to the manufacturer’s instructions and 
in compliance with local standards. The installer is responsible for installing the 
appliance and for compliance with national installation regulations. Under no 
circumstances may the manufacturer be held liable in the event of failure to comply 
with applicable local installation standards.
•	For any work other than the simple user maintenance described in this manual, the 
product should be referred to a qualified professional.
•	If the appliance suffers a malfunction, do not try to repair it yourself; instead contact 
a qualified technician.
•	Refer to the warranty conditions for details of the permitted water balance values 
for operating the appliance.
•	Deactivating, eliminating or by-passing any of the safety mechanisms integrated 
into the appliance shall automatically void the warranty, in addition to the use of 
spare parts manufactured by unauthorised third-party manufacturers.
•	Do not spray insecticide or any other chemical (inflammable or non-inflammable) 
in the direction of the appliance, as this may damage the body and cause a fire.
•	Do not touch the fan or moving parts and do not place any objects or your fingers 
in the vicinity of the moving parts during operation of the appliance. Moving parts 
can cause serious injury or even death.

1

 WARNINGS

Sayfa 4

WARNINGS ASSOCIATED WITH ELECTRICAL APPLIANCES
•	The electrical supply to the appliance must be protected by a 30 mA differential 
Residual Current protection Device (RCD), complying with the standards and 
regulations in force in the country in which it is installed.
•	For Australia and New-Zealand, this product must be installed and serviced by a 
licensed electrician inaccordance with AS/NZ 3000 - latest published/enforced 
edition, and any other local regulations.
•	Do not use any extension lead when connecting the appliance; connect the 
appliance directly to a suitable power supply circuit.
•	Before carrying out any operations, check that:
	- The voltage indicated on the appliance information plate corresponds to the 

mains voltage.
	- The power grid is adapted to the power requirements of the appliance, and is 

grounded. 
•	In the event of anormal operation or the release of unusual odours from the 
appliance, turn it off immediately, unplug it from its power supply and contact a 
professional.
•	Before any access to the appliance for service or maintenance, ensure that it is 
switched off and completely disconnected from the power supply. Furthermore, in 
addition to confirming that the heating priority (where applicable) is deactivated, 
ensure that any other equipment or accessories connected to the appliance are 
also disconnected from the power supply circuit.
•	Do not disconnect and reconnect the appliance to the power supply when in 
operation.
•	Do not pull on the power cord to disconnect it from the power supply.
•	If the power cord is damaged, it must be replaced by the manufacturer, its technician 
or a qualified person to guarantee safety.
•	Do not perform maintenance or servicing operations on the appliance with wet 
hands or if the appliance is wet.
•	Before connecting the appliance to the source of supply, ensure that the terminal 
block or supply socket to which the appliance will be connected is in good condition 
and is not damaged or corroded in any way.
•	For any component or sub-assembly containing a battery: do not recharge or 
dismantle the battery, or throw it into a fire. Do not expose it to high temperatures 
or direct sunlight.
•	In stormy weather, disconnect the appliance from the power supply to prevent it 
from suffering lightning damage.
•	Do not immerse the appliance in water or mud.
WARNINGS CONCERNING APPLIANCES CONTAINING REFRIGERANT
•	Do not release R32 fluid into the atmosphere. These are fluorinated greenhouse 
gases, covered by the Kyoto Protocol, with a Global Warming Potential (GWP) of 
675 for R32 (see EU Regulation 517/2014 on fluorinated greenhouse gases).
•	In order to comply with relevant environmental and installations standards and 
regulations such as, but not limited to, French decree No. 2015-1790 and/or the EU 
Regulation EU 517/2014, the cooling circuit must be checked for leakage at least 
once a year. This operation must be carried out by a certified cooling appliance 
specialist.

WARNINGS CONCERNING APPLIANCES CONTAINING R32 REFRIGERANT
•	This device contains R32 refrigerant, a class A2L refrigerant, which is considered to 
be potentially flammable.
•	The device must be stored in a ventilated place away from all sources of fire.
•	Install the unit outdoors.  Do not install the unit indoors or in an enclosed, non-
ventilated area outdoors.
•	Do not use means to accelerate the defrosting process or to clean, other than those 
recommended by the manufacturer.
•	The appliance shall be stored in a room without continuously operating ignition 
sources (for example: open flames, an operating gas appliance or an operating 
electric heater).

EN

2

Sayfa 5

•	Do not pierce or burn.
•	Be aware that refrigerants may not contain an odour.

INSTALLATION AND MAINTENANCE
•	The appliance may not be installed close to combustible materials, or an air duct 
inlet of an adjacent building.
•	With some appliances, it is essential to fit protection grids if the unit is installed in 
an area with uncontrolled access.
•	During installation, troubleshooting and maintenance, pipes may not be used as 
steps: the pipe could break under the weight, spilling coolant and possibly causing 
serious burns.
•	When servicing the appliance, the composition and state of the heat transfer fluid 
must be checked, as well as the absence of any traces of coolant.
•	During the appliance's annual sealing test in accordance with applicable legislation, 
the high and low pressure switches must be checked to ensure that they are 
securely fastened to the cooling circuit and that they cut off the electrical circuit 
when tripped.
•	During maintenance work, ensure there are no traces of corrosion or oil around 
the cooling components.
•	Before beginning work on the cooling circuit, stop the appliance and wait for a few 
minutes before fitting the temperature and pressure sensors. Some elements such 
as the compressor and piping may reach temperatures in excess of 100°C and high 
pressures with the consequent risk of severe burns.
TROUBLESHOOTING
•	All soldering work must be carried out by a someone qualified to do so.
•	Replacement pipes must always be made of copper in compliance with standard 
NF EN 12735-1.
•	Leak detection, pressure test:
	- never use oxygen or dry air (risk of fire or explosion) 
	- use dry nitrogen or the mixture of nitrogen and coolant indicated on the 

information plate, 
	- the test pressure for both the high and low pressure circuits must not exceed 42 

bar if the appliance is equipped with the optional pressure gauge.
•	The high pressure circuit pipes are made of copper and have a diameter equal to or 
greater than 1’’5/8. A certificate as indicated in §2.1 in compliance with standard NF 
EN 10204 will be requested from the supplier and filed with the facility's technical 
documentation.
•	Technical data relative to the safety requirements of the various applicable directives 
are indicated on the information plate. All this information must be recorded in 
the appliance's installation manual, which must be kept in the its technical file: 
model, code, serial number, maximum and minimum OT, OP, year of manufacture, 
CE marking, manufacturer’s address, coolant and weight, electrical parameters, 
thermo-dynamic and acoustic performance.

LABELLING
•	Equipment shall be labelled stating that it has been decommissioned and emptied 
of refrigerant.
•	The label shall be dated and signed.
•	For appliances containing flammable refrigerants, ensure that there are labels on 
the equipment stating the equipment contains flammable refrigerant.

RECOVERING
•	When removing refrigerant from a system. either for servicing or decommissioning, 
it is recommended good practice that all refrigerants are removed safely.
•	When transferring refrigerant into cylinders, ensure that only appropriate 
refrigerant recovery cylinders are employed. Ensure that the correct number of 
cylinders for holding the total system charge is available. All cylinders to be used 

3

Sayfa 6

are designated for the recovered refrigerant and labelled for that refrigerant (i.e. 
special cylinders for the recovery of refrigerant). Cylinders shall be complete with 
pressure-relief valve and associated shut-off valves in good working order. Empty 
recovery cylinders are evacuated and. if possible. cooled before recovery occurs.
•	The recovery equipment shall be in good working order with a set of instructions 
concerning the equipment that is at hand and shall be suitable for the recovery 
of all appropriate refrigerants including, when applicable, flammable refrigerants. 
In addition, a set of calibrated weighing scales shall be available and in good 
working order. Hoses shall be complete with leak-free disconnect couplings and in 
good condition. Before using the recovery machine, check that it is in satisfactory 
working order, has been properly maintained and that any associated electrical 
components are sealed to prevent ignition in the event of a refrigerant release. 
Consult manufacturer it in doubt.
•	The recovered refrigerant shall be returned to the refrigerant supplier in the 
correct recovery cylinder, and the relevant waste transfer note arranged. Do not 
mix refrigerants in recovery units and especially not in cylinders.
•	If compressors or compressor oils are to be removed. ensure that they have been 
evacuated to an acceptable level to make certain that flammable refrigerant does 
not remain within the lubricant. The evacuation process shall be carried out prior to 
returning the compressor to the suppliers. Only electric heating to the compressor 
body shall be employed to accelerate this process. When all is drained from a 
system, it shall be carried out safely.

Recycling
This symbol is required by European Community Directive 2012/19/UE on WEEE (Waste Electrical and 
Electronic Equipment) and means that your appliance must not be thrown into a normal bin. It will be 
selectively collected for the purpose of reuse, recycling or transformation. Any substances it may contain 
which are potentially dangerous to the environment shall be eliminated or neutralised. Request information 
on recycling procedures from your retailer.

EN

4

Sayfa 7

❶ Installation	
6

1.1 I  Selecting the location	
6

1.2 I  Hydraulic connections	
8

1.3 I  Accessing the electrical connection terminal boards	
9

1.4 I  Power connections	
9

1.5 I  Connecting options	
10

❷ Use	
11

2.1 I  Operating principle	
11

2.2 I  User interface presentation	
12

2.3 I  Operation	
13

2.4 I  User functions	
14

2.5 I  Connection to the iAquaLink™ app	
15

❸ Maintenance	
16

3.1 I  Winterizing	
16

3.2 I  Maintenance	
16

❹ Troubleshooting	
19

4.1 I  Appliance behaviour	
19

4.2 I  Error code display	
20

4.3 I  Lighting of LEDs on the printed circuit board	
21

4.4 I  Wiring diagrams	
21

❺ Characteristics	
22

5.1 I  Description	
22

5.2 I  Technical specifications	
23

5.3 I  Dimensions and marking	
23

Tip: to make it easier to contact your retailer

•	 Write down your retailer's contact details to help you find them more easily and fill in the "product" 
information on the back of the manual; your retailer will ask you for this information.

5

CONTENTS

Sayfa 8

❶ Installation

  
1.1 I  Selecting the location

•	 The appliance must be installed at 2 metres, minimum, from the surrounding edge of the 
pool. 
•	 Do not lift the appliance by the body; use straps (not provided, see § “1.1.1 I Setting up the 
device“).
•	 Exercice care during handling of the device. The evaporator (marking 
 in § “5.3 I Dimensions 
and marking“) can be easily damaged.
•	 The evaporator (marking 
 in § “5.3 I Dimensions and marking“) may contain 
sharp edges which can cause injury.
In order to prevent any injury, wear protective gloves during servicing 
operations which may involve contact with the evaporator.

•	 Only an outdoor installation is possible, provide free space around the appliance according to diagram  § ‘’1.2 I 
Hydraulic connections’’.
•	 Place the appliance on its anti-vibration blocks (integrated under its base, height adjustable) on a stable, solid and 
level surface, 
•	 This surface must be able to bear the weight (voir § 5.2 I “Technical specifications”) of the appliance (in particular in 
the case of installation on a roof, a balcony or any other support).  

View of the appliance base from below for installing the anti-vibration blocks

(MD4 / MD5 / MD7 / TD7 models)

View of the appliance base from below for installing the anti-vibration blocks

(MD8 / TD8 / MD9 / TD9 models)

The appliance must not be installed: 

•	 With the blowing towards a permanent or temporary obstacle (awning, brushwood, etc.) less than 5 metres away, 
•	 Within range of water or mud jets, sprays or run-off (take the effect of the wind into account),
•	 Near a heat source or flammable gas, 
•	 Near high-frequency equipment,
•	 In a location where it would be subject to snow build-up,
•	 In a location where it might be flooded by the condensates produced by the appliance when operating.

EN

: front
: rear
: connections 
: Anti-vibration blocks

6

Sayfa 9

Tip: reduce any noise annoyance from your heat pump

•	 Do not install it under or towards a window. 
•	 Do not tilt it towards your neighbours. 
•	 Install it in an open space (sound waves are reflected on surfaces). 
•	 Install an acoustic screen around the heat pump, respecting the distances (see diagram § «1.2 I Hydraulic 
connections»).
•	 Install 50 cm of flexible PVC pipe at the heat pump water inlet and outlet to absorb vibrations. 
•	 Increase the filtration time by 50% and activate "silence" mode. The heat pump will run for longer 
with less power, but much more quietly and with an improved COP (energy savings). «Silence» mode is 
particularly well suited for maintaining the water temperature once the setpoint temperature has been 
reached.

1.1.1 Setting up the device

•	 Use straps (not supplied) to lift the device to prevent damage during installation.

7

 : Strap

Sayfa 10

  
1.2 I  Hydraulic connections

•	 The device will be connected with a Ø50 PVC pipe, using the half union connectors supplied (see § ‘’5.1 I  Description’’), 
to the pool's filtration circuit, after the filter and before the water treatment.
•	 Respect the direction of hydraulic connection.
•	 A by-pass must be installed to make it easier to work on the appliance.

•	 To evacuate the condensates, fit a Ø18 pipe on the grooved elbow mounted under the appliance base.
•	 The elbow can be oriented at an angle of 280° beneath the appliance.

Condensate drainage elbow (view of the device from below)

Tip: condensate drainage
Caution, several litres of water can be drained from your appliance each day. We strongly recommend 
connecting the drain to a suitable water drainage system. 

: water inlet valve
: by-pass valve
: water outlet valve
: water inlet adjustment valve 
(optional)

EN

: water outlet adjustment valve 
(optional)

: water treatment
* minimum distance

8

Sayfa 11

  
1.3 I  Accessing the electrical connection terminal boards

Unscrew the 2 screws
Slide the door downwards

  
1.4 I  Power connections

•	 Before any work inside the appliance, you must cut the electricity supply to the appliance 
as there is a risk of electric shock which may cause material damage, serious injury or even 
death. 
•	 Incorrectly tightened terminals may cause the terminal box to heat up, which can invalidate 
the warranty.
•	 Only a qualified and experienced technician is authorised to carry out cabling work within the 
appliance or to replace the power cord.
•	 The installer must consult the electricity provided if necessary and ensure that the equipment 
is connected correctly to an electricity network with impedance under 0.095 ohm.

•	 The heat pump's electrical supply must be provided through a protection and circuit breaking device (not supplied) 
complying with the standards and regulations in force in the country where it is installed,
•	 The appliance is provided for connection to a general power supply with a TT or TN.S neutral regime.
•	 Electrical protection: by circuit breaker (D curve, rating to be defined according to the table § ‘’5.2 I  Technical 
specifications’’), with a suitable dedicated differential protection device (circuit breaker or switch).
•	 Additional protection may be required during installation to guarantee the II overvoltage category.
•	 The power supply must correspond to the voltage indicated on the appliance's information plate.
•	 The power cord must be insulated against any cutting or hot elements that may damage or crush it.
•	 The appliance must be connected to an earth socket.
•	 The electrical connection lines must be fixed.
•	 Use the gland to pass the power cord into the appliance.
•	 Use the power cord (RO2V type) adapted for outdoor or buried use (or run the cable into a protection duct) with an 
external diameter of between 9 and 18mm. 
•	 We recommend burying the cable at a depth of 50 cl (85 cm under a road or path) in an electrical duct (red ribbed). 
•	 If this buried cable meets another cable or pipe (gas, water, etc.), there must be more than 20 cm between them.
•	 Connect the power supply cord to the spring-cage terminal block (see § «1.4.1 I Wiring on a spring-cage terminal 
block») inside the appliance.

1.4.1 Wiring on a spring-cage terminal block

•	 Pull the lever to the maximum, then connect the cable(s) (see picture ❶).
•	 Return the lever to its original position (see image ❷).
❶
❷

9

Sayfa 12

  
1.5 I  Connecting options

Connecting the "Heating priority" and "On/off command" options:
•	 Before any work inside the appliance, you must cut the electricity supply to the appliance 
as there is a risk of electric shock which may cause material damage, serious injury or even 
death.
•	 There is a risk of electrical return current, injuries, material damage and death when working 
on terminals 1 to 8.
•	 Any connection error with terminals 1 to 8 may damage the appliance and invalidated its 
warranty.
•	 Terminals 1 to 8 are dedicated to the options and must never be used to directly supply other 
equipment.
•	 Use cables with a section of at least 2x0.75 mm²,  RO2V type and with a diameter between 8 
and 13 mm.

Before connecting any options: remove the seal (above the cable gland) and install the cable gland provided in order to 
pass the cables into the appliance. The cables used for the options and the power cord must be kept separate (risk of 
interference) using a collar inside the appliance just after the glands.

1.5.1 "Heating priority" option

•	 This function helps to keep the water temperature constant by checking the water temperature at regular time 
intervals (minimum 5 minute cycle every 120 minutes) by filtration pump control. The filtration is kept operating if 
the pool temperature is below the temperature requested.
•	 For the connection, connect the filtration timer to terminals 1 and 2 (dry contact, no polarity, maximum intensity 8A).

1

1- 
2: power for the filtration pump power contactor coil

: filtration timer

2

: power contactor (tripolar or bipolar) for the filtration system pump motor

: separate cable for the "heating priority" function

: heat pump terminal board

: fuse

1.5.2 Remote "on/off" control option

•	 This option enables the "on/off" button function to be transferred via a switch or a home automation system installed 
remotely.
•	 For the connection, remove the shunt between terminals 7-8 and connect the wire of the switch in place (potential 
free contact, no polarity, 220-240V ~ 50Hz).

: heat pump terminal board

: remote "on/off" switch

: separate connection wire

EN

10

Sayfa 13

❷ Use

  
2.1 I  Operating principle

2.1.1 General operation

Your heat pump uses the calories (heat) in the air to heat up your pool's water. The process to heat your pool's water to 
the temperature you want may take a few days as it depends on the weather conditions, your heat pump's power and 
the difference between the water temperature and the temperature you want. 
The warmer and damper the air, the better your heat pump will perform. The outdoor parameters for optimum operation 
are an air temperature of 27°C, a water temperature of 27°C and 80% relative humidity.

Tip: improve your pool's temperature rise and maintenance

•	 Anticipate the commissioning of your pool far enough in advance before you use it. 
•	 For the temperature rise, set the water circulation to continuous operation (24/24).
•	 To maintain the temperature throughout the season, run "automatic" circulation for at least 12 hours/
day (the longer this time the longer the heat pump will have enough operating range to heat up).
•	 Cover the pool with a sheet (bubble canopy, canvas, etc.) to prevent heat loss.
•	 The heat pump will be even more efficient if it operates during the warmest hours of the day.
•	 Keep the evaporator clean.
•	 Set the temperature you want and let the heat pump run (adjusting the setpoint to maximum will not 
heat the water more quickly).
•	 Connect the "Heating priority"; the filtration pump and heat pump operating time will be set according 
to requirements.

2.1.2 Operating modes (default settings)

: External air temperature

: Heat pump shutdown, outside of operating range

: Forced "Boost" mode

: Possibility of selecting the "Boost" or "Silence" operating mode

: Forced "Silence" mode

* depending on model, see § «5.2 I Technical specifications» page 26.

2.1.3 Precautions

•	 Even though the appliance can be used all year round, certain precautions must be taken to 
avoid damaging the condenser (for the precautions specific to winterising, refer to § 3.1).
•	 If the heat pump is subjected to extended exposure to negative outdoor temperatures 
(excluding winterising period), you must:

	- Activate the ‘‘Heating Priority’’ option: the filtration pump will operate while the pool’s 

temperature is below the heat pump’s setpoint temperature. If the setpoint is reached, the 
pump will operate for 5 minutes every 2 hours.
	- Make sure that the pool’s filtration pump is activated at least every 4 hours if the ‘‘Heating 

Priority’’ option is not activated on the heat pump. 

11

Sayfa 14

  
2.2 I  User interface presentation

•	 To lock or to unlock the keypad: simultaneously press 
 and 
 for 3 seconds.

2.2.1 Presentation of the display screen and function keys

Actual water temperature* 
*Displays the temperature measured during the last operation of the heat pump.

"On/off" button
Go back in the menus

Change settings button
Activate/deactivate "Silence" mode

 
Value setting buttons

2.2.2 Description of the display screen

Symbol
Name
Steady
Flashing
Off

Water flow
Water flow okay
Water flow too low or 
missing
Appliance switched off

Air temperature
/
Air temperature out of 
operating range

“Cold” mode
“Cold" mode activated
/
"Cold" mode 
desactivated

"Silence" mode
"Silence" mode 
activated
/
"Silence" mode 
desactivated

Wi-Fi
Wi-Fi connected
Wi-Fi pairing in 
progress
Wi-Fi not connected

2.2.3 Description of the LEDs showing the «appliance status»

LED
Appliance status
Meaning

Steady green
OK
Temperature reached or operation in "hot" mode

Steady blue
OK
Operation in "cold" mode

Steady red
Error in progress
Error in progress, see error message on the interface and meaning 
(see § ‘’4.2 I  Error code display’’)

The appliance shuts down after more than 4 errors in one hour and 
requires a manual restart after correcting the error (see § ‘’4.2 I  Error 
code display’’)

Flashing red
Stopped

Off
Stopped
Device off or not connected to the power supply

EN

Air temperature in the 
operating range

12

Sayfa 15

  
2.3 I  Operation

•	 Check that there are no tools or other foreign objects in the machine.
•	 The panel that provides access to the technical section (see § «5.3 I Dimensions and marking») must be put back in 
place.
•	 Set the valves as follows: valve B wide open, valves A, C, D and E closed.

•	 An incorrect by-pass setting may cause the heat pump to malfunction.

•	 Check that the hydraulic connections are correctly tightened and that there are no leaks.
•	 Check that the appliance is stable.
•	 Turn on the water flow (by activating filtration).
•	 Close valve B gradually so that the filter pressure is increased by 150g (0.150 bars).
•	 Open valves A, C and D fully then valve E by half (the air which has built up in the heat pump condenser and the 
filtration circuit will bleed out). If valves D and E are not present, open valve A wide and close valve C by half.
•	 Connect the power supply to the heat pump.

•	 The heat pump is on standby 

•	 Press 
 for 2 seconds: 
 (software version vary depending on the appliances) is displayed for 4 seconds, 

the last water temperature measured is then displayed 
.
This value varies depending on the last temperature recorded during the last connection.

If no water flow was present during the last connection, the screen will display the value 
.

•	 Set the desired temperature (called the "temperature setpoint" ) (see § ‘’2.4.2  Adjusting the temperature setpoint’’).

After the start-up steps for your heat pump: 

•	 Shut down the water circulation temporarily (by stopping the filtration or closing valve B or C) to check that you 
appliance stops after a few seconds (via the activation of the flow switch).
•	 Reduce the setpoint temperature to below the water temperature to check that the heat pump stops operating. 
•	 Switch off the heat pump by pressing and holding 
 for 2 seconds and check that it stops.

13

: water inlet valve

: by-pass valve

: water outlet valve

: water inlet adjustment valve (optional)

: water outlet adjustment valve (optional)

Sayfa 16

  
2.4 I  User functions

2.4.1 Locking/unlocking the keyboard

To lock or to unlock the keypad, press and hold 
 and 
 simultaneously for 3 seconds: 
 or 
.

2.4.2  Adjusting the temperature setpoint

•	 Press 
 or 
: the temperature setpoint is displayed and flashes, 
•	 Press 
 to increase the temperature by 0.5 °C*, 
•	 Press 
 to reduce the temperature by 0.5 °C**.
•	 Press 
 to confirm the desired setpoint temperature.
•	 The settings screen is automatically exited after 3 seconds of inactivity on the keypad or by pressing and releasing 
.
The heat pump stops automatically when the pool reaches the required temperature.

*Maximum setpoint temperature = 32 °C.
**Minimum setpoint temperature = 15 °C.

If the setpoint temperature has not been confirmed by pressing 
,  it will not be saved if the interface 
returns to the home screen (which takes place automatically after 3 seconds of inactivity on the keypad or 
by pressing and releasing 
).

2.4.3 Activating/deactivating “silence” mode

«Silence» mode is used to reduce the noise level emitted by the heat pump.
The appliance will operate for a longer period of time with less power, however with a lower noise level.

There are 2 ways to activate the “Silence” mode:

1st method

•	 Press and release
, the symbol 
 will light up.

2nd method

•	 Press and hold 
 

•	 Press 
  or 
 to display: 
.

•	 Press and release 
, the symbol 
 will light up.

•	 The home screen automatically reappears after 60 seconds of inactivity on the keypad or by pressing and releasing 
.

To deactivate the “Silence” mode, redo the manipulation, the symbol 
 will go out.

2.4.4 Activating/deactivating “cold" mode

Activation of «Cold» mode allows the machine’s cycle to be automatically reversed to cool the pool water when it 
exceeds the setpoint temperature by more than 2°C.

•	 Press and hold 

•	 Press 
 or 
 to display : 

•	 Press and release 
, the symbol 
 will light up.

•	 The home screen automatically reappears after 60 seconds of inactivity on the keypad or by pressing and releasing 
.

To deactivate the “cold/cooling” mode, redo the manipulation, the symbol 
 will go out.

«Cold» mode does not allow cooling to be activated manually.
For immediate activation, activate «Cold» mode then return to the main screen and lower the setpoint 
temperature to at least 2 degrees below the measured water temperature.

EN

14

Sayfa 17

  
2.5 I  Connection to the iAquaLink™ app

The Z400iQ heat pump may be controlled by remote, from a smartphone or tablet, via the iAquaLink™ app available for 
iOS and Android systems. 

Before you install the app, you must:
•	 Use a smartphone or tablet connected to Wi-Fi.
•	 Use a Wi-Fi network with a reasonably powerful signal when connecting to the heat pump.
•	 Have your home Wi-Fi network password at the ready.

❶. Download the iAquaLink™ app from the App Store (iOS) or Google Play Store (Android) then create an iAquaLink™ 
account (if the app is already installed, move onto the next step).

❷. Open the app then add the heat pump to the list of appliances, following the steps described on the smartphone 
or tablet.

•	 For the first step (pairing), stay near the appliance.

15

Sayfa 18

❸ Maintenance

  
3.1 I  Winterizing

•	 Although the device may be used year around, in the event that it will not be used during the 
winter months, proper winterizing is necessary in order to prevent damage to the condenser. 
Damage due to failure to properly winterize the unit when it is not use is not covered by the 
warranty.
•	 To prevent condensation from damaging the appliance: cover the appliance with the 
winterising cover supplied (do not hermetically-seal the appliance inside a cover).

•	 Set the regulator to "standby" mode by pressing and holding 
 for 2 seconds and disconnect the power supply, 
•	 Open valve B,
•	 Close valves A and C and open valves D and E (if present), 
•	 Make sure that there is no water circulating in the heat pump, 
•	 Drain the water from the condenser (risk of freezing) by unscrewing the two water inlet and outlet connectors on the 
back of the heat pump, 
•	 In the case of full winterizing for the pool (complete shutdown of the filtration system, bleed the filtration circuit 
or even pool drainage): tighten the two connectors by one turn to prevent any foreign bodies from getting into the 
condenser, 
•	 In the case of winterizing for the heat pump only (shutdown of the heating only, the filtration keeps running): to not 
tighten the connectors but add 2 caps (provided) on the condenser's water inlets and outlets.
•	 We recommend that you put the aired winterizing micro cover (provided) on the heat pump.

  
3.2 I  Maintenance

•	 Before performing any maintenance operation on the appliance, you must cut the electricity 
supply as there is a risk of electric shock which may cause material damage, serious injury or 
even death.
•	 It is recommended that the appliance undergo general servicing at least on a yearly basis 
to ensure proper operation, maintain performance levels and potentially prevent certain 
failures. These operations are carried out at the user's expense by a qualified technician.

3.2.1 Safety instructions concerning appliances containing R32 refrigerant

Area check
•	 Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the 
risk of ignition is minimised.
Work procedure
•	 Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being 
present while the work is being performed.
General work area
•	 AIl maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. 
Work in confined spaces shall be avoided.

Check for the presence of refrigerant
•	 The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician 
is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is 
suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
Check for the presence of a fire extinguisher
•	 If any work involving heat is to be conducted on the refrigerating equipment or any associated parts, appropriate 
fire extinguishing equipment shall be available to hand. Have a dry powder or CO2, fire extinguisher adjacent to the 
charging area.
No source of ignition
•	 No person carrying out work in relation to a refrigerating system which involves exposing any pipe work shall use 
any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, 
including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and 
disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the 
area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. «No 
Smoking» signs shall be displayed.
Area ventilation

EN

16

Sayfa 19

•	 Prior to penetrating the unit in any way to perform any required service, ensure that the area is open and adequately 
ventilated. Proper ventilation, to allow for safe dispersion of any refrigerant which may be inadvertently released to 
the atmosphere, should be maintained while service is being performed on the unit.
Refrigeration equipment check
•	 The manufacturer’s service and maintenance guidelines must be followed at all times.  When replacing any electrical 
components, be sure to use only components which are of the same type and rating and which are recommended/
approved by the manufacturer.  If in doubt, consult the manufacturer’s technical department for assistance.
•	 The following checks shall be applied to installations using flammable refrigerants:
	- if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
	- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
	- refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance 

which may corrode refrigerant containing components, unless the components are constructed of materials which 
are inherently resistant to being corroded or are suitably protected against being so corroded.
Electrical component check
•	 Repair and maintenance to electrical components shall include initial safety checks and component inspection 
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit 
until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, 
an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties 
are advised.
•	 Initial safety checks shall include:
	- that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
	- that no live electrical components and wiring are exposed while charging, recovering or purging the system;
	- that there is continuity of earth bonding.
Repair of insulated components
•	 During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked 
upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment 
during servicing, then a permanently operating form of leak detection shall be located at the most critical point to 
warn of a potentially hazardous situation.
•	 Particular attention shall be paid to the following to ensure that by working on electrical components, the casing 
is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive 
number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.
•	 Ensure that the apparatus is mounted securely.
•	 Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of 
preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s 
specifications.
Repair of intrinsically safe components
•	 Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed 
the permissible voltage and current permitted for the equipment in use.
•	 Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable 
atmosphere. The test apparatus shall be at the correct rating.
•	 Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant 
in the atmosphere from a leak.
Wiring
•	 Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other 
adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from 
sources such as compressors or fans.
Detection of flammable refrigerant
•	 Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant 
leaks. A halide torch (or any other detector using a naked flame) shall not be used.
•	 The following leak detection methods are deemed acceptable for all refrigerant systems.
•	 Electronic leak detectors may be used to detect refrigerant leaks but, in the ease of flammable refrigerants, the 
sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-
tree area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak 
detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant 
employed, and the appropriate percentage of gas (25% maximum} is confirmed.
•	 Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine 
shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
•	 If a leak is suspected, all naked names shall be removed/extinguished.
•	 If a leakage of refrigerant is found which requires brazing. all of the refrigerant shall be recovered from the system. or 
isolated (by means of shut off valves} in a part of the system remote from the leak.
Removal and discharge
•	 When breaking into the refrigerant circuit to make repairs - or for any other purpose - conventional procedures shall 
be used. However, for flammable refrigerants it is important that best practice is followed since flammability Is a 
consideration. The following procedure shall be adhered to:

	- remove refrigerant;
	- purge the circuit with inert gas (optional for A2L);

17

Sayfa 20

	- evacuate (optional for A2L);
	- purge with inert gas (optional for A2L);
	- open the circuit by cutting or brazing.
•	 The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable 
refrigerants other than A2L refrigerants, the system shall be purged with oxygen-free nitrogen to render the appliance 
safe for flammable refrigerants. This process may need to be repeated several times. Compressed air or oxygen shall 
not be used for purging refrigerant systems.
Loading procedures
•	 Ensure that the outlet tor the vacuum pump is not close to any potential ignition sources and that ventilation is 
available.
•	 In addition to conventional charging procedures, the following requirements shall be followed.
	- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines 

shall be as short as possible to minimise the amount of refrigerant contained in them.
	- Cylinders shall be kept in an appropriate position according to the instructions.
	- Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
	- Label the system when charging is complete (if not already).
	- Extreme care shall be taken not to overfill the refrigerating system.
•	 Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-
tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving 
the site.
Dismantling
•	 Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and 
all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried 
out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It 
is essential that electrical power is available before the task is commenced.
1.	Become familiar with the equipment and its operation.
2.	Isolate system electrically.
3.	Before attempting the procedure, ensure that:
	- mechanical handling equipment is available. if required. for handling refrigerant cylinders;
	- all personal protective equipment is available and being used correctly:
	- the recovery process is supervised at all times by a competent person;
	- recovery equipment and cylinders conform to the appropriate standards.
4.	Pump down refrigerant system, if possible.
5.	If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system
6.	Make sure that cylinder is situated on the scales before recovery takes place.
7.	Start the recovery machine and operate in accordance with instructions.
8.	Do not overfill cylinders (no more than 80 % volume liquid charge).
9.	Do not exceed the maximum working pressure of the cylinder, even temporarily.
10.	When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the 
equipment are removed from site promptly and alt isolation valves on the equipment are closed off.
11.	Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.

3.2.2 User maintenance

•	 Make sure that the ventilation grid is not blocked by any foreign bodies.
•	 Clean the evaporator (for location see § ‘’5.3 I  Dimensions and marking’’) using a soft brush and a fresh water spray 
(disconnect the power cable); do not fold over the metal wings, then clean the condensate drainage line to remove 
any impurities that may be blocking it.
•	 Do not use a high pressure jet. Do not spray with rain water, salt water or water which is full of minerals.
•	 Clean the outside of the appliance using a solvent-free product; a specific «PAC NET» cleaning kit is available as an 
accessory in the Zodiac catalogue for this purpose (see § ‘’5.1 I  Description’’).

3.2.3 Maintenance to be carried out by a qualified technician

•	 Please read the safety instructions before performing any of the maintenance operations 
described below, see ‘’3.2.1 Safety instructions concerning appliances containing R32 
refrigerant’’

•	 Check that the control system is operating correctly.
•	 Check that the condensates flow correctly when the appliance is in operation.
•	 Check the safety mechanisms.
•	 Check the connection of the metal masses to the earth.
•	 Check that the electrical cables are correctly tightened and connected and that the switch box is clean.

EN

18

Sayfa 21

❹ Troubleshooting

•	 If a problem occurs, before you contact your retailer, please carry out these few simple checks 
using the following tables. 
•	 If the problem continues, contact your retailer.

•	
: Actions to be performed by a qualified technician only

  
4.1 I  Appliance behaviour

•	 When the setpoint temperature is reached, the heat pump stops heating: the water temperature 
is higher than or equal to the setpoint temperature.
•	 When the water flow rate is zero or is not enough, the heat pump stops: check that the water is 
circulating correctly in the heat pump (see § ‘’2.2 I  User interface presentation’’) and that the 
hydraulic connections are correct.
•	 The heat pump stops when the outdoor temperature falls below -12 °C.
•	 It may be that the heat pump has detected an operating fault (see § ‘’4.2 I  Error code display’’). 
•	 If you have checked these points and the problem persists: contact your retailer.

The appliance 
does not start 
heating straight 
away

•	 Often called condensates. This water is the moisture contained in the air which condenses 
on contact with certain cold mechanisms in the heat pump, especially on the evaporator. The 
damper the air, the more condensates your heat pump will produce (your appliance may drain 
several litres of water per day). This water is retrieved by the base of the heat pump and drained 
by the condensate drainage elbow (see § ‘’1.2 I  Hydraulic connections’’). 
•	 To check that the water is not coming from a leak in the pool circuit on the heat pump, shut 
down the heat pump and run the filtration pump for the water to circulate in the heat pump. If 
the water continues to flow through the condensate drainage lines, there is a water leak in the 
heat pump; contact your retailer.

The appliance 
is discharging 
water 

•	 Your heat pump will soon switch to its defrost cycle to melt the ice.
•	 If your heat pump cannot manage to defrost its evaporator, it will stop itself; this means that the 
outdoor temperature is too low (below -12 °C).

The evaporator is 
iced over

•	 The machine has come to the end of the defrost cycle; water has changed to gaseous state and 
passes through the grid.
•	 If your heat pump is not in its defrost cycle, this is not normal. Switch off and disconnect the 
heat pump immediately and contact your retailer.

The appliance is 
"smoking"

•	
 If there is no display, check the supply voltage and the F2 fuse.
•	 When the setpoint temperature is reached, the heat pump stops heating: the water temperature 
is higher than or equal to the setpoint temperature.
•	 When the water flow rate is zero or is not enough, the heat pump stops: check that the water is 
circulating correctly in the heat pump (see § ‘’2.2 I  User interface presentation’’).
•	 The heat pump stops when the outdoor temperature falls below -12 °C or rises above +40 °C.
•	 It may be that the heat pump has detected an operating fault (see § ‘’4.2 I  Error code display’’). 

The appliance is 
not working

•	 Check that the automatic water filling controller (see diagram in § «2.3 I Operation») is not 
stuck in the open position: this will keep supplying cold water into the pool and will prevent the 
temperature from rising.
•	 There is too much heat loss. Install a heat insulated cover on your pool.
•	 The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 
it to restore its performances (see § ‘’3.2 I  Maintenance’’).
•	 Check that the external environment is not hindering the heat pump (see § ‘’❶ Installation’’).

The appliance 
is working 
but the water 
temperature 
does not increase

•	
 Check that the heat pump is the right size for this pool and its environment.
The fan is 
running but 
the compressor 
stops from time 
to time with no 
error message

•	 If the outdoor temperature is low, the heat pump performs defrost cycles under normal 
operation.
•	 The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 
it to restore its performances (see § ‘’3.2 I  Maintenance’’).

The appliance 
trips the circuit 
breaker

•	
 Check that the circuit breaker is correctly dimensioned and that the cable section used is 
appropriate (see § ‘’5.2 I  Technical specifications’’).

•	
 The supply voltage is too low: contact your electricity supplier.

19

Sayfa 22

  
4.2 I  Error code display

Display of
Possible causes
Solutions
Reset

ST4 sensor temperature 
too low

Wait until the exterior 
temperature rises
Automatic

Exchanger protection 
in "cooling" mode

ST3 sensor temperature 
over 60°C or evaporator 
scaled up

Clean the evaporator, if 
problem  persists, call a qualified 
technician

High temperature 
error on evaporator in 
"cooling" mode

Cabling not respected on 
the appliance's supply 
terminals,

 Invert phases on power 
terminals (appliance switched 
off )

By electricity supply 
disconnection or by pressing 
Electricity provider has 
changed the order of the 
phases

Phase order fault (on 
three phase models 
only)

Contact the electricity provided 
to find out if your installation has 
been modified.
Temporary disconnection 
of the power supply to one 
or more phases

Pressure fault in the low 
pressure circuit (if problem 
persists after resetting)

Call a qualified technician

Cooling circuit low 
pressure fault

Exchanger clogged with dirt
 Clean the water exchanger

Insufficient water flow
 Increase flow using the by-
pass, check that the pool filter is 
not clogged

Cooling circuit high 
pressure fault

Air and water emulsion has 
passed into the appliance
 Check the pool's hydraulic 
circuit

Flow switch is blocked 
 Check the flow switch

Compressor discharge 
temperature too high
Call a qualified technician

Compressor discharge 
temperature fault

Sensor is faulty or offline
 Reconnect or change the 
sensor

ST1 sensor fault - 
water inlet sensor

Sensor is faulty or offline
 Reconnect or change the 
sensor

ST4 sensor fault - fluid 
line sensor

Sensor is faulty or offline
 Reconnect or change the 
sensor

ST3 sensor fault - 
Defrost sensor

Automatic if ST3 sensor 
temperature below 45 °C

EN

•	 «Steady red» LED = 
automatic
•	 «Flashing red» LED = 
press 

•	 «Steady red» LED = 
automatic
•	 «Flashing red» LED = 
press 

•	 «Steady red» LED = 
automatic
•	 «Flashing red» LED = 
press 

By electricity supply 
disconnection or automatic 
if the fault disappears

By electricity supply 
disconnection or automatic 
if the fault disappears

By electricity supply 
disconnection or automatic 
if the fault disappears

20

Sayfa 23

Sensor is faulty or offline
 Reconnect or change the 
sensor

ST2 sensor fault - air 
inlet sensor

Sensor is faulty or offline
 Reconnect or change the 
sensor

ST5 sensor fault - 
compressor discharge 
sensor

Bad connection between 
the boards
 Check the connectors on the 
link cable between the boards
•	 «Steady red» LED = 
automatic
•	 «Flashing red» LED = 
press 
Board power supply fault
 Check the boards' power 
supply

Communication 
fault between the 
regulation board and 
the display board

Faulty boards
 Replace the boards

Wait until the water temperature 
rises (above 35°C) or switch to 
“Hot” mode if the appliance is in 
“Cooling”mode

ST1 sensor temperature 
too low

Condenser protection

  
4.3 I  Lighting of LEDs on the printed circuit board

LED1
LED2
LED3
LED4
LED5

No errors
Appliance 
switched off

No errors
Appliance in 
operation

Error 01

Error 02

Error 03

Error 04

Error 05

Error 06

Error 07

Error 08

Error 09

Error 10

Error 11

Error 12

Error 13

: LED steadily lit
: LED flashing
Empty: LED off

  
4.4 I  Wiring diagrams

Wiring diagrams are available at the end of the document see ‘’Schémas électriques / Wiring 
diagrams / Schaltplan / Elektrischschema / Esquema eléctrico / Esquema eléctrico / Schema 
elettrico’’

21

By electricity supply 
disconnection or automatic 
if the fault disappears

By electricity supply 
disconnection or automatic 
if the fault disappears

Automatic

Sayfa 24

❺ Characteristics

  
5.1 I  Description

 
    
 
    
 * 
         
 * 
     
*In the appliance's box

A
Z400iQ

B
Winterizing cap (x2) 

C
Ø50 connector to be glued (x2)

D
Winterizing cover

Heating priority

E
PAC NET
(cleaning product)

 : supplied 

: available as an accessory	

EN

22

Sayfa 25

  
5.2 I  Technical specifications

Z400iQ
MD4
MD5
MD7
TD7
MD8
TD8
MD9
TD9

Operating temperatures
air
 -12 to 40 °C
-12 to 38 °C
-12 to 35 °C
water
15 to 32°C
Defrosting by forced air circulation
T°C air > 10°C
Defrosting by cycle inversion
T°C air < 10°C

Voltage
220-240V / 1 / 50 Hz
380-
415V 
/ 3 /
50 Hz

380-
415V 
/ 3 /
50 Hz
Admissible variation in voltage
± 10 %
Nominal absorbed intensity*
A
6,9
10,1
13,9
6,1
16,2
7,7
19,4
8,5
Maximum current input
A
10
15
18,2
7,4
26
9,2
35,2
11,4

Minimum cable section**
mm²
3 x 2,5
5 x 2,5
3 x 6
5 x 2,5
3 x 6
5 x 2,5
3G2,5
5G2,5
3G6
5G2,5
3G6
5G2,5
Proof pressure
bar
2
Service pressure
bar
1,5
Head loss
mCE
1,4
1,5
1,5
1,5
1,1
1,1
1,1
1,1
Medium water flow
m³/h
4
5
6
7
8

Sound pressure (db(A))
Boost
64
65
66
68
64
65
64
66
Silence
61
63
63
66
61
62
62
63
Frequency band
GHz
2,412 - 2,484
Emitted power
dBm
+20
Type of refrigerant
R32
Refrigerant amount
kg
0,87
1,05
1,45
1,18
1,80
1,59
1,80
1,59
Net weight
kg
70
71
90
81
105
97
110
97
The appliances have an Ingress Protection (IP) rating of IP24. Please refer to the marking indicating the IP-rating on 
your particular product.
* Rated values measured in “Heating” mode according to EN 14511
** Values provided for information purposes for a maximum length of 20 metres (calculation base: NFC 15-100),
must be checked and adapted to the installation conditions and standards of the installation country.
•	 Maximum operating pressure of the refrigerant circuit: 4.2 MPa / 42 bar
•	 Minimum operating pressure of the refrigerant circuit: 0.05 MPa / 0.5 bar
•	 Maximum operating pressure of the water circuit: 0.3 MPa / 3 bar
•	 Minimum operating pressure of the water circuit: 0.05 MPa / 0.5 bar

  
5.3 I  Dimensions and marking

Z400iQ
MD4
MD5
MD7
TD7
MD8
TD8
MD9
TD9
A*
1030
1145
B*
450
480
C*
479
509
D*
880
1027
*Overall dimensions in mm

Front
Side
Rear
: Base
: Front panel
: Grid
: User interface
: Appliance status LEDs

: Side panel
: Technical access 
door

23

220-
240V 
/ 1 /
50 Hz

380-
415V 
/ 3 /
50 Hz

220-
240V 
/ 1 /
50 Hz

: Technical access door 
: Pool water inlet Ø1’’ 1/2
: Pool water outlet Ø 1’’ 1/2
: Evaporator
: Gland
: Rear panel

Sayfa 26

  
Schémas électriques / Wiring diagrams / Schaltplan / Elektrischschema / Esquema 
eléctrico / Esquema eléctrico / Schema elettrico

1.  Z400iQ MD4 - MD5 - MD7 (R32)

*

Sayfa 27

3.  Z400iQ MD8 (R32)

Sayfa 28

4.  Z400iQ MD9 (R32)

*

Sayfa 29

5.  Z400iQ TD7 - TD8 - TD9 (R32)

Sayfa 30

Français
English
Deutsch
Nederlands
A1
Carte électronique de 
régulation

HMI
Carte électronique (écran)
PCB display
Elektronikkarte (Display)
Elektronische kaart 
(scherm)
LED
Carte électronique LED
Led display
Elektronikkarte LED
Elektronische kaart LED
C1
Condensateur ventilateur
Fan motor capacitor
Kondensator für Lüfter
Condensorventilator
C2
Condensateur deuxième 
vitesse

Condensator tweede 
versnelling
C3
Condensateur 
compresseur

J1
Contrôleur de débit
Water flow detector
Paddelschalter
Debietsturing
R1
Contacteur pompe
Pump relay
Schütz für Pumpe
Contactor pomp
R2
Contacteur compresseur
Compressor relay
Schütz für Kompressor
Contactor compressor
R3
Contacteur moteur 
ventilateur

ST1
Sonde réglage débit eau
Regulation water sensor
Einstellfühler für 
Wasserdurchsatz

ST2
Sonde antigel
Antifeeze sensor & 
outdoor temperature

ST3
Sonde de dégivrage
Defrost sensor
Enteisungsfühler
Ontdooiingssensor
ST4
Sonde température liquide Refrigerant liquid 

Temperatuursensor 
vloeistof
ST5
Sonde température 
refoulement

Temperatuursensor 
perszijde
LP
Pressostat basse pression
Low pressure switch
Druckregler Niederdruck
Lagedrukpressostaat
HP
Pressostat haute pression
High pressure switch
Druckregler Hochdruck
Hogedrukpressostaat
REV VALV
Vanne d’inversion
Reversion valve
Umkehrventil
Omkeerklep
EXP VALVE
Détenteur électronique
Expansion valve
Elektronischer 
Druckminderer

M1
Moteur ventilateur
Fan motor
Lüftermotor
Ventilatormotor
M2
Moteur compresseur
Compressor motor
Kompressormotor
Compressormotor
HEATER
Résistance antigel 
(condenseur)

Antivriesweerstand 
(condensor)
FAN HEATER
Résistance convoyeur
Air conveyor resistance
Widerstand am 
Gebläseausgang

TP1
Bornier
Terminal plate
Klemmleiste
Klem
TP2
Bornier
Terminal plate
Klemmleiste
Klem
F1 - F2
Fusible
Fuse
Schmelzsicherung
Zekering
V1 - V2
Varistance
Varistor
Varistor
Varistor
V4
Tube décharge gaz
Gas discharge tube
Gasentladungsrohr
Gasexpansiebuis
RED
Rouge
Red
Rot
Rood
BLK
Noir
Black
Schwarz
Zwart
VLT
Violet
Violet
Violett
Paars
BLU
Bleu
Blue
Blau
Blauw
WHT
Blanc
White
Weiß
Wit
GRN/YEL
Vert-Jaune
Green-Yellow
Grün-Gelb
Groen-Geel
YEL
Jaune
Yellow
Gelb
Geel
BRN
Marron
Brown
Braun
Bruin
PNK
Rose
Pink
Rosa
Roze
ORG
Orange
Orange
Orange
Oranje

PCB main
Elektronische 
Steuerplatine

Elektronische stuurkaart

2nd speed capacitor
Kondensator für zweite 
Stufe

Compressor capacitor
Kondensator für 
Kompressor

Condensor-compressor

Fan motor relay
Schütz für Lüftermotor
Contactor ventilatormotor

Regelsensor waterdebiet

Frostschutzfühler
Antivriessensor

Flüssigkeitstemperatur-
fühler

temperature sensor

Compressor discharge 
temperature

Temperaturfühler an 
Druckseite

Elektronische ontspanner

Anti frost heater
Frostschutzwiderstand 
(Kondensator)

Weerstand transport

*

Sayfa 31

Español
Português
Italiano
Ελληνικά
A1
Tarjeta electrónica de 
regulación

Ηλεκτρονική κάρτα 
ελέγχου
HMI
Tarjeta electrónica 
(pantalla)

Ηλεκτρονική κάρτα 
(οθόνης)
LED
Tarjeta electrónica LED
Placa eletrónica led
Scheda elettronica Led
Ηλεκτρονική κάρτα led
C1
Condensador ventilador
Condensador ventilador
Condensatore ventilatore
Συμπυκνωτής ανεμιστήρα
C2
Condensador segunda 
velocidad

Συμπυκνωτής δεύτερης 
ταχύτητας
C3
Condensador compresor
Condensador compressor
Condensatore 
compressore

J1
Detector de caudal
Controlador de caudal
Regolatore di portata
Διάταξη ελέγχου ροής
R1
Contactor bomba
Contactor bomba
Contattore pompa
Επαφέας αντλίας
R2
Contactor compresor
Contactor compressor
Contattore compressore
Επαφέας συμπιεστή
R3
Contactor del motor de 
ventilador

Επαφέας του κινητήρα 
του ανεμιστήρα
ST1
Sonda de ajuste de caudal 
de agua

ST2
Sonda anticongelante
Sonda anti-gelo
Sonda anti-gelo
Αισθητήρας προστασίας 
από τον παγετό
ST3
Sonda de deshielo
Sonda de degelo
Sonda di sbrinamento
Αισθητήρας απόψυξης
ST4
Sonda de temperatura del 
líquido

υγρού
ST5
Sonda de temperatura de 
descarga

Αισθητήρας θερμοκρασίας 
κατάθλιψης
LP
Presostato de baja presión Pressostato baixa pressão
Pressostato bassa 
pressione

Πιεζοστάτης χαμηλής 
πίεσης
HP
Presostato de alta presión
Pressostato alta pressão
Pressostato alta pressione
Πιεζοστάτης υψηλής 
πίεσης
REV VALV
Válvula de inversión
Válvula de inversão
Valvola d'inversione
Βαλβίδα αντιστροφής
EXP VALVE
Reductor de presión 
electrónico

M1
Motor de ventilador
Motor do ventilador
Motore ventilatore
Κινητήρας ανεμιστήρα
M2
Motor compresor
Motor compressor
Motore compressore
Κινητήρας συμπιεστή
HEATER
Resistencia anticongelante 
(condensador)

Αντίσταση παγετού 
(συμπυκνωτής)
FAN HEATER
Resistencia transportador
Resistência transportador
Resistenza convogliatore
Αντίσταση του ιμάντα 
μεταφοράς
TP1
Regleta
Barra de terminais
Morsettiera
Μπλοκ ακροδεκτών
TP2
Regleta
Barra de terminais
Morsettiera
Μπλοκ ακροδεκτών
F1 - F2
Fusible
Fusível
Fusibile
Ασφάλεια
V1 - V2
Varistor
Varistância
Variatore
Βαρίστορ
V4
Tubo de descarga de gases Tubo descarga gás
Tubo scarico gas
Σωλήνας εκκένωσης 
αερίου
RED
Rojo
Vermelho
Rosso
Κόκκινο
BLK
Negro
Preto
Nero
Μαύρο
VLT
Violeta
Violet
Viola
Μωβ
BLU
Azul
Azul
Blu
Μπλε
WHT
Blanco
Branco
Bianco
Λευκό
GRN/YEL
Verde-Amarillo
Verde-Amarelo
Green-Yellow
Πράσινο-Κίτρινο
YEL
Amarillo
Amarelo
Giallo
Κίτρινο
BRN
Marón
Castanho
Marrone
Καφέ
PNK
Rosa
Rosa
Rosa
Ροζ
ORG
Naranja
Laranja
Arancione
Πορτοκαλί

Placa eletrónica de 
regulação

Scheda elettronica di 
regolazione

Placa eletrónica (ecrã)
Scheda elettronica 
(display)

Condensador segunda 
velocidade

Condensatore seconda 
velocità

Συμπυκνωτής συμπιεστή

Contactor motor 
ventilador

Contattore motore 
ventilatore

Sonda ajuste caudal de 
água

Sonda regolabile portata 
acqua

Αισθητήρας ελέγχου ροής

Sonda temperatura de 
líquido

Sonda temperatura liquida Αισθητήρας θερμοκρασίας 

Sonda temperatura 
retorno

Sonda temperatura di 
mandata

Válvula de expansão 
eletrónica

Riduttore elettronico
Ηλεκτρονικός ανιχνευτής

Resistência anti-gelo 
(condensador)

Resistenza antigelo 
(condensatore)

Sayfa 32

Votre revendeur 
Your retailer 

Modèle appareil 
Appliance model

Numéro de série 
Serial number

Pour plus d’informations, enregistrement produit et support client : 

For more information, product registration and customer support:  

Europe:
www.zodiac.com

Australia:
www.zodiac.com.au

See warranty details on : 

©2022 Zodiac Pool Systems LLC. All rights reserved. ZODIAC® is a registered trademark of Zodiac International, 
S.A.S.U., used under license. All other trademarks are the property of their respective owners.

EUROPE : ZPCE -  ZA La Balme - 31450 Belberaud - S.A.S.U. au capital de 1 267 140 € / SIRET 395 068 679 00046 / RCS TOULOUSE

AUSTRALIA : Zodiac Group Australia Pty Ltd - 219 Woodpark Road - Smithfield NSW 2164